HomeMy WebLinkAboutAPPROVED, New Manual JCalculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Oct-14 11:29:23 Right-Suite® Universal 2021 21.0.08 RSU29066 Page 1 ...ents\Wrightsoft HVAC\TBD E Easy St PSL Prop.rup Calc = MJ8 Front Door faces: N 1642Job:Load Short Form 10/14/2021Date:House Chris BatemanBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Betsinger Residence, NisAir Air ConditioningFor: TBD E Easy St, Fort Pierce, FL 34982 Design Information InfiltrationClgHtg SimplifiedMethod9041Outside db (°F) AverageConstruction quality7570Inside db (°F) 0Fireplaces1529Design TD (°F) L-Daily range 5030Inside humidity (%) 572Moisture difference (gr/lb) HEATING EQUIPMENT COOLING EQUIPMENT Make Make Lennox Trade Trade LENNOX Model Cond ML14XC1S030-230A** AHRI ref Coil CBA27UHE-030-230*++TDR AHRI ref 10259437 Efficiency 100 EFF Efficiency 13.0 EER, 16 SEER Heating input kW6.9 Sensible cooling Btuh20300 Heating output Btuh23456 Latent cooling Btuh8700 Temperature rise °F22 Total cooling Btuh29000 Actual air flow cfm967 Actual air flow cfm967 Air flow factor cfm/Btuh0.043 Air flow factor cfm/Btuh0.048 Static pressure in H2O0.70 Static pressure in H2O0.70 Space thermostat Load sensible heat ratio 0.78 ROOM NAME Area Htg load Clg load Htg AVF Clg AVF (ft²)(Btuh)(Btuh)(cfm)(cfm) M Hall 26 0 0 0 0 Laundry 68 908 991 39 48 Master Bath 90 1992 740 86 36 WIC 63 1611 581 70 28 Master Bed 247 2011 2232 87 108 Pantry 15 0 0 0 0 Kitchen/Nook 275 3644 4691 157 227 Great Room 377 4795 5909 207 285 Bed 3 173 2935 2068 127 100 Hall 30 0 0 0 0 Lin 8 0 0 0 0 Bath 50 738 406 32 20 Bed 2 182 3736 2394 161 116 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Oct-14 11:29:23 Right-Suite® Universal 2021 21.0.08 RSU29066 Page 2 ...ents\Wrightsoft HVAC\TBD E Easy St PSL Prop.rup Calc = MJ8 Front Door faces: N House 1602 22369 20014 967 967 Other equip loads 1467 779 Equip. @ 0.95 RSM 19837 Latent cooling 6029 TOTALS 1602 23835 25866 967 967 2021-Oct-14 11:29:23Right-Suite® Universal 2021 21.0.08 RSU29066 Page 1...ents\Wrightsoft HVAC\TBD E Easy St PSL Prop.rup Calc = MJ8 Front Door faces: N 1642Job:Building Analysis 10/14/2021Date:House Chris BatemanBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Betsinger Residence, NisAir Air ConditioningFor:TBD E Easy St, Fort Pierce, FL 34982 Design Conditions Location: CoolingHeatingIndoor:7570Indoor temperature (°F)St Lucie Co Intl, FL, US 1529Design TD (°F)ft26Elevation:5030Relative humidity (%)°N28Latitude:Outdoor:56.92.4Moisture difference (gr/lb)CoolingHeating Infiltration:9041Dry bulb (°F) SimplifiedMethod)L(15-Daily range (°F)AverageConstruction quality77-Wet bulb (°F)0Fireplaces7.515.0Wind speed (mph) Heating Walls Glazing Ceilings Floors Infiltration Ducts Ventilation % of loadBtuhBtuh/ft²Component 18.343723.1Walls 13.6324818.2Glazing 000Doors6.715881.0Ceilings 22.653923.43.4Floors 11.727822.0Infiltration 20.94987Ducts00Piping00Humidification6.21467Ventilation0Adjustments100.023835Total Cooling Walls Glazing Ceilings Infiltration Ducts Internal Gains Ventilation % of loadBtuhBtuh/ft²Component 13.127161.9Walls 17.0354419.8Glazing 000Doors11.323431.5Ceilings 000Floors3.77780.6Infiltration 27.05613Ducts3.7779Ventilation24.15020Internal gains 00Blower0Adjustments100.020793Total Latent Cooling Load = 6029 BtuhOverall U-value = 0.105 Btuh/ft²-°F Data entries checked. 2021-Oct-14 11:29:24 Right-Suite® Universal 2021 21.0.08 RSU29066 Page 1 ...ents\Wrightsoft HVAC\TBD E Easy St PSL Prop.rup Calc = MJ8 Front Door faces: N 1642Job:Component Constructions 10/14/2021Date:House Chris BatemanBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Betsinger Residence, NisAir Air ConditioningFor: TBD E Easy St, Fort Pierce, FL 34982 Design Conditions Location: CoolingHeatingIndoor:7570Indoor temperature (°F)St Lucie Co Intl, FL, US 1529Design TD (°F)ft26Elevation:5030Relative humidity (%)°N28Latitude: Outdoor:56.92.4Moisture difference (gr/lb)CoolingHeating Infiltration:9041Dry bulb (°F) SimplifiedMethod)L(15-Daily range (°F) AverageConstruction quality77-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLoss Clg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls Blk Wall, Stucco Ext, R-4.1 Ext Bd inI, 8" Thk, 1/2" Gyp Bd Int Fnsh 7553.155.10.109239n 4832.02 8922.0213953.155.10.109443e 5212.028143.155.10.109259s 5402.028443.155.10.109268w 24362.0238083.155.10.1091209all Partitions Frm Wall, 1/2" Gyp Bd Ext, R-11 Cav Ins, 1/2" Gyp Bd Int Fnsh, 2"x4", 16" OC Stud 2801.465642.9411.00.101192 WindowsImpact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.24); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 1 ft overhang (2.08 ft window ht, 1 ft sep.); 8 ft head ht 5211.57616.800.5805n Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.24); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 1 ft overhang (5.17 ft window ht, 1 ft sep.); 8 ft head ht 87228.152116.800.58031e Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.21); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 10 ft overhang (8 ft window ht, 1 ft sep.); 8 ft head ht 53711.290518.800.65048e Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.24); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 1 ft overhang (3.17 ft window ht, 1 ft sep.); 8 ft head ht 12813.516016.800.58010s Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.22); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 1 ft overhang (5.17 ft window ht, 1 ft sep.); 8 ft head ht 42127.227918.000.62016w 2021-Oct-14 11:29:24 Right-Suite® Universal 2021 21.0.08 RSU29066 Page 2 ...ents\Wrightsoft HVAC\TBD E Easy St PSL Prop.rup Calc = MJ8 Front Door faces: N Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.22); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 6 ft overhang (5.17 ft window ht, 1 ft sep.); 8 ft head ht 37716.840318.000.62022w Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.24); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 9.1 ft overhang (8 ft window ht, 1 ft sep.); 8 ft head ht 60312.690518.800.65048w Doors (none) CeilingsAttic, Shngls, R-30 Ceil Ins, 1/2" Gyp Bd Int Fnsh 0.0341602 23431.4615880.9930.0 FloorsOn Grade Depth, Tile Flr Fnsh 00539228.700.989188 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Oct-14 11:29:24Right-Suite® Universal 2021 21.0.08 RSU29066 Page 1...ents\Wrightsoft HVAC\TBD E Easy St PSL Prop.rup Calc = MJ8 Front Door faces: N 1642Job:Project Summary 10/14/2021Date:House Chris BatemanBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Betsinger Residence, NisAir Air ConditioningFor:TBD E Easy St, Fort Pierce, FL 34982 Notes: Design Information St Lucie Co Intl, FL, USWeather: Winter Design Conditions Summer Design Conditions Outside db °F41 Outside db °F90Inside db °F70 Inside db °F75Design TD °F29 Design TD °F15Daily range LRelative humidity %50Moisture difference gr/lb57 Heating Summary Sensible Cooling Equipment Load Sizing Structure Btuh17382 Structure Btuh14401Ducts Btuh4987 Ducts Btuh5613Central vent (46 cfm) 1467 Btuh Central vent (46 cfm) Btuh779Outside air Outside airHumidification Btuh0 Blower Btuh0Piping Btuh0Equipment load Btuh23835 Use manufacturer's data nRate/swing multiplier 0.95InfiltrationEquipment sensible load Btuh19837 Method Latent Cooling Equipment Load SizingSimplifiedConstruction quality Average0Fireplaces Structure Btuh2576Ducts Btuh1676Central vent (46 cfm) Btuh1778CoolingHeatingOutside air16021602Area (ft²) Equipment latent load Btuh60291378413784Volume (ft³)Air changes/hour 0.200.38 Equipment Total Load (Sen+Lat)Btuh25866Equiv. AVF (cfm) 4687 Req. total capacity at 0.70 SHR ton2.4 Heating Equipment Summary Cooling Equipment Summary Make Make LennoxTrade Trade LENNOXModel Cond ML14XC1S030-230A**AHRI ref Coil CBA27UHE-030-230*++TDRAHRI ref 10259437Efficiency 100 EFF Efficiency 13.0 EER, 16 SEERHeating input kW6.9 Sensible cooling Btuh20300Heating output Btuh23456 Latent cooling Btuh8700Temperature rise °F22 Total cooling Btuh29000Actual air flow cfm967 Actual air flow cfm967Air flow factor cfm/Btuh0.043 Air flow factor cfm/Btuh0.048Static pressure in H2O0.70 Static pressure in H2O0.70Space thermostat Load sensible heat ratio 0.78 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Oct-14 11:29:24Right-Suite® Universal 2021 21.0.08 RSU29066 Page 1...ents\Wrightsoft HVAC\TBD E Easy St PSL Prop.rup Calc = MJ8 Front Door faces: N 1642Job:Right-J® Worksheet 10/14/2021Date:House Chris BatemanBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name House M Hall 2 Exposed wall 188.0 ft 4.0 ft3Room height 8.6 ft 8.0 heat/coolft 4 Room dimensions ft6.5x4.05Room area 1601.8 ft²26.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Loadnumber(Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nn 3.153.15 2.022.02 244 239 755 483 0 0 0 0.GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nn 16.8216.82 11.4811.48 5 0 76 52 0 0 0 0.WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ee 3.153.15 2.022.02 522 443 1395 892 0 0 0 0.GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ee 16.8216.82 28.1328.13 31 0 521 872 0 0 0 011GGImpact, Clear Low-e 0.650Impact, Clear Low-e 0.650 ee 18.8518.85 11.2011.20 48 44 905 537 0 0 0 0WWBlk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ss 3.153.15 2.022.02 268 259 814 521 0 0 0 0GGImpact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ss 16.8216.82 13.4813.48 10 10 160 128 0 0 0 0WWBlk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ww 3.153.15 2.022.02 354 268 844 540 0 0 0 0 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 ww 17.9817.98 27.1827.18 16 0 279 421 0 0 0 0GGImpact, Clear Low-e 0.620Impact, Clear Low-e 0.620 ww 17.9817.98 16.8316.83 22 17 403 377 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 ww 18.8518.85 12.5712.57 48 39 905 603 0 0 0 0PPFrm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 192 192 564 280 32 32 94 47CCAttic, Shngls, R-30 0.034Attic, Shngls, R-30 0.034 --0.990.99 1.461.46 1602 1602 1588 2343 26 26 26 38FFOn Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 1602 188 5392 0 26 4 115 0 6 c) AED excursion 553 -5 Envelope loss/gain 14600 8603 235 80 12 a) Infiltration 2782 778 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 4 920 0 0 Appliances/other 4100 0 Subtotal (lines 6 to 13)17382 14401 235 80 Less external loadLess external load 0 0 0 0Less transferLess transfer 0 0 0 0RedistributionRedistribution00-235 -8014Subtotal173821440100 15 Duct loads 29%39%4987 5613 29%39%0 0 Total room load 22369 20014 0 0Air required (cfm)Air required (cfm)967 967 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Oct-14 11:29:24Right-Suite® Universal 2021 21.0.08 RSU29066 Page 2...ents\Wrightsoft HVAC\TBD E Easy St PSL Prop.rup Calc = MJ8 Front Door faces: N 1642Job:Right-J® Worksheet 10/14/2021Date:House Chris BatemanBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Laundry Master Bath 2 Exposed wall 10.5 ft 21.5 ft3Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft6.5x10.5 ft12.0x7.55Room area 68.3 ft²90.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Loadnumber(Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nn 3.153.15 2.022.02 0 0 0 0 96 91 288 184.GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nn 16.8216.82 11.4811.48 0 0 0 0 5 0 76 52.WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ee 3.153.15 2.022.02 0 0 0 0 16 16 50 32.GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ee 16.8216.82 28.1328.13 0 0 0 0 0 0 0 011GGImpact, Clear Low-e 0.650Impact, Clear Low-e 0.650 ee 18.8518.85 11.2011.20 0 0 0 0 0 0 0 0WWBlk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ss 3.153.15 2.022.02 0 0 0 0 0 0 0 0GGImpact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ss 16.8216.82 13.4813.48 0 0 0 0 0 0 0 0WWBlk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ww 3.153.15 2.022.02 0 0 0 0 12 12 38 24 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 ww 17.9817.98 27.1827.18 0 0 0 0 0 0 0 0GGImpact, Clear Low-e 0.620Impact, Clear Low-e 0.620 ww 17.9817.98 16.8316.83 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 ww 18.8518.85 12.5712.57 0 0 0 0 0 0 0 0PPFrm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 84 84 247 123 48 48 141 70CCAttic, Shngls, R-30 0.034Attic, Shngls, R-30 0.034 --0.990.99 1.461.46 68 68 68 100 90 90 89 132FFOn Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 68 11 301 0 90 22 617 0 6 c) AED excursion -40 -31 Envelope loss/gain 616 182 1299 463 12 a) Infiltration 0 0 249 69 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 500 0 Subtotal (lines 6 to 13)616 682 1548 533 Less external loadLess external load 0 0 0 0Less transferLess transfer 0 0 0 0RedistributionRedistribution90310014Subtotal7057131548533 15 Duct loads 29%39%202 278 29%39%444 208 Total room load 908 991 1992 740Air required (cfm)Air required (cfm)39 48 86 36 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Oct-14 11:29:24Right-Suite® Universal 2021 21.0.08 RSU29066 Page 3...ents\Wrightsoft HVAC\TBD E Easy St PSL Prop.rup Calc = MJ8 Front Door faces: N 1642Job:Right-J® Worksheet 10/14/2021Date:House Chris BatemanBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name WIC Master Bed 2 Exposed wall 17.0 ft 14.5 ft3Room height 8.0 heat/coolft 8.5 heat/coolft 4 Room dimensions ft11.5x5.5 ft17.0x14.55Room area 63.3 ft²246.5 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Loadnumber(Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nn 3.153.15 2.022.02 92 92 290 185 0 0 0 0.GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nn 16.8216.82 11.4811.48 0 0 0 0 0 0 0 0.WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ee 3.153.15 2.022.02 44 44 139 89 123 108 340 217.GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ee 16.8216.82 28.1328.13 0 0 0 0 16 0 261 43611GGImpact, Clear Low-e 0.650Impact, Clear Low-e 0.650 ee 18.8518.85 11.2011.20 0 0 0 0 0 0 0 0WWBlk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ss 3.153.15 2.022.02 0 0 0 0 0 0 0 0GGImpact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ss 16.8216.82 13.4813.48 0 0 0 0 0 0 0 0WWBlk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ww 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 ww 17.9817.98 27.1827.18 0 0 0 0 0 0 0 0GGImpact, Clear Low-e 0.620Impact, Clear Low-e 0.620 ww 17.9817.98 16.8316.83 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 ww 18.8518.85 12.5712.57 0 0 0 0 0 0 0 0PPFrm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0CCAttic, Shngls, R-30 0.034Attic, Shngls, R-30 0.034 --0.990.99 1.461.46 63 63 63 93 247 247 244 361FFOn Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 63 17 488 0 247 15 416 0 6 c) AED excursion -24 4 Envelope loss/gain 979 342 1260 1018 12 a) Infiltration 273 76 247 69 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 0 500 Subtotal (lines 6 to 13)1251 418 1508 1587 Less external loadLess external load 0 0 0 0Less transferLess transfer 0 0 0 0RedistributionRedistribution00551914Subtotal125141815631606 15 Duct loads 29%39%359 163 29%39%448 626 Total room load 1611 581 2011 2232Air required (cfm)Air required (cfm)70 28 87 108 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Oct-14 11:29:24Right-Suite® Universal 2021 21.0.08 RSU29066 Page 4...ents\Wrightsoft HVAC\TBD E Easy St PSL Prop.rup Calc = MJ8 Front Door faces: N 1642Job:Right-J® Worksheet 10/14/2021Date:House Chris BatemanBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Pantry Kitchen/Nook 2 Exposed wall 0 ft 23.5 ft3Room height 8.0 heat/coolft 9.3 heat/coolft 4 Room dimensions ft3.0x5.0 ft274.5x1.05Room area 15.0 ft²274.5 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Loadnumber(Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nn 3.153.15 2.022.02 0 0 0 0 0 0 0 0.GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nn 16.8216.82 11.4811.48 0 0 0 0 0 0 0 0.WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ee 3.153.15 2.022.02 0 0 0 0 219 171 537 344.GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ee 16.8216.82 28.1328.13 0 0 0 0 0 0 0 011GGImpact, Clear Low-e 0.650Impact, Clear Low-e 0.650 ee 18.8518.85 11.2011.20 0 0 0 0 48 44 905 537WWBlk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ss 3.153.15 2.022.02 0 0 0 0 0 0 0 0GGImpact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ss 16.8216.82 13.4813.48 0 0 0 0 0 0 0 0WWBlk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ww 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 ww 17.9817.98 27.1827.18 0 0 0 0 0 0 0 0GGImpact, Clear Low-e 0.620Impact, Clear Low-e 0.620 ww 17.9817.98 16.8316.83 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 ww 18.8518.85 12.5712.57 0 0 0 0 0 0 0 0PPFrm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0CCAttic, Shngls, R-30 0.034Attic, Shngls, R-30 0.034 --0.990.99 1.461.46 15 15 15 22 275 275 272 402FFOn Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 15 0 0 0 275 24 674 0 6 c) AED excursion -1 -197 Envelope loss/gain 15 21 2388 1086 12 a) Infiltration 0 0 438 122 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 2 460 Appliances/other 0 1700 Subtotal (lines 6 to 13)15 21 2826 3368 Less external loadLess external load 0 0 0 0Less transferLess transfer 0 0 0 0RedistributionRedistribution-15 -21 5 714Subtotal0028323376 15 Duct loads 29%39%0 0 29%39%812 1316 Total room load 0 0 3644 4691Air required (cfm)Air required (cfm)0 0 157 227 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Oct-14 11:29:24Right-Suite® Universal 2021 21.0.08 RSU29066 Page 5...ents\Wrightsoft HVAC\TBD E Easy St PSL Prop.rup Calc = MJ8 Front Door faces: N 1642Job:Right-J® Worksheet 10/14/2021Date:House Chris BatemanBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Great Room Bed 3 2 Exposed wall 29.0 ft 27.0 ft3Room height 9.3 heat/coolft 8.0 heat/coolft 4 Room dimensions ft14.5x26.0 ft172.5x1.05Room area 377.0 ft²172.5 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Loadnumber(Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nn 3.153.15 2.022.02 0 0 0 0 0 0 0 0.GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nn 16.8216.82 11.4811.48 0 0 0 0 0 0 0 0.WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ee 3.153.15 2.022.02 0 0 0 0 120 105 329 211.GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ee 16.8216.82 28.1328.13 0 0 0 0 16 0 261 43611GGImpact, Clear Low-e 0.650Impact, Clear Low-e 0.650 ee 18.8518.85 11.2011.20 0 0 0 0 0 0 0 0WWBlk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ss 3.153.15 2.022.02 0 0 0 0 96 96 302 193GGImpact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ss 16.8216.82 13.4813.48 0 0 0 0 0 0 0 0WWBlk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ww 3.153.15 2.022.02 242 171 540 345 0 0 0 0 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 ww 17.9817.98 27.1827.18 0 0 0 0 0 0 0 0GGImpact, Clear Low-e 0.620Impact, Clear Low-e 0.620 ww 17.9817.98 16.8316.83 22 17 403 377 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 ww 18.8518.85 12.5712.57 48 39 905 603 0 0 0 0PPFrm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 28 28 82 41 0 0 0 0CCAttic, Shngls, R-30 0.034Attic, Shngls, R-30 0.034 --0.990.99 1.461.46 377 377 374 552 173 173 171 252FFOn Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 377 29 832 0 173 27 774 0 6 c) AED excursion 785 11 Envelope loss/gain 3135 2703 1838 1103 12 a) Infiltration 485 136 433 121 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 2 460 0 0 Appliances/other 900 250 Subtotal (lines 6 to 13)3620 4198 2271 1474 Less external loadLess external load 0 0 0 0Less transferLess transfer 0 0 0 0RedistributionRedistribution10654101414Subtotal3726425222811488 15 Duct loads 29%39%1069 1657 29%39%654 580 Total room load 4795 5909 2935 2068Air required (cfm)Air required (cfm)207 285 127 100 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Oct-14 11:29:24Right-Suite® Universal 2021 21.0.08 RSU29066 Page 6...ents\Wrightsoft HVAC\TBD E Easy St PSL Prop.rup Calc = MJ8 Front Door faces: N 1642Job:Right-J® Worksheet 10/14/2021Date:House Chris BatemanBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Hall Lin 2 Exposed wall 0 ft 0 ft3Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft8.5x3.5 ft3.0x2.55Room area 29.8 ft²7.5 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Loadnumber(Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nn 3.153.15 2.022.02 0 0 0 0 0 0 0 0.GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nn 16.8216.82 11.4811.48 0 0 0 0 0 0 0 0.WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ee 3.153.15 2.022.02 0 0 0 0 0 0 0 0.GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ee 16.8216.82 28.1328.13 0 0 0 0 0 0 0 011GGImpact, Clear Low-e 0.650Impact, Clear Low-e 0.650 ee 18.8518.85 11.2011.20 0 0 0 0 0 0 0 0WWBlk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ss 3.153.15 2.022.02 0 0 0 0 0 0 0 0GGImpact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ss 16.8216.82 13.4813.48 0 0 0 0 0 0 0 0WWBlk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ww 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 ww 17.9817.98 27.1827.18 0 0 0 0 0 0 0 0GGImpact, Clear Low-e 0.620Impact, Clear Low-e 0.620 ww 17.9817.98 16.8316.83 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 ww 18.8518.85 12.5712.57 0 0 0 0 0 0 0 0PPFrm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0CCAttic, Shngls, R-30 0.034Attic, Shngls, R-30 0.034 --0.990.99 1.461.46 30 30 29 44 8 8 7 11FFOn Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 30 0 0 0 8 0 0 0 6 c) AED excursion -2 -1 Envelope loss/gain 29 41 7 10 12 a) Infiltration 0 0 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)29 41 7 10 Less external loadLess external load 0 0 0 0Less transferLess transfer 0 0 0 0RedistributionRedistribution-29 -41 -7 -1014Subtotal0000 15 Duct loads 29%39%0 0 29%39%0 0 Total room load 0 0 0 0Air required (cfm)Air required (cfm)0 0 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Oct-14 11:29:24Right-Suite® Universal 2021 21.0.08 RSU29066 Page 7...ents\Wrightsoft HVAC\TBD E Easy St PSL Prop.rup Calc = MJ8 Front Door faces: N 1642Job:Right-J® Worksheet 10/14/2021Date:House Chris BatemanBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Bath Bed 2 2 Exposed wall 5.5 ft 35.5 ft3Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft5.5x9.0 ft182.0x1.05Room area 49.5 ft²182.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Loadnumber(Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nn 3.153.15 2.022.02 0 0 0 0 56 56 176 113.GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nn 16.8216.82 11.4811.48 0 0 0 0 0 0 0 0.WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ee 3.153.15 2.022.02 0 0 0 0 0 0 0 0.GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ee 16.8216.82 28.1328.13 0 0 0 0 0 0 0 011GGImpact, Clear Low-e 0.650Impact, Clear Low-e 0.650 ee 18.8518.85 11.2011.20 0 0 0 0 0 0 0 0WWBlk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ss 3.153.15 2.022.02 44 35 109 70 128 128 403 258GGImpact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ss 16.8216.82 13.4813.48 10 10 160 128 0 0 0 0WWBlk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ww 3.153.15 2.022.02 0 0 0 0 100 85 266 170 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 ww 17.9817.98 27.1827.18 0 0 0 0 16 0 279 421GGImpact, Clear Low-e 0.620Impact, Clear Low-e 0.620 ww 17.9817.98 16.8316.83 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 ww 18.8518.85 12.5712.57 0 0 0 0 0 0 0 0PPFrm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0CCAttic, Shngls, R-30 0.034Attic, Shngls, R-30 0.034 --0.990.99 1.461.46 50 50 49 72 182 182 180 266FFOn Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 50 6 158 0 182 36 1018 0 6 c) AED excursion -16 71 Envelope loss/gain 475 254 2323 1300 12 a) Infiltration 88 25 569 159 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 0 250 Subtotal (lines 6 to 13)564 278 2893 1709 Less external loadLess external load 0 0 0 0Less transferLess transfer 0 0 0 0RedistributionRedistribution1014101414Subtotal57429229031723 15 Duct loads 29%39%165 114 29%39%833 672 Total room load 738 406 3736 2394Air required (cfm)Air required (cfm)32 20 161 116 2021-Oct-14 11:29:24 Right-Suite® Universal 2021 21.0.08 RSU29066 Page 1 ...ents\Wrightsoft HVAC\TBD E Easy St PSL Prop.rup Calc = MJ8 Front Door faces: N 1642Job:Duct System Summary 10/14/2021Date:House Chris BatemanBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Betsinger Residence, NisAir Air ConditioningFor: TBD E Easy St, Fort Pierce, FL 34982 CoolingHeating External static pressure in H2O0.70in H2O0.70 Pressure losses in H2O0in H2O0 Available static pressure in H2O0.70in H2O0.70 Supply / return available pressure 0.570 / 0.130 in H2O in H2O0.570 / 0.130 Lowest friction rate in/100ft0.298in/100ft0.298 Actual air flow cfm967cfm967 Total effective length (TEL) ft235 Supply Branch Detail Table Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv Name (Btuh)(cfm) (cfm)FR (in)(in)Matl Ln (ft)Ln (ft) Trunk st3135.044.7VlFx0x04.00.3172438738hBath st3140.051.6VlFx0x07.00.2981391943736hBed 2 st3140.049.6VlFx0x07.00.3011201522935hBed 3 st2110.036.0VlFx0x07.00.3911711242955cGreat Room st2110.036.8VlFx0x07.00.3891711242955cGreat Room-A st2110.036.9VlFx0x06.00.388136942346cKitchen/Nook st2110.035.8VlFx0x06.00.391136942346cKitchen/Nook-A 80.04.9VlFx0x04.00.6725747991cLaundry st1100.019.9VlFx0x05.00.476431031992hMaster Bath st195.022.1VlFx0x05.00.48765521116cMaster Bed st195.019.4VlFx0x05.00.49865521116cMaster Bed-A st195.019.8VlFx0x05.00.49734841611hWIC Supply Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk st1 Peak AVF 291 206 0.476 834 8.0 0x0 VinlFlx st3 Peak AVF 384 282 0.298 870 9.0 0x0 VinlFlx st2 st2 Peak AVF 822 897 0.298 839 14.0 0x0 VinlFlx Bold/italic values have been manually overridden 2021-Oct-14 11:29:24 Right-Suite® Universal 2021 21.0.08 RSU29066 Page 2 ...ents\Wrightsoft HVAC\TBD E Easy St PSL Prop.rup Calc = MJ8 Front Door faces: N Return Branch Detail Table Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size (in) (cfm)(cfm)(ft)FR (fpm)(in)(in)Opening (in) Matl Trunk rb5 0x 1880 163 43.6 0.298 538 8.0 x0 0 VlFx rb6 0x 6260 738 0 0 0 0 x0 0 VlFx rb4 0x 1940 139 0 0 0 0 x0 0 VlFx rb3 0x 1520 120 0 0 0 0 x0 0 VlFx 2021-Oct-14 11:29:24 Right-Suite® Universal 2021 21.0.08 RSU29066 Page 1 ...ents\Wrightsoft HVAC\TBD E Easy St PSL Prop.rup Calc = MJ8 Front Door faces: N 1642Job:Manual S Compliance Report 10/14/2021Date:House Chris BatemanBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Betsinger Residence, NisAir Air ConditioningFor: TBD E Easy St, Fort Pierce, FL 34982 Cooling Equipment Design Conditions °F76.9Entering coil DB:Btuh20793Sensible gain:°F90.4Outdoor design DB: °F64.0Entering coil WB:Btuh6029Latent gain:°F77.4Outdoor design WB: Btuh26823Total gain:°F75.0Indoor design DB: cfm967Estimated airflow:%50Indoor RH: Manufacturer's Performance Data at Actual Design Conditions Split ACEquipment type: ML14XC1S030-230A**+CBA27UHE-030-230*++TDRModel:LennoxManufacturer: cfm967Actual airflow: % of load98Btuh20300Sensible capacity: % of load144Btuh8700Latent capacity: %70SHR:% of load108Btuh29000Total capacity: Heating Equipment Design Conditions °F68.1Entering coil DB:Btuh23835Heat loss:°F41.0Outdoor design DB: °F70.0Indoor design DB: Manufacturer's Performance Data at Actual Design Conditions Elec stripEquipment type: Model:Manufacturer: cfm967Actual airflow: °F50Temp. rise:% of load98kW6.9Output capacity: Meets all requirements of ACCA Manual S.