Loading...
HomeMy WebLinkAboutDuck Leakage Test ReportDuct Leakage Test Report Residential Prescriptive, Performance or ERI Method Compliance 2020 Florida Building Code, Energy Conservation, 7th Edition Jurisdiction: Permit #: Job linfortitation Builder: HQ Construction Community: Lot: NA Add less: 5206 Paleo Circle City: Fort Pierce State: FL Zip: 34951 Du `t Leakage Test Results r System 1 cfm25 System 2 cfm25 System 3 cfm25 ' Sum of others cfm25 Total I of all cfm25 i - 1985 - On Total bf all Total Conditioned systems Square Footage Q Prescriptive Method cfm25 (Total) ' .To qualify as "substantially leak free" On Total must be less than or `equal #o. 0.04 if air handier unit is installed. If air handier unit.is not installed, On Total must be less than or equal to 0.03. This testing method meets the requirements in accordance witti Section R403.3.3. Is ihe.airliandlerunit installed during testing? ❑ YES (so. ❑ NO (sc°.) 0 PerformOceffi l Method cfm25 (Out or Total) To qualify using -this method', On must not be greater than the proposed. duct leakage On specified on Form R405-2020 or R406-2020 Leakage Type selected on Form Qn specfied on Form R405-2020 R405-2020 (EnergyCalc) or R406-2020 (EnergyCalc) or R406-2020, PASS FAI L Proposed Leak Free 0.03 Ductitightness shall be verified by testing in accordance with ANSI/RESNET/ICC380 by either individuals as defined in Section 553.993(5) or (7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(f), (g) or (i), Florida Statutes. Te tIQg9 Company Company Name: Phone: I hereby verify that the above duct leakage testing results are in accordance with the Florida Building Code requirements with the selected compliance path as stated above, either the Prescriptive Method or Performance Method. Sidnature of Tester: Date of Test: PriInted Name of Tester: License/Certification #: Issuing Authority: 11/24/2021 12:29:17 PM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 1