MIAMI-DADE COUNTY
PRODUCT CONTROL SECTION
11805 SW 26 Street, Room 208
DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) Miami, Florida 33175-2474
BOARD AND CODE ADMINISTRATION DIVISION T (786) 315-2590 F (786) 315-2599
NOTICE OF ACCEPTANCE (NOA) www.miamidade.gov/economy
PGT Industries, Inc.
1070 Technology Drive,
North Venice, FL 34275
SCOPE:
This NOA is being issued under the applicable rules and regulations governing the use of construction materials. The
documentation submitted has been reviewed and accepted by Miami -Dade County RER -Product Control Section to
be used in Miami Dade County and other areas where allowed by the Authority Having Jurisdiction (AHJ).
This NOA shall not be valid afterthe expiration date stated below. The Miami -Dade County Product Control Section
(In Miami Dade County) and/orthe AHJ (in areas other than Miami Dade County) reserve the right to have this
product or material tested for quality assurance purposes. If this product or material fails to perform in the accepted
manner, the manufacturer will incur the expense of such testing and the AHJ may immediately rev oke, in o dify, o r
suspend the use of such product or material within their jurisdiction. RER reserves the right to revoke this
acceptance, if it is determined by Miami -Dade County Product Control Section that this product or material fails to
meet the requirements of the applicable building code.
This product is approved as described herein and has been designed to comply with the Florida Building Code,
including the High Velocity Hurricane Zone.
DESCRIPTION: Series "5570/2770" Vinyl Sliding Glass Door (Reinforced) w/wo 90° & 135° corners-L.M.I.
APPROVAL DOCUMENT: Drawing No. MD-5570.0 Rev B, titled "Vinyl Sliding Glass Door NOA (LM)", sheets
1 through 21 of 21, prepared by manufacturer, dated 10/05/15 and last revised on 02/01/21, signed and sealed by
A. Lynn Miller, P.E., bearing the Miami -Dade County Product Control Revision stamp with the Notice of
Acceptance number and expiration date by the Miami -Dade County Product Control Section.
MISSILE IMPACT RATING: Large and Small Missile Impact Resistant
Limitations:
1. See table 1 (sheet 2) and table 2 (sheets forapplicable SGD unit sizes, design pressures, reinforcements types,
glass types, sill riser (see tables B-1 & B-2, sheets 7-8) and anchor layout sheets requirements in 11 thru 16.
2. Rigid White PVC, Tan (Non -white) Rigid PVC and Brown coated (Painted or laminated) white Rigid PVC to be
labeled per referenced NOA's requirements.
3. Egress operable doors must comply with min clear width or height per FBC requirement, as applicable.
4. Pocket walls under separate approval, to be reviewed by Building official
LABELING: Each unit shall bear a permanent label with the manufacturer's name or logo, city, state and series and
following statement: "Miami -Dade County Product Control Approved", noted herein.
RENEWAL of thisNOA shall be considered after a renewal application has been filed and there has been no
change in the applicable building code negative ly.affecting the performance of this product.
TERMINATION of this NOA will occur after the expiration date or if there has been a revision or change in the
materials, use, and/or manufacture of the product or process. Misuse of this NOA as an endorsement of any product,
for sales, advertising or any other purposes shall automatically terminate this NOA. Failure to comply with any
section of this NOA shall be cause for termination and removal of NOA.
ADVERTISEMENT: The NOA number preceded by the words Miami -Dade County, Florida, and followed by the
expiration date maybe displayed in advertising literature. If any portion of the NOA is displayed, then it shall be
done in its entirety.
INSPECTION: A copy of this entire NOA shall be provided to the user by the manufacturer or its distributors and
shall be available for inspection at the job site at the request of the Building Official.
This NOA revises & renews NOA#20-0429.05 and consists ofthis page 1 and evidence pages E-1, E-2, E-3, E-4,
E-5 & E-6 as well as approval document mentioned above.
The submitted documentation was reviewed by Ishaq L Chanda, P.E.
0�`02i-03
MIAMN•DAOE COUNTY Expiratio pri1 14, 2026
9 e //
ci(�G L�?hn�� Approva Date:March 25,2021
Page 1
PGT Industries, Inc.
NOTICE OF ACCEPTANCE: EVIDENCE SUBMITTED
1. Evidence submitted under previous NOA
A. DRAWINGS
1. Manufacturer's die drawings and sections.
(Submitted under NOA No. 11-0107.04)
2. Drawing No. MD-5570.0, titled "Vinyl Sliding Glass Door NOA (LM)", sheets 1
through 21 of 21, prepared by manufacturer, dated 10105115, with revision A dated
04/05/17, signed and sealed by A. Lynn Miller, P.E.
B. TESTS
1. Test report on 1) Uniform Static Air Pressure Test, per FBC, TAS 202-94
2) Large Missile Impact Test per FBC, TAS 201-94
3) Cyclic Wind Pressure Loading per FBC, TAS 203-94
along with marked -up drawings and installation diagram of vinyl sliding glass door, prepared
by Fenestration Testing Lab, Inc., Test Report No. FTL 8717, dated 12/07/15, signed and
sealed by Idalmis Ortega, P. E. (Test report revised on 02/15/16 and 02/24/16)
2. Test report on 1) Air Infiltration Test, per FBC, TAS 202-94
2) Uniform Static Air Pressure Test, per FBC, TAS 202-94
3) Water Resistance Test, per FBC, TAS 202-94.
4) Large Missile Impact Test per FBC, TAS 201-94
5) Cyclic Wind Pressure Loading per FBC, TAS 203-94
6) Forced Entry Test, per FBC, TAS 202-94
along with marked -up drawings and installation diagram of vinyl sliding glass door, prepared
by Fenestration Testing Lab, Inc., Test Report No. FTL 8546, dated 11/06/15, signed and
sealed by Idalmis Ortega, P. E. (Test report revised on 01/04/16 and 02/11/2016)
3. Test report on 1) Air Infiltration Test, per FBC, TAS 202-94
2) Uniform Static Air Pressure Test, per FBC, TAS 202-94
3) Water Resistance Test, per FBC, TAS 202-94
4) Large Missile Impact Test per FBC, TAS 201-94
5) Cyclic Wind Pressure Loading per FBC, TAS 203-94
6) Forced Entry Test, per FBC, TAS 202-94
along with marked -up drawings and installation diagram of vinyl sliding glass door, prepared
by Fenestration Testing Lab, Inc., Test Report No. FTL 8547, dated 12/04/15, signed and
sealed by Idalmis Ortega, P. E. (Test report revised on 02/15/16)
4. Test report on 1) Air Infiltration Test, per FBC, TAS 202-94
2) Uniform Static Air Pressure Test, per FBC, TAS 202-94
3) Water Resistance Test, per FBC, TAS 202-94
4) Large Missile Impact Test per FBC, TAS 201-94
5) Cyclic Wind Pressure Loading per FBC, TAS 203-94
6) Forced Entry Test, per FBC, TAS 202-94
along with marked -up drawings and installation diagram of vinyl sliding glass door, prepared
by Fenestration Testing Lab, Inc., Test Report No. FTL 8548, dated 12/04/15, signed and
sealed by Idalmis Ortega, P. E. (Test report revised on 01/04/16 and 02/11/16).
Ishaq I. Chanda, P.E.
Product Control Unit Supervisor
NOA No. 21-0205.03
Expiration Date: April 14, 2026
Approval Date: March 25, 2021
E -1
PGT Industries, Inc.
NOTICE OF ACCEPTANCE: EVIDENCE SUBMITTED
B. TESTS (continued)
5. Test report on 1) Air Infiltration Test, per FBC, TAS 202-94
2) Uniform Static Air Pressure Test, per FBC, TAS 202-94
3) Water Resistance Test, per FBC, TAS 202-94.
4) Large Missile Impact Test per FBC, TAS 201-94
5) Cyclic Wind Pressure Loading per FBC, TAS 203-94
6) Forced Entry Test, per FBC, TAS 202-94
along with marked -up drawings and installation diagram of vinyl sliding glass door, prepared
by Fenestration Testing Lab, Inc., Test Report No. FTL 8549, dated 11/06/15, signed and
sealed by Idalmis Ortega, P. E. (Test report revised on 12/04/15 and 02/11/16)
6. Test report on 1) Air Infiltration Test, per FBC, TAS 202-94
2) Uniform Static Air Pressure Test, per FBC, TAS 202-94
3) Water Resistance Test, per FBC, TAS 202-94.
4) Large Missile Impact Test per FBC, TAS 201-94
5) Cyclic Wind Pressure Loading per FBC, TAS 203-94
along with marked -up drawings and installation diagram of vinyl sliding glass door, prepared
by Fenestration Testing Lab, Inc., Test Report No. FTL 8552, dated 12/04/15, signed and
sealed by Idahnis Ortega, P. E. (Test report revised on 02/15/2016)
7. Test report on 1) Uniform Static Air Pressure Test, per FBC, TAS 202-94
2) Large Missile Impact Test per FBC, TAS 201-94
3) Cyclic Wind Pressure Loading per FBC, TAS 203-94
along with marked -up drawings and installation diagram of vinyl sliding glass door, prepared
by Fenestration Testing Lab, Inc., Test Report No. FTL 6638 (samples A-1 thru A-22), dated
11 /19/10, signed and sealed by Jorge A. Causo, P. E. (Submitted under NOA No.11-
0107.04)
8 Test report on 1) Air Infiltration Test, per FBC, TAS 202-94
2) Uniform Static Air Pressure Test, per FBC, TAS 202-94
3) Water Resistance Test, per FBC, TAS 202-94.
4) Large Missile Impact Test per FBC, TAS 201-94
5) Cyclic Wind Pressure Loading per FBC, TAS 203-94
6) Forced Entry Test, per FBC, TAS 202-94
along with marked -up drawings and installation diagram of vinyl sliding glass door, prepared
by Fenestration Testing Lab, Inc., Test Report No. FTL 6337 (samples A-1 thru A-5), dated
12/06/10, signed and sealed by Jorge A. Causo, P. E. (Submitted under NOA No.11-
0107.09)
C. CALCULATIONS
1. Anchor verification calculations and structural analysis, complying with FBC-2014,
prepared by PGT, dated 12/09/15and last revised on 02/15/16, signed and sealed by
Anthony L. Miller, P.E. (Submitted under NOA No. 15-1210. 01).
2. Glazing complies with ASTME-1300-09.
1 5t,-7 I. L�t�nek
Ishaq I. Chanda, P.E.
Product Control Unit Supervisor
NOA No. 21-0205.03
Expiration Date: April 14, 2026
Approval Date: March 25, 2021
E -2
PGT Industries, Inc.
NOTICE OF ACCEPTANCE: EVIDENCE SUBMITTED
D. QUALITY ASSURANCE
1. Miami Dade Department of Regulatory and Economic Resources (RER).
E. MATERIAL CERTIFICATIONS
1. Notice of Acceptance No.15-0528.14 issued to Vision Extrusion Limited for their
"White Rigid PVC Exterior Extrusions for Windows and Doors", dated 08/13/15,
expiring on 09/30/19.
2. Notice of Acceptance No.16-0920.08 issued to Vision Extrusion Limited for their "VE
1000 Tan 202 and lighter Shades (Non -White) Rigid PVC Exterior Extrusions for
Windows and Doors", dated 12/08/16, expiring on 12/29/21.
3. Notice of Acceptance No.15-0528.15 issued to Vision Extrusion Limited for their
"Brown Coated (Painted or Laminated) White Rigid PVC Exterior Extrusions for
Windows and Doors", dated 08/13/15, expiring on 09/30/19.
4. Notice of Acceptance No.16-0712.02 issued to ENERGI Fenestration Solutions USA,
Inc. for their "TAN 3040 and Lighter Shades (Non -White) Rigid PVC Exterior
Extrusions for Windows and Doors" dated 09/15/16, expiring on 02/04/21.
5. Notice of Acceptance No. 16-0712.04 issued to ENERGI Fenestration Solutions USA,
Inc. for their "Bronze and Lighter Shades of Cap Coated Rigid PVC Exterior
Extrusions for Windows and Doors" dated 09/15/16, expiring on 04/16/20.
6. Notice of Acceptance No.16-0712.03 issued to ENERGI Fenestration Solutions USA,
Inc. for their "White Rigid PVC Exterior Extrusions for Windows and Doors" dated
08/10/17, expiring on 02/28/18.
7. Test reports No(s). 10-002-792(A), 10-06-M0527, 535753-09, per ASTME-84,
ASTMD 1929 and ASTMD-635, issued by EXOVA to Vision Extrusion for cellulosic
composite material.
(Submitted under NOA No. 11-0107.04)
8. Notice of Acceptance No.14-0916.11 issued to Kuraray America., Inc. for their
"SentryGlas® (Clear and White) Interlayer", expiring on 07/04/18.
9. Notice of Acceptance No.16-1117.01 issued to Kuraray America, Inc. for their
"Trosifol® Ultraclear, Clear and Color PVB Interlayers", expiring on 07/08/19.
F. STATEMENTS
1. Statement letter of conformance with FBC-5th Edition (2014) and FBC-61h Edition
(2017), issued by manufacturer, dated 08/14/17, signed & sealed by Lynn Miller, P.E.
2. Statement letter of no financial interest, dated 04/18/17, issued by manufacturer, signed
& sealed by Lynn Miller, P.E.
3. Letter of lab compliance, part of the above test reports.
4. RER Test Proposal No. 17-0387, dated 05/05/17, signed by Ishaq Chanda, P.E.
G. OTHER
1. Notice of Acceptance No.15-1210.01, issued to PGT Industries, for their Series
"5570/2770" Vinyl Sliding Glass Door (Reinforced) — L.M.I.", expiring on 04/14/21.
15t".7 l
Z41iIJ4
Ishaq I. Chanda, P.E.
Product Control Unit Supervisor
NOA No. 21-0205.03
Expiration Date: April 14, 2026
Approval Date: March 25, 2021
E -3
PGT Industries, Inc.
NOTICE OF ACCEPTANCE: EVIDENCE SUBMITTED
2. Evidence Submitted under previous submittal
A. DRAWINGS
1. Drawing No. MD-5570.0 Rev B, titled "Vinyl Sliding Glass Door NOA (LM)", sheets
1 through 21 of 21, prepared by manufacturer, dated 10/05/15 and last revised on
04/22/20, signed and sealed by A. Lynn Miller, P.E.
B. TESTS
1. Test reports on: 1) Air Infiltration Test, per FBC, TAS 202-94
2) Uniform Static Air Pressure Test, Loading per FBC, TAS 202-94
3) Water Resistance Test, per FBC, TAS 202-94
4) Large Missile Impact Test per FBC, TAS 201-94
5) Cyclic Wind Pressure Loading per FBC, TAS 203-94
along with marked -up drawings and installation diagram of all PGT Industries, Inc.
representative units listed below and tested to qualify Dowsil 791 and Dowsil 983 silicones,
prepared by Fenestration Testing Laboratory, Inc., Test Reports No.:
FTL-7897, PGT PW5520 PVC Fixed Window (unit 6 in proposal), dated 09/03/14
FTL-20-2107.1, PGT SGD780 Aluminum Sliding Glass Door (unit 7 in proposal) FTL-20-
2107.2, PGT CA740 Alum. Outswing Casement Window (unit 8 in proposal) FTL-20-
2107.3, PGT PW7620A Aluminum Fixed Window (unit 9 in proposal) and FTL-20-2107.4,
PGT PW7620A Aluminum Fixed Window (unit 10 in proposal) dated 07/13/20, all signed
and sealed by Idalmis Ortega, P.E.
C. CALCULATIONS
1. Anchor verification calculations and structural analysis, complying with FBC 71h
Edition (2020), dated 04/22/20, prepared by manufacturer, signed and sealed by
Anthony Lynn Miller, P.E.
2. Glazing complies with ASTM E1300-04, -09, -12 and -16.
D. QUALITY ASSURANCE
Miami -Dade Department of Regulatory and Economic Resources (RER).
E. MATERIAL CERTIFICATIONS
1. Notice of Acceptance No.19-0305.02 issued to Kuraray America, Inc. for their
"Trosifol® Ultraclear, Clear, and Color PVB Glass Interlayers", expiring on
07/08/24.
2. Notice of Acceptance No.17-0808.02 issued to Kuraray America, Inc. for their
"SentryGlas® (Clear and White) Glass Interlayers", expiring on 07/04/23.
3. Notice of Acceptance No. 18-1106.10 issued to Vision Extrusions Limited for their
"Brown Coated (Painted or Laminated) White Rigid PVC Exterior Extrusions
for Windows and Doors", expiring on 09/30/24.
4. Notice of Acceptance No.18-1106.11 issued to Vision Extrusions Limited for their
series "VE 1000 Tan 202 and lighter shades (Non —White) Rigid Cellular PVC
Exterior Extrusions for Windows and Doors", expiring on 12/29/21. , st'G7 I L� �n
Ishaq I. Chanda, P.E.
Product Control Unit Supervisor
NOA No. 21-0205.03
Expiration Date: April 14, 2026
Approval Date: March 25, 2021
E -4
CGI Windows and Doors, Inc.
NOTICE OF ACCEPTANCE: EVIDENCE SUBMITTED
E. MATERIAL CERTIFICATIONS (continue)
5. Quanex Part Super Spacer Standard complying with ASTM C518 Thermal Conductivity
0.881 BTU -in/ hr.-ft2-OF, ASTM F 1249 WVTR-Pass, ASTM D3985 Oxygen —Pass, ASTM E
2190 I.G. Durability -No Fog -Pass. (Submitted under previous NOA No.15-0409.05)
6. Quanex Part Duraseal complying with ASTM C518 Thermal Conductivity 2.22 BTU -in/
hr.-ft2-OF, ASTM F 1249 WVTR-Pass, ASTM D 1434 Argon Permeance-Pass, ASTM E
2189 I.G. Durability -No Fog, ASTM E 546 Dew Point Development -20OF in 48 hrs.
(Submitted under NOA No. 15-0409.05).
7. Vision Extrusions, Ltd. Parts complying with PVC-AAMA 303-13, Voluntary Specification
for Rigid Polyvinyl Chloride (PVC) Exterior Profiles for Vision Extrusions, Ltd.-VEX-1 by
AAMA Fenestration Exterior Profile Certification Program. (Submitted under NOA No. 15-
0409.05)
8. Vision Extrusions, Ltd. Parts complying with PVC-AAMA 303-13.
(Submitted under NOA No.15-0409.05)
9. PVC-AAMA 303-13, Voluntary Specification for Rigid Polyvinyl Chloride (PVC) Exterior
Profiles for Vision Extrusions, Ltd.-VEX-1 by AAMA Fenestration Exterior Profile
Certification Program.
10. Notice of Acceptance No. 18-1217.14 issued to Energi Fenestration Solution, USA, Inc. for
their "Tan 3040 & light shade (non -white) White Rigid PVC Exterior Extrusions for
Windows and Doors", expiring on 02/04/21.
11. Notice of Acceptance No. 18-0122.02 issued to Energi Fenestration Solution, USA, Inc, for
their series "White Rigid PVC Exterior Extrusions for Windows and Doors", expiring on
02/28/23.
12. Notice of Acceptance No. 20-0203.03 issued to Energi Fenestration Solution, USA, Inc. for
their "Bronze & light shade cap coated White Rigid PVC Exterior Extrusions for
Windows and Doors", expiring on 04/16/25.
F. STATEMENTS
1. Statement letter of conformance to FBC 71h Edition (2020), dated 04/22/20, issued by
manufacturer, signed and sealed by Anthony Lynn Miller, P.E.
2. Statement letter of no financial interest and of independent, issued by manufacturer, dated
04/18/20, signed and sealed by Anthony Lynn Miller, P.E.
3. Private Labeling Agreement document between PGT, dated 03/30/15 and signed by all
involved parties.
G. OTHERS
1. This NOA revises NOA# 17-0420.06 (PVT w/CGI) and updates to FBC2020 (7th Edition),
expiring 04/21 /21.
2. RER Test proposals #19-1155 dated 01/10/20 approved by Ishaq I. Chanda, P.E, expiring
04/14/21.
Ishaq I. Chanda, P.E.
Product Control Unit Supervisor
NOA No. 21-0205.03
Expiration Date: April 14, 2026
Approval Date: March 25, 2021
E -5
PGT Industries, Inc.
NOTICE OF ACCEPTANCE: EVIDENCE SUBMITTED
3. New Evidence Submitted
A. DRAWINGS
1. Drawing No. MD-5570.0 Rev B, titled "Vinyl Sliding Glass Door NOA (LM)", sheets 1
through 21 of 21, prepared by manufacturer, dated 10/05/15 and last revised on 02/01/21,
signed and sealed by A. Lynn Miller, P.E.
Note: This revision consists replacement of same existing installation screw with flat head.
B. TESTS
1. None.
C. CALCULATIONS
1. None.
D. QUALITY ASSURANCE
1. Miami -Dade Department of Regulatory and Economic Resources (RER).
E. MATERIAL CERTIFICATIONS
1. Notice of Acceptance No.19-0305.02 issued to Kuraray America, Inc. for their
"Trosifol® Ultraclear, Clear, and Color PVB Glass Interlayers", expiring on 07/08/24.
2. Notice of Acceptance No.17-0808.02 issued to Kuraray America, Inc. for their
"SentryGlas® (Clear and White) Glass Interlayers", expiring on 07/04/23.
3. Notice of Acceptance No.18-1106.10 issued to Vision Extrusions Limited for their "Brown
Coated (Painted or Laminated) White Rigid PVC Exterior Extrusions for Windows
and Doors", expiring on 09/30/24.
4. Notice of Acceptance No.18-1106.11 issued to Vision Extrusions Limited for their series
"VE 1000 Tan 202 and lighter shades (Non —White) Rigid Cellular PVC Exterior
Extrusions for Windows and Doors", expiring on 12/29/21.
F. STATEMENTS
1. Statement letter of conformance to FBC 7" Edition (2020), dated 02/01/21, issued by
manufacturer, signed and sealed by Anthony Lynn Miller, P.E.
2. Private Labeling Agreement dated 03/08/21 between PGT Industries, Inc. and CGI
Windows and Doors Inc., signed by Dean M. Ruark, P.E., V.P. Engineering, on behalf of
both companies.
G. OTHERS
1. This NOA revises & renews NOA# 20-0429.05 (PLA w/CGI), expiring 04/14/26.
2. The current associated PLA CGI file #21-0205.01, expiring 04/14/26.
L4,q;l ,
Ishaq 1. Chanda, P.E.
Product Control Unit Supervisor
NOA No. 21-0205.03
Expiration Date: April 14, 2026
Approval Date: March 25, 2021
E -6
SERIES 5570 IMPACT RESISTANT SLIDING GLASS DOOR
GENERAL NOTES: INCLUDING POCKETS & 900/1350 CORNERS
1) GLAZING TYPE OPTIONS: SEE GLAZING DETAILS ON SHEET 10.
2) DESIGN PRESSURES:
A. NEGATIVE DESIGN LOADS BASED ON TESTED PRESSURE AND GLASS PER ASTM El300.
B. POSITIVE DESIGN LOADS BASED ON WATER TEST PRESSURE AND GLASS PER ASTM E1300.
C. DESIGN LOADS ARE BASED ON ALLOWABLE STRESS DESIGN, ASO.
3) ANCHORAGE: THE 33-1/3% STRESS INCREASE HAS NOT BEEN USED IN THE DESIGN OF THIS PRODUCT. MATERIALS,
INCLUDING BUT NOT LIMITED TO STEEL SCREWS, THAT COME INTO CONTACT WITH OTHER DISSIMILAR MATERIALS
SHALL MEET THE REQUIREMENTS OF THE FLORIDA BUILDING CODE (FBC).
4) SHUTTERS ARE NOT REQUIRED PER FBC REQUIREMENTS, AS APPLICABLE.
5) INSTALLATION SCREWS & FRAME SPLICES TO BE SEALED WITH NARROW JOINT SEALANT. OVERALL
SEALING/FLASHING STRATEGY FOR WATER RESISTANCE OF INSTALLATION SHALL BE DONE BY OTHERS AND IS
BEYOND THE SCOPE OF THESE INSTRUCTIONS.
6) REFERENCES (NOA'S): ELCO ULTRACON, DEWALT ULTRACON+, DEWALT/ELCO CRETEFLEX & AGGRE-GATOR
ANCHOR NOA'S, ENERGI FENESTRATION SOLUTIONS USA, INC. OR VISION EXTRUSION, LTD. WHITE RIGID PVC NOA, VE
1000 TAN 202 AND LIGHTER SHADES (NON -WHITE) RIGID PVC NOA AND BROWN COATED (PAINTED OR LAMINATED)
WHITE RIGID PVC NOA
REFERENCES (TEST REPORTS) FTL-6337, 6338,_8646-8649, 8652 & 8717, EXOVA-10-002-792(A) & 10-006-10231;
CAMBRIDGE 535753-09;
7) THIS PRODUCT HAS BEEN DESIGNED & TESTED TO COMPLY WITH THE REQUIREMENTS OF THE FBC, INCLUDING THE
HIGH VELOCITY HURRICANE ZONE (HVHZ). THE RIGID WHITE, BROWN & TAN PVC MANUFACTURED BY ENERGI
FENESTRATION SOLUTIONS USA, INC. OR VISION EXTRUSION, LTD. HAS BEEN TESTED TO COMPLY WITH THE FLORIDA
BUILDING CODE FOR PLASTICS, (COMPONENT REQUIREMENTS).
8) DOOR SIZES MUST BE VERIFIED FOR COMPLIANCE WITH EGRESS REQUIREMENTS OF THE FBC, AS APPLICABLE.
9) DRAWINGS DEPICT EXTERIOR -GLAZING, HOWEVER INTERIOR -GLAZING MAY BE SUBSTITUTED,
10) THE 5570 SERIES SLIDING GLASS DOOR MAY ALSO BE KNOWN AS THE 570/2770 SERIES.
ANCHOR NOTES:
1) FOR CONCRETE/CMU SUBSTRATE APPLICATIONS IN MIAMI-DADE COUNTY, USE ONLY MIAMI-DADE COUNTY
APPROVED ELCO ANCHORS. SEE TABLE A ON THIS SHEET FOR EMBEDMENT, EDGE DISTANCE AND SUBSTRATE
REQUIREMENTS.
2) FOR OTHER SUBSTRATE APPLICATIONS SEE TABLE A ON THIS SHEET.
3) WOOD BUCKS DEPICTED AS 1X ARE LESS THAN 1-1/2" THICK PROPERLY SECURED, 1X WOOD BUCKS ARE OPTIONAL
IF UNIT IS INSTALLED DIRECTLY TO SOLID CONCRETE OR CMU. WOOD BUCKS DEPICTED AS 2X ARE 1-1/2" THICK OR
GREATER. 1X AND 2X BUCKS (WHEN USED) SHALL BE DESIGNED TO PROPERLY TRANSFER LOADS TO THE
STRUCTURE. BUCK DESIGN AND INSTALLATION IS THE RESPONSIBILITY OF THE ENGINEER OR ARCHITECT OF RECORD
& TO BE REVIEWED BY THE BUILDING OFFICIAL.
4) METAL SUBSTRATE TO MEET MIN. STRENGTH AND THICKNESS REQUIREMENTS PER THE FBC AND TO BE REVIEWED
BY THE AUTHORITY HAVING JURISDICTION.
5) IF SILLa1S TIGHT TO SUBSTRATE, GROUT OR OTHER MATERIAL IS NOT REQUIRED. IF USED, NON -SHRINK,
NON-METALLIC GROUT, MAX. 114" THICK & 3400 PSI MIN., (DONE BY OTHERS) MUST FULLY SUPPORT THE ENTIRE
LENGTH OF THE SILL THAT IS NOT TIGHT TO THE SUBSTRATE, AND TRANSFER SHEAR LOAD TO SUBSTRATE. IF
SUBSTRATE IS WOOD, 30# FELT PAPER OR MASTIC IS REQUIRED BETWEEN THE GROUT AND WOOD SUBSTRATE, OR
AS APPROVED BY THE AUTHORITY HAVING JURISDICTION.
INSTRUCTIONS:
1) KNOWING THE REQUIRED DESIGN PRESSURE OF THE OPENING, THE ANCHOR REQUIREMENTS FOR THE
SLIDING GLASS DOORS MAY BE DETERMINED FROM DESIGN PRESSURE TABLES 1 OR 2, DEPENDING ON THE
GLASS/REINFORCEMENT.
2) LOCATE THE SLIDING GLASS DOOR SIZE ON THE TABLE, USING THE FRAME HEIGHT AND THE NOMINAL PANEL
WIDTH IF YOUR EXACT SIZE IS NOT LISTED, ROUND UP TO THE NEXT GREATER LISTED WIDTH AND/OR HEIGHT.
3) CHOOSE WHICH ANCHOR GROUP (A-D) IS MOST APPLICABLE. ANCHORS ARE DEFINED IN TABLE A, THIS
SHEET, ALONG WITH THE CORRESPONDING SUBSTRATE, MINIMUM EMBEDMENT AND MINIMUM EDGE DISTANCE.
4) FROM THE DESIGN PRESSURE TABLES (TABLES 1 OR 2), VERIFY THAT THE OPENING'S REQUIRED DESIGN
PRESSURE IS MET OR EXCEEDED. USE THE ANCHOR QUANTITIES SHOWN.
5) INSTALL AS PER THE GUIDELINES OF THIS SHEET -SET.
6) ADDITIONALLY, SEE THE EXAMPLE ON SHEET 9.
IMPACT RATING DESIGN PRESSURE RATING
RATED FOR LARGE & SMALL SEE TABLES 1, 2 & B1, B2
TABLE A:
MISSILE IMPACT RESISTANCE ON SHEETS 7 & 8
Group
Anchor
Subshata
Frame Member
Min. Edge
Distance
Min.
Embedment
A
#12, steel SMS (G5) or
410 S.S. SMS
(min. 11 threads'.)
P.T. Southem Pine, (SG=0.55)
Nead/SilUJamb/P-hook
9116"
1-3/8"
Aluminum, 6063-TS' (0.125" min.)
HeadlSili/Jamb/Pfiook
3/8"
1/8"
Sleel, A36', (O.O6d' min.)
Hea&SiIVJamb/P-hook
318"
0.060"
Steel Stud, A653 Gr. 33-, 0.071" min.
Head/SiIUJamb/P-hook
316'
0.071" (14 Ga.
1/4" Eloo Ultracon
P.T. Southern Pine, (SG=0.55)
Head/SiIVJamb/P-hook
1"
1-318"
1/4" DeWalI Uitracon+
114" Elco 410 S.S. CreteFlex
Jamb
1"
7318"
Head/SIII/Jamb1P-hook
1'
1-318"
B
#12, steel wood screw G5)
P.T. Southern Pine, SG=0,55
Head/SiWamb/P-hook
9/16"
1318"
1/4" Elco Ultreeon
Concrete, (min. 2.85 ksi)
P-hook
1"
1-318"
HeadlSill/Jamb
13/16"
1-wa..
Un routed CMU, (ASTM C-90)
Jamb/P-hook
1'•
1-1/4"
C
1/4" DeWalt Ilkracon+
Concrete, (min. 3 ksi)
Head/SiIVJamb
1-1/2'
1-3/8"
P-hook
1"
1-318"
Un routed CMU, ASTM G90)
Jamb/P-hook
T.
1-1/4"
114" DeWalt/Elco 410 S.S.
CreteFlex
Ungrouted CMU, (ASTM G90)
Jamb/P-hook
1.3/4"
1-1/4"
Concrete, (min. 3.35 ksi)
Head/SiIVJamb
1-3116'
13/4"
P-hook
1'
1-3/4"1/4"
DeWalt/Elco 18.8 S.S.
Aggre-Gator
Concrete, (min. 2.22 ksi)
HeadlSill/Jamb/P-hook
1-1/2"
1-318"
Ungrouted CMU, (ASTM G90)
Jamb/P-hook
2"
1-1/4"
P.T. Southern Pine, SG=0.55
Head/SilUJamb/P-hook
1"
13/8"
1/4" Elco Ultracon
Concrete, (min. 2.85 ksi)
Head/SiIVJamb/P-hook
2-1/7'
13/8"
Un muted CMU, (ASTM G90)
Jamb/P-hook
2-1/2"
1-1/4"
D
1/4" DeWait Ultracon+
Concrete, (min. 3 ksi)
Head/Sill/Jamb/P-hook
2-1/2"
1-318"
Un routed CMU, ASTM G90}
Jamb1P-hook
2-1/2"
1-1/4'
1/4' DeWaIVEIco 410 S.S.
CreteFlex
Concrete, (min. 3.35 ksi)
Head/SiIVJamb
2-112"
1-314"
P-hook
2-112'
1-3/8"
Un muted CMU, ASTM G90
Jamb/P-hook
2-1/2"
1-1/4"
vo OG rvrvv rnG mGIHL AU6JrrWIt. Mt1HL JUGSIHHIETQ
MEET MIN. STRENGTH AND THICKNESS REQUIREMENTS PER CURRENT FLORIDA
BUILDING CODE AND TO BE REVIEWED BY THE AUTHORITY HAVING JURISDICTION.
"UNGROUTED CMU" VALUES MAY BE USED FOR GROUTED CMU APPLICATIONS.
ALL ANCHOR HEAD TYPES APPLICABLE.
FOR THE MINIMUM STRENGTHS OF
ANCHORS AND SUBSTRATES, SEE TABLE
F, SHEET21.
CODES / STANDARDS USED:
• 2020 FLORIDA BUILDING CODE (FBC), 7TH EDITION
• ASTM E1300-09
• ANSI/AF&PA NDS-2018 FOR WOOD CONSTRUCTION
• ALUMINUM DESIGN MANUAL, ADM-2015
. AISI SIOD-16
• AISC 360-16
Mi
N. VENICE, FL 34275
(941)-480-1600
GENERAL NOTES.............1
EXAMPLE CONFIGS.......... 2
INSTALL DETAILS..............3-6
DP/ANCHOR TABLES ........
7-8
EXAMPLE ............................9
GLAZING DETAILS ......... ...10
ANCHOR LOCATIONS .......
11-16
PANEL TYPES...................17
EXTRUSIONS .....................18
ACCESSORIES..................19
SCREEN DETAILS.............20
PARTS LIST........................21
VINYL SLIDING GLASS DOOR NOA (LM)
GENERAL NOTES Is
C) REV. ANCH. HEAD SHEETS 3,4 & 6
IgI 10/05/l E
J ROSOWSKI
Jf 01/27/21
NTS Ill 1 OF 21 JA AI MD-5570.0
PRODUCT REVISED
as compiling with the Florida
Building Gode
.GA -No. 21-0205.03
Expiration Date 04/14/2026
LYNq/4�
* No�. 58705
•'•, 02/01 /21 •:
O STATE OF .• !(7`
S
!0NAL 1`Ia `
A.,LYNN MILLER, RE.
P.E.# 58705
MAX. UNIT WIDTH MAX. UNIT WIDTH MAX. UNIT WIDTH
I I MAX. UNIT WIDTH
NOM. PANEL WIDTH NOM. PANEL WIDTH NOM. PANEL WIDTH NOM. PANEL WIDTH
PER TABLES 1 & 2 a PER TABLES 1 & 2 PER TABL7�ES 1 & 2-, PER TABLES 1 —& 2
T 3 )� 1 3 )� MAX.. UNIT T )�
MAX. UNIT / I MAX. UNIT )� MAX. UNIT ) a )
HEIGHT )� HEIGHT �� ) HEIGHT 3 S )m HEIGHT )
PER TABLES 1& 2 2 PER TABLES 1& 2 / r o PER
1 Por�T I� � Po�ET i� PER 1 &2 � � � P� i� TABLES 1 &2 � � � � )g
IN
1-PANE4J J �- J
2-PANEL 3-PANEL CONFIGURATIONS 4-PANEL CONFIGURATIONS
CONFIGURATIONS a CONFIGURATIONS ta7a
MAX. UNIT WIDTH
MAX. UNIT WIDTH -I MAX. UNIT WIDTH NOM. PANEL WIDTH
NOM. PANEL WIDTH NOM. PANEL WIDTH 4 I PER TABLES 1 & 2
PER TABLES 1& 2 a PER TABLES 1& 2
) 3— ) MAX. UNIT 5
MAX. UNIT ' e ) MAX. UNIT a )w HEIGHT niE
HEIGHT a a ) HEIGHT a / ) TABLESRi & r / SHEET
X ET.
PER TABLES 1 & 2 / /
( )g PER TABLES 1 & 2 / / / / / )2 THIS
POCKET ) N / POST
J Jf_ J
5-PANEL CONFIGURATIONS 6-PANEL CONFIGURATIONS CORNER, TYP.
OUTSIDE CORNER SXOYM, INSIDE CORNER Slxl Wt
NOM. PANEL WIDTH
PER TABLES 1 & 2
MAX. UNIT
HEIGHT
PER TABLES 1 & 2
1
7-PANEL CONFIGURATIONS
CONFIGURATIONS NOTES:
NOM. PANT
PER TAB
MAX
HE
PER TAI
MAA. UNI I WIU I N
_L WIDTH
--ES�1 & 2�
°
UNIT
a
a
a
a
a
a
a
GHT
!LES 1& 2
8-PANEL
CONFIGURATIONS
"X" = OPERABLE PANEL
1) ALL CONFIGURATIONS SHOWN ARE ALSO AVAILABLE AS POCKET CONFIGURATIONS AT EITHER OR BOTH JAMB "O" = INOPERABLE PANEL
j LOCATIONS. EXAMPLE: 4-PANEL XXXX IN POCKET (p) CONFIGURATION CAN BE pXXXXp, pXXXX OR XXXXp. OXXX IN "p" = POCKET
POCKET CONFIGURATION CAN BE OXXXp.
2) 90° & 135° CORNER CONFIGURATIONS ARE A COMBINATION OF ANY 2 STRAIGHT CONFIGURATIONS.
3) POCKET WALL OR CAVITY IS NOT PART OF THIS APPROVAL AND IS TO BE DESIGNED BY OTHERS AND
REVIEWED BY THE AUTHORITY HAVING JURISDICTION. �—DETAIL LETTER
Ry.
4) FOR NOM. PANEL WIDTH, SEE TABLES 1 & 2. ® 1070 TECHNOLOGY DR
N. VENICE, FL 34275
5) MAX. ALLOWABLE FRAME SQUARE FOOTAGE = 472.656 FT' L—SHEET NUMBER (941)-480-1600
11 REGISTRATION 029M
PRODUCT REVISED
as comp)ying with the Florida
Building Code
NOA-No. 21.0205.03
-1
Expiration Date 04/14/2026
By IsI-71.L,
)d
—Miami-Bade Produet Control
_ J
DLO WIDTH = NOM. PANEL WIDTH - 8-9/16"
NOM. PANEL WIDTH = PANEL WIDTH + 1-3/16"
DLO HEIGHT= DOOR HEIGHT- 11-1/16"
PANEL HEIGHT= DOOR HEIGHT - 2-1/2"
1111 I I I i i
��•``�w- LYNA( ��''•,
��\ ��O •.10EN....
VINYL SLIDING GLASS DOOR NOA (LM)
8 10/05/16
Z .* No. 58705
02/01 /21 : • �'
iO,�' • S ATE OF
IiIIIl110% `
LYNN MILLER, P.E.
P.E.# Sf1705
EXAMPLE CONFIGURATIONS IA- J ROSOWSKI
C) NO CHANGES THIS SHEET.
01/27/21
-- -
3GD-5570
NTS
2 OF 21
g$
MD-5570.0
g