In-Place Density Test Report
Client:RJM CUSTOM HOMES, INC.UES Technician:Johnnie Smith
6917 Vista Parkway North, Suite 1
West Palm Beach, FL 33411
Date Tested:01/11/2022
Project:RJM CUSTOM HOMES
Various Locations, TBD County, FL
Type of Test:
Area Tested:9624 Knollwood Lane, Ft. Pierce -
Foundation Pad
Field:ASTM D-6938 Nuclear Gauge Method
Material:Fill Laboratory:ASTM D1557 Modified Proctor
Reference Datum:0 = Bottom of Footing
The tests below meet the 95% minimum compaction requirement.
Test
No.Location of Test Range
Maximum
Density
(pcf)
Optimum
Moisture
(%)
Field Dry
Density
(pcf)
Field
Moisture
(%)
Soil
Compaction
(%)
Pass
or
Fail
1 E Section 0-1 ft 118.8 10.8 117.1 9.9 99 Pass
2 W Section 0-1 ft 118.8 10.8 118.6 10.0 100 Pass
3 Center 0-1 ft 118.8 10.8 118.4 10.7 100 Pass
Remarks:1-2', 2-3', 3-4', bottom of footing HCP=50+, > 95% Compaction, PASS. HCP tests are empirically correlated to the
relative density of the soil.
Permit: 2108-0081
Reviewed By
GFA International, Inc
FBPE Registry No.4930
Allan G. Abubakar, P.E.
STATE OF FLORIDA
Professional Engineer No. 69952
This item has been digitally signed and sealed by Allan G.
Abubakar, P.E. on the date adjacent to the seal. Printed copies of
this document are not considered signed and sealed and the
signature must be verified on any electronic copies.
To establish a mutual protection to Universal's clients, the Public and ourselves, all reports are submitted as confidential property of our clients and
authorization for publication of statements, conclusions or extracts from or regarding Universal's reports is reserved pending our written approval.
Page 1