Loading...
HomeMy WebLinkAboutMechanical Plans Duplex Type 2A/C GENERAL NOTES 1- DRAWINGS ARE DIAGRAMMATIC. DO NOT SCALE DRAWINGS FOR EXACT LOCATION OF EQUIPMENT, PIPING, DUCTWORK, ETC. THESE DRAWINGS ARE NOT INTENDED TO SHOW EVERY MINOR DETAIL, BUT THE CONTRACTOR SHALL FURNISH AND INSTALL ALL ITEMS REQUIRED FOR A COMPLETE AND ACCEPTABLE WORKING INSTALLATION. 2- ALL WORKMANSHIP AND MATERIALS SHALL BE IN STRICT ACCORDANCE WITH APPLICABLE NATIONAL, STATE, AND LOCAL CODES, RULES AND REGULATIONS. INSTALLATIONS OF THE NFPA, ASHRAE, AND SMACNA. 3- ALL MATERIALS SHALL BE NEW AND BEAR THE UL LABEL WHERE APPLICABLE. 4- PROVIDE THERMOSTAT CONTROLS ON ALL FANS THAT EXHAUST MECHANICAL AND ELECTRICAL ROOMS. 5- PROVIDE TURNING VANES IN ALL 90 DEGREE ELBOWS. 6- MOUNT THERMOSTAT SENSORS 5' ABOVE FINISHED FLOOR. 7- NON FIRE -RATED CEILING SUPPLY DIFFUSERS AND RETURN AIR GRILLES TO BE ALUMINUM. ALL SUPPLY DIFFUSERS SHALL HAVE OPPOSED BLADE DAMPERS. 8- ALL CUTTING, PATCHING, STRUCTURAL STEEL, WEATHER PROOFING, PAINTING AND WALL OPENINGS SHALL BE BY THE GENERAL CONTRACTOR. 9- ALL OPENINGS IN THE BUILDING STRUCTURE, FOR DUCTWORK, PIPING, ETC. TO BE 1/2" LARGER(ON ALL SIDES) THAN THE OUTSIDE DIMENSIONS. FILL VOIDS WITH FIRE RETARDANT SILICONE FOAM.(I.E CHASE -FOAM CTC PR-855 BY CHASE TECHNOLOGY CORP.) 10- PROVIDE SMOKE DETECTORS IN ALL SUPPLY AIR DUCTS FOR FANS AND AHU'S SERVING A COMMON PLENUM OF 2000 CFM OR ABOVE. 11- PROVIDE FIRE DAMPERS IN ALL DUCTS PENETRATING FIRE RATED WALLS, PARTITIONS, FLOORS OR ROOF SLABS. 12- PROVIDE INDEPENDENT TEST AND BALANCE OF ALL MECHANICAL EQUIPMENT AND AIR DEVICES, EXTRACTORS, DAMPERS, AHU'S, & FANS. PROVIDE FINAL BALANCING FOR ALL SYSTEMS TO THE SATISFACTION OF THE OWNER. 13- CONTRACTOR SHALL PROVIDE ALL LABOR, MATERIALS, TOOLS AND EQUIPMENT TO INSTALL A COMPLETE AND OPERATING A/C SYSTEM. 14- CONTRACTOR TO PROVIDE ALL REQUIRED HVAC PERMITS. 15- CONTRACTOR SHALL PROVIDE EQUIPMENT OF THE CAPACITIES SCHEDULED ON PLAN. 16- COMPLY ^WITH ^NFPA^ 90A AND ALL APPLICABLE CODES. THIS IS THE / 17- SUPPLY, EXHAUST, OUTSIDE AND ANY EXPOSED AIR DUCTWORK SHALL BE SHEET METAL CONSTRUCTION, INSTALLED IN ACCORDANCE WITH ASHRAE AND SMACNA STANDARDS. FLEX DUCT SHALL BE OMNI SERIES OR APPROVED EQUAL. 10- THERMOSTATS. THE ELECTRICAL SUB -CONTRACTOR SHALL PROVIDE ALL SWITCHES, DISCONNECTS AND CONTROL WIRING. THERMOSTATS SHALL BE APPROVED BY EQUIPMENT MANUFACTURER. 19- ALL DUCT SIZES ARE CLEAR INSIDE DIMENSIONS. 20-PROVIDE FLEXIBLE DUCT CONNECTORS TO ALL FANS, A/C UNITS OR MECHANICAL EQUIPMENT. 21- PROVIDE MAINTENANCE AND OPERATION MANUALS ON ALL MECHANICAL EQUIPMENT OR SYSTEMS. PROVIDE FIVE SETS OF SUBMITTALS ON ALL HVAC EQUIPMENT. 22- TO THE BEST OF THE ENGINEER'S KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM BUILDING CODES AND THE APPLICABLE FIRE- SAFETY STANDARDS AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH THIS SECTION AND CHAPTER 633, FLORIDA STATUTES. Al 23- DUCTS IN PRIVATE GARAGE AND DUCTS PENETRATING THE WALL OR CEILINGS SEPARATING THE DWELLING UNIT FROM THE GARAGE, INCLUDING ITS ATTIC ` AREA, SHALL BE CONSTRUCTED OF SHEET STEEL OF LESS THAN 0.019 INCH IN, THICKNESS AND SHALL HAVE NO OPENINGS INTO THE GARAGE. J V NOTES ON DRAWINGS & SCHEDULES ® REVISIONS AHU AIR HANDLING UNIT rAD' ACCESS DOOR (DUCT) A_PJ ACCESS PANEL (CELING MOUNTED) AC PACKAGED TERMINAL AIR CONDITIONI AFF ELEVATION/ ABOVE FINISHED FLOOR BAS BUILDING AUTOMATION SYSTEM (CONTRACTOR BE BOTTOM ELEVATION LH CHILLER CV CONTROL VALVE DH DUCT HEATER EF EXHAUST FAN FM FLOW MEASUREMENT VENTURI —� CA OUTDOOR AIR RA RETURN AIR RBJ RUN BETWEEN JOISTS RV ROOF VENTILATOR SA SUPPLY AIR SF SUPPLY FAN TB VARIABLE AIR VOLUME TERMINAL BOX C CONDENSATE DRAIN LINE CHS CHILLED WATER SUPPLY CHR CHILLED WATER RETURN S.A. SHOCK ABSORBER S.O.V. SHUT-OFF VALVE --iII--- UNION JOINT —I I— FLANGE JOINT TEE - BRANCH OUT OF TOP -e -E TEE - BRANCH OUT OF BOTTOM —� ELBOW - UP —0 ELBOW - DOWN TRANSITIONS, F.O.T. = FLAT ON TOP OR F.O.H. = FLAT ON BOTTOM HVAC DESIGN CHART AC LEGEND AND ABBREVIATION --- DIRECTION OF FLOW FLEXIBLE CONNECTION Q THERMOMETER (o-so) PRESSURE GUAGE WITH GUAGE COCK -� (DIAL RANGE) ®— CEILING SUPPLY AIR DEVICE —ARROW DENOTES DIRECTION OF THROW zaxi2 RECTANGULAR DUCT SIZE DESIGNATION. FIRST DESIGNATION IS SIDE SHOW 2+xi2 FLAT OVAL DUCT SIZE DESIGNATION 07Jj TYPE 316 STAINLESS STEEL EXHAUST DUCT WITH ALL WELDED JOINTS AND FITTINGS TURNING VANES (NUMBER OF VANES SHALL BE BASED ON ACTURAL DUCT SIZE & NOT ON SCHEMATIC SYMBOL ON DRAWING RETURN OR OUTSIDE AIR DUCT ® DISCHARGE OR SUPPLY DUCT EXHAUST FAN OR GRILLE FLEXIBLE DUCT CONNECTION MANUAL VOLUME DAMPER o FIRE DAMPER WITH DUCT ACCESS DOOR DN DROP IN DIRECTION OF AIR FLOW R RISE IN DIRECTION OF AIR FLOW FLEXIBLE AIR DUCT SPIN COLLAR WITH MANUAL DAMPER AUTOMATIC DAMPER (MOTORIZED OR PNEUMATICALLY OPERATED AS NOTED) GLOBE VALVE PRESSURE RELIEF VALVE HVAC DESIGN REQUIRES: YES NO DUCT SMOKE DETECTOR FIRE DAMPER(S) SMOKE DAMPER(S) FIRE RATED ENCLOSURE FIRE RATED ROOF/FLOOR FIRE RATED CEILING ASSEMBLY FIRE STOPPING SMOKE CONTROL IJ P T� THERMOSTAT SD SMOKE DETECTOR HS HUMIDISTAT OR HUMIDITY SENSOR ELEVATION ELECTRIC DUCT HEATER WITH x j CONTROL AND TERMINAL CABINET. =y (DASHED LINE INDICATES REQUIRED CLEARANCE SPACE) —[><*— GATE VALVE fSWING TYPE CHECK VALVE BUTTERFLY VALVE (TAPPED LUG BODY) BALL VALVE C® VENTURI FLOW METER _>�,— PRESSURE REDUCING VALVE ---I y I— STRAINER MOTORIZED 3 WAY VALVE DOUBLE WALL DUCT MYLAR ENCAPSULATED K - 27 DUCT STATIC • SP PRESSURE SENSOR --�i- LIFT TYPE CHECK VALVE - PIPE REDUCER / INCREASER --�� — PIPE WELL EQUIPMENT DESIGNATION SYMBOL UC DOOR UNDERCUT CFM AND AIR 85 FLOW DIRECTION DESIGNATION SQUARE TO ROUND / OVAL TRANSITION HAMMOND & ASSOCIATES, INC. CONSULTING ENGINEERS 18800 N.W. 2ND AVENUE, SUITE 216 ht ¢ MIAMI, FLORIDA 33169 wri TEL: (305) 651-8522 FAX (305) 651-3376 ERIC J. HAMMOND P.E. MECHANICAL / ELECTRICAL ENGINEER ar A.F.G. MT. ABOVE FINISH GRADE MOUNT P.E. #3 9048 EB 531515 Rrck e MTD. MOUNTED U.O.N. UNLESS OTHERWISE NOTED (I C WT WATERTIGHT TYP. TYPICAL 154 Krog Street, #125 FIN. FINISH Atlanta, GA 30307 404-218-8460 ETR EXISTING TO REMAIN R.E. REMOVE EXISTING R REMOVE N NEW ETR EXISTING TO REMAIN — — — EXISTING NEW EXISTING TO BE REMOVED Q Z LG� Idd J fl- irs a °' � M z p z Z a� W W 0 o_J 0 Q oco W o Z �- W Ln W Q Z Q W 0 stamp: ERIC HAMMOND, PE EB 5315-PE 39048 revisions No. Description Date 1Q BLDG. DEPT. 01-27-21 COMM sheet title: MECHANICAL GENERAL NOTES Et SYMBOLS project number: 19-049 drawing date: 11.11.2020 scale as noted sheet number: m0=01 0 NOT ISSUED FOR CONSTRUCTION ❑ ISSUED FOR CONSTRUCTION DRAWING LEGEND: ACCU AIR COOLED CONDENSING UNIT EF EXHAUST FAN AHU AIR HANDLING UNIT T THERMOSTAT MECHANICAL KEY NOTES: 18 2 UP Y AI D CT R H —1 IN TH G AGE ELOW. 16X12 RETURN AIR DUCT FROM AHU-1 IN THE GARAGE BELOW. 30X18 RETURN AIR GRILLE ON WALL (TITUS 355R) 1250 CFM. U CAMMU3 i rHry tL_r—) nv 1_,LJLI EXHAUST DUCT IN CEILING. 5O LOCATION OF THE THERMOSTAT. ® 3/4" UNDERCUT DOOR. O LOUVERED DOOR. X X U T UCT IN HASE UP TO COND FLO CEILING. 1OX10 RETURN AIR GRILLE ON WALL (TITUS 355 R) 238 CFM. TO 6X8 MECHANICAL GENERAL NOTES: A. DOWNDRAFT COOKTOP SHALL PROVIDE WITH DUCT —FREE FILTER ACCESSORY KIT. DUPLEX TYPE 2 FIRST FLOOR MECHANICAL PLAN 1 /4 = V-0" HAMMOND & ASSOCIATES, INC. CONSULTING ENGINEERS 18800 N.W. 2ND AVENUE, SUITE 216 MIAMI, FLORIDA 33169 TEL: (305) 651-8522 FAX (305) 651-3376 ERIC J. HAMMOND P.E. MECHANICAL / ELECTRICAL ENGINEER P.E. #39048 EB 5315 Reviewed for Code C OMPliiance 12 Universal Engineering Sciences wrieht arrichl 11C 154 Krog Street, #125 Atlanta, GA 30307 404-218-8460 Q _Z dd J Q Z W 0 r� V 1 W tA N Q tJ V Z Q W V O stamp: ERIC HAMMOND, PE EB 5315-PE 39048 revisions I,- u7 o, M p Q Z p aCe UJ O OJ Ln W co oz w N z W M No. Description Date QBLDG. DEPT. 01-27-21 1 COMM sheet title: DUPLEX TYPE 2 FISRT FLOOR MECHANICAL PLAN project number: 19-049 drawing date: 11.11.2020 scale as noted sheet number: M1-02 ■ NOT ISSUED FOR CONSTRUCTION ❑ ISSUED FOR CONSTRUCTION DRAWING LEGEND: ACCU AIR COOLED CONDENSING UNIT EF EXHAUST FAN AHU AIR HANDLING UNIT T THERMOSTAT DUPLEX TYPE 2 THIRD FLOOR MECHANICAL PLAN 1 /4" = 1'-0" MECHANICAL KEY NOTES: 1� RETURN AIR DIFFUSERS ON CEILING. 18 REFRIGERANT LINES ON WALL SIZE PER MANUFACTURER'S 2� EXHAUST FAN(EF) IN CEILING WITH 6X6 EXHAUST DUCT. RECOMMENDATIONS �3 6X6 EXHAUST DUCT UP TO ROOFCAP ON ROOF. 19 REFRIGERANT LINES IN CEILING DOWN TO AHU-2 IN THE CLOSET/STORAGE. ® 16X12 SUPPLY DUCT IN CEILING UP TO AHU-2 IN THE CLOSET/STORAGE �0 REFRIGERANT LINES DOWN EXTERIOR WALL IN NEW LINE COVER. IN THIRD FLOOR. 21 AIR COOLED CONDENSING UNIT (ACCU) ON STAND. 0 14X12 RETURN AIR DUCT IN CEILING UP TO AHU-2 IN THE CLOSET/STORAGE 0 6X10 EXHAUST DUCT UP TO ROOFCAP ON ROOF. ROOM IN THE THIRD FLOOR. 4" DIAMETER EXHAUST DUCT UP TO ROOFCAP ON ROOF. 1 1 A L I N 9 FQ 8X6 RETURN AIR SIDEWALL GRILLE ON WALL (TITUSCFM. �35 R�)96 U 6X10 EXHAUST DUCT FROM SECOND FLOOR IN A CHASE UP TO CEILING . OFFSET 6.3 FEET TO THE LEFT WITHIN SECOND FLOOR CEILING BEFORE THIRD FLOOR CHASE. 10 LOUVERED DOOR. 11 24X12 RETURN AIR SIDEWALL GRILLE ON WALL (TITUS 355R) 680 CFM. 12 AIR HANDLING UNIT (AHU-2) ON STAND IN THE CLOSET/STORAGE. (13i 18X12 SUPPLY AIR DUCT FROM SECOND FLOOR. 12X12 OUTSIDE AIR LOUVER ON WALL (RUSKIN ELF6375DXD) 195CFM. NN TO AHU-1 M1-03 A. HAMMOND & ASSOCIATES, INC. CONSULTING ENGINEERS 18800 N.W. 2ND AVENUE, SUITE 216 MIAMI, FLORIDA 33169 TEL: (305) 651-8522 FAX (305) 651-3376 ERIC J. HAMMOND P.E. MECHANICAL / ELECTRICAL ENGINEER P.E. #39048 EB 5315 MECHANICAL GENERAL NOTES: ALL LOUVERS SHALL BE PROVIDED WITH 5/8" MESH X.040" (16X1) EXPANDED FLATTENED ALLUMINUM BIRD SCREEN IN REMOVABLE FRAME. B. ALL LOUVERS SHALL BE PROVIDED WITH MANUAL AND MOTORIZED DAMPERS. VENTILATION CALCULATIONS (LAUNDRY) EF-4 93 Pevie ed Yo, -K)c 6 AREA = LENGTH (L) X WIDTH (W) = 43 SQ.FT Ccmphan USING ASHRAE 62.1 2016 TABLE 6.5 Uo�sver�' — I?�- r,r,o- Sciences STORAGE AT 1 CFM/ SQ.FT AIR FLOW = AREA (A) X 1 CFM/SQ.FT EXHAUST AIR FLOW (A X 1) = 43 SQ.FT X 1 CFM/SQ.FT EXHAUST AIR FLOW (EF-4) = 43 CFM DUPLEX TYPE 2 SECOND FLOOR MECHANICAL PLAN 1 /4" = V-0" wri•ht war e ','rck i 'ecl 11C 154 Krog Street, #125 Atlanta, GA 30307 404-218-8460 J u7 Q M p z Z a� w W 0 o� C) to �u o a W �m a w tA N w Q J Z a W V O stamp: ERIC HAMMOND, PE EB 5315-PE 39048 revisions No. Description Date QBLDG. DEPT. 01-27-21 1 COMM sheet title: DUPLEX TYPE 2 SECOND Et ROOFTOP MECHANICAL PLANS project number: 19-049 drawing date: 11.11.2020 scale as noted sheet number: M1-03 0 NOT ISSUED FOR CONSTRUCTION ❑ ISSUED FOR CONSTRUCTION CHANGES MADE ON THE ENTRE `HEFT. 2\ DUPLEX TYPE 2 MECHANICAL ROOF PLAN M1-03) 1 /4" = 1'-0" HAMMOND & ASSOCIATES, INC. CONSULTING ENGINEERS 18800 N.W. 2ND AVENUE, SUITE 216 MIAMI, FLORIDA 33169 TEL: (305) 651-8522 FAX (305) 651-3376 ERIC J. HAMMOND P.E. MECHANICAL / ELECTRICAL ENGINEER P.E. #39048 EB 5315 Reviewed for Code Compliance ',_universal Engineering '91 1�ciences, wrieht a rhl 11C 154 Krog Street, #125 Atlanta, GA 30307 404-218-8460 Q Z ICU z W ILA W LA ton J 0 Z Q W V O r- un M Z p Q O 0 =3 V 0 w Ln �m 0z w V) z W stamp: ry 1 1 �yapY urn / C•`, / /Y �Y mow. '•` Lp' ERIC HAMMOND, PE EB 5315-PE 39048 revisions No. Description Date QBLDG. DEPT. 01-27-21 1 COMM sheet title: DUPLEX TYPE 2 MECHANICAL ROOF PLAN project number: 19-049 drawing date: 11.11.2020 scale as noted sheet number: M 1-04 0 NOT ISSUED FOR CONSTRUCTION ❑ ISSUED FOR CONSTRUCTION AIR CONDITIONING SYSTEM SCHEDULE AIR HANDLING UNIT AIR-COOLED CONDENSING UNIT SYSTEM UNIT TONS MAKE MODEL CFM WEIGHT E.S.P. FAN FAN UNIT ELECTRIC M.C.A MAX DIMENSION COMP. MAKE MODEL QTY FAN M.C.A MAX UNIT VOLTAGE WEIGHT DIMENSION CAPACITY (MBTU) UNIT (S)EER ENTERING AIR LEAVING AIR NO. NO. LBS H.P. FLA VOLTAGE HEATING FUSE WXLH(INCH) NO. RLA FUSE LBS WXLH(INCH) TEMP. TEMP. TOTAL SENS. AHU-1 /ACCU-1 3 TRANE TEM6AOC36 1350 155 0.5 0.5 4.3 208-230/1 /60 3.6 KW 24 25 27X22X52 TRANE 4TTR6036J1 1 13.6 18 30 200-230/1 /60 246 37X34X37 33.5 27.9 14.0 77 64.9 56.4 56.3 AHU-2/ACCU-2 5 TRANE TEM6AOD60 2125 181 0.5 3/4 6 208-230/1 /60 7.2 KW 51 60 27X22X54 TRANE 4TTR7060L 1 32 31 50 208-230/1 /60 312 37X34X45 54.7 43.2 14.0 77.3 65.1 56.5 56.4 NOTES: 1. THIS DESIGN IS TRANE 2. UNIT PERFORMANCE SHALL BE CERTIFIED IN ACCORDANCE WITH AHRI STANDARD 210/240. 6. PROVIDE UNIT DISCONNECT. 3. UNIT SHALL BE "UL/cUL" LISTED AND SHALL CONFORM TO NFPA 90A REQUIREMENTS. 7. PROVIDE TRANE OR APPROVE EQUAL 4. REFER TO THE PLANS FOR PIPING SYSTEM PLACEMENT, RETURN AIR, FRESH AIR DAMPER & OUTLET ARRANGEMENTS. 5. PROVIDE FILTER SECTION TO HOUSE 4" CARTRIDGE MERV 13 STANDARD. AIR BALANCE TABLE MARK AREA SERVED SUPPLY CFM RETURN CFM O/A CFM EXHAUST CFM BALANCE =(OA—EA)CFM AHU-1 KITCHEN/BR 1350 1250 100 100 0 AHU-2 BR/FAMILY ROOM 2125 1930 180 195 0 HAMMOND & ASSOCIATES, INC. CONSULTING ENGINEERS 18800 N.W. 2ND AVENUE, SUITE 216 ¢ MIAMI, FLORIDA 33169 TEL: (305) 651-8522 FAX (305) 651-3376 ERIC J. HAMMOND P.E. MECHANICAL / ELECTRICAL ENGINEER P.E. #39048 EB 5315 2 , wri het arhl 11C 154 Krog Street, #125 Atlanta, GA 30307 404-218-8460 �I z W 0 7A W 0C LA V) Q Z a W V O stamp: ERIC HAMMOND, PE EB 5315-PE 39048 revisions LC) o� �1- � M p Q Z p W � 0 0 o LLJ ca oz w N Z w I No. Description_ Date Al BLDG. DEPT 01-27-21 COMM sheet title: MECHANICAL SCHEDULES project number: 19-049 drawing date: 11.11.2020 scale as noted sheet number: M2eOO 0 NOT ISSUED FOR CONSTRUCTION ❑ ISSUED FOR CONSTRUCTION HANGER HANGERS MUST NOT DEFORM DUCT SHAPE HANGERS STRAPS- -HANGER RODS, WIR S 60" MAXIMUM OR STRAP - UNLESS FOOT �— � �._. A OF STRAP IS PLACED UNDER A CONCRETE ANCHORS D 7 BOTTOM REINFORCEMENT El :� , C HANGER STRAP —-HANGER ROD \ B EXPANSION SHIELDS SCREWS, "MIN. --- —-- SCREWS MAY BE BAND - J—z— OMITTED IF HANG ONE HALF -ROUND MAY BE USED � LOOPS IF DUCT SHAPE IS MAINTAINED LOAD RATEDFASTENERS--HANGER NUT- COUPLING RiAALTERNATE- -BAND OF SAMEI �AS HANGER ST HANGER ROD(Only CLEVIS HANGER FLAT IRON HANGER U-TYPE HANGER for wood const.) HANGER STRAP-- RETAINING CLIP ----HANGER ROD FASTENERS 6a C-CLAMP W/ RETAINING CLIP 6a C-CLAMP W/ LOCK NUT (OPTIONAL) WELDED STUDS STRAP HANGERS 24" DIA. 50" DIA.MAX. ,.o00A MAX. TA Ld or A _ SMACNA STANDARDS FOR ROUND SPIRAL AND. RECTANGULAR DUCTWORK. CENTER I -BEAM CLAMP SELF DRILLING ANCHOR TOP BEAM CLAMP 1 DUCT HANGING DETAIL 2 PIPE HANGING DETAIL M3.00 SCALE: N.T.S. I M3.00 SCALE: N.T.S. MIAMI DADE COUNTY APPROVAL 17-1226.24 REFER TO DADE COUNTY APPROVAL STANDARD FOR DESIGN TABLES UNIT DEPTH - �MAX. SIZE PER SCHEDULE z 12" MAX OVERHANG 4o o� o Q ' o � / L(1) '�-20 TOP OF ROOF THRU BOLT W/ FINISH NUT & WASHERS A/C UNIT WIDTH PER DESIGN TABLES CEILING STRUCTURE STANDARD SYSTEM: ROOF HOST STRUCTURE 18" TO 27" HEAVY SYSTEM: 24" TO 42" FIBERGLASS SUPPLY 4 ANCHORS PER PLATE BASE PLATE DUCT PLENUM STAND ASSEMBLY FRAME ASSEMBLY ELEVATION SCALE: N.T.S ISOMETRIC VIEW FLEX CONNECTION AIR HANDLING UNIT GENERAL NOTES: 7. PERMIT HOLDER SHALL VERIFY THE ADEQUACY OF THE EXISTING 1. THE SYSTEM DESCRIBED HERE HAS BEEN DESIGNED IN ACCORDANCE WITH THE FLORIDA BUILDING CODE FOR USE WITHIN VELOCITY HURRICAINE ZONE. STRUCTURE TO WITHSTAND SUPERIMPOSED LOADS. — - - WALL STRUCTURE 2. NO 33-1 /3% INCREASE IN ALLOWABLE STRESS HAS BEEN USED IN THE DESIGN 8. ALL EXTRUSIONS SHALL BE OF ALUMINUM ALLOY/TEMPER NOTED REFRIGERANT LINES OF THIS SYSTEM. HEREIN CONDENSATE DRAIN 3. POSITIVE AND NEGATIVE DESIGN PRESSURES CALCULATED FOR USE WITH THIS SYSTEM SHALL BE 9. ALL STEEL IN CONTACT WITH ALUMINUM SHALL BE PAINTED OR WITH TRAP DETERMINED BY OTHERS ON A JOB -SPECIFIC BASIC IN ACCORDANCE WITH THE GOVERNING CODE. PLATED, ET- 4. DIMENSIONS AND WEIGHT OF EACH A/C UNIT SHALL BE LIMITED TO THOSE SHOWN IN DESIGN 11 11NEOPRENE PAD SCHEDULES. 5. THE SYSTEM DETAILED HEREIN IS GENERIC AND DOES NOT PROVIDE INFORMATION FOR A SPECIFIC SITE, RETURN AIR PLENUM FOR SITE CONDITIONS DIFFERENT FROM THE CONDITIONS DIFFERENT FROM THE CONDITIONS DETAILED HEREIN, WITH 1 "X1 "X1 /4" ST A LICENSED ENGINEER OR REGISTERED ARCHITECT SHALL PREPARE SITE -SPECIFIC DOCUMENTS AND SUBMIT FOR ANGLE FRAME ONE -TIME NOTICE OF ACCEPTANCE IN CONJUNCTION WITH THIS DOCUMENT. 6, A/C STANDS SHALL BE PERMANENTLY LABELED WITH A MINIMUM OD ONE LABEL PER FRAME - RETURN AIR PLENUM ASSEMBLY CONTAINING THE FOLLOWING: BELOW AIR HANDLING UNIT METALLUM ENTREPRISES MIAMI-DADE PRODUCT CONTROL APPROVED. 3 ROOF MOUNTED CONDENSING UNIT DETAIL 4 TYPICAL AIR HANDLING UNIT DETAIL M3.00 SCALE: N.T.S. M3.00 SCALE: N.T.S. HAMMOND & ASSOCIATES, INC. CONSULTING ENGINEERS 18800 N.W. 2ND AVENUE, SUITE 216 MIAMI, FLORIDA 33169 TEL: (305) 651-8522 FAX (305) 651-3376 wri h t ERIC J. HAMMOND P.E. MECHANICAL / ELECTRICAL ENGINEER P.E. #39048 EB 5315 aar e arcki IIC 154 Kroll Street, #125 Atlanta, GA 30307 404-218-8460 Q _z J Ln un Q M- � M z®_ w ® J ® U W Un r ®z Ln z W N � ��J^^ V z Q Reviewed fear Code Compliance Universal Engineering Sciences stamp: CHANGES MADE ON THE ENTIRE '-;HEFT. ERIC HAMMOND, PE EB 5315-PE 39048 revisions No. Description Date QBLDG. DEPT. 01-27-21 1 COMM sheet title: MECHANICAL project number: 19-049 drawing date: 11.11.2020 scale as noted sheet number: 1 1� ® NOT ISSUED FOR CONSTRUCTION El ISSUED FOR CONSTRUCTION HAMMOND & ASSOCIATES, INC. CONSULTING ENGINEERS 18800 N.W. 2ND AVENUE, SUITE 216 MIAMI, FLORIDA 33169 TEL: (305) 651-8522 FAX (305) 651-3376 ERIC J. HAMMOND P.E. MECHANICAL / ELECTRICAL ENGINEER P.E. #39048 EB 5315 wrieht arhl 11C 154 Krog Street, #125 Atlanta, GA 30307 404-218-8460 a z ICULn � M � z Z Q IJJ W o� n O V W m Z W Ln N W N i a z <C W V O stamp: ERIC HAMMOND, PE EB 5315-PE 39048 revisions NO. Description Date QBLDG. DEPT. 01-27-21 1 COMM sheet title: MECHANICAL DETAILS CONTD. project number: 19-049 drawing date: 11.11.2020 scale as noted sheet number: M3*01 NOT ISSUED FOR CONSTRUCTION ❑ ISSUED FOR CONSTRUCTION ra JCAL NOTES D. LIGHTING PANELS 1. PROVIDE LIGHTING AND RECEPTACLES PANELS AS INDICATED ON THE PLANS AND AS SPECIFIED HEREIN. ALL PANELS SHALL BE DEAD FRONT, CIRCUIT BREAKER TYPE AND SHALL BEAR THE U.L. LABEL AS WELL AS MEET ALL APPLICABLE NEMA REQUIREMENTS. 2. ALL PANELS SHALL HAVE TYPEWRITTEN CIRCUITS DIRECTORIES MOUNTED INSIDE OF DOOR. 3. PANELS SHALL BE SUITABLE FOR THE SERVICE RATING INDICATED ON THE PANEL SCHEDULES. 4. ALL BREAKERS SHALL BE FULL SPACE, INDIVIDUAL FRAME TYPE. NO "PIGGYBACK" OR TANDEM BREAKERS WILL BE PERMITTED. E. SAFETY SWITCHES 1. SAFETY SWITCHES SHALL BE HEAVY DUTY TYPE FUSIBLE OR NON -FUSIBLE WITH POLES, AMPERE AND SERVICES RATINGS AS INDICATED ON THE PLANS. LUGS SHALL BE U.L. LISTED FOR CU. -AL. 2. ENCLOSURES FOR SAFETY SWITCHES SHALL BE NEMA 1, EXCEPT FOR SWITCHES MARKED "WP" (WEATHERPROOF) SHALL BE NEMA 4XSS. F. FUSES 1. ALL FUSES SHALL HAVE A 200,000 AMP RMS SYMETRICAL RATING UNLESS OTHERWISE NOTED. 2. FUSES RATED 0 TO 600 AMPS SHALL BE AS FOLLOW: a) CIRCUIT BREAKER PANEL PROTECTION-U.L. CLASS RK-1, DUAL ELEMENT(BUSSMANN "LOW PEAK" OR EQUAL). b) MOTOR CIRCUIT PROTECTION-U.L. CLASS RK-5, DUAL ELEMENT (BUSSMANN "FUSETRON" OR EQUAL). 3. FUSES RATED 601 AMPS OR LARGER SHALL BE U.L. CLASS L TIME DELAY (BUSSMANN "HI -CAP" OR EQUAL). G. SITE VISIT 1. BEFORE SUBMITTING A BID THE CONTRACTOR SHALL VISIT THE SITE AND DETERMINE CONDITIONS AT THE SITE AND ALL EXISTING STRUCTURES IN ORDER TO BECOME FAMILIAR WITH EXISTING CONDITIONS AND ELECTRICAL SYSTEMS WHICH WILL IN ANY WAY AFFECT THE WORK REQUIRED UNDER THE CONTRACT. THE CONTRACTOR SHALL INFORM THE ENGINEER IN WRITING OF ANY DISCREPANCIES FOUND DURING SAID SITE VISIT. NO SUBSEQUENT INCREASE IN CONTRACT COST WILL BE ALLOWED FOR ADDITIONAL WORK REQUIRED BECAUSE OF CONTRACTOR'S FAILURE TO FULFILL THIS REQUIREMENT. H. AS QUILTS 1. UPON COMPLETION OF PROJECT CONTRACTOR SHALL PROVIDE COMPLETE ASBUILT DRAWINGS, OPERATING AND MAINTENANCE MANUALS PER FBC EC-C405.6.4. PROVIDE CERTIFIED DOCUMENTS TO OWNER THAT LIGHTING CONTROLS MEEET DOCUMENTED PERFORMANCE CRITERIA OF SECTION C405 WITHIN 90 DAYS OF CERTIFICATE OF OCCUPANCY. 1 LAMP TOTAL MOUNTING TYPE WATTS SUBSTITUTIONS TO THE ABOVE FIXTURE SCHEDULE 12 WATTS 12 RECESSED MUST BE SUBMITTED 14 DAYS PRIOR TO BID & LED REVIEWED BY THE ARCHITECT, ENGINEER & OWNER. SUBSTITUTIONS WILL NOT BE REVIEWED AFTER 12 WATTS LED 12 RECESSED THIS TIME. SUBMITTAL PACKAGES MUST INCLUDE COLOR, CUT SHEETS, ALL PHOTOMETRICS & 15 WATTS 15 WALL FIXTURE SAMPLES FOR ALL DECORATIVE FIXTURES, LED LANDSCAPE FIXTURES & OUTDOOR FIXTURES. WITHOUT THIS INFORMATION NO REVIEW WILL BE 36 WATTS 63 SURFACE PROVIDED. LED 5 WATTS 5 PENDANT 35 WATTS - WALL 5 WATTS 5 CEILING LED 12 CEILING TYPICAL PANEL SECTI❑N 2 22K AIC 3 #3/0 & 1 #6 BOND —2"C 3#250 MCM & 1 #4 BOND —3'C 250A, 2P TYPICAL ENCLOSED PANEL BREAKER 22K AIC SECTI❑N 1 22K AIC #2 CU. GIRD. CONDUCTOR 3 #250 MCM IN 3"C oo INTER SYSTEM BONDING CWP, BLDG. STEEL FOR CATV &TEL A & BLDG. FOOTING STEEL �-- 5/8" x 8 FT GROUND ROD. FROM PAD MTD. TRANSFORMER TYPICAL RISER DIAGRAM N.T.S. HAMMOND & ASSOCIATES, INC. CONSULTING ENGINEERS 18800 N.W. 2ND AVENUE, SUITE 216 C � MIAMI, FLORIDA 33169 TEL: (305) 651-8522 FAX (305) 651-3376 ERIC J. HAMMOND P.E. MECHANICAL / ELECTRICAL ENGINEER Short Circuit Calculation Available Fault Current 'Isca' :1 60255 Distance to Vault 'L' :1 94 co C' Value ; 18593 Line to Line Voltage :1 240 # of runs of conduit :� 1 Numerator - T' Factor : 9798668.1 Denominator - W Factor :1 4462320� F' Factor :1 2.195868539 7 M' Factor :�0.312903985 Isca = Fault Current at MDP :1 18854.02959 Formula =1.73 X 'L' X 'Isca' Formula =(#of runs) x'C' x voltage Formula =(1)/(1+'F' Factor) Formula ='M'x'Isca' wrieht arh[ 11C 154 Krog Street, #125 Atlanta, GA 30307 404-218-8460 Q Z Ln Ln oV IV' M Q z Z LU t]G W o0 - �U oca W oz r- w to z La.i Q J 0 Z 4< W V 0 stamp: ERIC HAMMOND, PE EB 5315-PE 39048 revisions No. Description Date BLDG. DEPT. COMMENTS 1/27/21 A2ELECT. BLDG. DEPT. COMMENTS 3/22/21 sheet title: ELECTRICAL GENERAL NOTES project number: 19-049 drawing date: 11.11.2020 scale as noted sheet number: EO=O 1 NOT ISSUED FOR CONSTRUCTION ❑ ISSUED FOR CONSTRUCTION HAMMOND & ASSOCIATES, INC. CONSULTING ENGINEERS 18800 N.W. 2ND AVENUE, SUITE 216 MIAMI, FLORIDA 33169 TEL: (305) 651-8522 FAX (305) 651-3376 ERIC J. HAMMOND P.E. MECHANICAL / ELECTRICAL ENGINEER P.E. #39048 EB 5315 Reviewed for Code ED Compliance Universal Engineering Sciences /1\ wrieht arhl 11C 154 Krog Street, #125 Atlanta, GA 30307 404-218-8460 Q Z dd J Q Z W 7A W CC .LA V 1 J Ca z W V O stamp: h u7 M p Q Z p aLU o0 �_ �u oW �m oZ w Ln Z W ERIC HAMMOND, PE EB 5315-PE 39048 revisions No. Description Date 1 BLDG. DEPT. COMMENT 1 /27/21 2 ELECT. BLDG. DEPT. COMMENTS 3 22 21 / / sheet title: DUPLEX TYPE 2 GARAGE FLOOR ELECTRICAL PLAN project number: 19-049 drawing date: 11.11.2020 scale as noted sheet number: E1=01 0 NOT ISSUED FOR CONSTRUCTION ❑ ISSUED FOR CONSTRUCTION HAMMOND & ASSOCIATES, INC. CONSULTING ENGINEERS 18800 N.W. 2ND AVENUE, SUITE 216 MIAMI, FLORIDA 33169 TEL: (305) 651-8522 FAX (305) 651-3376 ERIC J. HAMMOND P.E. MECHANICAL / ELECTRICAL ENGINEER P.E. #39048 E8 5315 91 Reviewe C;omr��,�s: Unjver+sas �ciert::o>_ DUPLEX TYPE 2 FIRST FLOOR ELECTRICAL PLAN El -0,2, 1 /4" = 1'-0" wrieht arhl 11C 154 Krog Street, #125 Atlanta, GA 30307 404-218-8460 a Z Ice dJ � M Z Q � W o0 V o� W p[ o Z W A to W V 1 M a 0 z a W V O stamp: ERIC HAMMOND, PE EB 5315-PE 39048 revisions No. DescriDtion Date BLDG. DEPT. COMMENTS 1 /27/21 2 ELECT. BLDG. DEPT. COMMENTS 3/22/21 sheet title: DUPLEX TYPE 2 FISRT FLOOR ELECTRICAL PLAN project number: 19-049 drawing date: 11.11.2020 scale as noted sheet number: E1=02 0 NOT ISSUED FOR CONSTRUCTION ❑ ISSUED FOR CONSTRUCTION HAMMOND & ASSOCIATES, INC. CONSULTING ENGINEERS 18800 N.W. 2ND AVENUE, SUITE 216 MIAMI, FLORIDA 33169 TEL: (305) 651-8522 FAX (305) 651-3376 ERIC J. HAMMOND P.E. MECHANICAL / ELECTRICAL ENGINEER P.E. #39048 EB 5315 Reviewed for Cod, 0:�rrrpbia.=7�.e L)MversaE Engineerrnc 7 -U UUARU $'CHI L J -V V UM r\U rVAI L» 2 DUPLEX TYPE 2 SECOND FLOOR ELECTRICAL PLAN ■ wri ht ae rck, 'ecl Ilc 154 Krog Street, #125 Atlanta, GA 30307 404-218-8460 Z W J Ln Ln IT IT M p Z Z a� W o 0 LL- 0 :3 u W oco `� DC oz W L.n ILA V 1 "1 J Z Q W V O stamp: \\`r1111111iI/��� M�p0N0 UJ Ile- 01/ /00t f � � i � 71 `� •� I L/ '+► � YY t€it ERIC HAMMOND, PE EB 5315-PE 39048 revisions Nu. UtfbU IPLIUII UdIC BnMMFDNTPT 1/27/ 11 sheet title: DUPLEX TYPE 2 SECOND Et THIRD ELECTRICAL PLANS project number: 19-049 drawing date: 11.11.2020 scale as noted sheet number: E1=03 0 NOT ISSUED FOR CONSTRUCTION ❑ ISSUED FOR CONSTRUCTION AHU DUPLEX TYPE 2 THIRD FLOOR ELECTRICAL PLAN 1 /4" = V-0" HAMMOND & ASSOCIATES, INC. CONSULTING ENGINEERS 18800 N.W. 2ND AVENUE, SUITE 216 Ifh.. MIAMI, FLORIDA 33169 7 TEL: (305) 651-8522 FAX (305) 651-3376 ERIC J. HAMMOND P.E. MECHANICAL / ELECTRICAL ENGINEER P.E. #39048 EB 5315 Reviewed for Code Ce neerincg S WU-2 ■ wri ht ar e rc i ecl 11C 154 Krog Street, #125 Atlanta, GA 30307 404-218-8460 Q z ICU u7 Q � eJ- � M p Z Z a W o0 LL- �u W o tieoZ r- W . /� v^ NN W Q J Z Q W V O stamp: _ .z� A �I ERIC HAMMOND, PE EB 5315-PE 39048 revisions No. Description Date A1BLDG. DEPT. COMMENTS 1 /27/21 sheet title: DUPLEX TYPE 2 ELECTRICAL ROOF PLAN project number: 19-049 drawing date: 11.11.2020 scale as noted sheet number: El =04 NOT ISSUED FOR CONSTRUCTION ❑ ISSUED FOR CONSTRUCTION GENERAL PLUMBING NOTES 1 ALL WORKMANSHIP AND MATERIALS SHALL BE IN STRICT ACCORDANCE WITH APPLICABLE LOCAL CODES, RULES AND ORDINANCES. (FBC—PLUMBING 2020) 2 CONTRACTOR SHALL VISIT THE JOB SITE AND THOROUGHLY 1 FAMILIARLIZE HIMSELF WITH ALL EXISTING CONDITIONS. 3 ALL MATERIALS SHALL BE NEW 4 ALL WORK SHALL BE PERFORMED BY A LICENSED PLUMBING CONTRACTOR IN A FIRST CLASS WORKMANLIKE MANNER. THE COMPLETED SYSTEM SHALL BE FULLY OPERATIVE. 5 ALL EXCAVATION AND BACKFILL AS REQUIRED FOR THIS PHASE OF CONSTRUCTION SHALL BE A PART OF THIS CONTRACT. 6 REQUIRED INSURANCE SHALL BE PROVIDED BY THE CONTRACTOR FOR PROTECTION AGAINST PUBLIC LIABILITY AND PROPERTY DAMAGE FOR THE DURATION OF THE WORK. 7 CONTRACTOR SHALL SECURE AND PAY ALL PERMITS, FEES, INSPECTION AND TEST. 8 DRAWINGS ARE DIAGRAMMATIC. DO NOT SCALE FOR EXACT LOCATION OF FIXTURES, PIPING, EQUIPMENT, ETC. 9 ALL WORK SHALL BE COORDINATED WITH OTHER TRADES TO AVOID INTERFERENCE WITH THE PROGRESS OF CONSTRUCTION, REPORT ANY DISCREPANCY TO ENGINEER/ARCHITECT PRIOR TO BEGINNING CONSTRUCTION. 10 VERIFY LOCATION, SIZE, INVERTS AND ALL EXISTING UTILITIES PRIOR TO BEGINNING CONSTRUCTION. ADVISE ENGINEER OF ANY DESCREPANCIES. 11 WATER PIPING SHALL BE TYPE "L" COPPER FOR 2" AND UNDER AND TYPE "K" COPPER FOR 2 1/2" AND ABOVE. ALL UNDERGROUND WATER PIPING SHALL BE TYPE "K" COPPER. 12 SOIL, WASTE, VENT AND RAIN WATER PIPING ABOVE AND BELOW GRADE SHALL BE CAST IRON HUBLESS PIPE OR PVC SOLID WALL. 13 AIR CONDITIONING CONDENSATE DRAIN PIPING SHALL BE THREADED STEEL PIPE OR COPPER DRAIN WASTE AND VENT PIPE & FITTINGS. INSULATE ALL CONDENSATE PIPING EXCEPT UNDERGROUND. 14 INSULATE ALL CONDENSATE LINES ABOVE GRADE WITH 1/2" ARMAFLEX PREFORM 15 ALL FIXTURES MUST BE PROVIDED WITH READILY ACCESSIBLE STOPS AND MARKED ACCESS PANELS. 16 FURNISH AND INSTALL APPROVED AIR CHAMBERS AT EACH PLUMBING FIXTURE AND P.D.I. APPROVED SHOCK ARRESTORS ON MAIN LINES OR RISERS. 17 DIELECTRIC COUPLINGS ARE REQUIRED BETWEEN ALL DISSIMILAR METAL IN PIPING AND EQUIPMENT CONNECTIONS. 18 ISOLATE COPPER PIPE FROM HANGER OR SUPPORT WITH ISOLATOR PAD (HAIR FELT LINING) SUPER STRUT MODEL C/15/16. 19 ALL RATED FLOOR AND WALL PENETRATIONS (NO PVC) SHALL HAVE FIRE, SMOKE AND WATER STOPS BY FILLING VOIDS BETWEEN PIPE AND WALL/FLOOR SLEEVES WITH FIRE RATED FOAM, CHASE TECHNOLOGY CORP. —CIC PR 855 OR 3M, CP-25 CAULKING OR 303 PUTTY, TO ACHIEVE SAME RATING AS WALLS OR FLOORS. 20 CONTRACTOR SHALL GAURANTEE ALL MATERIALS AND WORKMANSHIP FREE FROM DEFECTS FOR A PERIOD OF NOT LESS THAN (1) YEAR FROM DATE FOR ACCEPTANCE. CORRECTION OF ANY DEFECTS SHALL BE COMPLETED WITHOUT ADDITIONAL CHARGE AND SHALL INCLUDE REPLACEMENT OR REPAIR OF ANY OTHER PHASE OF THE INSTALLATION WHICH MAY HAVE BEEN DAMAGED. 21 PROVIDE 1/2" TRAP PRIMER LINE FOR ALL FLOOR DRAINS FROM THE NEAREST LAVATORY OR SINK SUPPLY. 22 PROVIDE ACCESS PANELS FOR ALL CONCEALED VALVES AND ALL WATER HAMMER ARRESTORS. ACCESS PANELS IN RATED WALLS MUST MAINTAIN THE SAME RATING. ALL ACCESS PANELS MUST MATCH THE FINISH OF THE WALL IN WHICH IT IS INSTALLED.. 23 CONTRACTOR SHALL PROVIDE COMBINATION COVER PLATE AND CLEANOUT PLUG FOR ALL WALL CLEANOUTS — JOSAM 58890 SERIES. 24 ALL HOSE BIBBS SHALL BE CHROME PLATED 3/4" SOLID FLANGED THREADED HOSE AND LOOSE KEY W/VACUUM BREAKER — WATTS 8A, MOUNTED 26" ABOVE GRADE OR FINISH FLOOR. 25 DRAINS SHALL BE AS FOLLOWS: FLOOR : ROOF : J.R. SMITH #1419—UM-08068-20-0 26 INTERIOR FLOOR CLEANOUTSJAA§MI[k #909k SERIES 58370 27 ALL CONTROL VALVES SHALL BE TAGGED AND MARKED. A REPRODUCIBLE DIAGRAM LOCATING ALL VALVES SHALL BE PROVIDED FOR OWNER/OPERATOR OF THE SITE. 28 TO THE BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE MINIMUM BUILDING CODES AND THE APPLICABLE FIRE —SAFETY STANDARDS AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH THE SECTION AND CHAPTER 633, FLORIDA STATUTES. PLUMBING FIXTURE SCHEDULE NAME TYPE MANUFACTURE & MODEL# ACCESSORIES & NOTES FLOOR MOUNTED BRIGGS BRIGGS"ABINGDON" 4230, LOW CONSUMPTION WC-1 WATER CLOSET BRIGGS TOILET VITREOUS CHINA ELONGATED BOWL AND MODEL # ABINGDON 4230 TANK 14'Y2" BOWL ANTI -SIPHON COCK 1.6 GPF WHITE TANK TYPE SOLID PLASTIC CLOSED FRONT WITH COVER SEAT 19" ROUND, SELF -RIMMING COUNTER TOP L-1 LAVATORY BRIGGS PORCELAIN. DELTA 2520 TWO BLADE HANDLES, UNDERMOUND MODEL # HOMER 3012 4" CENTERSET, SNAP-N-POP UP DRAIN CHROME FINISH 33" X 22" DOUBLE COMPARTMENT SINK, 6" DEEP SK-1 KITCHEN SINK ELKAY HEAVY -GAUGE NICKEL BEARING STAINLESS STEEL, (DROP -IN) MODEL # DAYTON KJ-23322 POLISHED TO A BUFFED FINISH WITH J CHANNEL STAINLESS STEEL SELF RIM DEVICE, BOTTOM SOUND DEADENED PROVIDE GARBAGE DISPOSAL FOR THE SINK. HB 3/4" HOSE BIBB ZURN MODEL# Z-1350-VP INSTANT HOT TITAN 240V, 11.8KW EWH-1 ELECTRIC MODEL* N-120 WATER HEATER AMERICAN STANDARD ACID - RESISTANT PORCELAIN ENAMELED TUB TUB 2461-002 AMERICAST RECESSED BATH. INT APRON LUMBAR SUPPORT AND HEADREST. DRAIN KIT AMERICAN STANDARD PRESSURE BALANCED FAUCET WITH SHOWER SH SHOWER 2000.501 HEAD ANTI -SCALD. SET HOT WATER @ 110°F, PROVIDE SHOWER HEAD RELIANT 3 VALVE TRIM # TU385501WDXH 3 FUNCTION HAND SHOWER # 1660.766 WITH NON -POSITIVE SHUT-OFF IN -LINE VACUUM BREAKER # 1660.400 DRAIN: JAY R. SMITH #2005A & P-TRAP SHOWER HEAD: "FLOWISE" #1660.710 BACKFLOW PREVENTER: #1660.400.002 Al FLOW RATE - 1.5GPM EXP. THERMAL AMTROL 1.5 GALLON TANK EXPANSION TANK MODEL# ST-5 150 PSIG WORKING PRESSURE 3"FD 3" FUNNEL FLOOR DRAIN JOSAM OR APPROVED EQUAL POLISHED NICKEL CAST IRON FLOOR DRAIN WITH JAY R. SMITH TYPE E POLISHED NICKEL BRONZE STRAINER MODEL # 351 OY03-F11-07NB-PO50 4" DIAMETER PROOF 6" SQUARE TOP & TRAP PRIMER FIXTURE TYPE WATER PIPE SIZE NOMINAL SAN. SIZE MAX. FLOW RATES WATER CLOSET (TANK TYPE) 3/8" 3" 1.6 GPF LAVATORY 1/2" 1 1/4" 0.5 GPM SHOWER 1/2" 2" 2.5 GPM KITCHEN SINKS 1/2" 1 1/2" 1.5 GPM WATER HAMMER ARRESTOR SIOUX CHIEF SIZING AND SELECTION P.D.I. UNITS A B C D E F FIXTURES UNITS 1-11 12-32 33-60 61-113 114-15 155-33,0 PLUMBING SYMBOL, LEGEND & ABBREVIATION SYMBOL ABBREV DESCRIPTION REMARKS C COLD WATER PIPING H HOT WATER PIPING HWR HOT WATER RETURN S.A. SHOCK ABSORBER S.O.V. SHUT—OFF VALVE — SAN— S or W SANITARY or WASTE PIPING U.1.0. UNLESS INDICATED OTHERWISE — — — V VENT PIPING i BV BALL VALVE T_ . CV CHECK VALVE ---0 PIPE RISE D PIPE DROP BRANCH OFF TOP BRANCH OF BOTTOM v --il CO WALL CLEANOUT UNION --- JIL VTR VENT THRU ROOF _,L BALANCE COCK >< GV GATE VALVE PRV PRESS AND TEMP RELIEF VALVE U CO FLOOR CLEANOUT X-1 INDICATES RISER TP TRAP PRIMER I-� WH WALL HYDRANT HB HOSE BIBB HAMMOND & ASSOCIATES, INC. CONSULTING ENGINEERS kln 18800 N.W. 2ND AVENUE, SUITE 216 MIAMI, FLORIDA 33169 qT TEL: (305) 651-8522 FAX (305) 651-3376 ERIC J. HAMMOND P.E. MECHANICAL / ELECTRICAL ENGINEER P.E. #39048 EB 5315 wrieht arhl 11C 154 Krog Street, #125 Atlanta, GA 30307 404-218-8460 Z dtf J ~ v7 Q� � M o Z _ Z p� a W o0 �u W o� oz r- w ILA N w a J Z a W V O stamp: \"�,� WiiJii/to ``� ` OtAOND /x ." `3 `U UJ er z e Al S SIONPO e j//'/II 1111\0 ERIC HAMMOND, PE EB 5315-PE 39048 revisions No. Description Date Q BLDG. DEPT. 01-22-21 COMM sheet title: PLUMBING GENERAL NOTES SYMBOLS F± SCHEDULE project number: 19-049 drawing date: 11.11.2020 scale as noted sheet number: PO=01 NOT ISSUED FOR CONSTRUCTION ❑ ISSUED FOR CONSTRUCTION PLUMBING KEYED NOTES: O1 " COLD 3/4" HOT WATER RISER UP FROM SECOND FLOOR. O3" VENT RISER UP THRU ROOF. J _V '%1.ad//'1[xU r0MIL- 2 DUPLEX TYPE 2 THIRD PLOOR PLUMBING PLAN P1-03 1 /4' = V-0" PLUMBING KEYED NOTES: O3" SANITARY RISER FROM THIRD FLOOR & OFFSET IN CEILING. (2) 1" DOMESTIC WATER RISER UP TO THIRD FLOOR. O3" VENT RISER UP IN WALL. O1 V DOMESTIC COLD WATER RISER FROM FIRST FLOOR. O1" CONDENSATE RISER FROM AHU--2 ON 3RD FLOOR. O3" VENT RISER UP TO 3RD FLOOR. (7) 1 " COLD WATER & 3/4" HOT WATER RISER UP TO 3RD FLOOR. ( ti) 3" SANITARY PIPING DOWN IN WALL TO FIRST FLOOR CEILING. O3/4" HOT WATER SUPPLY RISER DOWN TO FIRST FLOOR & 3/4" RETURN RISER UP FROM FIRST FLOOR. 10 3" VENT RISER UP FROM FIRST FLOOR. A 2„ L-1 1"H&C WATER MAST R L-1 i/ 2 i I 1 "HOWATE ALK I 1 ' CD_ LLOSET IN CEILl ELEVATOR 3"SAN OFFSET IN CEILING(14 D U'S 7 3 SA 3"SAN OFFSET 8 IN CEILING 3 1 3"SA (7 DFU'S) EGRESS PANEL 3"RWL(725 SQ.FT) 2"SAN RISER DOWN FROM SINKS ON FLOOR MASTER ABOVE BEDROOM J"H&COLD WATE RISER UP TO SINKS ON FLOOR ABOVE 2"SAN OFFSET IN —� CEILING "SAN(10 DFU'S) 1�"HOT&COLD WATER 11 ( 1: U l-� 1 "CONDENSATE RISER DOWN TO - �T_= BELOW 3"SAN(12 DFU'S) -. 1 "CW 3"SAN DOWN __ (19 DFU'S) _ 4 1 "HW 3"SAN DOWN _ _ 0 FIRST FL(bOR _ 9 I EWH-1 (19 Df4.JA ) - I LAUNDRY `3/4" ( EXPANSION HRW I .� TANK /4„ HRW F 2»VENT DRDOM 1 I » I _1 BEDROOM 2 CIA FFSETAN X"H&C WATER I I ILL CEILING EGRESS - 1 EGRESS PANELLer�_ HAMMOND & ASSOCIATES, INC. CONSULTING ENGINEERS 18800 N.W. 2ND AVENUE, SUITE 216 ty MIAMI, FLORIDA 33169 TEL: (305) 651-8522 FAX (305) 651-3376 ERIC J. HAMMOND P.E. MECHANICAL / ELECTRICAL ENGINEER P.E. #39048 EB 5315 Al CHANGES MADE ON THE ENTIRE SHEET E-WfPigjed ff )r �: CJClh C01'90anc,E Univ@rsaf Engineen; lg S�:ienc�G� t T-0" GUARD RAIL EGRESS PANEL. - 3"RWL(725 SQ.FT) 1"H&C WATER 2"SAN RISER DOWN MASTER BEDROOM FROM SINKS ON FLOOR ABOVE 2- J"H&COLD WATER RISER UP TO SINKS ON FLOOR ABOVE M"HOT&COLD WATER 3"SAN(10 DFU'S) ;I 1 "CONDENSATE —I -_ _ -- _4 I RISER DOWN TO —} BELOW 3"SAN(12 DFU'S) 3"SAN DOWN (26 DFU'S) 1"HW 10 4 _ s Z3,SAN DOWN - - - TO FIRST FLOOR (26 DFU'S) EWH-1 9 -�---, � N LAU DRY-----I- 0____ EXPANSION 3» TANK 3/4"� I I HRW a 3/4 WO? j L::;;A— 1---- 2» %"CW- BEDROOM 1 2„ W�JAICK JILL EGRESS PANEL_. T-0" GUARD RAIL- T-0" GUARD RAIL DUPLEX TYPE 2 -SECOND FLOOR PLUMBING PLAN M. I \i "H&C WATER 3f' I IN, �&' INGWALK IN CLOSET 6 \ 0— I'm H ELEVATOR L3"SA OFFSET N C ILING(14 DFU'S) I „ 'dOSET SA 3"SAN OFFSET 3/4 CW IN CEILING (7 DFU'S) 3"SAN 3 (7 DFU'S) 2"VENT I ----V— I— - BEDROOM 2 %"H&C WATER ( I EGRESS PANEL 1 ■ wri h t a e rckicecl IIC 154 Krog Street, #125 Atlanta, GA 30307 404-218-8460 Q z ICU Lf) Q_ rn �1 �r M p Z Z a W o0 U_ 0 � U oco W oz W . /� v� VN W VI � J z Q W V 0 stamp: 00Ir1f; ,� Cr�Os 500 [� w„ °yea P , L 0 1 ! 6 t [ c r a ERIC HAMMOND, PE EB 5315-PE 39048 revisions IVU. UeJ.Ll 1PLIU1 I Udle QBLDG. DEPT. COMMENT 1 1-27-21 sheet title: DUPLEX TYPE 2 SECOND Et ROOFTOP PLUMBING PLANS project number: 19-049 drawing date: 11.11.2020 scale as noted sheet number: P1 =03 NOT ISSUED FOR CONSTRUCTION ❑ ISSUED FOR CONSTRUCTION xWWWRIM ROOF SHEATHINGa SUPER STUD COLD FORMED DUPLEX TYPE 2 PLUMBING ROOF PLAN 1 /4" = V-0" Al CHANGES MADE ON THE ENTIRE SHEET HAMMOND & ASSOCIATES, INC. CONSULTING ENGINEERS 18800 N.W. 2ND AVENUE, SUITE 216 MIAMI, FLORIDA 33169 TEL: (305) 651-8522 FAX (305) 651-3376 ERIC J. HAMMOND P.E. MECHANICAL / ELECTRICAL ENGINEER P.E. #39048 EB 5315 Reviewed for Cade [B Compliance Universal Engineering Sciences wrieht a rhl 11C 154 Krog Street, #125 Atlanta, GA 30307 404-218-8460 a z J Q Ln Ln en � M p Z Z W o-1 = ® u oa W Ln m oz w N Z W rw V 1 n J 0 Z <C W V O stamp: CJ ZZ lu ERIC HAMMOND, PE EB 5315-PE 39048 revisions No. Description Date Al BLDG. DEPT. 01-27-21 COMM sheet title: DUPLEX TYPE 2 PLUMBING ROOF PLAN project number: 19-049 drawing date: 11.11.2020 scale as noted sheet number: P1-04 NOT ISSUED FOR CONSTRUCTION 0 ISSUED FOR CONSTRUCTION / / I / / / I I / R0 I 0 / \ �2 S AN(2g J I I 13„SAN 2 3„SAN(> 2" AN / / 0 OR �T Fl / I I � S 3 SAN2 Oro (t2pqS pop 21'SAN `� 2NSPN SAN c�� 4 SA ,1 N � G t4� DFUS G ) 2''SAN A 4U Op R 2"SA Sk`1 N(2 �F , SCOPE �/g/F 1 /g/� 5�GPE Ai =ENTIRE (4 O�U AN Z„ S) / I � / y I / 5N / / / HAMMOND & ASSOCIATES, INC. CONSULTING ENGINEERS 18800 N.W. 2ND AVENUE, SUITE 216 MIAMI, FLORIDA 33169 TEL: (305) 651-8522 FAX (305) 651-3376 ERIC J. HAMMOND P.E. MECHANICAL / ELECTRICAL ENGINEER P.E. #39048 E8 5315 Reviewed for Cod(-, Compliance a wri ht arhel 11C 154 Krog Street, #125 Atlanta, GA 30307 404-218-8460 9 Z W 0 LA W W LA N V z W V O stamp: ERIC HAMMOND, PE EB 5315-PE 39048 revisions Ln o� M � Q Z p aLLI O Q :D V O w �co oz W VN Z W No. Description Date Al BLDG. DEPT. 01-27-21 Comm sheet title: SANITARY ISOMETRIC DUPLEX TYPE 2 UNIT 2 project number: 19-049 drawing date: 11.11.2020 scale as noted sheet number: P5=0 1 BUILDING 1 DUPLEX TYPE 2- UNIT 2 - PARTIAL SANITARY ISOMETRIC NOT ISSUED FOR CONSTRUCTION ❑ ISSUED FOR CONSTRUCTION )ND & ASSOCIATES, INC. CONSULTING ENGINEERS 18800 N.W. 2ND AVENUE, SUITE 216 MIAMI, FLORIDA 33169 (305) 651-8522 FAX (305) 651-3376 ERIC J. HAMMOND P.E. MECHANICAL / ELECTRICAL ENGINEER P.E. #39048 EB 5315 t PRE GRA E(�o wri ht arhef 11C 154 Krog Street, #125 Atlanta, GA 30307 404-218-8460 Q Z W J a z W 0 . IL J W W N N Z Q W V 0 stamp: ERIC HAMMOND, PE EB 5315-PE 39048 revisions h Ln ol� IT rn Z Q Q LU U O LL. E- _ Ln W O Z W Ln Z W n NO. Description Date 1Q BLDG. DEPT. 01 27 21 COMM sheet title: PARTIAL SANITARY ISOMETRIC DUPLEX TYPE 2 UNIT 2 project number: 19-049 drawing date: 11.11.2020 scale as noted sheet number: P5eO2 0 NOT ISSUED FOR CONSTRUCTION ❑ ISSUED FOR CONSTRUCTION