HomeMy WebLinkAboutROOF MOUNTED PV SYSTEMGodwin Engineering and
Design, LLC
8378 Foxtail Loop
Pensacola, FL 32526
D. Chad Godwin, PE
Chad@godwineng.com
R-1
# Modules (24)
Pitch: 22°
Azimuth: 277°
3'-5"
5'-9"
FRONT OF HOUSE
R-1
01/05/2022
KG
.
.
Green Ready
4705 Lena Rd. Unit 104
Bradenton, FL 34211
833-478-6797
Meets all requirements of NFPA-1 7th Edition and NFPA-101
3' Access Pathway
1st Responder Access
minimum of 36" unobstructed as per
Section R324 of the 2018 IRC
Customer Info:
S-1
Date:
Drawn by:
Revised by:
Rev #: 00
Rev Date:
Page:
Represents all Fire Clearance
including Alternative methods
Meets the requirements of the following- (2020 FL Residential Code & FBC, 7th Edition (2018 International
Residential Code) - 2nd Printing modified by the FL Building Standards, 2020 Florida Building Energy
Conservation Code 7th edition, County of St. Lucie Code, 2017 National Electric Code.)
Legend First responder access
Sheet Index
S-1 Cover Sheet / Site Plan
S-2 Detail
E-1 One - Line
E-2 Electrical Code
S-1A Mounting Plan
Utility Meter
PV Disconnect
Vent Pipe
Chimney
Satellite
FRONT OF HOUSE
N
Inverter Type:
PV Panel:
Racking:
Total Wattage:
Roof Type:
Wind Load:
Fastener Type:
Iron Ridge XR-100
Enphase IQ7PLUS-72-2-US
(24) DNA-120-MF26-360W
8,640W
Composition Shingle
20 to 27 Deg
Use 5/16" Dia 4.75" Lags
Layout Subject to Change Based on Site Conditions
Meets All Editions of Florida Fire Prevention Code 2020 7th Edition
Compass for Aerial
System meets the requirements of NFPA 70th Edition, Chapter 11.12 Install will be done to Manufacturer Spec
Edward June
8612 Cobblestone DR
Fort Pierce, FL
34945
-COGEN Disconnect
Located adjacent to
Utility meter
General Notes:
-Enphase IQ7PLUS-72-2-US Micro Inverters
are located on roof behind each module.
-First responder access maintained and
from adjacent roof.
-Wire run from array to connection is 40 feet.
Ground Access
3'1'-6"
2' Gutter
2' Gutter
Utility Meter
Solar
Pool
Heater
Solar
Pool
Heater
Godwin Engineering and
Design, LLC
8378 Foxtail Loop
Pensacola, FL 32526
D. Chad Godwin, PE
Chad@godwineng.com
01/05/2022
KG
.
.
Green Ready
4705 Lena Rd. Unit 104
Bradenton, FL 34211
833-478-6797-Roof Height 15'
-Per 2020 FBC, the Roof Mounted PV System
will be subject to the following design criteria:
Design Wind Speed(Vult) - 160mph 3 sec gust,
Exposure Category - B
-Designed as per ASCE7-16
General Notes:
- L Feet are secured to roof rafters.
using 5/16" x 4.75" stainless steel Lag bolts.
- Subject roof has One layer.
- All penetrations are sealed and flashed.
Customer Info:
S-2
Date:
Drawn by:
Revised by:
Rev #: 00
Rev Date:
Page:
Inverter Type:
PV Panel:
Racking:
Total Wattage:
Roof Type:
Wind Load:
Fastener Type:
Iron Ridge XR-100
Enphase IQ7PLUS-72-2-US
(24) DNA-120-MF26-360W
8,640W
Composition Shingle
20 to 27 Deg
Use 5/16" Dia 4.75" Lags
Install will be done to Manufacturer Spec
Edward June
8612 Cobblestone DR
Fort Pierce, FL
34945
Ironridge XR-100
Roof Section Pitch Roof Rafter and Spacing Overhang Notes:
R1 5/12 2"x4" @ 24 O.C.12"Truss
@ 72" O.C. in Zone 1, @ 72" O.C in Zone 2e,
@ 72" O.C. in Zone 2r & @ 72" O.C in Zone 3
Godwin Engineering and
Design, LLC
8378 Foxtail Loop
Pensacola, FL 32526
D. Chad Godwin, PE
Chad@godwineng.com
01/05/2022
KG
.
.
Green Ready
4705 Lena Rd. Unit 104
Bradenton, FL 34211
833-478-6797
In Case of Emergency Call
Green Ready LLC
at 833-478-6797
Customer Info:
E-1
Date:
Drawn by:
Revised by:
Rev #: 00
Rev Date:
Page:
GEC NOTES
- Ungrounded system per 690.41(A)(4)
- GEC must be installed per 250.64
- GEC must be continuous un-spliced or irreversibly spliced from
inverter to existing service ground system or continuous from the
arrays to the existing service ground system.
- GEC must be min #8 AWG and installed in conduit
- If GEC is not in conduit, it must be #6 min
#8 AWG THWN
(2) Hot
(1) Neutral
#8 AWG EGC
in @ least 3/4" Conduit Typically
GEC
40A
Main Service
150A
200A Bus
Load side connection Per 705.12(B)(2)(3)(b)
Use Matching or equivalent approved breaker if derating
Busbar Rating 200
150
90
90
40
Load Side Connection
Main Breaker Size
Bus Rating *1.2-Main Break Size
Max Allowable Load Side
Load Side Breaker Size
Utility PV AC Disco
Install will be done to Manufacturer Spec
Including the label below
Edward June
8612 Cobblestone DR
Fort Pierce, FL
34945
Manual Lockable Disconnect
Located Adjacent to Utility Meter
Note:
-All wiring to meet the 2017 NEC and
Florida electric codes.
60A Disconnect
-Type of conduit to be determined
on site by contractor.
Inverter Type:
Enphase IQ7PLUS-72-2-US
PV Panel:
(24)
DNA-120-MF26-360W
Total Wattage:
8,640W
System meets the grounding requirements of NEC 690.43
All Labels & Markings for photovoltaic system will be
reflective and meet all requirements for NFPA 11.12
Disconnects will be Visible, lockable, adjacent to
and within 10' of utility meter
Meets 11.12.2.1.5
#10 AWG THWN for Home runs
(1) Line 1
(1) Line 2
Per Circuit
#8 AWG THWN
(1) EGC
Inside @ least 3/4" Conduit (tbd on site)
Photovoltaics:
(24) DNA-120-MF26-360W
Inverters:
(24) Enphase IQ7PLUS-72-2-US Micro Inverters
Circuits:
(2) circuits of (12) Modules
Maximum Inverters Per 20A Circuit (13)
Roof
Enphase Combiner Box
(1) - 20A Breaker
Per Circuit
#8 AWG THWN
(1) Line 1
(1) Line 2
(1) Neutral
#8 (1) EGC
in @ least 3/4" Conduit Typically
Disconnect
AC Max Output Current
AC Max Output Current * 1.25%
Overcurrent Protection (A)
No. of Current Carrying Cond
Conductor Gauge (AWG)
Enphase Output Ckt Per String
To Overcurrent Protection Device
Enphase Total Output Ckt
AC Max Output Current
AC Max Output Current * 1.25%
Overcurrent Protection (A)
No. of Current Carrying Cond
Conductor Gauge (AWG)
NEC LABEL NOTES:
1.THE WARNING SIGN(S) OR LABEL(S) SHALL COMPLY
WITH NEC 110.21(B)
2.LABELS SHALL BE SUITABLE FOR THE ENVIRONMENT
WHERE THEY ARE INSTALLED.
3.LABELS TO BE A MIN LETTER HEIGHT OF 3/8" AND
PERMANENTLY AFFIXED.
4.LABELS SHALL ALSO COMPLY WITH THE SPECIFIC
REQUIREMENTS OF THE AUTHORITY HAVING
JURISDICTION.
WARNING
ELECTRIC SHOCK HAZARD
DO NOT TOUCH TERMINALS.
TERMINALS ON BOTH THE LINE AND
LOAD SIDES MAY BE ENERGIZED IN
THE OPEN POSITION
NEMA 3R
Junction Box
Black - L1
Red - L2
Green - Ground
Enphase IQ Trunk Cable
Q-12-240
#12AWG THHN-THWN-2
UL 9703
Grounding Conductor
to be bare #8 Awg
#X-IQ-AM1-240
Solar Combiner Box
240V
PHOTOVOLTAIC SYSTEM
! AC DISCONNECT !
RATED AC OUTPUT CURRENT: 29.04A
NOMINAL OPERATING VOLTAGE: 240VAC
2 Circuits
10/15A Breaker for Envoy
60A
Non-Fused
Disconnect
M
Godwin Engineering and
Design, LLC
8378 Foxtail Loop
Pensacola, FL 32526
D. Chad Godwin, PE
Chad@godwineng.com
01/05/2022
KG
.
.
Green Ready
4705 Lena Rd. Unit 104
Bradenton, FL 34211
833-478-6797
In Case of Emergency Call
Green Ready LLC
at 833-478-6797
In Case of Emergency Call
Green Ready LLC
at 833-478-6797
Customer Info:
E-2
Date:
Drawn by:
Revised by:
Rev #: 00
Rev Date:
Page:
GEC NOTES
- Ungrounded system per 690.41(A)(4)
- GEC must be installed per 250.64
- GEC must be continuous un-spliced or irreversibly spliced from
inverter to existing service ground system or continuous from the
arrays to the existing service ground system.
- GEC must be min #8 AWG and installed in conduit
- If GEC is not in conduit, it must be #6 min
Install will be done to Manufacturer Spec
Including the label below
Edward June
8612 Cobblestone DR
Fort Pierce, FL
34945
Inverter Type:
Enphase IQ7PLUS-72-2-US
PV Panel:
(24)
DNA-120-MF26-360W
Total Wattage:
8,640W
System meets the grounding requirements of NEC 690.43
All Labels & Markings for photovoltaic system will be
reflective and meet all requirements for NFPA 11.12
Disconnects will be Visible, lockable, adjacent to
and within 10' of utility meter
Note:
-Subject PV Systems has been designed
to meet the requirments of the NEC 2017,
and those set forth by the Florida Solar
Energy Center Certification, Including
Maximum Number of Module Strings,
Maximum number of modules per string,
Maximum Output, Module Manufacturer and
model number, inverter manufacturer and model
number, as applicable.
Rapid Shutdown Built in
Per Code NEC 690.12
Conductors have a min
ampacity of 60 amperes
Per Code NEC 230.79(D)
PV AC disconnect is
lockable in the open position
per code NEC 705.22(7)
Labels will be placed
in the correct location
Per Code NEC 690.56(B),
690.56(C), & 690.53
Metallic conduits, raceways or flexible metal conduit
exceeding 6 feet in length are not permitted in accordance
with NEC article 690.31(G).
Include required label for metallic raceways and conduits to
sheet E-1 per NEC article 690.31(G)(3).
Add required label to sheet E-1 per NEC article 705.10.
Include required label to sheet E-1 per NEC article 705.12(B)
Photovoltaic AC disconnect shall be capable of being locked
in the open position per NEC article 705.22(6).
Photovoltaic AC Overcurrent protection shall be located
within 10 feet of the point where conductors are connected to
the service per NEC 705.31.
705.12(B)(3)
705.12(B)(2)(3)(b)
NEC 705.10 A permanent plaque or directory, denoting the location of
all electric power source disconnecting means on or in the premises, shall
be installed at each service equipment location and at the location(s) of
the system disconnect(s) for all electric power production sources capable
of being interconnected. One sign required for each PV system.
-Markings Shall Be reflective, Weather Resistant and suitable for the environment.
-Markings Shall be red with white lettering with minimum 3
8" Capital Letters
Disconnect means shall be provided for all
disconnecting all ungrounded conductors that supply
or pass through the building or structure Per Code
2017 NEC Section 225.31 & Section 225.32
In compliance with NEC
250.58, NEC 690.8,
NEC 250.24, NEC250.24(D)
NEC 690.31 (G)(3)
NEC 690.35
E04. Construction documents specify PV system circuits
installed on or in buildings include a rapid shutdown function
that controls specific conductors in accordance with NEC
article 690.12.
E05. These construction documents specify that a label is
provided with the method to initiate rapid shut down per
690.12(4).
E06. Construction drawings specify buildings or structures
with both utility service and a PV system, complying with NEC
article 690.l2 shall have a permanent plaque or directory
including the following wording: “PHOTO VOLTAIC SYSTEM
EQUIPPED WITH RAPID SHUTDOWN” as per NEC article
690.56 (C).
E07. Construction documents specify PV power circuit labels
shall appear on every section of the wiring system that is
separated by enclosures, walls, partitions, ceilings, or floors.
E08. Construction documents specify all warning sign(s) or
label(s) shall comply with NEC article 110.21 (B). Label
warnings shall adequately warn of the hazard. Labels shall be
permanently affixed to the equipment, and Labels required
shall be suitable for the environment.
Markings shall be placed on all DC Conduits, DC Combiners,
Raceways, Enclosures, Junction Boxes, and Cable Assemblies
at every 10', turns, and above and below penetrations in
compliance with NFPA
System is in complaince with FFPC 1:11.12 7th Edition.
Smoke Detectors will be added as per FBC 553.883
Permanent sticker added to disconnect
Apply to Main Disconnect
Figure 690.56(C)(1)(a) Label for PV Systems that
Shut down the array and the conductors leaving the array
Disconnect is in compliance 230.72
Supply side disconnect adjacent to Msp
Over Current Protection Device is "Next size up"
Based on Inverter Maximum Continuous Output
Current Rating 2017 NEC 240.4(B)
All Exterior equipment is A minimum of Nema-R3 Rated
All Interactive System(S) Points of interconnection
with other sources shall be marked at an accesible
location at the disconnecting means as a power
source and with the rated ac output current and the
nominal operating AC voltage. Per NEC 690.54
-A placard will be added with
instructions and locations to be
in compliance with 690.12,
690.56(B) and NEC 705.10
-All new equipment
located adjacent to
Meter on exterior wall
Everything will be built to Code without all Specifics labeled on plan
In compliance with 230.71
The Placard shall be permanently
riveted..., and shall be made of red,
weatherproof, hard plastic, with
engraved white block lettering.
WARNING:
DUAL POWER SUPPLY
SOURCES: UTILITY GRID AND
PV SOLAR ELECTRIC SYSTEM
WARNING:
INVERTER OUTPUT CONNECTION:
DO NOT RELOCATE THIS
OVERCURRENT DEVICE
PHOTOVOLTAIC SYSTEM
EQUIPPED WITH
RAPID SHUTDOWN
WARNING:
DEDICATED SOLAR PANEL DO
NOT CONNECT ANY OTHER
LOADS
WARNING:PHOTOVOLTAIC
POWER SOURCE
SOLAR PV SYSTEM EQUIPPED
WITH RAPID SHUTDOWN
TURN RAPID
SHUTDOWN SWITCH TO
THE "OFF" POSITION TO
SHUT DOWN PV
SYSTEM AND REDUCE
SHOCK HAZARD IN THE
ARRAY.
SOLAR ELECTRIC
PV PANELS
3/8 IN MIN. TEXT
3/16 IN MIN. TEXT
! WARNING !
POWER SOURCE OUTPUT CONNECTION:
DO NOT RELOCATE THIS OVERCURRENT
DEVICE
Plans Satisfy NEC 250.94 & NEC250.53(A)(2)
8
50
Combiner box in compliance
Per Code NEC 705.12
2* 20A < 125A
*No other loads to be added
Load side connection will be done in Meter Main Combo Located Outside
Note:
-All wiring to meet the 2017 NEC and
Florida electric codes.
60A Disconnect
-Type of conduit to be determined
on site by contractor.
Godwin Engineering and
Design, LLC
8378 Foxtail Loop
Pensacola, FL 32526
D. Chad Godwin, PE
Chad@godwineng.com
1
Iron Ridge FF2
17'
14'
Splice Bar
4
8
Iron Ridge UFO's
34
52
8
Iron Ridge Sleeves/End Caps8
Iron Ridge Ground Lugs
1
2
Iron Ridge XR-100 Rail
DNA-120-MF26-360W
Enphase IQ7PLUS-72-2-US
24
24
Roof Top Combiner
Meter Main
1 Enphase Combiner Box
1 40A Breaker
60A Non-Fused Disconnect
2 20A 2P Breaker
3'-5"
5'-9"
R-1
# Modules (24)
Pitch: 22°
Azimuth: 277°
21'-1"
37'-3"
62'-3"
12'-0"
9'-1"
3'-10"
L L L L L L L L L
L L L L L L L L
L L L L L L L
L L L L L L L
L
L
L
2' Gutter
01/05/2022
KG
.
.
Green Ready
4705 Lena Rd. Unit 104
Bradenton, FL 34211
833-478-6797Customer Info:
S-1A
Date:
Drawn by:
Revised by:
Rev #: 00
Rev Date:
Page:
Inverter Type:
PV Panel:
Racking:
Total Wattage:
Roof Type:
Wind Load:
Fastener Type:
Iron Ridge XR-100
Enphase IQ7PLUS-72-2-US
(24) DNA-120-MF26-360W
8,640W
Composition Shingle
20 to 27 Deg
Use 5/16" Dia 4.75" Lags
Install will be done to Manufacturer Spec
Edward June
8612 Cobblestone DR
Fort Pierce, FL
34945
Plans satisfy zones FBC-1510.7.1
L Proposed Mounting locations
Max cantilever is 24" as per manufacturer spec.
Max Cantilever = Max Span * (1
3)=72"*(1
3)=24"Zone 1, 2e, 2r & 3:
aptos solar technologyTMSolar for InnovatorsDesigned & Engineered in Silicon Valley360W l 355W l 350WPatented DNATM technology boosts power r;u=oul-m1;şlo7Ѵ;;L1b;m17-m1;7 vrѴb| 1;ѴѴ |;1_moѴo] b|_ Ɩ Ѵ|u-Ŋ|_bm0v0-uv-ѴѴov=ouѴ;vvu;vbv|-m1;-m7lou;r_o|omcaptureOur DNATM"rѴb|;ѴѴ";ub;vblru;vvb;Ѵ1ol0bm;v-7-m1;7voѴ-u|;1_moѴo]b;v|ol-blb;r;u=oul-m1;ĺur-|;m|;7Dual Nano Absorber (DNATM) Technology allows the panel to or;u-|; -| _b]_Ŋ;L1;m1b;v bm ;|u;l; |;lr;u-|u;vĺom|-1|ouv-Ѵ;v|;-l|o7-|oѴ;-umlou;-0o|ouѴbm;o=_b]_Ŋ;L1b;m|voѴ-ur-m;Ѵvĺ7;-ѴvoѴঞom=ou-rrѴb1-ঞomv-@;1|;70v_-7bm]ѴѴŊ0Ѵ-1h7;vb]m=ourubvঞm;-;v|_;ঞ1vo;1;vvb;vbѴ;u0vvbm]ouub00omv!o0v| ruo71| 7;vb]m bv u;vѴb;m| bm ;|u;l;;-|_;uĺ&r|oƔƓƏƏ-vmoѴo-7-m7ƑƐƏlr_bm7vr;;7v30 Year Warranty3140 De La Cruz Blvd., Ste 200Santa Clara, CA 95054 wwww.aptossolar.com info@aptossolar.com3X IEC StandardsLinear Performance Warranty 1 year10 years20 years93.2%87.8%90.7%80.2%Aptos WarrantyIndustry Standard98%97%30 years25 years76.7%83.7%ƳƑĺƔѷƳƓĺƐѷƳƓĺƖѷƳƔĺƕѷ85.1%82.4%Standard Warrantyrঞom-Ѵ|;m7;7)-uu-m|RETC Top Performer!;vb7;mঞ-ѴѴoll;u1b-Ѵ120TMDNOvoDoro_bSolar for InnovatorsѴ;1|ub1-Ѵ"r;1bC-1ঞomv"$u-|;7|r|mpp (W)o7Ѵ;L1b;m1r;mbu1b|(oѴ|-];((Ő(ő"_ou|bu1b|uu;m|" (A)!-|;7(oѴ|-];(mmpŐ(ő!-|;7(oѴ|-];mmp (A)ƒѵƏ) ƒƔƔ) ƒƔƏ)ƐƖĺƕƒѷƐƖĺƓѵѷƐƖĺƐѶѷƓƏĺѵ ƓƏĺƓ ƓƏĺƑƐƐĺƑƓƒƒĺѶƐƏĺѵѵƐƐĺƐƓƒƒĺѵƐƏĺƔƕƐƐĺƏƓƒƒĺƓƐƏĺƓѶ"|-m7-u7$;v|om7bঞomv=ou=uom|Ŋ=-1;o=r-m;ѴĹƐƏƏƏ)ņlƑķƑƔŦķl;-vu;l;m|m1;u|-bm|<ƒѷ$;lr;u-|u;o;L1b;m|v$;lr;u-|u;o;L1b;m|vmmp$;lr;u-|u;o;L1b;m|vsc$;lr;u-|u;o;L1b;m|v(oul-Ѵr;u-ঞm];ѴѴ$;lr;u-|u;Ő$őŊƏĺƒѵѷƳƏĺƏƔѷņŦŊƏĺƑƖѷņŦƓƓŦ$;v|r;u-ঞm]om7bঞomv-bll";ub;v
v;-bll"v|;l(oѴ|-];-bllo-7-r-1b|Ő;u&ƐƕƏƒő
bu;;u=oul-m1;Ѵ-vvƑƏƐķƔƏƏ( Ő&şőƔƓƏƏ"moo-7ņƑƐƏlr_)bm7!-ঞm]Ѵ-vvņ$r;Ɛ-1h-]bm]omC]u-ঞomNumber of Modules per Palletl0;uo=-ѴѴ;|vr;uƓƏ[ĺom|-bm;u-ѴѴ;| bl;mvbomv-ѴѴ;|);b]_|Őh]őƒƏƑѵƐƕƓƏ*ƐƐƓƏ*ƐƐѵƔѵƓƏom|-bm;u);b]_|Őh]őƐѵѵƓƏ;1_-mb1-Ѵuor;uঞ;v;ѴѴ$r;Glass
u-l;m1ঞomo bl;mvbomv|r|-0Ѵ;omo1uv|-ѴѴbm;ƒĺƑllķ-mঞŊu;Y;1ঞom1o-ঞm]ķ_b]_|u-mvlbvvbomķѴobuomķ|;lr;u;7]Ѵ-vvmo7b;7ѴlbmlѴѴoѵѶƐƕƔѵ*ƐƏƒƖ*ƒƔllƓllƑŐ&őƐƑ)ķƒƖĺƒƕbmĺŐƐƑƏƏllő);b]_|-0Ѵ;;m]|_m1-rvѴ-m|ƓƔĺƐƖѴ0vĺŐƑƏĺƔh]őƐƑƏƏllAptos Solar Technology reserves the right to make specification changes without notice120TMDNaptos solar technologyTM35mm1039mm1756mm800mm1471mmDNA-120-MF26-360WDNA-120-MF26-355WDNA-120-MF26-350WI-V Curve ƏƑƓ6ѶƐƏƐƑƐƏƑƏƒƏƓƏƔƏƒѵƏ);uঞC1-ঞomvUL61730-1, UL61730-23535
Tech BriefSolar Is Not Always SunnyOver their lifetime, solar panels experience countless extreme weather events. Not just the worst storms in years, but the worst storms in 40 years. High winds capable of ripping panels from a roof, and snowfalls weighing enough to buckle a panel frame. XR Rails are the structural backbone preventing these results. They resist uplift, protect DJDLQVWEXFNOLQJDQGVDIHO\DQGHIÀFLHQWO\transfer loads into the building structure. Their superior spanning capability requires fewer roof attachments, reducing the number of roof penetrations and the amount of installation time.XR Rail FamilyForce-Stabilizing CurveSloped roofs generate both vertical and lateral forces on mounting rails which can cause them to bend and twist. The curved shape of XR Rails is specially designed to increase strength in both directions while resisting the twisting. This unique feature ensures greater security during extreme weather and a longer system lifetime.Compatible with Flat & Pitched RoofsRoof Mount utilizes XR Rails, along with optional all-in-one attachments, WRVHFXUHV\VWHPVÁXVKagainst residential roofs.Roof Mount utilizes XRRails, along with optionalall-in-one attachments,WRVHFXUHV\VWHPVÁXVKagainst residential roofs.Corrosion-Resistant MaterialsXR Rails are compatible with FlashFoot and other pitched roof attachments.IronRidge offers a range of tilt leg RSWLRQVIRUÁDWroof mounting applications.All XR Rails are made of 6000-series aluminum alloy, then protected with an DQRGL]HGÀQLVK$QRGL]LQJSUHYHQWVVXUIDFHand structural corrosion, while also providing a more attractive appearance. XR Rail Family7KH;55DLO)DPLO\RIIHUVWKHVWUHQJWKRIDFXUYHGUDLOLQWKUHHWDUJHWHGVL]HV(DFKVL]HVXSSRUWVVSHFLÀFdesign loads, while minimizing material costs. Depending on your location, there is an XR Rail to match. © 2020 IronRidge, Inc. All rights reserved. Visit www.ironridge.com or call 1-800-227-9523 for more information. Version 1.20Tech BriefRail SelectionThe table below was prepared in compliance with applicable engineering codes and standards.* Values are based on the following criteria: ASCE 7-16, Gable Roof Flush Mount, Roof Zones 1 & 2e, Exposure B, Roof 6ORSHRIWRGHJUHHVDQG0HDQ%XLOGLQJ+HLJKWRIIW9LVLW,URQ5LGJHFRPIRUGHWDLOHGFHUWLÀFDWLRQOHWWHUVLoadRail SpanSnow (PSF) Wind (MPH) 4’ 5’ 4” 6’ 8’ 10’ 12’None90120140XR10 XR100 XR100016020901201401603090160409016080 160120 160XR100XR100 is the ultimate residential mounting rail. It supports a range of wind and snow conditions, while also maximizing spans up to 10 feet.• ·VSDQQLQJFDSDELOLW\• Heavy load capability• &OHDU EODFNDQRGL]HGÀQLVK• Internal splices availableXR10;5LVDVOHHNORZSURÀOHPRXQWLQJrail, designed for regions with light or no snow. It achieves spans up to 6 feet, while remaining light and economical.• ·VSDQQLQJFDSDELOLW\• Moderate load capability• &OHDU EODFNDQRGL]HGÀQLVK• Internal splices availableXR1000XR1000 is a heavyweight among VRODUPRXQWLQJUDLOV,W·VEXLOWWRKDQGOHextreme climates and spans up to 12 feet for commercial applications.• ·VSDQQLQJFDSDELOLW\• Extreme load capability• &OHDUDQRGL]HGÀQLVK• Internal splices available;HISLPZTLHU[[VILHZPTWSPÄLKZWHUJOHY[MVYJVU]L`PUNNLULYHSYHPSJHWHIPSP[PLZ<ZLHWWYV]LKJLY[PÄJH[PVUSL[[LYZMVYHJ[\HSKLZPNUN\PKHUJL
GODWIN ENGINEERING AND DESIGN, LLC
8378 Foxtail Loop, Pensacola, FL 32526 | (850)712-4219 | chad@godwineng.com
January 6, 2022
To: St. Lucie County Building Division
2300 Virginia Avenue
Ft. Pierce, FL 34982
Re: June – Residential PV Roof Mount Installation
8612 Cobblestone Dr.
Fort Pierce, FL 34945
Plan Reviewer,
This letter is regarding the installation of a new roof mounted Solar PV System on the existing
residential structure at the address above. I have reviewed the attachment plan and have
determined that the roof mounted PV system is in compliance with the applicable sections of the
following Codes as amended and adopted by the jurisdiction:
2020 Florida Building Code 7th Edition, FBC
ASCE 7 Min. Design Loads for Buildings & Other Structures
Per 2020 FBC, the Roof Mounted PV system will be subject to the following design criteria:
Design Wind Speed(Vult) - 160mph 3sec gust, Exposure Category – B
The PV System consist of the modules, railing, and connection hardware. The system will add a
dead load of approximately 3 psf to the roof.
The existing roof covering is Asphalt Shingle with min. ½” plywood decking and 2” x 4” roof trusses
24” O.C. The roofing, decking, and roof trusses are in good condition. The existing structure will be
adequate for supporting the additional PV dead load and wind loads.
The securement method of the PV system is to be flush mounted to the asphalt shingle roof with the
Ironridge railing and flashings/attachments. The attachments can be attached up to 72” apart in
roof zones 1, 2e, 2r, & 3. The mounts should be staggered, where possible, to allow distribution of
the design loads evenly to the structure. The mounts shall be installed with a min. 5/16” lag screw
with minimum 2-5/16” thread length.
Please see attached documents and contact me should you have any questions.
Sincerely,
D. Chad Godwin, PE 81360
Exp. 02/28/2023
Risk Category II Table 1.5-1 Wind Speed (asd)124 mph FRC R301.2.1.3
Basic Wind Speed (Ult)160 mph Figure 26.5-1B Effective Wind Area 19.66 ft2 26.20
Roof Angle Wind Directionality Kd 0.85 Table 26.6-1
Roof Type Hip Topographic factor Kzt 1.00 26.8 or 26.8.2
Exposure Cat.B,C, or D B Section 26.7 Ground Elevation Factor Ke 1.00 Table 26.9-1
Mean Roof Height h 15.00 ft Velocity Exposure Coefficient Kz 0.70 Table 26.10-1
Roof attachment Array Edge Factor gE 1.50 29.4.4 *Modules are considered Exposed
Rafter/Truss Spacing 24 in O.C.Solar Panel Equalization Factor ga 0.68 Fig. 29.4-8
No. of Rails 2 Velocity Pressure qh 23.40 psf qh=0.00256 KzKztKdKeV2
No. of Modules - Portrait 24 Added Safety Factor 1.2
No. of Modules - Landscape 0 Allowable Pullout per mount 859.2 lbs
Module Model Number 0.4h or 0.6h 6.00 ft Flat - 0.6h, Gable, Hip - 0.4h
bldg. least horizontal dim (typ.)360 in 10% of least horizontal dim 3.00 ft
Elevation <1000 ft Roof Zone Set Back a 3.00 ft
Est. # of attachment points 34 h2 5 in Not > 10in(panel height above roof)
2h2 10 in *min distance array shall be from the roof edge, Gable Ridge, or hip ridge
24 0.25 in min gap between all panels but not > 6.7ft
Wmod 45 lbs 3.41 ft d1 1.00 ft Horizontal distance orthogonal to panel edge
Wmods 1085 lbs 5.76 ft d2 0.25 ft Horizontal distance from edge of one panel to the nearest edge in the next row
Wmic 96 lbs 19.66 ft2 0.5h 7.50 ft *modules are considered exposed that are within 1.5Lp from roof edge
WPV rail 18 lbs
Wtotal 1198 lbs Ultimate Allowable
AT 471.93 ft2 113.4 75.6 Eq.1 Point Load = Roof Zone psf * TA
DPV 2.54 psf -113.4 -75.6 Eq.2 TA = (Module Length /2) * Max Span
Weight/attachment 35.2 lbs Eq.3 *Max span Equation, SF = Allowable pullout / Point Load
Eq.4 Max Span = Allowable Pullout / (SF * Roof Zone psf * L/2)
1 2e 2r 3 0 0 a)
GCp - Uplift -1.3 -1.8 -1.8 -1.8 #N/A #N/A
GCp - Down 0.7 0.7 0.7 0.7 #N/A #N/A b)Allowable Module load ratings are determined by SF = 1.5
p = qh(GCp)(gE)(γa)-28.6 -40.6 -40.6 -40.6 #N/A #N/A psf 29.4-7
p = qh(GCp)(gE)(γa)16.8 16.8 16.8 16.8 #N/A #N/A psf 29.4-7
Max Allowable Span 6 6 6 6 #N/A #N/A ft *notes
Max Cantilever (in)24 24 24 24 #N/A #N/A Max span * 33% (in)
ASCE 7-16 CHAPTER 29 WIND LOADS - Rooftop Solar Panels Minimum Design Loads - Part 1: Enclosed(Gable,Hip,Flat h<60ft, 0°<θ<45°)
Notes
PV Attachment - Results
Total Weight
Total Area
Dead Load
Array
Width
Micro/optimizer
Length
PV Rail
Module Area
PV Dead Load Module and Racking Specs
# of Modules
The Max span between attachment points must not exceed the rail spans provided by racking manufacture.
Wind Load Paramaters
21° to 27°
DNA-120-MF26
Roof Zones - Hip 21° to 27°
10% of least hor. Dim. Or 0.4h, whichever is smaller, but not less than either 4% of Least hor. Or
3ft. (flat roof - 0.6h)
Module
Dimensions, LxWxH (in)
Load Rating - Snow(psf)
Load Rating - Wind(psf)
Wind Load Parameters - Inputs
5/16" x 4.75" Lag Screw
69.13 x 40.9 x 1.37
Module load ratings