' ARCHITECT PRODUCT REVIEW PRODUCT OPENING PRODUCT MANUFACTURER MODEL# APPROVAL# GLASS ATTACHMENT METHOD DESIGN DESIGN -TYPE PRESSURES PRESSURES (WORST CASE) WINDOW ZONE 4 -28 -80 PGT INDUSTRIES SH 700 FL# IMPACT Y" ULTRACONS @ HEAD 18-1/2" MAX. FROM TOP ZONE 5 -34 239.3 CORNERS, JAMBS-17-1/2" MAX. FROM TOP CORNERS, 15" MAX. FROM BOTTOM CORNERS AND 6" BELOW RETAIL MTG RAIL, 1-3/4" EDGE DISTANCE DOOR ZONE 4 -28 -75 PLASTPRO SERIES O _ FL# IMPACT Y" TAPCON @ 14" MAX O.C., 6" TYPE FROM EACH ZONE 5 -34 FIBERGLASS 15210.1 CORNER: WITH 1-1/4" MINIMUM EMBEDMENT & 2-1/2" EDGE. DISTANCE ROOF ZONE 1-24 -129.25 JA TAYLOR ROOFING 5 V CRIMP FL# N/A #9 X 15 CORROSION RESISTANT WITH SEALING WASHERS ZONE 2 -40 17443.1 W/ MIN. 5/16" PENETRATION OF ROOF DECK @ 6" O.C. ZONE 3 -60 PERIMETER & MAIN FIELD FASTENING @ 12" O.0 SIDING ZONE 4 -28 -105 JAMES HARDIE HARDIE SOFFITT FL# IMPACT 6d X 2" GALVANIZED BOX NAILS 4" MAX. O.C. FROM ZONE 5 -34 PANELS 13265.1 THE CORNER UNDERLAYMENT ZONE 1-24 N/A POLYGLASS USA, INC. POLYSTICK TU FL# N/A PEEL AND STICK (SELF -ADHERED) ZONE 2 -40 PLUS 5259.1 ZONE 3 -60 TNF fFAI LJFDCrIA11C DDrI111 non n.11 V In I�Inli-ATr �• In nr. nr.a. w.... ..... e....... �........._ .__ ___._.. �_ .._-_._ __. --------...._......-...-.-..��- ... �.,rvn1l11JJI"UtIvnc. Inc M-%-crIAIMLr.UrIntatFK000CISAND METHODS OF ATTACHMENT ARE BASED ENTIRELY UPON TEST DATA PROVIDED BY THE MANUFACTURER, WHICH CARRIES ITS OWN ENGINEER'S CERTIFICATION AND IMPLIES NO WARRANTY OR GUARANTEE BY THIS OFFICE FOR THESE PRODUCTS. INTERIOR FINISH CLASSIFICATION WALL FINISHES CLASS B FLAME SPREAD OF 26-75 SMOKE DEVELOPED 0 - 450 PER SECTION 803 TABLE 803.5 CEILING SUSPENSION SYSTEMS SHALL CLASS B CONFORIVI:ING WITH GENERALLY ACCEPTED ENGINEERING PRACTICE, IN ACCORDANCE WIT[I MANUFACTURER'S RECOMMMENDATIONS, AND BE INSTALLED IN ACCORDANCE WITH TILL PROVISION-S OF, ASTMC635 AND ASTM 636 FLOOR COVERING MATERIALS TO BE OF CLASS I OR CLASS II MATERIALS SHALL BE CLASSIFIED IN ACCORDANCE WITH. NFPA 253 CLASS 1, 0.45 WATTS/CM2 OR GREATER CLASS 11, 0.22 WATTS/C.M2 OR GREATER GYPSUM BOARD MATERIALS AND INSTALLATION SHALL CONFORM TO THE APPROPRIATE STANDARD LISTED BELOW. TABLE 2506.2 GYPSUM BOARD IMATFRIAI q AKIn nr'r`G'acncalr=c MATERIAL STANDARD Accessories for gypsum board ASTM C 1047 Adhesives for f lsteuing gypsum ASTM C 557 wallboard _ ....._.._.___--.-_-.-. ' ... Exterior soffit board.._____.....__...._�___._._.... AS'T'M C 931 •----------....-:_ Fiber-reinti)rcedypsumutels ASTM C 1278� ___ Glass mat gypsum backin�1janei .ASTM C 1178 Glass mat ypsurll substrate ASTM. C 1.177 Gypsum backing board and gypsum _ shaftliner board -__�-- ASTM C 4�42 G sum cLd n_� board ASTM C_ 1395 -_- Gypsum sheathing _ ASTM C 79 _ -- Gypsum wallboard _._.__............ ASTM C 36 ...._ _....._.._ ..._,. _..__.._.. Joint reinforcing tape and compounc'l ASTM C 474; C 475 Nails for gypsum boards ASTM C 514, F 547, F 1667 Nredccol.ated gYpsunl board C 960 Steel screws - --- - _ - _ _ - ASTM C 954, C 1002 Steel studs, loud bearing AS'4'M_ C 955 Steel studsvllOnload bea.rlll, _--AST,M C 645 Starld,lyd s�Tt tenon for board ASTM C 1396 Testing gypstlnl and trypstlnl products AS'1"M C 22; C 472; C 473 Watcr-resisl tart YpSum bncicin T hoard ASTM C 630 -� TABLE 2508.1 INSTALLATION OF crYPSUNI CONSTRUCTIO14 LINTEL SCHEDULE MANUFACTURER: CAST-CRETE LINTEL NO. LENGTH SAFE GRAVITY LOAD APPLIED GRAVITY LOAD SAFE UPLIFT LOAD APPLIED UPLIFT LOAD COMPOSITE BEAM L 1 2'10" 6113# _ 4460# 8F16/1T-1B L 2 3'-6" 6113# - 3547# 81`16/1T-18 L 3 4'-0" 6113# 3079# 8F16/1T-1B L 4 4'-6" 6113# - _ -4} It Cl :_ Z724# 229011 Z."Z 4.'* 8F16/1T-1B 8F16/1T-1B L 5 5'-4" 536511 1.6 51101, 4360# _ 2093# 8F16/IT-1B L 7' 6'-6" 3480# 18800 7L 5'40 } 8F16/IT-1B L8 7'-6" 2661# - 163411 8F16/1T-1B L 9_ _ 9'-4" 1843# _-T _ 1133# 8F16/1T-1B L 10 101-61, 15334 -_ 91411 -_ 8F16/1T-1B L 11 11'-4"- 136611 798# 8F16/1T-1B L 12 12'-0" 1254# i � 723# z 54 1W L13 13'-4" 1075# y 606# _8_F16/1T-1B 8F16/1T-1B L14 14'-0" - 1002# 55981 8F16/1T-18 L 15 14'-8" 1370# 519# 8F16/1T-IB L 16 15'-4" 1250# 485# 8F16/1T-1B L 17 17'-4" 9S0# _ 404111 - 8F16/1T-1B _ 1.18 19'-4" 750# 347# 8f16/17-16 L 19 21' 4"- 598#� 306# _ 8F16/1T-1B L 20 - 22'-0" 550# 295# 8F16/1T-1B L 21 24'-0" 450# 267# 8F16/1T-16 RECESSED LINTELS MANUFACTURER: CAST-CRETE LINTEL NO. LENGTH SAFE GRAVITY LOAD APPLIED GRAVITY LOAD SAFE UPLIFT LOAD APPLIED UPLIFT LOAD COMPOSITE BEAM RL-1 4'-4" 5206# 2635111 8F14/1T-18 RL-2 4'-6" -- 5206# - - -- - _ - 2525# 8F14/1T-1B RL-3 5'-8" 4567# 19601t 8F14/1T-1B RL-4 5'-10" 4242# 19001! SF14/1T-iB RL-5 6'-8" - -7'.6" _ 3120# 1651# 8F34/1T-16 RL-S 2459# 1462# ---- - - - --- -8F14/1T-1B - RL-7 1568# 1135# 8F14/1T-1B NOTES: ALL LOADS ARE IN POUNDS PER LINEAL FOOT. APPLIED LOADS SHOW WORST CASE FOR LINTEL SIZE. SEE STRUCTURAL NOTES FOR ADDITIONAL INFORMATION. 1 1, z"A; - .l.-I - 1 ,I /'jf 1 Certification for Design Load Compliance 1. DESIGN CODE: Florida J5U %k.'P%# l Cs, code 2017 Edition w/20_ supplements using ASCE 7-10 2. Structure Design is: A Enclosed Partially Enclosed Open Building 3. Risk Category: _,,I -A II - III _IV Exposure Category: K B rC _D Adjustment coefficient 1 e O 4. Design Wind Velocity 160 mph _ASD _LRFD End Zone Width eft. 5, Mean Roof Height: 1.51 ft. Roof Pitch: -5 :12 Parapet _ft, e 6. Components 81 Cladding Design Pressure used: (PSF, based on Actual sq. ft. 'MRH (worst case) Zone 1:- 7'0�' , Zone 2:- 40 Zone 3:- '0'0 Zone 4:- Z20 Zone 5:-1511�r Garage: O/A- 7. Design Loads: Floor: PSF Roof/Dead: I* PSF Roof/Live 310 PSF Balcony: WWI, PSF Dock: RI�1�PSF Deck: N,/PPSF Stairs: V PSF Fence: 0/A PSF Railing: t--�LA, PSF 8, Were Shear Walls Considered for Structure? X Yes _Not Applicable Explain Why Not: 9. Is a Continuous Load Path provided? X Yes _Not applicable Explain Why Not: 10. Minimum soil bearing pressure 2000 P.S.F. STRUCTURAL NOTES: 1. STRUCTURAL LUMBER TO BE HEM -FIR #2 GRADE OR BETTER WITH 1000 P.S.I. MIN, FIBER STRESS VALUE, 2. CONCRETE TO BE 3000 P.S.I. MIN. FOR BEAMS, COLUMNS, AND FILLED CELLS, CONCRETE SLABS AND FOOTINGS TO 2600 P.S.I. MIN. 3. REINFORCING STEEL SHALL BE GRADE 60 OR BETER WITH 30" MIN LAP, 4, CONCRETE COVER OVER REINFORCING STEEL FOOTINGS 3" BEAMS 1.112" COLUMNS 1-1/2" 5. FILL (SOIL) SHALL BE PLACED IN LIFTS NOT TO EXCEED 12" AND COMPACTED TO A MINIMUM OF 95%A MODIFIED PROCTOR DENSITY. 6. ALL COMPONENTS OF THIS STRUCTURE HAVE BEEN DESIGNED AND SELECTED TO WITHSTAND WIND FORCES PER THE FLORIDA BUILDING CODE DOOR AN WINDOW ASSEMBLY COMPONENTS TO BE CERTIFIED BY MANUFACTURER FOR WIND FORCES PER THE FLORDA BUILDING CODE 2017 EDITION PER WIND LOAD COMPLIANCE DESIGN PRESSURES. a. PRECAST/PRESTRESSED CONCRETE LINTELS TO HAVE 4" MINIMUM BEARING. SEE LINTEL SCHEDULE FOR ADDITIONAL INFORMATION. 9. MORTAR FOR MASONRY CONSTRUCTION SHALL CONFORM TO ARTICLES 2.1 AND 2.6 A OF TMS 602/ACI 530.0/ASCE6 10, FOR METHOD OF ATTACHMENT OF DOORS AND WINDOWS, SEE ATTACHED PRODUCT REVIEW AFFIDAVIT. 11. ALL LUMBER IN CONTACT WITH CONCRETE SHALL BE PRESSURE TREATED PER SECTION 2303.1.9.1 OF THE FLORIDA BUILDING CODE. 'NOTE: ALL SIMPSON STRONG -TIE PRODUCTS IN CONTACT WITH TREATED LUMBER SHALL HAVE A MINIMUM Z-MAX COATING OR BETTER. NOTE: CONTRACTOR TO FIELD VERIFY ALL DEMINSIONS PRIOR TO TRUSS FABRICATION WALL LEc13END �� EXISTING WALLS TO REMAIN EXISTING WALLS TO BE REMOVED PROPOSED CONCRETE BLOCK WALLS . "'° PROPOSED 2 X 4 FRAME WALI S BUILDING INFORMATION: 2017 FLORIDA BUILDING CODE BUILDING AREA: OFFICE 730 S.F. ENTRY 72 S.F. TOTAL BUILDING AREA 802 S.F. GROUP: B BUSINESS OCCUPANT LEAD PER TABLE 1004.1.2 730/100 = 7.3 TOTAL OCCUP ,374T LOAD 8 CONSTRUCTIC-V TYPE: TYPE VB ALLOWABLE AREA PER TABLE 503: GROUP B 9,000, S.F. BUILDING IS NON-6PRINKLERED REQUIREMENTS FOR AREA OF IMPROVEMENTS REQUIRED NUMBER OF FIXTURES PROVIDED NUMBER OF FIXTURES 1 WATER CLOSETS 1 WATER CLOSETS 1 LAVATORIES 1 LAVATORIES 0 SERVVCE SINK 0 SERVICE SINK 0 DRINKING FOI'"'TAIN 0 DRINKING FOUNTAIN REQUIRED EXITWIDTH 36" PROVIDED EXITWIDTH PROVIDED 36" REQUIRED NUMBER OF EXITS 1 PROVIDED NUMBER OF EXITS 1 REQUIRED ADA CORRIDOR WIDTH 42" PROVIDED ADA CORRIDOR WIDTH 60" TRAVEL DISTAWF`ALLOWED 200' TRAVEL DISTANCE: PROVIDED 44' Architectonic Inc 806 DELAWARE AVENUE FORT PIERCE, FLORIDA 34950 T: 772 460 7751 F: 772 460 4244 WWW.ARCHITECTONICINC.COM STATE REG # AA26003348 COPYRIGHT 2017 PROJECT PA L LAS OFFICE CONVERSION ST. LUCIE COUNTY, FLORID CLIENT CONSULTANTS REGISTR,4,TION IA': MICHAEL J. SEAL, AIA AR96898 REVISIONS NO. DATE REVISION SHEET TITLE / SHEET NUMBER a FILE up PROJECT NUMBER .(��•© DATE A, I (Cr,(24Z', ' I �ca•a.l�t< Ie (a) (b) BACK WALL SIDE WALL GRAS SAg111 AT WATER.CLOSET'S • RESTROOM DOORS TO BE EQUIPPED WITH LEVER HANDLE AND PRIVACY LOCK. • LAVATORY AND SINK CONTROLS TO BE LEVERTYPE. • SIGNS INDICATING ADA ACCESIBLE RESTROOM SHALL BE LOCATED ON LATCH SIDE OF DOOR,C(.6 Tb CEw mz) r PLUMBING TO BE WRAPPED WITH INSULATION. x © E� l 0) tv t 1 1/2 8 - 1114.11/2i 3f 3� CI3nT1- 1 KNEE CLEARANCE TOP CLEARANCE ��.�i._._._ DEPTH LAVATORY CLEARANCES ACCESSIBLE RESTROOM DETAILS r�+rrurririri r�nnrr_rrr,� rW Yur�rwiMrrr.rri.w�rnri NTS IFI %,F- 7t" r= s..,�; f-Q'e- � 42 ) CL ... ...... _ w.-...,........._..m..........,.,.. _ 1/4 max 1/4 TO 1/2 /6.5 /Bv-13Z t (C) (d ) Changes in Level Changes in Level THRESHOLD ON ACCESSIBLE RO[7TE NO SCAT..L FLORIDA ACCLSSIBIL.ITY CODE RFQUIREWNTS DRYWALL AND FURRING XrTACHMENT PA". 1 X 2 FURRING @ 16" O.C. FASTENED WITH 1 '/" CASE HARD NAILS a, 8" O.C. Yz" DRYWALL FASTENED TO FURRING WITH 1 1/8" DRYWALL SCREWS L), 8" O.C. PERIMETER AND 12" O.C. FIELD. 5/8" DRYWALL FAS"I'ENED T'O FURRING WITH 1 1/8" DRYWALL SCREWS a, 8" O.C. PERIMETER AND 12" O.C. FIELD. FIGURE 703.7.2.1 INTERNATIONAL SYM130L OF ACCESSIBILITY TABLE 703.5.5 vlCnAr r WAMAr`TCQ Hr'1(:HT i E2 (>r1 F -_ not In / plctogram field FIGURE 703.6.1 PICTOGRAM FIELD HEIGHT TO FINISH FLOOR OR GROUND HORIZONTAL VIEWING DISTANCE MINIMUM CHARACTER HEIGHT FROM BASELINE OF CHARACTER less than 72 inches (1830 mm _ _ 5/8 inch (16 mm� 5/8 inch (16 mm), plus 1/8 inch (3.2 mm) 40Inches (1015 mm) to less than or equal to 70 inches (1780 mm) 72 Inches (1830 mm) and greater per foot (305 mm) of viewing distance above 72 Inches 1830 mitt � � ch less than 180 Ines 70 mm (45T 2 inches 51 mm) 2 inches (51 mm), plus 1/8 Inch (3.2 mm) Greater than 70 inches (1780 mm) to less ihan or equal to 120 inches (3050 mm) 180 inches (4570 mm) and greater per foot (305 mm) of viewing distance above 180 inches (4570 rnm less than 21 feet 6400 mm 3 Inches (75 mm 21 feet (6400 mm) and greater 3 Inches (75 mm), plus 1/8 inch (3.2 mm) per foot (305 mm) of viewing distance Greater than 120 inches (3050 mm) above 21 feet 6400 mn2) N"\A -lv5 - z DIP-1�`.�r. i 1✓ � _— t -- o Sa�F1� c'AJ-4L''o 511AW,o .......... ........_d __-_ __.,_._....____. Y .Ct �•-- Ga 0-r94 N j'tj F 1-11 v, V- '. ROOF SHEATHING NAILING ZONE INFO. ZONE P1 REMAINING AREA W/8d RING SHANK @ 6" O.0 PERIMETER & 6" O.C. FIELD, ZONE P2 4` X LENGTH W/8d RING SHANK @ 4" O.0 PERIMETER & 6" O.C. FIELD, ZONE P3 5' X 5' @ HIP AND 5' X LENGTH @ GABLE ENDS W/8d RING SHANK @ 4" O.0 PERIMETER & 4" O.C. FIELD . NOTES: 19/32" CDX PLYWOOD SHEATHING 25' - 0" OR GREATER MEAN ROOF HEIGHT SHALL HAVE 10 d RINGSHANK NAILS. UNDERLAYMENT FELT SHALL BE PEEL & STICK.OR.30# FELT COMPLYING W/ ASTM.D226. NOTE: STUCCO ON RIBLATH OR PAPER BACKED WIRE LATH SHALL BE ATTACHED TO HORIZONTAL FRAMING AS PER ASTM C-1063: LATH SHALL BE ATTACHED TO FRAMING MEMBERS WITH CORROSION RESISTANT MATERIALS. ATTACHMENTS SHALL BE SPACED NOT MORE THAN 6" O.C. ALONG SUPPORTS, FASTENERS TO BE USED CAN BE 6D COMMON OR ROOFING NAILS HAVING A MIN. 1-3/4" PENETRATION INTO HORIZONTAL FRAMING MEMBERS OR STAPLES W1 A MIN. 3/4' CROWN ENGAGED NOT LESS THAN (3) STRANDS OR LATH AND MUST PENETRATE THE WOOD FRAMING MEMBERS 3/4' MIN. !2QOR AND WINDOW BUICKFAST�-NIN 1 X BUCKS SHALL BE ATTACHED WITH CASE HARD NAILS @ 12" O.C. WITH THE DOORS AND WINDOWS FASTENED WITH TAPCONS PER PRODUCT REVIEW AFFIDAVIT WITH A MIN, OF 1.1/4" EMBEDMENT INTO CONCRETE (THROUGH FRAME) BUCK SHALL EXTEND BEYOND THE INTERIOR FACE OF THE FRAME PER 2017 FLORIDA BUILDING CODE WITH AMENDMENTS. OPTIONAL 2 X BUCKS SHALL BE ATTACHED WITH 1/4" X 3-1/4" TAPCONS AT 12" O.C, WITH DOORS AND WINDOWS FASTENED WITH #10 WOOD SCREWS SPACED PER PRODUCT REVIEW AFFIDAVIT WITH A MINIMUM PENETRATION OF 1-1/4" INTO BUCK, BUCK SMALL EXTEND BEYOND THE, INTERIOR FACE OF FRAME PER 2017 FLORIDA BUILDING CODE WITH AMENDMENTS. et�/r-z Cam ARCHITECT Architectonic Inc 806 DELAWARE AVENUE FORT PIERCE, FLORIDA 34950 T: 772 460 7751 F: 772 460 4244 WWW.ARCHITECTONICINC.COM STATE REG # AA26003348 COPYRIGHT 2020 PROJECT PA L LAS OFFICE CONVERSION ST. LUCIE COUNTY, FLORIDA CLIENT CONSULTANTS REGISTRATION T' �1- L��. AL, AIA AR96898 REVISIONS KEY PLAN SHEET TITLE / SHEET NUMBER PROJECT NUMBERcrc DATE�fc�t�zcat 'c'ar sT"lttl-F a t1 °p Zx4 �Lr�c K try. c�Vo,C, i-, tF LS7 Fes'-�-• E "mil �.+�'�''_� c�;G • � I' I I �P �Ixel �(= la. ►�-��1 � � CCU � � F'1'L.I.E.P W'f �tjO © I'=�1 �o �.Jfc., (;'-o"d,c, c0ti,i,I�ZxI�IGr�Ir-.lG.1,.ih .5/4I' �Fi 6 t r.-;, le 13 mlu A.- zE r . At r i N• .r !��i "r � G F!LL1 CEC-L- C[iNNFfTnF? rrumi rr r TRUSS ID BEARING POINT(S) TRUSS ACTUAL UPLIFT (GROUPED, WORST CASE) SIMPSON CONNECTOR(S) CONNECTOR(5) UPLIFT DESIGN FASTENERS A B EACH FIRST 1245# 1257# (1) HETA 20 (1)HETA 20 1810# 1810# 9-10dxl-1/2" 9-10dx1 Y." SECOND HANGER BY TRUSS COMPANY GR GRA EACH FIRST 2265# 2265# (2) HETA 24 (2)HETA 24 2365# 2365# 12-16d x 3-1/2" 12-16d X 3 1/2" SECOND HANGER BY TRUSS COMPANY KING JACKS lsr BRG 715# (1) --MTS 16 990# (14) 10dxl-1/2" (KJ) 2"D BRG 372# (1) THJU26 780# (32) 10d x 3" 3RD BRG 123# 144# (2) 16d x 3-1/2" HIP JACKS 11T BRG 415# (1) MTS 16 990# (9) 10dxl-1/2" 2"D BRG 230# (1) THC37 (MAX) 510# (12) 8d x 1-1/2" VALLEY TRUSSES 3RD BRG 48" O.C. 107# 672# (1) MTS 16 144# 1000# (2) 16d x 3-1/2" 14-10dxl-1/2" --•-•••• •- ,v FnUV,UV- InUJJ Li-%TUUI /ANu tivhUvttKliVtj PKIUR TO POURING BEAM FOR REVIEW AND APPROVAL BY THE ARCHITECT K 0 F,�„ s, 1 C-5 Lo , rtr- FO S C H E D U L E S-1 4" (3000 PSI) POURED CONCRETE SLAB WITH FIBERMESH REINFORCING ON .006" VAPOR BARRIER OVER CLEAN COMPACTED TREATED FILL, F-1 12" X 12" THICI<ENED EDGE WITH 1 # 5 BAR CONTINUOUS. F-2 16" DEEP X 18" WIDE MONOLITHIC FOOTING WITH 3 # 5 BARS CONTINUOUS. D-1 # 5 DOWEL DRILLED 4" MIN. INTO EXISTING BLOCK SET IN EPDXY @ 24" O.C. VERT. D-2 3 # 5 DOWELS DRILLED 6" MIN. INTO EXISTING FOUNDATION SET IN EPDXY AND TIED TO NEW FOOTING STEEL. D-3 # 5 DOWELS DRILLED 6" MIN. INTO EXISITING FOUNDATION SET IN EPDXY @ 48" O.C. TIED TO NEW FOOTING ;S-FEEL. ARCHITECT Architectonic Inc 806 DELAWARE AVENUE FORT PIERCE, FLORIDA 34950 T: 772 460 7751 F: 772 460 4244 WWW.ARCHITECTONICINC.COM STATE REG # AA26003348 COPYRIGHT 2020 PROJECT PALLAS OFFICE CONVERSION ST. LUCIE COUNTY, FLORIDA CLIENT CONSULTANTS REGISTRATION ..t t_ MICHAEL J. SEAL, AIA AR96898 REVISIONS NO. DATE REVISION KEY PLAN SHEET TITLE / SHEET NUMBER 1 MLE Ml)v PROJECT NUMBER d -,r ,000 DATE 4 / ( zc zc� DUCTWORK SYSTEM SYMBOLS SYMBOL DESCRIPTION ® Ln SUPPLY AIR DUCT SECTION (UP/DOWN) z/© RETURN, OUTDOOR OR EXHAUST AIR DUCT SECTION (UP/DOWN) z/© OUTDOOR AIR DUCT SECTION (UP/DOWN) z/© EXHAUST AIR DUCT SECTION (UP/DOWN) �.� RETURN, EXHAUST OR TRANSFER AIR FLOW -�► SUPPLY AIR FLOW MD [174VAv4- MOTORIZED DAMPER VD L MANUAL VOLUME DAMPER FD D- FIRE DAMPER SD D- SMOKE DAMPER AD Q ACCESS DOOR /-� FLEXIBLE DUCT CONNECTION ELBOW WITH TURNING VANES SUPPLY DIFFUSER WITH 4-WAY BLOW SUPPLY DIFFUSER WITH 2-WAY BLOW SUPPLY DIFFUSER WITH QUADRANT BLOCK OSD - SIDEWALL DIFFUSER Fo_1 RETURN, TRANSFER OR EXHAUST GRILLE OR REGISTER ® EXHAUST FAN ROUND CEILING DIFFUSER L LINEAR DIFFUSER CDP-I AIR DEVICE, TYPE AND CAPACITY 100 SQUARE TO ROUND TRANSITION --- EXISTING DUCTWORK OR EQUIPMENT TO REMAIN -- - EXISTING DUCTWORK OR EQUIPMENT TO BE REMOVED NEW DUCTWORK OR EQUIPMENT OROOF CENTRIFUGAL FAN, EXHAUST OROOF CENTRIFUGAL FAN, SUPPLY ELECTRIC DUCT HEATER �-� 2" UNDERCUT CONTROL SYMBOLS THERMOSTAT - 4'-0" A.F.F. MOUNTING HEIGHT HUMIDISTAT - 4'-0" A.F.F. MOUNTING HEIGHT TEMPERATURE SENSOR �- STA11C PRESSURE SENSOR ® DUCT SMOKE DETECTOR /VD VOLUME DAMPER /AD AUTO DAMPER HVAC PIPING LEGEND CWR CONDENSER WATER RETURN CWS CONDENSER WATER SUPPLY CHWS CHILLED WATER SUPPLY CHWR CHILLED WATER RETURN HWS HOT WATER SUPPLY HWR HOT WATER RETURN - - - - - REFRIGERANT PIPING CONDENSATE DRAIN FROM COOLING COIL CD DOMESTIC COLD WATER - G GAS PIPING MECHANICAL SYMBOL LEGEND SCHEDULE FOR CEILING SUPPLY DIFFUSER 4 WAY BLOW 2 WAY BLOW )A QUADRANT BLOCK SYMBOL 0 NECK FLEX CONNECTION CFM RANGE FINISH REMARKS CDP-1 6" 6" 0 - 125 OFF-WHITE OA OB CDP-2 8" 8" 126 - 225 OFF-WHITE OA OB CDP-3 10" 10" 226 - 400 OFF-WHITE OA O CDP-4 12" 12" 401 - 600 OFF-WHITE OA BO I SCHEDULE FOR CEILING RETURN DIFFUSER SYMBOL 0 NECK FLEX CONNECTION CFM RANGE FINISH REMARKS RD-1 6" 6" 0 - 125 OFF-WHITE OC O RD-2 1 8" 8" 126 - 225 OFF-WHITE OC RD-3 10" 10" 226 - 400 OFF-WHITE (� RD-4 12" 12" 401 - 600 OFF-WHITE O - RD-5 14" 14" 601 - 900 OFF-WHITE OC RD-6 16" 16" 901 - 1250 OFF-WHITE OC REMARKS: - A. ALL SUPPLY DIFFUSERS SHALL BE 4-WAY BLOW UNLESS OTHERWISE SHOWN, METALIURE 5000, OR EQUAL BY TITUS. B. DO NOT INSTALL DAMPER IN DIFFUSERS USE DAMPER AT FLEX TAKE -OFF TO BALANCE AIR FLOW. DIFFUSERS IN INACCESSIBLE CEILINGS SHALL BE PROVIDED WITH CABLE: OPERATED DAMPERS ADJUSTABLE FROM DIFFUSER FACE. C. ALL RETURN DIFFUSERS SHALL BE METALAIRE RH, OR EQUAL BY TITUS. SPLIT SYSTEM EQUIPMENT SCHEDULE AIR HANDLERS DESIGNATION AHU-1 PROTOTYPE MANUFACTURER LENNOX MODEL CBA25UHV-024 WEIGHT (POUNDS) 150 NOM. TONS 2 SYSTEM CAPACITY (BTU/HR) 22,606 / 16,500 TOTAL / SENSIBLE TOTAL AIR FLOW (CFM) 675 OUTDOOR AIR FLOW (CFM) 1 100 EXTERNAL STATIC PRESSURE 0.6" COIL EAT 7 db/wb 7 / 64. COIL LAT'F db/wb 51.7 / 51.4 FAN MOTOR HP 1/2 H.P. HEATER, KW STAGES I 5KW / I ELEC.-VOLTS/PHASE/MCA/MOCP 230 / I / 29 / 30 CONDENSING UNITS (R-410A) DESIGNATION CU-1 PROTOTYPE MANUFACTURER LENNOX MODEL XC16-024-230 PIPE SIZE, SUCTION/LIQUID, IN. 3/4" / 3/8" ELEC.-VOLTS/PHASE/MCA/MOCP 1 230 / I / 15.6 / 20 NOTES: I. AIR HANDLER a CONDENSING UNIT SAME MANUFACTURER. 2. ALL EQUIPMENT TO COMPLY WITH FLORIDA ENERGY CODE. 3. EQUIPMENT MANUFACTURER LISTED IS USED AS THE BASIS OF DESIGN a IS NOT INTENDED TO LIMIT COMPETITION. ALTERNATE EQUIPMENT SHALL BE OF EQUIVALENT PERFORMANCE a QUALITY. 4. CONDENSING COIL TO HAVE FIELD APPLIED "ADVANCOAT SURFSIL" COATING. 5. PROVIDE FREEZE STAT ON INDOOR COIL. 6. SYSTEM SHALL HAVE DUAL SPEED COMPRESSOR WHICH SHALL STAGE BASED ON COOLING DEMAND. 7. PROVIDE LENNOX COMFORTSENSE 7500 PROGRAMMABLE THERMOSTAT WITH INTEGRAL HUMIDISTAT FOR "COOLING FOR DEHUMIDIFICATION." 8. INSTALL CORROSION "GRENADE" ON SUCTION LINE AT COMPRESSOR. NOTE: SOME NOTES & SYMBOLS SHOWN ON THIS LEGEND MAY NOT PERTAIN TO THIS PROJECT. REFRIGERANT PIPING NOTES 1. REFRIGERANT PIPING SHALL BE TYPE "K" OR "L" SOFT DRAWN COPPER TUBING WITH WROUGHT COPPER SOLDER TYPE FITTINGS SUITABLE FOR CONNECTION WITH SILVER SOLDER. 2. COOLING COIL DRIP PIPING SHALL BE TYPE "M" COPPER OR SCHEDULE 40 PVC. PROVIDE 4" DEEP TRAP. 3. PROVIDE ALL VALVES AND SPECIALTIES AS SHOWN BY THE DETAILS AND AS REQUIRED FOR A COMPLETE OPERATING REFRIGERATION SYSTEM. 4. VALVES AND SPECIALTIES SHALL BE AS FOLLOWS: 4.1. AGLOBE VALVES, FORGED BRASS, BACKSEATING TYPE 500 PSI 4.2. CHECK VALVES, FORGED BRASS, 500 PSI 4.3. SOLENOID VALVES, FORGED BRASS, 400 PSI 4.4. REFRIGERANT STRAINERS, BRASS, 350 PSI, 100 MESH STRAINER 4.5. MOISTURE INDICATOR, FORGED BRASS, OPTICAL GLASS, 500 PSI 4.6. FILTER DRYER, STEEL SHELL, REPLACEABLE FILTER DRYER 5. REFRIGERANT PIPING JOINTS: ALL JOINTS SHALL BE MADE WITH SILVER SOLDER. THE PIPING SHALL BE CHARGED WITH DRY NITROGEN WHILE CONSTRUCTING THE JOINTS. A REMOVABLE TYPE DRYER STRAINER SHALL BE INSTALLED IN THE LIQUID LINE. A THREE WAY VALVE BY-PASS SHALL BE PROVIDED FOR THE STRAINER, AFTER THE REFRIGERANT PIPING HAS BEEN COMPLETED, THE REFRIGERANT SYSTEM SHALL BE PRESSURE TESTED WITH NITROGEN AT A PRESSURE OF 300 PSI (HIGH SIDE) AND 150 PSI (LOW SIDE). WHILE THE SYSTEM IS BEING PRESSURE TESTED, AN ELECTRONIC LEAK DETECTOR SHALL BE USED TO CHECK FOR LEAKS. PRESSURE SHALL BE MAINTAINED ON THE SYSTEM FOR A MINIMUM OF 12 HOURS. THE SYSTEM SHALL THEN BE EVACUATED TO 2.0 MM MERCURY AND THEN CHARGED AND MADE READY FOR INSULATION. 6. PIPING EXPANSION AND VIBRATION ELIMINATION: PROVIDE REFRIGERANT TYPE FLEXIBLE CONNECTIONS AT THE AIR HANDLER AND AT THE CONDENSING UNIT. THE CONNECTORS SHALL BE AT LEAST 12' IN LENGTH AND SHALL BE LOCATED TO EFFECTIVELY CONTROL VIBRATION AND TO ALLOW FOR CHANGES IN PIPE LENGTH. PIPE INSULATION NOTES 1. CONDENSATE DRAIN LINES SHALL BE INSULATED WITH 1/2" THICK "ARMAFLEX", OR EQUAL 2. THE REFRIGERANT SUCTION LINES SHALL BE INSULATED WITH 1" THICK "ARMAFLEX", OR EQUAL THE SUCTION LINE SHALL BE INSULATED IN ITS ENTIRETY INCLUDING VALVES AND SPECIALTIES. VALVES AND SPECIALTIES THAT REQUIRE ACCESS SHALL HAVE SPECIAL REMOVABLE COVERS. 3. ALL INSULATION SHALL BE VAPOR SEALED AND BUTT JOINTS OF "ARMAFLEX" SHALL BE TAPED TO PREVENT INTRUSION AT THE JOINT. 4. SADDLES SHALL BE USED AT ALL PIPE HANGERS TO PREVENT COMPRESSION OF THE INSULATION. ELECTRICAL CONNECTION NOTES 1. COORDINATE POWER WIRING AND CONDUIT FROM PANEL THRU FUSED DISCONNECT TO UNIT WITH ELECTRICAL 2. COORDINATE THE FUSED DISCONNECTS WITH ELECTRICAL 3. MAKE FINAL CONNECTIONS TO AIR HANDLING UNIT WITH 'GREENFIELD". MAKE FINAL CONNECTION TO CONDENSING UNIT WITH "LIQUIDTITE". FINAL CONNECTIONS SHALL BE A MINIMUM OF 3 FT. 4. ALL WIRING SHALL BE COPPER. SEE ELECTRICAL DRAWINGS FOR WIRE SIZE. 5. CONTROL WIRING SHALL BE RUN IN CONDUIT. 6. MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR CONTROL WIRING. 7. AIR HANDLING UNIT SHALL BE PROVIDED WITH SINGLE POINT OF ELECTRIC ENTRY. 8. MECHANICAL CONTRACTOR SHALL PROVIDE MOTOR STARTER AND HEATER CONTACTORS IN CONTROL PANEL EXHAUST FAN SCHEDULE SYMBOL DESCRIPTION EF-I GREENHECK SP-1390,75 CFM W/ BACKDRAFT DAMPER - CONNECT TO LIGHT SWITCH. 120V-1o, 0.65A GENERAL NOTES: 1. PRIOR TO SUBMITTING A BID, THF CONTRACTOR SHALL VISIT THE JOB SITE TO THOROUGHLY FAMILIARIZE HIMSELF WITH THE EXISTING FIELD CONDITIONS AND PHYSICAL CONSTRAINTS ASSOCIATED WITH THE WORK TO BE ACCOMPLISHED UNDER THIS CONTRACT. 2. ALL WORK SHALL COMPLY WITH THE LATEST EDITION OF THE FOLLOWING CODES AND STANDARDS: FLORIDA MECHANICAL CODE, FLORIDA ENERGY CODE, NFPA-90A STANDARDS FOR THE INSTALLATION OF AIR CONDITIONING AND VENTILATING SYSTEMS, SMACNA DUCT CONSTRUCTION STANDARDS, ASHRAE 62.1 3. VERIFY FINAL LOCATIONS FOR ROUGH -INS WITH FIELD MEASUREMENTS AND WITH REQUIREMENTS OF THE ACTUAL EQUIPMENT TO BE INSTALLED. 4. COORDINATE THE CUTTING AND PATCHING OF BUILDING COMPONENTS TO ACCOMMODATE THE INSTALLATION OF HVAC EQUIPMENT AND MATERIALS. 5. PROVIDE WEATHER PROTECTION FOR ALL EQUIPMENT AND MATERIALS STORED ON SITE. 6. VENTILATION DUCTWORK SHALL BE SHEET METAL AND INSTALLED IN ACCORDANCE WITH SMACNA. ALL OTHER DUCTWORK SHALL BE AS SHOWN ON THE PROJECT PLANS. DUCTWORK INSULATION SHALL COMPLY WITH THE FLORIDA ENERGY CODE. 7. REFER TO ELECTRICAL CEILING GRID LIGHTING PLAN FOR EXACT LOCATION OF AIR DISTRIBUTION DEVICES 8. PROVIDE ALL DUCT TRANSITIONS REQUIRED TO CONNECT EQUIPMENT SHOWN TO DUCT SYSTEMS. 9. PROVIDE DUCT MOUNTED SMOKE DETECTORS ON THE SUPPLY OF ALL AIR HANDLING SYSTEMS 2000 CFM AND GREATER. 10. MECHANICAL EQUIPMENT ON ROOF OR ELEVATED STRUCTURES SHALL COMPLY WITH FMC-2017 SEC. 306.5 & FBC-2017 SEC. 1510.10. MECHANICAL EQUIPMENT INSTALLED IN ATTICS / ABOVE CEILINGS SHALL COMPLY WITH FMC-2017 SEC. 306.3. 11. MECHANICAL EQUIPMENT, APPLIANCES & SUPPORTS THAT ARE EXPOSED TO WIND SHALL BE DESIGNED & INSTALLED TO RESIST THE WIND PRESSURES DETERMINED IN ACCORDANCE WITH FBC-BUILDING. ALL WIND LOAD & OTHER COMPLIANCE CALCULATIONS AND / OR INSTALLATION DETAILS FOR ROOF MOUNTED EQUIPMENT AS REQUIRED BY FBC-2017 SEC. 1510, 1522, & CHAPTER 16 SHALL BE PROVIDED BY STRUCTURAL ENGINEER / ARCHITECT. CONTRACTOR TO PROVIDE WIND LOAD CALCULATIONS SIGNED & SEALED BY A FLORIDA REGISTERED STRUCTURAL ENGINEER FOR NON PRE -APPROVED CONFIGURATIONS DEVIATING FROM THE ORIGINAL CONSTRUCTION DOCUMENTS. 12. CONTRACTOR SHALL PATCH & REPAIR EXISTING ROOFING MATERIAL AS REQUIRED BY AN APPROVED ROOFING CONTRACTOR FOR ROOFING MEMBRANE ORIGINALLY INSTALLED SO AS TO NOT VOID WARRANTY. CONTRACTOR IS TO PROVIDE REQUIRED STRUCTURAL STEEL FRAMEWORK FOR ADDITIONAL SUPPORT. CONTRACTOR SHALL BE RESPONSIBLE FOR ACQUIRING A STRUCTURAL ENGINEER FOR SIZING OF STRUCTURAL STEEL FRAMEWORK REQUIRED. 13. CLEARANCE FOR MAINTENANCE, SERVICE, REPAIRS & REPLACEMENT FOR ALL MECHANICAL EQUIPMENT SHALL BE PROVIDED TO COMPLY WITH FMC-2017 SEC. 306. SERVICE ACCESS PANELS FOR MECHANICAL EQUIPMENT IN CONCEALED SPACES SHALL BE PROVIDED TO COMPLY WITH THE REQUIREMENTS OF SEC. 306. 14. PROVIDE AIR BALANCE TO QUANTITIES SHOWN ON THE PLANS. PROVIDE ALL VOLUME DAMPERS REQUIRED TO ACCOMPLISH AIR BALANCE. --SUBMIT BALANCE: REPORT FOR REVIEW 15. SYSTEM TEST & BALANCE REPORT (PREPARED BY SEPARATE 3RD PARTY AABC/NEBB CERTIFIED T&B CONTRACTOR) TO BE INCLUDED WITH INSTALIAIION. PROVIDE REPORT TO OWNER AND ENGINEER FOR REVIEW. INSTALLATION WILL NOT BE CONSIDERED COMPLETE WITHOUT T&B REPORT. HVAC CONTRACTOR IS RESPONSIBLE FOR PROVIDING ALL NECESSARY VOLUME DAMPERS, EQUIPMENT, ADJUSTMENTS, ETC. REQUIRED TO ACHIEVE SATISFACTORY T&B RESULTS. 16. THESE DRAWINGS ARE PREPARED PER ESTABLISHED INDUSTRY STANDARDS AND REPRESENT THE ENGINEER'S DESIGN CONCEPT. THEY ARE NOT INTENDED 'TO PROVIDE EVERY DETAIL OR CONDITION REQUIRED TO CONSTRUCT THE BUILDING. THE CONTRACTOR THROUGH SUBMITTALS AND OTHER COORDINATION EFFORTS IS FULLY RESPONSIBLE FOR PROVIDING A COMPLETE AND OPERATIONAL BUILDING WHETHER INDICATED ON THE PLANS OR NOT. FIBRE DUCT INSTALLATION DETAILS w Q 0 0 z Fort Pierce Engineering, Inc. Dependable Mechanical, Electrical & Plumbing Design Reg. No. 28173 315 South 7th Street Fort Pierce, FL. 34950 Phone: 772 672-4636 Fax: 772 672-4637 Q 0 w� z Qo w LL U M DUCT CONSTRUCTION NOTES ° � U U Q W J W 1. ALL DUCT WORK, DUCT FITTINGS, DUCT FLEXIBLE CONNECTIONS, AND FLEXIBLE DUCT SHALL BE CONSTRUCTED Wiz z o AND I TALLER, AS A MINIMUM, IN ACCORDANCE AND WITH THE STANDARDS AND RECOMMENDATIONS OF W U (D�p) o "SMACNA" LATEST PUBLICATIONS AND STANDARDS. ¢ 0 q 2. ALL. DUCT WORK SHALL BE CONSTRUCTED OF 1-1/2, FIBRE BOARD EXCEPT EXHAUST a VENTILATION DUCTS WHICH SHALL BE SHEET METAL. FIBRE DUCTS SHALL BE CONSTRUCTED WITH 1-1/2" BOARD WITH ANTI -FUNGAL INTERIOR COATING. EXPOSED SPIRAL DUCT SHALL BE DOUBLE WALL, I" INTERIOR INSULATION, PAINTED GALVANIZED STEEL. 3. DUCT HANGERS AND SUPPORTS SHALL COMPLY WITH "SMACNA" STANDARDS IN GENERAL, HOWEVER, DUCT W STRAPS SHALL BE USED UP TO 48' IN HORIZONTAL DIMENSION (OR ROUND). DUCTS GREATER THAN 48' SHALL > BE SUPPORTED WITH TRAPEZE HANGERS AND STEEL RODS. z O �- 4. ALL DUCTS SHALL BE OF THE SIZE AND SHAPE AS SHOWN BY CONTRACT DOCUMENTS U w 5. ALL FLEXIBLE DUCTS SHALL COMPLY WITH UI. 181. FLEX DUCTS SHALL NOT BE GREATER IN LENGTH THAN 10'. w w o � z �' Fr WHERE LENGTHS GREATER THAN 10' ARE SHOWN ON THE PLANS INSTALL ROUND SHEET METAL TO WITHIN 10' 2 w O T OF THE DEVICE BEING SERVED. Q + z O Q 0 LL_ 6. SHEET METAL TURNING VANES SHALL BE PROVIDED IN ALL SUPPLY AND RETURN RECTANGULAR DUCT WITH w D w ANGLES GREATER THAN 30DEG . v w Uj oUj a 7. DUCTWORK PENETRATING FIRE RATED WALLS SHALL BE EQUIPPED WITH FIRE DAMPERS. NO OPENINGS WITHIN 5' 0 o 0 ON ETHER SIDE OF THE FIRE RATED WALL DUCTWORK ON EACH SIDE OF A FIRE RATED WALL (5') SHALL BE 0.' A MINIMUM OF 26 GA. SHEET METAL ENGINEER SEAL 8. ALL DUCT DIMENSIONS SHOWN ARE CLEAR INSIDE DIMENSIONS ► t t t i �° DUCT INSULATION NOTES `� 'G ' V Qe 1. ALL INSULATION SHALL COMPLY WITH THE 'FLORIDA ENERGY CODE" LATEST EDITION. so 0 ;•* ; N r 982 2. FLEXIBLE DUCTS SHALL BE OF THE LOW PRESSURE FACTORY FABRICATED TYPE CONSISTING OF A ZINC COATED SPRING STEEL HELIX -0: NON-PEFORATED INNER LINING AND 1-1/2' THICK FIBERGLASS INSULATION i SATE WITH METALIZED MYLAR VAPOR BARRIER. ` OF o 3. ALL INSULATION SHALL HAVE A MAXIMUM FL AME SPREAD/ SMOKE DEVELOPED RATING OF 25/50 t ;:� �:� ',Fs'• •O R ��� -no0 "* ''� 11 ` 4. DUCT SUPPORT HANGERS SHALL PASS AROUND THE OUTSIDE OF THE INSULATION USING SHIELDS OR SADDLES 1"',, SO AS NOT TO COMPRESS THE INSULATION Eric J. Svoboda, PE P.E. No. 60982 MECHANICAL DRAWING INDEX THESE TED=KNTS,REM ARE INTENDED WITH THE RICEPTT E S EC DESIGNS PRESENTED H ARE ONLY SPECIFIC EFOR O FORT PIEtPoSE AND CLIENT ff ETRT P>E1iCE ENGDEERD'IG, INC, FOR CLVE WHICH THEY WERE PREPARED, REUSE OR IMPROPER REUANCE RI THESE MMENTS WHQIT WRITTEN NUTOWTIM AND ADAPTATIRI BY FORT PENCE EM MUNG, DC ML DE � DE �� `�T SHEET DESCRIPTION ISSUED E A�T� M-1 HVAC GENERAL NOTES, SYMBOLS a SCHEDULES YES SHEET TITLE M-2 MECHANICAL HVAC PLAN YES HVAC GENERAL M-3 MECHANICAL HVAC DETAILS YES NOTES, SYMBOLS & SCHEDULES ISSUE DATE: 04-15-2020 DRAWN: EJS APPROVED: EJS DRAWING NUMBER M "I SHEET I OF 3 20001-05 FILE �xtpy 100 CFM OUTSIDE AIR N E UJ UJO:,P,,K F::L,4N ALUMINUM HOOD WITH SCREEN. (TYPICAL) HVAC FL,4N EXISTIN:, / D-MG PLAN SCALE 114" = 1'-0" GENERAL NOTES: 1. REMOVE ANY 8H ALL EXISTING FIVAC SYSTEMS FROM EXISTING STRUCTURE. 2. ROUTE REFRIGERANT LINES FROM AHU ABOVE CEILING, THRU EXTERIOR WALL a DOWN IN METAL HAT CHANNEL TO CU. 3. ROUTE IN CONDENSATE DRAIN LdNE FROM AHU ABOVE CEILING, THRU EXTERIOR WALL a DOWN TO TERMINATE ABOVE GROUND IN LANDSCAPE AREA. 4. PROVIDE MOTORIZED DAMPER 8 VOLUME DAMPER IN O.A. INTAKE. MOTORIZED DAMPER TO OPEN WHEN SYSTEM CYCLES ON, CLOSE WHEN OFF. 5. COORDINATE EXACT AHU, DUCT 8H AIR DEVICE LOCATIONS WITH STRUCTURE & CEILING / LIGHTING LAYOUT. 6. LOCATE FILTER AT BASE OF AHU — NO FILTERS IN RETURN GRILLS. KEY NOTES: O REMOVE ANY a ALL EXISTING HVAC SYSTEMS FROM EXISTING STRUCTURE. 0 AHU ABOVE CEILING. OUTDOOR AIR CALCULATIONS AHU 1 6 PPL x 5 CFM = 30 CFM O.A. 660 SO FT x 0.06 CFM = 39.6 CFM O.A. 69.6 CFM O.A. REQUIRED 100 CFM O.A. PROVIDED U) z 0 w 11111111 WEEMENER Fort Pierce Engineering, Inc. Dependable Mechanical, Electrical & Plumbing Design Reg. No. 28173 315 South 7th Street Fort Pierce, FL. 34950 Phone: 772 672-4636 Fax: 772 672-4637 a .o W� Z Q O W Li- z <L o Qw W I-LW� LLJ of 0) J d CO LL_ n U 0 l--I C// w H U W W W FU-1 z U) Q (L+ o LL O Li l o U D W W w o0 u O O I � N O QI IZ N LL ENGINEER SEAL syco l Now 982 L l i- AZ,0 . cc:: IE OF 4v i O � � F• . / O R \ 'D 4j is '••s..•N'' 0 0NI ',`�`� Eric J. Svoboda, PE P.E. No. 60982 THESE Df1CUlENTS, ALM WITH THE CLI NEPTS AND OR DESIMS PRESENTED HEREIN ARE INTEIIDED OLY FOR THE SPECIFIC PIS Na CUENT OF FORT PIERCE DOMING, INC. FOR WHICH THEY WERE PREPARM WJSE OR INPRIPER RELIANCE OR THESE 11301 7TS WITHWT WRITTEN MTHO ATIEN AND ADAPTATDN BY FORT PIERCE D EERINfi, INC. SH LL IE vrmw LIABILITY III THE SAT£ CO'YRw0202D, FORT PIERCE DC CERIN., INC. ALL RIGHTS RESERVER SHEET TITLE HVAC PLAN ISSUE DATE: 04-15-2020 DRAWN: EJS APPROVED: EJS DRAWING NUMBER M-2 SHEET 2 OF 3 20001-05 STAINLESS STEEL BAND 3' SHAFT INSERT 1 1/2" INSULATION BRANCH DUCT BUTTERFLY DAMPER OPERATOR ON 1 1/2" STAND-OFF TO ALLOW FOR INSULATION USE ROUND SHEET METAL - DUCT HERE TO LIMIT FLEX DUCT TO 10'-0" IN LENGTH 6"SADDLE - DIRECTION OF AIR FLOW BRANCH �I DUCT 1 1/2" STRAPS TO STRUCTURE INSULATED FLEX DUCT I (I RADIUS NOT LESS THAN 1 1/2 x DUCT DIA. 3" SHAFT INSERT STAINLESS STEEL BAND INSULATE BELLS L CEILING CEILING DIFFUSER (TYP-) NOTE: USE BORDER TYPE 1 WHERE IN HARD CLGS. - BORDER TYPE C WHEN EXPOSED TAKE -OFF FITTING - CEILING DIFFUSER. INSULATE BELLS. SECURE FLEX DUCT TO TAKE -OFF SEE HVAC FLOOR FITTING WITH STAINLESS STEEL PLAN FOR LOCATION SCREW DRIVER OPERATED BAND OF DIFFUSER. FLEXIBLE DUCT STRAP DAMPER � CEILING SADDLE 1 1/2" INSULATION )NOTE: USE BORDER TYPE 1 WHERE IN HARD CLGS. - BORDER TYPE C WHEN EXPOSED L- PROVIDE GASKET BETWEEN TAKE OFF FITTING AND BRANCH DUCT. A FLEX DUCT CONNECTION DETAILS DX COOLING COIL TWX VALVE MOISTURE SIGHT GLASS NOTES: 1. PROVIDE ACCUMULATOR IF DEVELOPED LENGTH IS GREATER THAN 50' 2. PROVIDE REFRIGERANT PIPE SIZES RECOMMENDED BY MFG. 3. SEE ALSO REFRIGERANT SYSTEM NOTES CHARGE VALVE W/CAP IF NOT PROVIDED WITH UNIT CONDENSING UNIT SEE DETAIL & SCHEDULE BASE SENSING BULB FILTER DRYER WITH REPLACEABLE CORE ANGLE VALVES —" ISOLATION VALVES (TYPICAL) BALL TYPE ISOLATION VALVES IF NOT PROVIDED WITH UNIT E I REFRIGERANT PIPING SCHEMATIC THREADED ROD (TYP.) HEATER SECTION SUPPLY AIR FLEXIBLE CONNECTION UPPER ATTACHMENTS IN ACCORDANCE WITH SMACNA DETAILS SPRING VIBRATION ISOLATORS (TYP.) DUCTWORK AND COOLING FLEXIBLE CONN. ® COIL ® AS SE REQUIRED SEE DRAWINGS. 14�pl �l n I II I ( I R0 ETUR—N AIR I () I I COND. DRAIN SEE PLUMBING REMOVABLE FILTER AUX. DRAIN PAN. TRAP VRERIG. PIPING. i B I HORIZONTAL AHU DETAIL SCALE = (N.T.S.) SUCTION LINE LIQUID LINE THREADED CAP WITH WO HOLE DRILLED IN TOP, HAND TIGHTENED. TI IREADED CAP, HAND TIGHTENED AIR HANDLER SLOPE TO UNIT DRAIN DRAIN PAN CASING SLEEVE pa UNION NOTE. 1. FILL TRAP MANUALLY ON INITIAL START-UP. 2. PIPE SIZE SHALL NOT BE LESS THAN DRAIN PAN CONNECTION SIZE. 3. A = 1" + FAN SUCTION S.P. B = A / 2 4, ALL CONDENSATE PIPING TO BE PVC. 5. INSULATE ALL DRAIN LINES WITH 2 ARMAFLEX F CONDENSATE DRAIN TRAP DETAIL TYPICAL AIR COOLED CONDENSING UNIT. DO NOT LOCATE UNIT WHERE THE UPBLAST WILL STRIKE: ANY OVERHANG. LOCATE UNIT MINIMUM OF 2'-0' FROM BUILDING EXTERIOR WALL ANCHOR UNIT TO PAD WITH MIN. 1/4" DIA.— EXPANSION BOLTS 0 1 1/2" EMBEDMENT DEPTH & NEOPRENE PAD. (TYPICAL FOR 4) SUCTION & LIQUID REFRIGERANT LINES RUN REFRIGERANT LINES SHORTEST - DISTANCE TO BLDG. EXTERIOR WALL SEE PLANS FOR CONTINUATION. PAD TO BE 4' LARGER ALL AROUND THAN UNIT, FURNISHED WITH 14 REBARS AT 6' O.C. BOTH WAYS 4" a i�� a its o a o a 4' THICK CONCRETE PAD. 2" ABOVE GRADE AND 2" BELOW GRADE MIN. 3000 PSI NOTE: INSTALL TO WITHSTAND 170 MPH WINDS. SCALE=(N.T.S,� C AIR COOLED CONDENSING UNIT DETAIL SECURE TO STRUCTURE ABOVE AS RECOMMENDED BY SMACN4 1 20 GA GALV. METAL STRAP J'n-Aor, '-SHEET METAL SCREW, RIVET OR BOLT TO BOTH SIDES OF DUCT. TYPE 'A' TYPICAL RECTANGULAR DUCT BAND uF Di-\iviL DILL AS HANGER STRAP �tK \D RATED 3TENER 36" DIA. MAX TYPICAL ROUND DUCT I G I DUCT SUPPORT DETAILS DUCT SCHEDULE DUCT DIMENSIONS INCHES TYPE HANGER UP TO 18 A 19 TO 30 A/B 30 TO 60 B NOTE: 8'-0" MAX HANGER SPACING SECURE TO STRUCTURE ABOVE AS RECOMMENDED BY SMACNA HANGER ROD SIZE: Y' TYPE 'B' 1�"x1VOC GALVANIZED ANGLE HANGER RODS, WIRES OR STRAPS CONDENSATION SENSOR FOLDED SEAM CROSS BREAK NOTE: CONDENSATION SENSOR SHALL BE WATER GARD PRIMARY; SECONDARY PART 0401475B OR DROP IN SENSOR #k401485B W/ CONTROL BOARD. 24 VOLTS, 40 TO 75 VA. AUDIBLE ALARM AND/OR WARNING LIGHT. WIRED TO SHUT OFF A/C SYSTEM WHEN WATER LEVEL REACHES 1/16" 8 ACTIVATES THE ALARM OR WARNING LIGHT. MANUFACTURED BY WATER GARD, INC. 12211 CEDAR, GAP HOUSTON, TX 77072 888-652-9800 D EMERGENCY DRIP PAN DETAIL SCALE _ (N.T.S.) BAND ONE HALF -ROUND MAY BE USED IF DUCT SHAPE IS MAINTAINED 3/8" DIA. THREADED STEEL HANGER ROD SEE PLAN FOR EXHAUST DUCT CONTINUATION AND TERMINATION DUCT 1\ SLEEV L EXHAUST DUCT FLEX. CONNECTION TO EXHAUST FAN CABINET FAN NOTES: I. HANGERS: TWIN LOOP CHAIN #N (WORKING LOAD 155 LBS. PROVIDE "S" HOOKS) 2. PAN SHALL BE GALVANIZED STEEL 3. UP TO 4'x W-24 GAUGE. 4. OVER 4'x 5'-22 GAUGE. 5. ALL SEAMS SHALL BE SOLDERED. 6. PROVIDE CROSS BREAK FOR PAN OVER 36" LENGTH OR WIDTH. SCALE _ (N.T UPPER ATTACHMENTS IN ACCORDANCE WITH SMACNA DETAILS RUBBER -IN -SHEAR VIBRATION ELIMINATORS (TYPICAL FOR ALL 4 HANGER RODS) CEILING EXHAUST FAN CEILING GRILLE SCALE (N.T.S.) H CEILING CABINET ]EXHAUST FAN DETAIL _ Z 0 w Fort Pierce Engineering, Inc. Dependable Mechanical, Electrical & Plumbing Design Reg. No. 28173 315 South 7th Street Fort Pierce, FL. 34950 Phone: 772 672-4636 Fax: 772 672-4637 a 0 LLi � QO ww U fY z a0 aw w d Ld U (D tY 0) O O � U 00 L Ih z O vs W z OUj i— U w W _o W U z Tn rr Q (1 0 <o o Q z Q w Lon U 0 w W W w o 0-1O O 0 � N O n Q-I a- N L ENGINEER SEAL ``jjj1Iai►i'i ♦�♦ G 3. SVpe gee ♦♦ °.... ° �0 '�� 6 ee NS ♦�y. N 982 cc e'P S7(KTE OF F%410 I A\'00° P ." `% S °°°°°°° ° G e ee/ ;; ON A L `e♦ Eric J. Svoboda, PE P.E. No. 60982 THESE DDCIBIENfS, &M VM THE CDNCEPTS AND W DESD3IS PRESENTED IEREBJ ARE (WENDED DTLY FM TIE SPECIFIC PMSE Na CLIENT DF FDRT POU QlGDEEIM, INC. FM VW0i M VERE PREPARED WM W WRM FiLIANCE M THESE DDCIA£NTS VnMf WRITTEN NffHM nM AND ADAPTATO BY FMT PIERCE ENGDEUMB BE. SHALL IE Wn WT LIABILITY M TIE SANE, CWYMW 0MM, FMT PIERCE UMMCOU%, BW ALL RNMS RESERVED SHEET TITLE MECHANICAL DETAILS ISSUE DATE: 04-15-2020 DRAWN: EJS APPROVED: EJS DRAWING NUMBER M-3 SHEET 3 OF 3 SCALE = (N.T.S.) 20001-05 NU: UVIJI TANKLESS HEATER MOUNTED TO WALL BELOW COUNTER CW SHUT-OFF OM MECHANICAL TEMPERING /MIXING VALVE ASSE 1070 APPROVED ITN--rAII t1\— INIC`TAI I A-r1nK1 nC' IANKLLS�) WAI LK HLAI LK N.T.S. PLUMBING FIXTURE SCHEDULE CODE DESCRIPTION HW CW WASTE VENT TRAP REMARKS WATER CLOSET, FLOOR MOUNTED, AMERICAN STD. CADET RIGHT HEIGHT MODEL PRESSURE ASSISTED, VITREOUS EQUAL BY KOHLER OR WC-1 CHINA, ELONGATED RIM, OPEN FRONT — 1/2" 3" 2" INT TOTO SEAT LESS COVER, POLISHED CHROME ACTUATOR ON WIDE SIDE, ADA COMPLIANT. _ LAVATORY, WALL HUNG W/ FLOOR EQUAL BY KOHLER OR MOUNTED CONCEALED ARM CARRIER, AM. TOTO. PROVIDE BELOW STD. LUCERNE MODEL, VITREOUS CHINA, DECK ASSE 1070 L-1 (3)-4" CENTER HOLES, 4" HIGH BACK, 1 1/4" 1/2" 1/2" 2" 1 1/4" 1 1/4" APPROVED MECHANICAL. 'P' TRAP, GRID DRAIN. CHICAGO FAUCET MIXING / TEMPERING VALVE. MODEL 802-V VANDAL RESISTANT, ADA SET AT MAX 110 DEG. COMPLIANT. COUNTER TOP SINK, JUST MODEL SL-2122- PROVIDE BELOW DECK A-GR, S.S., SELF RIMMING, (4)4' CENTER ASSE 1070 APPROVED S-1 HOLES, 1 1/2" 'P' TRAP, JWF-201-W4 1/2" 1/2" 2" 1 1/2" 1 1/2" MECHANICAL MIXING I FAUCET WITH SPRAY, J-35 DRAIN. TEMPERING VALVE. SET AT MAX 120 DEG. PLUMBING EQUIPMENT SCHEDULE CODE DESCRIPTION REMARKS EXTERIOR CLEAN OUT, 2-WAY, ADJUSTABLE: SET IN 12" X 12" X4" CO-1 TOP, INTERNAL CLOSURE PLUG, HEAVY DUTY' CONCRETE COVER PLATE. WALL CLEAN OUT PLUG WITH CHROME PLATED CO-2 BRASS COVER PLATE. TANKLESS WATER HEATER, CHRONOMITE SR- MOUNT BELOW tUNTER. 15L, 1.8KW, 120V, 1 PHASE PROVIDE BELOW DECK ASSE 1070 AP ROVED TWH-1 MECHANICAL MIXING / TEMPERING VALVE. SET AT MAX 110 DEG. TANKLESS WATER HEATER, CHRONOMITE CM - MOUNT BELO DECK / 15L 1240, 3.6KW, 230V, 1 PHASE FIXTURE. PROVI E BELOW DECK ASS 11070 TWH-2 APPROVED MECHANICAL MIXING / TEMPER NG VALVE. SET AT MAX 1 2Q DEG. HOSE BIBB, ALL BRASS, 3/4" HOSE: PROVIDE SHUT-OFF TO HB-1 CONNECTION, VACUUM BREAKER, LOOSE KEY EACH HOSE BIBB PER STOP. CODE. PLUMBING SYMBOLS UtNERAL SYMBOLS DESCRIPTION — — COLD WATER (CW) - - HOT WATER (HW) 1. PLUMBING CONTRACTOR IS TO FURNISH AND INSTALL ALL SEWER (S) PLUMBING FIXTURES COMPLETE AS LISTED IN "PLUMBING FIXTURE SCHEDULE". — — — VENT LINE (V) 2. PLUMBING CONTRACTOR MAY USE SCHEDULE 40 OR 80 TYPE I, HWR— RECIR. HOT WATER GRADE I, POLYVINYL CHLORIDE PIPE FOR ALL SOIL, WASTE AND CD CONDENSATE DRAIN VENT PIPING WHERE PERMITTED BY LOCAL CODES. WHERE PVC PIPING IS NOT PERMITTED BY LOCAL CODES, USE STANDARD X EXISTING PIPE WEIGHT CAST IRON PIPING. ALL PIPING ABOVE GRADE MAY HAVE HUBLESS FITTINGS. PLASTIC PIPING SHALL NOT BE USED IN A e CONNECT TO EXISTING RETURN AIR PLENUM. COORDINATE THIS REQUIREMENT WITH —SD— STORM DRAIN (SD) H.V.A.C. CONTRACTOR. P PUMP 3. PROVIDE SHUT-OFF GATE VALVES ON ALL EQUIPMENT a HOSE BIBBS, a STOP COCKS IN HCT AND COLD WATER PIPING TO ALL VTR VENT THRU ROOF PLUMBING FIXTURES. WC WATER CLOSET 4. ALL WATER PIPING BELOW GRADE SHALL BE TYPE "L" SOFT UR URINAL TEMPERED COPPER AND ALL WATER PIPING ABOVE GRADE SHALL BE TYPE "L" HARD TEMPERED COPPER. HL HAND LAVATORY L-(No) LAVATORY 5. INSTALL I" FOAM RUBBER INSULATION ON ALL HOT WATER PIPING ABOVE a BELOW GRADE. ALL JOINTS IN INSULATION ARE HB HOSE BIBB TO BE TAPED. SS SERVICE SINK 6. ELEVATION OF ALL FLOOR DRAINS SHALL BE HELD 1/2" BELOW FINISH FLOOR TILE. DF DRINKING FOUNTIAN 7. ALL MATERIAL AND INSTALLATIONS SHALL BE IN ACCORDANCE EWC ELECTRIC WATER COOLER WITH ALL LOCAL AND STATE PLUMBING AND MECHANICAL CODES, EWH ELECTRIC WATER HEATER INCLUDING THE STANDARD BUILDING, PLUMBING AND MECHANICAL CODES, NFPA, ASME, ASHRAE, ASA AND AGA. GWH GAS WATER HEATER 8. THE SANITARY SYSTEM INCLUDES CONNECTION TO FIXTURES, SH SHOWER RUNNING OF SOIL AND WASTE LINE AND SOIL AND VENT HS HAND SINK SANITARY SEWER SYSTEM AND/OR SEPTIC TANKS AND DRAIN FIELDS AND ALL ITEMS AS SHOWN ON DRAWINGS. VENT STACKS FD FLOOR DRAIN SHALL EXTEND THROUGH ROOF WITH LEAD FLASHING. RD ROOF DRAIN 9. THE DOMESTIC WATER SYSTEM INCLUDES CONNECTIONS TO THE �-- GATE VALVE DESIGNED SYSTEM, CONTROL VALVES AND PIPING TO PLUMBING GLOBE VALVE FIXTURES, INCLUDING CONNECTIONS TO EQUIPMENT FURNISHED BY OTHERS. CHECK VALVE 10. PIPE INSTALLATIONS AND MATERIALS SHALL BE AS REQUIRED TO -Pa vco- BACK FLOW PREVENTER MAINTAIN FIRE RATINGS WHERE REQUIRED BETWEEN FLOORS AND/OR BETWEEN UNITS. VALVE IN YARD BOX u (TYPE AS NOTED) 11. ARRESTERS SHALL BE INSTALLED WHERE NECESSARY TO PRESURE RELEIF VALVE (RV) PREVENT WATER HAMMER. -- M�-- WATER METER 12. COPPER PIPING WHERE USED SHALL NOT CONTACT DISSIMILAR METALS OR MASONRY. PROVIDE ISOLATING BUSHINGS WHEN �p ELBOW - UP CONNECTING TO ANY DISSIMILAR METALS. —.Q-- RISE OR DROP 13. PLUMBING CONTRACTOR SHALL COORDINATE WITH ARCHITECT FOR �'-- CONCENTRIC REDUCER DETAILED DIMENSIONS AND LOCATIONS OF ALL FIXTURES AND EQUIPMENT AND FOR ANY CHANGES IN LAYOUT. —p— DIRECTION OF FLOW 14. PLUMBING CONTRACTOR SHALL MAKE ALL TEST AND ADJUST- C.O? CLEAN OUT (RISER) MENTS AS REQUIRED, UPON COMPLETION OF WORK AND PRIOR TO FINAL ACCEPTANCE BY OWNER. —C.O. _0_ C.O. CLEAN OUT 15. AFTER COMPLETION OF THIS WORK, THE CONTRACTOR SHALL WALL CLEAN OUT OBTAIN A CERTIFICATE OF FINAL INSPECTION AND APPROVAL rid FROM ALL AUTHORITY'S HAVING JURISDICTION. {� PLUGGED PIPE SHOWER HEAD 16. ALL WORKMANSHIP, MATERIALS AND APPARATUS UNDER THIS CONTRACT SHALL BE GUARANTEED FOR A PERIOD OF ONE YEAR FROM DATE OF FINAL ACCEPTANCE BY THE OWNER. PUMP W/FLOW DIRECTION FLOW SWITCH 17. THESE DRAWINGS ARE PREPARED PER ESTABLISHED INDUSTRY STANDARDS AND REPRESENT THE ENGINEER'S DESIGN CONCEPT. THEY PRESSURE SWITCH ARE NOT INTENDED TO PROVIDE EVERY DETAIL OR CONDITION REQUIRED TO CONSTRUCT THE BUILDING. THE CONTRACTOR THROUGH �A,B,C,D WATER HAMMER ARRESTER SUBMITTALS AND OTHER COORDINATION EFFORTS IS FULLY WITH P.D.I. SIZE RESPONSIBLE FOR PROVIDING A COMPLETE AND OPERATIONAL BUILDING WHETHER INDICATED ON THE PLANS OR NOT. SWEET DESCRIPTION ISSUED P-1 PLUMBING LEGEND, NOTES, SCHEDULES a DETAILS YES P-2 PLUMBING PLAN YES P-3 PLUMBING WASTE -VENT a WATER RISER YES W z 0 fy W F- a 0 11 Fort Pierce Engineering, Inc. Dependable Mechanical, Electrical & Plumbing Design Reg. No. 28173 31.5 South 7th Street Fort Pierce, FL. 34950 Phone: 772 672-4636 Fax: 772 672-4637 Q Ly 0 Qo U ww Qw U aw W wa w ��rn J c o L L n U O W O � U W W F_o w U z "' 0 (� O of Q G� a O LL z O U w O = U ~ J D w w W o O O 0 � N O CL A -I a_ N U_ ENGINEER SEAL ``XIIIIIIIIIIII Se0 O 00 0. - z o s Q: �L S ATE OF We ..06. .�. • ' O N A I- Eric J. Svobodo, PE P.E. No. 60982 THESE DOCUENTS, AUM WITH THE CNVTS AND FR DESIIDFS PRESENTED I£IZEDF ARE WDIDED IDLY FOR THE SPECI C PLWGSE AND MM OF FORT PIERCE DJGDEERD7G, INC. FOR WHICH THEY WERE PREPARED, REUSE OR DPRCFER RDIA CE ON THESE DDm"s wnw WRITTEN AUDQ:IZATIIN AND ADAPTATIIN BY FORT PIERCE ENGDEERMD, INC. SHALL BE WITH7IT LIABRITY TO THE SANE COPYRIGHT©M, FMT ROME ENMIntMG, DC. ALL RIGHTS RESERVED, SHEET TITLE PLUMBING LEGEND, NOTES, SCHEDULES & DETAILS ISSUE DATE: 04-15-2020 DRAWN: EJS APPROVED: EJS DRAWING NUMBER M, NOTE: SOME SYMBOLS SHOWN ON THUS LEGEND MAY NO 1, PERTAIN TO THIS PROJECT. EL d Q L U CC 0 4" WASTE. SEE SITE UTILITY PLAN. 8 DFU CO-1 PLU 1• WATER. SEE SITE HB-1 U1ILITY PLAN. 12 WFU BT4 — > ME31NC; FLAN EXISTING / DEMO FLAN SCALE 1/�" = I'-O" ACTIVE WASTE LINE CUT a CAP ABANDONED CONNECTION 2FT OR 2FT OR LESS LESS DEVELOPED DEVELOPED LENGTH LENGTH FROM ACTIVE WASTE LINE TO PREVENT DEAD-END. GENERAL NOTES: I. REMOVE EXISTING PLUMBING FIXTURES AS INDICATED. 2. CUT a CAP EXISTING WASTE a WATER CONNECTIONS AS NECESSARY. 3. FIELD VERIFY WASTE INVERT ELEVATIONS PRIOR TO ROUTING LINES. 4. ROUTE WATER LINES ALONG UNDERSIDE OF ROOF OR ABOVE CEILING AS INDICATED. KEY NOTES: 0 REMOVE EXISTING WATER CLOSET. 0 REMOVE EXISTING LAVATORY. 0 REMOVE EXISTING TUB / SHOWER. (4) REMOVE EXISTING SINK. �J ROUTE I" WATER UP ABOVE CEILING. O PROVIDE VALVE BOX FOR REFRIGERATOR WATER CONNECTION. (77) 2N VENT THRU ROOF. (8) TANKLESS WATER HEATER ON WALL BELOW FIXTURE. 11111111 NEENNEEN Fort Pierce Engineering, Inc. Dependable Mechanical, Electrical & Plumbing Design Reg. No. 28173 315 South 7th Street Fort Pierce, FL. 34950 Phone: 772 672-4636 Fax: 772 672-4637 a .o w� Qo w �- o' z a LI.i U U -1 W W W 0- Ljj U (0 x 0) P4 O O [t U CO LL FM 0 I� W W 0 U W W W �o w z 0 Q w 0 o p 0 z � Lv F_ rr U Z) w Lg a w o0 O O 0 a� N O P- LL N LL ENGINEER SEAL ee��►iirrriii ♦♦ee�G 3. SV% It 0 * 0982 .-10 o -)3STATE OF : w P. Z O 44/ 0 N A U Eric J. Svoboda, PE P.E. No. 60982 THESE DICIWO, ALORG VITH THE COKEPTS AND OR DESIM PRESENTED Hi M ARE INTENDED OLY FOR THE SPECIFIC PURPOSE AND CLIENT OF FORT PIERCE DaG4EERING, D& FOR VHDCH THEY WERE PREPARED. REUSE OR DPRIPER RELIANCE W THESE DOCNI ENTS WDMIT WRITTEN AUTHWMTILN AND ADAPTATILN BY FORT PIERCE DOURHG, DRC. VALL DE WITMUT LIABILITY TO THE SANE. COPYRIGHT®2020, FORT PIERCE D04MC, BE ALL RIUM REMNM SHEET TITLE A PLUMBING ACTIVE WATER BRANCH FLOOR PLAN CUT a CAP ABANDONED CONNECTION IMMEDIATELY AT ACTIVE BRANCH CONNECTION IN.ISSUE DATE: 04-15-2020 TAKE -OFF TO PREVENT DEAD -LEG. INDRAWN: EJS UJ,4ST� � �UATER DEMO DETAIL NTS APPROVED: EJS DRAWING NUMBER P-2 SHEET 2 OF 3 _ — 20001705 ELECTRICAL SYMBOL LEGEND SPECIFICATIONS: TELEPHONE/DATA SYSTEM SYMBOL DESCRIPTION PHONE/DATA OUTLETS MOUNTED AT RECEPTACLE HEIGHT UNLESS OTHERWISE NOTED. C = ABOVE THE COUNTER M = NUMBER OF DATA PORTS, DEFAULT = I N = NUMBER OF PHONE PORTS, DEFAULT = I MA DATA OUTLET, 8P8C 0 N PHONE OUTLET, RJ II M N COMBINED DATA/PHONE OUTLET, 8P8C/RJII ® TELEPHONE OUTLET FLOOR MOUNTED TTB TELEPHONE/COMPUTER TERMINAL BOARD mTmmmmmnmm � - TELEPHONE TERMINAL CABINET ", -T-�\ TELEPHONE SYSTEM RACEWAY TELEVISION RACEWAY SYSTEM TV❑ TELEVISION OUTLET FOR ANTENNA TV TELEVISION SIGNAL WALL OUTLET ,,,,-TV-.ATV DISTRIBUTION SYSTEM RACEWAY BE MAGNETIC LOCK CCTV CAMERA W/ CONDUIT TO VIDEO JUNCTION BOX PTZ PAN/ TILT/ ZOOM CCTV CAMERA W/CONDUIT TO VIDEO JUNCTION BOX - MOUNTED MIN 15' AFF OR o CEILING SYNCHRONOUS MASTER CLOCK SYSTEM -0 SYNCHRONOUS SYSTEM CLOCK FATC MASTER CLOCK CONTROL PANEL __can_ MASTER CLOCK SYSTEM CONDUIT AND WIRING DOORBELL SYSTEM -Q DOOR PUSH-BUTTON STATION WP = WEATHERPROOF D6 DOORBELL CHIME (SELF CONTAINED) ,---DB---, DOORBELL SYSTEM CONDUIT AND WIRING DOOR CONTROL SYSTEM ® MOTION DETECTOR 360 CR CARD READER K1 DIGITAL KEYPAD ® BALANCED MAGNETIC DOOR CONTACT FIRE ALARM/DETECTION SYSTEM SYMBOL DESCRIPTION F❑ MANUAL PULL STATION CEILING SMOKE DETECTOR, PHOTOELECTRIC TYPE UNLESS OTHERWISE NOTED E = ELEVATOR WITH RECALL CONTACTS I = IONIZATION DUCT SMOKE DETECTOR, SIMPLEX 4098-9686 OR EQUAL SA = SIMPLEX 4098-9687 OR EQUAL ® SUPERVISED CONTROL RELAY �R DUCT DETECTOR REMOTE ALARM INDICATOR AND, TEST STATION, WALL MOUNTED 72" AFF, SIMPLEX 4098-9835 OR EQUAL -® DUCT DETECTOR REMOTE A/V CONTROL STATION WITH TEST SWITCH, WALL MOUNTED 72" AFF, SIMPLEX 4098-9842 OR EQUAL COMBINATION AUDIBLE/VISUAL XXCD NOTIFICATION DEVICE CD = CANDELA RATING, MINIMUM 75 CD PER FBC 11-4.28.3(4) SS FIRE ALARM SPEAKER - CEILING MOUNTED -(© WALL MOUNTED SPEAKER WITH STROBE XXCD CD = CANDELA RATING -®S FIRE ALARM SPEAKER - WALL MOUNTED O FIRE ALARM SPEAKER WITH STROBE - CEILING MOUNTED CD = CANDELA RATING VISUAL SIGNALING UNIT, WALL MOUNTED (NO AUDIO DEVICE) �P FIREMAN'S PHONE JACK SPRINKLER TAMPER SWITCH CONNECTION FS SPRINKLER WATER FLOW SWITCH CONNECTION FP FIRE ALARM SYSTEM PRINTER -® ZONE ADDRESSABLE MODULE ® ELECTROMAGNETIC DOOR HOLD OPEN DEVICE ®H ELECTROMAGNETIC DOOR HOLD OPEN DEVICE HOLDER CONNECTION TO CLOSURE/ 19H ELECTROMAGNETIC DOOR HOLD OPEN DEVICE INCLUDES DETECTOR C%INECTION TO CLOSURE/ HOLDER O CEILING HEAT DETECTOR 135 F UNLESS OTHERWISE INDICATED. [04 BEAM DETECTOR - TRANSMIT?'ER 04 BEAM DETECTOR - RECEIVER Fo FIRE ALARM CONTROL PANEL Fo FIRE ALARM TERMINAL, CABINET FAAP FIRE ALARM ANNUNCIATOR PANEL - FLUSH MOUNTED F \ FIRE ALARM SYSTEM CONDUIT AND WIRING FIREMAN'S ELEVATOR 'WARNING LIGHT ® KNOX BOX -LOCATION TO BE COORDINATED WITH THE AHJ PAGING SYSTEM & BACKGROUND MUSIC INTERCOM SYSTEM LOUDSPEAKER/ TRANSFORMER/ BAFFLE/ IC MASTER STATION SUPPORT TRUSS. (CEILING MOUNTED) W = WALL MOUNTED C = COUNTER D = DESK LOUDSPEAKER/ TRANSFORMER/ BAFFLE/ W = WALL MOUNTED ENCLOSURE FOR EXPOSED CEILING AREAS H = HAND SET TYPE W = MALL MOUNTED HF = HANDS FREE WP = WEATHER PROOF ❑S 4 HORN/TRANSFORMER FOR HIGH NOISE AREAS IC INTERCOM SYSTEM SPEAKER W = WALL MOUNTED Po _ PAGING SYSTEM EQUIPMENT CABINET to INTERCOM EQUIPMENT CABINET PATC o PAGING SYSTEM TERMINAL CABINET ICCTTC INTERCOM TERMINAL CABINET ,,,-DR--,,,DOCTORS REGISTRY SYSTEM CONDUIT AND WIRING /-- IC INTERCOM SYSTEM CONDUIT AND WIRING So SOUND SYSTEM EQUIPMENT CABINET SSTC - SOUND SYSTEM TERMINAL CABINET SOUND SYSTEM CONDUIT AND WIRING VC VOLUME CONTROL GFCI DEAD FRONT/BLANK FACED, WHITE GFCI DEVICE. EATON # SGFD20 W. MOUNTED AT 48' AFF OR EQUAL cr= CONTROLLED RECEPTACLE. BREAK OUT TAB FOR SPLIT OPERATION. SHALL BE MARKED IN FIELD PER 406.3(E). WITH THIS SYMBOL: (-',- BOTTOM RECEPTACLE TO BE CONTROLLED. BASIC MATERIALS SYMBOL DESCRIPTION Sa SINGLE POLE SWITCH (SUBSCRIPT INDICATES ITEM CONTROLLED) S3 THREE-WAY SWITCH S4 FOUR-WAY SWITCH SD DIMMER SWITCH (1500 WATTS UNLESS OTHERWISE INDICATED) SF CEILING WHITE FAN/LIGHT CONTROL, DAN'S FAN CITY #423LW OR EQUA OLOR SK SINGLE POLE KEY SWITCH S3K THREE-WAY KEY SWITCH S4K FOUR-WAY KEY SWITCH SL SINGLE POLE SWITCH WITH SECURITY LOCKING KEY SLV LOW VOLTAGE SWITCH SM MOTOR RATED SNAP SWITCH, IHP MIN., 20A, 120/27TV LEVITON 1121-2 OR EQUAL SMp MANUAL MOTOR STARTER WITH OVERLOAD HEATERS AND PILOT LIGHT Sp SINGLE POLE SWITCH WITH PILOT LIGHT SR SINGLE POLE SWITCH CONTROLLING SWITCHED RECEPTACLE STD SINGLE POLE SWITCH - TIME DELAY FOR EXHAUST FAN/LIGHTS SWp SINGLE POLE SWITCH WITH WEATHERPROOF COVER SWST SPRING WOUND WALL SWITCH TIMER (30 MIN.) DUPLEX RECEPTACLE, 5-20R UNLESS OTHERWISE NOTED TE) SINGLE 5-20R RECEPTACLE, T DENOTES TWIST -LOCK GFCI DEAD FRONT/BLANK FACED, WHITE GFCI DEVICE. EATON # SGFD20 W. MOUNTED AT 48" AFF OR EQUAL (9= SURGE PROTECTION TYPE (TVSS) SP DUPLEX RECEPTACLE ® PEDESTAL MOUNTED RECEPTACLE ® FLOOR OUTLET BOX AND DUPLEX RECEPTACLE WITH APPROPRIATE FLANGE. FLOOR OUTLET BOX WITH DUPLEX RECEPTACLE ® AND ONE COMBINATION W/ VOICE/DATA OUTLET ® FLOOR OUTLET BOX WITH TWO DUPLEX RECEPTACLES AND ONE COMBINATION W/ VOICEMATA OUTLET © POKE THRU pp POWER POLE SINGLE POLE SWITCH/RECEPTACLE COMBINATION S DUPLEX RECEPTACLE WITH EACH HALF ON SEPARATE CIRCUIT (BREAKER SHALL BE TWO POLE WITH COMMON TRIP) DUPLEX RECEPTACLE MOUNTED ABOVE COUNTER DUPLEX TAMPER -RESISTANT RECEPTACLE. MOUNT COVER PLATE WITH SPANNER HEAD SCREWS DUPLEX RECEPTACLE WITH TOP HALF SWITCHED GFCI RECEPTACLE (EWC DENOTES ELECTRIC WATER COOLER. COORDINATE WITH EWC EWC INSTALLER FOR MOUNTING HEIGHT) - WPGFCI RECEPTACLE. WP DENOTES WEATHERPROOF COVER. GFCI RECEPTACLE MOUNTED ABOVE COUNTER TWO DUPLEX RECEPTACLES WITH COMMON COVER TWO DUPLEX RECEPTACLES WITH COMMON COVER MOUNTED ABOVE COUNTER C- CONTROLLED RECEPTACLE. BREAK OUT TAB FOR SPLIT OPERATION. SHALL BE MARKED IN FIELD PER 406.3(E). ISOLATED GROUND DUPLEX RECEPTACLE, IG (ORANGE DEVICE) DUPLEX RECEPTACLE NOTE: TICK MARKS SHOWN ON ANY DEVICE REPRESENTS RECEPTACLE CONNECTED TO THE EMERGENCY CIRCUIT (RED DEVICE) TYPICAL FOR ANY DEVICE IN LEGEND ® SPECIAL PURPOSE RECEPTACLE, RATING AS NOTED ASTRONOMIC TIME SWITCH ABLE TO RETAIN CEI PROGRAMMING AND THE TIME SETTING DURING LOSS OF POWER FOR A PERIOD OF AT LEAST 10 HOURS. ® PHOTOCELL, MOUNTED ON ROOF FACING NORTH ® GROUND BAR ® PLUG-IN STRIP WITH RECEPTACLES, 18" O.C. UNLESS OTHERWISE INDICATED ® UNDER GROUND CONCRETE ENCASED DUCTBANK JUNCTION BOX -<D JUNCTION BOX- WALL MOUNTED JUNCTION BOX- FURNITURE SYSTEM FEED ■ CONDUIT SEAL -OFF FITTINGS SP 3 SURGE PROTECTIVE DEVICE C3 = TYPE I, NEMA 4X, CITEL MDS300 OR EQUAL B3 = DISTRIBUTION BOARD DEVICE, SEE RISER FOR RATING A3 = PANEL BOARD DEVICE, MAX 125KA PER PHASE ST SHUNT -TRIP BUTTON - FLUSH MOUNTED UNLESS OTHERWISE NOTED NEMA 313 FOR EXTERIOR LOCATIONS EDH-X ELECTRIC DUCT HEATER MOTOR CONNECTION ® VARIABLE FREQUENCY DRIVE HD ELECTRIC HAND DRYER FD-D-a DIRECT DIGITAL CONTROL PANEL T❑ TRANSFORMER NOTE: SOME SYMBOLS SHOWN ON THIS LEGEND MAY NOT PERTAIN TO THIS PROJECT. BASIC MATERIALS CONT. SYMBOL DESCRIPTION E� AUTOMATIC TRANSFER SWITCH J NON -FUSED DISCONNECT SWITCH, AMP RATING / # OF POLES NEMA I IF INDOORS NEMA 3R IF OUTDOORS ®J 30AR FUSED DISCONNECT 20AF AR DENOTES AMP RATING OF SWITCH AF DENOTES AMP FUSE SIZE MCP DENOTES FUSE PER MANUFACTURER RECOMMENDATIONS SIZE` # OF POLES �i 30/3 3R COMBINATION MAGNETIC MOTOR STARTER, SIZE a # OF POLES 0 3 POLE UNLESS OTHERWISE NOTED ENCLOSURE NEMA RATING. NEMA STARTER SIZE -�■- BRANCH CIRCUIT PANEL BOARD, UNDER 250 VOLTS, SURFACE MOUNTED �C BRANCH CIRCUIT PANEL BOARD, UNDER 250 VOLTS, FLUSH MOUNTED BRANCH CIRCUIT PANEL BOARD, OVER 250 VOLTS, SURFACE MOUNTED BRANCH CIRCUIT PANEL BOARD, OVER 250 VOLTS, FLUSH MOUNTED BRANCH CIRCUIT CONDUIT CONCEALED ABOVE CEILING OR IN WALL. -� CONDUIT SHALL INCLUDE PHASE, NEUTRAL AND GROUND CONDUCTORS AS REQUIRED FOR CIRCUITS (UNLESS OTHERWISE NOTED). BRANCH CIRCUIT CONDUIT CONCEALED IN SLAB, UNDERGROUND OR UNDER FLOOR. BRANCH CIRCUIT CONDUIT EXPOSED ��-- GROUND OR GROUND ROD AS NOTED -EM-� EMERGENCY BRANCH CONDUIT -OUP CONDUIT TURNING UP DN CONDUIT TURNING DOWN -- ] CONDUIT STUB --� CONDUIT CONTINUED FLEXIBLE CONDUIT EXISTING TO BE REMOVED - EXISTING TO REMAIN -- EXISTING AFFECTED BY THIS PROJECT -- - FUTURE NEW LIGHTING I- 0� 4 LINEAR OR STRIP FIXTURE FIXTURE -A DESIGNATIOIN ® LAY -IN TROFFER FIXTURE CIRCUIT--2 a- LOWER CASE LETTER INDICATES LIGHTING CONTROL NUMBER LAY -IN TROFFER FIXTURE DIAGONAL SHADING DENOTES EMERGENCY LIGHT FIXTURE. WRAP AROUND OR SURFACE MOUNTED FIXTURE. `-� WALL MOUNTED VANITY OR CLOSET FIXTURE EXTERIOR WET LOCATION WALL MOUNTED FIXTURE 0 CEILING OR SOFFIT MOUNTED DOWNLIGIHT FIXTURE Q PENDANT OR BAY FIXTURE WALL WASH FIXTURE �- ACCENT FLOOD LIGHTING - AIMING AS INDICATED EXIT LIGHT FIXTURE 0 DIRECTION ARROWS AS SHOWN (SHADED QUADRANT INDICATES FACE(S) OF FIXTURE) F�o WALL MOUNTED EXIT LIGHT FIXTURE COMBINATION EXIT/EMERGENCY LIGHT (FIXTURE W/REMOTES POLE MOUNTED AREA LIGHT FIXTURE WITH ARMS AS SHOWN ON DRAWINGS PB ELECTRICAL PULL BOX TRACK WITH TRACK LIGHT FIXTURE (TRIANGLES INDICATE QUANTITY OF LIGHT FIXTURES) ® BATTERY PACK WITH TWIN HEADS (CEILING MOUNT) BATTERY PACK WITH TWIN HEADS (WALL MOUNT) LIGHTING CONTROL SYSTEM -o LIGHTING CONTROL PANEL SA WALL -MOUNTED, MANUAL ON/OFF SWITCH AND AUTOMATIC OFF OCCUPANCY SENSOR S P WALL -MOUNTED, ON PULSE / OFF PULSE BUTTON TIME SWITCH CONTROL PER FBC C405.2.2.1. is INDEPENDENT 7-DAY PROGRAMMING HOLIDAY SETTING, 10 HOUR PROGRAM BACKUP TWO-HOUR MANUAL OVERRIDE MODE. INTERMATIC ET2800 SERIES OR EQUAL DD PASSIVE INFRARED / ULTRASONIC OCCUPANCY SENSOR C = CEILING MOUNT W = WALL MOUNT ® DAYLIGHT SENSOR SMS SINGLE POLE SWITCH - PASSIVE INFRARED OCCUPANCY SENSOR ® LIGHTING ROOM CONTROLLER/POWER SUPPLY I. THE TOTAL ELECTRICAL INSTALLATION MUST MEET THE REQUIREMENTS OF THE CURRENT EDITION OF THE FLORIDA ADMINISTRATIVE CODE (FAC), SECTION 61GI5-33, AND, BY REFERENCE IN THE FAC, THE FLORIDA BUILDING CODE, 6TH EDITION, (2017), THE FLORIDA FIRE PREVENTION CODE, 6TH EDITION, (2017), AND THE 2014 EDITION OF NFPA 70, THE NATIONAL ELECTRICAL CODE. 2. ON ALL ELECTRICAL PLAN SHEETS, E.G. "E-11, "E-2.11, ETC., THE TERM "CONTRACTOR" SHALL MEAN "ELECTRICAL CONTRACTOR", SOMETIMES ALSO ABBREVIATED AS "E.C." 3. MATERIALS AND EQUIPMENT INSTALLED SHALL BE ENTIRELY NEW, UNLESS OTHERWISE NOTED, AND SHALL MEET U.L. REQUIREMENTS. 4. EQUIPMENT SHALL BE OF MATERIALS SUITABLE FOR AND RATED FOR THE ENVIRONMENT IN WHICH THEY ARE TO BE INSTALLED. 5. CONTRACTOR TO INSTALL A COMPLETE ELECTRICAL SYSTEM FOR LIGHTING AND POWER FROM THE EQUIPMENT REQUIRED BY SERVING ELECTRIC UTILITY AT THE POINT OF DELIVERY HANDHOLE TO AND THROUGH THE METER ENCLOSURE, SERVICE DISCONNECT, AND BRANCH -CIRCUIT PANEL "PI" TO AND INCLUDING ALL EQUIPMENT SPECIFIED ON THESE PLANS AND EQUIPMENT FURNISHED BY OTHERS AS MAY BE REQUIRED. 6. CONTRACTOR SHALL MAKE EARLY CONTACT AND MAINTAIN DIRECT COMMUNICATION WITH THE SERVING ELECTRIC UTILITY TO ENSURE CORRECT INSTALLATION OF CONDUITS PRIOR TO CONCRETE AND PAVEMENT INSTALLATIONS, TO ENSURE CORRECT INSTALLATION OF METERING FACILITIES, TO ASSIST THE OWNER IN OBTAINING A FAULT CURRENT LETTER, AND TO ENSURE THE TIMELY PROVISION OF ELECTRIC SERVICE. 7. SERVICE EQUIPMENT SHALL BE MARKED WITH THE MAXIMUM AVAILABLE FAULT CURRENT AMPERES ("FCA") PER NEC 110.24 AND THE DATE OF THE MARKING. SEE RISER DIAGRAM SHEET E-4 FOR FAULT CURRENT CALCULATED VALUES. 8. CONTRACTOR TO COMPLETE ALL WORK INCIDENTAL TO MECHANICAL TRADES FOR A COMPLETE INSTALLATION, INCLUDING CONTROL WIRING, MOTOR STARTERS, DISCONNECT SWITCHES AND EQUIPMENT GROUNDS. 9. DEFERRED SUBMITTALS FOR LOW VOLTAGE SYSTEMS SHALL BE SUBMITTED TO THIS ENGINEER AND TO THE BUILDING OFFICIAL PRIOR TO INSTALLATION. CONTRACTOR TO MAKE NECESSARY PROVISIONS FOR THE INSTALLATION OF ANY AND ALL SYSTEMS FOR THIS PROJECT, INCLUDING RACEWAYS, CABINETS, PULL BOXES AND OUTLETS. SEE SHOP DRAWINGS FOR EACH SYSTEM FOR ADDITIONAL DETAILS AND INSTRUCTIONS. 10. CONTRACTOR SHALL FURNISH AND INSTALL ALL FIXTURES COMPLETE AS LISTED IN THE "LIGHTING FIXTURE SCHEDULE". II. PANELBOARD AND DISCONNECT SWITCHES SHALL HAVE COPPER OR COPPER (NOMINAL 15% BY VOLUME) CLAD ALUMINUM BUS. 12. THE PANEL SHALL BE LABELED WITH A PERMANENT ENGRAVED LABEL. IDENTIFICATION ON THE LABEL MUST CONFORM TO THESE ELECTRICAL DRAWINGS. 13. DATED AND TYPEWRITTEN CIRCUIT IDENTIFICATION SHALL BE INSTALLED IN ALL PANELBOARDS, EACH BREAKER HAVING A DISTINCTIVE DESCRIPTION COMPLYING WITH NEC 408.4(A). ALL PANELBOARDS SHALL BE MARKED WITH THEIR SOURCE OF SUPPLY PER NEC 408.4(B). 14. THE FUSIBLE SERVICE DISCONNECT SHALL BE A QUICK -MAKE, QUICK -BREAK, LOAD -BREAK DEVICE. 15. CONDUIT FOR UNDERGROUND SHALL BE SCHEDULE 40 PVC OR MC CABLE LISTED FOR UNDERGROUND USE UNLESS OTHERWISE SHOWN AND/OR REQUIRED BY CODE. UNDERGROUND CONDUITS SHALL BE INSTALLED AT A DEPTH IN ACCORDANCE WITH TABLE 300.5. 16. CONDUIT FOR ABOVE GRADE SHALL BE "GRC", "SCH 80 PVC" OR 'EMT'. "LFNC" SHALL BE USED FOR CONNECTIONS TO AIR HANDLING UNITS, CONDENSING UNITS, WATER HEATERS AND OTHER EQUIPMENT. MC CABLE MAY BE USED FROM "J-BOXES" IN CEILING, OR, WHEN STUDS OR OTHER POINTS OF SECURE SUPPORT NOT GREATER THAN 6 FEET APART ARE AVAILABLE, FROM BRANCH -CIRCUIT PANELS TO SWITCHES, RECEPTACLES AND BETWEEN DEVICES. SPARE CONDUITS SHALL HAVE A PULL WIRE INSTALLED. 17. CONDUCTORS SHALL BE THHN/THWN EXCEPT WHERE SPECIFIED OTHERWISE ON THE DRAWINGS. CONDUCTORS NO. 8 AWG AND LARGER SHALL BE JOINED BY AN APPROVED PRESSURE CONNECTOR. CONNECTION TO GROUND CONDUCTORS NO. 1/0 AWG AND LARGER SHALL BE CAST BY FUSIBLE METAL PROCESS. ALL CONDUCTORS MUST BE INSTALLED IN CONDUIT, MC CABLE, OR LFNC. CONDUCTORS IN PANELS SHALL HAVE THEIR FACTORY LABELS VISIBLE TO A PERSON IN THE WORKING SPACE. 18. CONDUCTORS OF MULTIWIRE CIRCUITS SHALL BE GROUPED IN AT LEAST ONE LOCATION WITHIN THE PANELBOARD OR OTHER POINT OF ORIGIN BY WIRE TIES OR SIMILAR MEANS PER 200.40. MULTIWIRE CIRCUIT DISCONNECTS SHALL BE PROVIDED WITH A MEANS TO SIMULTANEOUSLY DISCONNECT ALL UNGROUNDED CONDUCTORS AT THE POINT WHERE THE BRANCH CIRCUIT ORIGINATES. 19. NO CONDUCTORS SMALLER THAN 12 AWG SHALL BE USED FOR POWER AND LIGHTING. ALL CONDUCTORS SHALL BE COPPER, UNLESS NOTED OTHERWISE. 20. COLOR CODE FOR 120/240V Io SYSTEM SHALL BE: BLACK, RED, WHITE, & GREEN. 21. CONTRACTOR SHALL VERIFY WITH ARCHITECT FOR DETAILED DIMENSIONS AND LOCATIONS OF OUTLETS AND EQUIPMENT AND FOR ANY REVISIONS IN LAYOUT. 22. MOUNT WALL SWITCHES 44" ABOVE FINISHED FLOOR, UNLESS OTHERWISE NOTED ON DRAWING. GANG SWITCHES WHEREVER POSSIBLE. 23. LIGHTING CONTROLS SHALL CONFORM TO THE REQUIREMENTS LISTED ON THE E-3 SERIES SHEETS IN THESE PLANS. CONTROLS SHALL BE WHITE OR IVORY IN COLOR. SWITCHES CONTROLLING LINE -TO -NEUTRAL LIGHTING LOADS SHALL COMPLY WITH NEC 404.2(C). 24. RECEPTACLES SHALL BE LOCATED 15" ABOVE FINISHED FLOOR TO CENTER LINE OF DEVICE, UNLESS OTHERWISE NOTED, ABOVE -COUNTER RECEPTACLES SHALL BE MOUNTED 6' ABOVE BACK SPLASH 'TO CENTERLINE OF DEVICE. 25. COVER PLATES SHALL BE WHITE PLASTIC, UNLESS OTHERWISE NOTED. RECEPTACLES WITH PLASTIC COVER PLATES SHALL BE MOUNTED SUCH THAT THE GROUND PIN IS MOUNTED DOWN, UNLESS OTHERWISE NOTED. RECEPTACLES WITH METAL COVER PLATES SHALL BE MOUNTED SUCH THAT THE GROUND PIN IS MOUNTED UP, UNLESS OTHERWISE NOTED. 26. ALL NEW 125V RECEPTACLES SHALL BE NEMA 5-20R, AND COLOR SHALL BE WHITE UNLESS NOTED OTHERWISE. RECEPTACLES SHALL BE EQUIPPED WITH BREAK OUT TAB FOR SPLIT OPERATION, AND CONTROLLED RECEPTACLES SHALL BEAR THE MARKING REQUIRED BY 406.3(E). A DUPLEX RECEPTACLE SHALL HAVE ITS BOTTOM OR RIGHT RECEPTACLE CONTROLLED. CONTROLLED RECEPTACLES SHALL BE POWERED BY STRIPED COLOR CODED WIRE. RECEPTACLES SHALL BE UL LISTED TAMPER RESISTANT TYPE WHERE REQUIRED BY THE NEC. OUTDOOR RECEPTACLES SHALL COMPLY WITH 406.9(A) OR (B) AS APPROPRIATE TO CONDITIONS. GFCI TYPE RECEPTACLES SHALL BE INSTALLED IN A READILY ACCESSIBLE LOCATION OR EQUIPPED WITH A BLANK FACE TEST/RESET PANEL OR BE PROTECTED BY A GFCI BREAKER. 27. CONTRACTOR SHALL CONNECT AIR CONDITIONERS, PUMPS, FANS AND OTHER EQUIPMENT. 28. AIR CONDITIONER BREAKER SHALL BE MARKED "LISTED HACR TYPE" AS REQUIRED BY NEC 110.3(B). IF BREAKER IS NOT MARKED, THE OUTSIDE DISCONNECT SHALL BE CHANGED TO A FUSED DISCONNECT WITH RATING AS NOTED ON A/C EQUIPMENT. 29. CONTRACTOR SHALL MAKE TESTS AND ADJUSTMENTS AS REQUIRED, UPON COMPLETION OF THE WORK AND BEFORE FINAL ACCEPTANCE BY THE OWNER. THE CONTRACTOR SHALL TEST THE COMPLETE ELECTRICAL SYSTEM IN THE PRESENCE OF THE ENGINEER/ARCHITECT FOR CONTINUITY, FUNCTION, CONTROL, PERFORMANCE„ LOAD BALANCE, GROUNDS AND GROUND RESISTANCE, SHORT CIRCUITS, AND TO INSURE SATISFACTORY OPERATION AND CONFORMANCE TO CONTRACT REQUIREMENTS. 30. EQUIPMENT, LABOR AND MATERIAL REQUIRED FOR TESTING SHALL BE FURNISHED BY THE CONTRACTOR(S) AS PART OF THIS CONTRACT. 31. PRIOR TO COMPLETION OF THE WORK, THE CONTRACTOR SHALL MARK THE SERVICE EQUIPMENT WITH THE AVAILABLE FAULT CURRENT PER NEC 110.24, USING EITHER THE FAULT -CURRENT FROM THE UTILITY FAULT CURRENT LETTER, OR THE SHORT CIRCUIT CURRENT CALCULATION FROM THESE PLANS. IF PROVIDED WITH THE FAULT CURRENT LETTER, THIS ENGINEER WILL UPDATE THE CALCULATION TO OBTAIN THE FAULT CURRENT AT THE SERVICE ENTRANCE. 32. AFTER COMPLETION OF THE WORK, THE CONTRACTOR SHALL SECURE CERTIFICATES OF FINAL INSPECTION AND APPROVAL FROM AUTHORITIES HAVING JURISDICTION (AHJ). 33. PER FBC C405.6.4.1, WITHIN 30 DAYS OF ELECTRICAL SYSTEM ACCEPTANCE BY THE NOTE: TO THE BEST OF THE ENGINEER'S KNOWLEDGE, THESE PLANS AND SPECIFICATIONS COMPLY WITH THE FLORIDA BUILDING CODE 6TH EDITION (2017) AND THE FLORIDA FIRE PREVENTION CODE 6TH EDITION (2017). AHJ, THE CONTRACTOR SHALL PROVIDE THE BUILDING OWNER WITH RECORD DRAWINGS OF THE ACTUAL INSTALLATION. THE RECORD DRAWINGS SHALL INCLUDE A SINGLE -LINE DIAGRAM OF THE: BUILDING ELECTRICAL DISTRIBUTION SYSTEM AND FLOOR PLANS INDICATING LOCATION AND AREA SERVED FOR ALL DISTRIBUTION. IF PROVIDED WITH COMPLETE FIELD MARKUPS ON THESE PLAN SHEETS, THE ENGINEER SHALL MODIFY THESE PLAN SHEETS INTO SAID RECORD DRAWINGS AND PROVIDE A COPY TO THE OWNER AND TO THE CONTRACTOR AND RETURN THE ORIGINAL FIELD MARKUP TO THE CONTRACTOR. 34. PER FBC C405.6.4.2, WITHIN 30 DAYS OF ELECTRICAL SYSTEM ACCEPTANCE BY THE AHJ, THE CONTRACTOR SHALL PROVIDE THE BUILDING OWNER AN OPERATING AND MAINTENANCE MANUAL FOR ALL 'ELECTRICAL SYSTEMS INSTALLED IN ACCORDANCE WITH THESE PLANS THAT REQUIRE MAINTENANCE. AT A MINIMUM, THE MANUAL SHALL INCLUDE: A. EQUIPMENT RATING AND SELECTED OPTIONS FOR EACH PIECE OF EQUIPMENT REQUIRING MAINTENANCE. B. OPERATION MANUALS AND MAINTENANCE MANUALS FOR EACH PIECE OF EQUIPMENT REQUIRING MAINTENANCE, REQUIRED ROUTINE MAINTENANCE ACTIONS SHALL BE CLEARLY IDENTIFIED. C. NAME AND ADDRESS OF AT LEAST ONE QUALIFIED SERVICE AGENCY. 41. WORKMANSHIP, MATERIALS AND APPARATUS UNDER THIS CONTRACT SHALL BE GUARANTEED FOR A PERIOD OF ONE YEAR FROM THE DATE OF FINAL ACCEPTANCE BY THE OWNER. 42. GREATER THAN 80% NONLINEAR LOADS: SHARED NEUTRALS AND GROUNDS ARE NOT PERMITTED FOR SINGLE PHASE CIRCUITS. 43. WORKING CLEARANCES FOR ELECTRICAL EQUIPMENT SHALL BE IN COMPLIANCE WITH NEC 110, AND WITH NEC 210.8 FOR GFCI DEVICES. 44. THE EXCLUSIVELY -DEDICATED SPACE EXTENDING FROM FLOOR TO STRUCTURAL CEILING WITH A WIDTH AND DEPTH OF THE PANEL BOARD OR SWITCHBOARD MUST BE CLEAR OF ALL PIPING, DUCTS OR EQUIPMENT FOREIGN TO THE ELECTRICAL EQUIPMENT OR ARCHITECTURAL APPURTENANCES IN ACCORDANCE WITH NEC 408. 45. WHEN ELECTRICAL BOXES ARE LOCATED IN VERTICAL FIRE -RESISTIVE ASSEMBLIES, (CLASSIFIED AS FIRE/SMOKE AND SMOKE PARTITIONS), THEY SHALL BE INSTALLED WITHOUT AFFECTING THE FIRE CLASSIFICATION. ALL OF THE FOLLOWING CONDITIONS AND FBC 714 SHALL_ BE MET: A. ALL ELECTRICAL BOXES SHALL BE METALLIC. B. BOX OPENING SHALL OCCUR ONLY ON ONE SIDE OF FRAMING SPACE. C. BOX OPENING SHALL NOT EXCEED 16 SQUARE INCHES. D. THE OPENING IN THE GYPSUM BOARD FACING SHALL BE CUT NOT TO EXCEED 1/8 INCH BETWEEN THE EDGES OF THE OUTLET BOX AND THE EDGES OF THE OPENING. E. ALL CLEARANCES BETWEEN OUTLET BOX AND GYPSUM BOARD SHALL BE COMPLETELY FILLED WITH JOINT COMPOUND (OR OTHER APPROVED MATERIAL). F. PROVIDE A WALL AROUND OUTLETS LARGER THAN 16 SQUARE INCHES. THE INTEGRITY OF THE WALL RATING SHALL BE MAINTAINED. G. THE TOTAL AGGREGATE SURFACE AREA OF THE BOXES SHALL NOT EXCEED 100 SQUARE INCHES PER 100 SQUARE FEET OF WALL AREA. H. OUTLET BOXES LOCATED ON OPPOSITE SIDES OF FIRE -RESISTIVE ASSEMBLIES SHALL BE SEPARATED BY A MINIMUM HORIZONTAL DISTANCE OF 24 INCHES. I. OUTLET BOXES SHALL BE SECURELY FASTENED TO WALL FRAMING MEMBERS. ELECTRICAL ABBREVIATIONS AFF: ABOVE FINISHED FLOOR L: LIGHTING LOAD AFG: ABOVE FINISHED GRADE M: MOTOR LOAD BFC: BELOW FINISHED CEILING MBJ: MAIN BONDING JUMPER E.C.: ELECTRICAL CONTRACTOR MH: MOUNTING HEIGHT EGC: EQUIPMENT GROUNDING CONDUCTOR NL: NIGHT LIGHT F: FAN LOAD P: PANEL FICA: FAULT CURRENT AMPERES R: RECEPTACLE LOAD GC: GROUNDED CONDUCTOR SA: SMOKE/CO ALARM LOAD GEC: GROUNDING ELECTRODE CONDUCTOR SN: SOLID NEUTRAL GFI: GROUND FAULT CIRCUIT -INTERRUPTER UON: UNLESS OTHERWISE NOTED IG: ISOLATED GROUND VP: VAPOR PROOF WP: WEATHER PROOF ELECTRICAL DRAWING INDEX SHEET DESCRIPTION E-I ELECTRICAL LEGEND, SPECIFICATIONS a ABBREVIATIONS E-2 ELECTRICAL POWER SYSTEMS FLOOR PLAN E-3 ELECTRICAL LIGHTING SYSTEMS FLOOR PLAN E-4 PANEL SCHEDULES, RISER, DETAILS AND CALCULATIONS YES YES YES YES V) Z O Of W a 0 a Fort Pierce Engineering, Inc. Dependable Mechanical, Electrical & Plumbing Design Reg. No. 28173 315 South 7th Street Fort Pierce, FL. 34950 Phone: 772 672-4636 Fax: 772 672-4637 a 0 Lv � Qo UU z <L o aw w U� W U CO 4 0) x oo-qj- Co IL Hf) O v� O � U W W fro W � z = 0_ (� 0 o Q fs+ a 0 `L z O Lv U U w a w o a O W o o w Q[ X N O A -I a- N U ENGINEER SEAL `O�IIIII11111 • lo. 6158V 4 // STATE OF ; c� 100. Timothy C. Trewyn, PE P.E. No. 61580 THESE DO(]WKS, ALWG VHH PE CMUTS MM W DESIGM PRESEMED HUM ARE IMEFDEED WLY FRt TIE SPECMC PURPOSE w a-W W FTRT POU ETAS, DIG FM VIM TWY WERE PREPARED, Wa RI DPPBU RBMU W TTESE DOCREMS VIDWf VRITTO AUTHfltIIA M AND ADAPTATDN BY FTRT PMM DOEME, DIG SHALL DE VITHWT LInim TD THE SAFE. CR'YR Grr02m, FORT PDRCE ETFQFEMM, INC. ALL WffS WMVED. SHEET TITLE ELECTRICAL SYMBOL LEGEND, SPECIFICATIONS & ABBREVIATIONS ISSUE DATE: 04-15-2020 DRAWN: TEC APPROVED: TCT DRAWING NUMBER Er'l SHEET I OF 4 20001-05 PI-7 4' X 8' X 3/4- PLYWOOD BACKBOARD: — (2) 2• PVC W/ PULL WIRES UNDERGROUND TELEPHONE SERVICE FROM UTILITY COMPANY POLE. COORDINATE / TERMINATIONS WITH U11LITY CO. COORDINATE TTB LOCATION / WITH OWNER PRIOR TO ROUGH -IN. UNDERGROUND ELECTRICAL SERVICE FROM UTILITY COMPANY POLE MOUNTED TRANSFORMERS AND HANDHOLE. COORDINATE TERMINATIONS WITH UTILITY CO. COORDINATE SERVICE LOCATION WITH OWNER AND T7B. UTILITY COMPANY METER SERVICE DISCONNECT ' WP HVAC SVC CONV PI-7 PI-22:24 (2)#12 & (1)#12G. IN 3/4- C. 30AR 3R NF ELECTRICAL KEY NOTES: 0 EXHAUST FAN TO BE CONNECTED TO AND CONTROLLED VIA THE ROOM LIGHT SWITCH. E.C. TO PROVIDE TOGGLE DISCONNECT ABOVE CEILING FOR THE EXHAUST FAN. 2 GFCI PROTECTED RECEPTACLES SHALL BE READILY ACCESSIBLE OR SHALL BE PROTECTED BY A GFCI CIRCUIT BREAKER IN THE PANEL. 3❑ PROVIDE CONDUIT AND BOXES FOR OA MOTORIZED DAMPER LOW VOLTAGE CIRCUIT. FLAN POUJEiZ SYSTEI"fS PLAN ELECTRICAL DEMOLITION KEY NOTES: QI REMOVE ALL EXISTING ROUGHED IN ELECTRICAL ITEMS THAT ARE WITHIN THE DASHED LINE ENCLOSED AREA, INCLUDING LIGHTING, POWER AND SYSTEM DEVICES, EXCEPT WHERE NOTED WITH THE SYMBOL <E>, <ER>, <ERC>, OR <ERP>. ANY WIRING AND CONDUIT CAN BE REUSED AT THE CONTRACTOR'S DISCRETION. CONTRACTOR SHALL ALSO REMOVE ANY OTHER ELECTRICAL EQUIPMENT THAT MAY NOT BE SHOWN, BUT IS PART OF THE DEMOLITION SHOWN BY ATTACHED NOTES. CONTRACTOR SHALL COORDINATE WITH THE ARCHITECTURAL DEMOLITION PLANS AND ALSO FIELD VERIFY, PRIOR TO ANY REMOVAL. ❑2 ALL REMOVED EQUIPMENT SHALL BE DISPOSED OF BY THE CONTRACTOR UNLESS DIRECTED TO DO OTHERWISE BY THE OWNER. ALL DISPOSAL OF MATERIAL TO CONFORM TO EPA REGULATIONS. 03 ALL EXISTING FLOOR BOXES (IF ANY) AND CONDUIT FOR POWER/TELEPHONE/DATA THAT ARE BEING REMOVED, SHALL BE ABANDONED IN PLACE. WIRE SHALL BE REMOVED AND PULL STRINGS INSTALLED WITH TAG, UNLESS NOTED "EXISTING TO REMAIN". ® ELECTRICAL CONTRACTOR SHALL BE HELD RESPONSIBLE FOR THE REPLACEMENT OF ANY DAMAGED EQUIPMENT AND OR MATERIALS NOT BEING REMOVED IN THIS DEMOLITION. EXISTING / DEMO PLAN SCALE 1/4" = 1'-0" GENERAL DEMOLITION NOTES: COORDINATE SEQUENCING WITH OWNER AND OTHER CONTRACTORS. IT WILL BE THE CONTRACTOR'S RESPONSIBILITY TO PROTECT AND MAINTAIN THE INTEGRITY OF THE REMAINING DEVICES AND EQUIPMENT. ELECTRICAL CONTRACTOR SHALL VISIT AND EXAMINE THE SITE PRIOR TO CONSTRUCTION TO ASCERTAIN THE EXISTING CONDITIONS AND LIMITS OF DEMOLITION AND CONSTRUCTION. DISCONNECT, REMOVE OR RELOCATE ALL EXISTING ELECTRICAL MATERIAL AND EQUIPMENT THAT INTERFERES WITH NEW INSTALLATION. THIS INCLUDES BUT IS NOT LIMITED TO PANELS, LIGHTING FIXTURES, WIRING DEVICES, SIGNAL EQUIPMENT, EXHAUST FANS, BASEBOARD HEATERS, UNIT HEATERS, ETC. SEE MECHANICAL DRAWINGS FOR HEATERS, EXHAUST FANS, ETC. WHICH MUST BE DISCONNECTED BY THIS CONTRACTOR FOR REMOVAL OR ABANDONMENT BY MECHANICAL CONTRACTOR. ALL REMOVED EQUIPMENT SHALL BE. ''DISPOSED OF BY THIS CONTRACTOR UNLESS DIRECTED TO DO OTHERWISE BY THE OWNER. ALL FLUORESCENT LAMPS AND PCB BALLASTS SHALL BE DISPOSED OF IN ACCORDANCE WITH STATE AND FEDERAL REGULATIONS. WHERE WORK BY GENERAL CONTRACTOR (WALL REMOVAL, NEW OR RELOCATED WALL OPENINGS, ETC.) RESULTS IN THE REMOVAL, RELOCATION OR REFEEDING OF ELECTRICAL DEVICES OR LIGHTING FIXTURES, THE ELECTRICAL. CONTRACTOR SHALL DISCONNECT AND RECONNECT ALL ACTIVE DEVICES REMAINING. ANY SUCH CONNECTIONS SHALL BE CONCEALED UNLESS LOCATED IN UNFINISHED AREAS. ANY EXISTING PANEL HOME RUNS, WHICH WILL REMAIN WITHIN THE AREA, MAY BE RETAINED AND USED AS PART OF THE NEW CIRCUITRY OR REMAIN AS SPARE EMPTY CONDUIT. SUCH EMPTY CONDUIT(S) SHALL BE MARKED AS TO PANEL AND END LOCATIONS. EXISTING OUTLET BOXES AND CONDUIT WHICH ARE LOCATED PROPERLY FOR NEW WORK MAY BE REUSED FOR NEW DEVICES AND WIRE. WHERE CONDUIT TO BE REMOVED STUBS THROUGH FLOORS, WALLS AND CEILINGS, SUCH CONDUIT SHALL BE REMOVED TO THE POINT WHERE THE FINISHED SURFACES CAN BE PATCHED ADEQUATELY SO THAT NO EVIDENCE OF THE FORMER INSTALLATION REMAINS. ALL CONDUIT AND WIRE REMOVED SHALL BE REMOVED TO THE SOURCE OF SUPPLY. ALL CUTTING, CORING AND PATCHING REQUIRED FOR ELECTRICAL WORK SHALL BE BY THE ELECTRICAL CONTRACTOR. INSTALL A BLANK COVER PLATE WHERE REQUIRED. WHILE PERFORMING DEMOLITION WORK, ALL CIRCUITING SERVING AREAS BEYOND THE DEMOLITION AREA SHALL BE MAINTAINED AND REPAIRED AS REQUIRED, AT THE CONTRACTORS EXPENSE, SO THAT ALL SUCH SYSTEMS REMAIN IN OPERATION. CONTINUITY SHALL REMAIN AT ALL TIMES WHILE DISCONNECTING EQUIPMENT AND DEVICES FROM CIRCUITS THAT ARE TO REMAIN. CONTINUOUS SERVICE ON FEEDERS, CIRCUITS, PARTIAL CIRCUITS, AND OUTLETS EFFECTED BY DEMOLITION WORK SHALL BE MAINTAINED, EXCEPT WHEN WRITTEN PERMISSION IS PROVIDED BY THE OWNER. ALL WORK REQUIRING SHUT -DOWN OF EXISTING SYSTEMS SHALL BE PERFORMED DURING OFF HOURS WITH THE: ARCHITECT'S APPROVAL AT NO ADDITIONAL COST TO THE OWNER. THE ELECTRICAL CONTRACTOR SHALL PLAN AND PERFORM WORK IN SUCH A WAY AS TO MINIMIZE THE OUTAGES AND SUBMIT TO THE OWNER A SCHEDULE OF THE REQUIRED OUTAGES. DEMOLITION PLANS SHALL ADHERE TO A PHASING SCHEDULE AS DETERMINED BY THE CONSTRUCTION MANAGEMENT. PRIOR TO THE INTERRUPTION OF EXISTING FEEDERS OR BRANCH CIRCUITS, THE CONTRACTOR SHALL VERIFY, BY MEANS OF TRACING ALL EXISTING CIRCUITS, THAT ALL BRANCH CIRCUITS BEING FED FROM DEMOLITIONED/RE:LOCATED FEEDERS AND BRANCH CIRCUITS ARE NOT SERVING AREAS WHICH ARE TO REMAIN. WHERE NECESSARY RECONNECT CIRCUITS TO CORRESPONDING NEW OR EXISTING TO REMAIN BRANCH CIRCUITS. THESE SAME CONDITIONS APPLY TO FIRE ALARM, COMMUNICATIONS, DATA, AND SPECIAL SYSTEMS. ANY CONCEALED CONDUITS MADE OBSOLETE DUE TO THE DEMOLITION SHALL BE CUT BACK TO FLOOR, WALL, OR CEILING WITH THE REMAINING ENDS PLUGGED TO ALLOW REFINISHING OF THE SURFACES. EXISTING CONDUITS THAT ARE IN WALLS OR FLOORS WHICH ARE TO REMAIN AND THE CONDUIT DOES NOT, AND WILL NOT INTERFERE WITH THE WORK OF ANY TRADE, MAY REMAIN. ALTHOUGH, ANY AND ALL ABANDONED WIRE SHALL BE REMOVED IN ITS ENTIRETY. REFER TO HVAC AND PLUMBING DRAWINGS FOR DEMOLITION/RELOCATION OF MECHANICAL OR PLUMBING EQUIPMENT. THE CONTRACTOR SHALL DISCONNECT AND REMOVE ALL CONDUIT, WIRE, AND ASSOCIATED DEVICES RELATING TO EQUIPMENT BEING REMOVED. FIRE ALARM SYSTEM NOTE: THE OCCUPANCY CLASSIFICATION IS BUSINESS GROUP B WITH AN OCCUPANT LOAD OF ALL FLOORS OF LESS THAN 500 PERSONS AND AN OCCUPANT LOAD OF LESS THAN 100 PERSONS ON THE FLOOR ABOVE THE LOWEST LEVEL OF EXIT DISCHARGE. PER FBC 907.2.2, A MANUAL FIRE ALARM SYSTEM IS NOT REQUIRED. Z 0 L Of W a 0 I I Fort Pierce Engineering, Inc. Dependable Mechanical, Electrical & Plumbing Design Reg. No. 28173 315 South 7th Street Fort Pierce, FL. 34950 Phone: 772 672-4636 Fax: 772 672-4637 a .o w� z Qo v w LL z aw O Qw WJ w w U cD Q rn x 00� U � CO LL rn 0 I--1 W C U LWLJ W 1 _0 W IU-� z Ct) E w o Q � 0 ow z p w F- Cn o� f U w w w 00 0� of o0 ofN O {� E1 N L_ ENGINEER SEAL 0 \CENS�•% i o. 6158 • 2 gam'• e t' r°7 8% • STATE OF •; 441 ••�•OR I O•••G�`�• Timothy C. Trewyn, PE P.E. No. 61580 THESE DWJ MS, &M KITH THE CENCEPTS AND DR DEMM PRESENTED HEREIN ARE DnEm RLY FOR TIE SPECIFIC PURPOSE AND CLIENT OF FCRT PIERCE EN6QEERIII5, INC. FOR WHICH THEY WERE PREPARM REUSE ER I PROPER RELWICE IN THESE DOUKHTS VITHRIT WRITTEN AUTH WMTIIN AND ADA.PTATDN BY FCRT PIERCE ENGIEERX INC. SHAU DE VITHw LTADD.ITY M THE SNEE COPYRIGHTOM, FORT PIERCE ENMNEERNG, R& ALL RIGHTS RESWM SHEET TITLE ELECTRICAL POWER SYSTEMS FLOOR PLAN ISSUE DATE: 04-15-2020 DRAWN: TEC APPROVED: TCTCHK? DRAWING NUMBER E-2 SHEET 2 OF 4 20001-05 FILE CORY fi I C E W W C�< FL � N LIGHTING FIXTURE SCHEDULE MARK MANUFACTURER -PART NUMBER LAMPS' VOLTS MOUNTING DESCRIPTION --:: REMARKS NO TYPE WATTS A H.E. WILLIAMS - LP 24 L60 835 LP24SMK - LED 48 120 SURFACE 2X4 LED FLAT PANEL, PMMA LENS,SURFACE MOUNTED SURFACE MOUNT KIT WHITE FINISH. 4800 LUMENS 5 YEAR LIMITED WARRANTY. B H.E. WILLIAMS - WMA 2 L30/835 AF DRV UNI WH - LED 12 120 WALL 24" LONG LED,FROSTED ACRYLIC LENS, WHITE FINISH, 3000 LUMENS WALL MOUNT ABOVE MIRROR CENTER LINE. COORDINATE WITH ARCHITECTURAL PLANS. C LITON - W Lis 120V T30 - LED 20 120 SURFACE 10' DIA. SURFACE MOUNTED LED FIXTURE, WHITE FIN., OPAL LENS, WET LOCATION. 1500 LUMENS 5 YEAR LIMITED WARRANTY. D BEGHELLI - PEH-1 4 LED 1.4 120 CEILING/WALL 2 LAMP UL 97 V-0 PLASTIC EMERGENCY LIGHTING FIXTURE. MOUNT 8'-0' A.F.F. FOR WALL MOUNT. E BEGHELLI APE LG U W R SEA 2 6V LED 5W 4 LED 5 120 WALL COMBINATION 2 LAMP THERMOPLASTIC EMERGENCY LIGHTING/EXIT SIGN. WA2) REMOTE HEADS. MOUNT 8 -0 A.F.F. FOR WALL MOUNT. F H.E. WILLIAMS-6DR TL L20 835 DRV UNV 0 M OF CS N - LED 20 120 CEILING 6' DIA. RECESSED DOWNLIGHT, CLEAR SEMI SPECULAR WHITE TRIM, 2000 LUMENS 5 YEAR LIMITED WARRANTY. GENERAL LIGHTING FIXTURE SCHEDULE NOTES: I. VERIFY TYPE OF CEILING FOR EACH FIXTURE WITH ARCHITECTURAL REFLECTED CEILING PLANS AND PROVIDE FIXTURE TRIM AS REQUIRED. 2. VERIFY VOLTAGES PRIOR TO BID AND INSTALLATION OF FIXTURES. 3. PROPOSED ALTERNATE LIGHTING BIDS MUST INCLUDE THE FOLLOWING: A. ORIGINAL AND ALTERNATE BID PRICES AND WARRANTIES SHALL BE PRESENTED BY THE VENDORS AND GENERAL CONTRACTOR TO THE OWNER. B. VENDOR SHALL PROVIDE PHOTOMETRIC LAYOUT OF PROPOSED ALTERNATE LIGHTING FIXTURES. IESNA LM-79 AND LM-80 TEST DATA MUST BE AVAILABLE FOR THE FIXTURE. C. ABOVE PHOTOMETRIC INFORMATION MUST BE SUPPLIED TO THE ENGINEER (3) DAYS PRIOR TO BID. 4. ALL COMPACT FLUORESCENT DOWNLIGHTS SHALL USE ELECTRONIC BALLASTS, UNLESS OTHERWISE NOTED. 5. PROVIDE APPROVED FIRE RATED ENCLOSURES FOR ALL LIGHT FIXTURES LOCATED IN FIRE RATED CEILINGS. 6. FIXTURES IN AREAS WITHOUT CEILINGS OR IN MECHANICAL AND ELECTRICAL ROOMS SHALL BE MOUNTED WITH I 1/2"A 1/2' IQNDORF CHANNEL SUPPORT SUSPENDED THREADED RODS. FIXTURES SHALL BE MOUNTED 10'-O'A.F.F. UNLESS OTHERWISE NOTED. FROM ROOF STRUCTURE WITH 7. ALL ACRYLIC LENSED FIXTURES SHALL HAVE A MINIMUM LENS THICKNESS OF .125 INCHES. 8. ALL SHEET STEEL USED IN FIXTURES ABOVE SHALL HAVE A PHOSPHATE LAYER APPLIED PRIOR TO PAINTING. LIGHTING CONTROL LEGEND: WATTSTOPPER # LMRC-101 SINGLE ZONE SWITCHING ROOM CONTROLLERS 101 WATTSTOPPER # LMDC-100 CEILING MOUNT DUAL TECH. OCCUPANCY SENSOR ® WATTSTOPPER # LMSW-101 SINGLE BUTTON SWITCH Dsw WATTSTOPPER #DSW-100 LINE VOLTAGE WALL MOUNT DUAL TECH. OCCUPANCY SENSOR FL WATTSTOPPER # LMPL-101 PLUG LOAD CONTROLLER. SWITCH LOWER HALF OF EACH INDICATED RECEPTACLE �► uc,N TING SYSTEMS PLAN EXISTING / DEMO FLAN SCALE 114" = 1'-0" ugnting Load _J 120/277 LMDC-100 Occupancy Sensor LMRC-101 Single Relay On/Off Room Controller nano To RJ45 (Typical) LMRJ Series Pre —Terminated Cables or CAT5e. Free Topology & Splitter Acceptable DLM Wall Switch LMSW— DEVICES ARE PRESET FOR PLUG n' GO- OPERATION, ADJUSTMENT IS OPTIONAL. Sequence of Operation: In this configuration The 1MRC-101 derauns to manual—on/automatic off. Maximum of 4 room controllers, controlling up to 8 loads and up to 24 communicating devices per DLM local network. For full operational details, adjustments and more features of the product, see the DLM System Installation Guide ut www.wattstopper.com PL LMPL-101 Digital Plug Load Room Controller "Break —off removal on hot side required for split —circuit wiring. One Zone Room with Automaticv Receptacle Controls I Provide LAW Series wall sensor instead of ceiling sensor aad switch where indicated on drawings. LIGHTING SYSTEMS NOTES I. LIGHTING CONTROLS SHALL COMPLY WITH FBC C405„2. A. PUBLIC CORRIDORS, REST ROOMS, PRIMARY BUILDING ENTRANCE AREAS, AND AREAS WHERE MANUAL -ON OCCUPANCY CONTROLLED OPERATION WOULD ENDANGER THE SAFETY OR SECURITY OF THE ROOM OR BUILDING OCCUPANTS ARE CONTROLLED BY FULL AUTOMATIC -ON OCCUPANCY SENSOR. B. BREAK ROOMS, OFFICES, AND OTHER SPACES 300SF OR LESS THAT ARE ENCLOSED BY FLOOR -TO -CEILING HEIGHT PARTITIONS ARE CONTROLLED BY MANUAL -ON OR CONTROLLED TO AUTOMATICALLY TURN THE LIGHTING ON TO NOT MORE THAN 50 PERCENT POWER. C. EXTERIOR LIGHTING CONTROL SHALL BE VIA ASTRONOMIC TIME SWITCH COMPLYING WITH C405.2.5. 2. EXIT SIGNS SHALL COMPLY WITH FBC C405.3, I.E. NOT EXCEED 5 WATTS PER SIDE. 3. SEE INTERIOR LIGHTING POWER CALCULATIONS PER FBC C405.4 ON THIS SHEET. 4. EXTERIOR LIGHTING POWER SHALL COMPLY WITH FBC C405.5. 5. PER FBC C402.5.8 RECESSED FIXTURES SHALL BE SEALED BETWEEN THE FIXTURE AND INSULATED SURFACE WITH A GASKET OR CAULK, IC RATED, AND LABELED WITH AN AIR LEAKAGE RATE OF 2CFM OR LESS PER ASTM E 283. ELECif RICAL KEY NOTES: i❑ EXIT SIGNS AND EMERGENCY BATTERY UNITS TO BE CONNECTED TO THE LIGHTING BRANCH CIRCUIT IN THE AREA AHEAD OF THE LIGHTING CONTROLS. ® REMOTE TWIN HEAD, LOW VOLTAGE, EMERGENCY FIXTURES POWERED VIA EXIT SIGN. ® WALL MOUNTED TIMER SWITCH, WHITE FINISH, ASTRONOMICAL FUNCTION, LED DISPLAY. LEVITON # VPT24-IPZ OR EQUAL. ® ASTRONOMIC TIME SWITCH WITH 10 HOUR POWER BACKUP FOR FRONT SIGN. CONSULT WITH OWNER ON LOCATION OF THIS SWITCH„ LEVITON # VPT24-IPZ OR EQUAL. a_ a `L U 0 U) z 0 L W w H Q 0 Fort Pierce Engineering, Inc. Dependable Mechanical, Electrical & Plumbing Design Reg. No. 28173 315 South 7th Street Fort Pierce, FL. 34950 Phone: 772 672-4636 Fax: 772 672-4637 a .o w� Qo w� z aw U U J I Ld fi7 w FL w U 0) O O J CO LL I'n U 4 O v� W 0 w w W �a 0 w U z Q 4.a~ o 0 z O U w I— o � U w LL j w O0 a. O O 0 fr N O CL A-1 a_ N LL. ENGINEER SEAL C ••eeeeeee I �.\� ••��CEIVS••,FGL�i o.611580;o, � O ;• STATE OF •, tc�` s•••�.0 R 1 O P•G� ``� s /111111 THM DDGBENTS, &M WITH THE CRICEPTS am OR DESI W PRESENTED HEREIN ARE INTENDED IDLY FOR THE SPECIFIC PUNK AND CLIENT IF FORT PERCE OGQEERING, DIG FOR VW TIEY WERE PREPARED. REUSE OR DFFDU RELMICE ON TFESE DDCIREMS VITTnor VRITrEN AIMERIZATDR AND ADAPTATIIDI BY FORT PIERCE DOURING, INC. SHALL BE VCTIEUT LIARM TD THE SATE. CID'YRaITOM, FMT PMU ENGDEE N, DIC. ALL RDin RESERVED. SHEET TITLE ELECTRICAL LIGHTING SYSTEMS FLOOR PLAN ISSUE DATE: 04-15-2020 DRAWN: TEC APPROVED: TCT DRAWING NUMBER E-3 SHEET 3 OF 4 20001-05 STUB ABOVE CEILING -\ ACOUSTICAL TILE CEILING 3/4' CONDUI ACCESSIBLE STUB ABOVE CE" ACOUSTICAL TILE CEILING 3/4' CON OUT NATIVE BACKFILL UNDER GRASSY AREAS WITH NO VEHICULAR TRAFFIC. FDOT SPEC SUBBASE MATERIAL BACKFILL UNDER VEHICULAR PAVEMENT. WARNING \\'` TAPE CONDUIT % . ,.\ NATIVE BACKFILL UNDER GRASSY AREAS WITH NO VEHICULAR TRAFFIC. FDOT SPEC SUBBASE MATERIAL BACKFILL UNDER VEHICULAR PAVEMENT. FIBERGLASS BODY ASS COVER. IDUIT TO BE WITH FOAM. ;ACE PG 8) BRASS'L' BOLT. 4'x41xl I/2' DEEP BOX WITH SINGLE GANG DATA/COMM. � `- ROCK BRANCH CIRCUIT PLASTER RING RECEPTACLE NOTE: CONTACT AHJ AT LEAST 48 HOURS CONDUITS (TYP.) IN ADVANCE TO ARRANGE FOR CONDUIT INSPECTION NOTE: CONTACT AHJ AT LEAST 48 HOURS PRIOR TO BACKFILL. SPOT FILLING TO PREVENT IN ADVANCE TO ARRANGE FOR CONDUIT INSPECTION lJOTESe FLOATING IS ACCEPTABLE. PRIOR TO BACKFILL. SPOT FILLING TO PREVENT FLOATING IS ACCEPTABLE. L FIBERGLASS PULL -BOX WITH SCREW DOWN COVER. SIZE AS REQUIRED. SHALL CONFORM FLOOR FLOOR TO ASTM C857 AND SHALL BE LIGHT DUTY, PEDESTRIAN; 3000 LBF UNLESS NOTED _ _ OTHERWISE AT PARTICULAR LOCATIONS ON THE PLANS. 2. SPLICES SHALL BE MADE WITH SPLIT -BOLT CONNECTORS OR SUBMERSIBLE WIRENUTS OR NOTE: SUBMERSIBLE MULTI -PORT CONNECTORS. SPLIT -BOLT CONNECTORS SHALL BE SEALED IN FOR GYPSUM CEILING TYPES, ROUTE CONDUIT WITH PULL -STRING BACK TO POINT SILICONE GEL THAT WILL BE CONTAINED IN A CLOSURE AROUND THE SPLIT BOLT TO OF BUILDING TELEPHONE/DATA SERVICE EQUIPMENT. PROVIDE A WATERPROOF CONNECTION. THIS CLOSURE SHALL BE UV RESISTANT, IMPACT RESISTANT AND ABRASION RESISTANT. A DATA/COMM. STUB -UP DETAIL B CONDUCTOR TRENCHING DETAIL C UTILITY SERVICE FEEDER TRENCHING DETAIL D PULL -BOX DETAIL SCALE _ (N.T.S.) SCALE _ (N.T.S.) SCALE _ (N.T.S.) SINGLE PHASE LINE -LINE SHORT-CIRCUIT CURRENT CALCULATION 50KVA=TRANSFORMER SIZE LINE TO LINE SHORT-CIRCUIT CURRENT CALCULATION ISM = 50000 VA X 50 KVA = 15207AMPS 240 V 1.37 % IZ (TRANSFORMER TO PANEL) 30 FEET OF 1 SET OF 2 GAUGE ALUMINUM WIRE WITHIN A NON-MAGNETIC WIREWAY. Wire 1 f= 2 X M. X 15207 A = 1 3,730 240 V M = 1 = 0.495 1 + 1.019 15207AMPS X 0.495 = 7531AMPS 40 FEET OF 1 SET OF 3 GAUGE COPPER WIRE WITHIN A NON-MAGNETIC WIREWAY. Wire 2 f= 2 X 40' X 7531ANIIPS = 1 4,811 240 M = 1 = 0.657 1 + 0.522 7531 AMPS X 0.657 = 4949 AID IPS LINE TO NEUTRAL SHORT-CIRCUIT CURRENT CALCULATION ISC = 1.5 X 15207AMPS = 22810AMPS 30 FEET OF 1 SET OF 2 GAUGE ALUMINUM WIRE WITHIN A NON-MAGNETIC WIREWAY. Wire 1 f= 2 X 30' X 22810A = 1 3,730 120V M = 1 = 0.246 1 + 3.058 22810AMPS X 0.246 = 5622AMPS 40 FEET OF 1 SET OF 3 GAUGE COPPER WIRE WITHIN A NON-MAGNETIC WIREWAY. Wire 2 f= 2 X Q. X 5622AMPS = 1 4,811 120V M = 1 = 0.562 1 + 0.779 5622AMPS X 0.562 = 3160AMIPS USE MINIMUM IOKA RATED EQUIPMENTAT PANEL 0.7791 PANEL: VOLTAGE: 120/240V 1PH 3W BUS/BREAKER AIC RATING: 22KA110KA RATING: 100A LOCATION: BREAK ROOM MOUNTING: FLUSH-NEMA 1 MAIN CONNECTION: M.LO. FED FROM: EXT. SERVICE DISCONNECT DEVICE FAMILY: SQUARE D QO OR EQUAL DESCRIPTION rc w "� W. n m P CONNECTED KVA, No. No. CONNECTED KVA P x x o m T w § A DESCRIPTION A D A B KE-BREAK RM.-REFRIGERATOR 12 20 1 0.50 1 2 0.54 1 20 12 R-BREAK RM WALLS GFCI R-BREAK RM.-COUNTER W 12 20 1 1.50 3 4 0.72 1 20 12 R-OFFICE R-BREAK RM.-COUNTER E 12 20 1 1.50 5 6 0.90 1 20 12 R-WORK AREA W R-EXTERIOR HVAC SVC CONV 12 20 1 0.36 7 8 0.90 1 20 12 R-WORK AREA E L-OFFICE, BRK. RM,WORK AREA,SIGN 12 20 1 0.55 9 10 1 1.80 2 20 12 WTR. HTR.-TWH-2 R-TELEPHONE BACKBOARD 12 20 1 0.72 11 12 1.80 12 3.6 KW L-EXTERIOR SIGN 12 20 1 1.20 13 14 1.80 1 20 12 WTR. HTR.-TWH-1 - 1.8KW SPARE 20 1 0.00 15 16 0.28 1 1 1 20 12 1 L/R/F REST ROOM SPARE 20 1 0.00 17 18 0.18 1 20 12 R-CORRIDOR SPACE 0.00 19 20 0.00 SPARE HVAC-AHU-1 10 30 2 3.06 21 22 1.80 2 20 12 HVAC-CU-1 - HACR CIR. BRK. HTR.-SKW, FAN-1/2HP 10 3.06 23 24 1.80 12 MCA-15.6 NO SPACE 0.00 25 26 0.00 NO SPACE NO SPACE 0.00 27 28 0.00 NO SPACE NO SPACE 0.00 29 30 0.00 1 _ NO SPACE NO SPACE 0.00 31 32 0.00 NO SPACE NO SPACE 0.00 33 34 0.00 NO SPACE NO SPACE 0.00 35 36 0.00 NO SPACE NO SPACE 0.00 37 38 0.00 NO SPACE NO SPACE 0.00 39 40 0.00 NO SPACE NO SPACE 0.00 41 42 0.00 NO SPACE 6.81 1 5.64 1 TOTAL 1 7.02 5.50 24.97 TOTAL CONNECTED KVA SERVES CONNECTED LOAD - KVA OF CALCULATED DEMAND -_KVA LIGHTING 1.77 1.25 2.21 RECEPTACLES (FIRST 10 KVA) 7.50 1.00 7.50 RECEPTACLES (OVER 10 KVA) 0.00 0.50 0.00 LARGEST MOTOR 1.12 1.25 1.40 OTHER MOTORS 0.08 10.40 1.00 1.00 0.08 10.40 EQUIPMENT/HEAT KITCHEN EQUIPMENT 0.50 1.00 0.50 TOTAL DEMAND KVA: 22.09 TOTAL AMPERAGE: 92.05 NOTES: 1. VERIFY ELECTRICAL REQUIREMENTS FOR ALL EQUIPMENT WITH MANUFACTURER'S MANUAL PRIOR TO BIDDING AND INSTALLATION. 2. PROVIDE DATED AND TYPEWRITTEN DIRECTORY ON INSIDE PANEL COVER. 3. NON -COINCIDENT HVAC LOAD. CALCULATION BASED ON HEATING MODE. I RISER DIAGRAM GENERAL NOTES: I. E.C. SHALL PROVIDE ARC FLASH HAZARD WARNING SIGNS PER NEC 110.16. 2. E.C. SHALL LEGIBLY FIELD MARK PANELBOARDS WITH THE DATE OF MARKING AND FAULT CURRENT AMPS (FCA) NOTED ON THE RISER DIAGRAM. 3. THE CONDUCTOR LENGTHS SHOWN ARE APPROXIMATE AND CONSERVATIVELY SHORT TO PROVIDE A MARGIN OF SAFETY IN THE CALCULATION OF FAULT CURRENTS. THE E.C. SHALL MAKE HIS OWN MEASUREMENTS AND ESTIMATE OF THE CONDUCTOR LENGTH REQUIRED. 4. PROVIDE SURGE PROTECTIVE DEVICE OVERCURRENT PROTECTION, CONDUCTOR AND CONDUIT PER SPD MFR'S INSTALLATION INSTRUCTIONS. 120/240V IPH 3W SERVICE FROM UTILITY POLE MOUNTED TRANSFORMER EST 25KVA 1.4%IZ ,.► 30 FT EST. #2 AL TPLX SERVICE CONDUCTORS AND PVC RACEWAY INSTALLED ON POLE BY UTILITY r-HANDHOLE PER UTILITY SPECS. GRADE N 40 FT EXTERIOR BLDG ELEVATION METER ENCLOSURE PER UTILITY SPECS. 0- 179 #6 CU MIN. INTERSYSTEM BONDING BAR PER NEC 250.94. (3) #3 CU #2 G.E.C. �� IN 1/2' IN 2 PVC. SCH 80 PVC EXOTHERMIC WELD #2 CU #2 CU WATER SERVICE 2' UG CU WATER PIPE DIRECT BURIAL COPPER GROUND CONNECTOR UL467 BURNDY GARI829 OR EQUAL 5/8'x8' CU CLAD STEEL GROUND ROD. ADD SECOND ROD MIN. 6 FT AWAY. E ELECTRICAL RISER DIAGRAM (3) #3 CU a IN 2" GRC. 2P IOOAR 3R IOOAFCL 7531 FCA rK -i I NOTE 4 PER MFR INTERIOR BREAK ROOM (3) #3 CU & (I) #8 CU E.G.C. IN 2" EMT GRADE D_ EL `U U o- 0 z 0 0I w a 0 0 z Fort Pierce Engineering, Inc. Dependable Mechanical, Electrical & Plumbing Design Reg. No. 28173 315 South 7th Street Fort Pierce, FL. 34950 Phone: 772 672-4636 Fax: 772 672-4637 Q W Q O U W L- Q L 0 aw W W iL E~ W P4 O O � U < CO 11- M 4 0 h--1 v� w C) U W W w Imo- o Q fi o LL 0 z Q 0 w I- C/1 OH Cr J () :D W w w o rr O O 0 0: N O ENGINEER SEAL C' r I T % i o. 61580 ' 2 STATE OF J �: ✓O 6 •° �•�°0 R O•:°G\?� 1111111111 Timothy C. Trewyn, PE P.E. No. 61580 THESE DDCHRENTS, &M VNH THE CMCEPTS AM IR BESIX PRESENTED HEREDI ARE DITE NIED OLY FOR THE SPECIFIC PIiZ M AND CLIENT OF FORT POM ENGIEEM, INC. FOR WHHICHH THEY WERE PREPAREHL REUSE DR DPRCPER REDANCE ON THESE DOU DHTS vmOUT VWTEN AUTHMMTDN AND ADAPTATDN BY FIRT POU DlGDEERDIG, DC SHALL DE WnHI1IT LIABILITY M THE SAES C"Off nW PD= DDDUJWN W_ ALL MHTS RESERVED. SHEET TITLE ELECTRICAL DETAILS, RISERS & SCHEDULES ISSUE DATE: 04-15-2020 DRAWN: TEC APPROVED: TCT DRAWING NUMBER E-4 SHEET 4 OF 4 SCALE _ (N.T.S.) 20001-05 FILE COPY