HomeMy WebLinkAboutAPPROVED MANJ (3)Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Aug-27 10:37:00
Right-Suite® Universal 2021 21.0.08 RSU29066 Page 1
...ments\Wrightsoft HVAC\2962 Bent Pine Dr GBI.rup Calc = MJ8 Front Door faces: N
1603Job:Load Short Form 8/25/2021Date:House Chris BatemanBy:
Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
Project Information
Wright Residence, Groza Builders, IncFor:
2962 Bent Pine Dr, Fort Pierce, FL 34951
Design Information
InfiltrationClgHtg
SimplifiedMethod9041Outside db (°F)
AverageConstruction quality7570Inside db (°F)
0Fireplaces1529Design TD (°F)
L-Daily range
5030Inside humidity (%)
572Moisture difference (gr/lb)
HEATING EQUIPMENT COOLING EQUIPMENT
Make Make Lennox
Trade Trade LENNOX
Model Cond ML14XC1S036-230C**
AHRI ref Coil CBA27UHE-036-230*++TDR
AHRI ref 204289057
Efficiency 100 EFF Efficiency 13.0 EER, 16 SEER
Heating input kW7.9 Sensible cooling Btuh24220
Heating output Btuh26993 Latent cooling Btuh10380
Temperature rise °F21 Total cooling Btuh34600
Actual air flow cfm1153 Actual air flow cfm1153
Air flow factor cfm/Btuh0.041 Air flow factor cfm/Btuh0.053
Static pressure in H2O0.70 Static pressure in H2O0.70
Space thermostat Load sensible heat ratio 0.73
ROOM NAME Area Htg load Clg load Htg AVF Clg AVF
(ft²)(Btuh)(Btuh)(cfm)(cfm)
Bath 83 620 186 25 10
Bath 2 81 1778 500 73 27
Bed 2 166 2833 1768 116 94
Bed 3 208 1735 921 71 49
Bed 4 197 3041 1674 124 89
Den 121 1352 860 55 46
Flex Room 156 2791 1717 114 91
Foyer 89 689 276 28 15
Great Room 445 2267 4485 93 239
Hall 45 0 0 0 0
Hall 2 40 0 0 0 0
Hers 42 647 173 26 9
His 37 595 158 24 8
Kit Nook 353 2086 4166 85 222
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Aug-27 10:37:00
Right-Suite® Universal 2021 21.0.08 RSU29066 Page 2
...ments\Wrightsoft HVAC\2962 Bent Pine Dr GBI.rup Calc = MJ8 Front Door faces: N
Laundry 75 1360 911 56 48
M Bath 162 1470 407 60 22
M Hall 20 0 0 0 0
Master Bed 259 4824 3393 197 181
Pantry 36 48 26 2 1
Wtr Clst 26 34 19 1 1
Wtr Clst2 23 30 17 1 1
House 2663 28199 21654 1153 1153
Other equip loads 2044 1085
Equip. @ 0.95 RSM 21694
Latent cooling 8415
TOTALS 2663 30243 30109 1153 1153
2021-Aug-27 10:37:00
Right-Suite® Universal 2021 21.0.08 RSU29066 Page 1
...ments\Wrightsoft HVAC\2962 Bent Pine Dr GBI.rup Calc = MJ8 Front Door faces: N
1603Job:Building Analysis 8/25/2021Date:House Chris BatemanBy:
Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
Project Information
Wright Residence, Groza Builders, IncFor:
2962 Bent Pine Dr, Fort Pierce, FL 34951
Design Conditions
Location: CoolingHeatingIndoor:7570Indoor temperature (°F)St Lucie Co Intl, FL, US
1529Design TD (°F)ft26Elevation:
5030Relative humidity (%)°N28Latitude:
Outdoor:56.92.4Moisture difference (gr/lb)CoolingHeating
Infiltration:9041Dry bulb (°F)
SimplifiedMethod)L(15-Daily range (°F)
AverageConstruction quality77-Wet bulb (°F)
0Fireplaces7.515.0Wind speed (mph)
Heating
Walls
Glazing
Other
Ceilings
Floors
Infiltration
Ducts
Ventilation
% of loadBtuhBtuh/ft²Component
15.647212.6Walls
7.823569.0Glazing
0.61693.7Doors
8.726291.0Ceilings
23.270272.62.6Floors
13.641012.3Infiltration
23.87195Ducts
00Piping
00Humidification
6.82044Ventilation0Adjustments
100.030243Total
Cooling
Walls
Glazing
Other
Ceilings
Infiltration Ducts
Internal Gains
Ventilation
% of loadBtuhBtuh/ft²Component
12.728861.6Walls
23.0522220.0Glazing
0.81713.7Doors
7.116140.6Ceilings
000Floors
4.810890.6Infiltration
22.75173Ducts
4.81085Ventilation
24.25500Internal gains
00Blower
0Adjustments
100.022740Total
Latent Cooling Load = 8415 Btuh
Overall U-value = 0.079 Btuh/ft²-°F
Data entries checked.
2021-Aug-27 10:37:00
Right-Suite® Universal 2021 21.0.08 RSU29066 Page 1
...ments\Wrightsoft HVAC\2962 Bent Pine Dr GBI.rup Calc = MJ8 Front Door faces: N
1603Job:Component Constructions 8/25/2021Date:House Chris BatemanBy:
Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
Project Information
Wright Residence, Groza Builders, IncFor:
2962 Bent Pine Dr, Fort Pierce, FL 34951
Design Conditions
Location: CoolingHeatingIndoor:
7570Indoor temperature (°F)St Lucie Co Intl, FL, US
1529Design TD (°F)ft26Elevation:
5030Relative humidity (%)°N28Latitude:
Outdoor:56.92.4Moisture difference (gr/lb)CoolingHeating
Infiltration:9041Dry bulb (°F)
SimplifiedMethod)L(15-Daily range (°F)
AverageConstruction quality77-Wet bulb (°F)
0Fireplaces7.515.0Wind speed (mph)
Construction descriptions GainLoss Clg HTMHtg HTMInsul RU-valueAreaOr
BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft²
Walls
Block R-9 Wall: Blk wall, Stuc Ext, 8" thk, R-9 Foam Fill, 1/2" Gyp Bd 8202.589.00.089318n 5241.65
4221.656602.589.00.089256e
8171.6512772.589.00.089496s
6611.6510332.589.00.089401w
24241.6537892.589.00.0891471all
Partitions
Frm Wall, 1/2" Gyp Bd Ext, R-11 Cav Ins, 1/2" Gyp Bd Int Fnsh, 2"x4", 16"
OC Stud
4621.469312.9411.00.101317
Windows
Impact: Impact; NFRC rated (SHGC=0.21); 50% blinds 45°, medium;
50% outdoor insect screen; foreground = green grass (0.23); 1 ft overhang
(0.67 ft window ht, 1 ft sep.); 6.8 ft head ht
127.17158.7000.3002n
Impact: Impact; NFRC rated (SHGC=0.21); 50% blinds 45°, medium;
50% outdoor insect screen; foreground = green grass (0.23); 1 ft overhang
(5.2 ft window ht, 1 ft sep.); 6.8 ft head ht
2247.172718.7000.30031n
34322.01368.7000.30016e
68622.02718.7000.30031e
1459.311368.7000.30016s
34322.01368.7000.30016w
174115.99508.7000.300109all
Impact: Impact; NFRC rated (SHGC=0.21); 50% blinds 45°, medium;
50% outdoor insect screen; foreground = green grass (0.23); 1 ft overhang
(5.25 ft window ht, 1 ft sep.); 6.8 ft head ht
51022.02028.7000.30023e
Impact: Impact; NFRC rated (SHGC=0.21); 50% blinds 45°, medium;
50% outdoor insect screen; foreground = green grass (0.23); 7.3 ft
overhang (5.2 ft window ht, 1 ft sep.); 6.8 ft head ht
2979.512718.7000.30031w
Impact: Impact; NFRC rated (SHGC=0.26); 50% blinds 45°, medium;
50% outdoor insect screen; foreground = green grass (0.23); 1 ft overhang
(8 ft window ht, 1 ft sep.); 6.8 ft head ht
90818.94599.5700.33048w
Impact: Impact; NFRC rated (SHGC=0.26); 50% blinds 45°, medium;
50% outdoor insect screen; foreground = green grass (0.23); 9.3 ft
overhang (8 ft window ht, 1 ft sep.); 6.8 ft head ht
61612.84599.5700.33048w
Doors
2021-Aug-27 10:37:00
Right-Suite® Universal 2021 21.0.08 RSU29066 Page 2
...ments\Wrightsoft HVAC\2962 Bent Pine Dr GBI.rup Calc = MJ8 Front Door faces: N
Fbrgls Door 673.73663.697.00.12718n
1043.731033.697.00.12728e
1713.731693.697.00.12746all
Ceilings
Attic, Metal Roof, R-30 Ceil Ins, 5/8" Gyp Bd 0.0342663 16140.6126290.9930.0
Floors
On Grade Depth, Tile Flr Fnsh 00702728.700.989245
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Aug-27 10:37:00
Right-Suite® Universal 2021 21.0.08 RSU29066 Page 1
...ments\Wrightsoft HVAC\2962 Bent Pine Dr GBI.rup Calc = MJ8 Front Door faces: N
1603Job:Project Summary 8/25/2021Date:House Chris BatemanBy:
Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
Project Information
Wright Residence, Groza Builders, IncFor:2962 Bent Pine Dr, Fort Pierce, FL 34951
Notes:
Design Information
St Lucie Co Intl, FL, USWeather:
Winter Design Conditions Summer Design Conditions
Outside db °F41 Outside db °F90Inside db °F70 Inside db °F75
Design TD °F29 Design TD °F15Daily range L
Relative humidity %50Moisture difference gr/lb57
Heating Summary Sensible Cooling Equipment Load Sizing
Structure Btuh21004 Structure Btuh16481
Ducts Btuh7195 Ducts Btuh5173Central vent (64 cfm) 2044 Btuh Central vent (64 cfm) Btuh1085
Outside air Outside airHumidification Btuh0 Blower Btuh0
Piping Btuh0Equipment load Btuh30243 Use manufacturer's data n
Rate/swing multiplier 0.95InfiltrationEquipment sensible load Btuh21694
Method Latent Cooling Equipment Load SizingSimplified
Construction quality Average0Fireplaces Structure Btuh3487
Ducts Btuh2451Central vent (64 cfm) Btuh2478
CoolingHeating Outside air26632663Area (ft²) Equipment latent load Btuh8415
2413024130Volume (ft³)Air changes/hour 0.160.32 Equipment Total Load (Sen+Lat)Btuh30109
Equiv. AVF (cfm) 64129 Req. total capacity at 0.70 SHR ton2.6
Heating Equipment Summary Cooling Equipment Summary
Make Make LennoxTrade Trade LENNOX
Model Cond ML14XC1S036-230C**AHRI ref Coil CBA27UHE-036-230*++TDR
AHRI ref 204289057Efficiency 100 EFF Efficiency 13.0 EER, 16 SEER
Heating input kW7.9 Sensible cooling Btuh24220Heating output Btuh26993 Latent cooling Btuh10380
Temperature rise °F21 Total cooling Btuh34600Actual air flow cfm1153 Actual air flow cfm1153
Air flow factor cfm/Btuh0.041 Air flow factor cfm/Btuh0.053Static pressure in H2O0.70 Static pressure in H2O0.70
Space thermostat Load sensible heat ratio 0.73
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Aug-27 10:37:00Right-Suite® Universal 2021 21.0.08 RSU29066 Page 1...ments\Wrightsoft HVAC\2962 Bent Pine Dr GBI.rup Calc = MJ8 Front Door faces: N
1603Job:Right-J® Worksheet 8/25/2021Date:House Chris BatemanBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name House Bath
2 Exposed wall 245.0 ft 5.5 ft
3 Room height 9.1 ft 8.0 heat/coolft
4 Room dimensions ft5.5x15.0
5 Room area 2662.5 ft²82.5 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW Block R-9 WallBlock R-9 Wall 0.0890.089 nn 2.582.58 1.651.65 369 318 820 524 0 0 0 0
.GG ImpactImpact 0.3000.300 nn 8.708.70 7.177.17 2 0 15 12 0 0 0 0
.GG ImpactImpact 0.3000.300 nn 8.708.70 7.177.17 31 0 271 224 0 0 0 0
.DD Fbrgls DoorFbrgls Door 0.1270.127 nn 3.693.69 3.733.73 18 18 66 67 0 0 0 0
11 WW Block R-9 WallBlock R-9 Wall 0.0890.089 ee 2.582.58 1.651.65 354 256 660 422 0 0 0 0
GG ImpactImpact 0.3000.300 ee 8.708.70 21.9921.99 16 0 136 343 0 0 0 0
GG ImpactImpact 0.3000.300 ee 8.708.70 21.9921.99 31 0 271 686 0 0 0 0
GG ImpactImpact 0.3000.300 ee 8.708.70 21.9921.99 23 0 202 510 0 0 0 0
DD Fbrgls DoorFbrgls Door 0.1270.127 ee 3.693.69 3.733.73 28 28 103 104 0 0 0 0
WW Block R-9 WallBlock R-9 Wall 0.0890.089 ss 2.582.58 1.651.65 511 496 1277 817 44 44 113 73
GG ImpactImpact 0.3000.300 ss 8.708.70 9.319.31 16 13 136 145 0 0 0 0
WW Block R-9 WallBlock R-9 Wall 0.0890.089 ww 2.582.58 1.651.65 544 401 1033 661 0 0 0 0
GG ImpactImpact 0.3000.300 ww 8.708.70 21.9921.99 16 0 136 343 0 0 0 0
GG ImpactImpact 0.3000.300 ww 8.708.70 9.519.51 31 30 271 297 0 0 0 0
GG ImpactImpact 0.3300.330 ww 9.579.57 18.9218.92 48 0 459 908 0 0 0 0
GG ImpactImpact 0.3300.330 ww 9.579.57 12.8412.84 48 40 459 616 0 0 0 0
PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 317 317 931 462 0 0 0 0
CC Attic, Metal Roof, R 0.034Attic, Metal Roof, R 0.034 --0.990.99 0.610.61 2663 2663 2629 1614 83 83 81 50
FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 2663 245 7027 0 83 6 158 0
6 c) AED excursion 1137 -12
Envelope loss/gain 16902 9892 353 110
12 a) Infiltration 4101 1089 102 27
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 5 1150 0 0
Appliances/other 4350 0
Subtotal (lines 6 to 13)21004 16481 454 137
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 0 0 8 4
14 Subtotal 21004 16481 462 141
15 Duct loads 34%31%7195 5173 34%31%158 44
Total room load 28199 21654 620 186
Air required (cfm)Air required (cfm)1153 1153 25 10
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Aug-27 10:37:00Right-Suite® Universal 2021 21.0.08 RSU29066 Page 2...ments\Wrightsoft HVAC\2962 Bent Pine Dr GBI.rup Calc = MJ8 Front Door faces: N
1603Job:Right-J® Worksheet 8/25/2021Date:House Chris BatemanBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name Bath 2 Bed 2
2 Exposed wall 18.0 ft 26.5 ft
3 Room height 8.0 heat/coolft 8.0 heat/coolft
4 Room dimensions ft9.5x8.5 ft165.8x1.0
5 Room area 80.8 ft²165.8 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW Block R-9 WallBlock R-9 Wall 0.0890.089 nn 2.582.58 1.651.65 76 58 150 96 0 0 0 0
.GG ImpactImpact 0.3000.300 nn 8.708.70 7.177.17 0 0 0 0 0 0 0 0
.GG ImpactImpact 0.3000.300 nn 8.708.70 7.177.17 0 0 0 0 0 0 0 0
.DD Fbrgls DoorFbrgls Door 0.1270.127 nn 3.693.69 3.733.73 18 18 66 67 0 0 0 0
11 WW Block R-9 WallBlock R-9 Wall 0.0890.089 ee 2.582.58 1.651.65 0 0 0 0 92 69 177 113
GG ImpactImpact 0.3000.300 ee 8.708.70 21.9921.99 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3000.300 ee 8.708.70 21.9921.99 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3000.300 ee 8.708.70 21.9921.99 0 0 0 0 23 0 202 510
DD Fbrgls DoorFbrgls Door 0.1270.127 ee 3.693.69 3.733.73 0 0 0 0 0 0 0 0
WW Block R-9 WallBlock R-9 Wall 0.0890.089 ss 2.582.58 1.651.65 0 0 0 0 120 120 309 198
GG ImpactImpact 0.3000.300 ss 8.708.70 9.319.31 0 0 0 0 0 0 0 0
WW Block R-9 WallBlock R-9 Wall 0.0890.089 ww 2.582.58 1.651.65 68 68 175 112 0 0 0 0
GG ImpactImpact 0.3000.300 ww 8.708.70 21.9921.99 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3000.300 ww 8.708.70 9.519.51 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3300.330 ww 9.579.57 18.9218.92 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3300.330 ww 9.579.57 12.8412.84 0 0 0 0 0 0 0 0
PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0
CC Attic, Metal Roof, R 0.034Attic, Metal Roof, R 0.034 --0.990.99 0.610.61 81 81 80 49 166 166 164 100
FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 81 18 516 0 166 27 760 0
6 c) AED excursion -34 39
Envelope loss/gain 987 289 1612 960
12 a) Infiltration 332 88 489 130
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 0 0 0 0
Appliances/other 0 250
Subtotal (lines 6 to 13)1319 378 2101 1340
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 5 3 9 5
14 Subtotal 1324 380 2110 1345
15 Duct loads 34%31%454 119 34%31%723 422
Total room load 1778 500 2833 1768
Air required (cfm)Air required (cfm)73 27 116 94
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Aug-27 10:37:00Right-Suite® Universal 2021 21.0.08 RSU29066 Page 3...ments\Wrightsoft HVAC\2962 Bent Pine Dr GBI.rup Calc = MJ8 Front Door faces: N
1603Job:Right-J® Worksheet 8/25/2021Date:House Chris BatemanBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name Bed 3 Bed 4
2 Exposed wall 14.5 ft 29.0 ft
3 Room height 8.0 heat/coolft 8.0 heat/coolft
4 Room dimensions ft207.5x1.0 ft197.4x1.0
5 Room area 207.5 ft²197.4 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW Block R-9 WallBlock R-9 Wall 0.0890.089 nn 2.582.58 1.651.65 0 0 0 0 0 0 0 0
.GG ImpactImpact 0.3000.300 nn 8.708.70 7.177.17 0 0 0 0 0 0 0 0
.GG ImpactImpact 0.3000.300 nn 8.708.70 7.177.17 0 0 0 0 0 0 0 0
.DD Fbrgls DoorFbrgls Door 0.1270.127 nn 3.693.69 3.733.73 0 0 0 0 0 0 0 0
11 WW Block R-9 WallBlock R-9 Wall 0.0890.089 ee 2.582.58 1.651.65 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3000.300 ee 8.708.70 21.9921.99 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3000.300 ee 8.708.70 21.9921.99 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3000.300 ee 8.708.70 21.9921.99 0 0 0 0 0 0 0 0
DD Fbrgls DoorFbrgls Door 0.1270.127 ee 3.693.69 3.733.73 0 0 0 0 0 0 0 0
WW Block R-9 WallBlock R-9 Wall 0.0890.089 ss 2.582.58 1.651.65 116 100 259 165 124 124 319 204
GG ImpactImpact 0.3000.300 ss 8.708.70 9.319.31 16 13 136 145 0 0 0 0
WW Block R-9 WallBlock R-9 Wall 0.0890.089 ww 2.582.58 1.651.65 0 0 0 0 108 92 238 152
GG ImpactImpact 0.3000.300 ww 8.708.70 21.9921.99 0 0 0 0 16 0 136 343
GG ImpactImpact 0.3000.300 ww 8.708.70 9.519.51 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3300.330 ww 9.579.57 18.9218.92 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3300.330 ww 9.579.57 12.8412.84 0 0 0 0 0 0 0 0
PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0
CC Attic, Metal Roof, R 0.034Attic, Metal Roof, R 0.034 --0.990.99 0.610.61 208 208 205 126 197 197 195 120
FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 208 15 416 0 197 29 832 0
6 c) AED excursion -62 57
Envelope loss/gain 1015 374 1720 876
12 a) Infiltration 268 71 535 142
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 0 0 0 0
Appliances/other 250 250
Subtotal (lines 6 to 13)1283 696 2255 1268
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 9 5 10 6
14 Subtotal 1292 701 2265 1274
15 Duct loads 34%31%443 220 34%31%776 400
Total room load 1735 921 3041 1674
Air required (cfm)Air required (cfm)71 49 124 89
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Aug-27 10:37:00Right-Suite® Universal 2021 21.0.08 RSU29066 Page 4...ments\Wrightsoft HVAC\2962 Bent Pine Dr GBI.rup Calc = MJ8 Front Door faces: N
1603Job:Right-J® Worksheet 8/25/2021Date:House Chris BatemanBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name Den Flex Room
2 Exposed wall 11.5 ft 25.0 ft
3 Room height 8.0 heat/coolft 10.0 heat/coolft
4 Room dimensions ft10.5x11.5 ft156.0x1.0
5 Room area 120.8 ft²156.0 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW Block R-9 WallBlock R-9 Wall 0.0890.089 nn 2.582.58 1.651.65 0 0 0 0 0 0 0 0
.GG ImpactImpact 0.3000.300 nn 8.708.70 7.177.17 0 0 0 0 0 0 0 0
.GG ImpactImpact 0.3000.300 nn 8.708.70 7.177.17 0 0 0 0 0 0 0 0
.DD Fbrgls DoorFbrgls Door 0.1270.127 nn 3.693.69 3.733.73 0 0 0 0 0 0 0 0
11 WW Block R-9 WallBlock R-9 Wall 0.0890.089 ee 2.582.58 1.651.65 92 76 197 126 120 89 229 146
GG ImpactImpact 0.3000.300 ee 8.708.70 21.9921.99 16 0 136 343 0 0 0 0
GG ImpactImpact 0.3000.300 ee 8.708.70 21.9921.99 0 0 0 0 31 0 271 686
GG ImpactImpact 0.3000.300 ee 8.708.70 21.9921.99 0 0 0 0 0 0 0 0
DD Fbrgls DoorFbrgls Door 0.1270.127 ee 3.693.69 3.733.73 0 0 0 0 0 0 0 0
WW Block R-9 WallBlock R-9 Wall 0.0890.089 ss 2.582.58 1.651.65 0 0 0 0 25 25 64 41
GG ImpactImpact 0.3000.300 ss 8.708.70 9.319.31 0 0 0 0 0 0 0 0
WW Block R-9 WallBlock R-9 Wall 0.0890.089 ww 2.582.58 1.651.65 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3000.300 ww 8.708.70 21.9921.99 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3000.300 ww 8.708.70 9.519.51 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3300.330 ww 9.579.57 18.9218.92 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3300.330 ww 9.579.57 12.8412.84 0 0 0 0 0 0 0 0
PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 105 105 308 153
CC Attic, Metal Roof, R 0.034Attic, Metal Roof, R 0.034 --0.990.99 0.610.61 121 121 119 73 156 156 154 95
FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 121 12 330 0 156 25 717 0
6 c) AED excursion 49 97
Envelope loss/gain 782 591 1744 1218
12 a) Infiltration 212 56 335 89
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 0 0 0 0
Appliances/other 0 0
Subtotal (lines 6 to 13)994 647 2079 1307
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 13 7 0 0
14 Subtotal 1007 655 2079 1307
15 Duct loads 34%31%345 206 34%31%712 410
Total room load 1352 860 2791 1717
Air required (cfm)Air required (cfm)55 46 114 91
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Aug-27 10:37:00Right-Suite® Universal 2021 21.0.08 RSU29066 Page 5...ments\Wrightsoft HVAC\2962 Bent Pine Dr GBI.rup Calc = MJ8 Front Door faces: N
1603Job:Right-J® Worksheet 8/25/2021Date:House Chris BatemanBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name Foyer Great Room
2 Exposed wall 5.0 ft 10.5 ft
3 Room height 10.0 heat/coolft 11.5 heat/coolft
4 Room dimensions ft88.5x1.0 ft444.8x1.0
5 Room area 88.5 ft²444.8 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW Block R-9 WallBlock R-9 Wall 0.0890.089 nn 2.582.58 1.651.65 0 0 0 0 0 0 0 0
.GG ImpactImpact 0.3000.300 nn 8.708.70 7.177.17 0 0 0 0 0 0 0 0
.GG ImpactImpact 0.3000.300 nn 8.708.70 7.177.17 0 0 0 0 0 0 0 0
.DD Fbrgls DoorFbrgls Door 0.1270.127 nn 3.693.69 3.733.73 0 0 0 0 0 0 0 0
11 WW Block R-9 WallBlock R-9 Wall 0.0890.089 ee 2.582.58 1.651.65 50 22 57 36 0 0 0 0
GG ImpactImpact 0.3000.300 ee 8.708.70 21.9921.99 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3000.300 ee 8.708.70 21.9921.99 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3000.300 ee 8.708.70 21.9921.99 0 0 0 0 0 0 0 0
DD Fbrgls DoorFbrgls Door 0.1270.127 ee 3.693.69 3.733.73 28 28 103 104 0 0 0 0
WW Block R-9 WallBlock R-9 Wall 0.0890.089 ss 2.582.58 1.651.65 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3000.300 ss 8.708.70 9.319.31 0 0 0 0 0 0 0 0
WW Block R-9 WallBlock R-9 Wall 0.0890.089 ww 2.582.58 1.651.65 0 0 0 0 121 73 187 120
GG ImpactImpact 0.3000.300 ww 8.708.70 21.9921.99 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3000.300 ww 8.708.70 9.519.51 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3300.330 ww 9.579.57 18.9218.92 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3300.330 ww 9.579.57 12.8412.84 0 0 0 0 48 40 459 616
PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0
CC Attic, Metal Roof, R 0.034Attic, Metal Roof, R 0.034 --0.990.99 0.610.61 89 89 87 54 445 445 439 270
FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 89 5 143 0 445 11 301 0
6 c) AED excursion -19 731
Envelope loss/gain 391 176 1387 1737
12 a) Infiltration 115 31 279 74
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 0 0 3 690
Appliances/other 0 900
Subtotal (lines 6 to 13)506 206 1666 3400
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 7 4 23 13
14 Subtotal 513 210 1688 3413
15 Duct loads 34%31%176 66 34%31%578 1071
Total room load 689 276 2267 4485
Air required (cfm)Air required (cfm)28 15 93 239
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Aug-27 10:37:00Right-Suite® Universal 2021 21.0.08 RSU29066 Page 6...ments\Wrightsoft HVAC\2962 Bent Pine Dr GBI.rup Calc = MJ8 Front Door faces: N
1603Job:Right-J® Worksheet 8/25/2021Date:House Chris BatemanBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name Hall Hall 2
2 Exposed wall 0 ft 0 ft
3 Room height 8.0 heat/coolft 8.0 heat/coolft
4 Room dimensions ft4.5x10.0 ft39.9x1.0
5 Room area 45.0 ft²39.9 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW Block R-9 WallBlock R-9 Wall 0.0890.089 nn 2.582.58 1.651.65 0 0 0 0 0 0 0 0
.GG ImpactImpact 0.3000.300 nn 8.708.70 7.177.17 0 0 0 0 0 0 0 0
.GG ImpactImpact 0.3000.300 nn 8.708.70 7.177.17 0 0 0 0 0 0 0 0
.DD Fbrgls DoorFbrgls Door 0.1270.127 nn 3.693.69 3.733.73 0 0 0 0 0 0 0 0
11 WW Block R-9 WallBlock R-9 Wall 0.0890.089 ee 2.582.58 1.651.65 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3000.300 ee 8.708.70 21.9921.99 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3000.300 ee 8.708.70 21.9921.99 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3000.300 ee 8.708.70 21.9921.99 0 0 0 0 0 0 0 0
DD Fbrgls DoorFbrgls Door 0.1270.127 ee 3.693.69 3.733.73 0 0 0 0 0 0 0 0
WW Block R-9 WallBlock R-9 Wall 0.0890.089 ss 2.582.58 1.651.65 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3000.300 ss 8.708.70 9.319.31 0 0 0 0 0 0 0 0
WW Block R-9 WallBlock R-9 Wall 0.0890.089 ww 2.582.58 1.651.65 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3000.300 ww 8.708.70 21.9921.99 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3000.300 ww 8.708.70 9.519.51 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3300.330 ww 9.579.57 18.9218.92 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3300.330 ww 9.579.57 12.8412.84 0 0 0 0 0 0 0 0
PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0
CC Attic, Metal Roof, R 0.034Attic, Metal Roof, R 0.034 --0.990.99 0.610.61 45 45 44 27 40 40 39 24
FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 45 0 0 0 40 0 0 0
6 c) AED excursion -2 -2
Envelope loss/gain 44 25 39 22
12 a) Infiltration 0 0 0 0
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 0 0 0 0
Appliances/other 0 0
Subtotal (lines 6 to 13)44 25 39 22
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution -44 -25 -39 -22
14 Subtotal 0 0 0 0
15 Duct loads 34%31%0 0 34%31%0 0
Total room load 0 0 0 0
Air required (cfm)Air required (cfm)0 0 0 0
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Aug-27 10:37:00Right-Suite® Universal 2021 21.0.08 RSU29066 Page 7...ments\Wrightsoft HVAC\2962 Bent Pine Dr GBI.rup Calc = MJ8 Front Door faces: N
1603Job:Right-J® Worksheet 8/25/2021Date:House Chris BatemanBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name Hers His
2 Exposed wall 6.5 ft 6.0 ft
3 Room height 8.0 heat/coolft 8.0 heat/coolft
4 Room dimensions ft6.5x6.5 ft37.0x1.0
5 Room area 42.3 ft²37.0 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW Block R-9 WallBlock R-9 Wall 0.0890.089 nn 2.582.58 1.651.65 52 52 134 86 48 48 124 79
.GG ImpactImpact 0.3000.300 nn 8.708.70 7.177.17 0 0 0 0 0 0 0 0
.GG ImpactImpact 0.3000.300 nn 8.708.70 7.177.17 0 0 0 0 0 0 0 0
.DD Fbrgls DoorFbrgls Door 0.1270.127 nn 3.693.69 3.733.73 0 0 0 0 0 0 0 0
11 WW Block R-9 WallBlock R-9 Wall 0.0890.089 ee 2.582.58 1.651.65 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3000.300 ee 8.708.70 21.9921.99 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3000.300 ee 8.708.70 21.9921.99 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3000.300 ee 8.708.70 21.9921.99 0 0 0 0 0 0 0 0
DD Fbrgls DoorFbrgls Door 0.1270.127 ee 3.693.69 3.733.73 0 0 0 0 0 0 0 0
WW Block R-9 WallBlock R-9 Wall 0.0890.089 ss 2.582.58 1.651.65 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3000.300 ss 8.708.70 9.319.31 0 0 0 0 0 0 0 0
WW Block R-9 WallBlock R-9 Wall 0.0890.089 ww 2.582.58 1.651.65 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3000.300 ww 8.708.70 21.9921.99 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3000.300 ww 8.708.70 9.519.51 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3300.330 ww 9.579.57 18.9218.92 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3300.330 ww 9.579.57 12.8412.84 0 0 0 0 0 0 0 0
PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0
CC Attic, Metal Roof, R 0.034Attic, Metal Roof, R 0.034 --0.990.99 0.610.61 42 42 42 26 37 37 37 22
FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 42 7 186 0 37 6 172 0
6 c) AED excursion -12 -11
Envelope loss/gain 362 99 332 91
12 a) Infiltration 120 32 111 29
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 0 0 0 0
Appliances/other 0 0
Subtotal (lines 6 to 13)482 131 443 120
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 0 0 0 0
14 Subtotal 482 131 443 120
15 Duct loads 34%31%165 41 34%31%152 38
Total room load 647 173 595 158
Air required (cfm)Air required (cfm)26 9 24 8
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Aug-27 10:37:00Right-Suite® Universal 2021 21.0.08 RSU29066 Page 8...ments\Wrightsoft HVAC\2962 Bent Pine Dr GBI.rup Calc = MJ8 Front Door faces: N
1603Job:Right-J® Worksheet 8/25/2021Date:House Chris BatemanBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name Kit Nook Laundry
2 Exposed wall 13.0 ft 18.0 ft
3 Room height 10.0 heat/coolft 8.0 heat/coolft
4 Room dimensions ft353.4x1.0 ft6.5x11.5
5 Room area 353.4 ft²74.8 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW Block R-9 WallBlock R-9 Wall 0.0890.089 nn 2.582.58 1.651.65 0 0 0 0 0 0 0 0
.GG ImpactImpact 0.3000.300 nn 8.708.70 7.177.17 0 0 0 0 0 0 0 0
.GG ImpactImpact 0.3000.300 nn 8.708.70 7.177.17 0 0 0 0 0 0 0 0
.DD Fbrgls DoorFbrgls Door 0.1270.127 nn 3.693.69 3.733.73 0 0 0 0 0 0 0 0
11 WW Block R-9 WallBlock R-9 Wall 0.0890.089 ee 2.582.58 1.651.65 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3000.300 ee 8.708.70 21.9921.99 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3000.300 ee 8.708.70 21.9921.99 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3000.300 ee 8.708.70 21.9921.99 0 0 0 0 0 0 0 0
DD Fbrgls DoorFbrgls Door 0.1270.127 ee 3.693.69 3.733.73 0 0 0 0 0 0 0 0
WW Block R-9 WallBlock R-9 Wall 0.0890.089 ss 2.582.58 1.651.65 20 20 52 33 0 0 0 0
GG ImpactImpact 0.3000.300 ss 8.708.70 9.319.31 0 0 0 0 0 0 0 0
WW Block R-9 WallBlock R-9 Wall 0.0890.089 ww 2.582.58 1.651.65 110 79 203 130 0 0 0 0
GG ImpactImpact 0.3000.300 ww 8.708.70 21.9921.99 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3000.300 ww 8.708.70 9.519.51 31 30 271 297 0 0 0 0
GG ImpactImpact 0.3300.330 ww 9.579.57 18.9218.92 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3300.330 ww 9.579.57 12.8412.84 0 0 0 0 0 0 0 0
PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 144 144 423 210
CC Attic, Metal Roof, R 0.034Attic, Metal Roof, R 0.034 --0.990.99 0.610.61 353 353 349 214 75 75 74 45
FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 353 13 373 0 75 18 516 0
6 c) AED excursion 254 -62
Envelope loss/gain 1248 928 1013 193
12 a) Infiltration 300 80 0 0
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 2 460 0 0
Appliances/other 1700 500
Subtotal (lines 6 to 13)1548 3167 1013 693
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 6 3 0 0
14 Subtotal 1554 3171 1013 693
15 Duct loads 34%31%532 995 34%31%347 218
Total room load 2086 4166 1360 911
Air required (cfm)Air required (cfm)85 222 56 48
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Aug-27 10:37:00Right-Suite® Universal 2021 21.0.08 RSU29066 Page 9...ments\Wrightsoft HVAC\2962 Bent Pine Dr GBI.rup Calc = MJ8 Front Door faces: N
1603Job:Right-J® Worksheet 8/25/2021Date:House Chris BatemanBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name M Bath M Hall
2 Exposed wall 15.5 ft 0 ft
3 Room height 8.0 heat/coolft 8.0 heat/coolft
4 Room dimensions ft162.3x1.0 ft4.5x4.5
5 Room area 162.3 ft²20.3 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW Block R-9 WallBlock R-9 Wall 0.0890.089 nn 2.582.58 1.651.65 56 54 140 90 0 0 0 0
.GG ImpactImpact 0.3000.300 nn 8.708.70 7.177.17 2 0 15 12 0 0 0 0
.GG ImpactImpact 0.3000.300 nn 8.708.70 7.177.17 0 0 0 0 0 0 0 0
.DD Fbrgls DoorFbrgls Door 0.1270.127 nn 3.693.69 3.733.73 0 0 0 0 0 0 0 0
11 WW Block R-9 WallBlock R-9 Wall 0.0890.089 ee 2.582.58 1.651.65 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3000.300 ee 8.708.70 21.9921.99 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3000.300 ee 8.708.70 21.9921.99 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3000.300 ee 8.708.70 21.9921.99 0 0 0 0 0 0 0 0
DD Fbrgls DoorFbrgls Door 0.1270.127 ee 3.693.69 3.733.73 0 0 0 0 0 0 0 0
WW Block R-9 WallBlock R-9 Wall 0.0890.089 ss 2.582.58 1.651.65 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3000.300 ss 8.708.70 9.319.31 0 0 0 0 0 0 0 0
WW Block R-9 WallBlock R-9 Wall 0.0890.089 ww 2.582.58 1.651.65 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3000.300 ww 8.708.70 21.9921.99 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3000.300 ww 8.708.70 9.519.51 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3300.330 ww 9.579.57 18.9218.92 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3300.330 ww 9.579.57 12.8412.84 0 0 0 0 0 0 0 0
PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 68 68 200 99 0 0 0 0
CC Attic, Metal Roof, R 0.034Attic, Metal Roof, R 0.034 --0.990.99 0.610.61 162 162 160 98 20 20 20 12
FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 162 16 445 0 20 0 0 0
6 c) AED excursion -28 -1
Envelope loss/gain 959 272 20 11
12 a) Infiltration 129 34 0 0
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 0 0 0 0
Appliances/other 0 0
Subtotal (lines 6 to 13)1088 306 20 11
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 7 4 -20 -11
14 Subtotal 1095 310 0 0
15 Duct loads 34%31%375 97 34%31%0 0
Total room load 1470 407 0 0
Air required (cfm)Air required (cfm)60 22 0 0
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Aug-27 10:37:00Right-Suite® Universal 2021 21.0.08 RSU29066 Page 10...ments\Wrightsoft HVAC\2962 Bent Pine Dr GBI.rup Calc = MJ8 Front Door faces: N
1603Job:Right-J® Worksheet 8/25/2021Date:House Chris BatemanBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name Master Bed Pantry
2 Exposed wall 40.5 ft 0 ft
3 Room height 8.3 heat/coolft 8.0 heat/coolft
4 Room dimensions ft259.1x1.0 ft9.0x4.0
5 Room area 259.1 ft²36.0 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW Block R-9 WallBlock R-9 Wall 0.0890.089 nn 2.582.58 1.651.65 137 106 272 174 0 0 0 0
.GG ImpactImpact 0.3000.300 nn 8.708.70 7.177.17 0 0 0 0 0 0 0 0
.GG ImpactImpact 0.3000.300 nn 8.708.70 7.177.17 31 0 271 224 0 0 0 0
.DD Fbrgls DoorFbrgls Door 0.1270.127 nn 3.693.69 3.733.73 0 0 0 0 0 0 0 0
11 WW Block R-9 WallBlock R-9 Wall 0.0890.089 ee 2.582.58 1.651.65 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3000.300 ee 8.708.70 21.9921.99 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3000.300 ee 8.708.70 21.9921.99 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3000.300 ee 8.708.70 21.9921.99 0 0 0 0 0 0 0 0
DD Fbrgls DoorFbrgls Door 0.1270.127 ee 3.693.69 3.733.73 0 0 0 0 0 0 0 0
WW Block R-9 WallBlock R-9 Wall 0.0890.089 ss 2.582.58 1.651.65 62 62 160 103 0 0 0 0
GG ImpactImpact 0.3000.300 ss 8.708.70 9.319.31 0 0 0 0 0 0 0 0
WW Block R-9 WallBlock R-9 Wall 0.0890.089 ww 2.582.58 1.651.65 137 89 229 147 0 0 0 0
GG ImpactImpact 0.3000.300 ww 8.708.70 21.9921.99 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3000.300 ww 8.708.70 9.519.51 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3300.330 ww 9.579.57 18.9218.92 48 0 459 908 0 0 0 0
GG ImpactImpact 0.3300.330 ww 9.579.57 12.8412.84 0 0 0 0 0 0 0 0
PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0
CC Attic, Metal Roof, R 0.034Attic, Metal Roof, R 0.034 --0.990.99 0.610.61 259 259 256 157 36 36 36 22
FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 259 41 1162 0 36 0 0 0
6 c) AED excursion 160 -2
Envelope loss/gain 2810 1872 36 20
12 a) Infiltration 775 206 0 0
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 0 0 0 0
Appliances/other 500 0
Subtotal (lines 6 to 13)3586 2578 36 20
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 7 4 0 0
14 Subtotal 3593 2582 36 20
15 Duct loads 34%31%1231 810 34%31%12 6
Total room load 4824 3393 48 26
Air required (cfm)Air required (cfm)197 181 2 1
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Aug-27 10:37:00Right-Suite® Universal 2021 21.0.08 RSU29066 Page 11...ments\Wrightsoft HVAC\2962 Bent Pine Dr GBI.rup Calc = MJ8 Front Door faces: N
1603Job:Right-J® Worksheet 8/25/2021Date:House Chris BatemanBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name Wtr Clst Wtr Clst2
2 Exposed wall 0 ft 0 ft
3 Room height 8.0 heat/coolft 8.0 heat/coolft
4 Room dimensions ft6.5x4.0 ft6.5x3.5
5 Room area 26.0 ft²22.8 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW Block R-9 WallBlock R-9 Wall 0.0890.089 nn 2.582.58 1.651.65 0 0 0 0 0 0 0 0
.GG ImpactImpact 0.3000.300 nn 8.708.70 7.177.17 0 0 0 0 0 0 0 0
.GG ImpactImpact 0.3000.300 nn 8.708.70 7.177.17 0 0 0 0 0 0 0 0
.DD Fbrgls DoorFbrgls Door 0.1270.127 nn 3.693.69 3.733.73 0 0 0 0 0 0 0 0
11 WW Block R-9 WallBlock R-9 Wall 0.0890.089 ee 2.582.58 1.651.65 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3000.300 ee 8.708.70 21.9921.99 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3000.300 ee 8.708.70 21.9921.99 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3000.300 ee 8.708.70 21.9921.99 0 0 0 0 0 0 0 0
DD Fbrgls DoorFbrgls Door 0.1270.127 ee 3.693.69 3.733.73 0 0 0 0 0 0 0 0
WW Block R-9 WallBlock R-9 Wall 0.0890.089 ss 2.582.58 1.651.65 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3000.300 ss 8.708.70 9.319.31 0 0 0 0 0 0 0 0
WW Block R-9 WallBlock R-9 Wall 0.0890.089 ww 2.582.58 1.651.65 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3000.300 ww 8.708.70 21.9921.99 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3000.300 ww 8.708.70 9.519.51 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3300.330 ww 9.579.57 18.9218.92 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3300.330 ww 9.579.57 12.8412.84 0 0 0 0 0 0 0 0
PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0
CC Attic, Metal Roof, R 0.034Attic, Metal Roof, R 0.034 --0.990.99 0.610.61 26 26 26 16 23 23 22 14
FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 26 0 0 0 23 0 0 0
6 c) AED excursion -1 -1
Envelope loss/gain 26 14 22 13
12 a) Infiltration 0 0 0 0
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 0 0 0 0
Appliances/other 0 0
Subtotal (lines 6 to 13)26 14 22 13
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 0 0 0 0
14 Subtotal 26 14 22 13
15 Duct loads 34%31%9 5 34%31%8 4
Total room load 34 19 30 17
Air required (cfm)Air required (cfm)1 1 1 1
2021-Aug-27 10:37:01
Right-Suite® Universal 2021 21.0.08 RSU29066 Page 1
...ments\Wrightsoft HVAC\2962 Bent Pine Dr GBI.rup Calc = MJ8 Front Door faces: N
1603Job:Duct System Summary 8/25/2021Date:House Chris BatemanBy:
Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
Project Information
Wright Residence, Groza Builders, IncFor:
2962 Bent Pine Dr, Fort Pierce, FL 34951
CoolingHeating
External static pressure in H2O0.70in H2O0.70
Pressure losses in H2O0in H2O0
Available static pressure in H2O0.70in H2O0.70
Supply / return available pressure 0.529 / 0.171 in H2O in H2O0.529 / 0.171
Lowest friction rate in/100ft0.255in/100ft0.255
Actual air flow cfm1153cfm1153
Total effective length (TEL) ft274
Supply Branch Detail Table
Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv
Name (Btuh)(cfm) (cfm)FR (in)(in)Matl Ln (ft)Ln (ft) Trunk
st5140.062.2VlFx0x04.00.2621230620hBath
st6140.067.5VlFx0x06.00.25532871778hBath 2
st5140.066.8VlFx0x07.00.2561131392833hBed 2
st6140.062.8VlFx0x06.00.26159851735hBed 3
st6140.062.7VlFx0x07.00.2611071493041hBed 4
st5140.058.0VlFx0x05.00.26755661352hDen
st3120.044.4VlFx0x06.00.3221101372791hFlex Room
st5140.063.2VlFx0x04.00.2611834689hFoyer
st1100.038.0VlFx0x06.00.384143562242cGreat Room
st1100.033.8VlFx0x06.00.396143562242cGreat Room-A
st295.017.8VlFx0x04.00.4691132647hHers
st295.013.4VlFx0x04.00.4881029595hHis
st1100.032.4VlFx0x06.00.400133512083cKit Nook
st1100.038.9VlFx0x06.00.381133512083cKit Nook-A
st3120.042.5VlFx0x05.00.32658671360hLaundry
st295.011.3VlFx0x05.00.49826721470hM Bath
st7125.039.5VlFx0x06.00.3221081182412hMaster Bed
st7125.038.5VlFx0x06.00.3241081182412hMaster Bed-A
st3120.038.8VlFx0x04.00.3332248hPantry
st3120.042.5VlFx0x04.00.3261234hWtr Clst
st295.012.0VlFx0x04.00.4951130hWtr Clst2
Bold/italic values have been manually overridden
2021-Aug-27 10:37:01
Right-Suite® Universal 2021 21.0.08 RSU29066 Page 2
...ments\Wrightsoft HVAC\2962 Bent Pine Dr GBI.rup Calc = MJ8 Front Door faces: N
Supply Trunk Detail Table
Trunk Htg Clg Design Veloc Diam H x W Duct
Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk
st3 Peak AVF 208 171 0.322 777 7.0 0x0 VinlFlx st1
st5 Peak AVF 270 197 0.256 610 9.0 0x0 VinlFlx st4
st6 Peak AVF 322 198 0.255 728 9.0 0x0 VinlFlx st4
st4 Peak AVF 591 395 0.255 753 12.0 0x0 VinlFlx st1
st1 Peak AVF 1013 1119 0.255 801 16.0 0x0 VinlFlx
st7 Peak AVF 237 217 0.322 678 8.0 0x0 VinlFlx st2
st2 Peak AVF 371 265 0.322 841 9.0 0x0 VinlFlx
Return Branch Detail Table
Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct
Name Size (in) (cfm)(cfm)(ft)FR (fpm)(in)(in)Opening (in) Matl Trunk
rb1 0x 7130 867 66.8 0.255 621 16.0 x0 0 VlFx
rb2 0x 2980 238 0 0 0 0 x0 0 VlFx
rb5 0x 1490 107 0 0 0 0 x0 0 VlFx
rb4 0x 850 59 0 0 0 0 x0 0 VlFx
rb6 0x 1390 113 0 0 0 0 x0 0 VlFx
2021-Aug-27 10:37:01
Right-Suite® Universal 2021 21.0.08 RSU29066 Page 1
...ments\Wrightsoft HVAC\2962 Bent Pine Dr GBI.rup Calc = MJ8 Front Door faces: N
1603Job:Manual S Compliance Report 8/25/2021Date:House Chris BatemanBy:
Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
Project Information
Wright Residence, Groza Builders, IncFor:
2962 Bent Pine Dr, Fort Pierce, FL 34951
Cooling Equipment
Design Conditions
°F76.4Entering coil DB:Btuh22740Sensible gain:°F90.4Outdoor design DB:
°F64.0Entering coil WB:Btuh8415Latent gain:°F77.4Outdoor design WB:
Btuh31155Total gain:°F75.0Indoor design DB:
cfm1153Estimated airflow:%50Indoor RH:
Manufacturer's Performance Data at Actual Design Conditions
Split ACEquipment type:
ML14XC1S036-230C**+CBA27UHE-036-230*++TDRModel:LennoxManufacturer:
cfm1153Actual airflow:
% of load107Btuh24220Sensible capacity:
% of load123Btuh10380Latent capacity:
%70SHR:% of load111Btuh34600Total capacity:
Heating Equipment
Design Conditions
°F67.8Entering coil DB:Btuh30243Heat loss:°F41.0Outdoor design DB:
°F70.0Indoor design DB:
Manufacturer's Performance Data at Actual Design Conditions
Elec stripEquipment type:
Model:Manufacturer:
cfm1153Actual airflow:
°F50Temp. rise:% of load89kW7.9Output capacity:
Meets all requirements of ACCA Manual S.