HomeMy WebLinkAboutEVALUATION REPORT NEMO I etc. Certificate of Authorization#32455 353 Christian Street, Unit#13 Oxford, CT 06478 (203) 262-9245 ENGINEER EVALUATE TEST CONSULT EVALUATION REPORT ICP Adhesives and Sealants,Inc. Evaluation Report 02768.02.06-R9 12505 NW 44th Street FL6276-119 Coral Springs, FL 33065 Date of Issuance:03/21/2006 (888)774-1419 Revision 9:09/29/2020 SCOPE: This Evaluation Report is issued under Rule 611320-3 and the applicable rules and regulations governing the use of construction materials in the State of Florida. The documentation submitted has been reviewed by Robert Nieminen, P.E. for use of the product under the Florida Building Code. The products described herein have been evaluated for compliance with the 71h Edition (2020) Florida Building Code sections noted herein. DESCRIPTION: POLYSETO RTA-1 LABELING: Labelingshall be in accordance with the requirements of the Accredited Quality Assurance Agency noted q Q Y g Y herein. CONTINUED COMPLIANCE: This Evaluation Report is valid until such time as the named product(s)changes,the referenced Quality Assurance or production facility location(s) changes, or Code provisions that relate to the product(s) change. Acceptance of our Evaluation Reports by the named client constitutes agreement to notify NEMO ETC, LLC of any changes to the product(s), the Quality Assurance or the production facility location(s). NEMO ETC, LLC requires a complete review of its Evaluation Report relative to updated Code requirements with each Code Cycle. ADVERTISEMENT: The Florida Product Approval Number (FL#) preceded by the words "NEMO Ietc. Evaluated" may be displayed in advertising literature. If any portion of the Evaluation Report is displayed, then it shall be done in its entirety. INSPECTION: Upon request, a copy of this entire Evaluation Report shall be provided to the user by the manufacturer or its distributors and shall be available for inspection at the job site at the request of the Building Official. This Evaluation Report consists of pages 1 through 9. Prepared by: -v- Robert J.M.Nieminen,P.E. The facsimile seal appearing was authorized by Robert •%T ..:: ...;.. S�': —•^'ti:,.•' Nieminen,P.E.on 09/29/2020. This does not serve as an Florida Registration No.59166,Florida DCA ANE1983 c......'`« 9 electronically signed document. CERTIFICATION OF INDEPENDENCE: 1. NEMO ETC, LLC does not have, nor does it intend to acquire or will it acquire, a financial interest in any company manufacturing or distributing products it evaluates. 2. NEMO ETC,LLC is not owned,operated or controlled by any company manufacturing or distributing products it evaluates. 3. Robert Nieminen, P.E.does not have nor will acquire, a financial interest in any company manufacturing or distributing products for which the evaluation reports are being issued. 4. Robert Nieminen, P.E.does not have, nor will acquire,a financial interest in any other entity involved in the approval process of the product. 5. This is a building code evaluation. Neither NEMO ETC,LLC nor Robert Nieminen,P.E.are,in any way,the Designer of Record for any project on which this Evaluation Report,or previous versions thereof, is/was used for permitting or design guidance unless retained specifically for that purpose. ETC,LLC F ►► E dorT ONEMOletc. ROOFING COMPONENT EVALUATION: Product Category: Roofing Sub-Category: Roof Tile Adhesive Compliance Statement: POLYSET® RTA-1, as produced by ICP Adhesives and Sealants, Inc., has demonstrated compliance with the following sections of the 7th Edition(2020)Florida Building Code through testing in accordance with the Standards set forth herein. Compliance is subject to the Installation Requirements and Limitations / Conditions of Use set forth herein. STANDARDS:2. Sections Pro a Standard Year 1504.2.1.1 Overturning resistance SSTD 11 1997 3. REFERENCES: Enti Examination Reference Date ERD(TST6049) Static Uplift—SSTD 11 E42730.08.13 08/23/2013 ERD(TST6049) Static Uplift—SSTD 11 ECM-SC6795.12.14-2 02/27/2015 Miami-Dade(CER 1592) HVHZ compliance 18-0131.02 07/12/2018 NEMO(TST6049) Static Uplift—SSTD 11 4L-ICP-18-001.05.18-1 05/1S/2018 NEMO(TST6049) Tensile Adhesion(underlayments) 4S-ICP-18-001.07.18-R1 08/01/2018 NEMO(TST6049) Static Uplift—SSTD 11 4S-ICP-18-001.10.18-1 10/04/2018 NEMO(TST6049) Static Uplift—SSTD 11 4S-ICP-18-001.10.18-3 10/04/2018 NEMO(TST6049) Tensile Adhesion(ridge metal) 4i-ECM-20-SSCRT-01 09/29/2020 PRI(TST5878) Static Uplift—SSTD 11 PFI-006-02-01 05/09/2005 PRI(TST5878) Static Uplift—SSTD 11 PFI-008-02-03 12/14/2005 PRI(TST5878) Static Uplift—SSTD 11 PFI-008-02-04 12/14/2005 PRI(TST5878) Static Uplift—SSTD 11 FOP-009-02-05 Rev2 06/01/2015 IAPMO LIES(QUA10547) Quality Assurance Service Confirmation 08/17/2020 4. ODDESCRIPTION: 4.1 POLYSET® RTA-1 is a single component polyurethane foam roof tile adhesive distributed in factory, pre-mixed canisters. S. LIMITATIONS: 5.1 This is a building code evaluation. Neither NEMO ETC, LLC nor Robert Nieminen, P.E.are, in any way,the Designer of Record for any project on which this Evaluation Report, or previous versions thereof, is/was used for permitting or design guidance unless retained specifically for that purpose. 5.2 This Evaluation Report is not for use in FBC High Velocity Hurricane Zone jurisdictions(i.e., Broward and Miami-Dade Counties). 5.3 This Evaluation Report pertains to above-deck roof components. Roof decks and structural members shall be in accordance with FBC requirements to the satisfaction of the Authority Having Jurisdiction. 5.4 This Evaluation Report does not include evaluation of fire classification. Refer to FBC 1505 or R902 for requirements and limitations regarding roof assembly fire classification. Refer to FBC 2603 for requirements and limitations concerning the use of foam plastic insulation. 5.5 This Evaluation Report does not include evaluation of roof edge termination. 5.6 POLYSET®RTA-1 may be used with flat,low and high profile tiles having a current Florida Statewide Product Approval or approved on a local-level by the Authority Having Jurisdiction. NEMO ETC,LLC Evaluation Report 02768.02.06-R9 Certificate of Authorization#32455 7TH EDITION(2020)FBC NON-HVHZ EVALUATION FL6276-R9 Polyset•RTA-1 Revision 9:09/29/2020 Page 2 of 9 ONEMOletc. 5.7 Field tiles,meeting the limitations of FBC 1609.5.3 and installed using POLYSET®RTA-1 are limited to projects having an Aerodynamic Uplift Moment (Ma), determined in accordance with Table 2HB, 2HC, 2HD, 2GB, 2GC or 2GD of FRSA/TRI Florida High Wind Concrete and Clay Roof Tile Installation Manual,Sixth Edition or FBC 1609.5.3,not greater than the following Allowable Overturning Moment values. Refer to Section 10 and ICP Adhesives and Sealants,Inc. published installation instructions for Adhesive Paddy Placement details. TABLE 1:FIELD TILES IN POLYSET•RTA-1 ALLOWABLE OVERTURNING MOMENT PERFORMANCE DATA MARGINS OF SAFETYALREADYAPPLIED) Tile(FBC 1609.5.3) Adhesive Paddy Placement(Section 10) Allowable Overturning Type Profile Placement Paddy Details Moment Detail (ft-lbf) Clay or Interdependent:Two(2)ribbons,11 grams each Concrete Flat/Low #1 Ensure minimum 8 inz contact area to underside of tile,and minimum 10 inz 50 contact area at the tile head lap Interdependent:Two(2)ribbons,11 grams each Concrete Medium #2 Ensure minimum 6 inz contact area to underside of tile,and minimum 10 inz 44 contact area at the tile head lap Clay High Interdependent:Two(2)ribbons: 36 • 22 grams tail-to-substrate #3 . 11 grams at head-lap Ensure minimum 12 inz contact area to underside of tile,and minimum 18 Concrete High inz contact area at the tile head lap 33 Independent: Pan Tile to Underlayment: Two(2)-7-inch long x-6 gram oblong shaped beads on underlayment,side-by-side,where the center of the pan tile contacts the deck starting-2 to 3-inches from the eave end of the pan tile ClayCap&Pan #4 Cap Tile to Pan Tile:One(1)"7-inch long x-6 gram oblong shaped bead at 93 (Barrel) each long edge of the cap tile,%to 1-inch from each edge,starting"2 to 3- inches from the eave end working towards the ridge. Turn cap tile over and install onto pan,butting the second course pan tile eave end on underlayment,side-by-side,where the center of the pan tile contacts the deck starting-2 to 3-inches from the eave end of the pan tile. Interdependent:Two(2)#8 wood screws at tail&one(1)ribbon, 11 gram at Concrete Clay Low/Flat #5 headlap 73 Ensure minimum 10 inz contact area at the tile head lap Interdependent:Two(2)#8 wood screws at tail&one(1)ribbon,11 gram at Concrete Medium #6 headlap 65 Ensure minimum 10 inz contact area at the tile head lap Clay High Interdependent:Two(2)#8 wood screws at tail&one(1)ribbon, 11 gram at 44 #7 headlap Concrete High Ensure minimum 18 inz contact area at the tile head lap 63 5.7.1 Data in Table 1 relates to installation over a TWO-PLY underlayment system,as detailed in the FRSA/TRI Florida High Wind Concrete and Clay Roof Tile Installation Manual,Sixth Edition, using a hot-asphalt-applied,ASTM D6380,Class M cap sheet(commonly called a'30/90 system'). Alternate underlayment systems are those having a current Florida Statewide Product Approval and/or approved on a local-level by the Authority Having Jurisdiction, listed specifically for use with POLYSET®RTA-1. NEMO ETC,LLC Evaluation Report 02768.02.06-R9 Certificate of Authorization#32455 7TH EDITION(2020)FBC NON-HVHZ EVALUATION FL6276-R9 Polyset•RTA-1 Revision 9:09/29/2020 Page 3 of 9 ONEMOletc. 5.7.2 Tile roof systems using tile types or profiles other than those listed above acquiring acceptance for use with POLYSET® RTA-1 shall be tested in accordance with SSTD it or Testing Application Standard TAS 101. For the interdependent multi-paddy method, an additional 2-to-1 margin of safety above that specified in SSTD 11 or Testing Application Standard TAS 101 shall be applied in determining the'allowable overturning moment'. 5.8 Hip and ridge tiles using POLYSET® RTA-1 are limited to projects having hip/ridge design pressure requirements, determined in accordance with Table 1A of FRSA/TRI Florida High Wind Concrete and Clay Roof Tile Installation Manual,Sixth Edition or the applicable design pressure determined in accordance with FBC 1609 or FBC Residential Chapter 3, not greater than the following values. Refer to ICP Adhesives and Sealants, Inc. published installation instructions for Adhesive Paddy Placement details. TABLE 2:Hip&RIDGE TILES IN POLYSETO RTA-1 ALLOWABLE UPLIFT RESISTANCE PERFORMANCE DATA (MARGINS OF SAFETY ALREADY APPLIED) Detail Allowable Tile Substrate (Section Attachment Details Design 10) Pressure(psf) Clay or Interdependent: Concrete 2x PT ridge board #8 Head:One(1)#10 x 2Y2"screw; 187 Overlap:1x6-inch x-10.5 gram East Coast Metals"Trim Lock""(FBC FL5394): Interdependent: Clay or aluminum or On Trim-Lock'"metal:One(1)-7- Concrete East Coast Metals"Trim Lock'"Plus"(FBC inch long x-10 gram oblong shaped 93 FL5394):aluminum,Galvalume®or stainless #9 paddy centered on metal. steel At Tile Headlap:One(1)-7-inch long Clay or East Coast Metals"Trim Lock""(FBC FL5394): x-10 gram oblong shaped bead at 110 Concrete Galvalume°or stainless steel tile headlap. INSTALLATION:6. 6.1 POLYSET®RTA-1 and the tile roof assembly shall be installed in accordance with the manufacturers'current published instructions,but not less than the requirements of FBC 1507.3 and the FRSA/TRI Florida High Wind Concrete and Clay Roof Tile Installation Manual,Sixth Edition,subject to the limitations in Section 5. 6.1.1 Installation of POLYSET® RTA-1 shall be performed by applicators that hold a valid Qualified Applicator Card presented by ICP Adhesives and Sealants,Inc. 6.2 Underlayment shall hold current Florida Product Approval for use with tile roofing systems. The underlayment Product Approval shall specify allowable use with POLYSET®RTA-1. The underlayment Product Approval shall specify attachment methods for the underlayment system to resist wind uplift design loads in accordance with Table 1A of FRSA/TRI Florida High Wind Concrete and Clay Roof Tile Installation Manual, Sixth Edition or the critical (highest) design pressure determined in accordance with FBC 1609 or FBC Residential Chapter 3. 6.3 Hip and ridge boards or hip/ridge metal shall be installed in accordance with the FRSA/TRI Florida High Wind Concrete and Clay Roof Tile Installation Manual,Sixth Edition. Proprietary hip and ridge metal shall be installed in accordance with the manufacturer's Florida Product Approval. REQUIREMENTS:7. BUILDING PERMIT As required by the Building Official or Authority Having Jurisdiction to properly evaluate the installation of this product. 8. MANUFACTURING PLANTS: Norton,OH QUALITY9. IAPMO UES-QUA10547; (909)223-4422;barry.lohnson@uniform-es.org NEMO ETC,LLC Evaluation Report 02768.02.06-R9 Certificate of Authorization#32455 7TH EDITION(2020)FBC NON-HVH2 EVALUATION FL6276-R9 Polyset•RTA-1 Revision 9:09/29/2020 Page 4 of 9 ONEMO etc. PADDY10. 10.1 Detail#1: Flat Profile Tile: Strengthening Ribs � 1 Ur.9�i.rfe�.n n�� ` �y Paddy on Deck Dispensed 1 ` Horizontally at Tile Course Line r Pad on Top of Tile Dispensed Horizontally at Head Lap Underlock Eave Course Line Overlock Eave Closure Start Eave Course Paddies at Tile Course Line 10.2 Detail#2:LOW/Medium Profile Tile: Pan of Tile Paddy on Top of the Tile Dispensed Horizontally at Head Lap (� \ Underlock Y Overlock Eave Course Line Eave Closure D Start Eave Course Paddies at Tile Course Line NEMO ETC,LLC Evaluation Report 02768.02.06-R9 Certificate of Authorization#32455 7-EDITION(2020)FBC NON-HVHZ EVALUATION FL6276-R9 Polyset®RTA-1 Revision 9:09/29/2020 Page 5 of 9 ONEMOletc. 10.3 Detail#3:High Profile Tile: Pon of Tile Paddy on Top of Tile Dispensed Horizontally at Head Lap { Eave Course Line Eave Closure Start Paddy Undemeath Pan Portion of Tile at High Profile Tile Course Line 10.4 Detail#4: Two Piece Barrel(Cap&Pan)Tile: One(t)-7"Paddy on each side under cover tiles(Detail) Two(2)-7'Oblong paddies side by side under pan tiles One(t)-7"Paddy on each side under cover tiles Eave Course Line Eave Closure Two(2)-10'Oblong paddies side by side under pan tiles 2-Piece Barrel Profile leave course only) NEMO ETC,LLC Evaluation Report 02768.02.06-119 Certificate of Authorization U32455 7-EDITION(2020)FBC NON-HVHZ EVALUATION FL6276-119 Polyset•RTA-1 Revision 9:09/29/2020 Page 6 of 9 ONEMOjetc. 10.5 Detail#5: Low/Flat Profile Tile;Hybrid System: Strengthening Ribs Two(21=8 Screws in Factory Hole Locations Underside of Tile Pad on Top of Tile Dispensed Honzontally at Head Lap Undenock 0 Eave Course Line Overlock Eave CIOSaIe Flat Profile 10.6 Detail#6: Medium Profile Tile;Hybrid System: Pan of Tile Two(2)=8 Screws in Factory Hole Locations Paddy on Top of the The Dispensed Horizontally at Head Lap Undedock Eave Course Overlock Line Eave Closure Low Profile NEW ETC,LLC Evaluation Report 02768.02.06-R9 Certificate of Authorization#32455 7TH EDITION(2020)FBC NON-HVHZ EVALUATION F1.6276-119 Polyset®RTA-1 Revision 9:09/29/I020 Page 7 of 9 ONEMOjetc. 10.7 Detail#7: High Profile Tile;Hybrid System: Pen of Tile Two(2)Screws in Factory Hole Locations Paddy an Top of Tile Dispensed Horizontally of Head Lop Eave Course Line Eave Closure Hlgn Profile 10.8 Detail#8: Hip and Ridge(interdependent with screw): l� 1( 1"•X•6"•Bead•of•ICP- r Adhesives• Polyset°RTA-1•roof- tile•adhesive••T•. #10•x•2-1/2"•Screw• Code•Approved- Fastener Adhere•starter- tile-%vith•a•2"•x•7"- Paddyplaced3"- down•from•head of•tile¶ NEMO ETC,LLC Evaluation Report 02768.02.06-R9 Certificate of Authorization#32455 7TH EDITION(2020)FBC NON-HVHZ EVALUATION FL6276-119 Polyset°RTA-1 Revision 9:09/29/2020 Page 8 of 9 ONEMOletc. 10.9 Detail#9: Hip and Ridge(interdependent placement): 7" Oblong Paddy 7" Oblong Paddy END OF EVALUATION REPORT- NEMO ETC,LLC Evaluation Report 02768.02.06-119 Certificate cf Authorization#32455 7TH EDITION(2020)FBC NON-HVH2 EVALUATION FL6276-R9 Polyset"RTA-1 Revision 9:09/29/2020 Page 9 of 9