Certificate of Authorization#32455
353 Christian Street, Unit#13
Oxford, CT 06478
(203) 262-9245
ENGINEER EVALUATE TEST CONSULT
EVALUATION REPORT
ICP Adhesives and Sealants,Inc. Evaluation Report 02768.02.06-R9
12505 NW 44th Street FL6276-119
Coral Springs, FL 33065 Date of Issuance:03/21/2006
(888)774-1419 Revision 9:09/29/2020
SCOPE:
This Evaluation Report is issued under Rule 611320-3 and the applicable rules and regulations governing the use of
construction materials in the State of Florida. The documentation submitted has been reviewed by Robert Nieminen,
P.E. for use of the product under the Florida Building Code. The products described herein have been evaluated for
compliance with the 71h Edition (2020) Florida Building Code sections noted herein.
DESCRIPTION: POLYSETO RTA-1
LABELING: Labelingshall be in accordance with the requirements of the Accredited Quality Assurance Agency noted
q Q Y g Y
herein.
CONTINUED COMPLIANCE: This Evaluation Report is valid until such time as the named product(s)changes,the referenced
Quality Assurance or production facility location(s) changes, or Code provisions that relate to the product(s) change.
Acceptance of our Evaluation Reports by the named client constitutes agreement to notify NEMO ETC, LLC of any
changes to the product(s), the Quality Assurance or the production facility location(s). NEMO ETC, LLC requires a
complete review of its Evaluation Report relative to updated Code requirements with each Code Cycle.
ADVERTISEMENT: The Florida Product Approval Number (FL#) preceded by the words "NEMO Ietc. Evaluated" may be
displayed in advertising literature. If any portion of the Evaluation Report is displayed, then it shall be done in its
entirety.
INSPECTION: Upon request, a copy of this entire Evaluation Report shall be provided to the user by the manufacturer or
its distributors and shall be available for inspection at the job site at the request of the Building Official.
This Evaluation Report consists of pages 1 through 9.
Prepared by:
-v-
Robert J.M.Nieminen,P.E. The facsimile seal appearing was authorized by Robert
•%T ..:: ...;..
S�': —•^'ti:,.•' Nieminen,P.E.on 09/29/2020. This does not serve as an
Florida Registration No.59166,Florida DCA ANE1983 c......'`«
9 electronically signed document.
CERTIFICATION OF INDEPENDENCE:
1. NEMO ETC, LLC does not have, nor does it intend to acquire or will it acquire, a financial interest in any company manufacturing or
distributing products it evaluates.
2. NEMO ETC,LLC is not owned,operated or controlled by any company manufacturing or distributing products it evaluates.
3. Robert Nieminen, P.E.does not have nor will acquire, a financial interest in any company manufacturing or distributing products for
which the evaluation reports are being issued.
4. Robert Nieminen, P.E.does not have, nor will acquire,a financial interest in any other entity involved in the approval process of the
product.
5. This is a building code evaluation. Neither NEMO ETC,LLC nor Robert Nieminen,P.E.are,in any way,the Designer of Record for any
project on which this Evaluation Report,or previous versions thereof, is/was used for permitting or design guidance unless retained
specifically for that purpose.
ETC,LLC
F
►► E dorT
ONEMOletc.
ROOFING COMPONENT EVALUATION:
Product Category: Roofing
Sub-Category: Roof Tile Adhesive
Compliance Statement: POLYSET® RTA-1, as produced by ICP Adhesives and Sealants, Inc., has demonstrated
compliance with the following sections of the 7th Edition(2020)Florida Building Code through testing in accordance
with the Standards set forth herein. Compliance is subject to the Installation Requirements and Limitations /
Conditions of Use set forth herein.
STANDARDS:2.
Sections Pro a Standard Year
1504.2.1.1 Overturning resistance SSTD 11 1997
3. REFERENCES:
Enti Examination Reference Date
ERD(TST6049) Static Uplift—SSTD 11 E42730.08.13 08/23/2013
ERD(TST6049) Static Uplift—SSTD 11 ECM-SC6795.12.14-2 02/27/2015
Miami-Dade(CER 1592) HVHZ compliance 18-0131.02 07/12/2018
NEMO(TST6049) Static Uplift—SSTD 11 4L-ICP-18-001.05.18-1 05/1S/2018
NEMO(TST6049) Tensile Adhesion(underlayments) 4S-ICP-18-001.07.18-R1 08/01/2018
NEMO(TST6049) Static Uplift—SSTD 11 4S-ICP-18-001.10.18-1 10/04/2018
NEMO(TST6049) Static Uplift—SSTD 11 4S-ICP-18-001.10.18-3 10/04/2018
NEMO(TST6049) Tensile Adhesion(ridge metal) 4i-ECM-20-SSCRT-01 09/29/2020
PRI(TST5878) Static Uplift—SSTD 11 PFI-006-02-01 05/09/2005
PRI(TST5878) Static Uplift—SSTD 11 PFI-008-02-03 12/14/2005
PRI(TST5878) Static Uplift—SSTD 11 PFI-008-02-04 12/14/2005
PRI(TST5878) Static Uplift—SSTD 11 FOP-009-02-05 Rev2 06/01/2015
IAPMO LIES(QUA10547) Quality Assurance Service Confirmation 08/17/2020
4. ODDESCRIPTION:
4.1 POLYSET® RTA-1 is a single component polyurethane foam roof tile adhesive distributed in factory, pre-mixed
canisters.
S. LIMITATIONS:
5.1 This is a building code evaluation. Neither NEMO ETC, LLC nor Robert Nieminen, P.E.are, in any way,the Designer of
Record for any project on which this Evaluation Report, or previous versions thereof, is/was used for permitting or
design guidance unless retained specifically for that purpose.
5.2 This Evaluation Report is not for use in FBC High Velocity Hurricane Zone jurisdictions(i.e., Broward and Miami-Dade
Counties).
5.3 This Evaluation Report pertains to above-deck roof components. Roof decks and structural members shall be in
accordance with FBC requirements to the satisfaction of the Authority Having Jurisdiction.
5.4 This Evaluation Report does not include evaluation of fire classification. Refer to FBC 1505 or R902 for requirements
and limitations regarding roof assembly fire classification. Refer to FBC 2603 for requirements and limitations
concerning the use of foam plastic insulation.
5.5 This Evaluation Report does not include evaluation of roof edge termination.
5.6 POLYSET®RTA-1 may be used with flat,low and high profile tiles having a current Florida Statewide Product Approval
or approved on a local-level by the Authority Having Jurisdiction.
NEMO ETC,LLC Evaluation Report 02768.02.06-R9
Certificate of Authorization#32455 7TH EDITION(2020)FBC NON-HVHZ EVALUATION FL6276-R9
Polyset•RTA-1 Revision 9:09/29/2020
Page 2 of 9
ONEMOletc.
5.7 Field tiles,meeting the limitations of FBC 1609.5.3 and installed using POLYSET®RTA-1 are limited to projects having
an Aerodynamic Uplift Moment (Ma), determined in accordance with Table 2HB, 2HC, 2HD, 2GB, 2GC or 2GD of
FRSA/TRI Florida High Wind Concrete and Clay Roof Tile Installation Manual,Sixth Edition or FBC 1609.5.3,not greater
than the following Allowable Overturning Moment values. Refer to Section 10 and ICP Adhesives and Sealants,Inc.
published installation instructions for Adhesive Paddy Placement details.
TABLE 1:FIELD TILES IN POLYSET•RTA-1
ALLOWABLE OVERTURNING MOMENT PERFORMANCE DATA
MARGINS OF SAFETYALREADYAPPLIED)
Tile(FBC 1609.5.3) Adhesive Paddy Placement(Section 10) Allowable
Overturning
Type Profile Placement Paddy Details Moment
Detail (ft-lbf)
Clay or Interdependent:Two(2)ribbons,11 grams each
Concrete Flat/Low #1 Ensure minimum 8 inz contact area to underside of tile,and minimum 10 inz 50
contact area at the tile head lap
Interdependent:Two(2)ribbons,11 grams each
Concrete Medium #2 Ensure minimum 6 inz contact area to underside of tile,and minimum 10 inz 44
contact area at the tile head lap
Clay High Interdependent:Two(2)ribbons: 36
• 22 grams tail-to-substrate
#3 . 11 grams at head-lap
Ensure minimum 12 inz contact area to underside of tile,and minimum 18
Concrete High inz contact area at the tile head lap 33
Independent:
Pan Tile to Underlayment: Two(2)-7-inch long x-6 gram oblong shaped
beads on underlayment,side-by-side,where the center of the pan tile
contacts the deck starting-2 to 3-inches from the eave end of the pan tile
ClayCap&Pan #4 Cap Tile to Pan Tile:One(1)"7-inch long x-6 gram oblong shaped bead at 93
(Barrel) each long edge of the cap tile,%to 1-inch from each edge,starting"2 to 3-
inches from the eave end working towards the ridge. Turn cap tile over and
install onto pan,butting the second course pan tile eave end on
underlayment,side-by-side,where the center of the pan tile contacts the
deck starting-2 to 3-inches from the eave end of the pan tile.
Interdependent:Two(2)#8 wood screws at tail&one(1)ribbon, 11 gram at
Concrete Clay Low/Flat #5 headlap 73
Ensure minimum 10 inz contact area at the tile head lap
Interdependent:Two(2)#8 wood screws at tail&one(1)ribbon,11 gram at
Concrete Medium #6 headlap 65
Ensure minimum 10 inz contact area at the tile head lap
Clay High Interdependent:Two(2)#8 wood screws at tail&one(1)ribbon, 11 gram at 44
#7 headlap
Concrete High Ensure minimum 18 inz contact area at the tile head lap 63
5.7.1 Data in Table 1 relates to installation over a TWO-PLY underlayment system,as detailed in the FRSA/TRI Florida High
Wind Concrete and Clay Roof Tile Installation Manual,Sixth Edition, using a hot-asphalt-applied,ASTM D6380,Class
M cap sheet(commonly called a'30/90 system').
Alternate underlayment systems are those having a current Florida Statewide Product Approval and/or approved on
a local-level by the Authority Having Jurisdiction, listed specifically for use with POLYSET®RTA-1.
NEMO ETC,LLC Evaluation Report 02768.02.06-R9
Certificate of Authorization#32455 7TH EDITION(2020)FBC NON-HVHZ EVALUATION FL6276-R9
Polyset•RTA-1 Revision 9:09/29/2020
Page 3 of 9
ONEMOletc.
5.7.2 Tile roof systems using tile types or profiles other than those listed above acquiring acceptance for use with POLYSET®
RTA-1 shall be tested in accordance with SSTD it or Testing Application Standard TAS 101. For the interdependent
multi-paddy method, an additional 2-to-1 margin of safety above that specified in SSTD 11 or Testing Application
Standard TAS 101 shall be applied in determining the'allowable overturning moment'.
5.8 Hip and ridge tiles using POLYSET® RTA-1 are limited to projects having hip/ridge design pressure requirements,
determined in accordance with Table 1A of FRSA/TRI Florida High Wind Concrete and Clay Roof Tile Installation
Manual,Sixth Edition or the applicable design pressure determined in accordance with FBC 1609 or FBC Residential
Chapter 3, not greater than the following values. Refer to ICP Adhesives and Sealants, Inc. published installation
instructions for Adhesive Paddy Placement details.
TABLE 2:Hip&RIDGE TILES IN POLYSETO RTA-1
ALLOWABLE UPLIFT RESISTANCE PERFORMANCE DATA
(MARGINS OF SAFETY ALREADY APPLIED)
Detail Allowable
Tile Substrate (Section Attachment Details Design
10) Pressure(psf)
Clay or Interdependent:
Concrete 2x PT ridge board #8 Head:One(1)#10 x 2Y2"screw; 187
Overlap:1x6-inch x-10.5 gram
East Coast Metals"Trim Lock""(FBC FL5394): Interdependent:
Clay or aluminum or On Trim-Lock'"metal:One(1)-7-
Concrete East Coast Metals"Trim Lock'"Plus"(FBC inch long x-10 gram oblong shaped 93
FL5394):aluminum,Galvalume®or stainless #9 paddy centered on metal.
steel At Tile Headlap:One(1)-7-inch long
Clay or East Coast Metals"Trim Lock""(FBC FL5394): x-10 gram oblong shaped bead at 110
Concrete Galvalume°or stainless steel tile headlap.
INSTALLATION:6.
6.1 POLYSET®RTA-1 and the tile roof assembly shall be installed in accordance with the manufacturers'current published
instructions,but not less than the requirements of FBC 1507.3 and the FRSA/TRI Florida High Wind Concrete and Clay
Roof Tile Installation Manual,Sixth Edition,subject to the limitations in Section 5.
6.1.1 Installation of POLYSET® RTA-1 shall be performed by applicators that hold a valid Qualified Applicator Card
presented by ICP Adhesives and Sealants,Inc.
6.2 Underlayment shall hold current Florida Product Approval for use with tile roofing systems. The underlayment
Product Approval shall specify allowable use with POLYSET®RTA-1. The underlayment Product Approval shall specify
attachment methods for the underlayment system to resist wind uplift design loads in accordance with Table 1A of
FRSA/TRI Florida High Wind Concrete and Clay Roof Tile Installation Manual, Sixth Edition or the critical (highest)
design pressure determined in accordance with FBC 1609 or FBC Residential Chapter 3.
6.3 Hip and ridge boards or hip/ridge metal shall be installed in accordance with the FRSA/TRI Florida High Wind Concrete
and Clay Roof Tile Installation Manual,Sixth Edition. Proprietary hip and ridge metal shall be installed in accordance
with the manufacturer's Florida Product Approval.
REQUIREMENTS:7. BUILDING PERMIT
As required by the Building Official or Authority Having Jurisdiction to properly evaluate the installation of this
product.
8. MANUFACTURING PLANTS:
Norton,OH
QUALITY9.
IAPMO UES-QUA10547; (909)223-4422;barry.lohnson@uniform-es.org
NEMO ETC,LLC Evaluation Report 02768.02.06-R9
Certificate of Authorization#32455 7TH EDITION(2020)FBC NON-HVH2 EVALUATION FL6276-R9
Polyset•RTA-1 Revision 9:09/29/2020
Page 4 of 9
ONEMO etc.
PADDY10.
10.1 Detail#1: Flat Profile Tile:
Strengthening Ribs
� 1
Ur.9�i.rfe�.n n�� ` �y Paddy on Deck Dispensed
1 ` Horizontally at Tile Course Line
r Pad on Top of Tile
Dispensed Horizontally
at Head Lap
Underlock
Eave Course Line
Overlock
Eave Closure
Start Eave Course Paddies
at Tile Course Line
10.2 Detail#2:LOW/Medium Profile Tile:
Pan of Tile
Paddy on Top of the Tile
Dispensed Horizontally
at Head Lap
(� \ Underlock
Y Overlock
Eave Course Line
Eave Closure D
Start Eave Course Paddies
at Tile Course Line
NEMO ETC,LLC Evaluation Report 02768.02.06-R9
Certificate of Authorization#32455 7-EDITION(2020)FBC NON-HVHZ EVALUATION FL6276-R9
Polyset®RTA-1 Revision 9:09/29/2020
Page 5 of 9
ONEMOletc.
10.3 Detail#3:High Profile Tile:
Pon of Tile
Paddy on Top of Tile
Dispensed Horizontally
at Head Lap
{
Eave Course
Line
Eave Closure
Start Paddy Undemeath Pan
Portion of Tile at
High Profile Tile Course Line
10.4 Detail#4: Two Piece Barrel(Cap&Pan)Tile:
One(t)-7"Paddy
on each side under
cover tiles(Detail)
Two(2)-7'Oblong
paddies side by
side under pan tiles
One(t)-7"Paddy
on each side under
cover tiles
Eave Course
Line
Eave Closure Two(2)-10'Oblong
paddies side by side
under pan tiles
2-Piece Barrel Profile leave course only)
NEMO ETC,LLC Evaluation Report 02768.02.06-119
Certificate of Authorization U32455 7-EDITION(2020)FBC NON-HVHZ EVALUATION FL6276-119
Polyset•RTA-1 Revision 9:09/29/2020
Page 6 of 9
ONEMOjetc.
10.5 Detail#5: Low/Flat Profile Tile;Hybrid System:
Strengthening Ribs
Two(21=8
Screws in Factory
Hole Locations
Underside of Tile
Pad on Top of Tile
Dispensed Honzontally
at Head Lap
Undenock
0
Eave Course
Line
Overlock
Eave CIOSaIe
Flat Profile
10.6 Detail#6: Medium Profile Tile;Hybrid System:
Pan of Tile
Two(2)=8 Screws in
Factory Hole Locations
Paddy on Top of the The
Dispensed Horizontally
at Head Lap
Undedock
Eave Course Overlock
Line
Eave Closure
Low Profile
NEW ETC,LLC Evaluation Report 02768.02.06-R9
Certificate of Authorization#32455 7TH EDITION(2020)FBC NON-HVHZ EVALUATION F1.6276-119
Polyset®RTA-1 Revision 9:09/29/I020
Page 7 of 9
ONEMOjetc.
10.7 Detail#7: High Profile Tile;Hybrid System:
Pen of Tile
Two(2)Screws in
Factory Hole Locations
Paddy an Top of Tile
Dispensed Horizontally
of Head Lop
Eave Course
Line
Eave Closure
Hlgn Profile
10.8 Detail#8: Hip and Ridge(interdependent with screw):
l�
1(
1"•X•6"•Bead•of•ICP-
r Adhesives•
Polyset°RTA-1•roof-
tile•adhesive••T•.
#10•x•2-1/2"•Screw•
Code•Approved-
Fastener
Adhere•starter-
tile-%vith•a•2"•x•7"-
Paddyplaced3"-
down•from•head
of•tile¶
NEMO ETC,LLC Evaluation Report 02768.02.06-R9
Certificate of Authorization#32455 7TH EDITION(2020)FBC NON-HVHZ EVALUATION FL6276-119
Polyset°RTA-1 Revision 9:09/29/2020
Page 8 of 9
ONEMOletc.
10.9 Detail#9: Hip and Ridge(interdependent placement):
7" Oblong Paddy
7" Oblong Paddy
END OF EVALUATION REPORT-
NEMO ETC,LLC Evaluation Report 02768.02.06-119
Certificate cf Authorization#32455 7TH EDITION(2020)FBC NON-HVH2 EVALUATION FL6276-R9
Polyset"RTA-1 Revision 9:09/29/2020
Page 9 of 9