HomeMy WebLinkAboutFIRE ALARM PLANJ i G F I i C B A 7 1. SCOPE OF WORK: e A. 11 GENERAL: EXPAND EXISTING SILENT KNIGHT FIRE ALARM SYSTEM TO PROVIDE FIRE SAFETY FUNCTIONS AND NOTIFICATION AT THE NEW BUILDING. B. FURNISH, INSTALL AND PROGRAM ALL MATERIAL, LABOR, DOCUMENTATION AND TESTING REQUIRED TO PROVIDE A FULLY - FUNCTIONAL, CODE -COMPLIANT OPERATIONAL SYSTEM. C. PERFORM INITIAL ACCEPTANCE TESTING ON NEW COMPONENTS AND RE -ACCEPTANCE TESTING OF EXISTING COMPONENTS. D. PREPARE NEW (OR AMEND EXISTING) OPERATION AND MAINTENANCE MANUAL FOR OWNER FOR EXPANDED SYSTEM. INSTRUCT OWNER'S PERSONNEL ON SYSTEM OPERATION. E. PROVIDE FIRE WATCH WHEN THE FIRE ALARM SYSTEM FUNCTION IS IMPAIRED FOR FOUR HOURS OR LONGER. F. INSTALL IN ACCORDANCE WITH APPLICABLE CODES (LISTED BELOW), NFPA 72, NFPA 70, AND THE CONTRACT DOCUMENTS. 7 G. COORDINATE WITH ALL BUILDING SYSTEMS, INCLUDING MECHANICAL/HVAC, ELECTRICAL, LIGHTING AND FIRE PROTECTION H. PROVIDE UNDERGROUND RACEWAYS AND CONNECTION TO EXISTING BUILDING A. 2. THE CONTENT OF THESE DRAWINGS IS BASED UPON RECORD DRAWINGS THAT HAVE BEEN FURNISHED TO THE EOR. THE FOR IS UNABLE TO VERIFY THE ACCURACY OF EXISTING, CONCEALED, - ENCLOSED, BURIED OR PROGRAMMED COMPONENTS. THE CONTRACTOR SHALL REPORT DISCREPANCIES DISCOVERED DURING THE WORK TO THE FOR IN A TIMELY MANNER SO AS NOT TO UNDULY IMPEDE PROGRESS OF THIS WORK OR OTHER SCOPES OF WORK CURRENTLY OCCURRING OR PLANNED TO OCCUR IN THE BUILDING. 6 FLORIDA 61G15 COMPLIANCE 1. THIS PROJECT'S SCOPE IS TO EXPAND THE EXISTING SILENT KNIGHT 5808 FIRE ALARM SYSTEM TO SYSTEM TO PROVIDE FIRE SAFETY FUNCTIONS AT THE EXPANDED BUILDING. 2. ADDRESS: AS SHOWN IN TITLEBLOCK 3. AHJ: CITY OF FT. PIERCE, FL 4. ENGINEER OF RECORD: GREG TABAKA, PE #73972 5. PRIMARY OCCUPANCY: GROUP F-1 FACTORY (FBC)/INDUSTRIAL (FFPC) 6. OTHER OCCUPANCIES: GROUPS B AND A-2 (FBC)/EXISTING 13USINESS AND EXISTING ASSEMBLY < 300 PERSONS (FFPC); GROUP S-1 (FBC)/ STORAGE (FFPC) 7. MONITORING: EXISTING TO REMAIN 8. CABLING AND SUPERVISION REQUIREMENTS. UNLESS NOTED OTHERWISE, THE FOLLOWING MINIMUM (AND OPTIONAL) WIRING 5 CLASSES ARE REQUIRED: A. IDC: CLASS B (OPTIONAL: A) B. SLC: CLASS B (OPTIONAL: A, X). C. NAC: CLASS B (OPTIONAL: A) D. AUXILIARY POWER: CLASS E E. ALL NEW CIRCUITS TO BE FREE -WIRED AND/OR ENCLOSED IN EMT ABOVEGROUND OR EXISTING EMT/UNDERGROUND RACEWAYS; BELOWGROUND IN PVC RACEWAYS. LIMITED USE OF FLEXIBLE METAL CONDUIT (FMC) AND METAL CLAD (MC) CABLE IS PERMITTED. 9. ADDRESSABLE: YES 10. CLASSIFICATION: PROTECTED PREMISES FIRE ALARM 11. INITIATING DEVICE ZONING: NONE 12. EVACUATION ZONING: NONE (GENERAL EVAC) 13. CAMPUS WIRING: ONE ADDRESSABLE DATA CIRCUIT (SLC) WITH FOUR BRANCHES WILL BE EXPANDED TO A FIFTH BRANCH SERVING THE 4 EXPANSION. EXISTING CIRCUITS WILL BE EXPANDED TO SERVE NEW DEVICES. 14. OPERATIONS AND MAINTENANCE PROCEDURES, MANUALS, SYSTEM DOCUMENTATION AND INSTRUCTION OF OWNER'S PERSONNEL TO BE DEVELOPED AND FURNISHED BY INSTALLING CONTRACTOR. 15. SYSTEM TEST REQUIREMENTS: COMPLY WITH NFPA 72 CH. 14 FOR INITIAL, RE -ACCEPTANCE AND PERIODIC TESTING. 16. SEE SHEET FA-400 FOR SEQUENCE OF OPERATIONS - CODE COMPLIANCE THIS SYSTEM HAS BEEN DESIGNED ACCORDING TO THE PRESCRIPTIVE REQUIREMENTS OF: 3 1. NFPA 72, NATIONAL FIRE ALARM AND SIGNALING CODE, 2016 EDITION 2. FLORIDA BUILDING CODE (FBC), 7T" EDITION 3. FLORIDA FIRE PREVENTION CODE (FFPC), 7T" EDITION 4. FLORIDA ELECTRICAL CODE (FEC), 2018 EDITION 5. NFPA 70, NATIONAL ELECTRICAL CODE (NEC), 2017 EDITION 6. AMERICANS WITH DISABILITIES ACT (ADA) 7. FLORIDA ACCESSIBILITY CODE (FAC), 7T" EDITION 8. FLORIDA 61G15-32.008 REVISED JULY 25, 2019 PERSONNEL REQURREMENTS AND CERTIFICATIONS 1. INSTALLATION PERSONNEL SHALL BE SUPERVISED BY PERSONS WHO ARE QUALIFIED AND EXPERIENCED IN THE INSTALLATION, INSPECTION, AND TESTING OF FIRE ALARM SYSTEMS, EXAMPLES OF QUALIFIED 2 PERSONNEL SHALL INCLUDE, BUT NOT BE LIMITED TO THE FOLLOWING: 1) FACTORY TRAINED AND CERTIFIED PERSONNEL, 2) NATIONAL I INSTITUTE OF CERTIFICATION IN ENGINEERING TECHNOLOGIES (NICET) FIRE ALARM LEVEL II OR HIGHER CERTIFIED PERSONNEL, AND 3) PERSONNEL LICENSED OR CERTIFIED BY STATE OR LOCAL AUTHORITY, PER NFPA 72. COPIES OF CERTIFICATION CARDS OF TECHNICIANS SHALL BE FURNISHED TO OWNER'S REPRESENTATIVE. 2. A COPY OF ALL SOFTWARE DOCUMENTATION SHALL BE MAINTAINED - I ON THE CONSTRUCTION SITE IN A BINDER, ARRANGED IN CHRONOLOGICAL ORDER. THIS BINDER SHALL BE TURNED OVER TO OWNER AFTER ALL START UP, TESTING, COMMISSIONING, PROGRAMMING AND DEMONSTRATIONS ARE COMPLETED. 3. ONCE THE FIRE ALARM SYSTEM IS PUT INTO SERVICE, IN WHOLE OR IN PART, NO SOFTWARE CHANGES SHALL BE PERFORMED WITHOUT WRITTEN CONSENT OF OWNER. IF SOFTWARE CHANGES ARE NEEDED, 1 THEY SHALL BE PERFORMED BY CERTIFIED MANUFAC rURER'S TECHNICIANS. 4. PROVIDE THE SERVICES OF THE INSTALLER'S SUPERVISOR OR PERSON WITH EQUIVALENT QUALIFICATIONS TO SUPERVISE INSPECTION AND TESTING, CORRECTION, AND ADJUSTMENTS. MATERIALS AND INSTALLATION REQUIREMENTS 1. ALL EQUIPMENT CONSTRUCTED AND INSTALLED IN CONFORMITY WITH THESE DESIGN DOCUMENTS SHALL BE LISTED FOR THE PURPOSE FOR WHICH IT IS USED AND SHALL BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURERS' INSTALLATION INSTRUCTIONS, APPLICABLE STANDARDS AND DESIGN DOCUMENTS. 2. ALL NEW COMPONENTS SHALL BE FM APPROVED OR UL LISTED FOR THEIR INTENDED USAGE. 3. ALL NEW FIRE ALARM COMPONENTS SHALL BE BY A SINGLE MANUFACTURER, EXCEPT THAT SURGE SUPPRESSION, FITTINGS, WIRING AND WIREWAYS MAY VARY. 4. SURGE SUPPRESSION A. SURGE SUPPRESSION SHALL BE INSTALLED TO SERVE ALL NEW FRCP, FARP AND NAC BOOSTER UNITS. SURGE SUPPRESSORS SHALL NOT BE MOUNTED ON FIRE ALARM PANEL ENCLOSURES. B. ANY CONDUCTORS ENTERING OR EXITING THE BUILDING SHALL BE PROTECTED BY APPROVED, LISTED SURGE PROTECTION DEVICES AND INSTALLED ACCORDING TO THE SURGE PROTECTION DETAIL. 5. MOUNTING LOCATIONS A. WHERE HORNS (SPEAKERS) AND COMBINATION HORN/STROBE (SPEAKER/STROBE) APPLIANCES ARE INSTALLED IN THE SAME ROOM, THEY SHALL BE MOUNTED AT THE SAME ELEVATION WITH RESPECT TO THE FINISHED FLOOR WHERE NFPA 72 §7.4.7 AND § 7.5.4 MOUNTING REQUIREMENTS HEIGHTS CAN BE SATISFIED. B. ALL FIRE ALARM SYSTEM DEVICES MUST BE COORDINATED AND INSTALLED SO AS TO BE SAFELY ACCESSIBLE FOR TESTING, INSPECTION AND MAINTENANCE. C. OBTAIN OWNER'S APPROVAL OF LOCATIONS OF DEVICES BEFORE INSTALLATION. D. PROVIDE SEMI -FLUSH MOUNTED FIRE ALARM CONTROL PANEL WHERE INSTALLED IN FINISHED AREAS; IN UNFINISHED AREAS, SURFACE MOUNTED UNITS ARE ACCEPTABLE. ENCLOSURE PAINTED WITH A CORROSION PROTECTIVE, HARDENED FINISH. DO NOT FLUSH -MOUNT IN FIRE-RESITANCE RATED WALLS. E. NO SMOKE SENSORS SHALL BE LOCATED WITHIN 60 INCHES OF ANY SUPPLY OR RETURN AIR DUCTS. 6. RACEWAYS AND JUNCTION BOXES A. ELECTRICAL METALLIC TUBING (EMT) SHALL BE A MINIMUM TRADE SIZE OF 3/4 INCH, NO RACEWAY MAY EXCEED 40% FILL. PROVIDE SUPPORT IN ACCORDANCE WITH APPLICABLE CODE. FOR DRY LOCATIONS NOT SUBJECT TO PHYSICAL DAMAGE: FLEXIBLE METAL CONDUIT (FMC) OR METAL CLAD (MC) CABLE WITHOUT AN OVERALL NONMETALLIC COATING MAY BE USED FOR FINAL CONNECTION WITHIN DUCTS, AIR HANDLING SPACES (PLENUMS) AND TO FIELD DEVICES. MAXIMUM LENGTH OF FLEX/MC CABLE SHALL NOT EXCEED 6 FT WITHOUT ENGINEERING APPROVAL. B. UNDERGROUND RACEWAYS SHALL BE PVC AND NO LESS THAN 1" SIZE. MINIMUM BURIAL COVER SHALL BE NO LESS THAN 24 INCHES AND IN COMPLIANCE WITH NFPA 70 §300.5. C. CONTRACTOR SHALL DOCUMENT ALL CONDUIT & JUNCTION BOXES 'AS -BUILT' WITH PIPE SIZE & CONTENTS ON THE RECORD DRAWINGS TURNED OVER AT THE END OF THE PROJECT. D. NEW CONDUIT SYSTEM J-BOX COVERS ARE TO BE PAINTED RED & PERMANENTLY LABELED ON BOTH SIDES (INTERIOR AND EXTERIOR) AS "FIRE ALARM SYSTEM". ALL NEW AND EXISTING CONDUITS LEAVING FACP ARE TO BE PERMANENTLY LABELED WITH THEIR DESTINATION & CONTENTS. E. CONCEAL ALL WIRING, CONDUIT, BOXES, AND SUPPORTS WHERE INSTALLED IN FINISHED AREAS. F. ALL FIRE ALARM CONDUITS SHALL BE ROUTED SO AS NOT TO OBSTRUCT THE EGRESS PATHWAYS OR MECHANICAL EQUIPMENT CLEARANCE. G. ALL CONDUITS IN COLD STORAGE AREAS, OR THAT PASS FROM THE INTERIOR TO THE EXTERIOR OF THE BUILDING, SHALL BE SEALED TO STOP CONDENSATION AS REQUIRED BY NFPA 70 760,3(H) AND 300.7. APPROVED MATERIALS INCLUDE REFRIGERATION PUTTY, POLYWATER DUCT SEALANT, DUCT SEAL PUTTY, OR EQUAL. H. CONDUITS SHALL NOT ENTER THE CONTROL PANEL OR ANY OTHER COMPONENT PROVIDED EXCEPT WHERE ENTRY IS SPECIFIED BY THE MANUFACTURER. I. CONDUIT ENTRY ON ALL EXTERIOR AND/OR WEATHERPROOF DEVICES SHALL ONLY BE MADE FROM THE BOTTOM OF THE BOX. J. PROVIDE BUSHINGS AT ALL CONDUIT/EMT ENTRIES INTO ENCLOSURES. 7. FREE WIRING A. COMPLY WITH NFPA 70 §760.135. PROVIDE LISTED FPLP (OR CMP) CABLE UNLESS NOTED OTHERWISE, BELOW. LOCATE TO PROVIDE MAXIMUM PROTECTION AGAINST PHYISCAL DAMAGE. WHERE LOCATED EXPOSED WITHIN 7 FT OF THE FLOOR, OR PASSING THROUGH A WALL WITHIN 7 FT: INSTALL WITHIN EMT. B, DUCTS FOR ENVIRONMENTAL AIR: FPLP (OR CMP). C. RISERS PENETRATING ONE OR MORE FLOORS: MAY USE FPLP/FPLR (CMP/CMR) OR FPL/FPLR/FPLP (CM/CMR/CMP) IN EMT. PROVIDE LISTED FIRESTOP ASSEMBLIES AT EACH FLOOR OR SHAFTWALL PENETRATION, D. SPACES NOT USED FOR ENVIRONMENTAL AIR: MAY USE FPL/FPLR/FPLP (OR CM/CMR/CMP). 8. PENETRATIONS A. ALL PENETRATIONS THROUGH FIRE/SMOKE PARTITIONS SHALL BE PROVIDED WITH APPROVED FIRESTOPPING, INSTALLED IN ACCORDANCE WITH A UL LISTED ASSEMBLY, B. SEAL NEW PENETRATIONS IN FIRE RESISTANCE RATED ASSEMBLIES WITH LISTED SEALANT SYSTEMS. MINIMUM F-RATING IS 2 HOURS IN STAIRS & ELEVATOR HOISTWAYS/MACHINERY SPACES, THROUGH FLOORS OR THROUGH ROOFS; 1 HOUR ELSEWHERE. PROVIDE LEAKAGE RATED (L-RATED) SEALANT. FLOOR PENETRATIONS SHALL BE T-RATED EQUAL (OR SUPERIOR) TO THE F-RATING. PENETRATIONS OF CORRIDOR WALLS AND STAIR ENCLOSURES SHALL BE SEALED BY SYSTEMS HAVING A L-RATING OF NOT MORE THAN 5.0 CFM/SF OF PENETRATION OPENING AT 0.30 INCH (WATER GAUGE). 9. PRIMARY POWER - PROVIDE 120-VAC POWER AT 60-HZ FROM A DEDICATED BRANCH CIRCUIT, IN ACCORDANCE WITH NFPA 70 AND NFPA 72. ALL FARP, NAC EXPANDER AND FACP UNITS IN THIS SCOPE OF WORK SHALL BE PROVIDED WITH 120 VAC POWER SUPPLIED FROM AN APPROVED POWER SOURCE ON DEDICATED CIRCUITS THAT DO NOT SERVE OTHER FUNCTIONS. MARKED CIRCUIT BREAKERS LOCK- ONS SHALL BE INSTALLED TO PREVENT INADVERTENT DISCONNECTION OF THIS EQUIPMENT AND RED IN COLOR. MATERIALS AND INSTALLATION REQUIREMENTS (CONTINUED) 10. SECONDARY POWER - PROVIDE BATTERY BACKUP FOR 24 HR OF STANDBY FOLLOWED BY FIVE MINUTES (0,0833 HR) OF ALARM. 11. VOICE SYSTEMS A, EVERY SPEAKER CIRCUIT AND AMPLIFIER SHALL BE SIZED TO PROVIDE 25% SPARE CAPACITY OR GREATER WITH RESPECT TO POWER OUTPUT. FOR CALCULATION, ALL SPEAKERS SHALL BE CALCULATED TAPPED NOT LESS THAN SHOWN OR: 2 WATTS IN LARGE MECHANICALL/ELECTRICAL SPACES, 1 WATT IN ASSEMBLY AREAS AND Yz WATT ELSEWHERE. B. CONTRACTOR SHALL PROVIDE, INSTALL AND PROGRAM A MINIMUM OF ONE BACK-UP AMPLIFIER THAT WILL AUTOMATICALLY BECOME ACTIVE WHEN A PRIMARY AMPLIFIER REPORTS FAILURE AS DESCRIBED IN NFPA 72 AAA.7.2.1 12. CALCULATIONS A. BATTERY CALCULATIONS SHALL ASSUME A STARTING VOLTAGE NOT GREATER THAN 20.4 VOLTS. B. VOLTAGE DROP CALCULATIONS SHALL UTILIZE THE MAXIMUM CURRENT FOR EACH DEVICE AT ITS INDICATED OUTPUT. 13, LABELING - PROVIDE LEGIBLE, PERMANENT LABELS FOR EACH CONTROL DEVICE, USING IDENTIFICATION USED IN OPERATION AND MAINTENANCE DATA. 14. WIRING A. ALL CABLE RUNS SHALL BE CONTINUOUS BETWEEN DEVICES, WITHOUT SPLICES, WHEREVER FEASIBLE. ALL OTHER CONNECTIONS SHALL BE TO TERMINAL BLOCKS. WIRE NUTS SHAI''_L NOT BE PERMITTED. WIRES CONNECTED TOGETHER SHALL HAVE THE SAME COLOR INSULATION. ALL CONNECTIONS SHALL BE ACCESSIBLE FOR INSPECTION AND SERVICING AND SHALL BE CLEARLY IDENTIFIED ON THE RECORD DRAWINGS. B. CONDUCTOR SIZE SHALL NOT BE LESS THAN 18 AWG FOR INITIATING DEVICES OR SIGNALING LINE CIRCUITS AND 14 AWG FOR NOTIFICATION APPLIANCE CIRCUITS. C. NEW WIRING IN WET LOCATIONS, INCLUDING UNDERGROUND, SHALL BE WET -RATED WIRE, D. WIRES INSTALLED OR RECONNECTED UNDER THIS SCOPE OF WORK SHALL BE CLEARLY LABELED FOR FUNCTIONALITY AND ZONING. E. WHERE EXISTING CIRCUITS ARE EXTENDED, EXTENSIONS SHALL MATCH EXISTING IN WIRE TYPE, GAUGE, INSULATION COLOR AND OUTER JACKET COLOR. 15. BATTERIES A. BATTERIES SERVING NEW COMPONENTS SHALL BE NEW. DEMOLISHED OLD BATTERIES SHALL BE RECYCLED BY THE CONTRACTOR. B. BATTERIES SHALL BE LEGIBLY AND PERMANENTLY DATED AT TIME OF INSTALLATION. 16. STROBE SYNCRONIZATION - TWO OR MORE STROBES VISIBLE WITHIN THE SAME FIELD OF VIEW SHALL BE SYNCHRONIZED. (NOT APPLICABLE TO SINGLE STROBES USED FOR FIRE SPRINKLER FLOW ANNUNCIATION). 17. COORDINATION A, CONTRACTOR SHALT_ COORDINATE WIRE PLACEMENT COMPATIBILITY REQUIREMENTS FOR CONDUCTORS THAT SHARE RACEWAYS OR ENCLOSURES. WIRES THAT ARE INCOMPATIBLE WITH EACH OTHER DUE TO ELECTROMAGNETIC INTERFERENCE OR OTHER REASONS SHALL BE APPROPRIATELY SEPARATED TO ELIMINATE OR REDUCE INCOMPATIBILITY TO MANUFACTURER - SPECIFIED LEVELS. B. CONTRACTOR SHALL COORDINATE WORK WITH THE OWNER AND OTHER CONTRACTORS ON SITE TO MINIMIZE DISRUPTION TO OPERATIONS. WHERE FIRE ALARM COMPONENTS ARE OUT OF SERVICE FOR FOUR HOURS OR MORE, CONTRACTOR SHALL NOTIFY THE AHJ AND PROVIDE FIRE WATCH. INSPECTION AND TESTING REQUIREMENTS 1. THE FIRE ALARM SYSTEM SHALL BE TESTED IN ACCORDANCE WITH NFPA 72 REQUIREMENTS OF LOCAL AUTHORITIES, INCLUDING UNDER NORMAL AND STANDBY POWER SUPPLIES AND AS INDICATED ON PLANS. DOCUMENT EACH INSPECTION AND TEST, 2. PREPARE FOR TESTING BY ENSURING THAT ALL WORK IS COMPLETE AND CORRECT; PERFORM PRELIMINARY TESTS AS REQUIRED, 3. NOTIFY AUTHORITIES HAVING JURISDICTION AND COMPLY WITH THEIR REQUIREMENTS FOR SCHEDULING INSPECTIONS AND TESTS AND FOR OBSERVATION BY THEIR PERSONNEL. 4. PROVIDE COMPLETED RECORD DRAWINGS, COMPLETED NFPA 72 RECORD OF COMPLETION AND COMPLETED NFPA INSPECTION AND TEST FORM AS REQUIRED 14 DAYS PRIOR TO COMMENCING FINAL ACCEPTANCE TEST. 5. PROVIDE ALL TOOLS, SOFTWARE, AND SUPPLIES REQUIRED TO ACCOMPLISH INSPECTION AND TESTING. 6. SYSTEM START UP AND COMMISSIONING SHALL INCLUDE TRIAL OPERATION OF ALL MAIN AND PERIPHERAL EQUIPMENT AND SOFTWARE PROGRAMMING OF LOCAL FACP. 7. DUCT SMOKE DETECTORS: PROPER AIR DUCT SENSOR AIR FLOW SHALL BE DEMONSTRATED USING MANUFACTURER'S APPROVED TEST EQUIPMENT. DOCUMENTATION OF AIR FLOW VELOCITY SHALL BE PROVIDED AND SHALL INCLUDE VELOCITY, AIR HANDLER NAME, SENSOR LOCATION, MANUFACTURER AND MODEL NUMBER OF TESTING DEVICE, THIS TESTING SHALL BE CONDUCTED AFTER THE AIR HANDLING SYSTEM'S TESTING AND BALANCING WORK HAS BEEN COMPLETED. F PROJECT CLOSE-OUT REQUIREMENTS 1. ALL NEW SYSTEM ADDRESS & CIRCUIT INFORMATION SHALL BE ON RECORD DRAWINGS & ON A DEVICE WIRING LEGEND. THREE COPIES OF THE LEGEND SHALL BE TURNED OVER W/ RECORD DRAWINGS, A COPY LEFT IN THE FRCP, AND A SOFTWARE COPY PROVIDED, 2. AT THE PROJECT COMPLETION, THE FIRE ALARM CONTRACTOR SHALL PROVIDE THE OWNER WITH A COMPLETE FIRE ALARM SYSTEM OPERATIONS AND MAINTENANCE (0&M) MANUAL, AND ALL NFPA 72 REQUIRED SYSTEM CLOSE-OUT DOCUMENTATION, THE FIRE ALARM SYSTEM SHALL BE OPERATED AND MAINTAINED IN ACCORDANCE WITH THE REQUIREMENTS OUTLINED IN NFPA 72. 3. EXACT INSTALLATION WIRING COUNTS SHALL BE SHOWN ON AS BUILT WIRING DIAGRAMS AND INSTALLATION DRAWINGS, UPON PROJECT ACCEPTANCE. 4. PROVIDE ALL NFPA 72 FORMS COMPLETELY FILLED OUT AFTER THE FINAL CERTIFICATE OF OCCUPANCY. 5. AS -BUILT DRAWINGS. NFPA FORMS, RECORD DRAWINGS AND FACP PROGRAM FILE SHALL BE STORED ON A FLASH DRIVE PROVIDED AND INSTALLED BY FA CONTRACTORS AND TRANSMITTED ELECTRONICALLY TO OWNER'S REPRESENTATIVE. LINE TYPE LEGEND NEW EXISTING -------- DEMOLISH - - - - UNDERGROUND SYMBOL LEGEND REFER TO LINE LEGEND FOR DEPICTION OF NEW/EXISTING/DEMO STATUS NOT ALL SYMBOLS MAY BE USED. FOR WIRE LEGEND, REFER TO SHEET FA-101. ANN REMOTE ANNUNCIATOR AMP AMPLIFIER FACU FIRE ALARM CONTROL UNIT FARP FIRE ALARM REMOTE TRANSPONDER NAC FIRE ALARM NAC EXPANDER (GENERAL) WF FIRE SPRINKLER FLOW SWITCH FT FIRE SPRINKLER TAMPER SWITCH ElFIRE SPRINKLER PRESSURE SWITCH T SPOT SMOKE DETECTOR AIM ADDRESSABLE SINGLE INPUT MODULE Alo ADDRESSABLE INPUT/OUTPUT MODULE AIM ADDRESSABLE DOUBLE INPUT MODULE 2 aADDRESSABLE OUTPUT MODULE /'�Slxj'YY-ZZ SLC DEVICE ON SYSTEM #X, CIRCUIT #YY, ��f DEVICE #ZZ WALL -MOUNT APPLIANCES: Q-� MANUAL PULL STATION STROBE HORN HORN/STROBE POD SPEAKER o SPEAKER/STROBE CHIME SOUNDER CEILING -MOUNT APPLIANCES: '1o' STROBE ` F HORN " 2 HORN/STROBE 09 SPEAKER SPEAKER/STROBE �c CHIME SOUNDER 0 FIRE ALARM SHEET LIST SHEET CURRENT CURRENT NUMBER SHEET NAME REVISION DATE FA-100 FIRE ALARM NOTES FIRE ALARM QUANTITIES 0 09/07/21 FA-101 1 10/08/21 FA-102 FIRE ALARM SITE PLAN 0 09/07/21 FA-110 FIRE ALARM OVERALL PLAN 0 09/07/21 FA-110.1 FIRE ALARM PARTIAL PLAN -ZONE 1 1 10/08/21 FA-110.2 FIRE ALARM PARTIAL PLAN - ZONE 2 0 09/07/21 FA-110.3 FIRE ALARM PARTIAL PLAN - ZONE 3 1 10/08/21 FA-110.4 I✓ E ALARM PARTIAL PLAN - ZONE: 4 1 10/08/21 0.5 P F RE ALARM PARTIAL PLAN - ZONE 5 1 10/08/21 10.6 F RE ALARM PARTIAL PLAN - ZONE 6 1 10/08/21 FA-110.7 FIRE ALARM PARTIAL PLAN -ZONE 7 0 09/07/21 FA-110.8 RE ALARM PARTIAL PLAN - ZONE 8 0 09/07/21 FA-110.9 FIRE ALARM PARTIAL PLAN - ZONE 9 0 09/07/21 FA-110.10 FIRE ALARM PARTIAL PLAN - ZONE 10 I 0 09/07/21 FA-400 SEQUENCE OF OPERATIONS AND DEVICE LABELS 1 10/08/21 FA-500 FIRE ALARM RISER DIAGRAM - NAC 1 10/08/21 FAFA-5 1010 FIRE ALARM RISER DIAGRAM - SLC 1 10/08/21 I FA-600 FIRE ALARM CALCULATIONS 1 1 10/08/21 FA-601 FIRE ALARM CALCULATIONS 2 0 09/07/21 A-602 FA_-7C6_ FIRE ALARM CALCULATIONS 3 FIRE ALARM DETAILS a 1 1 10/08/21 10/08/21 SUBSCRIPTS AND ABBREVIATIONS ABBREV. DESCRIPTION A AMPERE - AFF ABOVE FINISHED FLOOR AH AIR -HANDLER AHJ AUTHORITY HAVING JURISDICTION AIM ADDRESSABLE INPUT MODULE AMP AMPLIFIER AOM ADDRESSABLE OUTPUT MODULE BATT BATTERY CD CANDELA (E) EXISTING EMT ELECTRICAL METALLIC_ TUBING EOI END OF LINE EOLR END OF LINE RESISTOR EOR ENGINEER OF RECORD ER ELECTRICAL EQUIPMENT ROOM FACP FIRE ALARM CONTROL PANEL FATC FIRE ALARM TERMINATION CABINET FARP FIRE ALARM REMOTE TRANSPONDER PANEL FLA FULL LOAD AMPERES FMC FLEXIBLE METAL CONDUIT GFI GROUND FAULT CIRCUIT INTERRUPTING GRD GROUND HOA HAND/OFF/AUTOMATIC IDC INITIATING DEVICE CIRCUIT J-BOX JUNCTION BOX KV KILOVOLT KVA KILOVOLT AMPERE KW KILOWATT MC METAL CLAD CABLE ------------------- --- �MECH MECHANICAL MIC MICROPHONE (N) NEW NAC NOTIFICATION APPLIANCE CIRCUIT NC NORMALLY -CLOSED CONTACT NIC NOT IN CONT_RA_CT NTS NOT TO SCALE NO NORMALLY -OPEN CONTACT PS POWER SUPPLY PVC POLYVINYL CHLORIDE RACEWAY SLC SIGNALING LINE CIRCUIT TYP TYPICAL LION UNLESS OTHERWISE NOTED V VOLT VA _ VOLT AMPERE W 1 WATT Antinomy Consulting Engineers Code Consulting - fire Protection - Smoke Control 600 Rinehart Road Suite 2054 Lake Mary, FL 32746-4955 Tel. 321-888-2882 Online: antinomy.com Prepared For: d °a>4, EC #13001688 9 No 73972 '� v STATE OF °r 1r 11 ii' 0 e 10/08/21 This document has been digitally signed and sealed by Gregory A. Tabaka, PE on the date adjacent to the seal. Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies. Revisions No. Description Date 0 PERMIT SET 09/07/21 i COMPLETE ALARM INC. MAVERICK BOATS INC. Project Address ,$ 4551 ST. LUCIE BLVD s FT. PIERCE, FL 34946 ✓ FIRE ALARM NOTES' _ _ N Project Number ACE0146 Date _ 10/08/21 0 Drawn By G.TABAKA v, Checked By G.TABAKA o FA-1 00 2i W (REV. 0) Scale (UON) 1/$" = 1'-0" 0 U C M A LL u [] C E. A ANTINOMY 8 4 3 DESCRIPTION OF REVISIONS REVISION 0 SUBMITTED FOR PERMIT. REVISION 1 1. ADDED AN DEVICES FOR NEW BOOTH IN EXISTING PHASE, CONNECTED TO EXISTING RPS4. 2. ADDED DUCT SMOKE DETECTOR FOR NEW RAU-G2 AND ADDRESSABLE RELAY MODULE FOR SHUTDOWN. 3. CHANGED NAC EXPANDER RPS6 MATERIAL, 4. ADDED WIRING DETAIL FOR RPS6. 5. REALLOCATED NEW GELCOAT BOOTH (IN EXPANSION PHASE) AN APPLIANCES TO RPS6. 6. DELETED FOUR DUAL -MONITOR MODULES FOR FIRE SPRINKLER SUPERVISION; NOW SUPERVISED IN SERIES FROM ONE MODULE. 7. CHANGED SEVEN ADDRESSABLE PULLSTATIONS TO CONVENTIONAL; ADDED MONITOR MODULE TO SUPERVISE. 8. REVISED RISER DIAGRAM, CALCULATIONS AND QUANTITIES TO REFLECT CHANGES. FIRE ALARM BILL OF MATERIAL (NEW) • MANUFACTURER MODEL AUX. COMPONENT DESCRIPTION COUNT FIRE ALARM HEAD END • I SILENT KNIGHT SK-PS10 NAC EXPANDER, 10 AMP, 7 CKT. 2 ADDRESSABLE MODULES • SILENT KNIGHT SK-CONTROL ADDRESSABLE CONTROL MODULE FOR NAC, OUTPUTS=1 1 • SILENT KNIGHT SK-MONITOR ADDRESSABLE INPUT MODULE, INPUTS=1 3 • SILENT KNIGHT SK-MONITOR-2 ADDRESSABLE INPUT MODULE, INPUTS=2 1 • SILENT KNIGHT SK-RELAY ADDRESSABLE OUTPUT MODULE, OUTPUTS=1 7 INITIATING DEVICES • SILENT KNIGHT f SK-HEAT-W B300-6 BASE HEAT DETECTOR ON 6" BASE 2 • SILENT KNIGHT SK-PHOTO-R-W DNRW HOUSING, DST SAMPLING TUBE PHOTOELECTRIC SMOKE DETECTOR IN NEMA 4 DUCT DETECTOR HOUSING 5 • SILENT KNIGHT SK-PHOTO-W B300-6 BASE PHOTOELECTRIC SMOKE DETECTOR ON 6" BASE 1 • SILENT KNIGHT SK-PS-DA MANUAL PULL STATION, DOUBLE ACTION, CONVENTIONAL 7 • SILENT KNIGHT SK-PULL-DA MANUAL PULL STATION, DOUBLE ACTION 8 AUDIBLENISIBLE APPLIANCES, CEILING MOUNT • FEDERAL SIGNAL FHEX CEILING/WALL MOUNT EXPLOSIONPROOF HORN 4 • FEDERAL SIGNAL FSEX-HI _ CEILING/WALL MOUNT EXPLOSIONPROOF STROBE 4 • WHEELOCK HSC CEILING MOUNT HORN/STROBE, 15/30/60/75/115/150/177 CD SELECTABLE, 90/95/99 DB SELECTABLE 40 AUDIBLENISIBLE APPLIANCES, CEILING MOUNT, WEATHERPROOF • SYSTEM SENSOR PC2RHK WITH FACTORY -SUPPLIED PLASTIC BACKBOX/BASE _ RED CEILING MOUNT WEATHERPROOF STROBE, NEMA 4X, SELECTABLE 135/150/177/185 CD, SELECTABLE 83/86/88 DB 3 AUDIBLE/VISIBLE APPLIANCES, WALL MOUNT • WHEELOCK LHSR3 RED WALL MOUNT HORN/STROBE, _T 15/30/75/110 CD SELECTABLE 1 INTERFACES • DITEK DTK-2MHLP24B WB SURGE SUPPRESSOR, 24V, 4 CONTACTS 1 • DITEK DTK-120HW SURGE SUPPRESSOR, 120V, 2 CONTACTS 2 WIRE LEGEND (NEW) WIRE ESTIMATED RESIST. CAPACIT. TYPE DESCRIPTION LENGTH (0/kFT) (pF/kFT) AUX. POWER, STROBE (NAC), HORN WIRING (NAC) M8P 1 PAIR #18 COPPER, SOLID, TWISTED OR UNTWISTED, UNSHIELDED, 660 ft 8.45 N/A FPLP, WEST PENN 60980B [CI=260] P2P 1 PAIR #12 COPPER, SOLID OR STRANDED, TWISTED OR UNTWISTED, 4535 ft 2.05 N/A UNSHIELDED, FPLP, WEST PENN 60995B OR 60995BS [CI=880 SOLID, CI=920 STRAND] P4P 1 PAIR #14 COPPER, SOLID OR STRANDED, TWISTED OR UNTWISTED, 1290 ft 3.26 N/A UNSHIELDED, FPLP, WEST PENN 60993B OR 60993BS [CI=570 SOLID, CI=610 STRAND] P6P 1 PAIR #16 COPPER, SOLID OR STRANDED, TWISTED OR UNTWISTED, 1120 ft 5.29 N/A UNSHIELDED, FPLP, WEST PENN 60991B OR 60995BS [CI=380 SOLID, CI=420 STRAND] P8P 1 PAIR #18 COPPER, SOLID, TWISTED OR UNTWISTED, UNSHIELDED, 375 ft 8.45 N/A FPLP, WEST PENN 609808 [CI=260] SIGNALING LINE CIRCUIT WIRING (SLC) T8P 1 PAIR #18 COPPER, SOLID, TWISTED PAIR, UNSHIELDED, FPLP, WEST 2595 ft 8.45 0,031 PENN 60980B [CI=260] VOICE AUDIO WIRING (NAC) N/A INSTALLER'S CHOICE: MAY SUBSTITUTE LARGER WIRING FOR FOR AUX. POWER AND NAC CIRCUITS, BUT NOT LARGER THAN 12 AWG. QUANTITIES AND MATERIAL REVISED- Antinomy Consulting Engineers Code Consulting - Fire Protection - Smoke Control 600 Rinehart Road Suite 2054 Lake Mary, FL 32746-4955 Tel. 321-888-2882 Online: antinomy.com Prepared For: �a , jvh, EC #13001688 `��11111111///� No 73972 % STATE OF fill 1 l is 10/08/21 This document has been digitally signed and sealed by Gregory A. Tabaka, PE on the date adjacent to the seal. Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies. Revisions No. Description Date 0 PERMIT SET 09/07/21 1 NEW BOOTH, RPS6 REALLOC. 10/08/21 COMPLETE ALARM INC. MAVERICK BOATS, INC. Project Address 4551 ST. LUCIE BLVD FT. PIERCE, FL 34946 FIRE ALARM QUANTITIES Project Number ACE0146 Date 10/08/21 N w Drawn By G.TABAKA pp:_ Checked By G.TABAKA z FA-1 01 Q (REV. 1) LU cc U_ Scale (UON) J I H j G F E 19 It 3 A 8 VA 6 4 J , M Antinomy Consulting Engineers Code Consulting • Fire Protection - Smoke Control 600 Rinehart Road Suite 2054 Lake Mary, FL 32746-4955 Tel, 321-888-2882 Online: antinomy.com Prepared For: .,h r EC #13001688 ,``��►illlllf//// \PG OE �N S�q, No 73972 i 7� p ; 414 STATE OF too IN% '/// s f I iil i `� \\` 10/08/21 This document has been digitally signed and sealed by Gregory A. Tabaka, PE on the date adjacent to the seal. Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies. Revisions No. Description Date 0 PERMIT SET 09/ 77/21 COMPLETE ALARM INC. MAVERICK BOATS, INC. Project Address 4551 ST. LUCIE BLVD FT. PIERCE, FL 34946 FIRE ALARM SITE PLAN N O Project Number ACE0146 0 Date 10/08/21 Drawn By G.TABAKA Checked By G.TABAKA -- 73— FA-1 02 LU a (REV.0) LU U- - Scale (UON) 1" = 50'-0" N O 1 3 I I I N ( G I G c 4 3 2 1 Antinomy Consulting Engineers Code Consulting • fire Protection • Smoke Control 600 Rinehart Road Suite 2054 Lake Mary, FL 32746-4955 Tel. 321-888-2882 Online: antinomy.com Prepared for: .> 9 lv EC #13001688 No 73972 STATE OF !!� s/ r i t i `\ 10/08/21 This document has been digitally signed and sealed by Gregory A. Tabaka, PE on the date adjacent to the seal. Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies. Revisions No. Description Date 0 PERMIT SET 09/07/21 COMPLETE ALARM INC. MAVERICK BOATS, I_NC. Project Address 4551 ST. LUCIE BLVD FT. PIERCE, FL 34946 FIRE ALARM OVERALL PLAN N \ 0 CD 0 Project Number ACE0146 Date — 10/08/21 Drawn By GJABAKA Q Checked By G.TABAKA cc o FA-1 10 (REV.0) UJ U- scale (uoN) 1/32" = 1'-0" 8 7 6 5 4 3 2 H I G F E ( D C B I A TYPICAL N°TES: A N T I N 0 M Y 1. CEILING MOUNTED HORN/STROBES: A. SHALL BE EQUIPPED WITH MINIMUM 4"x4"x 2-1/8" BACKBOXES SUSPENDED FROM STRUCTURAL STEEL ON NUMBERED GRID LINES. B. BACKBOXES SHALL BE INSTALLED LEVEL, OPEN FACE DOWNWARDS AT AN ELEVATION OF NO HIGHER THAN 29'-10" ABOVE THE FLOOR / 2 3 4 5 �G 7 NEAR THE F-GRID LINE AND 25' NEAR THE B- GRID LINE. 1 1 C. ALL BACKBOXES SHALL HAVE A FACTORY - MADE 1/4 HOLE AT THE TRUE CENTER OF THE BOX. D. ATTACH TO STRUCTURE USING A LISTED SCREW -TYPE BEAM CLAMP (EQUAL TO CADDY Antinomy Consulting Engineers #4QTIBC TO SUPPORT 1/4" THREADED ROD. Code Consulting d Fire Protection •smoke Control ) 600 Rinehart Road Suite 2054 SUSPEND BACKBOX FROM THREADED ROD Lake Mary, FL 32746-4955 I ! ! USING SECURE ATTACHMENT, SUCH AS Tel. 321-888-2882 Online: antinomy.com DOUBLE OR JAM -NUTS. E. ALL BOXES ON AN EAST -WEST LINE SHALL BE Prepared For: AT EQUAL ELEVATION, DO NOT DEVIATE FROM �L`''P L'�� _ _ _ _ * _ _ _ _ T8P s1*1,5W-(M59) T8P THE ALIGNMENT SHOWN. C,G �_ S1 1.5W (M62) — T8P - -- �- — — — T8P - — — — — — — — — — � -----r - — � INSTALL WHEELOCK'UNIVERSAL MOUNTING F LJ i BASE' AT EACH. OAON� 1*1.5W (M61) S1*1.4-(M60) p� G. PROVIDE BUSHING OR CLAMP WHERE WIRE FAN SHUTDOWN TS —C.) C AIM GEL BOOTH SPKR TAMPER �p 3/4" IMC UNTIL ABOVE BOOTH I (RAU-BG1, EF-BG1, EF-BG2, E -BG3, C I � ENTERS OR EXITS BOX. ! EF-BG4) �� H. PROVIDE ADDITIONAL SUPPORT WHERE a � WITHIN BOOTH.. � c V6 5-1 1 XP'70 REQUIRED BY CODE OR AHJ. P6P WITHIN BOOTH C V6*6-1 /1'\1 2. NAC SUPPLY WIRING SHALL BE ROUTED ALONG \ ! TRANSVERSE PURLINS AND SUPPORTED WITH F�� P I ! WIRE J-HOOKS (EQUAL TO EATON BCH12-F3 OR -F4 EC #13001688 DEPENDING UPON STEEL FLANGE TYPE). PROVIDE SUPPPORT AT SPACING NO GREATER THAN 54" ON P4P, P6P CENTER BETWEEN HOOKS. I i I i I I I GELCOAT BOOTH 3. FOR WIRES TO BE SUPPORTED TRAVELING PARALLEL WITH NUMBERED STEEL, PROVIDE \- P2P T8P j I EATON BCH21-F3 OR -F4 (OR EQUAL) J-HOOKS ON I P2P, T8P P2P, 2x T8P P2P, 2x T8P I I SAME SPACING AS ABOVE. C * C C * 4. WHERE LOCATED WITHIN 10 FT OF THE FINISHED V545 - B V5 4 4 BOOTH V5 4 3 ABOVE BOOTH ABOVE FLOOR ALL WIRES SHALL BEENCLOSED 150 Cd 150 C T 150 Cd , A LIN EMT d �O<p99 dI3 { 99 dB j j 99 dB ' (3/4" MINIMUM). WHERE WIRES ENTER OR EXIT THIS EMT, PROVIDE LISTED BUSHING. r T8P 5. ALL WIRES SERVING, ENTERING OR LOCATED 1111111�� BOOTH: ASSUMED CLASS I, DI i ION I AREA f WITHIN THE BOOTHS SHALL BE IN THREADED %��`�'1F ,I r MINIMUM 3/4" IMC OR RMC. ��`G,.,�`'GE"N'''�,�'�'% s .y No 73972 RAU-BG1 SUPPLY DUCT (ROOF) WP 6. ROOFTOP EQUIPMENT: PROVIDE DEDICATED WIRE o7 LOOP THAT SERVES ONLY EQUIPMENT ABOVE THE I I I ' ROOFLINE. PRIOR TO CONNECTION TO FIRE ALARM E — — — — — — — — — — — — — — — — — — — — — — — — — -- ——YSTEM, PROVIDE SURGE SUPPRESSION. *, �� STATE OFO \ ;; 7. COORDINATE LOCATION AND CONNECTION OF FANON SHUTDOWN RELAYS WITH INSTALLER. s t 1111110/08/21 r This document has been digitally signed and sealed by Gregory A. Tabaka, PE on the date adjacent to the seal. Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies. — Revisions No. Description Date ! 0 PERMIT SET 09/07/21 ! ' 1 NEW BOOTH, RPS6 REALLOC. 10/08/21 P4P, P6P, T8P i � 1 1 r S1*1,5R-2(D�) P2P - P2P /� P2P 2xT8P 0 P2P 2xT8P RAU-SG1 SUPPLY DUCT (ROOF) f WP C i C C 150 Cd 5*3-5 150 Cd 5*3-4 150 Cd 5*3-3 FD 2xT8P i <,p99 dB ( 99 dB 99 dB ' - -- -- CB�— GELCOAT BOOTH-- i I C P4P, P6P, TBP C Fo pd V6*7-1 FF 0 v6*7-2 COMPLETE ALARM INC. 2xP2P � XP 1 XP I -'� C ( C v6*3-1 ;o; ' v6*4-1 MAVERICK BOATS, INC. 2xP2P P4P XP,150 F0 XP 1�0 ' 1p ' Project Address s1*1.4w (M63) /4" IMC UNTIL ABOVE BOOTH Al 4551 ST. LUCIE BLVD BOOTH: ASSUMED CLASS I, DIV* 1 ARE 1 FT. PIERCE, FL 34946 I 3/4" EMT TYP. PENETRATION: PROVIDE MIN 3/4" EMT STUB s1 1,4 (M64) P?P, P4P THROUGH WALL WITH BUSHINGS N BOTH ENDS. AOM FAN SH TDOWN P�P,2xP4P °° (RAU S 1, EF-SG1, EF SG2) o PLENUM iA _ FIRE ALARM PARTIAL ; S�S � I S1*1.4W�M26 � -� ... � -�►-� � -�-� � � ' 120 s1*1.4 -(D4) ! ! ! PLAN -ZONE 1 W r 0 CONNECT TO EXISTIN ® I Project Number ACE0146 120 V CIRCUIT / Date 10/08/21 ! HEAT DETECTOR WALL -MOUNTED - PAC _NAC TO PROTECT NAC BOOSTER IN LIEU •Q Drawn By G.TABAKA cc OF SMOKE DETECTO 1SK-Ps10 j sK-5499� RPS6 P 4 ' Checked By G.TABAKA a_cc G F E C' C I. A FA-110. REV. Scale (VON) 1/8" = V-0" r F J H G F E r If B A 8 7 6 5 4 3 2 iI I 8� 9 10 11 12 13 H S 1 * 1,5W-(M58) G F — T8P E D IC TYPICAL NOTES: 1. CEILING MOUNTED HORN/STROBES: A. SHALL BE EQUIPPED WITH MINIMUM 4"x4"x 2-1/8" BACKBOXES SUSPENDED FROM STRUCTURAL STEEL ON NUMBERED GRID LINES. B. BACKBOXES SHALL BE INSTALLED LEVEL, OPEN FACE DOWNWARDS AT AN ELEVATION OF NO HIGHER THAN 29'-10" ABOVE THE FLOOR NEAR THE F-GRID LINE AND 25' NEAR THE B- GRID LINE. C. ALL BACKBOXES SHALL HAVE A FACTORY - MADE 1/4" HOLE AT THE TRUE CENTER OF THE BOX. D. ATTACH TO STRUCTURE USING A LISTED SCREW -TYPE BEAM CLAMP (EQUAL TO CADDY #4QTIBC) TO SUPPORT 1/4" THREADED ROD. SUSPEND BACKBOX FROM THREADED ROD USING SECURE ATTACHMENT, SUCH AS DOUBLE OR JAM -NUTS. E. ALL BOXES ON AN EAST -WEST LINE SHALL BE AT EQUAL ELEVATION. DO NOT DEVIATE FROM THE ALIGNMENT SHOWN. _--_F_ INSTALL WHEELOCK'UNIVERSAL MOUNTING BASE' AT EACH. G. PROVIDE BUSHING OR CLAMP WHERE WIRE ENTERS OR EXITS BOX, H. PROVIDE ADDITIONAL SUPPORT WHERE REQUIRED BY CODE OR AHJ. 2. NAC SUPPLY WIRING SHALL BE ROUTED ALONG TRANSVERSE PURLINS AND SUPPORTED WITH WIRE J-HOOKS (EQUAL TO EATON BCH12-F3 OR -F4 DEPENDING UPON STEEL FLANGE TYPE). PROVIDE SUPPPORT AT SPACING NO GREATER THAN 54" ON CENTER BETWEEN HOOKS. 3. FOR WIRES TO BE SUPPORTED TRAVELING _ _—PARALLEL WITH NUMBERED STEEL, PROVIDE EATON BCH21-F3 OR -F4 (OR EQUAL) J-HOOKS ON SAME SPACING AS ABOVE, 4. WHERE LOCATED WITHIN 10 FT OF THE FINISHED FLOOR, ALL WIRES SHALL BE ENCLOSED IN EMT (3/4" MINIMUM). WHERE WIRES ENTER OR EXIT THIS EMT, PROVIDE LISTED BUSHING, 5. ALL WIRES SERVING, ENTERING OR LOCATED WITHIN THE BOOTHS SHALL BE IN THREADED MINIMUM 3/4" IMC OR RMC. 6. ROOFTOP EQUIPMENT: PROVIDE DEDICATED WIRE LOOP THAT SERVES ONLY EQUIPMENT ABOVE THE ROOFLINE. PRIOR TO CONNECTION TO FIRE ALARM SYSTEM, PROVIDE SURGE SUPPRESSION. 7. COORDINATE LOCATION AND CONNECTION OF FAN SHUTDOWN RELAYS WITH INSTALLER. ANTINOMY Antinomy Consulting Engineers Code Consulting - fire Protection - Smoke Control 600 Rinehart Road Suite 2054 Lake Mary, FL 32746-4955 Tel. 321-888-2882 Online: antinomy.com Prepared For T"- IL 1 EC #13001688 ``%��1111111��� -;% 1" No 73972 '� v .0 i-P % STATE OF $ tvW� 11 I i 1 t`♦♦ 10i08/21 This document has been digitally signed and sealed by Gregory A. Tabaka, PE on the date adjacent to the seal. Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies. Revisions No. Description Date 0 PERMIT SET 09/07/21 i COMPLETE ALARM INC. MAVERICK BOATS, INC. Project Address 4551 ST. LUCIE BLVD FT. PIERCE, FL 34946 N O FIRE ALARM PARTIAL PLAN - ZONE 2 N w z 0 Project Number ACE0146 N Date 10/08/21 J Drawn By G.TABAKA Checked By G.TABAKA a a FAIIIIIII111 10. W_ EV.0) N Scale (UON) 1/8" = 1'-Oil B 0 J I G I F E C C B A MA G - 6 CF 5 15 16 1 1 1 i I I 1 1 T8P 17 18 Z T6P,2xM8P T8P P2P CONY. --- -, S1*1.5 M99(!DC T6P FROM FACP, P2P 15 — _S1*1.5W-(M55) — T8P — U T8P FROM ROOF +1 I I 19 20 S1*1.5-(M99) M PULL STATIONS AT EXPANSI N ) S1*1.5-(M69) I' ELEC I M NAC TROUBLEMONITOR S1*1.5-(D3) '— M8P - - O 1 - --- NEW 12#2 + GROUND RUN IN 3/4 EMT TO 120 V POWER. 15 OR 20 A BREAKER. DEDICATED Ti0 FIRE ALARM V5 2-1 0120 SERVICE ONLY. PROVIDE RED BREAKER LOCK. T8P GROUND SURGE SUPPRESSOR. -�, NAC -47k R-PS10 ---- — — — — — --I— - - ---- - M8P __ 21 PLENUM r r r P6P 1 HULL & DECK r GRIND (SHUTDOWN CONTROL FOR FANS DCFH1 AND -- 3/4" EMT 1 DCF-D1 NOT REQUIRED AND WERE OMITTED) 1 i ' i I1 f C Wp r - 8xP2P, P6P, T6P, T8P - { WITHIN GRINDING BOOTH o V3*3-1 1 �i 177 1 f-- ----- - --------- 1 WITHIN GRINDING BOOTH - 3 o V3*3-2 1 — -- I P6P I i SURGE SUPPRESSION FOR ROOF -TOP SLC. PROVIDE #14 GROUND TO'BUILDING GROUND OR GROUND ROD. TYPICAL NOTES.- 1. CEILING MOUNTED HORN/STROBES; A. SHALL BE: EQUIPPED WITH MINIMUM 4"41x 2-1/8" BACKBOXES SUSPENDED FROM STRUCTURAL STEEL ON NUMBERED GRID LINES. B. BACKBOXES SHALL BE INSTALLED LEVEL, OPEN FACE DOWNWARDS AT AN ELEVATION OF NO HIGHER THAN 29'-10" ABOVE THE FLOOR NEAR THE: F-GRID LINE AND 25' NEAR THE B- GRID LINE, C. ALL BACKBOXES SHALL HAVE A FACTORY - MADE 1/4" HOLE AT THE TRUE CENTER OF THE BOX. D. ATTACH TO STRUCTURE USING A LISTED SCREW -TYPE BEAM CLAMP (EQUAL TO CADDY #4QTIBC) TO SUPPORT 1/4" THREADED ROD. SUSPEND BACKBOX FROM THREADED ROD USING SECURE ATTACHMENT, SUCH AS DOUBLE OR JAM -NUTS. E. ALL BOXES ON AN EAST -WEST LINE SHALL BE AT EQUAL ELEVATION. DO NOT DEVIATE FROM THE ALIGNMENT SHOWN. F: INSTALL WHEELOCK'UNIVERSAL MOUNTING BASEAT EACH, G. PROVIDE BUSHING OR CLAMP WHERE WIRE ENTERS OR EXITS BOX. H. PROVIDE ADDITIONAL SUPPORT WHERE REQUIRED BY CODE OR AHJ. 2. NAC SUPPLY WIRING SHALL BE ROUTED ALONG TRANSVERSE PURLINS AND SUPPORTED WITH WIRE J-HOOKS (EQUAL TO EATON BCH12-F3 OR -F4 DEPENDING UPON STEEL. FLANGE TYPE). PROVIDE SUPPPORT AT SPACING NO GREATER THAN 54" ON CENTER BETWEEN HOOKS. 3. FOR WIRES TO 13E SUPPORTED TRAVELING PARALLEL WITH NUMBERED STEEL, PROVIDE EATON BCH21-F3 OR -F4 (OR EQUAL) J-HOOKS ON SAME SPACING AS ABOVE. C C ' 4. WHERE LOCATED WITHIN 10 FT OF THE FINISHED V5*2-5 V5*2-2 � ABOVE GRINDING BOOTH -� V5*2-3 150 Cd 150 Cd I 150 Cd HULL & DECK r FLOOR ALL WIRES SHALL BE ENCLOSED IN EMT 99 dB I 99 dB i I I 99 dB GRIND I 1 (3/4" MINIMUM). WHERE WIRES ENTER OR EXIT 1 -- r THIS EMT, PROVIDE LISTED BUSHING. -- r 5. ALL WIRES SERVING, ENTERING OR LOCATED 1 WITHIN THE BOOTHS SHALL BE IN THREADED MINIMUM 3/4" IMC OR RMC. 1 � r 1 - 6. ROOFTOP EQUIPMENT; PROVIDE DEDICATED WIRE 1 I PLENUM 1 LOOP THAT SERVES ONLY EQUIPMENT ABOVE THE I I I I I I _ ROOFLINE. PRIOR TO CONNECTION TO FIRE ALARM - - - - - - - ----SYSTEM, PROVIDE SURGE SUPPRESSION. � r r i r 7. COORDINATE LOCATION AND CONNECTION OF FAN SHUTDOWN RELAYS WITH INSTALLER. C� C 1 150 Cd 5*1-1 � 150 Cd 5*1-2 1 99 dB I 99 dB 1 -I I P2P 1 I' 1 P6P, T6P C 1 I o V5*7-2 WOMEN 75 L - I, 1 1 1 c 1 o t/5*7-1 L MEN � 75 S11 _ � 1 �- SLEEVE WITH 3/4" EMT (WITH BUSHINGS) THROUGH WALL ®St*1.4E-(D5 NAC s1*1.4E-(M42) 1 RPS AOM) FAN SHUTDOWN I HEAT DETECTORI WALL -MOUNTED I I 1 TO PROTECT NAC BOOSTER IN LIEU 1 OF SMOKE DETE�TOR i 1 Antinom Code Co 600 RinE Lake Mai Tel. 321 This docume Tabaka, PE o document ar must be veril Revisions Col MA Project Ac FIF Project Ni Date Drawn By Checked I J H G F E D C 0 A J I I H I G I F E 0 C B A ANTINOMY Antinomy Consulting Engineers Code Consulting - Fire Protection - Smoke Control 600 Rinehart Road Suite 2054 Lake Mary, FL 32746-4955 Tel. 321-888-2882 Online: antinomy.com Prepared For: it L� ARM EC #13001688 ��Illlllllf//// E IV No 73972 i� STATE OF 1111111111 10/08/21 This document has been digitally signed and sealed by Gregory A. Tabaka, PE on the date adjacent to the seal. Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies. Revisions No. Description Date 0 PERMIT SET 09/07/21 1 NEW BOOTH, RPS6 REALLOC. 10/08/21 COMPLETE ALARM INC. MAVERICK BOATS, INC. Project Address 4551 ST. LUCIE BLVD FT. PIERCE, FL 34946 FIRE ALARM PARTIAL PLAN - ZONE 4 Project Number AC E0146 Date _ 10/08/21 Drawn By G.TABAKA Checked By G.TABAKA FA-1 10 - 4EV ,, Scale (LION) 1 /8" = 1'-0" 8 7 6 F 5 4 3 4 J I I I H 29 30 J I G F E IC C i31 32 �33 34 5 PROVIDE FMC TO EACH TAMPER SWITCH AND FLOW SWITCH. CONNECT TAMPERS IN PARALLEL AND CONNECT FLOW SWITCHES IN PARALLEL SO THAT ANY ON OPERATING WILL RESULT IN A SUPERVISORY OR ALARM SIGNAL RESPECTIVELY. LIO M81) TS TS TS -- TS _TS hAIM) ___SPKR FLOWS 5_@ WF WF ;WF]— F�J2 SPKR TAMPERS 5 _A 1 i4EE r 1*1j 1E-(M52) I 1*1.4E-(M4� — I UZJ RELOCATE BELL AOM FAN SHUTDOWN AOM FAN SH TDOWN 2 2 1 * 1.4E-(M46) A _ FIRE WATER FLOW BELL 0 _.S-1111111 - -- WP V2*A-1 H I G I F I E I D I C I B A TYPICAL NOTES: 1. CEILING MOUNTED HORN/STROBES: A. SHALL BE EQUIPPED WITH MINIMUM 4"x4"x 2-1/8" BACKBOXES SUSPENDED FROM STRUCTURAL STEEL ON NUMBERED GRID LINES. B. BACKBOXES SHALL BE INSTALLED LEVEL, OPEN FACE DOWNWARDS AT AN ELEVATION OF NO HIGHER THAN 29'-10" ABOVE THE FLOOR NEAR THE F-GRID LINE AND 25' NEAR THE B- GRID LINE. C. ALL BACKBOXES SHALL HAVE A FACTORY - MADE 1/4" HOLE AT THE TRUE CENTER OF THE BOX. D. ATTACH TO STRUCTURE USING A LISTED SCREW -TYPE BEAM CLAMP (EQUAL TO CADDY #4QTIBC) TO SUPPORT 1/4" THREADED ROD. SUSPEND BACKBOX FROM THREADED ROD USING SECURE ATTACHMENT, SUCH AS DOUBLE OR JAM -NUTS. E. ALL BOXES ON AN EAST -WEST LINE SHALL BE AT EQUAL ELEVATION. DO NOT DEVIATE FROM THE ALIGNMENT SHOWN. — F:- INSTALL WIHEELOCK'UNIVERSAL MOUNTING BASE' AT EACH. G. PROVIDE BUSHING OR CLAMP WHERE WIRE ENTERS OR EXITS BOX. H. PROVIDE ADDITIONAL SUPPORT WHERE REQUIRED DY CODE OR AHJ. 2. NAC SUPPLY KRING SHALL BE ROUTED ALONG TRANSVERSE PURLINS AND SUPPORTED WITH WIRE J-HOOKSS ;EQUAL TO EATON BCH12-F3 OR -F4 DEPENDING UPON STEEL FLANGE TYPE). PROVIDE SUPPPORT AT >PACING NO GREATER THAN 54" ON CENTER BETWEEN HOOKS. 3. FOR WIRES TO 3E SUPPORTED TRAVELING PARALLEL WITH NUMBERED STEEL, PROVIDE EATON BCH21-F3 OR -F4 (OR EQUAL) J-HOOKS ON SAME SPACING AS ABOVE. 4, WHERE LOCATED WITHIN 10 FT OF THE FINISHED FLOOR, ALL WARES SHALL BE ENCLOSED IN EMT (3/4" MINIMUM). WHERE WIRES ENTER OR EXIT THIS EMT, PROVIDE LISTED BUSHING, 5. ALL WIRES SERVING, ENTERING OR LOCATED WITHIN THE BOOTHS SHALL BE IN THREADED MINIMUM 3/4" IMC OR RMC. 6. ROOFTOP EQUIPMENT: PROVIDE DEDICATED WIRE LOOP THAT SERVES ONLY EQUIPMENT ABOVE THE ROOFLINE. PRIOR TO CONNECTION TO FIRE ALARM — ---SYSTEM, PROVIDE SURGE SUPPRESSION. 7. COORDINATE LOCATION AND CONNECTION OF FAN SHUTDOWN RELAYS WITH INSTALLER. Antinomy Consulting Engineers Code Consulting - fire Protection • Smoke Control 600 Rinehart Road Suite 2054 Lake Mary, FL 32746-4955 Tel. 321-888-2882 Online: antinomy.com Prepared For: s V I:L � A EC #13001688 %itttiit����e v �; • No 73972 i� STATE OF e e o i F 0 R 1 Doi •• �� °1 111 a iit 0 10/08/21 This document has been digltally signed and sealed by Gregory A. Tabaka, PE on the date adjacent to the seal. Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies. Revisions No. Description Date 0 PERMIT SET 09/07/21 1 NEW BOOTH, RPS6 REALLOC. 10/08/21 COMPLETE ALARM INC. MAVERICK BOATS, INC. Project Address 4551 ST. LUCIE BLVD FT. PIERCE, FL 34946 N 0 FIRE ALARM PARTIAL --- PLAN — ZONE 5 w 0 Project Number ACE0146 z Date 10/08/21 Drawn By G.TABAKA Checked By G.TABAKA LU FA111111 10. EV.1) 0 Scale (UON) 1/8" = 1'-0" r B I A U_ 3 1 I H G F E D C B A 8 7 4 3 2 1 1 2 3 4 5 6 7 TYPICAL NOTES: 1. CEILING MOUNTED HORN/STROBES: r A. SHALL BE EQUIPPED WITH MINIMUM 4"x4"x 2-1/8" BACKBOXES SUSPENDED FROM v 3/4" EMT TYP, PENETRATION: PROVIDE MIN �/4" EMT STUB S1*1.4-(M64) I P?P, P4P ' STRUCTURAL STEEL ON NUMBERED GRID THROUGH WALL WITH BUSHINGS QN BOTH ENDS. AOM FAN %TDOWN LINES. (RAU-SGI1, EF-SG1, EF-SG2) PLENUM P P'2xP4P B. BACKBOXES SHALL BE INSTALLED LEVEL, OPEN FACE DOWNWARDS AT AN ELEVATION S1*1,4W M2i - OF NO HIGHER THAN 29'-10" ABOVE THE FLOOR SIS s1*1.4 (D4) i M r NEAR THE F-GRID LINE AND 25' NEAR THE B- CONNECT TO EXISTIN 120 - 4 - _ - _ - GRID LINE. 120 V CIRCUIT 1*1AW-(M44) C. ALL BACKBOXES SHALL HAVE A FACTORY- NAC EXPANDER SUPERVISION ; MADE 1/4" HOLE AT THE TRUE CENTER OF THE S1*1.4W-(M27) HEAT DETECTOR WALL -MOUNTED - NAC NA,C }[�] TO PROTECT NAC BOOSTER IN LIEU BOX. 1 SK-PS10 S -5499 AOM RPS6 NAC TRIGGER 2 1 ' � I D. ATTACH TO STRUCTURE USING A LISTED OF SMOKE DETECTOR,,,.---,, _ : RPS6 " RP4 0. NA 4w- M4o FAa00 �. r SCREW -TYPE BEAM CLAMP (EQUAL TO CADDY SUPERVISE RPS6 THROUGH RPS4 MONITOR MODULE �/ac.�h�f FAN (SH SHUTDOWN O�.A ' #4QTIBC) TO SUPPORT 1/4"THREADED ROD. "t THREADED ROD SUSPEND BACKBOX FROM WITHIN BOOTH � ' * - USING SECURE ATTACHMENT, SUCH AS I I DOUBLE OR JAM -NUTS, E. ALL BOXES ON AN EAST -WEST LINE SHALL BE AT EQUAL ELEVATION. DO NOT DEVIATE FROM I I WITHIN BOOTH F ' I V4*2 1 ' THE ALIGNMENT SHOWN. <OXP _ r F. INSTALL WHEELOCK'UNIVERSAL MOUNTING -I BASE AT EACH. { 4 G. PROVIDE BUSHING OR CLAMP WHERE WIRE I w I IENTERS OR EXITS BOX. C C - C r H. PROVIDE ADDITIONAL SUPPORT WHERE * REQUIRED BY CODE OR AHJ. 150 Cd 150 Cd 150 Cd 99 dg 1*1.4 (M36)., 99 dB 2. NAC SUPPLY WIRING SHALL BE ROUTED ALONG - r ��, - TRANSVERSE PURLINS AND SUPPORTED WITH I I - r 0 FAN bHUtDOWN WIRE J-HOOKS (EQUAL TO EATON BCH12-F3 OR -F4 <Ol DEPENDING UPON STEEL FLANGE TYPE). PROVIDE I SUPPPORT AT SPACING NO GREATER THAN 54" ON I�� G * CENTER BETWEEN HOOKS. WITHIN BOOTH ,oN V4* 4-1 S1 1.5R 4(D1b) I P,150 RAU-G2 SUPPLY DUCT (ROOF) (NEW BOOTH BELOW, P4P WP r 3. FOR WIRES TO BE SUPPORTED TRAVELING NOT SHOWN) PARALLEL WITH NUMBERED STEEL, PROVIDE WITHIN BOOTH = F V4*3-1 — — _ =_ _ _ —EATON BCH21-F3 OR -F4 (OR EQUAL) J-HOOKS ON O T8P I SAME SPACING AS ABOVE. I C 150 Cd 99 dB I ��S1*1.2-(M11) fU 1-1 ' 2-(M34) AOM ESIN PUMP TANK SHUTDOWN 1 *1.2-(M35) AOM RESIN PUMP TANK SHUTDOWN i I I k 4. WHERE LOCATED WITHIN 10 FT OF THE FINISHED I I P4P, P6P 3/4" IMC UNTIL ABOVE BOOTH, FLOOR, ALL WIRES SHALL BE ENCLOSED IN EMT THEN 3/4" EMT OR FREE WIRE I (3/4" MINIMUM). WHERE WIRES ENTER OR EXIT P4P, P6P, T8P �� THIS EMT, PROVIDE LISTED BUSHING. — — . -- — — — — ._�-, - �_. 5—.ALL WIRES SERVING ENTERING OR LOCATED _,77WITHIN THE BOOTHS SHALL BE IN THREADED MINIMUM 3/4" IMC OR RMC. 6. ROOFTOP EQUIPMENT: PROVIDE DEDICATED WIRE I I I I LOOP THAT SERVES ONLY EQUIPMENT ABOVE THE r ROOFLINE. PRIOR TO CONNECTION TO FIRE ALARM SYSTEM, PROVIDE SURGE SUPPRESSION. - 7. COORDINATE LOCATION AND CONNECTION OF FAN SHUTDOWN RELAYS WITH INSTALLER. r ,I, I C I _ i c_ I in*n A 1 ANTINOMY Antinomy Consulting Engineers Code Consulting - Fire Protection - Smoke Control 600 Rinehart Road Suite 2054 Lake Mary, FL 32746-4955 Tel, 321-888-2882 Online: antinomy.com �n EC #13001688 No 73972 � STATE OF I11 1 S ,,O' R �,0 11 111 10/08/21 This document has been digitally signed and sealed by Gregory A. Tabaka, PE on the date adjacent to the seal. Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies. Revisions No. Description Date 0 PERMIT SET 09/07/21 1 NEW BOOTH, RPS6 REALLOC. 10/08/21 COMPLETE ALARM INC. MAVERICK BOATS, INC. Project Address 4551 ST. LUCIE BLVD FT. PIERCE, FL 34946 FIRE ALARM PARTIAL PLAN - ZONE 6 Project Number ACE0146 Date 10/08/21 Drawn By G.TABAKA Checked By G.TABAKA 110- FA- EV.1) Scale (UON) 1/8" = V-0" i I I H G I F I E I D C B A " J I H G F E 0 C B A Antinomy Consulting Engineers Code Consulting • fire Protection - Smoke Control 600 Rinehart Road Suite 2054 Lake Mary, FL 32746-4955 Tel. 321-888-2882 Online: antinomy.com Prepared For: . l 11 EC #13001688 No 73972 � STATE OF � ��; . A' /IFS 10 O 111111 , % 10/08/21 This document has been digitally signed and sealed by Gregory A. Tabaka, PE on the date adjacent to the seal. Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies. Revisions No. Description Date 0 PERMIT SET 09/07/21 COMPLETE ALARM INC. MAVERICK BOATS, INC. Project Address 4551 ST. LUCIE BLVD FT. PIERCE, FL 34946 FIRE ALARM PARTIAL PLAN — ZONE 7 Project Number ACE0146 — _- Date 10/08/21 Drawn By G.TABAKA Checked By G.TABAKA FA-1 10.7 (REV. 0) Scale (IJON) 1/8" = 1'-0" N ti O O 0 cc r- W z O a. z Q J Q a. J Q W LL 0 Q E 1' 1.3-(M 12) FAN SHUTDOWN I I I JAN. CORR I - 101B WOMEN 103 - V2*1-2 15 ;®;--� 102 V2*1-4 o C I I I I WP I 135 :.w . I f WP WOMEN SHOWER 2 V2*1-1 ® 15 I I' PANEL B� ` 30 L 102A 1 ELEC. I I DISCONNECT BELL FROM FACP NAC #4 AND 104 'Lul = I `'` CONNECT TO RIPS #2 A X POWER, RUN NEW WI, CORR SYNC CIRCUIT FROM F CP NAC #4 AND 2* 2 WOMEN SHOWER 101A CONFIGURE FOR WHEELOCK SYNC SIGNAL. -- - ! 30 F 1-06A C MEN V2*2-3 15 15 Q 106 DATA - lso 6 Q1 V2 2-1 Hr\ 105 1 15 - -- - — — L u C CORR 100 V2*1-5 V2* 1-6 C 15 V2*2-4 S1"1.1-(D2) — RPS2 ` RPS1 WP 135 I , V2*2-5 I L___1 F ACU H G B A TYPIC aL NOTES: 1. CEILING MOUNTED HORN/STROBES: A. SHALL BE EQUIPPED WITH MINIMUM 4"x4"x 2-1/8" BACKBOXES SUSPENDED FROM STRUCTURAL STEEL ON NUMBERED GRID LINES. B. BACKBOXES SHALL BE INSTALLED LEVEL, OPEN FACE DOWNWARDS AT AN ELEVATION OF NO HIGHER THAN 29'-10" ABOVE THE FLOOR NEAR THE F-GRID LINE AND 25' NEAR THE B- GRID LINE. C. ALL BACKBOXES SHALL HAVE A FACTORY - MADE 1/4" 'HOLE AT THE TRUE CENTER OF THE BOX. D. ATTACH TO, STRUCTURE USING A LISTED SCREW -TYPE BEAM CLAMP (EQUAL TO CADDY #4QTIBC) TO SUPPORT 1/4" THREADED ROD. SUSPEND BACKBOX FROM THREADED ROD USING SECURE ATTACHMENT, SUCH AS DOUBLE OR JAM -NUTS. E. ALL BOXES ON AN EAST -WEST LINE SHALL BE AT EQUAL ELEVATION. DO NOT DEVIATE FROM THE ALIGNMENT SHOWN. F. INSTALL WHEELOCK'UNIVERSAL MOUNTING BASE' AT EACH. G. PROVIDE BUSHING OR CLAMP WHERE WIRE ENTERS 0'R EXITE BOX. H. PROVIDE ADDITIONAL SUPPORT WHERE REQUIRED BY CODE OR AHJ. 2. NAC SUPPLY WIRING SHALL BE ROUTED ALONG TRANSVERSE PURLINS AND SUPPORTED WITH WIRE J-HOOKS" (EQUAL TO EATON BCH12-F3 OR -F4 DEPENDING UPON STEEL FLANGE TYPE). PROVIDE SUPPPORT AT SPACING NO GREATER THAN 54" ON CENTER BETWEEN HOOKS. 3. FOR WIRES TO BE SUPPORTED TRAVELING PARALLEL WI-'-H NUMBERED STEEL, PROVIDE EATON BCH21-F3 OR -F4 (OR EQUAL) J-HOOKS ON SAME SPACING AS ABOVE. 4. WHERE LOCATED WITHIN 10 FT OF THE FINISHED FLOOR, ALL WIRES SHALL BE ENCLOSED IN EMT (3/4" MINIMUM). WHERE WIRES ENTER OR EXIT THIS EMT, PROVIDE LISTED BUSHING. ---5ALL WIRES SERVING, ENTERING OR LOCATED WITHIN THE BOOTHS SHALL BE IN THREADED MINIMUM 3/4" IMC OR RMC, 6. ROOFTOP EQUIPMENT: PROVIDE DEDICATED WIRE LOOP THAT SERVES ONLY EQUIPMENT ABOVE THE ROOFLINE. PRIOR TO CONNECTION TO FIRE ALARM SYSTEM, PROVIDE SURGE SUPPRESSION, 7, COORDINATE LOCATION AND CONNECTION OF FAN SHUTDOWN RELAYS WITH INSTALLER. ANTINOMY Antinomy Consulting Engineers Code Consulting • Fire Protection - Smoke Control 600 Rinehart Road Suite 2054 Lake Mary, FL 32746-4955 Tel. 321-888-2882 Online: antinomy.com Prepared For: RM EC #13001688 No 7397244, f i ..0., STATE OF P� ONA I I t l 10% 10/08/21 This document has been digitally signed and sealed by Gregory A. Tabaka, PE on the date adjacent to the seal. Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies. Revisions No. Description Date 0 PERMIT SET 09/07/21 I - COMPLETE ALARM INC. MAVERICK BOATS, INC. Project Address 4551 ST. LUCIE BLVD FT. PIERCE, FL 34946 N CD FIRE ALARM PARTIAL PLAN - ZONE 8 co co UJ Project Number ACE0146 Date 10/08/21 J Drawn By G.TABAKA Checked By G.TABAKA LLJ FA 110 EV.0) Scale (LION) 1/8" = 1'-0" F E It, C I. A Q 8 7 C 5 4 Cl 0 J I H G F E D C B A 22 23 24 '25 i26 27 28 TYPICAL NOTES: A N T I N O 1 1 1. CEILING MOUNTED HORN/STROBES: A. SHALL BE EQUIPPED WITH MINIMUM 4"x4"x PLACE EOLR IN J-BOX ON TERMI AL � � 2-1/8" BACKBOXES SUSPENDED FROM STRIP FOR FUTURE EXPANSION STRUCTURAL STEEL ON NUMBERED GRID 1 0- JAN LINES. _ I [= B. BACKBOXES SHALL BE INSTALLED LEVEL, S1*1.4E-(M2�_ OPEN FACE DOWNWARDS AT AN ELEVATION .ow- - � =w_ _1111111111110 OF NO HIGHER THAN 29'-10" ABOVE THE FLOOR s1*1.4E4MI NEAR THE F-GRID LINE AND 25' NEAR THE B- FA SHUTDOWN .�........�......�_ 1 GRID LINE. ' 1 C SHALL HAVE A FACTORY - MADE 1/4""BHOLE SAT THE TRUE CENTER OF THE 1 I I j 1 BOX. 1 D. ATTACH TO STRUCTURE USING A LISTED _ SCREW -TYPE BEAM CLAMP (EQUAL TO CADDY Antinomy Consulting Engineers Code Consulting •fire Protection •Smoke Control #4QTIBC) TO SUPPORT 1/4" THREADED ROD. 600 Rinehart Road Suite 2054 1 I I SUSPEND BACKBOX FROM THREADED ROD Lake Mary, FL 32746-4955 r USING SECURE ATTACHMENT, SUCH AS Tel. 321-888-2882 online: antinomy.com I DOUBLE OR JAM -NUTS. 1 E. ALL BOXES ON AN EAST -WEST LINE SHALL BE Prepared For: I I I AT EQUAL ELEVATION. DO NOT DEVIATE FROM 4P L,�� THE ALIGNMENT SHOWN. B� — ' — — — — — — — __ _ _ _ _ _ _ _ _ I F. INSTALL WHEELOCK'UNIVERSAL MOUNTING fi BASE AT EACH. 1 - G. PROVIDE BUSHING OR CLAMP WHERE WIRE ENTERS OR EXITS BOX. f C C C H. PROVIDE ADDITIONAL SUPPORT WHERE �-p * n REQUIRED BY CODE OR AHJ. 150 Cd - C 150 Cd 150Cd - _ _ _ 151_ 1 99 dB j 99 dB 1 99 dB I 99 dB 2. NAC SUPPLY WIRING SHALL BE ROUTED ALONG TRANSVERSE PURLINS AND SUPPORTED WITH EC #13001688 WIRE J-HOOKS (EQUAL TO EATON BCH12-F3 OR -F4 1 DEPENDING UPON STEEL FLANGE TYPE). PROVIDE I I I 1 SUPPPORT AT SPACING NO GREATER THAN 54" ON 1� 1 CENTER BETWEEN HOOKS. 3. FOR WIRES TO BE SUPPORTED TRAVELING 1 ( PARALLEL WITH NUMBERED STEEL, PROVIDE — �- - — --� — - — — — I— — I — _--EATON BCH21-F3 OR -F4 (OR EQUAL) J-HOOKS ON � I SAME SPACING AS ABOVE. 4. WHERE LOCATED WITHIN 10 FT OF THE FINISHED 1 I j 1 FLOOR, ALL WIRES SHALL BE ENCLOSED IN EMT (3/4 MINIMUM). WHERE WIRES ENTER OR EXIT 1 THIS EMT, PROVIDE LISTED BUSHING. WIRES SERVING ENTERING OR LOCATED 1 WITHIN THE BOOTHS SHALL BE IN THREADEDI 1 MINIMUM 3/4" IMC OR RMC. ��� c��. "�'EIV e'�.� No 73972 I 1 1 6. ROOFTOP EQUIPMENT: PROVIDE DEDICATED WIRE '-7 I r LOOP THAT SERVES ONLY EQUIPMENT ABOVE THE ROOFLINE. PRIOR TO CONNECTION TO FIRE ALARM SYSTEM PROVIDE SURGE SUPPRESSION. E'� - - -j- - - - - - - - - - - - - - - - - - - - - - ' STATE OF I j 1 7. COORDINATE LOCATION AND CONNECTION OF FAN ,�0NA.... SHUTDOWN RELAYS WITH INSTALLER. ���+�� i I%�` 10/08/21 1 This document has been digitally signed and sealed by Gregory A. ' Tabaka, PE on the date adjacent to the seal. Printed copies of this ' document are not considered signed and sealed and the signature a I I i 1 must be verified on any electronic copies. 1 - Revisions i I 1 150 Cd 150 Cd 99 dB 99dB BREAK 107 J I H 135 V2*2-8 � c V2*2-7 75 1 S1*1.1-(M2) C G F E D I C i B COMPLETE ALARM INC. MAVERICK BOATS, INC. Project Address 4551 ST. LUCIE BLVD FT. PIERCE, FL 34946 N FIRE ALARM PARTIAL O c CD C) PLAN - ZONE 9 CM Project Number ACE0146 0 Date 10/08/21 Drawn By G.TABAKA Checked By G.TABAKA a FA 11 0U_ J EV.0) U_ Scale (uoN) j/$" — 1'-0" A LL 8 7 6 CEJ 1 4 F 2 1 J I I H G r2 (1 30 31 F E D I C 32 ( 33), 34 3' � 1 J I IH IG I F I E I D I C B A TYPICAL NOTES: 1. CEILING MOUNTED HORN/STROBES: A. SHALL BE EQUIPPED WITH MINIMUM 4"x4"x 2-1/8" BACKBOXES SUSPENDED FROM STRUCTU';ZAL STEEL ON NUMBERED GRID LINES. B. BACKBOXES SHALL BE INSTALLED LEVEL, OPEN FACIE DOWNWARDS AT AN ELEVATION — - OF NO HIGHER THAN 29'-10" ABOVE THE FLOOR NEAR THE F-GRID LANE AND 25' NEAR THE B- GRID LINE. C. ALL BACKI3OXES SHALL HAVE A FACTORY - MADE 1/4" HOLE AT THE TRUE CENTER OF THE BOX. D. ATTACH TO STRUCTURE USING A LISTED SCREW -TYPE BEAM CLAMP (EQUAL TO CADDY #4QTIBC) TO SUPPORT 1/4" THREADED ROD, SUSPEND IBACKBOX FROM THREADED ROD USING SEC/URE ATTACHMENT, SUCH AS DOUBLE OR JAM -NUTS. E. ALL BOXES ON AN EAST -WEST LINE SHALL BE AT EQUAL ELEVATION. DO NOT DEVIATE FROM THE ALIGNMENT SHOWN. F. INSTALL VIHEELOCK'UNIVERSAL MOUNTING BASE' AT EACH. G. PROVIDE.I3USHING OR CLAMP WHERE WIRE ENTERS OR EXITS BOX. H. PROVIDE ADDITIONAL SUPPORT WHERE REQUIRED BY CODE OR AHJ. 2. NAC SUPPLY WIRING SHALL BE ROUTED ALONG TRANSVERSE PURLINS AND SUPPORTED WITH WIRE J-HOOKS (EQUAL TO EATON BCH12-F3 OR -F4 DEPENDING UPON STEEL FLANGE TYPE). PROVIDE SUPPPORT AT SPACING NO GREATER THAN 54" ON CENTER BETWEEN HOOKS. 3. FOR WIRES TD BE SUPPORTED TRAVELING PARALLEL WITH NUMBERED STEEL, PROVIDE -_-__-EATON BCH2'1-F3 OR -F4 (OR EQUAL) J-HOOKS ON SAME SPACING AS ABOVE. 4. WHERE LOCATED WITHIN 10 FT OF THE FINISHED FLOOR, ALL WIRES SHALL BE ENCLOSED IN EMT (3/4" MINIMUM). WHERE WIRES ENTER OR EXIT THIS EMT, PROVIDE LISTED BUSHING. 5. ALL WIRES SERVING, ENTERING OR LOCATED WITHIN THE BOOTHS SHALL BE IN THREADED MINIMUM 3/4" IMC OR RMC. 6. ROOFTOP EQUIPMENT: PROVIDE DEDICATED WIRE LOOP THAT SERVES ONLY EQUIPMENT ABOVE THE ROOFLINE. PRIOR TO CONNECTION TO FIRE ALARM SYSTEM, PROVIDE: SURGE SUPPRESSION. 7. COORDINATE LOCATION AND CONNECTION OF FAN SHUTDOWN RELAYS WITH INSTALLER. 1 Antinomy Consulting Engineers Code Consulting • Fire Protection • Smoke Control 600 Rinehart Road Suite 2054 Lake Mary, FL 32746-4955 Tel. 321-888-2882 Online: antinomy.com Prepared For: k, EC #13001688 `���titti������ G,\Pc o iE �N No 73972 STATE OF R 0; % \ \ �NA � o i i i r 1 o/os/21 This document has been digitally signed and sealed by Gregory A. Tabaka, PE on the date adjacent to the seal. Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies. Revisions No. Description Date 0 PERMIT SET 09/07/21 i COMPLETE ALARM INC. MAVERICK BOATS, INC. Project Address 4551 ST. LUCIE BLVD FT. PIERCE, FL 34946 _ N ti O O FIRE ALARM PARTIAL co Ir PLAN — ZONE 10 w z 0 N Project Number ACE0146 z _ — - Date 10/08/21 d Drawn By G.TABAKA Checked By G.TABAKA J LU FAM1 10. 1 v.0) o Scale (LION) 1/8" = V-0" 1 J I I H I G I F E I D I C B I A LEGEND: 8 X - SYSTEM INPUT CAUSES SYSTEM OUTPUT FUNCTION • W - SAME AS X, EXCEPT ACTIVATION IS VIA FLOW SWITCH DRY CONTACTS (NOT PROGRAMMING) • 0 - OPTIONAL RESPONSE: SYSTEM INPUT MAY CAUSE SYSTEM OUTPUT FUNCTION • - - SEE RESPONSES BELOW FOR THIS GROUP. ### ALARM INPUTS 100 SPOT -STYLE SMOKE DETECTOR 7 110 SPOT -STYLE HEAT DETECTOR 120 WATER FLOW SWITCH 130 MANUAL PULL STATION 140 (RESERVED) 150 (RESERVED) 160 (RESERVED) SUPERVISORY INPUTS 400 SPRINKLER TAMPER SWITCH 410 1 SPRINKLER TAMPER SWITCH - AT BACKFLOW 420 DUCT SMOKE DETECTOR 430 (RESERVED) 440 (RESERVED) 6 440 (RESERVED) 440 (RESERVED) TROUBLE INPUTS 501 GROUND FAULT 502 SHORT CIRCUIT 503 OPEN CIRCUIT 504 BATTERY FAIL 505 A/C POWER FAIL 506 NAC EXPANDER FAIL 507 (RESERVED) 508 MISC. GENERAL SYSTEM TROUBLE 509 (RESERVED) 5 510 (RESERVED) 4 3 2 1 ANNUNCIATION INOTIFICATION may. v�4y o I C_ RV FIRE SAFETY FUNCTIONS ATA2:A3 B1: B2: B3 Cti C2: C3 D E F G H J K L M N X: X: X X Xi X X X X X X X X X X IX X: : : 1 X: , : X 'X X X X X X X X X X X X ' X I A14 A3 131! B2 B31 C1i C2: C31 D E F G H J _K1 L M N FIRE ALARM SEQUENCE OF OPERATIONS NOT TO SCALE I SLC DEVICE SCHEDULE - SK PROTOCOL (EXISTING DEVICES) SK. l - AUX POWER ADDRESS - MODEL PROGRAM LABEL ASSOCIATED FUNCTIONS SOURCE 1 - S1*1-0 SK-ISO-6 (NO LABEL OR ADDRESS) S1*1.1-D1 SK-PHOTO-W (EXISTING LABEL) S1*1.1-D2 SK-PHOTO-W (EXISTING LABEL) S1*1,1-M1 SK-PULL-DA (EXISTING LABEL) S1*1.1-M2 SK-PULL-DA (EXISTING LABEL) 1.2 S1*1.2-M3 SK-PULL-DA (EXISTING LABEL) S1*1.2-M5 SK-PULL-DA (EXISTING LABEL) S1*1,2-M6 SK-PULL-DA (EXISTING LABEL) S1*1.2-M7 SK-RELAY (EXISTING LABEL) FAN SHUTDOWN S1*1,2-M8 SK-PULL-DA (EXISTING LABEL) S1*1,2-M9 S1*1.2-M10 SK-RELAY SK-RELAY (EXISTING LABEL) (EXISTING LABEL) FAN SHUTDOWN FAN SHUTDOWN S1*1.2-M11 SK-PULL-DA (EXISTING LABEL) S1*1.2-M34 SK-RELAY (EXISTING LABEL) RESIN PUMP TANK SHUTDOWN S1*1.2435 SK-RELAY (EXISTING LABEL) RESIN PUMP TANK SHUTDOWN 1.3 S1*1.3-M12 SK-RELAY (EXISTING LABEL) FAN SHUTDOWN S1*1.3-M14 SK-RELAY (EXISTING LABEL) FAN SHUTDOWN S1*1.3-M15 SK-PULL-DA (EXISTING LABEL) f S1*1.3-M16 SK-RELAY (EXISTING LABEL) FAN SHUTDOWN S1*1,3417 SK-RELAY (EXISTING LABEL) FAN SHUTDOWN S1*1.3418 SK-PULL-DA (EXISTING LABEL)- S1*1.3-M19 SK-RELAY (EXISTING LABEL) FAN SHUTDOWN S1*1,3-M20 SK-RELAY (EXISTING LABEL) FAN SHUTDOWN S1*1.3421 SK-PULL-DA (EXISTING LABEL) S1*1.3-M22 I SK-PULL-DA (EXISTING LABEL) SLC DEVICE SCHEDULE - SK PROTOCOL (NEW DEVICES) SK AUX POWER ADDRESS MODEL PROGRAM LABEL ASSOCIATED FUNCTIONS SOURCE 1.3 S1*1.3-M53 SK-PULL-DA P/S @ S. WAREHOUSE WEST DOOR S1*1.3-M54 SK-PULL-DA P/S @ S. WAREHOUSE EAST DOOR 1.4 S1*1.4-M60 SK-MONITOR TIS @ EXPANSION NW GEL BOOTH GEL BOOTH SPKR TAMPER S1*1.4-M64 SK-RELAY FAN SHUTDOWN, EXPANSION SW FAN SHUTDOWN GEL BOOTHS 1.4E -I*IAE-D5 SK-HEAT"W HID-@iRPS3 S1*1.4E-M$0, M81 SK-MONITOR-2 ) (MATCH FUNCTIONS ;SPKR FLOWS 5 I @ EXPANSION � SPKR TAMPERS 5 @ EXPANSION 1 AW S1*1.4W-D4 SK-HEAT-W H/D @ RPS4, RPS6 S1*1.4W-M40 SK-RELAY NAC TRIGGER @ RPS6 FAN SHUTDOWN S1*1.4W-M45 SK-CONTROL NAC TRIGGER @ RPS6 RPS6 NAC TRIGGER N6*1-1 S1*1.4W-M63 SK-PULL-DA P/S @ EXPANSION, GRID A-1 S1*1.4W-M65 SK-RELAY FAN SHUTDOWN, RAU-SP1 FAN SHUTDOWN S1*1.4W-M66 SK-RELAY FAN SHUTDOWN, EF-SP1 FAN SHUTDOWN S1*1.4W-M67 SK-RELAY FAN SHUTDOWN, EF-SP2 FAN SHUTDOWN 1.5 S1*1.5-D3 SK-PHOTO-W SID @ EXPANSION ELEC RM. S1*1.5-M69 SK-MONITOR NAC TROUBLE @ RPS5 NAC TROUBLE MONITOR S1*1.5-M99 SK-MONITOR AIM FOR P/S @ EXPANSION PULL STATIONS AT EXPANSION 1.5R S1*1.5R-D6 SK PHOTO-R-W RAU-SP1 SUPPLY DUCT (ROOF) S1*1.5R-D7 SK-PHOTO-R-W RAU-SG1 SUPPLY DUCT (ROOF) S1*1.5R-D8 SK-PHOTO-R-W RAU-S1 SUPPLY DUCT (ROOF) S1*1.5R-D9 S1*15R-D1-0 SK-PHOTO-R-W RAU-BG1 SUPPLY DUCT (ROOF) RAU-G2 SUPPLY DUCT (ROOF) SK-PHOTO R-W 1.5W S1*1.5W-M55 SK-PULL-DA P/S @ EXPANSION, GRID G-17 S1*1.5W-M56 SK-PULL-DA P/S @ EXPANSION, GRID F-13 S1*1.5W-M57 SK-RELAY FAN SHUTDOWN RAU-S1 FAN SHUTDOWN S1*1.5W-M58 SK-PULL-DA P/S @ EXPANSION, GRID F-17 S1*1.5W-M59 SK-PULL-DA P/S @ EXPANSION, GRID F-6 S1*1.5W-M61 SK-RELAY FAN SHUTDOWN, EXPANSION NW GEL BOOTH P/S @ EXPANSION, GRID F 1 _ FAN SHUTDOWN S1*1.5W-M62 SK-PULL-DA NOTE: REVISE ADDRESSES AND LABELS AS NEEDED. PROVIDE CORRECT INFORMATION ON RECORD DOCUMENTS. SLC DEVICE SCHEDULE - SK PROTOCOL (EXISTING DEVICES) SK AUX POWER ADDRESS MODEL PROGRAM LABEL ASSOCIATED FUNCTIONS SOURCE 1.4 - S1*1.4-M23 SK-PULL-DA (EXISTING LABEL) S1*1.4-M36 SK-RELAY (EXISTING LABEL) _ FAN SHUTDOWN 1.4E S1*l.4E-M4 SK-RELAY ;(EXISTING LABEL) FAN SHUTDOWN S1*14E-M13 'SK-RELAY (EXISTING LABEL) FAN SHUTDOWN S1*1AE-M28 SK-PULL-DA (EXISTING LABEL) S1*1.4E-M29 SK-PULL-DA (EXISTING LABEL) S1*1AE-M30 SK-PULL-DA (EXISTING LABEL) S1*1AE-M31 SK-PULL-DA (EXISTING LABEL) S1*1.4E-M32 SK-MONITOR ! (EXISTING LABEL) SPKR MAIN ## FLOW S1*1.4E-M33 SK-MONITOR (EXISTING LABEL) SPKR MAIN ## TAMPER_ S1*1.4E-M41 SK-MONITOR (EXISTING LABEL) NAC EXPANDER SUPERVISION S1*1.4E-M42 SK-RELAY ,(EXISTING LABEL) FAN SHUTDOWN S1*1.4E-M43 SK-RELAY (EXISTING LABEL) FAN SHUTDOWN S1*1AE-M46 SK-RELAY (EXISTING LABEL) _ FIRE WATER FLOW BELL S1*1.4E-M47 SK-MONITOR (EXISTING LABEL) TAMPERS AT BACKFLOW S1*1.4E-M48 SK-MONITOR (EXISTING LABEL) SPKR MAIN ## FLOW S1*1.4E-M49 SK-MONITOR _ (EXISTING LABEL) SPKR MAIN ## TAMPER S1*1.4E-M50 SK-MONITOR (EXISTING LABEL) SPKR MAIN ## FLOW S1*1.4E-M51 SK-MONITOR (EXISTING LABEL) SPKR MAIN ## TAMPER S1*1.4E-M5'2 LSK-RELAY (EXISTING LABEL) FAN SHUTDOWN ---- ------ II AW S1*1.4W-M24 SK-PULL-DA (EXISTING LABEL) - S1*1.4W-M25 SK-PULL-DA (EXISTING LABEL) S1*1.4W-M26 SK-PULL-DA (EXISTING LABEL) _ S1*1.4W-M27 SK-PULL-DA (EXISTING LABEL) FAN SHUTDOWN S1*1.4W-M37 SK-RELAY (EXISTING LABEL) S1*1.4W-M38 SK-RELAY (EXISTING LABEL) L,AKL) FAN SHUTDOWN S1*1AW-M39 SK-RELAY -,-(EXISTING- FAN SHUTDOWN S1*1.4W-M44 SK-MONITOR RPS4/RPS6 TROUBLE NAC EXPANDER SUPERVISION ANTINOMY Antinomy Consulting Engineers Code Consulting - Fire Protection - Smoke Control 600 Rinehart Road Suite 2054 Lake Mary, FL 32746-4955 Tel. 321-888-2882 Online: antinomy.com Prepared For: 6tll L A rr'' Rw EC #13001688 `�111111rrrrrr� Z IQ7e No 73972 0 :-7 STATE OF i�.n • A, •• �� �r 11 11111 `` 10/08/21 This document has been digitally signed and sealed by Gregory A. Tabaka, PE on the date adjacent to the seal. Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies. Revisions No. Description Date 0 IPERMITSET 09/07/21 1 1 NEW BOOTH, RPS6 REALLOC. 10/08/21 COMPLETE ALARM INC. MAVERICK BOATS, INC. Project Address 4551 ST. LUCIE BLVD FT. PIERCE, FL 34946 SEQUENCE OF OPERATIONS AND DEVICE LABELS Project Number ACE0146 Date 10/08/21 Drawn By G.TABAKA Checked By G.TABAKA FA-_400 (REV. 1) Scale (UON) 12, = 1'_0" N 00 0 0 J I I I H G F E D C B A F_ J I I H G I F E I D I C B ANTINOMY 8' EOLR 0< 0< V6*7-2 V6*7-1 EOLR 1771<1 V6*6-1 EOLR X V6*5-1 7 EOLR X V6*4-1 EOLR X V6*3-1 EOLR RPS6 2 6 FA-700 5 4 3 2 S1 *1.4W-(M45) V6*1-1 - SS 0 EOLR 0< 0< V5*7-2 V5*7-1 EOLR ° V5*6-6 V5*6-5 V5*6-4 V5*6-3 V5*6-2 V5*6-1 EOLR V5*5-6 V5*5-5 V5*5-4 V5*5-3 V5*5-2 V5*5-1 EOLR V5*4-5 V5*44 V5*4-3 V5*4-2 V5*4-1 EOLR V5*3-5 V5*34 V5*3-3 V5*3-2 V5*3-1 i - It�IV 0`1 9< 9<l 9< k"<I V5*2-7 V5*2-6 V5*2-5 V5*24 V5*2-3 V5*2-2 V5*2-1 EOLR V5*1-6 V5*1-5 V5*14 V5*1-3 V5*1-2 V5*1-1 (SPARE) V4*4-1 0< EOLR °� EOLR V4*3-1 V3*3-2 V3*3-1 0< EOLR EOLR o o V4*2-1 V3*2-1 V2*2-8 V2*2-7 V2*2-6 V2*2-5 - X., EOLR 0< Z< EOLR V4*1-1 V3*1-2 V3*1-1 I V2*1-6 V2*1-5 (SPARE) t�PS3 V1*3-5 V1*3-4 V1*3-3 V1*3-2 V1*3-1 V1*2-6 V1*2-5 V1*24 V1*2-3 V1*2-2 V1*2-1 EOLR o V1*1-5 V1*1-4 V1*1-3 V1*1-2 V1*1-1 FIRE ALARM RISER D NOT TO SCALE IAGRAM - NAC LJ SS AOM V2*A-1 S 1 *1.4E-(M46) (SPARE) V2*34 V2*3-3 V2*3-2 V2*3-1 V2*2-4 V2*2-3 V2*2-2 V2*2-1 . \®s 1 ads 1 V2*1-4 V2*1-3 V2*1-2 V2*1-1 EOLR — EOLR VO*3-5 VO*3-4 VO*3-3 VO*3-2 VO*3-1 EOLR VO*2-6 VO*2-5 VO*24 VO*2-3 VO*2-2 VO'21 QQ S< 011 911 VO*1-6 V0*1-5 VO*1-4 VO*1-3 VO*1-2 V0*1-1 ss FA-500 J I I H I G ( F I E D C B SS (DISCONNECT BELL CIRCUIT FROM FACP AND RESUPPLY FROM RPS2 AUX POWER ALWAYS -ON CIRCUIT. CONNECT NEW CIRCUIT FROM FACP TO RPS5 INPUT TRIGGER.) A Antinomy Consulting Engineers Code Consulting • fire Protection - Smoke Control 600 Rinehart Road Suite 2054 Lake Mary, FL 32746-4955 Tel. 321-888-2882 Online: antinomy.com Prepared For: ygfi r EC #13001688 No 73972 •�/�- i .7 "0 ;• STATE OFlV;: "// // 11111 \\ 10/08/21 This document has been dighally signed and sealed by Gregory A. Tabaka, PE on the date adjacent to the seal, Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies. Revisions No. Description Date 0 PERMIT SET 09/07/21 1 NEW BOOTH, RPS6 REALLOC. 10/08/21 COMPLETE ALARM INC. MAVERICK BOATS, INC. Project Address 4551 ST. LUCIE BLVD FT. PIERCE, FL 34946 FIRE ALARM RISER N C DIAGRAM - NAC T Cr Q Project Number ACE0146 z Date 10/08/21 Drawn By G.TABAKA Q Checked By G.TABAKA Lu FA- 500 LU J w (REV. 1)Cf' Scale (LION)1" = 60'-011 a _�J J I I H G F E D I C I B I A ANTINOMY 8 7 6 5 4 3 2 1 1 1 I 1 1 1 1 ss S1*1.5R-0.2 S1*1.5R-1(D6) S1*1.51R-2(1]17) S1*1.5R-3(D8) S1*1,5R-4(D9) AIM AIM O 1+ 9 AOM 9 � AIM AOM O o O 0 0 S1*1.5-(M99) S1*1.5-(M69) S1*1.5-(D3) SI*1.5W-(M55) S1*1.5W-(M56) S1*1,5W-(M57) S1*1.5W-(M58) S1*1.5W-(M59) SI*1.4-(M60) S1*1.5W-(M61) S1*1.5W-(M62) IDC ` S1*1.5-M99(IDC#1)S1*1.5-M99(IDC#2) S1*1.5-M99(IDC#3) S1*1.5-M99(IDC#4) S1*1.5-M99(IDC#5) S1*1.5-M99(IDC#6) S1*1.5-M99(IDC#7) AOM Z� AQM S1 *1 AW-(M66) S1 *1,4W-(M45) V6*1-1 AOM AOM O Q S1*1.4W-(M67) S1*l.4W-(M65) S1*1.4W-(D4) S1*1.4W-(M63) - AQM AOM AQM AQM AIM S1*1.4W-(M39) S1*1.4W-(M38) S1*1.4W-(M24) S1*1.4W-(M37) S1*1.4W-(M25) S1*1.4-(M36) S1*1.4W-(M26) S1*1.4W-(M44) S1*1.4W-(M27) S1 *1.4E-(M52) SI*1.4E-(M50) S1*1.4E-(M51) ® AQM O AOM O i AIM O AIM O M � AIM O S1*1.4E-(D5) S1*1.4E-(M13?) S1*1.4E-(M4) SI*1.4E-(M48) S1*1.4E-(M49) V2*A-1 S1*1.4E-(N M81) O O O SS O O O O S1*1.4-(M23) SI*1.4E-(M41) S1*1.4E-(M42) S1*1.4E-(M43) S1*1.4E-(M28) S1*1.4E-(M29) S1*1.4E-(M30) S1*1.4E-(M31) S1*1.4E-(M46) S1*1.4E-(M32) S1*1.4E-(M33) S1*1.4E-(M47) 2 S 1 *1.3-(M53) S 1 *1.3-(M54) - AOM am a AQM O a aO S1*1.3-(MI2) S1*1.3-(M14) SI*1.3-(MI5) S1*1.3-(M16) S1*1.3-(M17) S1*1.3-(M18) S1*1.3-(M19) S1*1.3-(M20) S1*1.3-(M21) S1*1.3-(M22) aO O AOM S1*1.2-(M3) S1*1.2-(M5) S1*1.2-(M6) SI*1,2-(M7) S1*1.2-(M8) SI*1.2-(M9) S1*1.2-(M10) S1*1.2-(M11) S1*1.2-(M34) C1*1.2-(M35r V S1*1.1-(DI) S1*1,1-(D2) S1*1.1-(M1) SI*1.1-(M2) FIRE ALARM RISER DIAGRAM - SLC NOT TO SCALE J I I H G F I E D C B A Antinomy Consulting Engineers Code Consulting - fire Protection - Smoke Control 600 Rinehart Road Suite 2054 Lake Mary, FL 32746-4955 Tel. 321-888-2882 Online: antinomy.com Prepared For: tT F 3 , N"N il"�. EC #13001688 ```111111111//// C>%� \ ENS .,�•6 i��' No 73972 ' `40 STATE OF • c • �� 01 I I lil l� ``` 10/08/21 his document has been digitally signed and sealed by Gregory A. abaka, PE on the date adjacent to the seal. Printed copies of this ocument are not considered signed and sealed and the signature rust be verified on any electronic copies. Revisions No. Description Date 0 PERMIT SET 09/07/21 1 NEW BOOTH, RPS6 REALLOC. 10/08/21 COMPLETE ALARM INC. MAVERICK BOATS, INC. Project Address 4551 ST. LUCIE BLVD FT. PIERCE, FL 34946 N W FIRE ALARM RISER DIAGRAM - SLC U J Project Number ACE0146 Date 10/08/21 Drawn By G.TABAKA Checked By G.TABAKA N LU FA-501 (REV. 1) Scale (uoN) 1 " = 60'-0" Q 7 J H EXISTING (EXPANDED) FRCP CALCULATIONS G F A III '. �• �; E 0 C B A 8 7 6 5 4 3 FRCP LOADS PART 1 - PANEL AND MODULES DEVICES • MANUFACTURER MODEL LOOP COUNT ALARM CURRENT STANDBY CURRENT EACH SUBTOTAL EACH SUBTOTAL • SILENT KNIGHT SK-5860 1 20.0 mA 20.0 mA 25.0 mA 25.0 mA • SILENT KNIGHT 5808 1 365.0 mA 365.0 mA 170.0 mA 170.0 mA 385.0 mA 195.0 mA 1 1 • SILENT KNIGHT SK-ISO-6 1 1 102.0 mA 102.0 mA 2.7 mA 1 2.7 mA 102.0 mA 2.7 mA 1.1 • SILENT KNIGHT SK-PULL-DA 1.1 2 0.4 mA 0.8 mA 0.4 mA 0.8 mA • SILENT KNIGHT SK-PHOTO-W 1.1 2 2.0 mA 4.0 mA 0.3 mA 0.6 mA 4.8 mA 1.4 mA 1.2 • _ SILENT KNIGHT SK-RELAY 1.2 5 0.3 mA 1.3 mA 0.3 mA 1.3 mA • SILENT KNIGHT SK-PULL-DA 1.2 5 0.4 mA 1.9 mA 0.4 mA 1.9 mA 3.2 mA 3.2 mA 1.3 • SILENT KNIGHT SK-RELAY 1.31 61 0.3 mA 1.6 mA 0.3 mA 1.6 mA • SILENT KNIGHT SK-PULL-DA 1.31 61 0.4 mA 1 2.3 mA 0.4 mA 2.3 mA 3.8 mA 3.8 mA 1.4 • _ SILENT KNIGHT SK-RELAY 1.4 2 0.3 mA 0.5 mA 0.3 mA 0.5 mA • SILENT KNIGHT SK-MONITOR 1.4 1 0.4 mA 0.4 mA 0.4 mA 0.4 mA • SILENT KNIGHT j SK-PULL-DA 1.4 1 0.4 mA 0.4 mA 0.4 mA 0.4 mA 1.3 mA 1.3 mA 1.4E • SILENT KNIGHT SK-HEAT-W 1.4E 1 2.0 mA 2.0 mA 0.2 mA 0.2 mA • SILENT KNIGHT SK-RELAY 1.4E 1.4E 6 0.3 mA 1.6 mA 0.3 mA 1.6 mA • SILENT KNIGHT SK-MONITOR 8 0.4 mA 3.0 mA 0.4 mA 3.0 mA • SILENT KNIGHT SK-MONITOR-2 1.4E 1 0.8 mA 0.8 mA 0.8 mA 0.8 mA • SILENT KNIGHT SK-PULL-DA 1.4E 4 0.4 mA 1.5 MAI 0.4 mA 1.5 mA 8.9 mA 7.1 mA 1AW • SILENT KNIGHT SK-HEAT-W 1AW 1 2.0 mA 2.0 mA 0.2 mA 0.2 mA • SILENT KNIGHT SK-RELAY 1AW 7 0.3 mA 1.8 mA 0.3 mA 1.8 mA • SILENT KNIGHT SK-CONTROL 1AW 1 0.4 mA 0.4 mA 0.4 mA 0.4 mA • SILENT KNIGHT SK-MONITOR 1AW 1 0A mA 0.4 mA 0.4 mA 0.4 mA • SILENT KNIGHT SK-PULL-DA 1AW 5 0.4 mA 1.9 mA 0.4 mA 1.9 mA 6.5 mA 4.7 mA 1.5 • SILENT KNIGHT SK-MONITOR 1.5 1.5 2 0.4 mA 0.8 mA 0.4 mA 0.8 mA • SILENT KNIGHT j SK-PHOTO-W 1 2.0 mA 2.0 mA 0.3 mA 0.3 mA 2.8 mA 1.1 mA 1.5R • SILENT KNIGHT SK-PHOTO-R-W 1.5R 51 2.0 mA 1 10.0 mA 0.3 mA 1.5 mA 10.0 mA 1.5 mA 1.5W • SILENT KNIGHT SK-RELAY 1.5W 2 0.3 mA 0.5 mA 0.3 mA 0.5 mA • SILENT KNIGHT SK-PULL-DA 1.5W 5 0.4 mA 1.9 mA 0.4 mA 1.9 mA 2.4 mA 2.4 mA SUBTOTAL'PART V- INTERNAL AND ADDRESSABLE COMPONENTS 530.6 mA 224.1 mA, FRCP LOADS PART 2 - AN AND AUX POWER • MANUFACTURER MODEL TAP - ALARM CURRENT COUNT EACHI SUBTOTAL STANDBY CURRENT EACH I SUBTOTAL 0 - 1 • WHEELOCK HSC 1 150 Cd 99 dB 6 242.0 mA 1,452.0 mkF 0.0 mA 0.0 mA 1,452.0 mA 0.0 mA 2 • WHEELOCK HSC 150 Cd 99 dB 6' 242.0mAJ 1,452.0mAJ 0.0 mA 0.0 mA 1,452.0 mA 0.0 mA 3 • WHEELOCK HSC 150 Cd 99 dB 61 242.0 mA 1,452.0 mA 0.0 mA 0.0 mA 1,452.0 mA 0.0 mA 4,356.0 mA 0.0 mA SUBTOTAL'PART 2'- VISIBLE AND AUXILIARY POWER 4,356.0 mA 0.0 mA FACP LOAD SUMMARY DESCRIPTION CURRENT BATTERY CAPACITY PART 1 PART 2 TOTAL TIME (HR) LOAD (A-HR) A-HR x 1.25 ALARM CONDITIONS 530.0 mA 4,356.0 mA 4,886.0 mA 0.083 0.407 0.509 _ _ STANDBY CONDITIONS 223.5 mA 0.0 mA 223.5 mA 24.000 5.363 6.704 ALARM + STANDBY CAPACITY BATTERY CAPACITY T 5.776 7.213 MINIMUM BATTERY SIZE (AMP-HR) NO CHANGE FROM MINIMUM 2x17 A-HR BATTERIES REQ'D FOR SK-5808. 1 J I H L SLC POINT -LOAD CALCULATIONS PLAN LABEL MODEL WIRE_ PROPERTIES RESIST. CAPACIT. LENGTH!, TYPE (D&FT) (pF/kFT) CAPACIT. (pF) ALARM CURRENT VOLTAGE DROP 1 1 S1*1-0(0) SK-ISO-6 20 ft T8P 8.450 0.031 0.0006 102.0 mA 0,034 V 20 ft 0.0006 102.0 mA 0,034 V 1.1 S1*1.1-(D1) SK-PHOTO-W 20 ft T8P 8.450 0.031 0,0006 2.0 mA 0,002 V S1*1.1-(D2) SK-PHOTO-W 20 ft T8P 8.450 0.031 0,0006 2.0 mA 0.002 V S1*1.1-(M1) SK-PULL-DA 85 ft T8P 8.450 0.031 0.0026 0.4 mA 0.007 V S1*1.1-(M2) SK-PULL-DA 110 ft T8P 8.450 0.031 0,0034 0.4 mA 0,009 V 1.1 235 ft 0.0073 4.8 mA 0.019 V 1.2 S1*1.2-(M3) SK-PULL-DA 70 ft T8P 8,450 0.031 0.0022 0.4 mA 0,004 V S1*1.2-(M5) SK-PULL DA 120 ft T8P 8.450 0.031 0.0037 0.4 mA 0,006 V S1*1.2-(M6) SK-PULL-DA 120 ft T8P 8.450 0.031 0,0037 0.4 mA 0,006 V S1*1.2-(M7) SK-RELAY 50 ftJ T8P 8.450 0.031 0.0016 0.3 mA 0,003 V S1*1.2-(M8) SK-PULL-DA 90 ft I! T8P 8.45011 0.031 0.0028 0.4 mA 0.005 V S1*1.2-(M9) SK-RELAY 20 ft' T8P 8.4501 0.031 0.0006 0.3 mA 0.001 V S1*1.2-(M10) SK-RELAY 80 ft T8P 8.4501 0.031 0.0025 0.3 mA 0.004 V S1*1.2-(M11) SK-PULL-DA 70ftl T8P 8.4501 0.0311 0.0022 0.4 mA 0.004 V S1*1.2-(M34)_- S1*1.2-(M35) SK-RELAY SK-RELAY 60 ft! T8P 20 ft T8P 8.4501 8.4501 0.031' 0.0311 0.0019 0.0006 0.3 mA 0.3 mA 0.003 V 0.001 V 1.2 700 ft 0.0217 3.2 mA 0.038 V 1.3 S1*1.3-(M12) SK-RELAY 80 ft T8P 8.450 0.031 0.0025 0.3 mA 0,005 V S1*1.3-(M14) SK-RELAY 160 ft T8P 8.450 0.031 0.0050 0.3 mA 0.010 V S1*1.3-(M15) SK-PULL-DA 35 ft T8P 8.450 0.031 0.0011 0.4 mA 0.002 V S1*1,3-(M16) SK-RELAY 25 ft T8P 8.450 0.031 0.0008 0.3 mA 0.002 V S1*1.3-(M17) SK-RELAY 60 ft T8P 8.450 0.031 0.0019 0.3 mA 0.004 V S1*1.3-(M18) SK-PULL-DA 70 ft T8P 8.450 0.031 0.0022 0.4 mA 0.005 V S1*1.3-(M19) SK-RELAY 55 ft T8P 8.450 0.031 0.0017 0.3 mA 0.004 V S1*1.3-(M20) SK-RELAY 55 ft T8P 8.450' 0.031 0.0017 0.3 mA 0.004 V S1*1.3-(M21) SK-PULL-DA 70 ft T8P 8,4501 0.031 0.0022 0.4 mA 0.005 V S1*1.3-(M22) SK-PULL-DA 120 ft T8P 8.45011 0.031 0.0037 0.4 mA 0.008 V S1*1.3-(M53) SK-PULL-DA 30 ft T8P 8.4501 0.031 0.0009 0.4 mA 0.002 V S1*1.3-(M54) SK-PULL-DA 60 ft T8P 8.4501 0.031 0.0019 0.4 mA 0.004 V 1.3 820 ft 0.0254 3.8 mA 0.053 V 1.4 S1*1.4-(M23) SK-PULL-DA 240 ft T8P 8.450 0.031 0,0074 0.4 mA 0.005 V S1*1.4-(M36) SK-RELAY 90 ft T8P 8.450 0.031 0.0028 0.3 mA 0.002 V S1*1.4-(M60) SK-MONITOR 100 ft T8P 8.450 0.031 0.0031 0.4 mA 0.002 V S1*1.4-(M64) SK-RELAY 70 ft T8P 8.450 0.031 0.0022 0.3 mA 0.002 V 1.4 500 ft 0.0155 1.3 mA 0.011 V 1.4E S1*1.4E-(D5) SK-HEAT-W 20 ft T8P 8.450 0,031 0.0006 2.0 mA 0.003 V S1*1.4E-(M4) SK-RELAY 30 ft T8P 8.450 0.031 0.0009 0.3 mA 0.004 V S1*1.4E-(M13?) SK-RELAY 80 ft T8P 8.450 0.031 0.0025 0.3 mA 0.012 V S1*1.4E-(M28) SK-PULL-DA 300 ft T8P 8.450 0.031 0.0093 0.4 mA 0.045 V S1*1.4E-(M29) SK-PULL-DA 260 ft T8P 8.450 0.031 0.0081 0.4 mA 0.039 V S1*1.4E-(M30) SK-PULL-DA 260 ft T8P 8.450 0.031 0.0081 0.4 mA 0,039 V S1*1.4E-(M31) SK-PULL-DA 260 ft T8P 8.450 0.031 0.0081 0.4 mA 0.039 V S1*1.4E-(M32) SK-MONITOR 20 ft T8P 8.450 0.031 0.0006 0.4 mA 0.003 V S1*1.4E-(M33) SK-MONITOR 20 ft T8P 8.450 0.031 0.0006 0.4 mA 0.003 V S1*1.4E-(M41) SK-MONITOR 20 ft T8P 8.450 0.031 0.0006 0.4 mA 0.003 V S1*1.4E-(M42) SK-RELAY 90 ft T8P 8.450 0.031 0.0028 0.3 mA 0.013 V S1*1.4E-(M43) SK-RELAY 20 ft T8P 8,450 0,031 0.0006 0.3 mA 0.003 V S1*1.4E-(M46) SK-RELAY 20 ft T8P 8.450 0.031 0.0006 0.3 mA 0.003 V S1*1.4E-(M47) SK-MONITOR 20 ft _ T8P 8.450' 0.031 0.0006 0.4 mA 0.003 V S1*1.4E-(M48) SK-MONITOR 20 ft T8P 8.450 0.031 0.0006 0.4 mA 0.003 V S1*1.4E-(M49) SK-MONITOR 20 ft T8P 8.450 0.031 0.0006 0.4 mA 0.003 V S1*1.4E-(M50) SK-MONITOR 20 ft T8P 8.450 0.031 0.0006 0.4 mA 0.003 V S1*1.4E-(M51) SK-MONITOR 20 ft T8P 8.450 0.031 0.0006 0.4 mA 0.003 V S1*l.4E-(M52) SK-RELAY 70 ft T8P 8.450 0.031 0.0022 0.3 mA 0,010 V S1*1.4E-(M80, M81_) SK-MONITOR-2 30 ft T8P 8.450 0.031 0.0009 0.8 mA 0.004 V 1.4E 1,600 ft 0.0496 8.9 mA 0.240 V G G E CALCULATIONS IiEVISED 11 SLC POINT -LOAD CALCULATIONS PLAN LABEL MODEL WIRE PROPERTIES ALARM CAPACIT.' VOLTAGE (HF) CURRENT DROP LENGTH I TYPE RESIST. (S21kFT) CAPACIT. (HFIkFT) 1AW S 1 * 1.4W-(D4) SK-H EAT-W 20 ft T8P 8.450 0.031 0.0006 2.0 mA 0.002 V S1*1AW-(M24) SK-PULL-DA 160 ft T8P 8.450 0.031 0,0050 0.0071 0.4 mA 0.4 mA 0.018 V 0.025 V S1*1AW-(M25) SK-PULL-DA 230 ft T8P 8.450 0.031 S1*1.4W-(M26) SK-PULL-DA 240 ft T8P 8.450 0.031 0.0074 0.4 mA 0.026 V S1*1.4W-(M27) SK-PULL-DA 165 ft T8P i 8.450 0.031 0.0051 0.4 mA 0.018 V S1*1.4W-(M37) SK-RELAY 115 ft T8P 8.450 0.031 0.0036 0.3 mA 0.013 V S1*1.4W-(M38) SK-RELAY 170 ft T8P 8.450 0.031 0.0053 0.3 mA 0.019 V S1*1.4W-(M39) SK-RELAY 160 ft T8P 8.450 0.031 0.0050 0.3 mA 0,018 V S1*1.4W-(M40) SK-RELAY 20 ft' (none) 1 0.3 mA S1*1.4W-(M44) SK-MONITOR 20 ft T8P 8.450 0.031 0.0006j 0.4 mA 0.002 V S1*1.4W-(M45) V6*1-1 SK-CONTROL - 20 ft T8P 8.450 0.031 0.0006 j 0.4 mA 0.002 V (----) S1*1.4W- M63 SK PULL-DA 30 ft T8P 8.450 - _ 0.031 0.031 0.0009 j 0.4 mA 0.003 V S1*1.4W-(M65) SK-RELAY 20 ft T8P 8.450 0.0006j 0.3 mA 0.002 V S1*1.4W-(M66) SK-RELAY 20 ft T8P 8.450 0.031 0.0006 0.3 mA! 0.002 V S1*1.4W-(M67) SK-RELAY 40 ft T8P 8.450 0.031 0.0012� 0.3 mA 0.004 V 1AW 1,430 ft 0.0437 6.5 mA 0.154 V 1.5 S1*1.5-(D3) _ SK-PHOTO-W 30 ft T8P 8.450 0.031 0.0009 2.0 mA! 0.001 V S1*1 5-(M69) _ SK-MONITOR 10 ft T8P 8.450 0.031 0.0003 0.4 mA 0.000 V S1*1 5-(M99) - SK-MONITOR 400 ft T8P 8.450 0.031 0.0124 0.4 mA j 0.019 V 1.5 440 ft 0.0136 2.8 mA 0.021 V 1.5R S1*L5R-0.2 DTK-2MHLP24BWB 20 ft T8P 8,450 0.031 0.031 0.0006 0.0 mA 0.003 V S1*1.5R-1(D6) SK-PHOTO-R-W 350 ft T8P 8.450 0.0109 2.0 mA 0.059 V S1*1.5R-2(D7) SK-PHOTO-R-W 120 ft T8P 8.450 0.031 0.031 0.0037 2.0 mA 0.020 V S1*1.5R-3(D8) SK-PHOTO-R-W 150 ft T8P 8.450 0.0047 2.0 mA 0.025 V S1*1.5R-4(D9) SK-PHOTO-R-W 200 ft T8P 8.450 0.031 0,0062 2.0 mA 0.034 V S1*1.5R-4(D10) SK-PHOTO-R-W 330 ft T8P 8.450 0.031 0.0102 2.0 mA 0.056 V 1.5R 1,170 ft 0.0363 10.0 mA 0.198 V 1.5W S1*1.5W-(M55) SK-PULL-DA 45 ft T8P 8.450 0.031 0,0014 0.4 mA 0.002 V S1*1.5W-(M56) SK-PULL-DA _ 120 ft T8P 8.450 0.031 0.0037 0.4 mA 0.005 V S1*1.5W-(M57) SK-RELAY 120 ft T8P 8.450 0.031 0.0037 0.3 mA' 0.005 V S1*1.5W-(M58) SK-PULL-DA 30 ft T8P 8,450 0.031 0,0009 0.4 mA 0.001 V S1*1.5W-(M59) SK-PULL-DA 100 ft T8P 8.450 0.031 0.0031 0.4 mA 0A04 V S1*1.5W-(M61) SK-RELAY 60 ft T8P 8.450 0.031 0.0019' 0.3 mA 0.002 V S1*1.5W-(M62) SK-PULL-DA 50 ft T8P 8.450 0.031 0.0016 0.4 mA 0.002 V 1.5W 525 ft 0.0163 2.4 mA 0.021 V SLC LOADING/FAUL.T ISOLATOR CALCULATION SK-5808 SLC IS RATED AT 32 VDC, 150 mA. SK-ISO-6 MODULE DRAWS 2.7 mA UNDER NORMAL CONDITIONS OR 17 mA PER CIRCUIT ISOLATED. AS SHOWN ON RISER DIAGRAM, FIVE TAPS ARE USED. WHEN A CIRCUIT IS ISOLATED, ITS LOAD IS DISCONNECTED FROM THE FRCP. WORST CASE CURRENT DRAW ON THE SLC OCCURS WHEN CIRCUITS LOADED LESS THAN 17 mA ARE DISCONNECTED/ISOLATED: THESE AIRE CIRCUITS 1.1, 1.2,1.3 AND 1.5. CALCULATION ABOVE SHOWS MAXIMUM 102 mA CURRENT DRAW FOR SIX DISCONNECTED CIRCUITS, WHICH IS OVERLY -CONSERVATIVE. WORST CASE CURRENT LOAD ON THE SLC WITH RED LEDS ON DETECTORS IS: CKT 1: CKT 1.1: CKT 1.2: CKT 1.3: CKT 1.4: CKT 1.5: EMPTY #6: TOTAL 2.7 + 17.0 +17.0 +17.0 + (1.3 + 8.9 + 6.5) +17.0 + 0 87.4mA SILENT KNIGHT 5808: MAXIMUM SLC LINE: CAPACITANCE: 0.50 NF MAXIMUM SLC LINE: RESISTANCE, PER PAIR, PER LEG: 40 OHM (SK, APPROX 3,900 F-I @ 18 AWG) MAXIMUM SLC AGGREGATE WIRE DISTANCE WITH T-TAPS: 40,000 FT MAXIMUM SBUS LINE CAPACITANCE: NO STATED LIMIT MAXIMUM SBUS LINE LENGTH: 4,688 FT @ 18 AWG MAXIMUM SBUS VOLTAGE DROP: 6.0 V MAXIMUM CURRENT DRAW: 6.0 A C 11 Antinomy Consulting Engineers Code Consulting - Fire Protection - Smoke Control 600 Rinehart Road Suite 2054 Lake Mary, FL 32746-4955 Tel. 321-888-2882 Online: antinomy.com Prepared For - g�r EC #13001688 fitiii No 73972 0 STATE OF tv; �'� �� � i I t i ► � � � ``` 10/08/21 This document has been digitally signed and sealed by Gregory A. Tabaka, PE on the date adjacent to the seal. Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies. Revisions No. Description Date 0 PERMIT SET 09/07/21 1 NEW BOOTH, RPS6 REALLOC. 10/08/21 COMPLETE ALARM INC. MAVERICK BOATS, INC. Project Address 4551 ST. LUCIE BLVD FT. PIERCE, FL 34946 FIRE ALARM CALCULATIONS 1 Project Number ACE0146 Date 10/08/21 Drawn By G.TABAKA Checked By G.TABAKA FA -boo (REV. 1) Scale (IJON) N a 0 z 0 a J U J Q U a Q cc LL 6 0 a Ul J I j PANEL RPS 2 CALCULATIONS H I G I F E PANEL IRPS3 CALCULATIONS 0 C B PANEL RPS4 CALCULATIONS A 11111�1 I, lim 8' 71 6' 51 4 3 21 RPS2 NAC LINE LOSS CALCULATIONS (NEW CIRCUIT) -- - ---------- PROPERTIES --WIRE RESIST. SEGMENT DEVICE PLAN LABEL MODEL TAP MAX LOAD LENGTH TYPE (i?JkFT) CURRENT V DROPS VOLT 2 3 V2*3-1 HSC 95 Cd 176.0 mA 320 ft P4P 3.26 704.0 mA 1.469 V 18.931 V 99 dB V2*3-2 HSC 95 Cd 176.0 mA 70 ft P4P 3.26 528.0 mA 0.241 V 18.690 V 99 dB V2*3-3 HSC 95 Cd 176.0 mA 70 ft P4P 3.26 352.0 mA 0.161 V 18.529 V 99 dB V2*34 HSC 95 Cd 176.0 mA 70 ft P41P 3.26 176.0 mA 0.080 V 18.449 V 99 dB 3 530 ft 1.951 V RPS2 LOADS (NEW AND EXISTING) • MANUFACTURER MODEL TAP COUNT ALARM CURRENT STANDBY CURRENT EACH SUBTOTAL EACH I SUBTOTAL 2 • SILENT KNIGHT SK-5496 1 160.0 mA 160.0 mA 1 40.0 mAJ 40.0 mA 160.0 mA 40.0 mA 1 • WHEELOCK HS 15 1 65.0 mA 65.0 mA 0.0 mA 0.0 mA • WHEELOCK STIR 15 1 57.0 mA 57.0 mA 0.0 mA 0.0 mA • WHEELOCK HSC 15 2 65.0 mA 130.0 mA 0.0 mA 0.0 mA • WHEELOCK ASWP-24MCWH-FR 135 1 0.4 mA 0.4 mA 0.0 mA 0.0 mA • WHEELOCK RSSWP-2475W-FR 30 1 138.0 mA 138.0 mA 0.0 mA 0.0 mA 390.4 mA 0.0 mA 2 HS 15 1 65.0 mA 65.0 mA 0.0 mA 0.0 mA UWHEELOCK STR 15 1 57.0 mA 57.0 mA 0.0 mA 0.0 mA HSC 15 1 65.0 mA 65.0 mA 0.0 mA 0.0 mA • WHEELOCK HSC 75 2 136.0 mA 272.0 mA 0.0 mA 0.0 mA • WHEELOCK ASWP-24MCWH-FR 1351 2 0.4 mA 0.7 mA 0.0 mA 0.0 mA • WHEELOCK RSSWP-2475W-FR 3oT 1 138.0 mA 138.0 mA 0.0 mA 0.0 mA 597.7 mA 0.0 mA 3 • WHEELOCK HSC 95 Cd 99 dB', 41 176.0 mA 704.0 mA 0.0 mA 0.0 mA 704.0 mA 0.0 mA A • WHEELOCK MB-G6-24-R --�1 11 40.0 mA 40.0 mA 0.0 mA 0.0 mA 40.0 mA 0.0 mA 1,892.1 mA 40.0 mA TOTAL VISIBLE AND AUXILIARY POWER 1,892,1 mA 40.0 mA RPS2 LOAD SUMMARY DESCRIPTION TOTAL BATTERY CAPACITY TIME (HR) LOAD (A-HR) A-HR x 1.25 ALARM CONDITIONS 1,892.1 mA 0.083 0.158 0.197 STANDBY CONDITIONS 40.0 mA 24.000 0.960 1.200 ALARM + STANDBY CAPACITY BATTERY CAPACITY F 1.118 1.397 MINIMUM BATTERY SIZE (AMP-HR) RETAIN EXISTING 2x7 A-HR BATTERIES. CIRCUIT NOTE: MINIMUM EOL VOLTAGE: 18.00 V FOR BELL RPS3 NAC LINE LOSS CALCULATIONS (NEW CIRCUITS) PLAN LABEL MODEL TAP _ WIRE PROPERTIES RESIST. SEGMENT LENGTH - MAX LOAD] TYPE (0JkFT) CURRENT V DROP DEVICE VOLT- _--_- 3 2 V3*2-1 JPC2RHK 1351 245.0 mA 300 ft I P6P 1 5.291 245.0 mA 0.778 V 19.622 V 2 300 ft 0.778 V 3 V3*3-1 PC2RHK 177 290.0 mA 360 ft P6P 5.29 590.0 mA 2.247 V 18.153 V V3*3-2 PC2RHK 177 290.0 mA 20 ft P6P 5.29 290.0 mA 0.061 V 18.092 V 3 380 ft 2.308 V RPS3 LOADS (NEW AND EXISTING) • MANUFACTURER MODEL TAP COUNT ALARM CURRENT STANDBY CURRENT EACH SUBTOTAL EACH SUBTOTAL • SILENT KNIGHT SK-5499 SK-5496 T 1 205.0 mA 205.0 mA 75.0 MAT 75.0 mA 205.0 mA 75.0 mA 1 • WHEELOCK ASWP-2475C-FR 115 2 355.0 In 710.0 mA 0.0 mA 0.0 mA 710.0 mA 0.0 mA 2 • SYSTEM SENSOR PC2RHK 135 1 245.0 mA� 245.0 rnA 0.0 mA 0.0 mA - - - 245.0 rnA 0.0 mA 3 • SYSTEM SENSOR JPC2RHK 1 1771 21 290.0 mA 58 1.0 mA 0.0 mA 0.0 mA -- 580.0 mA 0.0 mA 1,740.0 rnA 75.0 mA TOTAL VISIBLE AND AUXILIARY POWER 1,740.0 rnA 75.0 mA RPS3 LOAD SUMMARY DESCRIPTION TOTAL BATTERY CAPACITY TIME (HR) LOAD (A-HR) A-HR x 1.25 ALARM CONDITIONS 1,740.0 mA 0.083 0.145 0.181 STANDBY CONDITIONS 75.0 mA 24.000 1.800 2.250 2.431 ALARM + STANDBY CAPACITY BATTERY CAPACITY I 1.945 r MINIMUM BATTERY SIZE (AMP-HR) RETAIN EXISTING 2x7 A -FIR BATTERIES. RPS4 NAC LINE LOSS CALCULATIONS (NEW CIRCUITS) --- ------------ - WIRE PROPERTIES --- RESIST. SEGMENT DEVICE PLAN LABEL MODEL TAP MAX LOAD] LENGTH 1 TYPE (S21kFT) CURRENT V DROP VOLT 4 3 V4*3-1 FHEX XP 1,20).0 mA 220 ft P6P 5.29 1,200.0 mA 2.793 V 17.607 V 3 220 ft 2.793 V 4 V4*4-1 FSEX-HI XP,15 1,900.0 mA 200 ft P4P 3.26 1,900.0 mA 2.478 V 17.922 V 0 4 200 ft 2.478 V • MANUFACTURER MODEL RPS4 LOADS (NEW AND EXISTING) ALARM CURRENT TAP COUNT EACH; SUBTOTAL STANDBY CURRENT EACH SUBTOTAL 4 • SILENT KNIGHT SK-5499 SK-5499 1 205.0 mA 1 205.0 mA 75.0 MAI 75.0 mA 1 205.0 mA 75.0 mA • FEDERAL SIGNAL FSEX-HI XP,150 1 1,900.0 mA 1,900.0 mA 0.0 mA 0.0 mA 2 1,900.0 mA 0.0 mA • FEDERAL SIGNAL FHEX XPI 11 1,200.0 mA 1,200.0 MAT 0.0 mA 1 0.0 mA 3 1,200.0 mA 0.0 mA • FEDERAL SIGNAL FHEX XP 1 1,200.0 mA 1,200.0 mA 0.0 mA 0.0 mA 4 1,200,0 mA 0.0 mA • FEDERAL SIGNAL FSEX-HI XP,150 1 1,900.0 mA 1,900,0 mA 0.0 mA 0.0 mA TOTAL VISIBLE AND AUXILIARY POWER 1,900,0 mA, 6,405,0 mA 6,405.0 mA 0.0 mA 75.0 mA 75.0 mA RPS4 LOAD SUMMARY DESCRIPTION TOTAL BATTERY CAPACITY TIME (HR) LOAD (A-HR) A-HR x 1.25 ALARM CONDITIONS 6,405.0 mA 0.083 0.534 0.667 STANDBY CONDITIONS 75.0 mA 24.000 1.800 2.250 ALARM + STANDBY CAPACITY BATTERY CAPACITY 2.334 2.917 MINIMUM BATTERY SIZE (AMP-HR) RETAIN EXISTING 2x7 A-HR BATTERIES. Antinomy Consulting Engineers Code Consulting - fire Protection - Smoke Control 600 Rinehart Road Suite 2054 Lake Mary, FL 32746-4955 Tel. 321-888-2882 Online: antinomy.com Prepared For: E ' xo EC #13001688 c, E N No 73972 44,� 0% STATE OF 0 I I t i t t 10l08/21 This document has been digitally signed and sealed by Gregory A. Tabaka, PE on the date adjacent to the seal. Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies. Revisions No. Description Date 0 PERMIT SET 09/07/21 COMPLETE ALARM INC. MAVERICK BOATS, INC. Project Address 4551 ST. LUCIE BLVD FT. PIERCE, FL 34946 FIHL ALAKIVI N CD CALCULATIONS 2 Project Number ACE0146 N Cn Date 10/08/21 0 Drawn By G.TABAKA Checked By G.TABAKA FA-601LU (REV. 0) U_ Scale (LION)co J I H I G I F E I 0 C B A J i H PANEL RPS 5 CALCULATIONS G F E PANEL RPS5 CALCULATIONS - CONTINUED D C B I PANEL RPS6 CALCULATIONS ANTINOMY 8 7 5 4 3 K RPS5 NAC LINE LOSS CALCULATIONS PLAN LABEL MODEL -._T TAP MAX LOAD WIRE PROPERTIES - V DROP -- -- - - - DEVICE VOLT --- LENGTH TYPE RESIST. ((VkFT) SEGMENT CURRENT 5 1 V5*1-1 HSC 150 Cd 99 dB 242.0 mA 180 ft P2P 2.05 1,452.0 mA 1.072 V 19.328 V V5*1-2 HSC 150 Cd 99 dB 242.0 mA 70 ft P2P 2.05 1,210,0 mA 0.347 V 18.981 V V5*1-3 HSC 150 Cd 99 dB 242.0 mA 70 ft P2P 2.05 968.0 mA 0.278 V 18.703 V V5*1-4 HSC 150 Cd 99 dB 242.0 mA 210 ft P2P 2.05 726.0 mA 0.625 V 18.078 V V5*1-5 HSC 150 Cd 99 dB 242.0 mA 70 ft P2P 2.05 484.0 mA 0.139 V 17.939 V V5*1-6 HSC 150 Cd 99 dB 242.0 mA 70 ft P2P 2.05 242.0 mA 0.069 V 17.870 V 1 670 ft 2.530 V 2 V5*2-1 LHSR3 15 46.0 mA 20 ft P2P 2.05 1,498.0 mA 0.123 V 20.277 V V5*2-2 HSC 150 Cd 99 dB 242.0 mA 95 ft P2P 2.05 1,452.0 mA 0.566 V' 19.711 V V5*2-3 HSC 150 Cd 99 dB 242.0 mA 170 ft P2P 2.05 1,210.0 mA 0.843 V 18.868 V V5*2.4 HSC 150 Cd 99 dB 242.0 mA 70 ft P2P 2.05 968.0 mA 0.278 V 18.590 V V5*2-5 HSC 150 Cd 99 dB 242.0 mA 210 ft P2P 2.05 726.0 mA 0.625 V 17.965 V V5*2-6 HSC 150 Cd 99 dB 242.0 mA 70 ft P2P 2.05 484.0 mA 0.139 V 17,826 V V5*2-7 HSC 150 Cd 99 dB 242.0 mA 70 ft P2P 2.05 242.0 mA 0.069 V 17,757 V 2 705 ft 2.643 V 3 V5*3-1 HSC 150 Cd 99 dB 242.0 mA 390 ft P2P j 2.05 1,210.0 mA 1.935 V j 18,465 V V5*3-2 HSC 150 Cd 99 dB 242.0 mA 70 ft P2P 2.05 968.0 mA 0.278 V 18.187 V V5*3-3 HSC 150 Cd 99 dB 242.0 mA 70 ft P2P 2.05 726.0 mA 0.208 V 17.979 V V5*34 HSC 150 Cd 99 dB 242.0 mA 70 ft P2P 2.05 484.0 mA 0.139 V 17.840 V V5*3-5 HSC 150 Cd 99 dB 242.0 mA 70 ft P2P 2.05 242.0 mA 0.069 V 17,771 V 3 670 ft 2.629 V 4 V5*4-1 HSC 150 Cd 99 dB 242.0 mA 320 ft P2P 2,05 1,210.0 mA 1.588 V 18.812 V V5*4-2 HSC 150 Cd 99 dB 242A mA 70 ft P21P 2.05 968.0 mA 0.278 V 18.534 V V5*4-3 HSC 150 Cd 99 dB 242.0 mA 242.0 mA 70 ft P21P 2.05 726.0 mA 0.208 V 18.326 V V5*44 HSC 150 Cd 99 dB 70 ft P2P 2.05 484.0 mA 0.139 V 18.187 V V5*4-5 HSC 150 Cd 99 dB 242.0 mA 70 ft P2P 2.05 242.0 mA 0.069 V 18.118 V 4 600 ft 2.282 V 5 V5*5-1 HSC 150 Cd 99 dB 242.0 mA 320 ft P2P 2.05 1,452.0 mA 1.905 V 18.495-V V5*5-2 HSC 150 Cd 99 dB 242.0 mA 70 ft P2P 2.05 1,210.0 mA 0.347 V 18.148 V V5*5-3 HSC 150 Cd 99 dB 242.0 mA 70 ft P2P 2.05 968.0 mA 0.278 V 17.870 V V5*5-4 HSC 150 Cd 99 dB 242.0 mA 70 ft P2P 2.05 726.0 mA 0.208 V 17.662 V V5*5-5 HSC 150 Cd 99 d6 242.0 mA 70 ft P2P 2.05 484.0 mA 0.139 V 17.524 V V5*5-6 HSC 150 Cd 99 dB 242.0 mA 70 ft P2P 2.05 242.0 mA 0.069 V 17.455 V 5 670 ft 2.946 V 6 V5*6-1 HSC 150 Cd 99 dB 242.0 mA 310 ft P2P 2.05 1,452.0 mA 1.845 V 18,555 V V5*6-2 HSC 150 Cd 99 dB 242.0 mA 70 ft P2P 2.05 1,210.0 mA 0.347 V 18.208 V V5*6-3 HSC 150 Cd 99 dB 242.0 mA 70 ft P2P 2.05 968.0 mA 0.278 V 17.930 V V5*64 HSC 150 Cd 99 dB 242.0 mA 70 ft P2P 2.05 726.0 mA 0.208 V 17.722 V V5*6-5 HSC 150 Cd 99 dB 242.0 mA i 70 ft P2P 2.05 484.0 mA 0.139 V 17.583 V V5*6-6 HSC 150 Cd 99 dB 242.0 mA 70 ft P2P 2.05 242.0 mA 0.069 V 17.514 V 6 660 ft 2.886 V 7 V5*7-1 HSC 75 136.0 mA 320 ft P2P 2.05 272.0 mA 0.357 V 20.043 V V5*7-2 HSC 75 136.0 mA 20 ft P2P 2.05 136.0 mA 0.011 V 20.032 V 7 340 ft 0.368 V SILENT KNIGHT PS-10/PS-6 ALLOWABLE VOLTAGE DROP AT FULL LOAD: 3.20 V RPS5 LOADS • MANUFACTURER MODEL TAP COUNT ALARM CURRENT STANDBY CURRENT EACH SUBTOTAL EACH SUBTOTAL 5 • SILENT KNIGHT SK-PS10 SK-PS10 1 185.0 mA 185.0 mA 6.0 mA 156.0 mA 185.0 mA 156,0 mA 1 • WHEELOCK HSC 150 Cd 99 dB 6 242.0 mA 1,452.0 mA 0.0 mA 0,0 mA 1,452.0 mA 0.0 mA 2 • WHEELOCK LHSR3 15 1 46.0 mA 46.0 mA 0.0 mA 0.0 mA • WHEELOCK IHSC 150 Cd 99 dB 6 242.0 mA 1,452.0 mA 0.0 mA 0.0 mA 1,498.0 mA 0.0 mA 3 • WHEELOCK JHSC 150 Cd 99 dB 51 242.0 mA 1,210.0 mA 0,0 mA 0.0 mA 1,210.0 mA 0.0 mA 4 • WHEELOCK JHSC 150 Cd 99 dB 5 242.0 mA 1,210.0 mA'[ 0.0 mA 0.0 mA 1,210.0 mA 0.0 mA 5 •I WHEELOCK JHSC 150 Cd 99 dB 6 242.0 mA 1,452.0 mA 0.0 mA 0,0 mA 1,452.0 mA 0.0 mA 6 • WHEELOCK JHSC 150 Cd 99 dB 6 242.0 mA 1,452.0 mA 0.0 mA 0.0 mA 1,452.0 mA 0.0 mA 7 •WHEELOCK HSC - 75 136.0 mA 2' - -- I 272.0 A � 0. m _ J0 mA 0,0 mA _-- 272.0 mA 0.0 mA 8,731.0 mA 156.0 mA TOTAL VISIBLE AND AUXILIARY POWER 8,731.0 mA 156.0 mA RPS5 LOAD SUMMARY DESCRIPTION TOTAL BATTERY CAPACITY TIME (HR) LOAD (A-HR) A-HR x 1.25 ALARM CONDITIONS STANDBY CONDITIONS 8,731.0 mA 156.0 mA 0,083 0.728 24.000 3,744 0.909 4.680 ALARM + STANDBY CAPACITY BATTERY CAPACITY 1 4.472 MINIMUM BATTERY SIZE (AMP-HR) PROVIDE 2x7 A-HR BATTERIES. RPS6 NAC LINE LOSS CALCULATIONS PLAN LABEL MODEL TAP MAX LOAD WIRE PROPERTIES V DROP DEVICE VOLT LENGTH TYPE RESIST. (Q/kFT) SEGMENT CURRENT 6 1 P1*1.4W-V6*1-1 SK-CONTROL NAC 7.0 mA 5ftl P8P 8.45 7.0 mA 0.001 V 20.399 V 1 5 ft 0.001 V 3 V6*3-1 FSEX-HI XP, 150 1,900.0 mA 160 ft I P4P 1 3.26 1,900.0 mA 1.982 V 18.418 V 3 160 ft 1.982 V 4 V6*4-1 FSEX-HI XP, 150 1,900.0 mA 200 ft P4P 3.26 1,900.0 mA 2.478 V 17,922 V 4 200 ft 2.478 V 5 V6*5-1 FSEX-HI XP,150 1,900.0 mA 1 200 ft I P4P 1 3.26 1,900.0 mA 2.478 V 17.922 V 5 200 ft 2.478 V 6 V6*6-1 FHEX XP 1,200.0 n 220 ft I P6P 5.29 1,200.0 mA 2.793 V'' 17.607 V 6 220 ft 2.793 V 7 V6*7-1 FHEX XP 1,200.0 mA 180 ft P2P 2.05 2,400.0 mA 1.771 V 18.629 V V6*7-2 FHEX XP 1,200.0 mA 40 ft P2P 2.05 1,200.0 mA 0.197 V 18.432 V 7 220 ft 1.968 V RPS6 LOADS • MANUFACTURER MODEL TAP COUNT ALARM CURRENT STANDBY CURRENT EACH SUBTOTAL EACH SUBTOTAL 6 • SILENT KNIGHT SK-PS10 SK-PS10 1 185.0 mA 185.0 mA 156.0 mA 156.0 mA 185.0 mA 156.0 mA 1 • SILENT KNIGHT SK-CONTROL NACI 11 7.0 mA 1.7 mA 1.7 mA 7.0 mA 1.7 mA 3 • FEDERAL SIGNAL FSEX-HI XP, 150 1 1,900.0 mA 1,900.0 mA 0.0 mA 0.0 mA 1,900.0 mA 0.0 mA 4 • FEDERAL SIGNAL FSEX-HI XP,150 1 1,900.0 mA 1,900.0 mA 0.0 mA 0.0 mA 1,900.0 mA 0.0 mA 5 • FEDERAL SIGNAL FSEX-HI XP, 150 1 1,900.0 mA 1,900.0 mA 0.0 mA 0.0 mA 1,900.0 mA 0.0 mA 6 • FEDERAL SIGNAL FHEX XP 1 1,200.0 mA 1,200.0 mA 0.0 mA 0.0 mA 1,200.0 mA 0.0 mA 7 • FEDERAL SIGNAL FHEX XPI 21 1,200.0 mA 2,400.0 mA 0.0 mA 0.0 mA 2,400.0 mA 0.0 mA 9,492.0 mA 157.7 mA TOTAL VISIBLE AND AUXILIARY POWER 9,492.0 rnA 157.7 mA RPS6 LOAD SUMMARY DESCRIPTION_____ TOTAL BATTERY CAPACITY TIME (HR) LOAD (A-HR) A-HR x 1.25 ALARM CONDITIONS _ 9,492.0 mA 0.083 0.791 0.989 STANDBY CONDITIONS 157.7 mA 24.000 3.785 4.731 ALARM + STANDBY CAPACITY BATTERY CAPACITY i 4.576 5.720 MINIMUM BATTERY SIZE ;AMP-HR) PROVIDE 2x7 A-HR BATTERIES. J RPS6 CALCS REVISED A Antinomy Consulting Engineers Code Consulting - fire Protection - Smoke Control 600 Rinehart Road Suite 2054 Lake Mary, FL 32746-4955 Tel. 321-888-2882 Online: antinomy.com Prepared For: 4114 ,, .a •g h EC #13001688 �111111111///�/ ' r� No 73972 �� STATE OF i F i r C� RON �/ I i 1 i 1 10/08/21 This document has been digitally signed and sealed by Gregory A. Tabaka, PE on the date adjacent to the seal. Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies. Revisions No. Description I Date 0 PERMIT SET 09/07/21 1 NEW BOOTH, RPS6 REALLOC. 10/08/21 COMPLETE ALARM INC. MAVERICK BOATS, INC. Project Address 4551 ST. LUCIE BLVD FT. PIERCE, FL 34946 FIRE ALARM O CALCULATIONS 3 Project Number ACE0146 co Cn Date 10/08/21 0 Drawn By _ G.TABAKA Checked By G.TABAKA FA-602LU (REV. 1) U- Scale (UON) J G E I it B J I H G F E D C B A CEILING MOUNTED SMOKE/HEAT DETECTOR 5'(MIN) ANTINOMY 81 71 61 51 4 3 21 AUDIO ONLY FA MOUNTING DETAIL NOT TO SCALE AUDIOVISUAL & VISUAL -ONLY APPI IANrFS A/C SUPPLY DIFFUSER OR RETURN GRILLE ACCEPTABLE HERE DETAIL NOTES: 1. NOT ALL DEVICES SHOWN ON THIS DETAIL APPLY TO THIS PROJECT. SEE THE PLAN VIEW LAYOUT OF THE FIRE ALARM SYSTEM TO VERIFY WHICH APPLIANCES APPLY, AND WHICH DO NOT, 2. CHECK WITH MANUFACTURE'S INSTALLATION SHEET FOR THE EXACT ROUGH -IN HEIGHTS, LOCATION OF BACK. BOXES, AND WIRING REQUIREMENTS. o tzw (D W w OO z z w O w Q w O Oz cco � � m Q � c~n C/) O� O O 0 0 0 RPS4 (BATTERIES NOT SHOWN) RpCF 1/1/IRIRIn nPTAII Ot-I L-U. U - I -U G F E 12" (MAX) REMOTE ANNUNCIATOR NOTES: ' 1 1, THIS DETAIL APPLIES ONLY TO RPS6, WHICH SERVES NEW BOOTH AN APPLIANCES. 2. WIRE CIRCUITS AS SHOWN IN THIS DETAIL. 3. INTENTION IS TO DELAY ACTIVATION OF HORNS SLIGHTLY TO PERMIT HIGH INRUSH CURRENT DRAW OF EXPLOSIONPROOF STROBES TO CONCLUDE TO AVOID OVERLOADING THE POWER SUPPLY. 4. IF DELAY TIME IS INSUFFICIENT: CONFIGURE IN2 FOR TEMPORAL DEBOUNCE. 5. FOR MOUNTING, BATTERY AND OTHER DETAILS, REFER TO NAC EXPANDER INSTALLATION INSTRUCTIONS. 6. ADD THIS SK-CONTROL TO PROGRAM TO ACTIVATE WITH OTHER AN CIRCUITS. 7. CHANGE PROGRAM LABEL OF RPS4 TROUBLE MONITOR MODULE. ALTERNATE: MAY INSTALL SK-MINIMON OR EQUAL TO SUPERVISE RPS6 TROUBLE CONTACTS. Antinomy Consulting Engineers Code Consulting - Fire Protection • Smoke Control 600 Rinehart Road Suite 2054 Lake Mary, FL 32746-4955 Tel. 321-888-2882 Online: antinomy.com Prepared For: r 8 EC #13001688 `fit\Illlllr���� No 73972 STATE OF 1° 0 N A L l\% 10/08/21 This document has been digitally signed and sealed by Gregory A. Tabaka, PE on the date adjacent to the seal, Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies. Revisions No. Description I Date 0 PERMIT SET 09/07/2I 1 NEW BOOTH, RPS6 REALLOC. 10/08/21 COMPLETE ALARM INC. MAVERICK BOATS, INC. Project Address 4551 ST. LUCIE BLVD FT. PIERCE, FL 34946 FIRE ALARM DETAILS Project Number Date Drawn By Checked By F Scale (UON) N O ACE0146 10/08/21 G.TABAKA Q G.TABAKA o A-7 Ir (REV. 1) U_ 00 As indicated Q LL L J I I H /A'