Fire Sprinkler Piping Plan
�14 f
SCALE 1/8"=1'-0"
WATER SUPPLY
FLOW TEST
FIRE PUMP
DATE OF TEST: 7-10-17
RATED CAPACITY:
TIME OF TEST: 9:00 AM
RATED PRESSURE:
STATIC PRESSURE: 66
PUMP TYPE:
RESIDUAL PRESSURE: 58
WELL PUMP
GALLONS FLOWING: 920
GPM AVAILABLE:
TESTED BY: FT. PIERCE UTILITIES PSI AVAILABLE:
FIRE PROTECTION NOTES:
A. NEW GEL BOOTH — WET PIPE SYSTEM THROUGHOUT THE BUILDING IN ACCORDANCE WITH NFPA 13,
2016 EDITION AND THE LOCAL AUTHORITY. THE SPRINKLER SYSTEM IS HYDRAULICALLY DEISGNED TO
PROVIDE .20 GPM/SQ FT THROUGHOUT THE GEL BOOTH.
2. ALL 1 " THROUGH 1 %" DIAMETER PIPE TO BE SCH. 40 BLACK STEEL PER ASTM A-135/A-795
AND SHALL BE JOINED BY CLASS 125 ANSI B16.4 CAST IRON THREADED FITTINGS. ALL 1-1/2" AND
LARGER SHALL BE SCHEDULE 10 BLACK STEEL PER ASTM A-135/A-795 AND SHALL BE JOINED BY
MECHANICAL COUPLINGS.
3. ALL MATERIAL AND INSTALLATION TO BE IN ACCORDANCE WITH NFPA STANDARDS 13 & 24, 2016
EDITIONS AND THE LOCAL AUTHORITY.
4. PROVIDE HANGERS INCLUDING TRAPEZE HANGERS AS REQUIRED TO COMPLY WITH NFPA 13.
5. SPRINKLER SYSTEM FLOW AND TAMPER SWITCHES TO BE PROVIDED AND INSTALLED BY THE
SPRINKLER CONTRACTOR AND CONNECTED TO THE ALARM BY THE ELECTRICAL CONTRACTOR. ALL
SPRINKLER SYSTEM CONTROL 'VALVES AND WATERFLOW DETECTION DEVICES SHALL BE MONITORED
IN ACCORDANCE WITH NFPA 72.
6. FLUSH AND HYDROSTATICALLY TEST SYSTEM IN ACCORDANCE WITH NFPA STANDARDS 13 & 24.
7. SEAL ALL OPENINGS THROUGH FLOORS, CEILINGS, AND PARTITIONS TO RE—ESTABLISH IT'S FIRE
RATING. SEE THE ARCHITECTUAL. DRAWINGS FOR FIRE RATINGS.
8. SPRINKLER SYSTEM INSTALLATION MUST BE PERFORMED BY A CLASS 1 OR CLASS 2 FIRE
PROTECTION CONTRACTOR. THE CONTRACTOR SHALL OBTAIN ALL REQUIRED PERMITS AND PAY ALL
RELATED FEES.
9. ALL MATERIAL AND DEVICES TO BE U.L. LISTED FOR FIRE PROTECTION SERVICE.
10. PROVIDE AUX. DRAINS AS NECESSARY TO COMPLY WITH NFPA 13.
HANGER LOCATION DETAIL
PIPE SIZE
A
B*
C
1"
3'-0" MAX.
12'-0" MAX.
3" MIN.
1�/A"
4'-0" MAX.
12'-0" MAX.
3" MIN.
1%"-8"
5'-0" MAX.
15'-0" MAX.
3" MIN.
A B*
C
SPRINKLER HEAD
STEEL PIPE
.HANGER RING
* MAXIMUM HANGER SPACING FOR ST EL PIPE
SELF -DRILLING, SELF -
TAPPING METAL ANCHOR
EQUAL TO "SAMMY" -
SWDR 1" W/ RET. NUT
STRUCTURAL
FRAMING
1R
HANGER RING
Hanger Detail
LEGEND
O — EXISTING UPRIGHT SPRINKLER HEAD TO REMAIN AS INSTALLED.
"A" — DENOTES NEW PENDENT SPRINKLER HEAD TO BE ADDED BY COLEMAN FIRE.
— NEW SCH. 40 BLACK STEEL PIPE BY COLEMAN FIRE.
— — — — — — — — — EXISTING BLACK STEEL PIPE TO REMAIN AS INSTALLED.
AREA ON WORK
DAVIS & CLEATON ENGINEERING, INC.
101 SUNNYTOWN ROAD, SUITE 109
CASSELBERRY, FLORIDA 32707
PH. #407-539-2353 LIC. #35816
CERTIFICATE OF AUTORIZATION #8689
No Scale
N
W E
S
Key Plan
No Scale
OVERHEAD PIPING PLAN — FIRE PROTECTION