HomeMy WebLinkAboutSOLAR POWER SYSTEMPV MODULE
MICRO-
INVERTER
PM1-34
315W
11 IN
BRANCH
11 IN
BRANCH
12 IN
BRANCH
1 2
3 4
5 6
7
JUNCTION BOX
2
1 3
JB1
AC COMBINER
CB2
15A
CB1
15A
4
CB3
15A C1
8
PV DISCONNECTF1-2
45A
5
SW1
60A
AC
GEC
LOADS
KWHR
LOAD
LINE
KWHR
LOAD
LINE
UTILITY METER
(200A MSP W/200A MCB)
240/120V 1ΙΈ, 3W
9 10
MODULES
REF.QTY.MAKE AND MODEL PMAX PTC ISC IMP VOC VMP TEMP. COEFF. OF VOC FUSE RATING
PM1-34 34
HYUNDAI HID-S315RG(BK)315W 289W 9.99A 9.51A 40.5V 33.4V
-0.126V/°C (-0.31%/°C)20A
INVERTERS
REF.QTY.MAKE AND MODEL AC VOLTAGE GROUND RATED POWER MAX OUTPUT CURRENT MAX INPUT CURRENT MAX INPUT VOLTAGE CEC WEIGHTED EFFICIENCY
I1-34 34 ENPHASE IQ7-60-2-US 240V NOT SOLIDLY GROUNDED 240W 1.0A 15.0A 48V 97.0%
DISCONNECTS
REF.QTY.MAKE AND MODEL RATED CURRENT MAX RATED VOLTAGE
SW1 1 EATON DG222NRB OR EQUIV.60A 240VAC
OCPDS
REF.QTY.RATED CURRENT MAX VOLTAGE
CB1-3 3 15A 240VAC
F1-2 2 45A 0VAC
SYSTEM SUMMARY
BRANCH 1 BRANCH 2 BRANCH 3
INVERTERS PER BRANCH 11 11 12
MAX AC CURRENT 11A 11A 12A
MAX AC OUTPUT 2,640W 2,640W 2,880W
ARRAY STC POWER 10,710W
ARRAY PTC POWER 9,840W
MAX AC CURRENT 34A
MAX AC POWER OUTPUT 8,160W
DERATED AC POWER OUTPUT 6,936W
NOTES
THE DC AND AC CONNECTORS OF THE ENPHASE IQ7-60-2-US AND ARE LISTED TO MEET REQUIREMENTS AS A DISCONNECT MEANS AS ALLOWED BY NEC 690.15(D). MATING CONNECTORS
SHALL COMPLY WITH NEC 690.33.
1
THE ENPHASE IQ7-60-2-US HAS A CLASS II DOUBLE-INSULATED RATING AND DOES NOT REQUIRE GROUNDING ELECTRODE CONDUCTORS (GEC) OR EQUIPMENT GROUNDING
CONDUCTORS (EGC). THE RATING INCLUDES GROUND FAULT PROTECTION (GFP). TO SUPPORT GFP, USE ONLY PV MODULES EQUIPPED WITH DC CABLES LABELED PV WIRE OR PV CABLE.
2
ENPHASE SYSTEM MEETS REQUIREMENTS FOR PHOTOVOLTAIC RAPID SHUTDOWN SYSTEM (PVRSS), AS PER NEC 690.12(B).3
MICROINVERTER BRANCH CIRCUIT CONDUCTORS ARE MANUFACTURED ENPHASE Q CABLES LISTED FOR USE IN 20A OR LESS CIRCUITS OF ENPHASE IQ MICROINVERTERS. THEY ARE
ROHS, OIL RESISTANT, AND UV RESISTANT. THEY CONTAIN TWO 12 AWG CONDUCTORS OF TYPE THHN/THWN-2 DRY/WET AND CERTIFIED TO UL3003 AND UL 9703.
4
DC PV CONDUCTORS ARE NOT SOLIDLY-GROUNDED. NO DC PV CONDUCTOR SHALL BE WHITE- OR GRAY-COLORED5
ALL METAL ENCLOSURES, RACEWAYS, CABLES AND EXPOSED NONCURRENT-CARRYING METAL PARTS OF EQUIPMENT SHALL BE GROUNDED TO EARTH AS REQUIRED BY NEC 250.4(A)
AND PART III OF ARTICLE 250 AND EQUIPMENT GROUNDING CONDUCTORS SHALL BE SIZED ACCORDING TO NEC 690.45. THE GROUNDING ELECTRODE SYSTEM SHALL ADHERE TO NEC
690.47(A) AND NEC 250.169. THE DC GROUNDING ELECTRODE SHALL BE SIZED ACCORDING TO NEC 250.166 AND INSTALLED IN COMPLIANCE WITH NEC 250.64.
6
7 MAX DC VOLTAGE OF PV MODULE IS 43.6V AT 0°C (0°C - 25°C) X -0.126V/C + 40.5V = 43.6V).
8 AC AGGREGATION PANEL BUSBAR AND THE OVERCURRENT PROTECTION PROTECTING THE BUSBAR SHALL BE SIZED IN ACCORDANCE WITH NEC 705.12(B)(2)(3)(C)
POINT-OF-CONNECTION IS ON THE SUPPLY SIDE OF SERVICE DISCONNECT, INSIDE PANELBOARD ENCLOSURE USING UNUSED TERMINALS, TERMINALS THAT ARE SUITABLE FOR DOUBLE
LUGGING, OR USING OTHER LOCALLY-APPROVED METHODS AND HARDWARE, IN COMPLIANCE WITH NEC 705.12(A). THE PANELBOARD SHALL HAVE SUFFICIENT SPACE TO ALLOW FOR
ANY TAP HARDWARE AS REQUIRED BY NEC 110.3 AND NEC 312.8(A)
9
PV SYSTEM DISCONNECT SHALL BE A VISIBLE KNIFE-BLADE TYPE DISCONNECT THAT IS ACCESSIBLE AND LOCKABLE BY THE UTILITY. THE DISCONNECT SHALL BE LOCATED WITHIN 10 FT
OF UTILITY METER. DISCONNECT SHALL BE GROUPED IN ACCORDANCE WITH NEC 230.72.
10
CONDUCTOR AND CONDUIT SCHEDULE W/ELECTRICAL CALCULATIONS
ID TYPICAL CONDUCTOR CONDUIT / CABLE
CURRENT-CARRYING
CONDUCTORS IN
CONDUIT / CABLE
OCPD EGC TEMP. CORR.
FACTOR FILL FACTOR CONT.
CURRENT
MAX.
CURRENT
(125%)
BASE AMP.DERATED
AMP.
TERM.
TEMP.
RATING
AMP. @ TERM.
TEMP. RATING LENGTH VOLTAGE
DROP
1 1 12 AWG THWN-2, COPPER 0.5" DIA.6 15A 12 AWG THWN-2, COPPER 0.76 (54°C)0.8 11A 13.75A 30A 18.24A 90°C 30A 9FT 0.16%
2 1 12 AWG THWN-2, COPPER 0.5" DIA.6 15A 12 AWG THWN-2, COPPER 0.76 (54°C)0.8 11A 13.75A 30A 18.24A 90°C 30A 9FT 0.16%
3 1 12 AWG THWN-2, COPPER 0.5" DIA.6 15A 12 AWG THWN-2, COPPER 0.76 (54°C)0.8 12A 15A 30A 18.24A 90°C 30A 9FT 0.18%
4 1 6 AWG THWN-2, COPPER 0.75" DIA.3 45A 8 AWG THWN-2, COPPER 0.96 (34°C)1.0 34A 42.5A 75A 72A 75°C 65A 48IN 0.06%
5 1 6 AWG THWN-2, COPPER 0.75" DIA.3 45A N/A 0.96 (34°C)1.0 34A 42.5A 75A 72A 75°C 65A 48IN 0.06%
REVISIONS
CREATED BY:GRID-TIED SOLAR POWER SYSTEMDATE: 8/10/21
N.T.
SINGLE-LINE DIAGRAM
GROUNDING NOTES
1
ALL EQUIPMENT SHALL BE
PROPERLY GROUNDED PER THE
REQUIREMENTS OF NEC ARTICLES
250 & 690
2
PV MODULES SHALL BE GROUNDED
TO MOUNTING RAILS USING MODULE
LUGS OR RACKING INTEGRATED
GROUNDING CLAMPS AS ALLOWED
BY LOCAL JURISDICTION. ALL OTHER
EXPOSED METAL PARTS SHALL BE
GROUNDED USING UL-LISTED LAY-IN
LUGS.
3
INSTALLER SHALL CONFIRM THAT
MOUNTING SYSTEM HAS BEEN
EVALUATED FOR COMPLIANCE WITH
UL 2703 "GROUNDING AND BONDING"
WHEN USED WITH PROPOSED PV
MODULE.
4
IF THE EXISTING MAIN SERVICE
PANEL DOES NOT HAVE A
VERIFIABLE GROUNDING
ELECTRODE, IT IS THE
CONTRACTOR'S RESPONSIBILITY TO
INSTALL A SUPPLEMENTAL
GROUNDING ELECTRODE.
5
AC SYSTEM GROUNDING
ELECTRODE CONDUCTOR (GEC)
SHALL BE A MINIMUM SIZE #8AWG
WHEN INSULATED, #6AWG IF BARE
WIRE.
6
EQUIPMENT GROUNDING
CONDUCTORS SHALL BE SIZED
ACCORDING TO NEC ARTICLE 690.45,
AND BE A MINIMUM OF #10AWG
WHEN NOT EXPOSED TO DAMAGE,
AND #6AWG SHALL BE USED WHEN
EXPOSED TO DAMAGE
7
GROUNDING AND BONDING
CONDUCTORS, IF INSULATED, SHALL
BE COLOR CODED GREEN, OR
MARKED GREEN IF #4AWG OR
LARGER
GENERAL ELECTRICAL
NOTES
1
UTILITY HAS 24-HR UNRESTRICTED
ACCESS TO ALL PHOTOVOLTAIC
SYSTEM COMPONENTS LOCATED AT
THE SERVICE ENTRANCE.
2
CONDUCTORS EXPOSED TO
SUNLIGHT SHALL BE LISTED AS
SUNLIGHT RESISTANT PER NEC
ARTICLE 300.6 (C) (1) AND ARTICLE
310.10 (D).
3
CONDUCTORS EXPOSED TO WET
LOCATIONS SHALL BE SUITABLE FOR
USE IN WET LOCATIONS PER NEC
ARTICLE 310.10 (C).
4 CONDUIT CONNECTION UP TO
CONTRACTOR DISCRETION.
SCALE:NTS
SINGLE-LINE DIAGRAM
PV-2
1
THIS DOCUMENT HAS BEEN CREATED FOR THE PURPOSE OF DESCRIBING THE DESIGN OF A PROPOSED PHOTOVOLTAIC POWER SYSTEM WITH ENOUGH DETAIL TO DEMONSTRATE COMPLIANCE WITH ALL APPLICABLE CODES AND REGULATIONS. THE DOCUMENT SHOULD NOT BE RELIED UPON AS A SUBSTITUTE FOR
FOLLOWING MANUFACTURER INSTALLATION MANUALS. INSTALLER SHALL INSTALL ALL EQUIPMENT IN ACCORDANCE WITH MANUFACTURER INSTALLATION MANUALS. NOTHING IN THIS DOCUMENT SHOULD BE INTERPRETED IN A WAY THAT OVERRIDES THE INSTRUCTIONS IN MANUFACTURER INSTALLATION MANUALS.PV-2BAIARDI RESIDENCE438 SE TRANQUILLA AVE PORT ST. LUCIE, FL 34983