1. SCOPE OF WORK:
e A. 11 GENERAL: EXPAND EXISTING SILENT KNIGHT FIRE ALARM SYSTEM
TO PROVIDE FIRE SAFETY FUNCTIONS AND NOTIFICATION AT THE
NEW BUILDING.
B. FURNISH, INSTALL AND PROGRAM ALL MATERIAL, LABOR,
DOCUMENTATION AND TESTING REQUIRED TO PROVIDE A FULLY -
FUNCTIONAL, CODE -COMPLIANT OPERATIONAL SYSTEM.
C. PERFORM INITIAL ACCEPTANCE TESTING ON NEW COMPONENTS
AND RE -ACCEPTANCE TESTING OF EXISTING COMPONENTS.
D. PREPARE NEW (OR AMEND EXISTING) OPERATION AND
MAINTENANCE MANUAL FOR OWNER FOR EXPANDED SYSTEM.
INSTRUCT OWNER'S PERSONNEL ON SYSTEM OPERATION.
E. PROVIDE FIRE WATCH WHEN THE FIRE ALARM SYSTEM FUNCTION
IS IMPAIRED FOR FOUR HOURS OR LONGER.
F. INSTALL IN ACCORDANCE WITH APPLICABLE CODES (LISTED
BELOW), NFPA 72, NFPA 70, AND THE CONTRACT DOCUMENTS.
7 G. COORDINATE WITH ALL BUILDING SYSTEMS, INCLUDING
MECHANICAL/HVAC, ELECTRICAL, LIGHTING AND FIRE PROTECTION
H. PROVIDE UNDERGROUND RACEWAYS AND CONNECTION TO
EXISTING BUILDING A.
2. THE CONTENT OF THESE DRAWINGS IS BASED UPON RECORD
DRAWINGS THAT HAVE BEEN FURNISHED TO THE EOR. THE FOR IS
UNABLE TO VERIFY THE ACCURACY OF EXISTING, CONCEALED,
- ENCLOSED, BURIED OR PROGRAMMED COMPONENTS. THE
CONTRACTOR SHALL REPORT DISCREPANCIES DISCOVERED DURING
THE WORK TO THE FOR IN A TIMELY MANNER SO AS NOT TO UNDULY
IMPEDE PROGRESS OF THIS WORK OR OTHER SCOPES OF WORK
CURRENTLY OCCURRING OR PLANNED TO OCCUR IN THE BUILDING.
6 FLORIDA 61G15 COMPLIANCE
1. THIS PROJECT'S SCOPE IS TO EXPAND THE EXISTING SILENT KNIGHT
5808 FIRE ALARM SYSTEM TO SYSTEM TO PROVIDE FIRE SAFETY
FUNCTIONS AT THE EXPANDED BUILDING.
2. ADDRESS: AS SHOWN IN TITLEBLOCK
3. AHJ: CITY OF FT. PIERCE, FL
4. ENGINEER OF RECORD: GREG TABAKA, PE #73972
5. PRIMARY OCCUPANCY: GROUP F-1 FACTORY (FBC)/INDUSTRIAL (FFPC)
6. OTHER OCCUPANCIES: GROUPS B AND A-2 (FBC)/EXISTING 13USINESS
AND EXISTING ASSEMBLY < 300 PERSONS (FFPC); GROUP S-1 (FBC)/
STORAGE (FFPC)
7. MONITORING: EXISTING TO REMAIN
8. CABLING AND SUPERVISION REQUIREMENTS. UNLESS NOTED
OTHERWISE, THE FOLLOWING MINIMUM (AND OPTIONAL) WIRING
5 CLASSES ARE REQUIRED:
A. IDC: CLASS B (OPTIONAL: A)
B. SLC: CLASS B (OPTIONAL: A, X).
C. NAC: CLASS B (OPTIONAL: A)
D. AUXILIARY POWER: CLASS E
E. ALL NEW CIRCUITS TO BE FREE -WIRED AND/OR ENCLOSED IN EMT
ABOVEGROUND OR EXISTING EMT/UNDERGROUND RACEWAYS;
BELOWGROUND IN PVC RACEWAYS. LIMITED USE OF FLEXIBLE
METAL CONDUIT (FMC) AND METAL CLAD (MC) CABLE IS PERMITTED.
9. ADDRESSABLE: YES
10. CLASSIFICATION: PROTECTED PREMISES FIRE ALARM
11. INITIATING DEVICE ZONING: NONE
12. EVACUATION ZONING: NONE (GENERAL EVAC)
13. CAMPUS WIRING: ONE ADDRESSABLE DATA CIRCUIT (SLC) WITH FOUR
BRANCHES WILL BE EXPANDED TO A FIFTH BRANCH SERVING THE
4 EXPANSION. EXISTING CIRCUITS WILL BE EXPANDED TO SERVE NEW
DEVICES.
14. OPERATIONS AND MAINTENANCE PROCEDURES, MANUALS, SYSTEM
DOCUMENTATION AND INSTRUCTION OF OWNER'S PERSONNEL TO BE
DEVELOPED AND FURNISHED BY INSTALLING CONTRACTOR.
15. SYSTEM TEST REQUIREMENTS: COMPLY WITH NFPA 72 CH. 14 FOR
INITIAL, RE -ACCEPTANCE AND PERIODIC TESTING.
16. SEE SHEET FA-400 FOR SEQUENCE OF OPERATIONS -
CODE COMPLIANCE
THIS SYSTEM HAS BEEN DESIGNED ACCORDING TO THE PRESCRIPTIVE
REQUIREMENTS OF:
3 1. NFPA 72, NATIONAL FIRE ALARM AND SIGNALING CODE, 2016 EDITION
2. FLORIDA BUILDING CODE (FBC), 7T" EDITION
3. FLORIDA FIRE PREVENTION CODE (FFPC), 7T" EDITION
4. FLORIDA ELECTRICAL CODE (FEC), 2018 EDITION
5. NFPA 70, NATIONAL ELECTRICAL CODE (NEC), 2017 EDITION
6. AMERICANS WITH DISABILITIES ACT (ADA)
7. FLORIDA ACCESSIBILITY CODE (FAC), 7T" EDITION
8. FLORIDA 61G15-32.008 REVISED JULY 25, 2019
PERSONNEL REQURREMENTS AND CERTIFICATIONS
1. INSTALLATION PERSONNEL SHALL BE SUPERVISED BY PERSONS WHO
ARE QUALIFIED AND EXPERIENCED IN THE INSTALLATION, INSPECTION,
AND TESTING OF FIRE ALARM SYSTEMS, EXAMPLES OF QUALIFIED
2 PERSONNEL SHALL INCLUDE, BUT NOT BE LIMITED TO THE FOLLOWING:
1) FACTORY TRAINED AND CERTIFIED PERSONNEL, 2) NATIONAL
I INSTITUTE OF CERTIFICATION IN ENGINEERING TECHNOLOGIES (NICET)
FIRE ALARM LEVEL II OR HIGHER CERTIFIED PERSONNEL, AND 3)
PERSONNEL LICENSED OR CERTIFIED BY STATE OR LOCAL
AUTHORITY, PER NFPA 72. COPIES OF CERTIFICATION CARDS OF
TECHNICIANS SHALL BE FURNISHED TO OWNER'S REPRESENTATIVE.
2. A COPY OF ALL SOFTWARE DOCUMENTATION SHALL BE MAINTAINED
- I ON THE CONSTRUCTION SITE IN A BINDER, ARRANGED IN
CHRONOLOGICAL ORDER. THIS BINDER SHALL BE TURNED OVER TO
OWNER AFTER ALL START UP, TESTING, COMMISSIONING,
PROGRAMMING AND DEMONSTRATIONS ARE COMPLETED.
3. ONCE THE FIRE ALARM SYSTEM IS PUT INTO SERVICE, IN WHOLE OR IN
PART, NO SOFTWARE CHANGES SHALL BE PERFORMED WITHOUT
WRITTEN CONSENT OF OWNER. IF SOFTWARE CHANGES ARE NEEDED,
1 THEY SHALL BE PERFORMED BY CERTIFIED MANUFAC rURER'S
TECHNICIANS.
4. PROVIDE THE SERVICES OF THE INSTALLER'S SUPERVISOR OR
PERSON WITH EQUIVALENT QUALIFICATIONS TO SUPERVISE
INSPECTION AND TESTING, CORRECTION, AND ADJUSTMENTS.
MATERIALS AND INSTALLATION REQUIREMENTS
1. ALL EQUIPMENT CONSTRUCTED AND INSTALLED IN CONFORMITY WITH
THESE DESIGN DOCUMENTS SHALL BE LISTED FOR THE PURPOSE FOR
WHICH IT IS USED AND SHALL BE INSTALLED IN ACCORDANCE WITH
THE MANUFACTURERS' INSTALLATION INSTRUCTIONS, APPLICABLE
STANDARDS AND DESIGN DOCUMENTS.
2. ALL NEW COMPONENTS SHALL BE FM APPROVED OR UL LISTED FOR
THEIR INTENDED USAGE.
3. ALL NEW FIRE ALARM COMPONENTS SHALL BE BY A SINGLE
MANUFACTURER, EXCEPT THAT SURGE SUPPRESSION, FITTINGS,
WIRING AND WIREWAYS MAY VARY.
4. SURGE SUPPRESSION
A. SURGE SUPPRESSION SHALL BE INSTALLED TO SERVE ALL NEW
FRCP, FARP AND NAC BOOSTER UNITS. SURGE SUPPRESSORS
SHALL NOT BE MOUNTED ON FIRE ALARM PANEL ENCLOSURES.
B. ANY CONDUCTORS ENTERING OR EXITING THE BUILDING SHALL BE
PROTECTED BY APPROVED, LISTED SURGE PROTECTION DEVICES
AND INSTALLED ACCORDING TO THE SURGE PROTECTION DETAIL.
5. MOUNTING LOCATIONS
A. WHERE HORNS (SPEAKERS) AND COMBINATION HORN/STROBE
(SPEAKER/STROBE) APPLIANCES ARE INSTALLED IN THE SAME
ROOM, THEY SHALL BE MOUNTED AT THE SAME ELEVATION WITH
RESPECT TO THE FINISHED FLOOR WHERE NFPA 72 §7.4.7 AND §
7.5.4 MOUNTING REQUIREMENTS HEIGHTS CAN BE SATISFIED.
B. ALL FIRE ALARM SYSTEM DEVICES MUST BE COORDINATED AND
INSTALLED SO AS TO BE SAFELY ACCESSIBLE FOR TESTING,
INSPECTION AND MAINTENANCE.
C. OBTAIN OWNER'S APPROVAL OF LOCATIONS OF DEVICES BEFORE
INSTALLATION.
D. PROVIDE SEMI -FLUSH MOUNTED FIRE ALARM CONTROL PANEL
WHERE INSTALLED IN FINISHED AREAS; IN UNFINISHED AREAS,
SURFACE MOUNTED UNITS ARE ACCEPTABLE. ENCLOSURE
PAINTED WITH A CORROSION PROTECTIVE, HARDENED FINISH. DO
NOT FLUSH -MOUNT IN FIRE-RESITANCE RATED WALLS.
E. NO SMOKE SENSORS SHALL BE LOCATED WITHIN 60 INCHES OF
ANY SUPPLY OR RETURN AIR DUCTS.
6. RACEWAYS AND JUNCTION BOXES
A. ELECTRICAL METALLIC TUBING (EMT) SHALL BE A MINIMUM TRADE
SIZE OF 3/4 INCH, NO RACEWAY MAY EXCEED 40% FILL. PROVIDE
SUPPORT IN ACCORDANCE WITH APPLICABLE CODE. FOR DRY
LOCATIONS NOT SUBJECT TO PHYSICAL DAMAGE: FLEXIBLE METAL
CONDUIT (FMC) OR METAL CLAD (MC) CABLE WITHOUT AN OVERALL
NONMETALLIC COATING MAY BE USED FOR FINAL CONNECTION
WITHIN DUCTS, AIR HANDLING SPACES (PLENUMS) AND TO FIELD
DEVICES. MAXIMUM LENGTH OF FLEX/MC CABLE SHALL NOT
EXCEED 6 FT WITHOUT ENGINEERING APPROVAL.
B. UNDERGROUND RACEWAYS SHALL BE PVC AND NO LESS THAN 1"
SIZE. MINIMUM BURIAL COVER SHALL BE NO LESS THAN 24 INCHES
AND IN COMPLIANCE WITH NFPA 70 §300.5.
C. CONTRACTOR SHALL DOCUMENT ALL CONDUIT & JUNCTION BOXES
'AS -BUILT' WITH PIPE SIZE & CONTENTS ON THE RECORD
DRAWINGS TURNED OVER AT THE END OF THE PROJECT.
D. NEW CONDUIT SYSTEM J-BOX COVERS ARE TO BE PAINTED RED &
PERMANENTLY LABELED ON BOTH SIDES (INTERIOR AND
EXTERIOR) AS "FIRE ALARM SYSTEM". ALL NEW AND EXISTING
CONDUITS LEAVING FACP ARE TO BE PERMANENTLY LABELED WITH
THEIR DESTINATION & CONTENTS.
E. CONCEAL ALL WIRING, CONDUIT, BOXES, AND SUPPORTS WHERE
INSTALLED IN FINISHED AREAS.
F. ALL FIRE ALARM CONDUITS SHALL BE ROUTED SO AS NOT TO
OBSTRUCT THE EGRESS PATHWAYS OR MECHANICAL EQUIPMENT
CLEARANCE.
G. ALL CONDUITS IN COLD STORAGE AREAS, OR THAT PASS FROM
THE INTERIOR TO THE EXTERIOR OF THE BUILDING, SHALL BE
SEALED TO STOP CONDENSATION AS REQUIRED BY NFPA 70
760,3(H) AND 300.7. APPROVED MATERIALS INCLUDE
REFRIGERATION PUTTY, POLYWATER DUCT SEALANT, DUCT SEAL
PUTTY, OR EQUAL.
H. CONDUITS SHALL NOT ENTER THE CONTROL PANEL OR ANY OTHER
COMPONENT PROVIDED EXCEPT WHERE ENTRY IS SPECIFIED BY
THE MANUFACTURER.
I. CONDUIT ENTRY ON ALL EXTERIOR AND/OR WEATHERPROOF
DEVICES SHALL ONLY BE MADE FROM THE BOTTOM OF THE BOX.
J. PROVIDE BUSHINGS AT ALL CONDUIT/EMT ENTRIES INTO
ENCLOSURES.
7. FREE WIRING
A. COMPLY WITH NFPA 70 §760.135. PROVIDE LISTED FPLP (OR CMP)
CABLE UNLESS NOTED OTHERWISE, BELOW. LOCATE TO PROVIDE
MAXIMUM PROTECTION AGAINST PHYISCAL DAMAGE. WHERE
LOCATED EXPOSED WITHIN 7 FT OF THE FLOOR, OR PASSING
THROUGH A WALL WITHIN 7 FT: INSTALL WITHIN EMT.
B, DUCTS FOR ENVIRONMENTAL AIR: FPLP (OR CMP).
C. RISERS PENETRATING ONE OR MORE FLOORS: MAY USE FPLP/FPLR
(CMP/CMR) OR FPL/FPLR/FPLP (CM/CMR/CMP) IN EMT. PROVIDE
LISTED FIRESTOP ASSEMBLIES AT EACH FLOOR OR SHAFTWALL
PENETRATION,
D. SPACES NOT USED FOR ENVIRONMENTAL AIR: MAY USE
FPL/FPLR/FPLP (OR CM/CMR/CMP).
8. PENETRATIONS
A. ALL PENETRATIONS THROUGH FIRE/SMOKE PARTITIONS SHALL BE
PROVIDED WITH APPROVED FIRESTOPPING, INSTALLED IN
ACCORDANCE WITH A UL LISTED ASSEMBLY,
B. SEAL NEW PENETRATIONS IN FIRE RESISTANCE RATED
ASSEMBLIES WITH LISTED SEALANT SYSTEMS. MINIMUM F-RATING
IS 2 HOURS IN STAIRS & ELEVATOR HOISTWAYS/MACHINERY
SPACES, THROUGH FLOORS OR THROUGH ROOFS; 1 HOUR
ELSEWHERE. PROVIDE LEAKAGE RATED (L-RATED) SEALANT.
FLOOR PENETRATIONS SHALL BE T-RATED EQUAL (OR SUPERIOR)
TO THE F-RATING. PENETRATIONS OF CORRIDOR WALLS AND STAIR
ENCLOSURES SHALL BE SEALED BY SYSTEMS HAVING A L-RATING
OF NOT MORE THAN 5.0 CFM/SF OF PENETRATION OPENING AT 0.30
INCH (WATER GAUGE).
9. PRIMARY POWER - PROVIDE 120-VAC POWER AT 60-HZ FROM A
DEDICATED BRANCH CIRCUIT, IN ACCORDANCE WITH NFPA 70 AND
NFPA 72. ALL FARP, NAC EXPANDER AND FACP UNITS IN THIS SCOPE
OF WORK SHALL BE PROVIDED WITH 120 VAC POWER SUPPLIED FROM
AN APPROVED POWER SOURCE ON DEDICATED CIRCUITS THAT DO
NOT SERVE OTHER FUNCTIONS. MARKED CIRCUIT BREAKERS LOCK-
ONS SHALL BE INSTALLED TO PREVENT INADVERTENT
DISCONNECTION OF THIS EQUIPMENT AND RED IN COLOR.
MATERIALS AND INSTALLATION REQUIREMENTS (CONTINUED)
10. SECONDARY POWER - PROVIDE BATTERY BACKUP FOR 24 HR OF
STANDBY FOLLOWED BY FIVE MINUTES (0,0833 HR) OF ALARM.
11. VOICE SYSTEMS
A, EVERY SPEAKER CIRCUIT AND AMPLIFIER SHALL BE SIZED TO
PROVIDE 25% SPARE CAPACITY OR GREATER WITH RESPECT TO
POWER OUTPUT. FOR CALCULATION, ALL SPEAKERS SHALL BE
CALCULATED TAPPED NOT LESS THAN SHOWN OR: 2 WATTS IN
LARGE MECHANICALL/ELECTRICAL SPACES, 1 WATT IN ASSEMBLY
AREAS AND Yz WATT ELSEWHERE.
B. CONTRACTOR SHALL PROVIDE, INSTALL AND PROGRAM A MINIMUM
OF ONE BACK-UP AMPLIFIER THAT WILL AUTOMATICALLY BECOME
ACTIVE WHEN A PRIMARY AMPLIFIER REPORTS FAILURE AS
DESCRIBED IN NFPA 72 AAA.7.2.1
12. CALCULATIONS
A. BATTERY CALCULATIONS SHALL ASSUME A STARTING VOLTAGE
NOT GREATER THAN 20.4 VOLTS.
B. VOLTAGE DROP CALCULATIONS SHALL UTILIZE THE MAXIMUM
CURRENT FOR EACH DEVICE AT ITS INDICATED OUTPUT.
13, LABELING - PROVIDE LEGIBLE, PERMANENT LABELS FOR EACH
CONTROL DEVICE, USING IDENTIFICATION USED IN OPERATION AND
MAINTENANCE DATA.
14. WIRING
A. ALL CABLE RUNS SHALL BE CONTINUOUS BETWEEN DEVICES,
WITHOUT SPLICES, WHEREVER FEASIBLE. ALL OTHER
CONNECTIONS SHALL BE TO TERMINAL BLOCKS. WIRE NUTS SHAI''_L
NOT BE PERMITTED. WIRES CONNECTED TOGETHER SHALL HAVE
THE SAME COLOR INSULATION. ALL CONNECTIONS SHALL BE
ACCESSIBLE FOR INSPECTION AND SERVICING AND SHALL BE
CLEARLY IDENTIFIED ON THE RECORD DRAWINGS.
B. CONDUCTOR SIZE SHALL NOT BE LESS THAN 18 AWG FOR
INITIATING DEVICES OR SIGNALING LINE CIRCUITS AND 14 AWG FOR
NOTIFICATION APPLIANCE CIRCUITS.
C. NEW WIRING IN WET LOCATIONS, INCLUDING UNDERGROUND,
SHALL BE WET -RATED WIRE,
D. WIRES INSTALLED OR RECONNECTED UNDER THIS SCOPE OF
WORK SHALL BE CLEARLY LABELED FOR FUNCTIONALITY AND
ZONING.
E. WHERE EXISTING CIRCUITS ARE EXTENDED, EXTENSIONS SHALL
MATCH EXISTING IN WIRE TYPE, GAUGE, INSULATION COLOR AND
OUTER JACKET COLOR.
15. BATTERIES
A. BATTERIES SERVING NEW COMPONENTS SHALL BE NEW.
DEMOLISHED OLD BATTERIES SHALL BE RECYCLED BY THE
CONTRACTOR.
B. BATTERIES SHALL BE LEGIBLY AND PERMANENTLY DATED AT TIME
OF INSTALLATION.
16. STROBE SYNCRONIZATION - TWO OR MORE STROBES VISIBLE WITHIN
THE SAME FIELD OF VIEW SHALL BE SYNCHRONIZED. (NOT APPLICABLE
TO SINGLE STROBES USED FOR FIRE SPRINKLER FLOW
ANNUNCIATION).
17. COORDINATION
A, CONTRACTOR SHALT_ COORDINATE WIRE PLACEMENT
COMPATIBILITY REQUIREMENTS FOR CONDUCTORS THAT SHARE
RACEWAYS OR ENCLOSURES. WIRES THAT ARE INCOMPATIBLE
WITH EACH OTHER DUE TO ELECTROMAGNETIC INTERFERENCE OR
OTHER REASONS SHALL BE APPROPRIATELY SEPARATED TO
ELIMINATE OR REDUCE INCOMPATIBILITY TO MANUFACTURER -
SPECIFIED LEVELS.
B. CONTRACTOR SHALL COORDINATE WORK WITH THE OWNER AND
OTHER CONTRACTORS ON SITE TO MINIMIZE DISRUPTION TO
OPERATIONS. WHERE FIRE ALARM COMPONENTS ARE OUT OF
SERVICE FOR FOUR HOURS OR MORE, CONTRACTOR SHALL
NOTIFY THE AHJ AND PROVIDE FIRE WATCH.
INSPECTION AND TESTING REQUIREMENTS
1. THE FIRE ALARM SYSTEM SHALL BE TESTED IN ACCORDANCE WITH
NFPA 72 REQUIREMENTS OF LOCAL AUTHORITIES, INCLUDING UNDER
NORMAL AND STANDBY POWER SUPPLIES AND AS INDICATED ON
PLANS. DOCUMENT EACH INSPECTION AND TEST,
2. PREPARE FOR TESTING BY ENSURING THAT ALL WORK IS COMPLETE
AND CORRECT; PERFORM PRELIMINARY TESTS AS REQUIRED,
3. NOTIFY AUTHORITIES HAVING JURISDICTION AND COMPLY WITH THEIR
REQUIREMENTS FOR SCHEDULING INSPECTIONS AND TESTS AND FOR
OBSERVATION BY THEIR PERSONNEL.
4. PROVIDE COMPLETED RECORD DRAWINGS, COMPLETED NFPA 72
RECORD OF COMPLETION AND COMPLETED NFPA INSPECTION AND
TEST FORM AS REQUIRED 14 DAYS PRIOR TO COMMENCING FINAL
ACCEPTANCE TEST.
5. PROVIDE ALL TOOLS, SOFTWARE, AND SUPPLIES REQUIRED TO
ACCOMPLISH INSPECTION AND TESTING.
6. SYSTEM START UP AND COMMISSIONING SHALL INCLUDE TRIAL
OPERATION OF ALL MAIN AND PERIPHERAL EQUIPMENT AND
SOFTWARE PROGRAMMING OF LOCAL FACP.
7. DUCT SMOKE DETECTORS: PROPER AIR DUCT SENSOR AIR FLOW
SHALL BE DEMONSTRATED USING MANUFACTURER'S APPROVED TEST
EQUIPMENT. DOCUMENTATION OF AIR FLOW VELOCITY SHALL BE
PROVIDED AND SHALL INCLUDE VELOCITY, AIR HANDLER NAME,
SENSOR LOCATION, MANUFACTURER AND MODEL NUMBER OF
TESTING DEVICE, THIS TESTING SHALL BE CONDUCTED AFTER THE AIR
HANDLING SYSTEM'S TESTING AND BALANCING WORK HAS BEEN
COMPLETED.
F
PROJECT CLOSE-OUT REQUIREMENTS
1. ALL NEW SYSTEM ADDRESS & CIRCUIT INFORMATION SHALL BE ON
RECORD DRAWINGS & ON A DEVICE WIRING LEGEND. THREE COPIES
OF THE LEGEND SHALL BE TURNED OVER W/ RECORD DRAWINGS, A
COPY LEFT IN THE FRCP, AND A SOFTWARE COPY PROVIDED,
2. AT THE PROJECT COMPLETION, THE FIRE ALARM CONTRACTOR SHALL
PROVIDE THE OWNER WITH A COMPLETE FIRE ALARM SYSTEM
OPERATIONS AND MAINTENANCE (0&M) MANUAL, AND ALL NFPA 72
REQUIRED SYSTEM CLOSE-OUT DOCUMENTATION, THE FIRE ALARM
SYSTEM SHALL BE OPERATED AND MAINTAINED IN ACCORDANCE WITH
THE REQUIREMENTS OUTLINED IN NFPA 72.
3. EXACT INSTALLATION WIRING COUNTS SHALL BE SHOWN ON AS BUILT
WIRING DIAGRAMS AND INSTALLATION DRAWINGS, UPON PROJECT
ACCEPTANCE.
4. PROVIDE ALL NFPA 72 FORMS COMPLETELY FILLED OUT AFTER THE
FINAL CERTIFICATE OF OCCUPANCY.
5. AS -BUILT DRAWINGS. NFPA FORMS, RECORD DRAWINGS AND FACP
PROGRAM FILE SHALL BE STORED ON A FLASH DRIVE PROVIDED AND
INSTALLED BY FA CONTRACTORS AND TRANSMITTED
ELECTRONICALLY TO OWNER'S REPRESENTATIVE.
LINE TYPE LEGEND
NEW
EXISTING
-------- DEMOLISH
- - - - UNDERGROUND
SYMBOL LEGEND
REFER TO LINE LEGEND FOR DEPICTION OF NEW/EXISTING/DEMO STATUS
NOT ALL SYMBOLS MAY BE USED.
FOR WIRE LEGEND, REFER TO SHEET FA-101.
ANN
REMOTE ANNUNCIATOR
AMP
AMPLIFIER
FACU
FIRE ALARM CONTROL UNIT
FARP
FIRE ALARM REMOTE TRANSPONDER
NAC
FIRE ALARM NAC EXPANDER (GENERAL)
WF
FIRE SPRINKLER FLOW SWITCH
FT
FIRE SPRINKLER TAMPER SWITCH
ElFIRE
SPRINKLER PRESSURE SWITCH
T
SPOT SMOKE DETECTOR
AIM
ADDRESSABLE SINGLE INPUT MODULE
Alo
ADDRESSABLE INPUT/OUTPUT MODULE
AIM
ADDRESSABLE DOUBLE INPUT MODULE
2
aADDRESSABLE
OUTPUT MODULE
/'�Slxj'YY-ZZ
SLC DEVICE ON SYSTEM #X, CIRCUIT #YY,
��f
DEVICE #ZZ
WALL -MOUNT APPLIANCES:
Q-� MANUAL PULL STATION
STROBE
HORN
HORN/STROBE
POD SPEAKER
o SPEAKER/STROBE
CHIME SOUNDER
CEILING -MOUNT APPLIANCES:
'1o'
STROBE
` F
HORN
" 2
HORN/STROBE
09
SPEAKER
SPEAKER/STROBE
�c
CHIME SOUNDER
0
FIRE ALARM SHEET LIST
SHEET CURRENT CURRENT
NUMBER SHEET NAME REVISION DATE
FA-100
FIRE ALARM NOTES
FIRE ALARM QUANTITIES
0
09/07/21
FA-101
1
10/08/21
FA-102
FIRE ALARM SITE PLAN
0
09/07/21
FA-110
FIRE ALARM OVERALL PLAN
0
09/07/21
FA-110.1
FIRE ALARM PARTIAL PLAN -ZONE 1
1
10/08/21
FA-110.2
FIRE ALARM PARTIAL PLAN - ZONE 2
0
09/07/21
FA-110.3
FIRE ALARM PARTIAL PLAN - ZONE 3
1
10/08/21
FA-110.4
I✓ E ALARM PARTIAL PLAN - ZONE: 4
1
10/08/21
0.5
P
F RE ALARM PARTIAL PLAN - ZONE 5
1
10/08/21
10.6
F RE ALARM PARTIAL PLAN - ZONE 6
1
10/08/21
FA-110.7
FIRE ALARM PARTIAL PLAN -ZONE 7
0
09/07/21
FA-110.8
RE ALARM PARTIAL PLAN - ZONE 8
0
09/07/21
FA-110.9
FIRE ALARM PARTIAL PLAN - ZONE 9
0
09/07/21
FA-110.10
FIRE ALARM PARTIAL PLAN - ZONE 10 I
0
09/07/21
FA-400
SEQUENCE OF OPERATIONS AND
DEVICE LABELS
1
10/08/21
FA-500
FIRE ALARM RISER DIAGRAM - NAC
1
10/08/21
FAFA-5 1010
FIRE ALARM RISER DIAGRAM - SLC
1
10/08/21
I FA-600
FIRE ALARM CALCULATIONS 1
1
10/08/21
FA-601
FIRE ALARM CALCULATIONS 2
0
09/07/21
A-602
FA_-7C6_
FIRE ALARM CALCULATIONS 3
FIRE ALARM DETAILS a
1
1
10/08/21
10/08/21
SUBSCRIPTS AND ABBREVIATIONS
ABBREV. DESCRIPTION
A AMPERE -
AFF ABOVE FINISHED FLOOR
AH AIR -HANDLER
AHJ AUTHORITY HAVING JURISDICTION
AIM ADDRESSABLE INPUT MODULE
AMP AMPLIFIER
AOM ADDRESSABLE OUTPUT MODULE
BATT BATTERY
CD CANDELA
(E) EXISTING
EMT ELECTRICAL METALLIC_ TUBING
EOI END OF LINE
EOLR END OF LINE RESISTOR
EOR ENGINEER OF RECORD
ER ELECTRICAL EQUIPMENT ROOM
FACP FIRE ALARM CONTROL PANEL
FATC FIRE ALARM TERMINATION CABINET
FARP FIRE ALARM REMOTE TRANSPONDER PANEL
FLA FULL LOAD AMPERES
FMC FLEXIBLE METAL CONDUIT
GFI GROUND FAULT CIRCUIT INTERRUPTING
GRD GROUND
HOA HAND/OFF/AUTOMATIC
IDC INITIATING DEVICE CIRCUIT
J-BOX JUNCTION BOX
KV KILOVOLT
KVA KILOVOLT AMPERE
KW KILOWATT
MC METAL CLAD CABLE
------------------- ---
�MECH MECHANICAL
MIC MICROPHONE
(N) NEW
NAC NOTIFICATION APPLIANCE CIRCUIT
NC NORMALLY -CLOSED CONTACT
NIC NOT IN CONT_RA_CT
NTS NOT TO SCALE
NO NORMALLY -OPEN CONTACT
PS POWER SUPPLY
PVC POLYVINYL CHLORIDE RACEWAY
SLC SIGNALING LINE CIRCUIT
TYP TYPICAL
LION UNLESS OTHERWISE NOTED
V VOLT
VA _ VOLT AMPERE
W 1 WATT
Antinomy Consulting Engineers
Code Consulting - fire Protection - Smoke Control
600 Rinehart Road Suite 2054
Lake Mary, FL 32746-4955
Tel. 321-888-2882 Online: antinomy.com
Prepared For:
d
°a>4,
EC #13001688
9
No 73972 '� v
STATE OF
°r 1r 11 ii' 0 e 10/08/21
This document has been digitally signed and sealed by Gregory A.
Tabaka, PE on the date adjacent to the seal. Printed copies of this
document are not considered signed and sealed and the signature
must be verified on any electronic copies.
Revisions
No. Description Date
0 PERMIT SET 09/07/21
i
COMPLETE ALARM INC.
MAVERICK BOATS INC.
Project Address ,$
4551 ST. LUCIE BLVD s
FT. PIERCE, FL 34946 ✓
FIRE ALARM NOTES'
_ _ N
Project Number ACE0146
Date _ 10/08/21 0
Drawn By G.TABAKA v,
Checked By G.TABAKA
o
FA-1 00
2i
W
(REV. 0)
Scale (UON) 1/$" = 1'-0"
0
U
C
M
A
LL
u
[]
C
E.
A
ANTINOMY
8
4
3
DESCRIPTION OF REVISIONS
REVISION 0
SUBMITTED FOR PERMIT.
REVISION 1
1. ADDED AN DEVICES FOR NEW BOOTH IN EXISTING PHASE,
CONNECTED TO EXISTING RPS4.
2. ADDED DUCT SMOKE DETECTOR FOR NEW RAU-G2 AND
ADDRESSABLE RELAY MODULE FOR SHUTDOWN.
3. CHANGED NAC EXPANDER RPS6 MATERIAL,
4. ADDED WIRING DETAIL FOR RPS6.
5. REALLOCATED NEW GELCOAT BOOTH (IN EXPANSION PHASE) AN
APPLIANCES TO RPS6.
6. DELETED FOUR DUAL -MONITOR MODULES FOR FIRE SPRINKLER
SUPERVISION; NOW SUPERVISED IN SERIES FROM ONE MODULE.
7. CHANGED SEVEN ADDRESSABLE PULLSTATIONS TO CONVENTIONAL;
ADDED MONITOR MODULE TO SUPERVISE.
8. REVISED RISER DIAGRAM, CALCULATIONS AND QUANTITIES TO
REFLECT CHANGES.
FIRE ALARM BILL OF MATERIAL (NEW)
• MANUFACTURER MODEL
AUX. COMPONENT
DESCRIPTION COUNT
FIRE ALARM HEAD END
•
I SILENT KNIGHT
SK-PS10
NAC EXPANDER, 10 AMP, 7 CKT.
2
ADDRESSABLE MODULES
•
SILENT KNIGHT
SK-CONTROL
ADDRESSABLE CONTROL MODULE FOR
NAC, OUTPUTS=1
1
•
SILENT KNIGHT
SK-MONITOR
ADDRESSABLE INPUT MODULE, INPUTS=1
3
•
SILENT KNIGHT
SK-MONITOR-2
ADDRESSABLE INPUT MODULE, INPUTS=2
1
•
SILENT KNIGHT
SK-RELAY
ADDRESSABLE OUTPUT MODULE,
OUTPUTS=1
7
INITIATING DEVICES
•
SILENT KNIGHT
f SK-HEAT-W
B300-6 BASE
HEAT DETECTOR ON 6" BASE
2
•
SILENT KNIGHT
SK-PHOTO-R-W
DNRW HOUSING, DST
SAMPLING TUBE
PHOTOELECTRIC SMOKE DETECTOR IN
NEMA 4 DUCT DETECTOR HOUSING
5
•
SILENT KNIGHT
SK-PHOTO-W
B300-6 BASE
PHOTOELECTRIC SMOKE DETECTOR ON 6"
BASE
1
•
SILENT KNIGHT
SK-PS-DA
MANUAL PULL STATION, DOUBLE ACTION,
CONVENTIONAL
7
•
SILENT KNIGHT
SK-PULL-DA
MANUAL PULL STATION, DOUBLE ACTION
8
AUDIBLENISIBLE APPLIANCES, CEILING MOUNT
•
FEDERAL SIGNAL
FHEX
CEILING/WALL MOUNT EXPLOSIONPROOF
HORN
4
•
FEDERAL SIGNAL
FSEX-HI
_
CEILING/WALL MOUNT EXPLOSIONPROOF
STROBE
4
•
WHEELOCK
HSC
CEILING MOUNT HORN/STROBE,
15/30/60/75/115/150/177 CD SELECTABLE,
90/95/99 DB SELECTABLE
40
AUDIBLENISIBLE APPLIANCES, CEILING MOUNT, WEATHERPROOF
•
SYSTEM SENSOR PC2RHK WITH FACTORY -SUPPLIED
PLASTIC BACKBOX/BASE
_
RED CEILING MOUNT WEATHERPROOF
STROBE, NEMA 4X, SELECTABLE
135/150/177/185 CD, SELECTABLE 83/86/88 DB
3
AUDIBLE/VISIBLE APPLIANCES, WALL MOUNT
•
WHEELOCK
LHSR3
RED WALL MOUNT HORN/STROBE, _T
15/30/75/110 CD SELECTABLE
1
INTERFACES
•
DITEK
DTK-2MHLP24B
WB
SURGE SUPPRESSOR, 24V, 4 CONTACTS
1
•
DITEK
DTK-120HW
SURGE SUPPRESSOR, 120V, 2 CONTACTS
2
WIRE LEGEND (NEW)
WIRE
ESTIMATED
RESIST.
CAPACIT.
TYPE
DESCRIPTION
LENGTH
(0/kFT)
(pF/kFT)
AUX. POWER,
STROBE (NAC), HORN WIRING (NAC)
M8P
1 PAIR #18 COPPER, SOLID, TWISTED OR UNTWISTED, UNSHIELDED,
660 ft
8.45
N/A
FPLP, WEST PENN 60980B [CI=260]
P2P
1 PAIR #12 COPPER, SOLID OR STRANDED, TWISTED OR UNTWISTED,
4535 ft
2.05
N/A
UNSHIELDED, FPLP, WEST PENN 60995B OR 60995BS [CI=880 SOLID,
CI=920 STRAND]
P4P
1 PAIR #14 COPPER, SOLID OR STRANDED, TWISTED OR UNTWISTED,
1290 ft
3.26
N/A
UNSHIELDED, FPLP, WEST PENN 60993B OR 60993BS [CI=570 SOLID,
CI=610 STRAND]
P6P
1 PAIR #16 COPPER, SOLID OR STRANDED, TWISTED OR UNTWISTED,
1120 ft
5.29
N/A
UNSHIELDED, FPLP, WEST PENN 60991B OR 60995BS [CI=380 SOLID,
CI=420 STRAND]
P8P
1 PAIR #18 COPPER, SOLID, TWISTED OR UNTWISTED, UNSHIELDED,
375 ft
8.45
N/A
FPLP, WEST PENN 609808 [CI=260]
SIGNALING LINE CIRCUIT WIRING (SLC)
T8P
1 PAIR #18 COPPER, SOLID, TWISTED PAIR, UNSHIELDED, FPLP, WEST
2595 ft
8.45
0,031
PENN 60980B [CI=260]
VOICE AUDIO WIRING (NAC)
N/A
INSTALLER'S CHOICE: MAY SUBSTITUTE LARGER WIRING FOR FOR AUX. POWER AND NAC CIRCUITS, BUT NOT LARGER THAN 12 AWG.
QUANTITIES AND MATERIAL REVISED-
Antinomy Consulting Engineers
Code Consulting - Fire Protection - Smoke Control
600 Rinehart Road Suite 2054
Lake Mary, FL 32746-4955
Tel. 321-888-2882 Online: antinomy.com
Prepared For:
�a
,
jvh,
EC #13001688
`��11111111///�
No 73972
% STATE OF
fill 1 l is 10/08/21
This document has been digitally signed and sealed by Gregory A.
Tabaka, PE on the date adjacent to the seal. Printed copies of this
document are not considered signed and sealed and the signature
must be verified on any electronic copies.
Revisions
No. Description Date
0 PERMIT SET 09/07/21
1 NEW BOOTH, RPS6 REALLOC. 10/08/21
COMPLETE ALARM INC.
MAVERICK BOATS, INC.
Project Address
4551 ST. LUCIE BLVD
FT. PIERCE, FL 34946
FIRE ALARM QUANTITIES
Project Number
ACE0146
Date
10/08/21
N
w
Drawn By
G.TABAKA
pp:_
Checked By
G.TABAKA
z
FA-1
01
Q
(REV. 1)
LU
cc
U_
Scale (UON)
J I H j G F E
19
It
3
A
8
VA
6
4
J , M
Antinomy Consulting Engineers
Code Consulting • Fire Protection - Smoke Control
600 Rinehart Road Suite 2054
Lake Mary, FL 32746-4955
Tel, 321-888-2882 Online: antinomy.com
Prepared For:
.,h
r
EC #13001688
,``��►illlllf////
\PG OE �N S�q,
No 73972 i
7�
p ; 414
STATE OF
too IN%
'/// s f I iil i `� \\` 10/08/21
This document has been digitally signed and sealed by Gregory A.
Tabaka, PE on the date adjacent to the seal. Printed copies of this
document are not considered signed and sealed and the signature
must be verified on any electronic copies.
Revisions
No. Description Date
0 PERMIT SET 09/ 77/21
COMPLETE ALARM INC.
MAVERICK BOATS, INC.
Project Address
4551 ST. LUCIE BLVD
FT. PIERCE, FL 34946
FIRE ALARM
SITE PLAN
N
O
Project Number
ACE0146
0
Date
10/08/21
Drawn By
G.TABAKA
Checked By
G.TABAKA
--
73—
FA-1
02
LU
a
(REV.0)
LU
U-
-
Scale (UON)
1" = 50'-0"
N
O
1 3 I I I N ( G I G
c
4
3
2
1
Antinomy Consulting Engineers
Code Consulting • fire Protection • Smoke Control
600 Rinehart Road Suite 2054
Lake Mary, FL 32746-4955
Tel. 321-888-2882 Online: antinomy.com
Prepared for:
.>
9
lv
EC #13001688
No 73972
STATE OF
!!� s/ r i t i `\ 10/08/21
This document has been digitally signed and sealed by Gregory A.
Tabaka, PE on the date adjacent to the seal. Printed copies of this
document are not considered signed and sealed and the signature
must be verified on any electronic copies.
Revisions
No. Description Date
0 PERMIT SET 09/07/21
COMPLETE ALARM INC.
MAVERICK BOATS, I_NC.
Project Address
4551 ST. LUCIE BLVD
FT. PIERCE, FL 34946
FIRE ALARM OVERALL
PLAN
N
\
0
CD
0
Project Number ACE0146
Date — 10/08/21
Drawn By GJABAKA
Q
Checked By G.TABAKA
cc
o
FA-1 10
(REV.0)
UJ
U-
scale (uoN) 1/32" = 1'-0"
8
7
6
5
4
3
2
H I G F E ( D C B I A
TYPICAL N°TES: A N T I N 0 M Y
1. CEILING MOUNTED HORN/STROBES:
A. SHALL BE EQUIPPED WITH MINIMUM 4"x4"x
2-1/8" BACKBOXES SUSPENDED FROM
STRUCTURAL STEEL ON NUMBERED GRID
LINES.
B. BACKBOXES SHALL BE INSTALLED LEVEL,
OPEN FACE DOWNWARDS AT AN ELEVATION
OF NO HIGHER THAN 29'-10" ABOVE THE FLOOR
/ 2 3 4 5 �G 7 NEAR THE F-GRID LINE AND 25' NEAR THE B-
GRID LINE.
1 1 C. ALL BACKBOXES SHALL HAVE A FACTORY -
MADE 1/4 HOLE AT THE TRUE CENTER OF THE
BOX.
D. ATTACH TO STRUCTURE USING A LISTED
SCREW -TYPE BEAM CLAMP (EQUAL TO CADDY Antinomy Consulting Engineers
#4QTIBC TO SUPPORT 1/4" THREADED ROD. Code Consulting d Fire Protection •smoke Control
) 600 Rinehart Road Suite 2054
SUSPEND BACKBOX FROM THREADED ROD Lake Mary, FL 32746-4955
I ! ! USING SECURE ATTACHMENT, SUCH AS Tel. 321-888-2882 Online: antinomy.com
DOUBLE OR JAM -NUTS.
E. ALL BOXES ON AN EAST -WEST LINE SHALL BE Prepared For:
AT EQUAL ELEVATION, DO NOT DEVIATE FROM �L`''P
L'��
_ _ _ _ * _ _ _ _ T8P s1*1,5W-(M59) T8P THE ALIGNMENT SHOWN.
C,G �_ S1 1.5W (M62) — T8P - -- �- — — — T8P - — — — — — — — — —
� -----r - — � INSTALL WHEELOCK'UNIVERSAL MOUNTING
F LJ i BASE' AT EACH.
OAON�
1*1.5W (M61) S1*1.4-(M60) p� G. PROVIDE BUSHING OR CLAMP WHERE WIRE
FAN SHUTDOWN TS —C.) C
AIM GEL BOOTH SPKR TAMPER �p 3/4" IMC UNTIL ABOVE BOOTH I
(RAU-BG1, EF-BG1, EF-BG2, E -BG3,
C I � ENTERS OR EXITS BOX.
! EF-BG4) �� H. PROVIDE ADDITIONAL SUPPORT WHERE a
� WITHIN BOOTH.. � c V6 5-1 1 XP'70 REQUIRED BY CODE OR AHJ.
P6P
WITHIN BOOTH C V6*6-1 /1'\1 2. NAC SUPPLY WIRING SHALL BE ROUTED ALONG \
!
TRANSVERSE PURLINS AND SUPPORTED WITH F�� P I ! WIRE J-HOOKS (EQUAL TO EATON BCH12-F3 OR -F4 EC #13001688
DEPENDING UPON STEEL FLANGE TYPE). PROVIDE
SUPPPORT AT SPACING NO GREATER THAN 54" ON
P4P, P6P CENTER BETWEEN HOOKS.
I i I i I I
I GELCOAT BOOTH 3. FOR WIRES TO BE SUPPORTED TRAVELING
PARALLEL WITH NUMBERED STEEL, PROVIDE
\- P2P T8P j I EATON BCH21-F3 OR -F4 (OR EQUAL) J-HOOKS ON
I P2P, T8P P2P, 2x T8P P2P, 2x T8P
I I SAME SPACING AS ABOVE.
C * C C * 4. WHERE LOCATED WITHIN 10 FT OF THE FINISHED
V545 -
B V5 4 4 BOOTH V5 4 3
ABOVE BOOTH ABOVE
FLOOR ALL WIRES SHALL BEENCLOSED
150 Cd 150 C T 150 Cd , A LIN EMT
d
�O<p99 dI3 { 99 dB j j 99 dB ' (3/4" MINIMUM). WHERE WIRES ENTER OR EXIT
THIS EMT, PROVIDE LISTED BUSHING.
r
T8P 5. ALL WIRES SERVING, ENTERING OR LOCATED
1111111��
BOOTH: ASSUMED CLASS I, DI i ION I AREA f WITHIN THE BOOTHS SHALL BE IN THREADED %��`�'1F
,I r MINIMUM 3/4" IMC OR RMC. ��`G,.,�`'GE"N'''�,�'�'%
s .y
No 73972
RAU-BG1 SUPPLY DUCT (ROOF)
WP 6. ROOFTOP EQUIPMENT: PROVIDE DEDICATED WIRE o7
LOOP THAT SERVES ONLY EQUIPMENT ABOVE THE
I I I ' ROOFLINE. PRIOR TO CONNECTION TO FIRE ALARM
E — — — — — — — — — — — — — — — — — — — — — — — — — -- ——YSTEM, PROVIDE SURGE SUPPRESSION. *, ��
STATE OFO \ ;;
7. COORDINATE LOCATION AND CONNECTION OF FANON
SHUTDOWN RELAYS WITH INSTALLER.
s t 1111110/08/21
r
This document has been digitally signed and sealed by Gregory A.
Tabaka, PE on the date adjacent to the seal. Printed copies of this
document are not considered signed and sealed and the signature
must be verified on any electronic copies.
— Revisions
No. Description Date
!
0 PERMIT SET 09/07/21
! ' 1 NEW BOOTH, RPS6 REALLOC. 10/08/21
P4P, P6P, T8P
i � 1
1
r S1*1,5R-2(D�)
P2P - P2P /� P2P 2xT8P 0 P2P 2xT8P RAU-SG1 SUPPLY DUCT (ROOF) f
WP
C i C C
150 Cd 5*3-5 150 Cd 5*3-4 150 Cd 5*3-3
FD 2xT8P
i <,p99 dB ( 99 dB 99 dB ' - -- --
CB�—
GELCOAT BOOTH--
i I C
P4P, P6P, TBP C
Fo pd V6*7-1 FF 0 v6*7-2 COMPLETE ALARM INC.
2xP2P � XP 1 XP I
-'� C ( C
v6*3-1 ;o; ' v6*4-1 MAVERICK BOATS, INC.
2xP2P P4P XP,150 F0 XP 1�0
' 1p ' Project Address
s1*1.4w (M63) /4" IMC UNTIL ABOVE BOOTH Al
4551 ST. LUCIE BLVD
BOOTH: ASSUMED CLASS I, DIV* 1 ARE 1 FT. PIERCE, FL 34946
I 3/4" EMT TYP. PENETRATION: PROVIDE MIN 3/4" EMT STUB s1 1,4 (M64) P?P, P4P
THROUGH WALL WITH BUSHINGS N BOTH ENDS. AOM FAN SH TDOWN
P�P,2xP4P °°
(RAU S 1, EF-SG1, EF SG2) o
PLENUM
iA _ FIRE ALARM PARTIAL ;
S�S � I S1*1.4W�M26 � -� ... � -�►-� � -�-� � � '
120 s1*1.4 -(D4) ! ! ! PLAN -ZONE 1 W
r 0
CONNECT TO EXISTIN ® I Project Number ACE0146
120 V CIRCUIT
/ Date 10/08/21
! HEAT DETECTOR WALL -MOUNTED - PAC _NAC
TO PROTECT NAC BOOSTER IN LIEU •Q Drawn By G.TABAKA cc
OF SMOKE DETECTO 1SK-Ps10 j sK-5499� RPS6 P 4 ' Checked By G.TABAKA a_cc
G
F
E
C'
C
I.
A
FA-110.
REV.
Scale (VON) 1/8" = V-0" r
F
J
H
G
F
E
r
If
B
A
8
7
6
5
4
3
2
iI I
8� 9 10 11 12 13
H
S 1 * 1,5W-(M58)
G
F
— T8P
E
D IC
TYPICAL NOTES:
1. CEILING MOUNTED HORN/STROBES:
A. SHALL BE EQUIPPED WITH MINIMUM 4"x4"x
2-1/8" BACKBOXES SUSPENDED FROM
STRUCTURAL STEEL ON NUMBERED GRID
LINES.
B. BACKBOXES SHALL BE INSTALLED LEVEL,
OPEN FACE DOWNWARDS AT AN ELEVATION
OF NO HIGHER THAN 29'-10" ABOVE THE FLOOR
NEAR THE F-GRID LINE AND 25' NEAR THE B-
GRID LINE.
C. ALL BACKBOXES SHALL HAVE A FACTORY -
MADE 1/4" HOLE AT THE TRUE CENTER OF THE
BOX.
D. ATTACH TO STRUCTURE USING A LISTED
SCREW -TYPE BEAM CLAMP (EQUAL TO CADDY
#4QTIBC) TO SUPPORT 1/4" THREADED ROD.
SUSPEND BACKBOX FROM THREADED ROD
USING SECURE ATTACHMENT, SUCH AS
DOUBLE OR JAM -NUTS.
E. ALL BOXES ON AN EAST -WEST LINE SHALL BE
AT EQUAL ELEVATION. DO NOT DEVIATE FROM
THE ALIGNMENT SHOWN.
_--_F_ INSTALL WHEELOCK'UNIVERSAL MOUNTING
BASE' AT EACH.
G. PROVIDE BUSHING OR CLAMP WHERE WIRE
ENTERS OR EXITS BOX,
H. PROVIDE ADDITIONAL SUPPORT WHERE
REQUIRED BY CODE OR AHJ.
2. NAC SUPPLY WIRING SHALL BE ROUTED ALONG
TRANSVERSE PURLINS AND SUPPORTED WITH
WIRE J-HOOKS (EQUAL TO EATON BCH12-F3 OR -F4
DEPENDING UPON STEEL FLANGE TYPE). PROVIDE
SUPPPORT AT SPACING NO GREATER THAN 54" ON
CENTER BETWEEN HOOKS.
3. FOR WIRES TO BE SUPPORTED TRAVELING
_ _—PARALLEL WITH NUMBERED STEEL, PROVIDE
EATON BCH21-F3 OR -F4 (OR EQUAL) J-HOOKS ON
SAME SPACING AS ABOVE,
4. WHERE LOCATED WITHIN 10 FT OF THE FINISHED
FLOOR, ALL WIRES SHALL BE ENCLOSED IN EMT
(3/4" MINIMUM). WHERE WIRES ENTER OR EXIT
THIS EMT, PROVIDE LISTED BUSHING,
5. ALL WIRES SERVING, ENTERING OR LOCATED
WITHIN THE BOOTHS SHALL BE IN THREADED
MINIMUM 3/4" IMC OR RMC.
6. ROOFTOP EQUIPMENT: PROVIDE DEDICATED WIRE
LOOP THAT SERVES ONLY EQUIPMENT ABOVE THE
ROOFLINE. PRIOR TO CONNECTION TO FIRE ALARM
SYSTEM, PROVIDE SURGE SUPPRESSION.
7. COORDINATE LOCATION AND CONNECTION OF FAN
SHUTDOWN RELAYS WITH INSTALLER.
ANTINOMY
Antinomy Consulting Engineers
Code Consulting - fire Protection - Smoke Control
600 Rinehart Road Suite 2054
Lake Mary, FL 32746-4955
Tel. 321-888-2882 Online: antinomy.com
Prepared For
T"-
IL
1
EC #13001688
``%��1111111���
-;% 1" No 73972 '�
v
.0
i-P % STATE OF $ tvW�
11 I i 1 t`♦♦ 10i08/21
This document has been digitally signed and sealed by Gregory A.
Tabaka, PE on the date adjacent to the seal. Printed copies of this
document are not considered signed and sealed and the signature
must be verified on any electronic copies.
Revisions
No. Description Date
0 PERMIT SET 09/07/21
i
COMPLETE ALARM INC.
MAVERICK BOATS, INC.
Project Address
4551 ST. LUCIE BLVD
FT. PIERCE, FL 34946
N
O
FIRE ALARM PARTIAL
PLAN - ZONE 2 N
w
z
0
Project Number ACE0146 N
Date 10/08/21
J
Drawn By G.TABAKA
Checked By G.TABAKA a
a
FAIIIIIII111 10. W_
EV.0) N
Scale (UON) 1/8" = 1'-Oil
B
0
J
I
G I F
E
C
C
B
A
MA
G -
6
CF
5
15 16
1 1
1
i I I
1
1
T8P
17 18
Z T6P,2xM8P T8P
P2P
CONY. --- -, S1*1.5 M99(!DC
T6P FROM FACP, P2P 15
— _S1*1.5W-(M55) — T8P —
U
T8P FROM ROOF +1
I
I
19 20
S1*1.5-(M99)
M PULL STATIONS AT EXPANSI N )
S1*1.5-(M69) I' ELEC I
M NAC TROUBLEMONITOR
S1*1.5-(D3) '— M8P - -
O 1 - --- NEW 12#2 + GROUND RUN IN 3/4 EMT TO 120 V POWER.
15 OR 20 A BREAKER. DEDICATED Ti0 FIRE ALARM
V5 2-1 0120 SERVICE ONLY. PROVIDE RED BREAKER LOCK.
T8P GROUND SURGE SUPPRESSOR. -�,
NAC -47k R-PS10 ---- — — — — — --I— - - ---- - M8P __
21
PLENUM r
r
r
P6P 1
HULL & DECK r
GRIND
(SHUTDOWN CONTROL FOR FANS DCFH1 AND -- 3/4" EMT 1
DCF-D1 NOT REQUIRED AND WERE OMITTED) 1
i
' i I1
f C Wp r
- 8xP2P, P6P, T6P, T8P - { WITHIN GRINDING BOOTH o V3*3-1 1
�i 177 1
f-- ----- - ---------
1
WITHIN GRINDING BOOTH - 3 o V3*3-2 1
— -- I P6P
I i
SURGE SUPPRESSION FOR ROOF -TOP SLC.
PROVIDE #14 GROUND TO'BUILDING GROUND OR GROUND ROD.
TYPICAL NOTES.-
1. CEILING MOUNTED HORN/STROBES;
A. SHALL BE: EQUIPPED WITH MINIMUM 4"41x
2-1/8" BACKBOXES SUSPENDED FROM
STRUCTURAL STEEL ON NUMBERED GRID
LINES.
B. BACKBOXES SHALL BE INSTALLED LEVEL,
OPEN FACE DOWNWARDS AT AN ELEVATION
OF NO HIGHER THAN 29'-10" ABOVE THE FLOOR
NEAR THE: F-GRID LINE AND 25' NEAR THE B-
GRID LINE,
C. ALL BACKBOXES SHALL HAVE A FACTORY -
MADE 1/4" HOLE AT THE TRUE CENTER OF THE
BOX.
D. ATTACH TO STRUCTURE USING A LISTED
SCREW -TYPE BEAM CLAMP (EQUAL TO CADDY
#4QTIBC) TO SUPPORT 1/4" THREADED ROD.
SUSPEND BACKBOX FROM THREADED ROD
USING SECURE ATTACHMENT, SUCH AS
DOUBLE OR JAM -NUTS.
E. ALL BOXES ON AN EAST -WEST LINE SHALL BE
AT EQUAL ELEVATION. DO NOT DEVIATE FROM
THE ALIGNMENT SHOWN.
F: INSTALL WHEELOCK'UNIVERSAL MOUNTING
BASEAT EACH,
G. PROVIDE BUSHING OR CLAMP WHERE WIRE
ENTERS OR EXITS BOX.
H. PROVIDE ADDITIONAL SUPPORT WHERE
REQUIRED BY CODE OR AHJ.
2. NAC SUPPLY WIRING SHALL BE ROUTED ALONG
TRANSVERSE PURLINS AND SUPPORTED WITH
WIRE J-HOOKS (EQUAL TO EATON BCH12-F3 OR -F4
DEPENDING UPON STEEL. FLANGE TYPE). PROVIDE
SUPPPORT AT SPACING NO GREATER THAN 54" ON
CENTER BETWEEN HOOKS.
3. FOR WIRES TO 13E SUPPORTED TRAVELING
PARALLEL WITH NUMBERED STEEL, PROVIDE
EATON BCH21-F3 OR -F4 (OR EQUAL) J-HOOKS ON
SAME SPACING AS ABOVE.
C C ' 4. WHERE LOCATED WITHIN 10 FT OF THE FINISHED
V5*2-5 V5*2-2 � ABOVE GRINDING BOOTH -� V5*2-3
150 Cd 150 Cd I 150 Cd HULL & DECK r FLOOR ALL WIRES SHALL BE ENCLOSED IN EMT
99 dB I 99 dB i I I 99 dB GRIND I 1 (3/4" MINIMUM). WHERE WIRES ENTER OR EXIT
1 -- r THIS EMT, PROVIDE LISTED BUSHING.
-- r 5. ALL WIRES SERVING, ENTERING OR LOCATED
1 WITHIN THE BOOTHS SHALL BE IN THREADED
MINIMUM 3/4" IMC OR RMC.
1 � r
1 - 6. ROOFTOP EQUIPMENT; PROVIDE DEDICATED WIRE
1 I PLENUM
1 LOOP THAT SERVES ONLY EQUIPMENT ABOVE THE
I I I I I I _ ROOFLINE. PRIOR TO CONNECTION TO FIRE ALARM
- - - - - - - ----SYSTEM, PROVIDE SURGE SUPPRESSION.
� r
r i r 7. COORDINATE LOCATION AND CONNECTION OF FAN
SHUTDOWN RELAYS WITH INSTALLER.
C� C 1
150 Cd 5*1-1 � 150 Cd 5*1-2 1
99 dB I 99 dB 1
-I I P2P 1
I' 1
P6P, T6P
C 1
I o V5*7-2
WOMEN 75
L - I,
1
1
1
c 1
o t/5*7-1
L MEN � 75
S11
_ � 1
�- SLEEVE WITH 3/4" EMT (WITH BUSHINGS) THROUGH WALL ®St*1.4E-(D5 NAC s1*1.4E-(M42) 1
RPS AOM) FAN SHUTDOWN
I
HEAT DETECTORI WALL -MOUNTED I I 1
TO PROTECT NAC BOOSTER IN LIEU 1
OF SMOKE DETE�TOR
i 1
Antinom
Code Co
600 RinE
Lake Mai
Tel. 321
This docume
Tabaka, PE o
document ar
must be veril
Revisions
Col
MA
Project Ac
FIF
Project Ni
Date
Drawn By
Checked I
J
H G F E
D C
0
A
J I I H I G I F
E
0
C
B
A
ANTINOMY
Antinomy Consulting Engineers
Code Consulting - Fire Protection - Smoke Control
600 Rinehart Road Suite 2054
Lake Mary, FL 32746-4955
Tel. 321-888-2882 Online: antinomy.com
Prepared For:
it L�
ARM
EC #13001688
��Illlllllf////
E IV
No 73972
i� STATE OF
1111111111 10/08/21
This document has been digitally signed and sealed by Gregory A.
Tabaka, PE on the date adjacent to the seal. Printed copies of this
document are not considered signed and sealed and the signature
must be verified on any electronic copies.
Revisions
No. Description Date
0 PERMIT SET 09/07/21
1 NEW BOOTH, RPS6 REALLOC. 10/08/21
COMPLETE ALARM INC.
MAVERICK BOATS, INC.
Project Address
4551 ST. LUCIE BLVD
FT. PIERCE, FL 34946
FIRE ALARM PARTIAL
PLAN - ZONE 4
Project Number AC E0146
Date _ 10/08/21
Drawn By G.TABAKA
Checked By G.TABAKA
FA-1 10 - 4EV ,,
Scale (LION)
1 /8" = 1'-0"
8
7
6
F
5
4
3
4
J
I I I H
29 30
J I
G
F
E
IC
C
i31 32 �33 34 5
PROVIDE FMC TO EACH TAMPER SWITCH AND
FLOW SWITCH. CONNECT TAMPERS IN
PARALLEL AND CONNECT FLOW SWITCHES IN
PARALLEL SO THAT ANY ON OPERATING
WILL RESULT IN A SUPERVISORY OR ALARM
SIGNAL RESPECTIVELY.
LIO
M81)
TS TS TS -- TS _TS hAIM) ___SPKR FLOWS 5_@
WF WF ;WF]—
F�J2 SPKR TAMPERS 5 _A
1 i4EE r
1*1j 1E-(M52) I 1*1.4E-(M4� — I UZJ
RELOCATE BELL AOM FAN SHUTDOWN AOM FAN SH TDOWN 2 2
1 * 1.4E-(M46)
A _ FIRE WATER FLOW BELL
0 _.S-1111111 - --
WP
V2*A-1
H I G I F I E I D I C I
B A
TYPICAL NOTES:
1. CEILING MOUNTED HORN/STROBES:
A. SHALL BE EQUIPPED WITH MINIMUM 4"x4"x
2-1/8" BACKBOXES SUSPENDED FROM
STRUCTURAL STEEL ON NUMBERED GRID
LINES.
B. BACKBOXES SHALL BE INSTALLED LEVEL,
OPEN FACE DOWNWARDS AT AN ELEVATION
OF NO HIGHER THAN 29'-10" ABOVE THE FLOOR
NEAR THE F-GRID LINE AND 25' NEAR THE B-
GRID LINE.
C. ALL BACKBOXES SHALL HAVE A FACTORY -
MADE 1/4" HOLE AT THE TRUE CENTER OF THE
BOX.
D. ATTACH TO STRUCTURE USING A LISTED
SCREW -TYPE BEAM CLAMP (EQUAL TO CADDY
#4QTIBC) TO SUPPORT 1/4" THREADED ROD.
SUSPEND BACKBOX FROM THREADED ROD
USING SECURE ATTACHMENT, SUCH AS
DOUBLE OR JAM -NUTS.
E. ALL BOXES ON AN EAST -WEST LINE SHALL BE
AT EQUAL ELEVATION. DO NOT DEVIATE FROM
THE ALIGNMENT SHOWN.
— F:- INSTALL WIHEELOCK'UNIVERSAL MOUNTING
BASE' AT EACH.
G. PROVIDE BUSHING OR CLAMP WHERE WIRE
ENTERS OR EXITS BOX.
H. PROVIDE ADDITIONAL SUPPORT WHERE
REQUIRED DY CODE OR AHJ.
2. NAC SUPPLY KRING SHALL BE ROUTED ALONG
TRANSVERSE PURLINS AND SUPPORTED WITH
WIRE J-HOOKSS ;EQUAL TO EATON BCH12-F3 OR -F4
DEPENDING UPON STEEL FLANGE TYPE). PROVIDE
SUPPPORT AT >PACING NO GREATER THAN 54" ON
CENTER BETWEEN HOOKS.
3. FOR WIRES TO 3E SUPPORTED TRAVELING
PARALLEL WITH NUMBERED STEEL, PROVIDE
EATON BCH21-F3 OR -F4 (OR EQUAL) J-HOOKS ON
SAME SPACING AS ABOVE.
4, WHERE LOCATED WITHIN 10 FT OF THE FINISHED
FLOOR, ALL WARES SHALL BE ENCLOSED IN EMT
(3/4" MINIMUM). WHERE WIRES ENTER OR EXIT
THIS EMT, PROVIDE LISTED BUSHING,
5. ALL WIRES SERVING, ENTERING OR LOCATED
WITHIN THE BOOTHS SHALL BE IN THREADED
MINIMUM 3/4" IMC OR RMC.
6. ROOFTOP EQUIPMENT: PROVIDE DEDICATED WIRE
LOOP THAT SERVES ONLY EQUIPMENT ABOVE THE
ROOFLINE. PRIOR TO CONNECTION TO FIRE ALARM
— ---SYSTEM, PROVIDE SURGE SUPPRESSION.
7. COORDINATE LOCATION AND CONNECTION OF FAN
SHUTDOWN RELAYS WITH INSTALLER.
Antinomy Consulting Engineers
Code Consulting - fire Protection • Smoke Control
600 Rinehart Road Suite 2054
Lake Mary, FL 32746-4955
Tel. 321-888-2882 Online: antinomy.com
Prepared For:
s
V
I:L � A
EC #13001688
%itttiit����e
v
�; • No 73972
i� STATE OF e e o
i F
0 R 1 Doi •• ��
°1 111 a iit 0 10/08/21
This document has been digltally signed and sealed by Gregory A.
Tabaka, PE on the date adjacent to the seal. Printed copies of this
document are not considered signed and sealed and the signature
must be verified on any electronic copies.
Revisions
No. Description Date
0 PERMIT SET 09/07/21
1 NEW BOOTH, RPS6 REALLOC. 10/08/21
COMPLETE ALARM INC.
MAVERICK BOATS, INC.
Project Address
4551 ST. LUCIE BLVD
FT. PIERCE, FL 34946
N
0
FIRE ALARM PARTIAL
--- PLAN — ZONE 5 w
0
Project Number ACE0146 z
Date 10/08/21
Drawn By G.TABAKA
Checked By G.TABAKA
LU
FA111111 10.
EV.1)
0
Scale (UON) 1/8" = 1'-0" r
B I A U_
3 1 I H G F E D C B A
8
7
4
3
2
1
1 2 3 4 5 6 7 TYPICAL NOTES:
1. CEILING MOUNTED HORN/STROBES:
r A. SHALL BE EQUIPPED WITH MINIMUM 4"x4"x
2-1/8" BACKBOXES SUSPENDED FROM
v 3/4" EMT TYP, PENETRATION: PROVIDE MIN �/4" EMT STUB S1*1.4-(M64) I P?P, P4P ' STRUCTURAL STEEL ON NUMBERED GRID
THROUGH WALL WITH BUSHINGS QN BOTH ENDS. AOM FAN %TDOWN LINES.
(RAU-SGI1, EF-SG1, EF-SG2) PLENUM P P'2xP4P B. BACKBOXES SHALL BE INSTALLED LEVEL,
OPEN FACE DOWNWARDS AT AN ELEVATION
S1*1,4W M2i
- OF NO HIGHER THAN 29'-10" ABOVE THE FLOOR
SIS
s1*1.4 (D4) i M r NEAR THE F-GRID LINE AND 25' NEAR THE B-
CONNECT TO EXISTIN 120 - 4 - _ - _ -
GRID LINE.
120 V CIRCUIT 1*1AW-(M44) C. ALL BACKBOXES SHALL HAVE A FACTORY-
NAC EXPANDER SUPERVISION ; MADE 1/4" HOLE AT THE TRUE CENTER OF THE
S1*1.4W-(M27) HEAT DETECTOR WALL -MOUNTED - NAC NA,C
}[�] TO PROTECT NAC BOOSTER IN LIEU BOX.
1 SK-PS10 S -5499 AOM RPS6 NAC TRIGGER 2 1 '
� I D. ATTACH TO STRUCTURE USING A LISTED
OF SMOKE DETECTOR,,,.---,, _ : RPS6 " RP4 0.
NA 4w- M4o FAa00 �. r SCREW -TYPE BEAM CLAMP (EQUAL TO CADDY
SUPERVISE RPS6 THROUGH RPS4 MONITOR MODULE �/ac.�h�f FAN (SH SHUTDOWN
O�.A ' #4QTIBC) TO SUPPORT 1/4"THREADED ROD.
"t THREADED ROD
SUSPEND BACKBOX FROM
WITHIN BOOTH � ' * - USING SECURE ATTACHMENT, SUCH AS
I I
DOUBLE OR JAM -NUTS,
E. ALL BOXES ON AN EAST -WEST LINE SHALL BE
AT EQUAL ELEVATION. DO NOT DEVIATE FROM
I I WITHIN BOOTH F ' I V4*2 1 ' THE ALIGNMENT SHOWN.
<OXP _ r F. INSTALL WHEELOCK'UNIVERSAL MOUNTING
-I BASE AT EACH.
{ 4 G. PROVIDE BUSHING OR CLAMP WHERE WIRE
I w I IENTERS OR EXITS BOX.
C C - C r H. PROVIDE ADDITIONAL SUPPORT WHERE
* REQUIRED BY CODE OR AHJ.
150 Cd 150 Cd 150 Cd
99 dg 1*1.4 (M36)., 99 dB 2. NAC SUPPLY WIRING SHALL BE ROUTED ALONG
- r ��,
- TRANSVERSE PURLINS AND SUPPORTED WITH
I I - r
0 FAN bHUtDOWN
WIRE J-HOOKS (EQUAL TO EATON BCH12-F3 OR -F4
<Ol DEPENDING UPON STEEL FLANGE TYPE). PROVIDE
I SUPPPORT AT SPACING NO GREATER THAN 54" ON
I�� G * CENTER BETWEEN HOOKS.
WITHIN BOOTH ,oN V4* 4-1 S1 1.5R 4(D1b)
I P,150 RAU-G2 SUPPLY DUCT (ROOF)
(NEW BOOTH BELOW, P4P WP r 3. FOR WIRES TO BE SUPPORTED TRAVELING
NOT SHOWN)
PARALLEL WITH NUMBERED STEEL, PROVIDE
WITHIN BOOTH = F V4*3-1 — — _ =_ _ _ —EATON BCH21-F3 OR -F4 (OR EQUAL) J-HOOKS ON
O T8P I SAME SPACING AS ABOVE.
I C
150 Cd
99 dB
I
��S1*1.2-(M11)
fU
1-1 ' 2-(M34)
AOM ESIN PUMP TANK SHUTDOWN
1 *1.2-(M35)
AOM RESIN PUMP TANK SHUTDOWN
i I
I k
4. WHERE LOCATED WITHIN 10 FT OF THE FINISHED
I I P4P, P6P 3/4" IMC UNTIL ABOVE BOOTH, FLOOR, ALL WIRES SHALL BE ENCLOSED IN EMT
THEN 3/4" EMT OR FREE WIRE I (3/4" MINIMUM). WHERE WIRES ENTER OR EXIT
P4P, P6P, T8P �� THIS EMT, PROVIDE LISTED BUSHING.
— — . -- —
— — —
._�-, - �_. 5—.ALL WIRES SERVING ENTERING OR LOCATED
_,77WITHIN THE BOOTHS SHALL BE IN THREADED
MINIMUM 3/4" IMC OR RMC.
6. ROOFTOP EQUIPMENT: PROVIDE DEDICATED WIRE
I I I I LOOP THAT SERVES ONLY EQUIPMENT ABOVE THE
r ROOFLINE. PRIOR TO CONNECTION TO FIRE ALARM
SYSTEM, PROVIDE SURGE SUPPRESSION.
- 7. COORDINATE LOCATION AND CONNECTION OF FAN
SHUTDOWN RELAYS WITH INSTALLER.
r
,I, I C I _ i c_
I in*n A
1
ANTINOMY
Antinomy Consulting Engineers
Code Consulting - Fire Protection - Smoke Control
600 Rinehart Road Suite 2054
Lake Mary, FL 32746-4955
Tel, 321-888-2882 Online: antinomy.com
�n
EC #13001688
No 73972
� STATE OF
I11 1 S ,,O' R
�,0 11 111 10/08/21
This document has been digitally signed and sealed by Gregory A.
Tabaka, PE on the date adjacent to the seal. Printed copies of this
document are not considered signed and sealed and the signature
must be verified on any electronic copies.
Revisions
No. Description Date
0 PERMIT SET 09/07/21
1 NEW BOOTH, RPS6 REALLOC. 10/08/21
COMPLETE ALARM INC.
MAVERICK BOATS, INC.
Project Address
4551 ST. LUCIE BLVD
FT. PIERCE, FL 34946
FIRE ALARM PARTIAL
PLAN - ZONE 6
Project Number ACE0146
Date 10/08/21
Drawn By G.TABAKA
Checked By G.TABAKA
110-
FA-
EV.1)
Scale (UON) 1/8" = V-0"
i
I I H
G I F I E I D C B
A "
J I H G F E
0
C
B
A
Antinomy Consulting Engineers
Code Consulting • fire Protection - Smoke Control
600 Rinehart Road Suite 2054
Lake Mary, FL 32746-4955
Tel. 321-888-2882 Online: antinomy.com
Prepared For:
. l 11
EC #13001688
No 73972
� STATE OF � ��;
. A'
/IFS 10
O 111111 , % 10/08/21
This document has been digitally signed and sealed by Gregory A.
Tabaka, PE on the date adjacent to the seal. Printed copies of this
document are not considered signed and sealed and the signature
must be verified on any electronic copies.
Revisions
No. Description Date
0 PERMIT SET 09/07/21
COMPLETE ALARM INC.
MAVERICK BOATS, INC.
Project Address
4551 ST. LUCIE BLVD
FT. PIERCE, FL 34946
FIRE ALARM PARTIAL
PLAN — ZONE 7
Project Number ACE0146
— _-
Date 10/08/21
Drawn By G.TABAKA
Checked By G.TABAKA
FA-1 10.7
(REV. 0)
Scale (IJON) 1/8" = 1'-0"
N
ti
O
O
0
cc
r-
W
z
O
a.
z
Q
J
Q
a.
J
Q
W
LL
0
Q
E
1' 1.3-(M 12)
FAN SHUTDOWN
I I I JAN. CORR
I - 101B
WOMEN
103 - V2*1-2 15 ;®;--� 102
V2*1-4 o C
I I I I WP
I 135 :.w . I f WP WOMEN SHOWER
2 V2*1-1 ® 15
I I'
PANEL B� ` 30 L 102A 1
ELEC.
I I DISCONNECT BELL FROM FACP NAC #4 AND 104 'Lul = I `'`
CONNECT TO RIPS #2 A X POWER, RUN NEW WI, CORR
SYNC CIRCUIT FROM F CP NAC #4 AND
2* 2 WOMEN SHOWER 101A
CONFIGURE FOR WHEELOCK SYNC SIGNAL. -- - ! 30 F 1-06A C
MEN V2*2-3 15 15
Q
106
DATA -
lso 6 Q1 V2 2-1
Hr\ 105 1 15
- -- - — — L
u
C
CORR
100
V2*1-5
V2* 1-6
C
15
V2*2-4
S1"1.1-(D2)
— RPS2 `
RPS1 WP 135
I , V2*2-5
I L___1 F ACU
H
G
B
A
TYPIC aL NOTES:
1. CEILING MOUNTED HORN/STROBES:
A. SHALL BE EQUIPPED WITH MINIMUM 4"x4"x
2-1/8" BACKBOXES SUSPENDED FROM
STRUCTURAL STEEL ON NUMBERED GRID
LINES.
B. BACKBOXES SHALL BE INSTALLED LEVEL,
OPEN FACE DOWNWARDS AT AN ELEVATION
OF NO HIGHER THAN 29'-10" ABOVE THE FLOOR
NEAR THE F-GRID LINE AND 25' NEAR THE B-
GRID LINE.
C. ALL BACKBOXES SHALL HAVE A FACTORY -
MADE 1/4" 'HOLE AT THE TRUE CENTER OF THE
BOX.
D. ATTACH TO, STRUCTURE USING A LISTED
SCREW -TYPE BEAM CLAMP (EQUAL TO CADDY
#4QTIBC) TO SUPPORT 1/4" THREADED ROD.
SUSPEND BACKBOX FROM THREADED ROD
USING SECURE ATTACHMENT, SUCH AS
DOUBLE OR JAM -NUTS.
E. ALL BOXES ON AN EAST -WEST LINE SHALL BE
AT EQUAL ELEVATION. DO NOT DEVIATE FROM
THE ALIGNMENT SHOWN.
F. INSTALL WHEELOCK'UNIVERSAL MOUNTING
BASE' AT EACH.
G. PROVIDE BUSHING OR CLAMP WHERE WIRE
ENTERS 0'R EXITE BOX.
H. PROVIDE ADDITIONAL SUPPORT WHERE
REQUIRED BY CODE OR AHJ.
2. NAC SUPPLY WIRING SHALL BE ROUTED ALONG
TRANSVERSE PURLINS AND SUPPORTED WITH
WIRE J-HOOKS" (EQUAL TO EATON BCH12-F3 OR -F4
DEPENDING UPON STEEL FLANGE TYPE). PROVIDE
SUPPPORT AT SPACING NO GREATER THAN 54" ON
CENTER BETWEEN HOOKS.
3. FOR WIRES TO BE SUPPORTED TRAVELING
PARALLEL WI-'-H NUMBERED STEEL, PROVIDE
EATON BCH21-F3 OR -F4 (OR EQUAL) J-HOOKS ON
SAME SPACING AS ABOVE.
4. WHERE LOCATED WITHIN 10 FT OF THE FINISHED
FLOOR, ALL WIRES SHALL BE ENCLOSED IN EMT
(3/4" MINIMUM). WHERE WIRES ENTER OR EXIT
THIS EMT, PROVIDE LISTED BUSHING.
---5ALL WIRES SERVING, ENTERING OR LOCATED
WITHIN THE BOOTHS SHALL BE IN THREADED
MINIMUM 3/4" IMC OR RMC,
6. ROOFTOP EQUIPMENT: PROVIDE DEDICATED WIRE
LOOP THAT SERVES ONLY EQUIPMENT ABOVE THE
ROOFLINE. PRIOR TO CONNECTION TO FIRE ALARM
SYSTEM, PROVIDE SURGE SUPPRESSION,
7, COORDINATE LOCATION AND CONNECTION OF FAN
SHUTDOWN RELAYS WITH INSTALLER.
ANTINOMY
Antinomy Consulting Engineers
Code Consulting • Fire Protection - Smoke Control
600 Rinehart Road Suite 2054
Lake Mary, FL 32746-4955
Tel. 321-888-2882 Online: antinomy.com
Prepared For:
RM
EC #13001688
No 7397244,
f i
..0., STATE OF
P�
ONA
I I t l 10% 10/08/21
This document has been digitally signed and sealed by Gregory A.
Tabaka, PE on the date adjacent to the seal. Printed copies of this
document are not considered signed and sealed and the signature
must be verified on any electronic copies.
Revisions
No. Description Date
0 PERMIT SET 09/07/21
I -
COMPLETE ALARM INC.
MAVERICK BOATS, INC.
Project Address
4551 ST. LUCIE BLVD
FT. PIERCE, FL 34946
N
CD
FIRE ALARM PARTIAL
PLAN - ZONE 8 co
co
UJ
Project Number ACE0146
Date 10/08/21
J
Drawn By G.TABAKA
Checked By G.TABAKA
LLJ
FA 110
EV.0)
Scale (LION) 1/8" = 1'-0"
F
E
It,
C
I.
A
Q
8
7
C
5
4
Cl
0
J I H G F E D C B
A
22 23 24 '25 i26 27 28
TYPICAL NOTES: A N T I N O
1 1
1. CEILING MOUNTED HORN/STROBES:
A. SHALL BE EQUIPPED WITH MINIMUM 4"x4"x
PLACE EOLR IN J-BOX ON TERMI AL � � 2-1/8" BACKBOXES SUSPENDED FROM
STRIP FOR FUTURE EXPANSION
STRUCTURAL STEEL ON NUMBERED GRID
1 0-
JAN LINES.
_ I [= B. BACKBOXES SHALL BE INSTALLED LEVEL,
S1*1.4E-(M2�_ OPEN FACE DOWNWARDS AT AN ELEVATION
.ow- - � =w_ _1111111111110 OF NO HIGHER THAN 29'-10" ABOVE THE FLOOR
s1*1.4E4MI NEAR THE F-GRID LINE AND 25' NEAR THE B-
FA SHUTDOWN .�........�......�_
1 GRID LINE.
' 1 C SHALL HAVE A FACTORY -
MADE 1/4""BHOLE SAT THE TRUE CENTER OF THE
1 I I j 1 BOX.
1 D. ATTACH TO STRUCTURE USING A LISTED
_ SCREW -TYPE BEAM CLAMP (EQUAL TO CADDY Antinomy Consulting Engineers
Code Consulting •fire Protection •Smoke Control
#4QTIBC) TO SUPPORT 1/4" THREADED ROD. 600 Rinehart Road Suite 2054
1 I I SUSPEND BACKBOX FROM THREADED ROD Lake Mary, FL 32746-4955
r USING SECURE ATTACHMENT, SUCH AS Tel. 321-888-2882 online: antinomy.com
I DOUBLE OR JAM -NUTS.
1 E. ALL BOXES ON AN EAST -WEST LINE SHALL BE Prepared For:
I I I AT EQUAL ELEVATION. DO NOT DEVIATE FROM 4P L,��
THE ALIGNMENT SHOWN.
B� — ' — — — — — — — __ _ _ _ _ _ _ _ _ I F. INSTALL WHEELOCK'UNIVERSAL MOUNTING
fi BASE AT EACH.
1 - G. PROVIDE BUSHING OR CLAMP WHERE WIRE
ENTERS OR EXITS BOX.
f C C C H. PROVIDE ADDITIONAL SUPPORT WHERE �-p
* n REQUIRED BY CODE OR AHJ.
150 Cd - C 150 Cd 150Cd - _ _ _ 151_
1 99 dB j 99 dB 1 99 dB I 99 dB 2. NAC SUPPLY WIRING SHALL BE ROUTED ALONG
TRANSVERSE PURLINS AND SUPPORTED WITH EC #13001688
WIRE J-HOOKS (EQUAL TO EATON BCH12-F3 OR -F4
1 DEPENDING UPON STEEL FLANGE TYPE). PROVIDE
I I I
1 SUPPPORT AT SPACING NO GREATER THAN 54" ON
1� 1 CENTER BETWEEN HOOKS.
3. FOR WIRES TO BE SUPPORTED TRAVELING
1 ( PARALLEL WITH NUMBERED STEEL, PROVIDE
— �- - — --� — - — — — I— — I — _--EATON BCH21-F3 OR -F4 (OR EQUAL) J-HOOKS ON
� I
SAME SPACING AS ABOVE.
4. WHERE LOCATED WITHIN 10 FT OF THE FINISHED
1 I j 1 FLOOR, ALL WIRES SHALL BE ENCLOSED IN EMT
(3/4 MINIMUM). WHERE WIRES ENTER OR EXIT
1 THIS EMT, PROVIDE LISTED BUSHING.
WIRES SERVING ENTERING OR LOCATED
1 WITHIN THE BOOTHS SHALL BE IN THREADEDI
1 MINIMUM 3/4" IMC OR RMC. ��� c��. "�'EIV e'�.�
No 73972
I 1 1 6. ROOFTOP EQUIPMENT: PROVIDE DEDICATED WIRE '-7
I r LOOP THAT SERVES ONLY EQUIPMENT ABOVE THE
ROOFLINE. PRIOR TO CONNECTION TO FIRE ALARM
SYSTEM PROVIDE SURGE SUPPRESSION. E'� - - -j- - - - - - - - - - - - - - - - - - - - - -
' STATE OF
I j 1 7. COORDINATE LOCATION AND CONNECTION OF FAN ,�0NA....
SHUTDOWN RELAYS WITH INSTALLER. ���+�� i I%�` 10/08/21
1 This document has been digitally signed and sealed by Gregory A.
' Tabaka, PE on the date adjacent to the seal. Printed copies of this
' document are not considered signed and sealed and the signature
a I I i 1 must be verified on any electronic copies.
1 - Revisions
i I 1
150 Cd 150 Cd
99 dB 99dB
BREAK
107
J I H
135 V2*2-8
� c
V2*2-7
75 1
S1*1.1-(M2)
C
G
F
E
D I C i B
COMPLETE ALARM INC.
MAVERICK BOATS, INC.
Project Address
4551 ST. LUCIE BLVD
FT. PIERCE, FL 34946
N
FIRE ALARM PARTIAL
O
c
CD
C)
PLAN - ZONE 9
CM
Project Number ACE0146
0
Date 10/08/21
Drawn By G.TABAKA
Checked By G.TABAKA
a
FA 11 0U_
J
EV.0)
U_
Scale (uoN) j/$" — 1'-0"
A
LL
8
7
6
CEJ
1
4
F
2
1
J I I H G
r2 (1 30 31
F E D I C
32 ( 33), 34 3'
� 1
J I IH IG I F I E I D I C
B A
TYPICAL NOTES:
1. CEILING MOUNTED HORN/STROBES:
A. SHALL BE EQUIPPED WITH MINIMUM 4"x4"x
2-1/8" BACKBOXES SUSPENDED FROM
STRUCTU';ZAL STEEL ON NUMBERED GRID
LINES.
B. BACKBOXES SHALL BE INSTALLED LEVEL,
OPEN FACIE DOWNWARDS AT AN ELEVATION
— - OF NO HIGHER THAN 29'-10" ABOVE THE FLOOR
NEAR THE F-GRID LANE AND 25' NEAR THE B-
GRID LINE.
C. ALL BACKI3OXES SHALL HAVE A FACTORY -
MADE 1/4" HOLE AT THE TRUE CENTER OF THE
BOX.
D. ATTACH TO STRUCTURE USING A LISTED
SCREW -TYPE BEAM CLAMP (EQUAL TO CADDY
#4QTIBC) TO SUPPORT 1/4" THREADED ROD,
SUSPEND IBACKBOX FROM THREADED ROD
USING SEC/URE ATTACHMENT, SUCH AS
DOUBLE OR JAM -NUTS.
E. ALL BOXES ON AN EAST -WEST LINE SHALL BE
AT EQUAL ELEVATION. DO NOT DEVIATE FROM
THE ALIGNMENT SHOWN.
F. INSTALL VIHEELOCK'UNIVERSAL MOUNTING
BASE' AT EACH.
G. PROVIDE.I3USHING OR CLAMP WHERE WIRE
ENTERS OR EXITS BOX.
H. PROVIDE ADDITIONAL SUPPORT WHERE
REQUIRED BY CODE OR AHJ.
2. NAC SUPPLY WIRING SHALL BE ROUTED ALONG
TRANSVERSE PURLINS AND SUPPORTED WITH
WIRE J-HOOKS (EQUAL TO EATON BCH12-F3 OR -F4
DEPENDING UPON STEEL FLANGE TYPE). PROVIDE
SUPPPORT AT SPACING NO GREATER THAN 54" ON
CENTER BETWEEN HOOKS.
3. FOR WIRES TD BE SUPPORTED TRAVELING
PARALLEL WITH NUMBERED STEEL, PROVIDE
-_-__-EATON BCH2'1-F3 OR -F4 (OR EQUAL) J-HOOKS ON
SAME SPACING AS ABOVE.
4. WHERE LOCATED WITHIN 10 FT OF THE FINISHED
FLOOR, ALL WIRES SHALL BE ENCLOSED IN EMT
(3/4" MINIMUM). WHERE WIRES ENTER OR EXIT
THIS EMT, PROVIDE LISTED BUSHING.
5. ALL WIRES SERVING, ENTERING OR LOCATED
WITHIN THE BOOTHS SHALL BE IN THREADED
MINIMUM 3/4" IMC OR RMC.
6. ROOFTOP EQUIPMENT: PROVIDE DEDICATED WIRE
LOOP THAT SERVES ONLY EQUIPMENT ABOVE THE
ROOFLINE. PRIOR TO CONNECTION TO FIRE ALARM
SYSTEM, PROVIDE: SURGE SUPPRESSION.
7. COORDINATE LOCATION AND CONNECTION OF FAN
SHUTDOWN RELAYS WITH INSTALLER.
1
Antinomy Consulting Engineers
Code Consulting • Fire Protection • Smoke Control
600 Rinehart Road Suite 2054
Lake Mary, FL 32746-4955
Tel. 321-888-2882 Online: antinomy.com
Prepared For:
k,
EC #13001688
`���titti������
G,\Pc o iE �N
No 73972
STATE OF
R 0; % \ \
�NA
� o i i i r 1 o/os/21
This document has been digitally signed and sealed by Gregory A.
Tabaka, PE on the date adjacent to the seal. Printed copies of this
document are not considered signed and sealed and the signature
must be verified on any electronic copies.
Revisions
No. Description Date
0 PERMIT SET 09/07/21
i
COMPLETE ALARM INC.
MAVERICK BOATS, INC.
Project Address
4551 ST. LUCIE BLVD
FT. PIERCE, FL 34946
_
N
ti
O
O
FIRE ALARM PARTIAL co
Ir
PLAN — ZONE 10 w
z
0
N
Project Number ACE0146 z
_
— -
Date 10/08/21
d
Drawn By G.TABAKA
Checked By G.TABAKA
J
LU
FAM1 10. 1
v.0) o
Scale (LION) 1/8" = V-0"
1
J I I H I G I F
E I D I C B I A
LEGEND:
8 X - SYSTEM INPUT CAUSES SYSTEM OUTPUT
FUNCTION
• W - SAME AS X, EXCEPT ACTIVATION IS VIA
FLOW SWITCH DRY CONTACTS (NOT
PROGRAMMING)
• 0 - OPTIONAL RESPONSE: SYSTEM INPUT MAY
CAUSE SYSTEM OUTPUT FUNCTION
• - - SEE RESPONSES BELOW FOR THIS GROUP.
### ALARM INPUTS
100 SPOT -STYLE SMOKE DETECTOR
7 110 SPOT -STYLE HEAT DETECTOR
120 WATER FLOW SWITCH
130 MANUAL PULL STATION
140 (RESERVED)
150 (RESERVED)
160 (RESERVED)
SUPERVISORY INPUTS
400 SPRINKLER TAMPER SWITCH
410 1 SPRINKLER TAMPER SWITCH - AT BACKFLOW
420 DUCT SMOKE DETECTOR
430 (RESERVED)
440 (RESERVED)
6 440 (RESERVED)
440 (RESERVED)
TROUBLE INPUTS
501 GROUND FAULT
502 SHORT CIRCUIT
503 OPEN CIRCUIT
504 BATTERY FAIL
505 A/C POWER FAIL
506 NAC EXPANDER FAIL
507 (RESERVED)
508 MISC. GENERAL SYSTEM TROUBLE
509 (RESERVED)
5 510 (RESERVED)
4
3
2
1
ANNUNCIATION INOTIFICATION
may.
v�4y o I
C_
RV
FIRE SAFETY FUNCTIONS
ATA2:A3
B1: B2: B3
Cti C2: C3
D
E
F
G
H
J
K
L
M
N
X:
X:
X
X
Xi
X
X
X
X
X
X
X
X
X
X
IX
X:
: :
1
X:
,
:
X
'X
X
X
X
X
X
X
X
X
X
X
X
'
X
I
A14 A3
131! B2 B31
C1i C2: C31
D
E
F
G
H
J
_K1
L
M
N
FIRE ALARM SEQUENCE OF OPERATIONS
NOT TO SCALE
I
SLC DEVICE SCHEDULE - SK PROTOCOL (EXISTING DEVICES)
SK. l - AUX POWER
ADDRESS - MODEL PROGRAM LABEL ASSOCIATED FUNCTIONS SOURCE
1
-
S1*1-0 SK-ISO-6 (NO LABEL OR ADDRESS)
S1*1.1-D1
SK-PHOTO-W
(EXISTING LABEL)
S1*1.1-D2
SK-PHOTO-W
(EXISTING LABEL)
S1*1,1-M1
SK-PULL-DA
(EXISTING LABEL)
S1*1.1-M2
SK-PULL-DA
(EXISTING LABEL)
1.2
S1*1.2-M3
SK-PULL-DA
(EXISTING LABEL)
S1*1.2-M5
SK-PULL-DA
(EXISTING LABEL)
S1*1,2-M6
SK-PULL-DA
(EXISTING LABEL)
S1*1.2-M7
SK-RELAY
(EXISTING LABEL) FAN SHUTDOWN
S1*1,2-M8
SK-PULL-DA
(EXISTING LABEL)
S1*1,2-M9
S1*1.2-M10
SK-RELAY
SK-RELAY
(EXISTING LABEL)
(EXISTING LABEL)
FAN SHUTDOWN
FAN SHUTDOWN
S1*1.2-M11
SK-PULL-DA
(EXISTING LABEL)
S1*1.2-M34
SK-RELAY
(EXISTING LABEL)
RESIN PUMP TANK SHUTDOWN
S1*1.2435
SK-RELAY
(EXISTING LABEL)
RESIN PUMP TANK SHUTDOWN
1.3
S1*1.3-M12
SK-RELAY
(EXISTING LABEL)
FAN SHUTDOWN
S1*1.3-M14
SK-RELAY
(EXISTING LABEL)
FAN SHUTDOWN
S1*1.3-M15
SK-PULL-DA
(EXISTING LABEL)
f
S1*1.3-M16
SK-RELAY
(EXISTING LABEL)
FAN SHUTDOWN
S1*1,3417
SK-RELAY
(EXISTING LABEL)
FAN SHUTDOWN
S1*1.3418
SK-PULL-DA
(EXISTING LABEL)-
S1*1.3-M19
SK-RELAY
(EXISTING LABEL)
FAN SHUTDOWN
S1*1,3-M20
SK-RELAY
(EXISTING LABEL)
FAN SHUTDOWN
S1*1.3421
SK-PULL-DA
(EXISTING LABEL)
S1*1.3-M22 I
SK-PULL-DA
(EXISTING LABEL)
SLC DEVICE SCHEDULE - SK PROTOCOL (NEW DEVICES)
SK AUX POWER
ADDRESS MODEL PROGRAM LABEL ASSOCIATED FUNCTIONS SOURCE
1.3
S1*1.3-M53
SK-PULL-DA
P/S @ S. WAREHOUSE WEST DOOR
S1*1.3-M54
SK-PULL-DA
P/S @ S. WAREHOUSE EAST DOOR
1.4
S1*1.4-M60
SK-MONITOR
TIS @ EXPANSION NW GEL BOOTH
GEL BOOTH SPKR TAMPER
S1*1.4-M64 SK-RELAY FAN SHUTDOWN, EXPANSION SW FAN SHUTDOWN
GEL BOOTHS
1.4E
-I*IAE-D5 SK-HEAT"W HID-@iRPS3
S1*1.4E-M$0,
M81
SK-MONITOR-2 )
(MATCH FUNCTIONS
;SPKR FLOWS 5
I @ EXPANSION �
SPKR TAMPERS 5 @ EXPANSION
1 AW
S1*1.4W-D4
SK-HEAT-W
H/D @ RPS4, RPS6
S1*1.4W-M40
SK-RELAY
NAC TRIGGER @ RPS6
FAN SHUTDOWN
S1*1.4W-M45
SK-CONTROL
NAC TRIGGER @ RPS6
RPS6 NAC TRIGGER
N6*1-1
S1*1.4W-M63
SK-PULL-DA
P/S @ EXPANSION, GRID A-1
S1*1.4W-M65
SK-RELAY
FAN SHUTDOWN, RAU-SP1
FAN SHUTDOWN
S1*1.4W-M66
SK-RELAY
FAN SHUTDOWN, EF-SP1
FAN SHUTDOWN
S1*1.4W-M67 SK-RELAY FAN SHUTDOWN, EF-SP2 FAN SHUTDOWN
1.5
S1*1.5-D3
SK-PHOTO-W
SID @ EXPANSION ELEC RM.
S1*1.5-M69
SK-MONITOR
NAC TROUBLE @ RPS5
NAC TROUBLE MONITOR
S1*1.5-M99
SK-MONITOR
AIM FOR P/S @ EXPANSION
PULL STATIONS AT EXPANSION
1.5R
S1*1.5R-D6
SK PHOTO-R-W
RAU-SP1 SUPPLY DUCT (ROOF)
S1*1.5R-D7
SK-PHOTO-R-W
RAU-SG1 SUPPLY DUCT (ROOF)
S1*1.5R-D8
SK-PHOTO-R-W
RAU-S1 SUPPLY DUCT (ROOF)
S1*1.5R-D9
S1*15R-D1-0
SK-PHOTO-R-W
RAU-BG1 SUPPLY DUCT (ROOF)
RAU-G2 SUPPLY DUCT (ROOF)
SK-PHOTO R-W
1.5W
S1*1.5W-M55
SK-PULL-DA
P/S @ EXPANSION, GRID G-17
S1*1.5W-M56
SK-PULL-DA
P/S @ EXPANSION, GRID F-13
S1*1.5W-M57
SK-RELAY
FAN SHUTDOWN RAU-S1
FAN SHUTDOWN
S1*1.5W-M58
SK-PULL-DA
P/S @ EXPANSION, GRID F-17
S1*1.5W-M59
SK-PULL-DA
P/S @ EXPANSION, GRID F-6
S1*1.5W-M61
SK-RELAY
FAN SHUTDOWN, EXPANSION NW
GEL BOOTH
P/S @ EXPANSION, GRID F 1
_
FAN SHUTDOWN
S1*1.5W-M62
SK-PULL-DA
NOTE: REVISE ADDRESSES AND LABELS AS NEEDED. PROVIDE CORRECT INFORMATION ON RECORD DOCUMENTS.
SLC DEVICE SCHEDULE - SK PROTOCOL (EXISTING DEVICES)
SK AUX POWER
ADDRESS MODEL PROGRAM LABEL ASSOCIATED FUNCTIONS SOURCE
1.4 -
S1*1.4-M23
SK-PULL-DA
(EXISTING LABEL)
S1*1.4-M36
SK-RELAY
(EXISTING LABEL) _
FAN SHUTDOWN
1.4E
S1*l.4E-M4 SK-RELAY ;(EXISTING LABEL) FAN SHUTDOWN
S1*14E-M13 'SK-RELAY
(EXISTING LABEL)
FAN SHUTDOWN
S1*1AE-M28
SK-PULL-DA
(EXISTING LABEL)
S1*1.4E-M29
SK-PULL-DA
(EXISTING LABEL)
S1*1AE-M30
SK-PULL-DA
(EXISTING LABEL)
S1*1AE-M31
SK-PULL-DA
(EXISTING LABEL)
S1*1.4E-M32
SK-MONITOR
! (EXISTING LABEL)
SPKR MAIN ## FLOW
S1*1.4E-M33
SK-MONITOR
(EXISTING LABEL)
SPKR MAIN ## TAMPER_
S1*1.4E-M41
SK-MONITOR
(EXISTING LABEL)
NAC EXPANDER SUPERVISION
S1*1.4E-M42
SK-RELAY
,(EXISTING LABEL)
FAN SHUTDOWN
S1*1.4E-M43
SK-RELAY
(EXISTING LABEL)
FAN SHUTDOWN
S1*1AE-M46
SK-RELAY
(EXISTING LABEL)
_
FIRE WATER FLOW BELL
S1*1.4E-M47
SK-MONITOR
(EXISTING LABEL)
TAMPERS AT BACKFLOW
S1*1.4E-M48
SK-MONITOR
(EXISTING LABEL)
SPKR MAIN ## FLOW
S1*1.4E-M49
SK-MONITOR
_
(EXISTING LABEL)
SPKR MAIN ## TAMPER
S1*1.4E-M50
SK-MONITOR
(EXISTING LABEL)
SPKR MAIN ## FLOW
S1*1.4E-M51 SK-MONITOR (EXISTING LABEL) SPKR MAIN ## TAMPER
S1*1.4E-M5'2 LSK-RELAY (EXISTING LABEL) FAN SHUTDOWN
---- ------
II AW
S1*1.4W-M24
SK-PULL-DA
(EXISTING LABEL) -
S1*1.4W-M25
SK-PULL-DA
(EXISTING LABEL)
S1*1.4W-M26
SK-PULL-DA
(EXISTING LABEL)
_
S1*1.4W-M27
SK-PULL-DA
(EXISTING LABEL)
FAN SHUTDOWN
S1*1.4W-M37
SK-RELAY
(EXISTING LABEL)
S1*1.4W-M38
SK-RELAY
(EXISTING LABEL)
L,AKL)
FAN SHUTDOWN
S1*1AW-M39
SK-RELAY -,-(EXISTING-
FAN SHUTDOWN
S1*1.4W-M44
SK-MONITOR
RPS4/RPS6 TROUBLE
NAC EXPANDER SUPERVISION
ANTINOMY
Antinomy Consulting Engineers
Code Consulting - Fire Protection - Smoke Control
600 Rinehart Road Suite 2054
Lake Mary, FL 32746-4955
Tel. 321-888-2882 Online: antinomy.com
Prepared For:
6tll
L
A rr''
Rw
EC #13001688
`�111111rrrrrr�
Z IQ7e No 73972
0 :-7
STATE OF
i�.n • A, •• ��
�r 11 11111 `` 10/08/21
This document has been digitally signed and sealed by Gregory A.
Tabaka, PE on the date adjacent to the seal. Printed copies of this
document are not considered signed and sealed and the signature
must be verified on any electronic copies.
Revisions
No. Description Date
0 IPERMITSET 09/07/21
1 1 NEW BOOTH, RPS6 REALLOC. 10/08/21
COMPLETE ALARM INC.
MAVERICK BOATS, INC.
Project Address
4551 ST. LUCIE BLVD
FT. PIERCE, FL 34946
SEQUENCE OF
OPERATIONS AND
DEVICE LABELS
Project Number ACE0146
Date 10/08/21
Drawn By G.TABAKA
Checked By G.TABAKA
FA-_400 (REV. 1)
Scale (UON) 12, = 1'_0"
N
00
0
0
J I I I H
G
F
E
D
C
B
A
F_
J
I I H
G I
F
E I D I C B
ANTINOMY
8'
EOLR 0< 0<
V6*7-2 V6*7-1
EOLR 1771<1
V6*6-1
EOLR X
V6*5-1
7
EOLR X
V6*4-1
EOLR X
V6*3-1
EOLR RPS6
2
6
FA-700
5
4
3
2
S1 *1.4W-(M45)
V6*1-1 -
SS
0
EOLR
0<
0<
V5*7-2
V5*7-1
EOLR
°
V5*6-6
V5*6-5
V5*6-4
V5*6-3
V5*6-2
V5*6-1
EOLR
V5*5-6
V5*5-5
V5*5-4
V5*5-3
V5*5-2
V5*5-1
EOLR
V5*4-5
V5*44
V5*4-3
V5*4-2
V5*4-1
EOLR
V5*3-5
V5*34
V5*3-3
V5*3-2
V5*3-1
i
- It�IV
0`1
9<
9<l
9<
k"<I
V5*2-7
V5*2-6
V5*2-5
V5*24
V5*2-3
V5*2-2
V5*2-1
EOLR
V5*1-6
V5*1-5
V5*14
V5*1-3
V5*1-2
V5*1-1
(SPARE)
V4*4-1
0< EOLR °� EOLR
V4*3-1 V3*3-2 V3*3-1
0< EOLR EOLR o o
V4*2-1 V3*2-1 V2*2-8 V2*2-7 V2*2-6 V2*2-5
- X., EOLR 0< Z< EOLR
V4*1-1 V3*1-2 V3*1-1 I V2*1-6 V2*1-5
(SPARE)
t�PS3
V1*3-5
V1*3-4
V1*3-3
V1*3-2
V1*3-1
V1*2-6
V1*2-5
V1*24
V1*2-3
V1*2-2
V1*2-1
EOLR
o
V1*1-5
V1*1-4
V1*1-3
V1*1-2
V1*1-1
FIRE ALARM RISER D
NOT TO SCALE
IAGRAM - NAC
LJ SS AOM
V2*A-1 S 1 *1.4E-(M46)
(SPARE)
V2*34
V2*3-3
V2*3-2
V2*3-1
V2*2-4
V2*2-3
V2*2-2
V2*2-1
.
\®s
1
ads
1
V2*1-4
V2*1-3
V2*1-2
V2*1-1
EOLR —
EOLR
VO*3-5
VO*3-4
VO*3-3
VO*3-2
VO*3-1
EOLR
VO*2-6
VO*2-5
VO*24
VO*2-3
VO*2-2
VO'21
QQ
S<
011
911
VO*1-6 V0*1-5
VO*1-4
VO*1-3
VO*1-2
V0*1-1
ss
FA-500
J I I H I G ( F I E D C B
SS
(DISCONNECT BELL
CIRCUIT FROM FACP AND
RESUPPLY FROM RPS2
AUX POWER ALWAYS -ON
CIRCUIT. CONNECT NEW
CIRCUIT FROM FACP TO
RPS5 INPUT TRIGGER.)
A
Antinomy Consulting Engineers
Code Consulting • fire Protection - Smoke Control
600 Rinehart Road Suite 2054
Lake Mary, FL 32746-4955
Tel. 321-888-2882 Online: antinomy.com
Prepared For:
ygfi
r
EC #13001688
No 73972 •�/�- i
.7
"0 ;• STATE OFlV;:
"// // 11111 \\ 10/08/21
This document has been dighally signed and sealed by Gregory A.
Tabaka, PE on the date adjacent to the seal, Printed copies of this
document are not considered signed and sealed and the signature
must be verified on any electronic copies.
Revisions
No. Description Date
0 PERMIT SET 09/07/21
1 NEW BOOTH, RPS6 REALLOC. 10/08/21
COMPLETE ALARM INC.
MAVERICK BOATS, INC.
Project Address
4551 ST. LUCIE BLVD
FT. PIERCE, FL 34946
FIRE ALARM RISER
N
C
DIAGRAM - NAC
T
Cr
Q
Project Number ACE0146
z
Date 10/08/21
Drawn By G.TABAKA
Q
Checked By G.TABAKA
Lu
FA- 500
LU
J
w
(REV. 1)Cf'
Scale (LION)1" = 60'-011
a
_�J
J I I H G F E D I C I B I A
ANTINOMY
8
7
6
5
4
3
2
1 1 1 I
1 1 1 1
ss
S1*1.5R-0.2 S1*1.5R-1(D6) S1*1.51R-2(1]17) S1*1.5R-3(D8) S1*1,5R-4(D9)
AIM AIM O 1+ 9 AOM 9 � AIM AOM O o O 0 0
S1*1.5-(M99) S1*1.5-(M69) S1*1.5-(D3) SI*1.5W-(M55) S1*1.5W-(M56) S1*1,5W-(M57) S1*1.5W-(M58) S1*1.5W-(M59) SI*1.4-(M60) S1*1.5W-(M61) S1*1.5W-(M62)
IDC `
S1*1.5-M99(IDC#1)S1*1.5-M99(IDC#2) S1*1.5-M99(IDC#3) S1*1.5-M99(IDC#4) S1*1.5-M99(IDC#5) S1*1.5-M99(IDC#6) S1*1.5-M99(IDC#7)
AOM Z� AQM
S1 *1 AW-(M66) S1 *1,4W-(M45)
V6*1-1
AOM AOM
O Q
S1*1.4W-(M67) S1*l.4W-(M65) S1*1.4W-(D4) S1*1.4W-(M63)
- AQM AOM AQM AQM AIM
S1*1.4W-(M39) S1*1.4W-(M38) S1*1.4W-(M24) S1*1.4W-(M37) S1*1.4W-(M25) S1*1.4-(M36) S1*1.4W-(M26) S1*1.4W-(M44) S1*1.4W-(M27)
S1 *1.4E-(M52)
SI*1.4E-(M50) S1*1.4E-(M51)
®
AQM
O
AOM
O
i
AIM
O
AIM
O
M
�
AIM
O
S1*1.4E-(D5)
S1*1.4E-(M13?)
S1*1.4E-(M4)
SI*1.4E-(M48)
S1*1.4E-(M49)
V2*A-1
S1*1.4E-(N
M81)
O
O
O
SS
O
O
O
O
S1*1.4-(M23)
SI*1.4E-(M41)
S1*1.4E-(M42)
S1*1.4E-(M43)
S1*1.4E-(M28)
S1*1.4E-(M29)
S1*1.4E-(M30)
S1*1.4E-(M31)
S1*1.4E-(M46)
S1*1.4E-(M32)
S1*1.4E-(M33)
S1*1.4E-(M47)
2
S 1 *1.3-(M53)
S 1 *1.3-(M54)
- AOM
am
a
AQM
O
a
aO
S1*1.3-(MI2)
S1*1.3-(M14)
SI*1.3-(MI5)
S1*1.3-(M16)
S1*1.3-(M17)
S1*1.3-(M18)
S1*1.3-(M19)
S1*1.3-(M20)
S1*1.3-(M21)
S1*1.3-(M22)
aO
O
AOM
S1*1.2-(M3)
S1*1.2-(M5)
S1*1.2-(M6)
SI*1,2-(M7)
S1*1.2-(M8)
SI*1.2-(M9)
S1*1.2-(M10)
S1*1.2-(M11)
S1*1.2-(M34)
C1*1.2-(M35r
V
S1*1.1-(DI)
S1*1,1-(D2)
S1*1.1-(M1)
SI*1.1-(M2)
FIRE ALARM RISER DIAGRAM - SLC
NOT TO SCALE
J I I H G F I E D C B A
Antinomy Consulting Engineers
Code Consulting - fire Protection - Smoke Control
600 Rinehart Road Suite 2054
Lake Mary, FL 32746-4955
Tel. 321-888-2882 Online: antinomy.com
Prepared For:
tT
F
3
, N"N il"�.
EC #13001688
```111111111////
C>%� \ ENS .,�•6 i��'
No 73972
' `40
STATE OF
• c • ��
01 I I lil l� ``` 10/08/21
his document has been digitally signed and sealed by Gregory A.
abaka, PE on the date adjacent to the seal. Printed copies of this
ocument are not considered signed and sealed and the signature
rust be verified on any electronic copies.
Revisions
No. Description Date
0 PERMIT SET 09/07/21
1 NEW BOOTH, RPS6 REALLOC. 10/08/21
COMPLETE ALARM INC.
MAVERICK BOATS, INC.
Project Address
4551 ST. LUCIE BLVD
FT. PIERCE, FL 34946
N
W
FIRE ALARM RISER
DIAGRAM - SLC
U
J
Project Number ACE0146
Date 10/08/21
Drawn By G.TABAKA
Checked By G.TABAKA N
LU
FA-501
(REV. 1)
Scale (uoN) 1 " = 60'-0"
Q
7
J
H
EXISTING (EXPANDED) FRCP CALCULATIONS
G
F
A III
'. �• �;
E
0
C
B
A
8
7
6
5
4
3
FRCP LOADS PART 1 - PANEL AND MODULES DEVICES
•
MANUFACTURER
MODEL
LOOP
COUNT
ALARM CURRENT
STANDBY CURRENT
EACH
SUBTOTAL
EACH
SUBTOTAL
•
SILENT KNIGHT
SK-5860
1
20.0 mA
20.0 mA
25.0 mA
25.0 mA
•
SILENT KNIGHT
5808
1
365.0 mA
365.0 mA
170.0 mA
170.0 mA
385.0 mA 195.0 mA
1
1
•
SILENT KNIGHT SK-ISO-6
1
1
102.0 mA
102.0 mA
2.7 mA
1 2.7 mA
102.0 mA 2.7 mA
1.1
•
SILENT KNIGHT SK-PULL-DA
1.1
2
0.4 mA
0.8 mA
0.4 mA
0.8 mA
•
SILENT KNIGHT SK-PHOTO-W
1.1
2
2.0 mA
4.0 mA
0.3 mA
0.6 mA
4.8 mA 1.4 mA
1.2
•
_
SILENT KNIGHT SK-RELAY
1.2
5
0.3 mA
1.3 mA
0.3 mA
1.3 mA
•
SILENT KNIGHT SK-PULL-DA
1.2
5
0.4 mA
1.9 mA
0.4 mA
1.9 mA
3.2 mA 3.2 mA
1.3
•
SILENT KNIGHT SK-RELAY
1.31
61
0.3 mA
1.6 mA
0.3 mA
1.6 mA
•
SILENT KNIGHT SK-PULL-DA
1.31
61
0.4 mA
1 2.3 mA
0.4 mA
2.3 mA
3.8 mA 3.8 mA
1.4
•
_
SILENT KNIGHT
SK-RELAY
1.4
2
0.3 mA
0.5 mA
0.3 mA
0.5 mA
•
SILENT KNIGHT
SK-MONITOR
1.4
1
0.4 mA
0.4 mA
0.4 mA
0.4 mA
•
SILENT KNIGHT
j SK-PULL-DA
1.4
1
0.4 mA
0.4 mA
0.4 mA
0.4 mA
1.3 mA 1.3 mA
1.4E
•
SILENT KNIGHT
SK-HEAT-W
1.4E
1
2.0 mA
2.0 mA
0.2 mA
0.2 mA
•
SILENT KNIGHT
SK-RELAY
1.4E
1.4E
6
0.3 mA
1.6 mA
0.3 mA
1.6 mA
•
SILENT KNIGHT
SK-MONITOR
8
0.4 mA
3.0 mA
0.4 mA
3.0 mA
•
SILENT KNIGHT
SK-MONITOR-2
1.4E
1
0.8 mA
0.8 mA
0.8 mA
0.8 mA
•
SILENT KNIGHT
SK-PULL-DA
1.4E
4
0.4 mA
1.5 MAI
0.4 mA
1.5 mA
8.9 mA 7.1 mA
1AW
•
SILENT KNIGHT
SK-HEAT-W
1AW
1
2.0 mA
2.0 mA
0.2 mA
0.2 mA
•
SILENT KNIGHT
SK-RELAY
1AW
7
0.3 mA
1.8 mA
0.3 mA
1.8 mA
•
SILENT KNIGHT
SK-CONTROL
1AW
1
0.4 mA
0.4 mA
0.4 mA
0.4 mA
•
SILENT KNIGHT
SK-MONITOR
1AW
1
0A mA
0.4 mA
0.4 mA
0.4 mA
•
SILENT KNIGHT
SK-PULL-DA
1AW
5
0.4 mA
1.9 mA
0.4 mA
1.9 mA
6.5 mA 4.7 mA
1.5
•
SILENT KNIGHT
SK-MONITOR
1.5
1.5
2
0.4 mA
0.8 mA 0.4 mA
0.8 mA
•
SILENT KNIGHT
j SK-PHOTO-W
1
2.0 mA
2.0 mA 0.3 mA
0.3 mA
2.8 mA 1.1 mA
1.5R
• SILENT KNIGHT SK-PHOTO-R-W 1.5R 51 2.0 mA 1 10.0 mA 0.3 mA 1.5 mA
10.0 mA 1.5 mA
1.5W
•
SILENT KNIGHT
SK-RELAY
1.5W
2 0.3 mA
0.5 mA
0.3 mA
0.5 mA
•
SILENT KNIGHT
SK-PULL-DA
1.5W
5 0.4 mA
1.9 mA
0.4 mA
1.9 mA
2.4 mA 2.4 mA
SUBTOTAL'PART V- INTERNAL AND ADDRESSABLE COMPONENTS 530.6 mA 224.1 mA,
FRCP LOADS PART 2 - AN AND AUX POWER
•
MANUFACTURER
MODEL
TAP
- ALARM CURRENT
COUNT EACHI SUBTOTAL
STANDBY CURRENT
EACH
I SUBTOTAL
0 -
1
•
WHEELOCK
HSC
1 150 Cd 99 dB
6 242.0 mA
1,452.0 mkF
0.0 mA
0.0 mA
1,452.0 mA 0.0 mA
2
•
WHEELOCK
HSC
150 Cd 99 dB
6'
242.0mAJ
1,452.0mAJ
0.0 mA
0.0 mA
1,452.0 mA 0.0 mA
3
•
WHEELOCK
HSC
150 Cd 99 dB
61 242.0 mA
1,452.0 mA
0.0 mA
0.0 mA
1,452.0 mA 0.0 mA
4,356.0 mA 0.0 mA
SUBTOTAL'PART 2'- VISIBLE AND AUXILIARY POWER 4,356.0 mA 0.0 mA
FACP LOAD SUMMARY
DESCRIPTION
CURRENT
BATTERY CAPACITY
PART 1
PART 2
TOTAL
TIME (HR)
LOAD (A-HR) A-HR x 1.25
ALARM CONDITIONS
530.0 mA
4,356.0 mA
4,886.0 mA
0.083
0.407 0.509
_ _
STANDBY CONDITIONS
223.5 mA
0.0 mA
223.5 mA
24.000
5.363 6.704
ALARM + STANDBY CAPACITY BATTERY CAPACITY
T 5.776 7.213
MINIMUM BATTERY SIZE (AMP-HR)
NO CHANGE FROM MINIMUM 2x17 A-HR
BATTERIES REQ'D FOR SK-5808.
1 J I H
L
SLC POINT -LOAD CALCULATIONS
PLAN LABEL
MODEL
WIRE_ PROPERTIES
RESIST. CAPACIT.
LENGTH!, TYPE (D&FT) (pF/kFT)
CAPACIT.
(pF)
ALARM
CURRENT
VOLTAGE
DROP
1
1
S1*1-0(0)
SK-ISO-6
20 ft
T8P
8.450
0.031 0.0006
102.0 mA
0,034 V
20 ft 0.0006 102.0 mA 0,034 V
1.1
S1*1.1-(D1)
SK-PHOTO-W
20 ft
T8P
8.450
0.031
0,0006
2.0 mA
0,002 V
S1*1.1-(D2)
SK-PHOTO-W
20 ft
T8P
8.450
0.031
0,0006
2.0 mA
0.002 V
S1*1.1-(M1)
SK-PULL-DA
85 ft
T8P
8.450
0.031
0.0026
0.4 mA
0.007 V
S1*1.1-(M2)
SK-PULL-DA
110 ft
T8P
8.450
0.031
0,0034
0.4 mA
0,009 V
1.1 235 ft 0.0073 4.8 mA 0.019 V
1.2
S1*1.2-(M3)
SK-PULL-DA
70 ft T8P
8,450
0.031
0.0022
0.4 mA
0,004 V
S1*1.2-(M5)
SK-PULL DA
120 ft T8P
8.450
0.031
0.0037
0.4 mA
0,006 V
S1*1.2-(M6)
SK-PULL-DA
120 ft T8P
8.450
0.031
0,0037
0.4 mA
0,006 V
S1*1.2-(M7)
SK-RELAY
50 ftJ T8P
8.450
0.031
0.0016
0.3 mA
0,003 V
S1*1.2-(M8)
SK-PULL-DA
90 ft I! T8P
8.45011
0.031
0.0028
0.4 mA
0.005 V
S1*1.2-(M9)
SK-RELAY
20 ft' T8P
8.4501
0.031
0.0006
0.3 mA
0.001 V
S1*1.2-(M10)
SK-RELAY
80 ft T8P
8.4501
0.031
0.0025
0.3 mA
0.004 V
S1*1.2-(M11)
SK-PULL-DA
70ftl T8P
8.4501
0.0311
0.0022
0.4 mA
0.004 V
S1*1.2-(M34)_-
S1*1.2-(M35)
SK-RELAY
SK-RELAY
60 ft! T8P
20 ft T8P
8.4501
8.4501
0.031'
0.0311
0.0019
0.0006
0.3 mA
0.3 mA
0.003 V
0.001 V
1.2 700 ft 0.0217 3.2 mA 0.038 V
1.3
S1*1.3-(M12)
SK-RELAY
80 ft
T8P
8.450
0.031
0.0025
0.3 mA
0,005 V
S1*1.3-(M14)
SK-RELAY
160 ft
T8P
8.450
0.031
0.0050
0.3 mA
0.010 V
S1*1.3-(M15)
SK-PULL-DA
35 ft
T8P
8.450
0.031
0.0011
0.4 mA
0.002 V
S1*1,3-(M16)
SK-RELAY
25 ft
T8P
8.450
0.031
0.0008
0.3 mA
0.002 V
S1*1.3-(M17)
SK-RELAY
60 ft
T8P
8.450
0.031
0.0019
0.3 mA
0.004 V
S1*1.3-(M18)
SK-PULL-DA
70 ft
T8P
8.450
0.031
0.0022
0.4 mA
0.005 V
S1*1.3-(M19)
SK-RELAY
55 ft
T8P
8.450
0.031
0.0017
0.3 mA
0.004 V
S1*1.3-(M20)
SK-RELAY
55 ft
T8P
8.450'
0.031
0.0017
0.3 mA
0.004 V
S1*1.3-(M21)
SK-PULL-DA
70 ft
T8P
8,4501
0.031
0.0022
0.4 mA
0.005 V
S1*1.3-(M22)
SK-PULL-DA
120 ft
T8P
8.45011
0.031
0.0037
0.4 mA
0.008 V
S1*1.3-(M53)
SK-PULL-DA
30 ft
T8P
8.4501
0.031
0.0009
0.4 mA
0.002 V
S1*1.3-(M54)
SK-PULL-DA
60 ft
T8P
8.4501
0.031
0.0019
0.4 mA
0.004 V
1.3 820 ft 0.0254 3.8 mA 0.053 V
1.4
S1*1.4-(M23)
SK-PULL-DA
240 ft
T8P
8.450
0.031
0,0074
0.4 mA
0.005 V
S1*1.4-(M36)
SK-RELAY
90 ft
T8P
8.450
0.031
0.0028
0.3 mA
0.002 V
S1*1.4-(M60)
SK-MONITOR
100 ft
T8P
8.450
0.031
0.0031
0.4 mA
0.002 V
S1*1.4-(M64)
SK-RELAY
70 ft
T8P
8.450
0.031
0.0022
0.3 mA
0.002 V
1.4 500 ft 0.0155 1.3 mA 0.011 V
1.4E
S1*1.4E-(D5)
SK-HEAT-W
20 ft
T8P
8.450
0,031
0.0006
2.0 mA
0.003 V
S1*1.4E-(M4)
SK-RELAY
30 ft
T8P
8.450
0.031
0.0009
0.3 mA
0.004 V
S1*1.4E-(M13?)
SK-RELAY
80 ft
T8P
8.450
0.031
0.0025
0.3 mA
0.012 V
S1*1.4E-(M28)
SK-PULL-DA
300 ft
T8P
8.450
0.031
0.0093
0.4 mA
0.045 V
S1*1.4E-(M29)
SK-PULL-DA
260 ft
T8P
8.450
0.031
0.0081
0.4 mA
0.039 V
S1*1.4E-(M30)
SK-PULL-DA
260 ft
T8P
8.450
0.031
0.0081
0.4 mA
0,039 V
S1*1.4E-(M31)
SK-PULL-DA
260 ft
T8P
8.450
0.031
0.0081
0.4 mA
0.039 V
S1*1.4E-(M32)
SK-MONITOR
20 ft
T8P
8.450
0.031
0.0006
0.4 mA
0.003 V
S1*1.4E-(M33)
SK-MONITOR
20 ft
T8P
8.450
0.031
0.0006
0.4 mA
0.003 V
S1*1.4E-(M41)
SK-MONITOR
20 ft
T8P
8.450
0.031
0.0006
0.4 mA
0.003 V
S1*1.4E-(M42)
SK-RELAY
90 ft
T8P
8.450
0.031
0.0028
0.3 mA
0.013 V
S1*1.4E-(M43)
SK-RELAY
20 ft
T8P
8,450
0,031
0.0006
0.3 mA
0.003 V
S1*1.4E-(M46)
SK-RELAY
20 ft
T8P
8.450
0.031
0.0006
0.3 mA
0.003 V
S1*1.4E-(M47)
SK-MONITOR
20 ft
_
T8P
8.450'
0.031
0.0006
0.4 mA
0.003 V
S1*1.4E-(M48)
SK-MONITOR
20 ft
T8P
8.450
0.031
0.0006
0.4 mA
0.003 V
S1*1.4E-(M49)
SK-MONITOR
20 ft
T8P
8.450
0.031
0.0006
0.4 mA
0.003 V
S1*1.4E-(M50)
SK-MONITOR
20 ft
T8P
8.450
0.031
0.0006
0.4 mA
0.003 V
S1*1.4E-(M51)
SK-MONITOR
20 ft
T8P
8.450
0.031
0.0006
0.4 mA
0.003 V
S1*l.4E-(M52)
SK-RELAY
70 ft
T8P
8.450
0.031
0.0022
0.3 mA
0,010 V
S1*1.4E-(M80, M81_)
SK-MONITOR-2
30 ft
T8P
8.450
0.031
0.0009
0.8 mA
0.004 V
1.4E 1,600 ft 0.0496 8.9 mA 0.240 V
G
G
E
CALCULATIONS IiEVISED
11
SLC POINT -LOAD CALCULATIONS
PLAN LABEL
MODEL
WIRE PROPERTIES
ALARM
CAPACIT.' VOLTAGE
(HF) CURRENT DROP
LENGTH
I TYPE
RESIST.
(S21kFT)
CAPACIT.
(HFIkFT)
1AW
S 1 * 1.4W-(D4)
SK-H EAT-W
20 ft
T8P
8.450
0.031
0.0006
2.0 mA
0.002 V
S1*1AW-(M24)
SK-PULL-DA
160 ft
T8P
8.450
0.031
0,0050
0.0071
0.4 mA
0.4 mA
0.018 V
0.025 V
S1*1AW-(M25)
SK-PULL-DA
230 ft
T8P
8.450
0.031
S1*1.4W-(M26)
SK-PULL-DA
240 ft
T8P
8.450
0.031
0.0074
0.4 mA
0.026 V
S1*1.4W-(M27)
SK-PULL-DA
165 ft
T8P
i 8.450
0.031
0.0051
0.4 mA
0.018 V
S1*1.4W-(M37)
SK-RELAY
115 ft
T8P
8.450
0.031
0.0036
0.3 mA
0.013 V
S1*1.4W-(M38)
SK-RELAY
170 ft
T8P
8.450
0.031
0.0053
0.3 mA
0.019 V
S1*1.4W-(M39)
SK-RELAY
160 ft
T8P
8.450
0.031
0.0050
0.3 mA
0,018 V
S1*1.4W-(M40)
SK-RELAY
20 ft'
(none)
1 0.3 mA
S1*1.4W-(M44)
SK-MONITOR
20 ft
T8P
8.450
0.031
0.0006j
0.4 mA
0.002 V
S1*1.4W-(M45)
V6*1-1
SK-CONTROL
-
20 ft
T8P
8.450
0.031
0.0006
j 0.4 mA
0.002 V
(----)
S1*1.4W- M63
SK PULL-DA
30 ft
T8P
8.450
-
_ 0.031
0.031
0.0009
j 0.4 mA
0.003 V
S1*1.4W-(M65)
SK-RELAY
20 ft
T8P
8.450
0.0006j
0.3 mA
0.002 V
S1*1.4W-(M66)
SK-RELAY
20 ft
T8P
8.450
0.031
0.0006
0.3 mA!
0.002 V
S1*1.4W-(M67)
SK-RELAY
40 ft
T8P
8.450
0.031
0.0012� 0.3 mA
0.004 V
1AW 1,430 ft 0.0437 6.5 mA 0.154 V
1.5
S1*1.5-(D3) _
SK-PHOTO-W
30 ft
T8P
8.450
0.031
0.0009
2.0 mA!
0.001 V
S1*1 5-(M69)
_
SK-MONITOR
10 ft
T8P
8.450
0.031
0.0003
0.4 mA
0.000 V
S1*1 5-(M99) -
SK-MONITOR
400 ft
T8P
8.450
0.031
0.0124
0.4 mA
j 0.019 V
1.5 440 ft 0.0136 2.8 mA 0.021 V
1.5R
S1*L5R-0.2
DTK-2MHLP24BWB
20 ft
T8P
8,450
0.031
0.031
0.0006
0.0 mA
0.003 V
S1*1.5R-1(D6)
SK-PHOTO-R-W
350 ft
T8P
8.450
0.0109
2.0 mA
0.059 V
S1*1.5R-2(D7)
SK-PHOTO-R-W
120 ft
T8P
8.450
0.031
0.031
0.0037
2.0 mA
0.020 V
S1*1.5R-3(D8)
SK-PHOTO-R-W
150 ft
T8P
8.450
0.0047
2.0 mA
0.025 V
S1*1.5R-4(D9)
SK-PHOTO-R-W
200 ft
T8P
8.450
0.031
0,0062
2.0 mA
0.034 V
S1*1.5R-4(D10)
SK-PHOTO-R-W
330 ft
T8P
8.450
0.031
0.0102
2.0 mA
0.056 V
1.5R 1,170 ft 0.0363 10.0 mA 0.198 V
1.5W
S1*1.5W-(M55)
SK-PULL-DA
45 ft
T8P
8.450
0.031
0,0014
0.4 mA
0.002 V
S1*1.5W-(M56)
SK-PULL-DA _
120 ft
T8P
8.450
0.031
0.0037
0.4 mA
0.005 V
S1*1.5W-(M57)
SK-RELAY
120 ft
T8P
8.450
0.031
0.0037
0.3 mA'
0.005 V
S1*1.5W-(M58)
SK-PULL-DA
30 ft
T8P
8,450
0.031
0,0009
0.4 mA
0.001 V
S1*1.5W-(M59)
SK-PULL-DA
100 ft
T8P
8.450
0.031
0.0031
0.4 mA
0A04 V
S1*1.5W-(M61)
SK-RELAY
60 ft
T8P
8.450
0.031
0.0019'
0.3 mA
0.002 V
S1*1.5W-(M62)
SK-PULL-DA
50 ft
T8P
8.450
0.031
0.0016
0.4 mA
0.002 V
1.5W 525 ft 0.0163 2.4 mA 0.021 V
SLC LOADING/FAUL.T ISOLATOR CALCULATION
SK-5808 SLC IS RATED AT 32 VDC, 150 mA. SK-ISO-6 MODULE DRAWS 2.7 mA UNDER NORMAL CONDITIONS OR 17 mA PER
CIRCUIT ISOLATED. AS SHOWN ON RISER DIAGRAM, FIVE TAPS ARE USED. WHEN A CIRCUIT IS ISOLATED, ITS LOAD IS
DISCONNECTED FROM THE FRCP. WORST CASE CURRENT DRAW ON THE SLC OCCURS WHEN CIRCUITS LOADED LESS THAN 17
mA ARE DISCONNECTED/ISOLATED: THESE AIRE CIRCUITS 1.1, 1.2,1.3 AND 1.5. CALCULATION ABOVE SHOWS MAXIMUM 102 mA
CURRENT DRAW FOR SIX DISCONNECTED CIRCUITS, WHICH IS OVERLY -CONSERVATIVE. WORST CASE CURRENT LOAD ON THE
SLC WITH RED LEDS ON DETECTORS IS:
CKT 1: CKT 1.1: CKT 1.2: CKT 1.3: CKT 1.4: CKT 1.5: EMPTY #6: TOTAL
2.7 + 17.0 +17.0 +17.0 + (1.3 + 8.9 + 6.5) +17.0 + 0 87.4mA
SILENT KNIGHT 5808:
MAXIMUM SLC LINE: CAPACITANCE: 0.50 NF
MAXIMUM SLC LINE: RESISTANCE, PER PAIR, PER LEG: 40 OHM (SK, APPROX 3,900 F-I @ 18 AWG)
MAXIMUM SLC AGGREGATE WIRE DISTANCE WITH T-TAPS: 40,000 FT
MAXIMUM SBUS LINE CAPACITANCE: NO STATED LIMIT
MAXIMUM SBUS LINE LENGTH: 4,688 FT @ 18 AWG
MAXIMUM SBUS VOLTAGE DROP: 6.0 V
MAXIMUM CURRENT DRAW: 6.0 A
C
11
Antinomy Consulting Engineers
Code Consulting - Fire Protection - Smoke Control
600 Rinehart Road Suite 2054
Lake Mary, FL 32746-4955
Tel. 321-888-2882 Online: antinomy.com
Prepared For
- g�r
EC #13001688
fitiii
No 73972
0 STATE OF tv;
�'� �� � i I t i ► � � � ``` 10/08/21
This document has been digitally signed and sealed by Gregory A.
Tabaka, PE on the date adjacent to the seal. Printed copies of this
document are not considered signed and sealed and the signature
must be verified on any electronic copies.
Revisions
No. Description Date
0 PERMIT SET 09/07/21
1 NEW BOOTH, RPS6 REALLOC. 10/08/21
COMPLETE ALARM INC.
MAVERICK BOATS, INC.
Project Address
4551 ST. LUCIE BLVD
FT. PIERCE, FL 34946
FIRE ALARM
CALCULATIONS 1
Project Number ACE0146
Date 10/08/21
Drawn By G.TABAKA
Checked By G.TABAKA
FA -boo (REV. 1)
Scale (IJON)
N
a
0
z
0
a
J
U
J
Q
U
a
Q
cc
LL
6
0
a
Ul
J
I j
PANEL RPS 2 CALCULATIONS
H I G I F E
PANEL IRPS3 CALCULATIONS
0
C
B
PANEL RPS4 CALCULATIONS
A
11111�1 I, lim
8'
71
6'
51
4
3
21
RPS2 NAC LINE LOSS CALCULATIONS (NEW CIRCUIT)
--
- ----------
PROPERTIES
--WIRE
RESIST.
SEGMENT
DEVICE
PLAN LABEL
MODEL
TAP
MAX LOAD
LENGTH
TYPE
(i?JkFT)
CURRENT
V DROPS
VOLT
2
3
V2*3-1
HSC
95 Cd
176.0 mA
320 ft
P4P
3.26
704.0 mA
1.469 V
18.931 V
99 dB
V2*3-2
HSC
95 Cd
176.0 mA
70 ft
P4P
3.26
528.0 mA
0.241 V
18.690 V
99 dB
V2*3-3
HSC
95 Cd
176.0 mA
70 ft
P4P
3.26
352.0 mA
0.161 V
18.529 V
99 dB
V2*34
HSC
95 Cd
176.0 mA
70 ft
P41P
3.26
176.0 mA
0.080 V
18.449 V
99 dB
3 530 ft 1.951 V
RPS2 LOADS (NEW AND EXISTING)
•
MANUFACTURER
MODEL TAP
COUNT
ALARM CURRENT
STANDBY CURRENT
EACH
SUBTOTAL
EACH
I SUBTOTAL
2
•
SILENT KNIGHT
SK-5496
1
160.0 mA
160.0 mA
1 40.0 mAJ
40.0 mA
160.0 mA 40.0 mA
1
• WHEELOCK HS 15 1 65.0 mA 65.0 mA 0.0 mA 0.0 mA
• WHEELOCK STIR 15 1 57.0 mA 57.0 mA 0.0 mA 0.0 mA
• WHEELOCK HSC 15 2 65.0 mA 130.0 mA 0.0 mA 0.0 mA
• WHEELOCK ASWP-24MCWH-FR 135 1 0.4 mA 0.4 mA 0.0 mA 0.0 mA
•
WHEELOCK
RSSWP-2475W-FR
30
1
138.0 mA
138.0 mA
0.0 mA
0.0 mA
390.4 mA 0.0 mA
2
HS
15
1
65.0 mA
65.0 mA
0.0 mA
0.0 mA
UWHEELOCK
STR
15
1
57.0 mA
57.0 mA
0.0 mA
0.0 mA
HSC
15
1
65.0 mA
65.0 mA
0.0 mA
0.0 mA
•
WHEELOCK
HSC
75
2
136.0 mA
272.0 mA
0.0 mA
0.0 mA
•
WHEELOCK
ASWP-24MCWH-FR
1351
2
0.4 mA
0.7 mA
0.0 mA
0.0 mA
•
WHEELOCK
RSSWP-2475W-FR
3oT
1
138.0 mA
138.0 mA
0.0 mA
0.0 mA
597.7 mA 0.0 mA
3
•
WHEELOCK
HSC
95 Cd 99 dB', 41 176.0 mA
704.0 mA
0.0 mA
0.0 mA
704.0 mA 0.0 mA
A
•
WHEELOCK MB-G6-24-R --�1
11
40.0 mA
40.0 mA 0.0 mA
0.0 mA
40.0 mA 0.0 mA
1,892.1 mA 40.0 mA
TOTAL VISIBLE AND AUXILIARY POWER 1,892,1 mA 40.0 mA
RPS2 LOAD SUMMARY
DESCRIPTION
TOTAL
BATTERY CAPACITY
TIME (HR) LOAD (A-HR)
A-HR x 1.25
ALARM CONDITIONS
1,892.1 mA
0.083 0.158
0.197
STANDBY CONDITIONS
40.0 mA
24.000 0.960
1.200
ALARM + STANDBY CAPACITY BATTERY CAPACITY
F 1.118
1.397
MINIMUM BATTERY SIZE (AMP-HR)
RETAIN EXISTING 2x7 A-HR BATTERIES.
CIRCUIT NOTE:
MINIMUM EOL VOLTAGE: 18.00 V FOR BELL
RPS3 NAC LINE LOSS CALCULATIONS (NEW CIRCUITS)
PLAN LABEL
MODEL
TAP
_ WIRE PROPERTIES
RESIST. SEGMENT
LENGTH -
MAX LOAD] TYPE (0JkFT) CURRENT
V DROP
DEVICE
VOLT-
_--_-
3
2
V3*2-1
JPC2RHK
1351
245.0 mA
300 ft
I P6P
1 5.291
245.0 mA
0.778 V
19.622 V
2 300 ft 0.778 V
3
V3*3-1
PC2RHK
177
290.0 mA
360 ft
P6P
5.29
590.0 mA
2.247 V
18.153 V
V3*3-2
PC2RHK
177
290.0 mA
20 ft
P6P
5.29
290.0 mA
0.061 V
18.092 V
3 380 ft 2.308 V
RPS3 LOADS (NEW AND EXISTING)
•
MANUFACTURER
MODEL TAP
COUNT
ALARM CURRENT
STANDBY CURRENT
EACH
SUBTOTAL
EACH
SUBTOTAL
•
SILENT KNIGHT
SK-5499
SK-5496
T 1
205.0 mA
205.0 mA
75.0 MAT
75.0 mA
205.0 mA 75.0 mA
1
•
WHEELOCK
ASWP-2475C-FR
115
2
355.0 In
710.0 mA
0.0 mA
0.0 mA
710.0 mA 0.0 mA
2
•
SYSTEM SENSOR
PC2RHK
135
1
245.0 mA�
245.0 rnA 0.0 mA
0.0 mA
- - -
245.0 rnA 0.0 mA
3
•
SYSTEM SENSOR
JPC2RHK
1 1771
21
290.0 mA
58 1.0 mA
0.0 mA
0.0 mA
--
580.0 mA 0.0 mA
1,740.0 rnA 75.0 mA
TOTAL VISIBLE AND AUXILIARY POWER 1,740.0 rnA 75.0 mA
RPS3 LOAD SUMMARY
DESCRIPTION
TOTAL
BATTERY CAPACITY
TIME (HR) LOAD (A-HR)
A-HR x 1.25
ALARM CONDITIONS
1,740.0 mA
0.083 0.145
0.181
STANDBY CONDITIONS
75.0 mA
24.000 1.800
2.250
2.431
ALARM + STANDBY CAPACITY BATTERY CAPACITY
I 1.945
r
MINIMUM BATTERY SIZE (AMP-HR)
RETAIN EXISTING 2x7 A -FIR BATTERIES.
RPS4 NAC LINE LOSS CALCULATIONS (NEW CIRCUITS)
---
------------ -
WIRE PROPERTIES
---
RESIST. SEGMENT
DEVICE
PLAN LABEL
MODEL TAP
MAX LOAD]
LENGTH 1 TYPE (S21kFT) CURRENT
V DROP
VOLT
4
3
V4*3-1
FHEX
XP
1,20).0 mA
220 ft
P6P
5.29
1,200.0 mA
2.793 V
17.607 V
3
220 ft
2.793 V
4
V4*4-1
FSEX-HI
XP,15
1,900.0 mA
200 ft
P4P
3.26
1,900.0 mA
2.478 V
17.922 V
0
4
200 ft
2.478 V
•
MANUFACTURER
MODEL
RPS4 LOADS (NEW AND EXISTING)
ALARM CURRENT
TAP COUNT EACH; SUBTOTAL
STANDBY CURRENT
EACH SUBTOTAL
4
•
SILENT KNIGHT
SK-5499
SK-5499
1
205.0 mA
1 205.0 mA
75.0 MAI
75.0 mA
1
205.0 mA
75.0 mA
•
FEDERAL SIGNAL
FSEX-HI
XP,150
1
1,900.0 mA
1,900.0 mA
0.0 mA
0.0 mA
2
1,900.0 mA
0.0 mA
•
FEDERAL SIGNAL
FHEX
XPI
11
1,200.0 mA
1,200.0 MAT
0.0 mA
1
0.0 mA
3
1,200.0 mA
0.0 mA
•
FEDERAL SIGNAL
FHEX
XP
1
1,200.0 mA
1,200.0 mA
0.0 mA
0.0 mA
4
1,200,0 mA
0.0 mA
•
FEDERAL SIGNAL
FSEX-HI
XP,150
1
1,900.0 mA
1,900,0 mA
0.0 mA
0.0 mA
TOTAL VISIBLE AND AUXILIARY POWER
1,900,0 mA,
6,405,0 mA
6,405.0 mA
0.0 mA
75.0 mA
75.0 mA
RPS4 LOAD SUMMARY
DESCRIPTION
TOTAL
BATTERY CAPACITY
TIME (HR) LOAD (A-HR)
A-HR x 1.25
ALARM CONDITIONS
6,405.0 mA
0.083 0.534
0.667
STANDBY CONDITIONS
75.0 mA
24.000 1.800
2.250
ALARM + STANDBY CAPACITY BATTERY CAPACITY
2.334
2.917
MINIMUM BATTERY SIZE (AMP-HR)
RETAIN EXISTING 2x7 A-HR BATTERIES.
Antinomy Consulting Engineers
Code Consulting - fire Protection - Smoke Control
600 Rinehart Road Suite 2054
Lake Mary, FL 32746-4955
Tel. 321-888-2882 Online: antinomy.com
Prepared For:
E ' xo
EC #13001688
c, E N
No 73972
44,�
0% STATE OF
0 I I t i t t 10l08/21
This document has been digitally signed and sealed by Gregory A.
Tabaka, PE on the date adjacent to the seal. Printed copies of this
document are not considered signed and sealed and the signature
must be verified on any electronic copies.
Revisions
No. Description Date
0 PERMIT SET 09/07/21
COMPLETE ALARM INC.
MAVERICK BOATS, INC.
Project Address
4551 ST. LUCIE BLVD
FT. PIERCE, FL 34946
FIHL ALAKIVI N
CD
CALCULATIONS 2
Project Number ACE0146 N
Cn
Date 10/08/21 0
Drawn By G.TABAKA
Checked By G.TABAKA
FA-601LU
(REV. 0) U_
Scale (LION)co
J I H I G I F E I 0 C B A
J i H
PANEL RPS 5 CALCULATIONS
G F E
PANEL RPS5 CALCULATIONS - CONTINUED
D C B
I
PANEL RPS6 CALCULATIONS
ANTINOMY
8
7
5
4
3
K
RPS5 NAC LINE LOSS CALCULATIONS
PLAN LABEL
MODEL
-._T
TAP
MAX LOAD
WIRE PROPERTIES
-
V DROP
-- -- - - -
DEVICE
VOLT
---
LENGTH
TYPE
RESIST.
((VkFT)
SEGMENT
CURRENT
5
1
V5*1-1
HSC
150 Cd 99 dB
242.0 mA
180 ft
P2P
2.05
1,452.0 mA
1.072 V
19.328 V
V5*1-2
HSC
150 Cd 99 dB
242.0 mA
70 ft
P2P
2.05
1,210,0 mA
0.347 V
18.981 V
V5*1-3
HSC
150 Cd 99 dB
242.0 mA
70 ft
P2P
2.05
968.0 mA
0.278 V
18.703 V
V5*1-4
HSC
150 Cd 99 dB
242.0 mA
210 ft
P2P
2.05
726.0 mA
0.625 V
18.078 V
V5*1-5
HSC
150 Cd 99 dB
242.0 mA
70 ft
P2P
2.05
484.0 mA
0.139 V
17.939 V
V5*1-6
HSC
150 Cd 99 dB
242.0 mA
70 ft
P2P
2.05
242.0 mA
0.069 V
17.870 V
1 670 ft 2.530 V
2
V5*2-1
LHSR3
15
46.0 mA
20 ft
P2P
2.05
1,498.0 mA
0.123 V
20.277 V
V5*2-2
HSC
150 Cd 99 dB
242.0 mA
95 ft
P2P
2.05
1,452.0 mA
0.566 V'
19.711 V
V5*2-3
HSC
150 Cd 99 dB
242.0 mA
170 ft
P2P
2.05
1,210.0 mA
0.843 V
18.868 V
V5*2.4
HSC
150 Cd 99 dB
242.0 mA
70 ft
P2P
2.05
968.0 mA
0.278 V
18.590 V
V5*2-5
HSC
150 Cd 99 dB
242.0 mA
210 ft
P2P
2.05
726.0 mA
0.625 V
17.965 V
V5*2-6
HSC
150 Cd 99 dB
242.0 mA
70 ft
P2P
2.05
484.0 mA
0.139 V
17,826 V
V5*2-7
HSC
150 Cd 99 dB
242.0 mA
70 ft
P2P
2.05
242.0 mA
0.069 V
17,757 V
2 705 ft 2.643 V
3
V5*3-1
HSC
150 Cd 99 dB
242.0 mA
390 ft
P2P
j 2.05
1,210.0 mA
1.935 V
j 18,465 V
V5*3-2
HSC
150 Cd 99 dB
242.0 mA
70 ft
P2P
2.05
968.0 mA
0.278 V
18.187 V
V5*3-3
HSC
150 Cd 99 dB
242.0 mA
70 ft
P2P
2.05
726.0 mA
0.208 V
17.979 V
V5*34
HSC
150 Cd 99 dB
242.0 mA
70 ft
P2P
2.05
484.0 mA
0.139 V
17.840 V
V5*3-5
HSC
150 Cd 99 dB
242.0 mA
70 ft
P2P
2.05
242.0 mA
0.069 V
17,771 V
3 670 ft 2.629 V
4
V5*4-1 HSC 150 Cd 99 dB 242.0 mA 320 ft P2P 2,05 1,210.0 mA 1.588 V 18.812 V
V5*4-2
HSC
150 Cd 99 dB
242A mA
70 ft
P21P
2.05
968.0 mA
0.278 V
18.534 V
V5*4-3
HSC
150 Cd 99 dB
242.0 mA
242.0 mA
70 ft
P21P
2.05
726.0 mA
0.208 V
18.326 V
V5*44
HSC
150 Cd 99 dB
70 ft
P2P
2.05
484.0 mA
0.139 V
18.187 V
V5*4-5
HSC
150 Cd 99 dB
242.0 mA
70 ft
P2P
2.05
242.0 mA
0.069 V
18.118 V
4 600 ft 2.282 V
5
V5*5-1
HSC
150 Cd 99 dB
242.0 mA
320 ft
P2P
2.05
1,452.0 mA
1.905 V
18.495-V
V5*5-2
HSC
150 Cd 99 dB
242.0 mA
70 ft
P2P
2.05
1,210.0 mA
0.347 V
18.148 V
V5*5-3
HSC
150 Cd 99 dB
242.0 mA
70 ft
P2P
2.05
968.0 mA
0.278 V
17.870 V
V5*5-4
HSC
150 Cd 99 dB
242.0 mA
70 ft
P2P
2.05
726.0 mA
0.208 V
17.662 V
V5*5-5
HSC
150 Cd 99 d6
242.0 mA
70 ft
P2P
2.05
484.0 mA
0.139 V
17.524 V
V5*5-6
HSC
150 Cd 99 dB
242.0 mA
70 ft
P2P
2.05
242.0 mA
0.069 V
17.455 V
5 670 ft 2.946 V
6
V5*6-1
HSC
150 Cd 99 dB
242.0 mA
310 ft
P2P
2.05
1,452.0 mA
1.845 V
18,555 V
V5*6-2
HSC
150 Cd 99 dB
242.0 mA
70 ft
P2P
2.05
1,210.0 mA
0.347 V
18.208 V
V5*6-3
HSC
150 Cd 99 dB
242.0 mA
70 ft
P2P
2.05
968.0 mA
0.278 V
17.930 V
V5*64
HSC
150 Cd 99 dB
242.0 mA
70 ft
P2P
2.05
726.0 mA
0.208 V
17.722 V
V5*6-5
HSC
150 Cd 99 dB
242.0 mA
i 70 ft
P2P
2.05
484.0 mA
0.139 V
17.583 V
V5*6-6
HSC
150 Cd 99 dB
242.0 mA
70 ft
P2P
2.05
242.0 mA
0.069 V
17.514 V
6 660 ft 2.886 V
7
V5*7-1
HSC
75
136.0 mA 320 ft
P2P
2.05
272.0 mA
0.357 V
20.043 V
V5*7-2
HSC
75
136.0 mA 20 ft
P2P
2.05
136.0 mA
0.011 V
20.032 V
7 340 ft 0.368 V
SILENT KNIGHT PS-10/PS-6
ALLOWABLE VOLTAGE DROP AT FULL LOAD: 3.20 V
RPS5 LOADS
•
MANUFACTURER
MODEL
TAP
COUNT
ALARM CURRENT
STANDBY CURRENT
EACH
SUBTOTAL
EACH
SUBTOTAL
5
•
SILENT KNIGHT
SK-PS10
SK-PS10
1
185.0 mA
185.0 mA
6.0 mA
156.0 mA
185.0 mA 156,0 mA
1
•
WHEELOCK
HSC
150 Cd 99 dB
6
242.0 mA
1,452.0 mA
0.0 mA
0,0 mA
1,452.0 mA 0.0 mA
2
•
WHEELOCK
LHSR3
15
1
46.0 mA
46.0 mA
0.0 mA
0.0 mA
•
WHEELOCK
IHSC
150 Cd 99 dB
6
242.0 mA
1,452.0 mA
0.0 mA
0.0 mA
1,498.0 mA 0.0 mA
3
•
WHEELOCK
JHSC
150 Cd 99 dB
51
242.0 mA
1,210.0 mA
0,0 mA
0.0 mA
1,210.0 mA 0.0 mA
4
•
WHEELOCK
JHSC
150 Cd 99 dB
5
242.0 mA
1,210.0 mA'[ 0.0 mA 0.0 mA
1,210.0 mA 0.0 mA
5
•I
WHEELOCK
JHSC
150 Cd 99 dB
6
242.0 mA
1,452.0 mA
0.0 mA
0,0 mA
1,452.0 mA 0.0 mA
6
•
WHEELOCK
JHSC
150 Cd 99 dB
6
242.0 mA
1,452.0 mA
0.0 mA
0.0 mA
1,452.0 mA 0.0 mA
7
•WHEELOCK
HSC
-
75
136.0 mA
2' - --
I 272.0 A � 0.
m
_ J0 mA 0,0 mA _--
272.0 mA 0.0 mA
8,731.0 mA 156.0 mA
TOTAL VISIBLE AND AUXILIARY POWER 8,731.0 mA 156.0 mA
RPS5 LOAD SUMMARY
DESCRIPTION
TOTAL
BATTERY CAPACITY
TIME (HR) LOAD (A-HR)
A-HR x 1.25
ALARM CONDITIONS
STANDBY CONDITIONS
8,731.0 mA
156.0 mA
0,083 0.728
24.000 3,744
0.909
4.680
ALARM + STANDBY CAPACITY BATTERY CAPACITY
1 4.472
MINIMUM BATTERY SIZE (AMP-HR)
PROVIDE 2x7 A-HR BATTERIES.
RPS6 NAC LINE LOSS CALCULATIONS
PLAN LABEL
MODEL
TAP
MAX LOAD
WIRE PROPERTIES
V DROP
DEVICE
VOLT
LENGTH
TYPE
RESIST.
(Q/kFT)
SEGMENT
CURRENT
6
1
P1*1.4W-V6*1-1
SK-CONTROL
NAC
7.0 mA
5ftl
P8P
8.45
7.0 mA
0.001 V
20.399 V
1 5 ft 0.001 V
3
V6*3-1
FSEX-HI
XP, 150
1,900.0 mA
160 ft
I P4P
1 3.26
1,900.0 mA
1.982 V
18.418 V
3 160 ft 1.982 V
4
V6*4-1
FSEX-HI
XP, 150
1,900.0 mA
200 ft
P4P
3.26
1,900.0 mA
2.478 V
17,922 V
4 200 ft 2.478 V
5
V6*5-1
FSEX-HI
XP,150
1,900.0 mA
1 200 ft
I P4P
1 3.26
1,900.0 mA
2.478 V
17.922 V
5 200 ft 2.478 V
6
V6*6-1
FHEX
XP
1,200.0 n
220 ft
I P6P
5.29
1,200.0 mA
2.793 V'' 17.607 V
6 220 ft 2.793 V
7
V6*7-1
FHEX
XP
1,200.0 mA
180 ft
P2P
2.05
2,400.0 mA
1.771 V
18.629 V
V6*7-2
FHEX
XP
1,200.0 mA
40 ft
P2P
2.05
1,200.0 mA
0.197 V
18.432 V
7 220 ft 1.968 V
RPS6 LOADS
•
MANUFACTURER
MODEL
TAP
COUNT
ALARM CURRENT
STANDBY CURRENT
EACH
SUBTOTAL
EACH SUBTOTAL
6
•
SILENT KNIGHT
SK-PS10
SK-PS10
1
185.0 mA
185.0 mA
156.0 mA
156.0 mA
185.0 mA 156.0 mA
1
•
SILENT KNIGHT
SK-CONTROL
NACI
11
7.0 mA
1.7 mA
1.7 mA
7.0 mA 1.7 mA
3
•
FEDERAL SIGNAL FSEX-HI
XP, 150
1
1,900.0 mA
1,900.0 mA
0.0 mA
0.0 mA
1,900.0 mA 0.0 mA
4
•
FEDERAL SIGNAL
FSEX-HI
XP,150
1
1,900.0 mA
1,900.0 mA
0.0 mA
0.0 mA
1,900.0 mA 0.0 mA
5
• FEDERAL SIGNAL FSEX-HI XP, 150 1 1,900.0 mA 1,900.0 mA 0.0 mA 0.0 mA
1,900.0 mA 0.0 mA
6
•
FEDERAL SIGNAL
FHEX
XP
1
1,200.0 mA
1,200.0 mA
0.0 mA
0.0 mA
1,200.0 mA 0.0 mA
7
•
FEDERAL SIGNAL
FHEX
XPI
21
1,200.0 mA
2,400.0 mA
0.0 mA
0.0 mA
2,400.0 mA 0.0 mA
9,492.0 mA 157.7 mA
TOTAL VISIBLE AND AUXILIARY POWER 9,492.0 rnA 157.7 mA
RPS6 LOAD SUMMARY
DESCRIPTION_____
TOTAL
BATTERY CAPACITY
TIME (HR) LOAD (A-HR)
A-HR x 1.25
ALARM CONDITIONS
_
9,492.0 mA
0.083 0.791
0.989
STANDBY CONDITIONS
157.7 mA
24.000 3.785
4.731
ALARM + STANDBY CAPACITY BATTERY CAPACITY i 4.576
5.720
MINIMUM BATTERY SIZE ;AMP-HR)
PROVIDE 2x7 A-HR BATTERIES.
J RPS6 CALCS REVISED
A
Antinomy Consulting Engineers
Code Consulting - fire Protection - Smoke Control
600 Rinehart Road Suite 2054
Lake Mary, FL 32746-4955
Tel. 321-888-2882 Online: antinomy.com
Prepared For:
4114
,, .a •g
h
EC #13001688
�111111111///�/ '
r�
No 73972
�� STATE OF
i F
i
r C� RON
�/ I i 1 i 1 10/08/21
This document has been digitally signed and sealed by Gregory A.
Tabaka, PE on the date adjacent to the seal. Printed copies of this
document are not considered signed and sealed and the signature
must be verified on any electronic copies.
Revisions
No. Description I Date
0 PERMIT SET 09/07/21
1 NEW BOOTH, RPS6 REALLOC. 10/08/21
COMPLETE ALARM INC.
MAVERICK BOATS, INC.
Project Address
4551 ST. LUCIE BLVD
FT. PIERCE, FL 34946
FIRE ALARM
O
CALCULATIONS 3
Project Number ACE0146 co
Cn
Date 10/08/21 0
Drawn By _ G.TABAKA
Checked By G.TABAKA
FA-602LU
(REV. 1) U-
Scale (UON)
J
G
E
I
it
B
J I H G F E D C B A
CEILING MOUNTED
SMOKE/HEAT
DETECTOR
5'(MIN)
ANTINOMY
81
71
61
51
4
3
21
AUDIO ONLY
FA MOUNTING DETAIL
NOT TO SCALE
AUDIOVISUAL
& VISUAL -ONLY
APPI IANrFS
A/C SUPPLY DIFFUSER
OR RETURN GRILLE
ACCEPTABLE HERE
DETAIL NOTES:
1. NOT ALL DEVICES SHOWN ON THIS DETAIL APPLY TO THIS PROJECT. SEE THE PLAN VIEW LAYOUT OF THE FIRE ALARM SYSTEM TO VERIFY WHICH APPLIANCES APPLY, AND WHICH DO NOT,
2. CHECK WITH MANUFACTURE'S INSTALLATION SHEET FOR THE EXACT ROUGH -IN HEIGHTS, LOCATION OF BACK. BOXES, AND WIRING REQUIREMENTS.
o
tzw
(D W
w OO
z z
w
O
w
Q
w
O
Oz
cco �
� m
Q
�
c~n
C/)
O�
O O
0
0
0
RPS4
(BATTERIES NOT SHOWN)
RpCF 1/1/IRIRIn nPTAII
Ot-I L-U. U - I -U
G F E
12" (MAX)
REMOTE
ANNUNCIATOR
NOTES: '
1
1, THIS DETAIL APPLIES ONLY TO RPS6, WHICH SERVES NEW BOOTH AN
APPLIANCES.
2. WIRE CIRCUITS AS SHOWN IN THIS DETAIL.
3. INTENTION IS TO DELAY ACTIVATION OF HORNS SLIGHTLY TO PERMIT
HIGH INRUSH CURRENT DRAW OF EXPLOSIONPROOF STROBES TO
CONCLUDE TO AVOID OVERLOADING THE POWER SUPPLY.
4. IF DELAY TIME IS INSUFFICIENT: CONFIGURE IN2 FOR TEMPORAL
DEBOUNCE.
5. FOR MOUNTING, BATTERY AND OTHER DETAILS, REFER TO NAC
EXPANDER INSTALLATION INSTRUCTIONS.
6. ADD THIS SK-CONTROL TO PROGRAM TO ACTIVATE WITH OTHER AN
CIRCUITS.
7. CHANGE PROGRAM LABEL OF RPS4 TROUBLE MONITOR MODULE.
ALTERNATE: MAY INSTALL SK-MINIMON OR EQUAL TO SUPERVISE RPS6
TROUBLE CONTACTS.
Antinomy Consulting Engineers
Code Consulting - Fire Protection • Smoke Control
600 Rinehart Road Suite 2054
Lake Mary, FL 32746-4955
Tel. 321-888-2882 Online: antinomy.com
Prepared For:
r
8
EC #13001688
`fit\Illlllr����
No 73972
STATE OF
1° 0 N A L l\% 10/08/21
This document has been digitally signed and sealed by Gregory A.
Tabaka, PE on the date adjacent to the seal, Printed copies of this
document are not considered signed and sealed and the signature
must be verified on any electronic copies.
Revisions
No. Description I Date
0 PERMIT SET 09/07/2I
1 NEW BOOTH, RPS6 REALLOC. 10/08/21
COMPLETE ALARM INC.
MAVERICK BOATS, INC.
Project Address
4551 ST. LUCIE BLVD
FT. PIERCE, FL 34946
FIRE ALARM DETAILS
Project Number
Date
Drawn By
Checked By
F
Scale (UON)
N
O
ACE0146
10/08/21
G.TABAKA
Q
G.TABAKA o
A-7 Ir
(REV. 1) U_ 00
As indicated
Q
LL
L
J I I H
/A'