HomeMy WebLinkAboutAPPROVED AC Manual J(1)Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Aug-10 10:37:40
Right-Suite® Universal 2021 21.0.08 RSU29066 Page 1
...ents\Wrightsoft HVAC\5406 Birch Dr PSL Prop.rup Calc = MJ8 Front Door faces: N
1588Job:Load Short Form 8/10/2021Date:House Chris BatemanBy:
Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
Project Information
Key Largo Spec Home (LHF), Air Conditioning UnlimitedFor:
5406 Birch Dr, Fort Pierce, FL 34982
Design Information
InfiltrationClgHtg
SimplifiedMethod9041Outside db (°F)
AverageConstruction quality7570Inside db (°F)
0Fireplaces1529Design TD (°F)
L-Daily range
5030Inside humidity (%)
572Moisture difference (gr/lb)
HEATING EQUIPMENT COOLING EQUIPMENT
Make Make Goodman Mfg.
Trade Trade GOODMAN
Model Cond GSX16S361A
AHRI ref Coil ASPT47D14A
AHRI ref 201785534
Efficiency 80 AFUE Efficiency 13.0 EER, 16 SEER
Heating input Btuh0 Sensible cooling Btuh24500
Heating output Btuh0 Latent cooling Btuh10500
Temperature rise °F0 Total cooling Btuh35000
Actual air flow cfm1167 Actual air flow cfm1167
Air flow factor cfm/Btuh0.046 Air flow factor cfm/Btuh0.052
Static pressure in H2O0 Static pressure in H2O0
Space thermostat Load sensible heat ratio 0.76
ROOM NAME Area Htg load Clg load Htg AVF Clg AVF
(ft²)(Btuh)(Btuh)(cfm)(cfm)
Laundry 36 425 796 20 41
Bed 2 136 2380 1551 110 81
Bath 42 58 37 3 2
Bath 2 51 760 447 35 23
Hall 30 0 0 0 0
Bed 3 153 3171 2363 147 123
Bed 4 157 2465 1690 114 88
Foyer GR 426 5173 5658 239 295
Pantry 14 0 0 0 0
Kitchen DR 411 4595 6483 213 338
Master Bath 95 2049 829 95 43
Hers 20 402 131 19 7
His 9 12 7 1 0
Master Bed 222 3716 2376 172 124
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Aug-10 10:37:40
Right-Suite® Universal 2021 21.0.08 RSU29066 Page 2
...ents\Wrightsoft HVAC\5406 Birch Dr PSL Prop.rup Calc = MJ8 Front Door faces: N
House 1801 25206 22367 1167 1167
Other equip loads 1769 939
Equip. @ 0.95 RSM 22235
Latent cooling 7228
TOTALS 1801 26975 29462 1167 1167
2021-Aug-10 10:37:40
Right-Suite® Universal 2021 21.0.08 RSU29066 Page 1
...ents\Wrightsoft HVAC\5406 Birch Dr PSL Prop.rup Calc = MJ8 Front Door faces: N
1588Job:Building Analysis 8/10/2021Date:House Chris BatemanBy:
Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
Project Information
Key Largo Spec Home (LHF), Air Conditioning UnlimitedFor:
5406 Birch Dr, Fort Pierce, FL 34982
Design Conditions
Location: CoolingHeatingIndoor:7570Indoor temperature (°F)St Lucie Co Intl, FL, US
1529Design TD (°F)ft26Elevation:
5030Relative humidity (%)°N28Latitude:
Outdoor:56.92.4Moisture difference (gr/lb)CoolingHeating
Infiltration:9041Dry bulb (°F)
SimplifiedMethod)L(15-Daily range (°F)
AverageConstruction quality77-Wet bulb (°F)
0Fireplaces7.515.0Wind speed (mph)
Heating
Walls
Glazing
Ceilings
Floors
Infiltration
Ducts
Ventilation
% of loadBtuhBtuh/ft²Component
17.246503.1Walls
14.0377717.4Glazing
000Doors
6.617851.0Ceilings
21.357343.23.2Floors
11.831842.2Infiltration
22.56076Ducts
00Piping
00Humidification
6.61769Ventilation0Adjustments
100.026975Total
Cooling
Walls
Glazing
Ceilings
Infiltration
Ducts
Internal Gains
Ventilation
% of loadBtuhBtuh/ft²Component
12.328671.9Walls
20.3472021.8Glazing
000Doors
4.710960.6Ceilings
000Floors
3.88900.6Infiltration
29.26795Ducts
4.0939Ventilation
25.76000Internal gains
00Blower
0Adjustments
100.023307Total
Latent Cooling Load = 7228 Btuh
Overall U-value = 0.104 Btuh/ft²-°F
Data entries checked.
2021-Aug-10 10:37:40
Right-Suite® Universal 2021 21.0.08 RSU29066 Page 1
...ents\Wrightsoft HVAC\5406 Birch Dr PSL Prop.rup Calc = MJ8 Front Door faces: N
1588Job:Component Constructions 8/10/2021Date:House Chris BatemanBy:
Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
Project Information
Key Largo Spec Home (LHF), Air Conditioning UnlimitedFor:
5406 Birch Dr, Fort Pierce, FL 34982
Design Conditions
Location: CoolingHeatingIndoor:
7570Indoor temperature (°F)St Lucie Co Intl, FL, US
1529Design TD (°F)ft26Elevation:
5030Relative humidity (%)°N28Latitude:
Outdoor:56.92.4Moisture difference (gr/lb)CoolingHeating
Infiltration:9041Dry bulb (°F)
SimplifiedMethod)L(15-Daily range (°F)
AverageConstruction quality77-Wet bulb (°F)
0Fireplaces7.515.0Wind speed (mph)
Construction descriptions GainLoss Clg HTMHtg HTMInsul RU-valueAreaOr
BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft²
Walls
Blk Wall, Stucco Ext, R-4.1 Ext Bd inI, 8" Thk, 1/2" Gyp Bd Int Fnsh 11693.155.10.109371ne 7482.02
5062.027913.155.10.109251se
4592.027173.155.10.109228sw
7802.0212203.155.10.109387nw
24932.0238973.155.10.1091237all
Partitions
Frm Wall, 1/2" Gyp Bd Ext, R-11 Cav Ins, 1/2" Gyp Bd Int Fnsh, 2"x4", 16"
OC Stud
3741.467542.9411.00.101257
Windows
Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.22);
50% blinds 45°, medium; 50% outdoor insect screen; foreground = green
grass (0.23); 1 ft overhang (5.2 ft window ht, 1 ft sep.); 6.8 ft head ht
100121.484118.000.62047se
Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.24);
50% blinds 45°, medium; 50% outdoor insect screen; foreground = green
grass (0.23); 4.7 ft overhang (6.7 ft window ht, 1 ft sep.); 6.8 ft head ht
40510.167616.800.58040se
Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.24);
50% blinds 45°, medium; 50% outdoor insect screen; foreground = green
grass (0.23); 1 ft overhang (2.2 ft window ht, 1 ft sep.); 6.8 ft head ht
13420.311116.800.5807sw
Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.24);
50% blinds 45°, medium; 50% outdoor insect screen; foreground = green
grass (0.23); 1 ft overhang (5.2 ft window ht, 1 ft sep.); 6.8 ft head ht
68121.852516.800.58031sw
70622.652516.800.58031nw
138722.2105016.800.58062all
Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.24);
50% blinds 45°, medium; 50% outdoor insect screen; foreground = green
grass (0.23); 1 ft overhang (2.17 ft window ht, 1 ft sep.); 6.8 ft head ht
10622.67916.800.5805nw
2021-Aug-10 10:37:40
Right-Suite® Universal 2021 21.0.08 RSU29066 Page 2
...ents\Wrightsoft HVAC\5406 Birch Dr PSL Prop.rup Calc = MJ8 Front Door faces: N
Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.24);
50% blinds 45°, medium; 50% outdoor insect screen; foreground = green
grass (0.23); 8 ft overhang (5.2 ft window ht, 1 ft sep.); 6.8 ft head ht
35322.626216.800.58016nw
Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.21);
50% blinds 45°, medium; 50% outdoor insect screen; foreground = green
grass (0.23); 8 ft overhang (6.7 ft window ht, 1 ft sep.); 6.8 ft head ht
88622.075818.800.65040nw
Doors
(none)
Ceilings
Attic, Metal Roof, R-30 Ceil Ins, 1/2" Gyp Bd Int Fnsh 0.0341801 10960.6117850.9930.0
Floors
On Grade Depth, Tile Flr Fnsh 00573428.700.989200
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Aug-10 10:37:40
Right-Suite® Universal 2021 21.0.08 RSU29066 Page 1
...ents\Wrightsoft HVAC\5406 Birch Dr PSL Prop.rup Calc = MJ8 Front Door faces: N
1588Job:Project Summary 8/10/2021Date:House Chris BatemanBy:
Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
Project Information
Key Largo Spec Home (LHF), Air Conditioning UnlimitedFor:5406 Birch Dr, Fort Pierce, FL 34982
Notes:
Design Information
St Lucie Co Intl, FL, USWeather:
Winter Design Conditions Summer Design Conditions
Outside db °F41 Outside db °F90Inside db °F70 Inside db °F75
Design TD °F29 Design TD °F15Daily range L
Relative humidity %50Moisture difference gr/lb57
Heating Summary Sensible Cooling Equipment Load Sizing
Structure Btuh19130 Structure Btuh15572
Ducts Btuh6076 Ducts Btuh6795Central vent (56 cfm) 1769 Btuh Central vent (56 cfm) Btuh939
Outside air Outside airHumidification Btuh0 Blower Btuh0
Piping Btuh0Equipment load Btuh26975 Use manufacturer's data n
Rate/swing multiplier 0.95InfiltrationEquipment sensible load Btuh22235
Method Latent Cooling Equipment Load SizingSimplified
Construction quality Average0Fireplaces Structure Btuh3032
Ducts Btuh2051Central vent (56 cfm) Btuh2145
CoolingHeating Outside air18011801Area (ft²) Equipment latent load Btuh7228
1577215772Volume (ft³)Air changes/hour 0.200.38 Equipment Total Load (Sen+Lat)Btuh29462
Equiv. AVF (cfm) 53100 Req. total capacity at 0.70 SHR ton2.6
Heating Equipment Summary Cooling Equipment Summary
Make Make Goodman Mfg.Trade Trade GOODMAN
Model Cond GSX16S361AAHRI ref Coil ASPT47D14A
AHRI ref 201785534Efficiency 80 AFUE Efficiency 13.0 EER, 16 SEER
Heating input Btuh0 Sensible cooling Btuh24500Heating output Btuh0 Latent cooling Btuh10500
Temperature rise °F0 Total cooling Btuh35000Actual air flow cfm1167 Actual air flow cfm1167
Air flow factor cfm/Btuh0.046 Air flow factor cfm/Btuh0.052Static pressure in H2O0 Static pressure in H2O0
Space thermostat Load sensible heat ratio 0.76
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Aug-10 10:37:40Right-Suite® Universal 2021 21.0.08 RSU29066 Page 1...ents\Wrightsoft HVAC\5406 Birch Dr PSL Prop.rup Calc = MJ8 Front Door faces: N
1588Job:Right-J® Worksheet 8/10/2021Date:House Chris BatemanBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name House Laundry
2 Exposed wall 199.9 ft 5.5 ft
3 Room height 8.8 ft 8.0 heat/coolft
4 Room dimensions ft6.5x5.5
5 Room area 1800.8 ft²35.8 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 371 371 1169 748 0 0 0 0
.WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 338 251 791 506 0 0 0 0
.GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 sese 17.9817.98 21.3921.39 47 6 841 1001 0 0 0 0
.GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 10.0710.07 40 40 676 405 0 0 0 0
11 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 266 228 717 459 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 20.2520.25 7 2 111 134 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.8221.82 31 4 525 681 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 479 387 1220 780 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 5 0 79 106 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 31 0 525 706 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 16 0 262 353 0 0 0 0
GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nwnw 18.8518.85 22.0422.04 40 0 758 886 0 0 0 0
PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 257 257 754 374 44 44 129 64
CC Attic, Metal Roof, R 0.034Attic, Metal Roof, R 0.034 --0.990.99 0.610.61 1801 1801 1785 1096 36 36 35 22
FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 1801 200 5734 0 36 6 158 0
6 c) AED excursion 447 -32
Envelope loss/gain 15946 8682 322 54
12 a) Infiltration 3184 890 0 0
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 5 1150 0 0
Appliances/other 4850 500
Subtotal (lines 6 to 13)19130 15572 322 554
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 0 0 0 0
14 Subtotal 19130 15572 322 554
15 Duct loads 32%44%6076 6795 32%44%102 242
Total room load 25206 22367 425 796
Air required (cfm)Air required (cfm)1167 1167 20 41
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Aug-10 10:37:40Right-Suite® Universal 2021 21.0.08 RSU29066 Page 2...ents\Wrightsoft HVAC\5406 Birch Dr PSL Prop.rup Calc = MJ8 Front Door faces: N
1588Job:Right-J® Worksheet 8/10/2021Date:House Chris BatemanBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name Bed 2 Bath
2 Exposed wall 24.0 ft 0 ft
3 Room height 8.0 heat/coolft 8.0 heat/coolft
4 Room dimensions ft135.8x1.0 ft6.0x7.0
5 Room area 135.8 ft²42.0 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 0 0 0 0 0 0 0 0
.WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 0 0 0 0 0 0 0 0
.GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 sese 17.9817.98 21.3921.39 0 0 0 0 0 0 0 0
.GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 10.0710.07 0 0 0 0 0 0 0 0
11 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 84 68 216 138 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 20.2520.25 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.8221.82 16 2 262 340 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nwnw 18.8518.85 22.0422.04 0 0 0 0 0 0 0 0
PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 108 108 317 158 0 0 0 0
CC Attic, Metal Roof, R 0.034Attic, Metal Roof, R 0.034 --0.990.99 0.610.61 136 136 135 83 42 42 42 26
FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 136 24 688 0 42 0 0 0
6 c) AED excursion 58 -1
Envelope loss/gain 1618 776 42 24
12 a) Infiltration 184 51 0 0
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 0 0 0 0
Appliances/other 250 0
Subtotal (lines 6 to 13)1802 1078 42 24
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 4 2 2 1
14 Subtotal 1806 1080 44 26
15 Duct loads 32%44%574 471 32%44%14 11
Total room load 2380 1551 58 37
Air required (cfm)Air required (cfm)110 81 3 2
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Aug-10 10:37:40Right-Suite® Universal 2021 21.0.08 RSU29066 Page 3...ents\Wrightsoft HVAC\5406 Birch Dr PSL Prop.rup Calc = MJ8 Front Door faces: N
1588Job:Right-J® Worksheet 8/10/2021Date:House Chris BatemanBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name Bath 2 Hall
2 Exposed wall 6.0 ft 0 ft
3 Room height 8.0 heat/coolft 8.0 heat/coolft
4 Room dimensions ft6.0x8.5 ft8.5x3.5
5 Room area 51.0 ft²29.8 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 0 0 0 0 0 0 0 0
.WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 0 0 0 0 0 0 0 0
.GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 sese 17.9817.98 21.3921.39 0 0 0 0 0 0 0 0
.GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 10.0710.07 0 0 0 0 0 0 0 0
11 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 48 41 130 83 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 20.2520.25 7 2 111 134 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.8221.82 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nwnw 18.8518.85 22.0422.04 0 0 0 0 0 0 0 0
PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0
CC Attic, Metal Roof, R 0.034Attic, Metal Roof, R 0.034 --0.990.99 0.610.61 51 51 51 31 30 30 29 18
FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 51 6 172 0 30 0 0 0
6 c) AED excursion 29 -1
Envelope loss/gain 464 278 29 17
12 a) Infiltration 105 29 0 0
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 0 0 0 0
Appliances/other 0 0
Subtotal (lines 6 to 13)569 307 29 17
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 7 4 -29 -17
14 Subtotal 577 311 0 0
15 Duct loads 32%44%183 136 32%44%0 0
Total room load 760 447 0 0
Air required (cfm)Air required (cfm)35 23 0 0
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Aug-10 10:37:40Right-Suite® Universal 2021 21.0.08 RSU29066 Page 4...ents\Wrightsoft HVAC\5406 Birch Dr PSL Prop.rup Calc = MJ8 Front Door faces: N
1588Job:Right-J® Worksheet 8/10/2021Date:House Chris BatemanBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name Bed 3 Bed 4
2 Exposed wall 25.5 ft 21.0 ft
3 Room height 8.0 heat/coolft 8.0 heat/coolft
4 Room dimensions ft153.3x1.0 ft157.0x1.0
5 Room area 153.3 ft²157.0 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 0 0 0 0 64 64 202 129
.WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 0 0 0 0 0 0 0 0
.GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 sese 17.9817.98 21.3921.39 0 0 0 0 0 0 0 0
.GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 10.0710.07 0 0 0 0 0 0 0 0
11 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 108 92 291 186 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 20.2520.25 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.8221.82 16 2 262 340 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 96 80 253 162 104 88 279 178
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 16 0 262 353 16 0 262 353
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nwnw 18.8518.85 22.0422.04 0 0 0 0 0 0 0 0
PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0
CC Attic, Metal Roof, R 0.034Attic, Metal Roof, R 0.034 --0.990.99 0.610.61 153 153 152 93 157 157 156 96
FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 153 26 731 0 157 21 602 0
6 c) AED excursion 131 66
Envelope loss/gain 1953 1266 1501 822
12 a) Infiltration 447 125 368 103
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 0 0 0 0
Appliances/other 250 250
Subtotal (lines 6 to 13)2399 1641 1869 1175
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 7 4 2 1
14 Subtotal 2407 1645 1871 1176
15 Duct loads 32%44%764 718 32%44%594 513
Total room load 3171 2363 2465 1690
Air required (cfm)Air required (cfm)147 123 114 88
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Aug-10 10:37:40Right-Suite® Universal 2021 21.0.08 RSU29066 Page 5...ents\Wrightsoft HVAC\5406 Birch Dr PSL Prop.rup Calc = MJ8 Front Door faces: N
1588Job:Right-J® Worksheet 8/10/2021Date:House Chris BatemanBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name Foyer GR Pantry
2 Exposed wall 34.5 ft 0 ft
3 Room height 9.5 heat/coolft 8.0 heat/coolft
4 Room dimensions ft426.3x1.0 ft5.5x2.5
5 Room area 426.3 ft²13.8 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 0 0 0 0 0 0 0 0
.WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 223 152 478 306 0 0 0 0
.GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 sese 17.9817.98 21.3921.39 31 4 561 668 0 0 0 0
.GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 10.0710.07 40 40 676 405 0 0 0 0
11 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 20.2520.25 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.8221.82 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nwnw 18.8518.85 22.0422.04 0 0 0 0 0 0 0 0
PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 105 105 307 152 0 0 0 0
CC Attic, Metal Roof, R 0.034Attic, Metal Roof, R 0.034 --0.990.99 0.610.61 426 426 423 259 14 14 14 8
FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 426 35 989 0 14 0 0 0
6 c) AED excursion -79 0
Envelope loss/gain 3435 1711 14 8
12 a) Infiltration 489 137 0 0
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 3 690 0 0
Appliances/other 1400 0
Subtotal (lines 6 to 13)3924 3938 14 8
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 2 1 -14 -8
14 Subtotal 3926 3939 0 0
15 Duct loads 32%44%1247 1719 32%44%0 0
Total room load 5173 5658 0 0
Air required (cfm)Air required (cfm)239 295 0 0
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Aug-10 10:37:40Right-Suite® Universal 2021 21.0.08 RSU29066 Page 6...ents\Wrightsoft HVAC\5406 Birch Dr PSL Prop.rup Calc = MJ8 Front Door faces: N
1588Job:Right-J® Worksheet 8/10/2021Date:House Chris BatemanBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name Kitchen DR Master Bath
2 Exposed wall 28.0 ft 19.5 ft
3 Room height 9.5 heat/coolft 8.0 heat/coolft
4 Room dimensions ft410.5x1.0 ft9.0x10.5
5 Room area 410.5 ft²94.5 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 71 71 224 144 72 72 227 145
.WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 0 0 0 0 0 0 0 0
.GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 sese 17.9817.98 21.3921.39 0 0 0 0 0 0 0 0
.GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 10.0710.07 0 0 0 0 0 0 0 0
11 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 20.2520.25 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.8221.82 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 195 139 438 280 84 79 250 160
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 5 0 79 106
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 16 0 262 353 0 0 0 0
GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nwnw 18.8518.85 22.0422.04 40 0 758 886 0 0 0 0
PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0
CC Attic, Metal Roof, R 0.034Attic, Metal Roof, R 0.034 --0.990.99 0.610.61 411 411 407 250 95 95 94 57
FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 411 28 803 0 95 20 559 0
6 c) AED excursion 271 10
Envelope loss/gain 2892 2184 1209 479
12 a) Infiltration 583 163 342 96
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 2 460 0 0
Appliances/other 1700 0
Subtotal (lines 6 to 13)3475 4507 1550 574
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 12 7 5 3
14 Subtotal 3487 4514 1555 577
15 Duct loads 32%44%1108 1970 32%44%494 252
Total room load 4595 6483 2049 829
Air required (cfm)Air required (cfm)213 338 95 43
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Aug-10 10:37:40Right-Suite® Universal 2021 21.0.08 RSU29066 Page 7...ents\Wrightsoft HVAC\5406 Birch Dr PSL Prop.rup Calc = MJ8 Front Door faces: N
1588Job:Right-J® Worksheet 8/10/2021Date:House Chris BatemanBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name Hers His
2 Exposed wall 4.0 ft 0 ft
3 Room height 8.0 heat/coolft 8.0 heat/coolft
4 Room dimensions ft4.0x5.0 ft8.9x1.0
5 Room area 20.0 ft²8.9 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 32 32 101 64 0 0 0 0
.WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 0 0 0 0 0 0 0 0
.GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 sese 17.9817.98 21.3921.39 0 0 0 0 0 0 0 0
.GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 10.0710.07 0 0 0 0 0 0 0 0
11 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 20.2520.25 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.8221.82 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nwnw 18.8518.85 22.0422.04 0 0 0 0 0 0 0 0
PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0
CC Attic, Metal Roof, R 0.034Attic, Metal Roof, R 0.034 --0.990.99 0.610.61 20 20 20 12 9 9 9 5
FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 20 4 115 0 9 0 0 0
6 c) AED excursion -5 0
Envelope loss/gain 235 71 9 5
12 a) Infiltration 70 20 0 0
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 0 0 0 0
Appliances/other 0 0
Subtotal (lines 6 to 13)305 91 9 5
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 0 0 0 0
14 Subtotal 305 91 9 5
15 Duct loads 32%44%97 40 32%44%3 2
Total room load 402 131 12 7
Air required (cfm)Air required (cfm)19 7 1 0
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Aug-10 10:37:40Right-Suite® Universal 2021 21.0.08 RSU29066 Page 8...ents\Wrightsoft HVAC\5406 Birch Dr PSL Prop.rup Calc = MJ8 Front Door faces: N
1588Job:Right-J® Worksheet 8/10/2021Date:House Chris BatemanBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name Master Bed
2 Exposed wall 31.9 ft
3 Room height 8.5 heat/coolft
4 Room dimensions ft222.4x1.0
5 Room area 222.4 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area Load
number (Btuh/ft²-°F)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 W Blk Wall, Stucco Ext 0.109 ne 3.15 2.02 132 132 415 266
.W Blk Wall, Stucco Ext 0.109 se 3.15 2.02 115 99 312 200
.G Impact, Clear Low-e 0.620 se 17.98 21.39 16 2 280 334
.G Impact, Clear Low-e 0.580 se 16.82 10.07 0 0 0 0
11 W Blk Wall, Stucco Ext 0.109 sw 3.15 2.02 26 26 80 51
G Impact, Clear Low-e 0.580 sw 16.82 20.25 0 0 0 0
G Impact, Clear Low-e 0.580 sw 16.82 21.82 0 0 0 0
W Blk Wall, Stucco Ext 0.109 nw 3.15 2.02 0 0 0 0
G Impact, Clear Low-e 0.580 nw 16.82 22.64 0 0 0 0
G Impact, Clear Low-e 0.580 nw 16.82 22.64 0 0 0 0
G Impact, Clear Low-e 0.580 nw 16.82 22.64 0 0 0 0
G Impact, Clear Low-e 0.650 nw 18.85 22.04 0 0 0 0
P Frm Wall, 1/2" Gyp B 0.101 -2.94 1.46 0 0 0 0
C Attic, Metal Roof, R 0.034 -0.99 0.61 222 222 220 135
F On Grade Depth, Tile 0.989 -28.68 0.00 222 32 915 0
6 c) AED excursion 2
Envelope loss/gain 2224 988
12 a) Infiltration 596 167
b) Room ventilation 0 0
13 Internal gains: Occupants @ 230 0 0
Appliances/other 500
Subtotal (lines 6 to 13)2820 1654
Less external load 0 0
Less transfer 0 0
Redistribution 0 0
14 Subtotal 2820 1654
15 Duct loads 32%44%896 722
Total room load 3716 2376
Air required (cfm)172 124
2021-Aug-10 10:37:40
Right-Suite® Universal 2021 21.0.08 RSU29066 Page 1
...ents\Wrightsoft HVAC\5406 Birch Dr PSL Prop.rup Calc = MJ8 Front Door faces: N
1588Job:Duct System Summary 8/10/2021Date:House Chris BatemanBy:
Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
Project Information
Key Largo Spec Home (LHF), Air Conditioning UnlimitedFor:
5406 Birch Dr, Fort Pierce, FL 34982
CoolingHeating
External static pressure in H2O0in H2O0
Pressure losses in H2O0in H2O0
Available static pressure in H2O0in H2O0
Supply / return available pressure 0.000 / 0.000 in H2O in H2O0.000 / 0.000
Lowest friction rate in/100ft0in/100ft0
Actual air flow cfm1167cfm1167
Total effective length (TEL) ft259
Supply Branch Detail Table
Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv
Name (Btuh)(cfm) (cfm)FR (in)(in)Matl Ln (ft)Ln (ft) Trunk
st195.013.1VlFx0x0002337hBath
st3120.025.2VlFx0x0002842447hBath 2
st195.012.3VlFx0x000971321551hBed 2
st3120.029.1VlFx0x0001481762363hBed 3
st3120.024.2VlFx0x0001061371690hBed 4
st2100.032.8VlFx0x0001771442829cFoyer GR
st2100.032.9VlFx0x0001771442829cFoyer GR-A
st4130.048.8VlFx0x000822131hHers
st4125.044.3VlFx0x000017hHis
st2100.032.7VlFx0x0002031283242cKitchen DR-A
st2100.032.4VlFx0x0002031283242cKitchen DR-B
st195.013.1VlFx0x0005024796cLaundry
st4125.050.7VlFx0x00052114829hMaster Bath
st4125.048.5VlFx0x000741031188hMaster Bed
st4125.044.1VlFx0x000741031188hMaster Bed-A
Supply Trunk Detail Table
Trunk Htg Clg Design Veloc Diam H x W Duct
Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk
st4 Peak AVF 343 209 0 0 0 0x0 VinlFlx st2
st3 Peak AVF 355 282 0 0 0 0x0 VinlFlx st1
st1 Peak AVF 514 431 0 0 0 0x0 VinlFlx
st2 Peak AVF 886 969 0 0 0 0x0 VinlFlx
Bold/italic values have been manually overridden
2021-Aug-10 10:37:40
Right-Suite® Universal 2021 21.0.08 RSU29066 Page 2
...ents\Wrightsoft HVAC\5406 Birch Dr PSL Prop.rup Calc = MJ8 Front Door faces: N
Return Branch Detail Table
Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct
Name Size (in) (cfm)(cfm)(ft)FR (fpm)(in)(in)Opening (in) Matl Trunk
rb5 0x 1370 106 79.1 0 0 0 x0 0 VlFx rt1
rb6 0x 1760 148 80.5 0 0 0 x0 0 VlFx rt1
rb7 0x 1320 97 66.3 0 0 0 x0 0 VlFx rt1
rb1 0x 7250 892 36.9 0 0 0 x0 0 VlFx rt1
rb8 0x 2290 157 0 0 0 0 x0 0 VlFx
Return Trunk Detail Table
Trunk Htg Clg Design Veloc Diam H x W Duct
Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk
rt1 Peak AVF 1171 1243 0 703 18.0 0x0 VinlFlx
2021-Aug-10 10:37:40
Right-Suite® Universal 2021 21.0.08 RSU29066 Page 1
...ents\Wrightsoft HVAC\5406 Birch Dr PSL Prop.rup Calc = MJ8 Front Door faces: N
1588Job:Manual S Compliance Report 8/10/2021Date:House Chris BatemanBy:
Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
Project Information
Key Largo Spec Home (LHF), Air Conditioning UnlimitedFor:
5406 Birch Dr, Fort Pierce, FL 34982
Cooling Equipment
Design Conditions
°F76.8Entering coil DB:Btuh23307Sensible gain:°F90.4Outdoor design DB:
°F64.0Entering coil WB:Btuh7228Latent gain:°F77.4Outdoor design WB:
Btuh30534Total gain:°F75.0Indoor design DB:
cfm1167Estimated airflow:%50Indoor RH:
Manufacturer's Performance Data at Actual Design Conditions
Split ACEquipment type:
GSX16S361A+ASPT47D14AModel:Goodman Mfg.Manufacturer:
cfm1167Actual airflow:
% of load105Btuh24500Sensible capacity:
% of load145Btuh10500Latent capacity:
%70SHR:% of load115Btuh35000Total capacity:
Heating Equipment
Design Conditions
°F68.1Entering coil DB:Btuh26975Heat loss:°F41.0Outdoor design DB:
°F70.0Indoor design DB:
Manufacturer's Performance Data at Actual Design Conditions
Gas furnaceEquipment type:
Model:Manufacturer:
cfm1167Actual airflow:
°F0Temp. rise:% of load0Btuh0Output capacity:
Meets all requirements of ACCA Manual S.