HomeMy WebLinkAboutPHOTOVOLTAIC SYSTEM INSTALLATION5.51 KW
SYSTEM SIZE : 7.505KW DC STC
VICINITY MAP
SITE MAP (N.T.S)
A-01
SITE MAP &
VICINITY MAP
DEBRA PERKINS
NEW GRID-INTERACTIVE PHOTOVOLTAIC SYSTEM
DC SYSTEM SIZE ( 7.505KW)
33
0
0 PSF
170MPH (ASCE 7-16)
II
B
22.99 A
(19) ENPHASE IQ7PLUS-72-2-US
MICROINVERTERS
LOAD SIDE TAP IN THE MSP
WIND FLOW MAP
(1) BRANCH OF 10 MODULES
(1) BRANCH OF 09 MODULES
SHEET NUMBER
SHEET NAMEDESCRIPTIONREVREVISIONSDATEPERMIT DEVELOPER
OCS
12/02/2021
DESIGNER
REVIEWER
DATEDEBRA PERKINS2812 EAGLES NEST WAY, PORT ST LUCIE,FL 34952. USA.Signature with Seal
ADD : 7300 BRYAN DAIRY RD SUITE
400 SEMINOLE FL 33777, USA
CONTACT : 7275714141
LICENSE #AEC-07807
ENGG.DC RATING OF SYSTEM
AC RATING OF SYSTEM
AC OUTPUT CURRENT
NO. OF MODULES
NO. OF INVERTERS
POINT OF CONNECTION
ARRAY STRINGING
DESCRIPTION NEW GRID-INTERACTIVE PHOTOVOLTAIC
SYSTEM WITH NO BATTERY STORAGE
SYSTEM DETAILS
GOVERNING CODES
FLORIDA RESIDENTIAL CODE, 7TH EDITION 2020 (FRC)
FLORIDA BUILDING CODE, 7TH EDITION 2020 (FBC)
FLORIDA FIRE PREVENTION CODE, 7TH EDITION 2020 (FFPC)
NATIONAL ELECTRIC CODE, NEC 2017 CODE BOOK, NFPA 70
SITE MAP & VICINITY MAPA - 01
A - 02
S - 01
ELECTRICAL LINE DIAGRAM
WIRING CALCULATIONS
SYSTEM LABELING
MODULE DATASHEET
E - 01
E - 02
E - 03
STRUCTURAL ATTACHMENT DETAIL
INVERTER DATASHEET
COMBINER BOX DATASHEET
ATTACHMENT DATASHEET
DS - 01
DS - 02
DS - 04
DS - 05
S - 02
SHEET INDEX
SHEET NO.SHEET NAME
ROOF PLAN & MODULES
ARRAY LAYOUT
SITE DETAILS
ASHRAE EXTREME LOW
ASHRAE 2% HIGH
GROUND SNOW LOAD
WIND SPEED
RISK CATEGORY
WIND EXPOSURE CATEGORY
(19) HANWHA Q.PEAK DUO BLK ML-G10
(395W) MODULES
RACKING DATASHEETDS - 06 LAYOUT SUBJECT TO CHANGE
BASED ON SITE CONDITIONS
41.1"74"JUNCTION BOX DATASHEETDS - 03 97'-11"40'-6"1 3 '-6 "8'-3"95'-1"62'26'-2"6'-1"18'-1"5'-4"
DRIVEWAY M(E) METER MAIN COMBO
(OUTSIDE HOUSE) SSP(E) SUB SERVICE PANEL
(INSIDE HOUSE)
EAGLES NEST WAY
3' SETBACK
18" SETBACK
ROOF 1
PV ARRAY
ROOF 2
ROOF 3
A-02
& MODULES
ROOF PLAN
MODULE TYPE, DIMENSIONS & WEIGHT
SHEET NUMBER
SHEET NAMEDESCRIPTIONREVREVISIONSDATEPERMIT DEVELOPER
OCS
12/02/2021
DESIGNER
REVIEWER
DATEDEBRA PERKINS2812 EAGLES NEST WAY, PORT ST LUCIE,FL 34952. USA.Signature with Seal
ADD : 7300 BRYAN DAIRY RD SUITE
400 SEMINOLE FL 33777, USA
CONTACT : 7275714141
LICENSE #AEC-07807
ENGG.I CERTIFY THAT THE INSTALLATION OF THE MODULES IS IN
COMPLIANCE WITH FBC: RESIDENTIAL CHAPTER 3.BUILDING
STRUCTURE WILL SAFELY ACCOMMODATE LATERAL AND UPLIFT
WIND LOADS, AND EQUIPMENT DEAD LOADS. *
GENERAL INSTALLATION PLAN NOTES:
1) ROOF ATTACHMENTS TO TRUSSES SHALL BE INSTALLED
AS SHOWN IN SHEET S-01 AND AS FOLLOWS FOR EACH WIND
ZONE:.
WIND ZONE 1: MAX SPAN 4' O.C.
WIND ZONE 2: MAX SPAN 2' O.C.
WIND ZONE 3: MAX SPAN 2' O.C.
2) EXISTING RESIDENTIAL BUILDING ROOF WITH MEAN ROOF
HEIGHT 15 FT AND 2"X4" WOOD ROOF TRUSSES SPACED 24" O.C.
CONTRACTOR TO FIELD VERIFY AND SHALL REPORT TO THE
ENGINEER IF ANY DISCREPANCIES EXIST BETWEEN PLANS
AND IN FIELD CONDITIONS.
LEGENDS
UM
ACD
PM
MSP
- UTILITY METER
JB
- AC DISCONNECT
- PRODUCTION METER
- MAIN SERVICE PANEL
- VENT, ATTIC FAN
(ROOF OBSTRUCTION)
- JUNCTION BOX
CP - COMBINER PANEL
- CONDUIT
- MICROINVERTER
- FIRE SETBACK
NUMBER OF MODULES = 19 MODULES
MODULE TYPE = HANWHA Q.PEAK DUO BLK ML-G10 (395W) MODULES
WEIGHT = 48.5 LBS / 22 KG.
MODULE DIMENSIONS = 74" X 41.1" = 21.12 SF
NUMBER OF INVERTER = 19 MICROINVERTERS
INVERTER TYPE = ENPHASE IQ7PLUS-72-2-US MICROINVERTERS
DC SYSTEM SIZE: 7.505KW
AC SYSTEM SIZE: 5.51 KW
NOTES:
1. LOCATION OF JUNCTION BOX(ES), AC
DISCONNECTS(S), AC COMBINER PANEL(S), AND
OTHER ELECTRICAL EQUIPMENT(S) RELEVANT TO
PV INSTALLATION SUBJECT TO CHANGE BASED
ON SITE CONDITIONS.
2. SETBACKS AT RIDGES CAN BE REDUCED TO 18
INCHES IN COMPLIANCE WITH FBC R 324.6.2:
TOTAL PLAN VIEW AREA = 2640.18 SQFT
TOTAL PV AREA = 19(74 IN)(41.1 IN)/(144 IN^2)
= 401.3 SQFT
( 401.3 SQFT/ 2640.18 SQFT)100 = 15.2 %
TOTAL PV AREA POPULATES 15.2 % OF TOTAL
PLAN VIEW AREA AND IS WITHIN THE 33%
REQUIREMENT.
M - METER MAIN COMBOM(E) METER MAIN COMBO
(OUTSIDE HOUSE) SSP(E) SUB SERVICE PANEL
(INSIDE HOUSE)
3' SETBACK
18" SETBACK
ROOF 1
PV ARRAY
ROOF 2
ROOF 3 ACDCP(N) AC DISCONNECT
(N) COMBINER PANEL
(E) FRONT YARD
(E) BACK YARD
JB
CONDUIT RUN
ROOF ACCESS POINT
ROOF ACCESS POINT
ROOF ACCESS POINT
S-01
ARRAY
LAYOUT
ROOF DESCRIPTION:
SHEET NUMBER
SHEET NAMEDESCRIPTIONREVREVISIONSDATEPERMIT DEVELOPER
OCS
12/02/2021
DESIGNER
REVIEWER
DATEDEBRA PERKINS2812 EAGLES NEST WAY, PORT ST LUCIE,FL 34952. USA.Signature with Seal
ADD : 7300 BRYAN DAIRY RD SUITE
400 SEMINOLE FL 33777, USA
CONTACT : 7275714141
LICENSE #AEC-07807
ENGG.WIND LOAD INFORMATION:
THIS SYSTEM HAS BEEN DESIGN TO MEET
THE REQUIREMENTS OF THE 7TH EDITION OF
THE FLORIDA BUILDING CODE AND USED
THE FOLLOWING DESIGN PARAMETERS:
ULTIMATE WIND SPEED: 170 MPH
EXPOSURE CATEGORY: B
RISK CATEGORY: II
MEAN ROOF HEIGHT: 15 FEET
ROOF SLOPE: 7-20
LEGENDS
- VENT, ATTIC FAN
(ROOF OBSTRUCTION)
- PV ROOF ATTACHMENT
- RAFTERS / TRUSSES
- FIRE SETBACK
WIND ZONE 1
- WIND ZONE 1
- WIND ZONE 1'
WIND ZONE 2
- WIND ZONE (2)
- WIND ZONE (2r)
- WIND ZONE (2e)
- WIND ZONE (2n)
WIND ZONE 3
- WIND ZONE (3)
- WIND ZONE (3r)
- WIND ZONE (3e)
- RAIL
- METAL SEAM
(ROOF #1)
MODULES - 03
ROOF TILT - 12
ROOF AZIMUTH - 181
TRUSSES SIZE - 2"X4" @ 24" O.C.
(ROOF #3)
MODULES -08
ROOF TILT - 12
ROOF AZIMUTH - 271
TRUSSES SIZE - 2"X4" @ 24" O.C.
(ROOF #2)
MODULES - 08
ROOF TILT - 12
ROOF AZIMUTH - 91
TRUSSES SIZE - 2"X4" @ 24" O.C.
24'-2"8'-4"7'-5"10'-8"16'-3"50'-7"
22'-3"11'-5"1
4
'-
1
"
30'-6"
21'-8"15'-1"30'-6"12'-2"ROOF #1
ROOF #2
ROOF #3
18" SETBACK3' SETBACK
SOLAR MODULE
PHOTOVOLTAIC MODULE GENERAL NOTES:
1. APPLICABLE CODE: 2020 FLORIDA BUILDING CODE 7th ED. & ASCE 7-16
MINIMUM DESIGN LOADS FOR BUILDING AND OTHER STRUCTURES
2. BOLT DIAMETER AND EMBEDMENT LENGTHS ARE DESIGNED PER NDS(2012)
REQUIREMENTS. ALL BOLT CAPACITIES ARE BASED ON A
WOOD ROOF TRUSS AS EMBEDMENT MATERIAL.
3. ALL WIND DESIGN CRITERIA AND PARAMETERS ARE FOR HIP AND GABLE
MAXIMUM 6/12 PITCH) ROOF IN SCHEDULE. ALL RESIDENTIAL ROOFS SHALL NOT
EXCEED 30'-0" MEAN ROOF HEIGHT.
4. ROOF SEALANTS SHALL CONFORM TO ASTM C920 AND ASTM 6511.
5. THIS SHEET REFLECTS STRUCTURAL CONNECTIONS ONLY. REFER TO
MANUFACTURERS' MANUAL FOR ALL ARCHITECTURAL, MECHANICAL,
ELECTRICAL, AND SOLAR SPECS.
6. ALL ALUMINUM COMPONENTS SHALL BE ANODIZED ALUMINUM 6105-T5 UNLESS
OTHERWISE NOTED.
7. LAG BOLTS SHALL BE ASTM A276 STAINLESS STEEL UNLESS OTHERWISE NOTED.
8. ALL RAILING AND MODULES SHALL BE INSTALLED PER
MANUFACTURERS' INSTRUCTIONS.
9. I CERTIFY THAT THE INSTALLATION OF THE MODULES IS IN COMPLIANCE
WITH FBC:BUILDING CHAPTER 16 AND FBC:RESIDENTIAL CHAPTER 3.
BUILDING STRUCTURE WILL SAFELY ACCOMMODATE CALCULATED
WIND LATERAL AND UPLIFT FORCES, AND EQUIPMENT DEAD LOADS.
S-02
STRUCTURAL
ATTACHMENT
DETAILS
SHEET NUMBER
SHEET NAMEDESCRIPTIONREVREVISIONSDATEPERMIT DEVELOPER
OCS
12/02/2021
DESIGNER
REVIEWER
DATEDEBRA PERKINS2812 EAGLES NEST WAY, PORT ST LUCIE,FL 34952. USA.Signature with Seal
ADD : 7300 BRYAN DAIRY RD SUITE
400 SEMINOLE FL 33777, USA
CONTACT : 7275714141
LICENSE #AEC-07807
ENGG.BOM
ROOF TECH MINI II: 65
Q RAIL LIGHT:14
Q MOUNT END CLAMP:24
Q MOUNT MID CLAMP:26
Q MOUNT GROUND LUG :6
HANWHA Q.PEAK DUO BLK ML-G10 (395W): 19
ENPHASE IQ7PLUS-72-2-US: 19
60A FUSED AC DISCONNECT: 1
STRUCTURAL DETAILS
L FOOT
ROOF TECH MINI II
USE TWO 5/60 MM
MOUNTING SCREWS TO
ATTACH EACH RT-MINI II TO
THE RAFTERS.
5/16"x1" STAINLESS
STEEL HEX BOLT
ROOF TRUSS
RAILMODULE CLAMP PV MODULE
MINIMUM 7/16" OSB OR PLYWOOD
NOTE:
1. SUBJECT PV SYSTEMS HAS BEEN DESIGNED TO MEET THE
REQUIREMENTS OF THE NEC 2017, NFPA 70 AND THOSE SET FORTH BY
THE FLORIDA SOLAR ENERGY CENTER CERTIFICATION, INCLUDING
MAXIMUM NUMBER OF MODULE STRINGS, MAXIMUM NUMBER OF
MODULES PER STRING, MAXIMUM OUTPUT, MODULE MANUFACTURER
AND MODEL NUMBER, INVERTER MANUFACTURER AND MODEL
NUMBER, AS APPLICABLE.
2. PROVIDE TAP BOX IN COMPLIANCE WITH 312.8 IF PANEL GUTTER
SPACE IS INADEQUATE.
E-01
SINGLE
LINE DIAGRAM
SHEET NUMBER
SHEET NAMEDESCRIPTIONREVREVISIONSDATEPERMIT DEVELOPER
OCS
12/02/2021
DESIGNER
REVIEWER
DATEDEBRA PERKINS2812 EAGLES NEST WAY, PORT ST LUCIE,FL 34952. USA.Signature with Seal
ADD : 7300 BRYAN DAIRY RD SUITE
400 SEMINOLE FL 33777, USA
CONTACT : 7275714141
LICENSE #AEC-07807
ENGG.SOLAR ARRAY ( 7.505KW-DC STC)
(19) HANWHA Q.PEAK DUO BLK ML-G10 (395W) MODULES
(1) BRANCH OF 10 MODULES.
(1) BRANCH OF 09 MODULES
INVERTER SPECIFICATIONS
MANUFACTURER ENPHASE
MODEL NO.IQ7PLUS-72-2-US
MAX DC INPUT VOLTAGE 60 V
MAX OUTPUT POWER 290 VA
NOMINAL AC OUTPUT VOLTAGE 240 V
NOMINAL AC OUTPUT CURRENT 1.21 A
MODULE SPECIFICATION
MODEL NO.
HANWHA Q.PEAK
DUO BLK ML-G10
(395W)
PEAK POWER 395W
RATED VOLTAGE (Vmpp)36.88 V
RATED CURRENT (Impp)10.71 A
OPEN CIRCUIT VOLTAGE (Voc)45.27 V
SHORT CIRCUIT CURRENT (Isc)11.10A
G
(N) JUNCTION
BOX
1 STRING OF
10 MODULES WITH
MICROINVERTERS
1 STRING OF
09 MODULES WITH
MICROINVERTERS 20A/2P
20A/2P
G
(N) IQ AC
ENVOY IQ
15A/2P
COMBINER PANEL
(2) # AWG THWN-2 - L1
(2) # AWG THWN-2 - L2
(1) # AWG THWN-2 GND
IN 3/4" IMC, RMC, FMC, LFMC,
PVC, HDPE, NUCC, RTRC,
LFNC, FMT, ENT OR EMT
CONDUIT RUN
ENPHASE
Q CABLES
#6 BARE COPPER GND
(E) 200A
120/240V
PANEL
SUB SERVICE
FUSED
DISCONNECT
(N) 60A AC
G
NG
302P
(E) 200A
(3) #10 AWG THWN-2
(1) #10 AWG THWN-2 GND
IN 3/4" IMC, RMC, FMC, LFMC,
PVC, HDPE, NUCC, RTRC,
LFNC, FMT, ENT OR EMT
CONDUIT RUN
LOAD SIDE TAP
NEC 705312(B)(2)(1)(b)
N
(E) 200A
NG
UM
N
120/240V
PANEL
MAIN SERVICE
(E) 200A
(3) #10 AWG THWN-2
(1) #10 AWG THWN-2 GND
IN 3/4" IMC, RMC, FMC, LFMC,
PVC, HDPE, NUCC, RTRC,
LFNC, FMT, ENT OR EMT
CONDUIT RUN
ELECTRICAL NOTES
1. ALL EQUIPMENT TO BE LISTED BY UL OR OTHER NRTL, AND
LABELED FOR ITS APPLICATION.
2. ALL CONDUCTORS SHALL BE COPPER, RATED FOR 600 V AND 90
DEGREE C WET ENVIRONMENT.THE TERMINALS ARE RATED FOR
75 DEGREE C.
3. CONDUCTOR TERMINATION AND SPLICING AS PER NEC 110.14
4. WIRING, CONDUIT, AND RACEWAYS MOUNTED ON ROOFTOPS
SHALL BE ROUTED DIRECTLY TO, AND LOCATED AS CLOSE AS
POSSIBLE TO THE NEAREST RIDGE, HIP, OR VALLEY.
5. WORKING CLEARANCES AROUND ALL NEW AND EXISTING
ELECTRICAL EQUIPMENT SHALL COMPLY WITH NEC 110.26.
6. DRAWINGS INDICATE THE GENERAL ARRANGEMENT OF SYSTEMS.
CONTRACTOR SHALL FURNISH ALL NECESSARY OUTLETS,
SUPPORTS, FITTINGS AND ACCESSORIES TO FULFILL APPLICABLE
CODES AND STANDARDS.
7. WHERE SIZES OF JUNCTION BOXES, RACEWAYS, AND CONDUITS
ARE NOT SPECIFIED, THE CONTRACTOR SHALL SIZE THEM
ACCORDINGLY.
8. ALL WIRE TERMINATIONS SHALL BE APPROPRIATELY LABELED
AND READILY VISIBLE.
9. MODULE GROUNDING CLIPS TO BE INSTALLED BETWEEN MODULE
FRAME AND MODULE SUPPORT RAIL, PER THE GROUNDING CLIP
MANUFACTURER'S INSTRUCTION.
10. MODULE SUPPORT RAIL TO BE BONDED TO CONTINUOUS COPPER
G.E.C. VIA WEEB LUG OR ILSCO GBL-4DBT LAY-IN LUG.
11. THE POLARITY OF THE GROUNDED CONDUCTORS IS NEGATIVE .
12. UTILITY HAS 24-HR UNRESTRICTED ACCESS TO ALL
PHOTOVOLTAIC SYSTEM COMPONENTS LOCATED AT THE SERVICE
ENTRANCE.
13. MODULES CONFORM TO AND ARE LISTED UNDER UL 1703.
14. RACKING CONFORMS TO AND IS LISTED UNDER UL 2703.
15. CONDUCTORS EXPOSED TO SUNLIGHT SHALL BE LISTED AS
SUNLIGHT RESISTANT PER NEC ARTICLE 300.6 (C) (1) AND ARTICLE
310.10 (D).
16. CONDUCTORS EXPOSED TO WET LOCATIONS SHALL BE SUITABLE
FOR USE IN WET LOCATIONS PER NEC ARTICLE 310.10 (C).
E-02
WIRING
CALCULATIONS
MAX VOLTAGE DROP CALCULATION
CABLE SIZE CABLE DESCRIPTION
ONE WAY
DISTANCE IN
FEET (D)
BRANCH
CURRENT (I)
RESISTANCE OF
CONDUCTOR(R)VOLTAGE (V)% VOLTAGE
DROP=(0.2*D*I*R)/V
#10 THWN-2 JUNCTION BOX TO
COMBINER PANEL 20 22.99 1.24 240 0.48
SHEET NUMBER
SHEET NAMEDESCRIPTIONREVREVISIONSDATEPERMIT DEVELOPER
OCS
12/02/2021
DESIGNER
REVIEWER
DATEDEBRA PERKINS2812 EAGLES NEST WAY, PORT ST LUCIE,FL 34952. USA.Signature with Seal
ADD : 7300 BRYAN DAIRY RD SUITE
400 SEMINOLE FL 33777, USA
CONTACT : 7275714141
LICENSE #AEC-07807
ENGG.
WARNING
ELECTRIC SHOCK HAZARD
!
DO NOT TOUCH TERMINALS
TERMINALS ON BOTH LINE AND
LOAD SIDES MAY BE ENERGIZED
IN THE OPEN POSITION
PHOTOVOLTAIC SYSTEM AC DISCONNECT
RATED AC OPERATING CURRENT 22.99 AMPS
AC NOMINAL OPERATING VOLTAGE 240 VOLTS
WARNING
INVERTER OUTPUT CONNECTION DO NOT
RELOCATE THIS OVERCURRENT DEVICE
PHOTOVOLTAIC SYSTEM
EQUIPPED WITH RAPID
E-03
WARNING DUAL POWER SOURCE
SECOND SOURCE IS PHOTOVOLTAIC SYSTEM
WARNING PHOTOVOLTAIC
POWER SOURCE
!
727-571-4141
EMERGENCY CONTACT
WARNING!
INVERTER OUTPUT CONNECTION
DO NOT RELOCATE THIS
OVERCURRENT DEVICE
WARNING!
DEDICATED SOLAR PANELS DO
NOT CONNECT ANY OTHER LOADSSHUTDOWN
SOLAR PV SYSTEM EQUIPPED
WITH RAPID SHUTDOWN
SHEET NUMBER
SHEET NAMEDESCRIPTIONREVREVISIONSDATEPERMIT DEVELOPER
OCS
12/02/2021
DESIGNER
REVIEWER
DATEDEBRA PERKINS2812 EAGLES NEST WAY, PORT ST LUCIE,FL 34952. USA.Signature with Seal
ADD : 7300 BRYAN DAIRY RD SUITE
400 SEMINOLE FL 33777, USA
CONTACT : 7275714141
LICENSE #AEC-07807
ENGG.SYSTEM
LABELING
LABEL LOCATION:
AC DISCONNECT, POINT OF INTERCONNECTION,
COMBINER PANEL
(PER CODE: NEC 690.13(B))
LABEL LOCATION:
AC DISCONNECT, INVERTER
(PER CODE: NEC 690.54)
LABEL LOCATION:
CONDUIT RUNWAY
(PER CODE: NEC690.31(G)(3)(4))
LABEL LOCATION:
MAIN SERVICE DISCONNECT
(NEC 705.12(B)(3-4) & NEC 690.59)
ADHESIVE FASTENED SIGNS:
GUIDELINES FOR SUITABLE FONT SIZES, WORDS, COLORS, SYMBOLS, AND
LOCATION REQUIREMENTS FOR LABELS. NEC 110.21(B)(1)
ENVIRONMENT INVOLVED. NEC 110.21(B)(3)
ADHERED. VINYL SIGNS SHALL BE WEATHER RESISTANT. IFC 605.11.1.3
LABEL LOCATION:
COMBINER PANEL, AC DISCONNECT
(PER CODE: NEC 690.52)
LABEL LOCATION:
POINT OF INTERCONNECTION, MAIN SERVICE DISCONNECT
(PER CODE: NEC 705.12 (B)(2)(c))
[Not required if panelboard is rated not less than sum of ampere ratings
of all overcurrent devices supplying it]
DATA PER PANEL
LABEL LOCATION:
AC DISCONNECT, DC DISCONNECT, POINT OF
INTERCONNECTION
(PER CODE: NEC 690.56(C)(3))
IFC 605.11.3.1(1) & 690.56(C)(1)(a) Label for PV Systems that
Shut down the array and the conductors leaving the array
NOMINAL OPERATING AC VOLTAGE -
NOMINAL OPERATING AC FREQUENCY-
MAXIMUM AC POWER-
MAXIMUM AC CURRENT-
MAXIMUM OVERCURRENT DEVICE RATING
FOR AC MODULE PROTECTION PER CIRCUIT-
240
290
1.21
20
V
VA
60 Hz
A
A
DS-01
DATASHEET
MODULE
SHEET NUMBER
SHEET NAME
PERMIT DEVELOPER
OCS
12/02/2021
DESIGNER
REVIEWER
DATE
Signature with Seal
ADD : 7300 BRYAN DAIRY RD SUITE
400 SEMINOLE FL 33777, USA
CONTACT : 7275714141
LICENSE #AEC-07807
DS-02
DATASHEET
INVERTER
SHEET NUMBER
SHEET NAME
PERMIT DEVELOPER
OCS
12/02/2021
DESIGNER
REVIEWER
DATE
Signature with Seal
ADD : 7300 BRYAN DAIRY RD SUITE
400 SEMINOLE FL 33777, USA
CONTACT : 7275714141
LICENSE #AEC-07807
DS-03
DATASHEET
MODULE
SHEET NUMBER
SHEET NAME
PERMIT DEVELOPER
OCS
12/02/2021
DESIGNER
REVIEWER
DATE
Signature with Seal
ADD : 7300 BRYAN DAIRY RD SUITE
400 SEMINOLE FL 33777, USA
CONTACT : 7275714141
LICENSE #AEC-07807
DS-04
DATASHEET
COMBINER BOX
SHEET NUMBER
SHEET NAME
PERMIT DEVELOPER
OCS
12/02/2021
DESIGNER
REVIEWER
DATE
Signature with Seal
ADD : 7300 BRYAN DAIRY RD SUITE
400 SEMINOLE FL 33777, USA
CONTACT : 7275714141
LICENSE #AEC-07807
DS-05
DATASHEET
ATTACHMENT
SHEET NUMBER
SHEET NAME
PERMIT DEVELOPER
OCS
12/02/2021
DESIGNER
REVIEWER
DATE
Signature with Seal
ADD : 7300 BRYAN DAIRY RD SUITE
400 SEMINOLE FL 33777, USA
CONTACT : 7275714141
LICENSE #AEC-07807
DS-06
DATASHEET
RACKING
SHEET NUMBER
SHEET NAME
PERMIT DEVELOPER
OCS
12/02/2021
DESIGNER
REVIEWER
DATE
Signature with Seal
ADD : 7300 BRYAN DAIRY RD SUITE
400 SEMINOLE FL 33777, USA
CONTACT : 7275714141
LICENSE #AEC-07807