HomeMy WebLinkAboutAPPROVED2020 PolyGlass ModiBit PRODUCT APPNEMO|etc. NEMO ETC, LLC Evaluation Report P9290.02.08-R25 for FL1654-R27 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 25: 09/30/2020 ©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 1 of 94 APPENDIX 1: ATTACHMENT REQUIREMENTS FOR WIND UPLIFT RESISTANCE TABLE DECK APPLICATION TYPE DESCRIPTION PAGE 1A Wood New or Reroof (Tear-Off) A-1 Bonded Insulation, Bonded Roof Cover 5 1B Wood New or Reroof (Tear-Off) A-2 Mech. Attached Anchor Sheet, Bonded Insulation, Bonded Roof Cover 6-12 1C Wood New, Reroof (Tear-Off) or Recover A-2 Mech. Attached Anchor Sheet, Bonded Insulation, Bonded Roof Cover 12-14 1D Wood New, Reroof (Tear-Off) or Recover B-1 Mech. Attached Base Insulation, Bonded Top Insulation, Bonded Roof Cover 14-15 1E Wood New, Reroof (Tear-Off) or Recover C-1 Mech. Attached Insulation, Bonded Roof Cover 15-19 1F Wood New, Reroof (Tear-Off) or Recover D-2 Insulated, Mech. Attached Base Sheet, Bonded Roof Cover 19-23 1G Wood New or Reroof (Tear-Off) E-2 Non-Insulated, Mech. Attached Base Sheet (nails), Bonded Roof Cover 23-29 1H Wood New, Reroof (Tear-Off) or Recover E-2 Non-Insulated, Mech. Attached Base Sheet (screws & plates), Bonded Roof Cover 29-36 1I Wood New or Reroof (Tear-Off) F Non-Insulated, Bonded Roof Cover 37 2A Steel or Structural concrete New, Reroof (Tear-Off) or Recover B-1 Mech. Attached Base Insulation, Bonded Top Insulation, Bonded Roof Cover 38-43 2B Steel or Structural concrete New, Reroof (Tear-Off) or Recover C-1 Mech. Attached Insulation, Bonded Roof Cover 44-50 2C Steel or Structural concrete New, Reroof (Tear-Off) or Recover D-2 Insulated, Mech. Attached Base Sheet, Bonded Roof Cover 51-53 2D Steel or Structural concrete New, Reroof (Tear-Off) or Recover D-2 Insulated, Mech. Attached Velociflex, Bonded Roof Cover 53-55 3A Structural concrete New or Reroof (Tear-Off) A-1 Bonded Insulation, Bonded Roof Cover 56-68 3B Structural concrete New or Reroof (Tear-Off) F Non-Insulated, Bonded Roof Cover 68 4A Lightweight concrete New or Reroof (Tear-Off) A-1 Bonded Insulation, Bonded Roof Cover 69-73 4B Lightweight concrete New or Reroof (Tear-Off) A-2 Mech. Attached Anchor Sheet, Bonded Insulation, Bonded Roof Cover 73-47 4C Lightweight concrete New or Reroof (Tear-Off) E-2 Non-Insulated, Mech. Attached Base Sheet, Bonded Roof Cover 74-78 5A Cementitious wood fiber Reroof (Tear-Off) A-1 Bonded Insulation, Bonded Roof Cover 79-80 5B Cementitious wood fiber Reroof (Tear-Off) or Recover A-2 Mech. Attached Anchor Sheet, Bonded Insulation, Bonded Roof Cover 80-82 5C Cementitious wood fiber Reroof (Tear-Off) or Recover B-1 Mech. Attached Base Insulation, Bonded Top Insulation, Bonded Roof Cover 82 5D Cementitious wood fiber Reroof (Tear-Off) or Recover C-1 Mech. Attached Insulation, Bonded Roof Cover 83 5E Cementitious wood fiber Reroof (Tear-Off) or Recover E-2 Non-Insulated, Mech. Attached Base Sheet, Bonded Roof Cover 83 6A Existing gypsum Reroof (Tear-Off) A-1 Bonded Insulation, Bonded Roof Cover 84-88 6B Existing gypsum Reroof (Tear-Off) or Recover A-2 Mech. Attached Anchor Sheet, Bonded Insulation, Bonded Roof Cover 88 6C Existing gypsum Reroof (Tear-Off) or Recover C-1 Mech. Attached Insulation, Bonded Roof Cover 88 6D Existing gypsum Reroof (Tear-Off) or Recover E-2 Non-Insulated, Mech. Attached Base Sheet, Bonded Roof Cover 88 7A Various Recover A-1 Bonded Insulation, Bonded Roof Cover 89-94 7B Various Recover F Non-Insulated, Bonded Roof Cover 94 NEMO|etc. NEMO ETC, LLC Evaluation Report P9290.02.08-R25 for FL1654-R27 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 25: 09/30/2020 ©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 2 of 94 The following notes apply to the systems outlined herein: 1 The roof system evaluation herein pertains to above-deck roof components. Roof decks and structural members shall be in accordance with FBC requirements to the satisfaction of the Authority Having Jurisdiction. 2 Fasteners shall be of sufficient length for the following engagements: ➢ Wood Deck: Minimum 1-inch plywood penetration or wood plank embedment. ➢ Steel Deck: Minimum 0.75-inch steel penetration and engage the top flute of the steel deck. ➢ Structural Concrete: Minimum 1-inch embedment into pilot hole in accordance with published installation instructions. 3 Unless otherwise noted, insulation may be any one layer or combination of FBC Approved (Local or Statewide) board(s) that meet FBC 1505 and, for foam plastic, FBC Chapter 26, when installed with the roof cover. 4 Minimum 200 psi, minimum 2-inch thick FBC Approved lightweight insulating concrete may be substituted for rigid insulation board for System Types B-1, C-1, C-2, D-1 or D-2, whereby fasteners are installed through the lightweight insulating concrete to engage the structural deck. The structural deck shall be of equal or greater type, thickness and strength to the steel and structural concrete deck listings. Roof decks and structural members shall be in accordance with FBC requirements to the satisfaction of the Authority Having Jurisdi ction. This is a wind uplift resistance allowance and does not purport to address non-wind-uplift-related issues, such as deck venting or moisture levels within the LWIC and the potential effect on overlying components. 5 Preliminary insulation attachment for System Type D: Unless otherwise noted, refer to Section 2.2.10.1.3 of FM Loss Prevention Data Sheet 1-29 (February 2020). 6 Unless otherwise noted, insulation adhesive application rates are as follows. Ribbon or bead width is at the time of application; the ribbons/beads shall expand as noted in the manufacturer’s published instructions. ➢ Hot asphalt (HA): Full coverage at 25-30 lbs/square. ➢ DuPont INSTA STIK Quik Set Insulation Adhesive (D-IS): Continuous 0.75 to 1-inch wide ribbons, 12-inch o.c. ➢ H.B. Fuller Millennium One Step Foamable Adhesive (M-OSFA): Continuous 0.25 to 0.5-inch wide ribbons, 12-inch o.c. ➢ H.B. Fuller Millennium PG-1 Pump Grade Adhesive (M-PG1): Continuous 0.25 to 0.5-inch wide ribbons, 12-inch o.c. ➢ OMG OlyBond 500 (OB500): Continuous 0.75 to 1-inch wide ribbons, 12-inch o.c. Note: OlyBond Green may be used where OlyBond 500 is referenced. ➢ OlyBond Classic (OB Classic): Full coverage at 1 gal/square. ➢ ICP Adhesive & Sealants Polyset CR-20: Continuous 2.5-3.5-inch wide ribbons, 12-inch o.c. ➢ Note: When multiple layers(s) of insulation and/or coverboard are installed in ribbon-applied adhesive, board joints shall be staggered. ➢ Note: The maximum edge distance from the adhesive ribbon to the edge of the insulation board shall be not less than one -half the specified ribbons spacing. 7 Unless otherwise noted, all insulations are flat-stock or taper board of the minimum thickness noted. Tapered polyisocyanurate at the following thickness limitations may be substituted with the following Maximum Design Pressure (MDP) limitations. In no case shall these values be used to ‘increase’ the MDP listings in the tables; rather if MDP listing below meets or exceeds that listed for a particular system in the tables, then the thinner board listed below may be used as a drop-in for the equivalent thicker material listed in the table. ➢ H.B. Fuller Millennium One Step Foamable Adhesive (M-OSFA): MDP = -157.5 psf (Min. 0.5-inch thick) ➢ H.B. Fuller Millennium PG-1 Pump Grade Adhesive (M-PG1): MDP = -157.5 psf (Min. 0.5-inch thick) ➢ OMG OlyBond 500 (OB500): MDP = -45.0 psf (Min. 0.5-inch thick Multi-Max FA-3) ➢ OMG OlyBond 500 (OB500): MDP = -187.5 psf (Min. 0.5-inch thick ISO 95+ GL) ➢ OMG OlyBond 500 (OB500): MDP = -315.0 psf (Min. 0.5-inch thick ENRGY 3) ➢ OMG OlyBond 500 (OB500): MDP = -487.5 psf (Min. 0.5-inch thick ACFoam II) ➢ ICP Adhesives & Sealants Polyset CR-20: MDP = -117.5 psf (Min. 1.0-inch thick) 8 For adhered roof insulation and board-size: Unless otherwise noted, refer to Section 2.2.10.6.2 of FM Loss Prevention Data Sheet 1-29 (February 2020). 9 For mechanically attached components or partially-bonded insulation, the maximum design pressure for the selected assembly shall meet or exceed at least the Zone 1 PRIME design pressure determined in accordance with FBC Chapter 16. Elevated pressure zones shall employ an attachment density designed by a qualified design professional to resist the elevated pressure criteria. Commonly used methods are NEMO|etc. NEMO ETC, LLC Evaluation Report P9290.02.08-R25 for FL1654-R27 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 25: 09/30/2020 ©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 3 of 94 ANSI/SPRI WD1, FM Loss Prevention Data Sheet 1-29, Roofing Application Standard RAS 117 and Roofing Application Standard RAS 137. Assemblies marked with an asterisk* carry the limitations set forth in Section 2.2.10.1 of FM Loss Prevention Data Sheet 1-29 (February 2020) for Zone 2/3 enhancements. 10 For assemblies with all components fully bonded, the maximum design pressure for the selected assembly shall meet or exceed critical design pressure determined in accordance with FBC Chapter 16. No rational analysis is permitted for these systems. 11 For mechanically attached components over existing decks, fasteners shall be tested in the existing deck for withdrawal resistance. A qualified design professional sh all review the data for comparison to the minimum requirements for the system. Testing and analysis shall be in accordance with ANSI/SPRI FX-1 or Testing Application Standard TAS 105. 12 For bonded insulation or membrane over existing substrates in a re-roof (tear off) or recover installation, the existing deck or existing roof surface shall be examined for compatibility with the adhesive to be installed. If any surface conditions exist that bring system performance into question, field uplift testing in accordance s hall be conducted on mock-ups of the proposed new roof assembly. For bonded insulation or membrane over existing substrates in a recover installation, the existing roof system shall be capable of resisting project design pressures on its own merit to the satisfaction of the Authority Having Jurisdiction, as documented through field uplift testing. Field uplift testing shall be in accordance with ASTM E907, FM Loss Prevention Data Sheet 1-52 or Testing Application Standard TAS 124. 13 Refer to FBC 1511 for requirements and limitations regarding recover installations. For Structural Concrete Deck or Recover Applications using System Type C-1, C-2, D-1 or D-2, the insulation is optional. Alternatively, an FBC Approved insulation board or coverboard may be used as a separation layer. Board products shall be preliminarily attached prior to roof cover installation (Note 5 herein). The separator component shall be documented as meeting FBC 1505 and, for foam plastic, FBC Chapter 26, when installed with the roof cover in Recover applications. 14 Lightweight insulating concrete (LWIC) shall be cast in accordance with FBC Section 1917 to the satisfaction of the Authority Having Jurisdiction. For systems where specific LWIC i s referenced, refer to current LWIC Product Approval for specific deck construction and limitations. Unless otherwise noted, for systems where specific LWIC is not referenced, the minimum design mix shall be 300 psi. In all cases, the minimum top-coat thickness is 2-inches. For LWIC over structural concrete, reference is made to FBC Section 1917.4.1, Point 1. For “pre-existent” LWIC references, listings were established through testing over lightweight concrete cast using only foaming agent (ASTM C896), water and Portland cement (ASTM C150), with no proprietary additives, in accordance with procedures adopted by Miami-Dade BCCO (FBC CER1592). Use of these listings in new construction or re-roof (tear-off) applications is at the discretion of the Designer or Record and Authority Having Jurisdiction. 15 For bonded membrane applications, unless otherwise noted, refer to the following. MEMBRANE / ADHESIVE COMBINATIONS REFERENCE LAYER MATERIAL APPLICATION BP-AA (Base and Ply sheets, Asphalt-Applied) Base Ply One or more plies Polyglass G2 Base, FBC Approved ASTM D4601, Type II Hot Asphalt at 20-40 lbs/square Ply One or more plies Polyglass Ply IV, Polyglass Ply VI, FBC Approved ASTM D2178, Type IV or VI Note: Asphalt-applied sheets or insulation shall not be applied to poly-film surfaced membranes. SBS-CA1 Base Ply One ply Elastobase (sand/sand), Elastoflex V, Elastoflex S6, Elastoflex S6 HP, Elastoshield HT PG350 at 1.5-2.0 gal/square Cap Ply Elastoshield HT G, Elastoshield HT G FR, Elastoflex V G, Elastoflex V G FR, Elastoflex S6, Elastoflex S6 HP, Elastoflex S6 G, Elastoflex S6 G FR, Elastoshield TS G, Elastoshield TS G FR, Polyfresko G SBS (sand-backed), Polyfresko G SBS FR (sand-backed) SBS-CA2 Base Ply One ply Elastobase (sand/sand), Elastoflex V, Elastoflex S6, Elastoflex S6 HP Polyplus 35 at 1.5-2.0 gal/square Cap Ply Elastoshield HT G, Elastoshield HT G FR, Elastoflex V G, Elastoflex V G FR, Elastoflex S6, Elastoflex S6 HP, Elastoflex S6 G, Elastoflex S6 G FR, Elastoshield TS G, Elastoshield TS G FR, Polyfresko G SBS (sand-backed), Polyfresko G SBS FR (sand-backed) SBS-AA (SBS, Asphalt-Applied) Base Ply or Ply One or more plies Elastobase (sand/sand or poly/sand), Elastobase P (sand/sand or poly/sand), Elastoflex V, Elastoflex S6, Elastoflex S6 HP, Elastoshield HT Hot Asphalt at 20-40 lbs/square Cap Ply Elastoshield HT G, Elastoshield HT G FR, Elastoflex V, Elastoflex V G, Elastoflex V G FR, Elastoflex S6, Elastoflex S6 HP, Elastoflex S6 G, Elastoflex S6 G FR, Elastoshield TS G, Elastoshield TS G FR, Polyfresko G SBS (sand-backed), Polyfresko G SBS FR (sand-backed) Note: Asphalt-applied sheets or insulation shall not be applied to poly-film surfaced membranes. SBS-TA (SBS, Torch-Applied) Base Ply or Ply One or more plies Elastobase (sand/poly), Elastobase (poly/poly), Elastoflex V, Elastoflex S6, Elastoflex S6 HP, Elastoshield HT Torch-Applied Cap Ply Elastoshield HT G, Elastoshield HT G FR, Elastoflex V, Elastoflex V G, Elastoflex V G FR, Elastoflex S6, Elastoflex S6 HP, Elastoflex S6 G, Elastoflex S6 G FR, Elastoshield TS G, Elastoshield TS G FR, Polyfresko G SBS (poly-film backed), Polyfresko G SBS FR (poly-film backed) NEMO|etc. NEMO ETC, LLC Evaluation Report P9290.02.08-R25 for FL1654-R27 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 25: 09/30/2020 ©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 4 of 94 MEMBRANE / ADHESIVE COMBINATIONS REFERENCE LAYER MATERIAL APPLICATION SBS-SA-H (SBS, Self-Adhering, Hybrid Systems) Base Ply Elastobase SA Self-adhering (followed by torch-applied sheet) SBS-SA (SBS, Self-Adhering) Base Ply One or more plies Elastoflex SA V, Elastoflex SA V FR, Elastoflex SA V Plus, Elastoflex SA V Plus FR, Elastoflex SA Base HD Self-Adhering Cap Ply Elastoflex SA P, Elastoflex SA P FR, Polyreflect Note: Unless otherwise noted, permissible membrane substrates for SBS-SA are limited to the SBS-SA Base Ply options herein, Elastobase (poly/sand) or Elastobase (poly/poly). APP-CA1 Cap Ply Polyflex G FR PG350 at 1.5-2.0 gal/square APP-TA (APP, Torch-Applied) Base Ply or Ply One or more plies Polyglass Base, Polyflex, Polybond Torch-Applied Cap Ply Polyflex, Polyflex G, Polyflex G FR, Polybond, Polybond G, Polyfresko G, Polyfresko G FR APP-SA-H (APP, Self-Adhering, Hybrid Systems) Base Ply Polyflex SA Base Self-adhering (followed by torch-applied sheet) APP-SA (APP, Self-Adhering) Cap Ply Polyflex SA P, Polyflex SA P FR, Polyfresko G SA, Polyfresko G SA FR, Polykool Self-Adhering Note: Unless otherwise noted, permissible membrane substrates for APP-SA are limited to the SBS-SA Base Ply options herein, Elastobase (poly/sand) or Elastobase (poly/poly). 16 Vapor barrier options for use over structural concrete deck followed by bonded insulation carry the following MDP limitations. The lesser of the MDP listings below vs. those in Table 3A applies. VAPOR BARRIER OPTIONS; STRUCTURAL CONCRETE DECK; FOLLOWED BY ADHESIVE-APPLIED INSULATION PER TABLE 3A: OPTION # PRIMER VAPOR BARRIER INSULATION ADHESIVE MDP (PSF) TYPE (NOTE 15) APPLICATION C-VB-1. PG100 Elastoflex SA V Plus Self-Adhering D-IS or CR-20, 12-inch o.c. -60.0 C-VB-2. PG100 Polyglass Base Torch-applied D-IS or CR-20, 12-inch o.c. -75.0 C-VB-3. PG100 Elastoflex SA P Self-Adhering D-IS, 12-inch o.c. -75.0 C-VB-4. PG100 Elastoflex SA P Self-Adhering M-OSFA, 12-inch o.c. -157.5 C-VB-5. PG100 Elastoflex SA P Self-Adhering CR-20, 12-inch o.c. -270.0 C-VB-6. PG100 Elastoflex SA V, Elastoflex SA V FR, Elastoflex SA V Plus, Elastoflex SA V Plus FR Self-Adhering M-OSFA, M-PG-1, OB500 or CR-20, 12-inch o.c. -290.0 C-VB-7. PG100 SBS-TA (with sanded-top-surface) Torch-applied M-OSFA, M-PG-1, OB500 or CR-20, 12-inch o.c. -290.0 17 The following surfacing may be applied to the Cap Ply without adverse effect on the system wind load performance. Refer to current Florida Product Approval for approved Polyglass and KM Coatings roof coatings for application limitations and a Roofing Materials Directory for fire ratings associated with coating usage. SURFACING OPTIONS FOR POLYGLASS MODIFIED BITUMEN ROOF SYSTEMS OPTION # SURFACING FLORIDA PRODUCT APPROVAL SURF-1. PG 300 FL10291 SURF-2. PG 600 FL10291 SURF-3. PG 650 FL10291 SURF-4. PG 700 FL10291 SURF-5. PG 700 QS FL10291 SURF-6. PG 800 FL10291 SURF-7. Polyplus 60 FL10291 NEMO|etc. NEMO ETC, LLC Evaluation Report P9290.02.08-R25 for FL1654-R27 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 25: 09/30/2020 ©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 5 of 94 SURFACING OPTIONS FOR POLYGLASS MODIFIED BITUMEN ROOF SYSTEMS OPTION # SURFACING FLORIDA PRODUCT APPROVAL SURF-8. Polyplus 65 FL10291 SURF-9. PolyBrite 60-FC NOA 20-0611.01 SURF-10. PolyBrite 70 FL10291 SURF-11. PolyBrite 70 QS FL10291 SURF-12. PolyBrite 75 FL10291 SURF-13. PolyBrite 71 HS FL10291 SURF-14. PolyBrite 90 FL10291 SURF-15. PolyBrite 90.1 NOA 19-0610.02 SURF-16. PolyBrite 95 FL10291 SURF-17. PolyBrite 95.1 NOA 19-0610.02 SURF-18. KM Acryl 15 FL27409 SURF-19. KM Acryl 15 QS FL27409 SURF-20. KM Acryl 25 FL27409 SURF-21. KM Acryl 25 QS FL27409 SURF-22. KM Acryl 40 HS FL27409 SURF-23. KM Acryl 85 FL27409 SURF-24. KM PS#250 FL27409 SURF-25. KM PS#220 FL27409 SURF-26. Turbo-Set FL10291 18 “MDP” = Maximum Design Pressure is the result of testing for wind load resistance based on allowable wind loads. Refer to FBC 1609 for determination of design wind loads TABLE 1A: WOOD DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF) SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER System No. Deck (Note 1) Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP (psf) Type Attach (Notes 6,7,8) Type Attach (Notes 6,7,8) Base Ply Ply Cap Ply SELF-ADHERING BASE PLY: W-1 Min. 15/32- inch plywood Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY-3, Polytherm H, H-Shield, H-Shield CG, Multi-Max FA3 D-IS, M-OSFA, OB500 or CR-20 (Optional) additional layers(s) of base insulation D-IS, M-OSFA, OB500 or CR-20 SBS-SA (Optional) SBS-SA, SBS- TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -52.5 HYBRID SYSTEMS WITH SELF-ADHERING APP BASE PLY: W-2 Min. 15/32- inch plywood Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY-3, Polytherm H, H-Shield, H-Shield CG, Multi-Max FA3 D-IS, M-OSFA, OB500 or CR-20 (Optional) additional layers(s) of base insulation D-IS, M-OSFA, OB500 or CR-20 APP-SA-H (Optional) APP-TA APP-TA -52.5 HYBRID SYSTEMS WITH SELF-ADHERING SBS BASE PLY: W-3 Min. 15/32- inch plywood Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY-3, Polytherm H, H-Shield, H-Shield CG, Multi-Max FA3 D-IS, M-OSFA, OB500 or CR-20 (Optional) additional layers(s) of base insulation D-IS, M-OSFA, OB500 or CR-20 SBS-SA-H (Optional) SBS-TA SBS-TA -52.5 NEMO|etc. NEMO ETC, LLC Evaluation Report P9290.02.08-R25 for FL1654-R27 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 25: 09/30/2020 ©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 6 of 94 TABLE 1B: WOOD DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF) SYSTEM TYPE A-2: MECHANICALLY ATTACHED ANCHOR SHEET, BONDED INSULATION, BONDED ROOF COVER System No. Deck (Note 1) Anchor Sheet Base Insulation Top Insulation Roof Cover (Note 15) MDP (psf) Type Fasten (Note 11) Attach Type Attach (Notes 6,7,8) Type Attach (Notes 6,7,8) Base Ply Ply Cap Ply ASPHALT-APPLIED OR TORCH-APPLIED BASE PLY: W-4 Min. 15/32- inch plywood Elastobase, Elastobase P (sanded-top) Simplex MAXX Cap 9-inch o.c. at min. 2-inch lap and 18- inch o.c. at two (2), equally spaced, staggered center rows (Optional) Min. 1.5- inch Polytherm, ACFoam II, ENRGY-3, Polytherm H, H-Shield, H-Shield CG, Multi- Max FA3 Hot asphalt Min. 0.75-inch Fesco Board (homogeneous) or min. 0.5-inch Structodek High Density Fiberboard Roof Insulation Hot asphalt BP-AA or SBS- AA (Optional) BP-AA or SBS-AA SBS-AA, SBS-TA, APP-TA -45.0* W-5 Min. 15/32- inch plywood Elastobase, Elastobase P (sanded-top) Simplex MAXX Cap 9-inch o.c. at min. 2-inch lap and 18- inch o.c. at two (2), equally spaced, staggered center rows (Optional) Min. 1.5- inch Polytherm, ACFoam II, ENRGY-3, Polytherm H, H-Shield, H-Shield CG, Multi- Max FA3 Hot asphalt Min. 0.25-inch DensDeck, DensDeck Prime, SECUROCK Gypsum-Fiber Roof Board Hot asphalt BP-AA, SBS- AA, SBS-TA, APP-TA (Optional) BP-AA, SBS- AA, SBS-TA, APP-TA SBS-AA, SBS-TA, APP-TA -45.0* W-6 Min. 15/32- inch plywood Elastobase, Elastobase P (sanded-top) Simplex MAXX Cap 9-inch o.c. at min. 2-inch lap and 12- inch o.c. at two (2), equally spaced, staggered center rows (Optional) Min. 1.5- inch Polytherm, ACFoam II, ENRGY-3, Polytherm H, H-Shield, H-Shield CG, Multi- Max FA3 Hot asphalt Min. 0.75-inch Fesco Board (homogeneous) or min. 0.5-inch Structodek High Density Fiberboard Roof Insulation Hot asphalt BP-AA or SBS- AA (Optional) BP-AA or SBS-AA SBS-AA, SBS-TA, APP-TA -52.5 W-7 Min. 15/32- inch plywood Elastobase, Elastobase P (sanded-top) Simplex MAXX Cap 9-inch o.c. at min. 2-inch lap and 12- inch o.c. at two (2), equally spaced, staggered center rows (Optional) Min. 1.5- inch Polytherm, ACFoam II, ENRGY-3, Polytherm H, H-Shield, H-Shield CG, Multi- Max FA3 Hot asphalt Min. 0.25-inch DensDeck, DensDeck Prime, SECUROCK Gypsum-Fiber Roof Board Hot asphalt BP-AA, SBS- AA, SBS-TA, APP-TA (Optional) BP-AA, SBS- AA, SBS-TA, APP-TA SBS-AA, SBS-TA, APP-TA -52.5 W-8 Min. 19/32- inch plywood Polyglass G2 Base, Elastobase, Elastobase P (sanded-top), Elastovent, CertainTeed Glasbase, Firestone MB Base, JM Perma- Ply 28 or GAFGLAS #75 32 ga., 1-5/8- inch diameter tin caps with 11 ga. annular ring shank nails 8-inch o.c. at min. 4-inch lap and 8- inch o.c. at three (3), equally spaced, staggered center rows (Optional) Min. 1.5- inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY- 3, Polytherm H, H- Shield, H-Shield CG, Multi-Max FA3 Hot asphalt Min. 0.75-inch Fesco Board (homogeneous) or min. 0.5-inch Structodek High Density Fiberboard Roof Insulation Hot asphalt BP-AA or SBS- AA (Optional) BP-AA or SBS-AA SBS-AA, SBS-TA, APP-TA -60.0 NEMO|etc. NEMO ETC, LLC Evaluation Report P9290.02.08-R25 for FL1654-R27 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 25: 09/30/2020 ©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 7 of 94 TABLE 1B: WOOD DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF) SYSTEM TYPE A-2: MECHANICALLY ATTACHED ANCHOR SHEET, BONDED INSULATION, BONDED ROOF COVER System No. Deck (Note 1) Anchor Sheet Base Insulation Top Insulation Roof Cover (Note 15) MDP (psf) Type Fasten (Note 11) Attach Type Attach (Notes 6,7,8) Type Attach (Notes 6,7,8) Base Ply Ply Cap Ply W-9 Min. 19/32- inch plywood Polyglass G2 Base, Elastobase, Elastobase P (sanded-top), Elastovent, CertainTeed Glasbase, Firestone MB Base, JM Perma- Ply 28 or GAFGLAS #75 32 ga., 1-5/8- inch diameter tin caps with 11 ga. annular ring shank nails 8-inch o.c. at min. 4-inch lap and 8- inch o.c. at three (3), equally spaced, staggered center rows (Optional) Min. 1.5- inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY- 3, Polytherm H, H- Shield, H-Shield CG, Multi-Max FA3 Hot asphalt Min. 0.25-inch DensDeck Prime, SECUROCK Gypsum- Fiber Roof Board Hot asphalt BP-AA, SBS- AA, SBS-TA, APP-TA (Optional) BP-AA, SBS- AA, SBS-TA, APP-TA SBS-AA, SBS-TA, APP-TA -60.0 W-10 Min. 19/32- inch plywood Elastobase, Elastobase P (sanded-top) Simplex MAXX Cap Fasteners 12-inch o.c. at min. 4-inch lap and 12- inch o.c. at two (2), equally spaced, staggered center rows (Optional) Min. 1.5- inch Polytherm, ACFoam II, ENRGY-3, Polytherm H, H-Shield, H-Shield CG, Multi- Max FA3 Hot asphalt Min. 0.75-inch Fesco Board (homogeneous) or min. 0.5-inch Structodek High Density Fiberboard Roof Insulation Hot asphalt BP-AA or SBS- AA (Optional) BP-AA or SBS-AA SBS-AA, SBS-TA, APP-TA -60.0 W-11 Min. 19/32- inch plywood Elastobase, Elastobase P (sanded-top) Simplex MAXX Cap Fasteners 12-inch o.c. at min. 4-inch lap and 12- inch o.c. at two (2), equally spaced, staggered center rows (Optional) Min. 1.5- inch Polytherm, ACFoam II, ENRGY-3, Polytherm H, H-Shield, H-Shield CG, Multi- Max FA3 Hot asphalt Min. 0.25-inch DensDeck, DensDeck Prime, SECUROCK Gypsum-Fiber Roof Board Hot asphalt BP-AA, SBS- AA, SBS-TA, APP-TA (Optional) BP-AA, SBS- AA, SBS-TA, APP-TA SBS-AA, SBS-TA, APP-TA -60.0 W-12 Min. 15/32- inch plywood Elastobase, Elastobase P(sanded-top) or Elastovent 32 ga., 1-5/8- inch diameter tin caps with 12 ga. annular ring shank nails 8-inch o.c. at min. 4-inch lap and 8- inch o.c. at four (4), equally spaced, staggered center rows (Optional) Min. 1.5- inch Polytherm, ACFoam II, ENRGY-3, Polytherm H, H-Shield, H-Shield CG, Multi- Max FA3 Hot asphalt Min. 0.25-inch DensDeck Prime, SECUROCK Gypsum- Fiber Roof Board Hot asphalt BP-AA, SBS- AA, SBS-TA, APP-TA (Optional) BP-AA, SBS- AA, SBS-TA, APP-TA SBS-AA, SBS-TA, APP-TA -67.5 W-13 Min. 15/32- inch plywood Polyglass G2 Base Simplex MAXX Cap 9-inch o.c. at min. 4-inch lap and 9- inch o.c. at four (4), equally spaced, staggered center rows (Optional) Min. 1.5- inch Polytherm, ACFoam II, ENRGY-3, Polytherm H, H-Shield, H-Shield CG, Multi- Max FA3 Hot asphalt Min. 0.25-inch DensDeck Prime, SECUROCK Gypsum- Fiber Roof Board Hot asphalt BP-AA, SBS- AA, SBS-TA, APP-TA (Optional) BP-AA, SBS- AA, SBS-TA, APP-TA SBS-AA, SBS-TA, APP-TA -82.5 NEMO|etc. NEMO ETC, LLC Evaluation Report P9290.02.08-R25 for FL1654-R27 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 25: 09/30/2020 ©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 8 of 94 TABLE 1B: WOOD DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF) SYSTEM TYPE A-2: MECHANICALLY ATTACHED ANCHOR SHEET, BONDED INSULATION, BONDED ROOF COVER System No. Deck (Note 1) Anchor Sheet Base Insulation Top Insulation Roof Cover (Note 15) MDP (psf) Type Fasten (Note 11) Attach Type Attach (Notes 6,7,8) Type Attach (Notes 6,7,8) Base Ply Ply Cap Ply W-14 Min. 15/32- inch plywood Polyglass G2 Base, Elastobase, Elastobase P (sanded-top) or Elastovent 32 ga., 1-5/8- inch diameter tin caps with 12 ga. annular ring shank nails 6-inch o.c. at min. 4-inch lap and 6- inch o.c. at five (5) equally spaced, staggered center rows (Optional) Min. 1.5- inch Polytherm, ACFoam II, ENRGY-3, Polytherm H, H-Shield, H-Shield CG, Multi- Max FA3 Hot asphalt Min. 0.25-inch DensDeck Prime, SECUROCK Gypsum- Fiber Roof Board Hot asphalt BP-AA, SBS- AA, SBS-TA, APP-TA (Optional) BP-AA, SBS- AA, SBS-TA, APP-TA SBS-AA, SBS-TA, APP-TA -90.0 W-15 Min. 15/32- inch plywood Elastobase, Elastobase P (sanded-top) Simplex MAXX Cap 6-inch o.c. at min. 2-inch lap and 6- inch o.c. at two (2), equally spaced, staggered center rows (Optional) Min. 1.5- inch Polytherm, ACFoam II, ENRGY-3, Polytherm H, H-Shield, H-Shield CG, Multi- Max FA3 Hot asphalt Min. 0.25-inch DensDeck Prime, SECUROCK Gypsum- Fiber Roof Board Hot asphalt BP-AA, SBS- AA, SBS-TA, APP-TA (Optional) BP-AA, SBS- AA, SBS-TA, APP-TA SBS-AA, SBS-TA, APP-TA -90.0 W-16 Min. 19/32- inch plywood Elastobase, Elastobase P (sanded-top) or Elastovent 32 ga., 1-5/8- inch diameter tin caps with 12 ga. annular ring shank nails 6-inch o.c. at min. 4-inch lap and 6- inch o.c. at four (4), equally spaced, staggered center rows Min. 2-inch Polytherm, ACFoam II, III, Polytherm H, H-Shield, H-Shield CG, Multi- Max FA3 or ENRGY-3 D-IS, OB500, CR-20 or M- OSFA, atop fastener rows, 7-inch o.c. Min. 0.25-inch DensDeck, DensDeck Prime or SECUROCK Gypsum-Fiber Roof Board D-IS, OB500, CR- 20 or M- OSFA BP-AA, SBS- AA, SBS-TA, APP-TA (Optional) BP-AA, SBS- AA, SBS-TA, APP-TA SBS-AA, SBS-TA, APP-TA -60.0* SELF-ADHERING BASE PLY: W-17 Min. 15/32- inch plywood Elastobase, Elastobase P (sanded-top) Simplex MAXX Cap 9-inch o.c. at min. 2-inch lap and 18- inch o.c. at two, equally spaced, staggered center rows (Optional) Min. 1.5- inch Polytherm, ACFoam II, ENRGY-3, Polytherm H, H-Shield, H-Shield CG, Multi- Max FA3 Hot asphalt Min. 0.25-inch DensDeck, DensDeck Prime, SECUROCK Gypsum-Fiber Roof Board Hot asphalt SBS-SA (Optional) SBS-SA, SBS-TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -45.0* W-18 Min. 15/32- inch plywood Elastobase, Elastobase P (sanded-top) Simplex MAXX Cap 9-inch o.c. at min. 2-inch lap and 12- inch o.c. at two, equally spaced, staggered center rows (Optional) Min. 1.5- inch Polytherm, ACFoam II, ENRGY-3, Polytherm H, H-Shield, H-Shield CG, Multi- Max FA3 Hot asphalt Min. 0.25-inch DensDeck, DensDeck Prime, SECUROCK Gypsum-Fiber Roof Board Hot asphalt SBS-SA (Optional) SBS-SA, SBS-TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -52.5 NEMO|etc. NEMO ETC, LLC Evaluation Report P9290.02.08-R25 for FL1654-R27 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 25: 09/30/2020 ©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 9 of 94 TABLE 1B: WOOD DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF) SYSTEM TYPE A-2: MECHANICALLY ATTACHED ANCHOR SHEET, BONDED INSULATION, BONDED ROOF COVER System No. Deck (Note 1) Anchor Sheet Base Insulation Top Insulation Roof Cover (Note 15) MDP (psf) Type Fasten (Note 11) Attach Type Attach (Notes 6,7,8) Type Attach (Notes 6,7,8) Base Ply Ply Cap Ply W-19 Min. 19/32- inch plywood Polyglass G2 Base, Elastobase, Elastobase P (sanded-top), Elastovent, CertainTeed Glasbase, Firestone MB Base, JM Perma- Ply 28 or GAFGLAS #75 32 ga., 1-5/8- inch diameter tin caps with 11 ga. annular ring shank nails 8-inch o.c. at min. 4-inch lap and 8- inch o.c. at three (3), equally spaced, staggered center rows (Optional) Min. 1.5- inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY- 3, Polytherm H, H- Shield, H-Shield CG, Multi-Max FA3 Hot asphalt Min. 0.25-inch DensDeck, DensDeck Prime, SECUROCK Gypsum-Fiber Roof Board Hot asphalt SBS-SA (Optional) SBS-SA, SBS-TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -60.0 W-20 Min. 19/32- inch plywood Elastobase, Elastobase P (sanded-top) Simplex MAXX Cap Fasteners 12-inch o.c. at min. 4-inch lap and 12- inch o.c. at two (2), equally spaced, staggered center rows (Optional) Min. 1.5- inch Polytherm, ACFoam II, ENRGY-3, Polytherm H, H-Shield, H-Shield CG, Multi- Max FA3 Hot asphalt Min. 0.25-inch DensDeck, DensDeck Prime, SECUROCK Gypsum-Fiber Roof Board Hot asphalt SBS-SA (Optional) SBS-SA, SBS-TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -60.0 W-21 Min. 19/32- inch plywood Elastobase, Elastobase P (sanded-top) 32 ga., 1-5/8- inch diameter tin caps with 12 ga. annular ring shank nails 6-inch o.c. at min. 4-inch lap and 6- inch o.c. at four (4), equally spaced, staggered center rows Min. 2-inch Polytherm, ACFoam II, III, Polytherm H, H-Shield, H-Shield CG, Multi- Max FA3 or ENRGY-3 D-IS, OB500, CR-20 or M- OSFA, atop fastener rows, 7-inch o.c. (Optional) Additional layers of base insulation D-IS, OB500, CR- 20 or M- OSFA SBS-SA (Optional) SBS-SA, SBS-TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -60.0* HYBRID SYSTEMS WITH SELF-ADHERING APP BASE PLY: W-22 Min. 15/32- inch plywood Elastobase, Elastobase P (sanded-top) Simplex MAXX Cap 9-inch o.c. at min. 2-inch lap and 18- inch o.c. at two, equally spaced, staggered center rows (Optional) Min. 1.5- inch Polytherm, ACFoam II, ENRGY-3, Polytherm H, H-Shield, H-Shield CG, Multi- Max FA3 Hot asphalt Min. 0.25-inch DensDeck, DensDeck Prime, SECUROCK Gypsum-Fiber Roof Board Hot asphalt APP- SA-H (Optional) APP-TA APP-TA -45.0* W-23 Min. 15/32- inch plywood Elastobase, Elastobase P (sanded-top) Simplex MAXX Cap 9-inch o.c. at min. 2-inch lap and 12- inch o.c. at two, equally spaced, staggered center rows (Optional) Min. 1.5- inch Polytherm, ACFoam II, ENRGY-3, Polytherm H, H-Shield, H-Shield CG, Multi- Max FA3 Hot asphalt Min. 0.25-inch DensDeck, DensDeck Prime, SECUROCK Gypsum-Fiber Roof Board Hot asphalt APP- SA-H (Optional) APP-TA APP-TA -52.5 NEMO|etc. NEMO ETC, LLC Evaluation Report P9290.02.08-R25 for FL1654-R27 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 25: 09/30/2020 ©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 10 of 94 TABLE 1B: WOOD DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF) SYSTEM TYPE A-2: MECHANICALLY ATTACHED ANCHOR SHEET, BONDED INSULATION, BONDED ROOF COVER System No. Deck (Note 1) Anchor Sheet Base Insulation Top Insulation Roof Cover (Note 15) MDP (psf) Type Fasten (Note 11) Attach Type Attach (Notes 6,7,8) Type Attach (Notes 6,7,8) Base Ply Ply Cap Ply W-24 Min. 19/32- inch plywood Polyglass G2 Base, Elastobase, Elastobase P (sanded-top), Elastovent, CertainTeed Glasbase, Firestone MB Base, JM Perma- Ply 28 or GAFGLAS #75 32 ga., 1-5/8- inch diameter tin caps with 11 ga. annular ring shank nails 8-inch o.c. at min. 4-inch lap and 8- inch o.c. at three (3), equally spaced, staggered center rows (Optional) Min. 1.5- inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY- 3, Polytherm H, H- Shield, H-Shield CG, Multi-Max FA3 Hot asphalt Min. 0.25-inch DensDeck, DensDeck Prime, SECUROCK Gypsum-Fiber Roof Board Hot asphalt APP- SA-H (Optional) APP-TA APP-TA -60.0 W-25 Min. 19/32- inch plywood Elastobase, Elastobase P (sanded-top) Simplex MAXX Cap Fasteners 12-inch o.c. at min. 4-inch lap and 12- inch o.c. at two (2), equally spaced, staggered center rows (Optional) Min. 1.5- inch Polytherm, ACFoam II, ENRGY-3, Polytherm H, H-Shield, H-Shield CG, Multi- Max FA3 Hot asphalt Min. 0.25-inch DensDeck, DensDeck Prime, SECUROCK Gypsum-Fiber Roof Board Hot asphalt APP- SA-H (Optional) APP-TA APP-TA -60.0 W-26 Min. 15/32- inch plywood Polyglass G2 Base, Elastobase, Elastobase P (sanded-top) or Elastovent 32 ga., 1-5/8- inch diameter tin caps with 12 ga. annular ring shank nails 8-inch o.c. at min. 4-inch lap and 8- inch o.c. at four (4), equally spaced, staggered center rows (Optional) Min. 1.5- inch Polytherm, ACFoam II, ENRGY-3, Polytherm H, H-Shield, H-Shield CG, Multi- Max FA3 Hot asphalt Min. 0.25-inch DensDeck Prime, SECUROCK Gypsum- Fiber Roof Board Hot asphalt APP- SA-H (Optional) APP-TA APP-TA -67.5 W-27 Min. 15/32- inch plywood Polyglass G2 Base Simplex MAXX Cap 9-inch o.c. at min. 4-inch lap and 9- inch o.c. at four (4), equally spaced, staggered center rows (Optional) Min. 1.5- inch Polytherm, ACFoam II, ENRGY-3, Polytherm H, H-Shield, H-Shield CG, Multi- Max FA3 Hot asphalt Min. 0.25-inch DensDeck Prime, SECUROCK Gypsum- Fiber Roof Board Hot asphalt APP- SA-H (Optional) APP-TA APP-TA -82.5 W-28 Min. 15/32- inch plywood Polyglass G2 Base, Elastobase, Elastobase P (sanded-top) or Elastovent 32 ga., 1-5/8- inch diameter tin caps with 12 ga. annular ring shank nails 6-inch o.c. at min. 4-inch lap and 6- inch o.c. at five (5) equally spaced, staggered center rows (Optional) Min. 1.5- inch Polytherm, ACFoam II, ENRGY-3, Polytherm H, H-Shield, H-Shield CG, Multi- Max FA3 Hot asphalt Min. 0.25-inch DensDeck Prime, SECUROCK Gypsum- Fiber Roof Board Hot asphalt APP- SA-H (Optional) APP-TA APP-TA -90.0 NEMO|etc. NEMO ETC, LLC Evaluation Report P9290.02.08-R25 for FL1654-R27 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 25: 09/30/2020 ©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 11 of 94 TABLE 1B: WOOD DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF) SYSTEM TYPE A-2: MECHANICALLY ATTACHED ANCHOR SHEET, BONDED INSULATION, BONDED ROOF COVER System No. Deck (Note 1) Anchor Sheet Base Insulation Top Insulation Roof Cover (Note 15) MDP (psf) Type Fasten (Note 11) Attach Type Attach (Notes 6,7,8) Type Attach (Notes 6,7,8) Base Ply Ply Cap Ply W-29 Min. 15/32- inch plywood Elastobase, Elastobase P (sanded-top) Simplex MAXX Cap 6-inch o.c. at min. 2-inch lap and 6- inch o.c. at two (2), equally spaced, staggered center rows (Optional) Min. 1.5- inch Polytherm, ACFoam II, ENRGY-3, Polytherm H, H-Shield, H-Shield CG, Multi- Max FA3 Hot asphalt Min. 0.25-inch DensDeck Prime, SECUROCK Gypsum- Fiber Roof Board Hot asphalt APP- SA-H (Optional) APP-TA APP-TA -90.0 W-30 Min. 19/32- inch plywood Elastobase, Elastobase P (sanded-top) 32 ga., 1-5/8- inch diameter tin caps with 12 ga. annular ring shank nails 6-inch o.c. at min. 4-inch lap and 6- inch o.c. at four (4), equally spaced, staggered center rows Min. 2-inch Polytherm, ACFoam II, III, Polytherm H, H-Shield, H-Shield CG, Multi- Max FA3 or ENRGY-3 D-IS, OB500, CR-20 or M- OSFA, atop fastener rows, 7-inch o.c. (Optional) Additional layers of base insulation D-IS, OB500, CR- 20 or M- OSFA APP- SA-H (Optional) APP-TA APP-TA -60.0* HYBRID SYSTEMS WITH SELF-ADHERING SBS BASE PLY: W-31 Min. 15/32- inch plywood Elastobase, Elastobase P (sanded-top) Simplex MAXX Cap 9-inch o.c. at min. 2-inch lap and 18- inch o.c. at two, equally spaced, staggered center rows (Optional) Min. 1.5- inch Polytherm, ACFoam II, ENRGY-3, Polytherm H, H-Shield, H-Shield CG, Multi- Max FA3 Hot asphalt Min. 0.25-inch DensDeck, DensDeck Prime, SECUROCK Gypsum-Fiber Roof Board Hot asphalt SBS-SA- H (Optional) SBS-TA SBS-TA -45.0* W-32 Min. 15/32- inch plywood Elastobase, Elastobase P (sanded-top) Simplex MAXX Cap 9-inch o.c. at min. 2-inch lap and 12- inch o.c. at two, equally spaced, staggered center rows (Optional) Min. 1.5- inch Polytherm, ACFoam II, ENRGY-3, Polytherm H, H-Shield, H-Shield CG, Multi- Max FA3 Hot asphalt Min. 0.25-inch DensDeck, DensDeck Prime, SECUROCK Gypsum-Fiber Roof Board Hot asphalt SBS-SA- H (Optional) SBS-TA SBS-TA -52.5 W-33 Min. 19/32- inch plywood Polyglass G2 Base, Elastobase, Elastobase P (sanded-top), Elastovent, CertainTeed Glasbase, Firestone MB Base, JM Perma- Ply 28 or GAFGLAS #75 32 ga., 1-5/8- inch diameter tin caps with 11 ga. annular ring shank nails 8-inch o.c. at min. 4-inch lap and 8- inch o.c. at three (3), equally spaced, staggered center rows (Optional) Min. 1.5- inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY- 3, Polytherm H, H- Shield, H-Shield CG, Multi-Max FA3 Hot asphalt Min. 0.25-inch DensDeck, DensDeck Prime, SECUROCK Gypsum-Fiber Roof Board Hot asphalt SBS-SA- H (Optional) SBS-TA SBS-TA -60.0 NEMO|etc. NEMO ETC, LLC Evaluation Report P9290.02.08-R25 for FL1654-R27 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 25: 09/30/2020 ©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 12 of 94 TABLE 1B: WOOD DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF) SYSTEM TYPE A-2: MECHANICALLY ATTACHED ANCHOR SHEET, BONDED INSULATION, BONDED ROOF COVER System No. Deck (Note 1) Anchor Sheet Base Insulation Top Insulation Roof Cover (Note 15) MDP (psf) Type Fasten (Note 11) Attach Type Attach (Notes 6,7,8) Type Attach (Notes 6,7,8) Base Ply Ply Cap Ply W-34 Min. 19/32- inch plywood Elastobase, Elastobase P (sanded-top) Simplex MAXX Cap Fasteners 12-inch o.c. at min. 4-inch lap and 12- inch o.c. at two (2), equally spaced, staggered center rows (Optional) Min. 1.5- inch Polytherm, ACFoam II, ENRGY-3, Polytherm H, H-Shield, H-Shield CG, Multi- Max FA3 Hot asphalt Min. 0.25-inch DensDeck, DensDeck Prime, SECUROCK Gypsum-Fiber Roof Board Hot asphalt SBS-SA- H (Optional) SBS-TA SBS-TA -60.0 W-35 Min. 19/32- inch plywood Elastobase, Elastobase P (sanded-top) 32 ga., 1-5/8- inch diameter tin caps with 12 ga. annular ring shank nails 6-inch o.c. at min. 4-inch lap and 6- inch o.c. at four (4), equally spaced, staggered center rows Min. 2-inch Polytherm, ACFoam II, III, Polytherm H, H-Shield, H-Shield CG, Multi- Max FA3 or ENRGY-3 D-IS, OB500, CR-20 or M- OSFA, atop fastener rows, 7-inch o.c. (Optional) Additional layers of base insulation D-IS, OB500, CR- 20 or M- OSFA SBS-SA- H (Optional) SBS-TA SBS-TA -60.0* TABLE 1C: WOOD DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER SYSTEM TYPE A-2: MECHANICALLY ATTACHED ANCHOR SHEET, BONDED INSULATION, BONDED ROOF COVER System No. Deck (Note 1) Anchor Sheet Base Insulation Top Insulation Roof Cover (Note 15) MDP (psf) Type Fasten (Note 11) Attach Type Attach (Notes 6,7,8) Type Attach (Notes 6,7,8) Base Ply Ply Cap Ply ASPHALT-APPLIED OR TORCH-APPLIED BASE PLY: W-36 Min. 15/32- inch plywood Polyglass G2 Base, Elastobase, Elastobase P (sanded-top) or Elastovent Dekfast Hex (aka, Dekfast PLT-H-2- 7/8) with Dekfast #14, OMG 3” Round Metal Plate with OMG HD, OMG Flat Bottom Plate (Accutrac) with Roofgrip #14 or Trufast 3” Metal Insulation Plate with Trufast #14 HD. 10-inch o.c. at min. 4-inch lap and 10-inch o.c. at three (3), equally spaced, staggered center rows (Optional) Min. 1.5- inch Polytherm, ACFoam II, ENRGY- 3, Polytherm H, H- Shield, H-Shield CG, Multi-Max FA3 Hot asphalt Min. 0.25-inch DensDeck, DensDeck Prime, SECUROCK Gypsum-Fiber Roof Board Hot asphalt BP-AA, SBS-AA, SBS-TA, APP-TA (Optional) BP-AA, SBS- AA, SBS-TA, APP-TA SBS-AA, SBS-TA, APP-TA -52.5 W-37 Min. 19/32- inch plywood Elastobase, Elastobase P (sanded-top) or Elastovent OMG Flat Bottom Plates (square) with Roofgrip #12 12-inch o.c. at min. 4-inch lap and 12-inch o.c. at two (2), equally spaced, staggered center rows (Optional) Min. 1.5- inch Polytherm, ACFoam II, ENRGY- 3, Polytherm H, H- Shield, H-Shield CG, Multi-Max FA3 Hot asphalt Min. 0.75-inch Fesco Board (homogeneous) or min. 0.5-inch Structodek High Density Fiberboard Roof Insulation Hot asphalt BP-AA or SBS-AA (Optional) BP-AA or SBS-AA SBS-AA, SBS-TA, APP-TA -60.0 NEMO|etc. NEMO ETC, LLC Evaluation Report P9290.02.08-R25 for FL1654-R27 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 25: 09/30/2020 ©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 13 of 94 TABLE 1C: WOOD DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER SYSTEM TYPE A-2: MECHANICALLY ATTACHED ANCHOR SHEET, BONDED INSULATION, BONDED ROOF COVER System No. Deck (Note 1) Anchor Sheet Base Insulation Top Insulation Roof Cover (Note 15) MDP (psf) Type Fasten (Note 11) Attach Type Attach (Notes 6,7,8) Type Attach (Notes 6,7,8) Base Ply Ply Cap Ply W-38 Min. 19/32- inch plywood Elastobase, Elastobase P (sanded-top) or Elastovent OMG Flat Bottom Plates (square) with Roofgrip #12 12-inch o.c. at min. 4-inch lap and 12-inch o.c. at two (2), equally spaced, staggered center rows (Optional) Min. 1.5- inch Polytherm, ACFoam II, ENRGY- 3, Polytherm H, H- Shield, H-Shield CG, Multi-Max FA3 Hot asphalt Min. 0.25-inch DensDeck, DensDeck Prime, SECUROCK Gypsum-Fiber Roof Board Hot asphalt BP-AA, SBS-AA, SBS-TA, APP-TA (Optional) BP-AA, SBS- AA, SBS-TA, APP-TA SBS-AA, SBS-TA, APP-TA -60.0 W-39 Min. 15/32- inch plywood Polyglass G2 Base, Elastobase, Elastobase P (sanded-top) or Elastovent Dekfast Hex (aka, Dekfast PLT-H-2- 7/8) with Dekfast #14, OMG 3” Round Metal Plate with OMG HD, OMG Flat Bottom Plate (Accutrac) with Roofgrip #14 or Trufast 3” Metal Insulation Plate with Trufast #14 HD. 9-inch o.c. at min. 4-inch lap and 9-inch o.c. at four (4), equally spaced, staggered center rows (Optional) Min. 1.5- inch Polytherm, ACFoam II, ENRGY- 3, Polytherm H, H- Shield, H-Shield CG, Multi-Max FA3 Hot asphalt Min. 0.25-inch DensDeck, DensDeck Prime, SECUROCK Gypsum-Fiber Roof Board Hot asphalt BP-AA, SBS-AA, SBS-TA, APP-TA (Optional) BP-AA, SBS- AA, SBS-TA, APP-TA SBS-AA, SBS-TA, APP-TA -82.5 SELF-ADHERING BASE PLY: W-40 Min. 19/32- inch plywood Elastobase, Elastobase P (sanded-top) or Elastovent OMG Flat Bottom Plates (square) with Roofgrip #12 12-inch o.c. at min. 4-inch lap and 12-inch o.c. at two (2), equally spaced, staggered center rows (Optional) Min. 1.5- inch Polytherm, ACFoam II, ENRGY- 3, Polytherm H, H- Shield, H-Shield CG, Multi-Max FA3 Hot asphalt Min. 0.25-inch DensDeck, DensDeck Prime, SECUROCK Gypsum-Fiber Roof Board Hot asphalt SBS-SA (Optional) SBS-SA, SBS-TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -60.0 HYBRID SYSTEMS WITH SELF-ADHERING APP BASE PLY: W-41 Min. 15/32- inch plywood Polyglass G2 Base, Elastobase, Elastobase P (sanded-top) or Elastovent Dekfast Hex (aka, Dekfast PLT-H-2- 7/8) with Dekfast #14, OMG 3” Round Metal Plate with OMG HD, OMG Flat Bottom Plate (Accutrac) with Roofgrip #14 or Trufast 3” Metal Insulation Plate with Trufast #14 HD. 10-inch o.c. at min. 4-inch lap and 10-inch o.c. at three (3), equally spaced, staggered center rows (Optional) Min. 1.5- inch Polytherm, ACFoam II, ENRGY- 3, Polytherm H, H- Shield, H-Shield CG, Multi-Max FA3 Hot asphalt Min. 0.25-inch DensDeck, DensDeck Prime, SECUROCK Gypsum-Fiber Roof Board Hot asphalt APP-SA-H (Optional) APP-TA APP-TA -52.5 W-42 Min. 19/32- inch plywood Elastobase, Elastobase P (sanded-top) or Elastovent OMG Flat Bottom Plates (square) with Roofgrip #12 12-inch o.c. at min. 4-inch lap and 12-inch o.c. at two (2), equally spaced, staggered center rows (Optional) Min. 1.5- inch Polytherm, ACFoam II, ENRGY- 3, Polytherm H, H- Shield, H-Shield CG, Multi-Max FA3 Hot asphalt Min. 0.25-inch DensDeck, DensDeck Prime, SECUROCK Gypsum-Fiber Roof Board Hot asphalt APP-SA-H (Optional) APP-TA APP-TA -60.0 NEMO|etc. NEMO ETC, LLC Evaluation Report P9290.02.08-R25 for FL1654-R27 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 25: 09/30/2020 ©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 14 of 94 TABLE 1C: WOOD DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER SYSTEM TYPE A-2: MECHANICALLY ATTACHED ANCHOR SHEET, BONDED INSULATION, BONDED ROOF COVER System No. Deck (Note 1) Anchor Sheet Base Insulation Top Insulation Roof Cover (Note 15) MDP (psf) Type Fasten (Note 11) Attach Type Attach (Notes 6,7,8) Type Attach (Notes 6,7,8) Base Ply Ply Cap Ply W-43 Min. 15/32- inch plywood Polyglass G2 Base, Elastobase, Elastobase P (sanded-top) or Elastovent Dekfast Hex (aka, Dekfast PLT-H-2- 7/8) with Dekfast #14, OMG 3” Round Metal Plate with OMG HD, OMG Flat Bottom Plate (Accutrac) with Roofgrip #14 or Trufast 3” Metal Insulation Plate with Trufast #14 HD. 9-inch o.c. at min. 4-inch lap and 9-inch o.c. at four (4), equally spaced, staggered center rows (Optional) Min. 1.5- inch Polytherm, ACFoam II, ENRGY- 3, Polytherm H, H- Shield, H-Shield CG, Multi-Max FA3 Hot asphalt Min. 0.25-inch DensDeck, DensDeck Prime, SECUROCK Gypsum-Fiber Roof Board Hot asphalt APP-SA-H (Optional) APP-TA APP-TA -82.5 HYBRID SYSTEMS WITH SELF-ADHERING SBS BASE PLY: W-44 Min. 19/32- inch plywood Elastobase, Elastobase P (sanded-top) or Elastovent OMG Flat Bottom Plates (square) with Roofgrip #12 12-inch o.c. at min. 4-inch lap and 12-inch o.c. at two (2), equally spaced, staggered center rows (Optional) Min. 1.5- inch Polytherm, ACFoam II, ENRGY- 3, Polytherm H, H- Shield, H-Shield CG, Multi-Max FA3 Hot asphalt Min. 0.25-inch DensDeck, DensDeck Prime, SECUROCK Gypsum-Fiber Roof Board Hot asphalt SBS-SA-H (Optional) SBS-TA SBS-TA -60.0 TABLE 1D: WOOD DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER SYSTEM TYPE B-1: MECHANICALLY ATTACHED BASE INSULATION, BONDED TOP INSULATION, BONDED ROOF COVER System No. Deck (Note 1) Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP (psf) Type Fasten (Note 11) Attach Type Attach (Notes 6,7,8) Base Ply Ply Cap Ply ASPHALT-APPLIED OR TORCH-APPLIED BASE PLY: W-45 Min. 19/32- inch plywood Min. 1.5-inch ENRGY 3, H-Shield or Polytherm Dekfast Hex (aka, Dekfast PLT-H- 2-7/8) with Dekfast #12 or Trufast 3” Metal Insulation Plate with Trufast DP 1 per 1.3 ft2 Min. 0.75-inch Fesco Board (homogeneous) or min. 0.5-inch Structodek High Density Fiberboard Roof Insulation Hot asphalt (Optional if using AA Ply) BP-AA, SBS-AA (Optional if using AA Base) BP-AA, SBS-AA, SBS-TA or APP-TA SBS-AA, SBS-TA, APP-TA -60.0 W-46 Min. 15/32- inch plywood Min. 2-inch Polytherm, ACFoam II, ENRGY-3, EnergyGuard Polyiso Insulation, H-Shield or Multi-Max FA3 Dekfast #14 with Dekfast Hex (aka, Dekfast PLT-H-2-7/8), OMG #14 HD with OMG 3” Galvalume Steel Plates or Trufast #14 HD with Trufast 3-inch Insulation Plates 1 per 1.0 ft2 Min. 0.25-inch DensDeck Prime or SECUROCK Gypsum Fiber Roof Board Hot asphalt SBS-AA, SBS- TA, APP-TA (Optional) SBS-AA, SBS-TA, APP-TA SBS-AA, SBS-TA, APP-TA -75.0 HYBRID SYSTEMS WITH SELF-ADHERING APP BASE PLY: NEMO|etc. NEMO ETC, LLC Evaluation Report P9290.02.08-R25 for FL1654-R27 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 25: 09/30/2020 ©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 15 of 94 TABLE 1D: WOOD DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER SYSTEM TYPE B-1: MECHANICALLY ATTACHED BASE INSULATION, BONDED TOP INSULATION, BONDED ROOF COVER System No. Deck (Note 1) Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP (psf) Type Fasten (Note 11) Attach Type Attach (Notes 6,7,8) Base Ply Ply Cap Ply W-47 Min. 15/32- inch plywood Min. 2-inch Polytherm, ACFoam II, ENRGY-3, EnergyGuard Polyiso Insulation, H-Shield or Multi-Max FA3 Dekfast #14 with Dekfast Hex (aka, Dekfast PLT-H-2-7/8), OMG #14 HD with OMG 3” Galvalume Steel Plates or Trufast #14 HD with Trufast 3-inch Insulation Plates 1 per 1.0 ft2 Min. 0.25-inch DensDeck Prime or SECUROCK Gypsum Fiber Roof Board Hot asphalt APP-SA-H (Optional) APP-TA APP-TA -75.0 TABLE 1E: WOOD DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER SYSTEM TYPE C-1: MECHANICALLY ATTACHED INSULATION, BONDED ROOF COVER System No. Deck (Note 1) Base Insulation Layer (Note 13) Top Insulation Layer Roof Cover (Note 15) MDP (psf) Type Fasten (Note 11) Attach Base Ply Ply Cap Ply ASPHALT-APPLIED OR TORCH-APPLIED BASE PLY: W-48 Min. 15/32- inch plywood (Optional) One or more layers, any combination, loose laid Min. 0.25-inch DensDeck Prime or SECUROCK Gypsum-Fiber Roof Board Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with Dekfast #14, OMG 3” Round Metal Plate with OMG HD, OMG Flat Bottom Plate (Accutrac) with Roofgrip #14 or Trufast 3” Metal Insulation Plate with Trufast #14 HD. 1 per 2.0 ft2 BP-AA, SBS- AA, SBS-TA, APP-TA (Optional) BP- AA, SBS-AA, SBS-TA, APP-TA SBS-AA, SBS- TA, APP-TA -30.0 W-49 Min. 15/32- inch plywood (Optional) One or more layers, any combination, loose laid Min. 0.25-inch DensDeck Prime or SECUROCK Gypsum-Fiber Roof Board Dekfast #14 with Dekfast Hex (aka, Dekfast PLT-H- 2-7/8), OMG #14 HD with OMG 3” Galvalume Steel Plates or Trufast #14 HD with Trufast 3-inch Insulation Plates 1 per 1.8 ft2 SBS-AA, SBS- TA, APP-TA (Optional) SBS- AA, SBS-TA, APP-TA SBS-AA, SBS- TA, APP-TA -45.0 W-50 Min. 15/32- inch plywood (Optional) One or more layers, any combination, loose laid Min. 0.25-inch DensDeck Prime or SECUROCK Gypsum-Fiber Roof Board Dekfast #14 with Dekfast Hex (aka, Dekfast PLT-H- 2-7/8), OMG #14 HD with OMG 3” Galvalume Steel Plates or Trufast #14 HD with Trufast 3-inch Insulation Plates 1 per 1.0 ft2 SBS-AA, SBS- TA, APP-TA (Optional) SBS- AA, SBS-TA, APP-TA SBS-AA, SBS- TA, APP-TA -75.0 W-51 Min. 19/32- inch plywood (Optional) One or more layers, any combination, loose laid Min. 0.5-inch Structodek High Density Fiberboard Roof Insulation or min. 0.25-inch DensDeck, DensDeck Prime or SECUROCK Gypsum-Fiber Roof Board Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with Dekfast #12 DP 1 per 1.3 ft2 (Optional if using AA Ply) BP-AA, SBS- AA (Optional if using AA Base) BP-AA, SBS-AA, SBS-TA or APP- TA SBS-AA, SBS- TA, APP-TA -82.5 SELF-ADHERING BASE PLY: W-52 Min. 15/32- inch plywood (Optional) One or more layers, any combination, loose laid Min. 1.5-inch Polytherm, ACFoam II, H-Shield or Polytherm Dekfast #14 with Dekfast Hex (aka, Dekfast PLT-H- 2-7/8), OMG #14 HD with OMG 3” Galvalume Steel Plates or Trufast #14 HD with Trufast 3-inch Insulation Plates 1 per 2.7 ft2 SBS-SA (Optional) SBS- SA, SBS-TA, APP-TA SBS-SA, APP- SA, SBS-TA, APP-TA -30.0 NEMO|etc. NEMO ETC, LLC Evaluation Report P9290.02.08-R25 for FL1654-R27 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 25: 09/30/2020 ©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 16 of 94 TABLE 1E: WOOD DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER SYSTEM TYPE C-1: MECHANICALLY ATTACHED INSULATION, BONDED ROOF COVER System No. Deck (Note 1) Base Insulation Layer (Note 13) Top Insulation Layer Roof Cover (Note 15) MDP (psf) Type Fasten (Note 11) Attach Base Ply Ply Cap Ply W-53 Min. 15/32- inch plywood (Optional) One or more layers, any combination, loose laid Min. 0.25-inch DensDeck Prime or SECUROCK Gypsum-Fiber Roof Board Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with Dekfast #14, OMG 3” Round Metal Plate with OMG HD, OMG Flat Bottom Plate (Accutrac) with Roofgrip #14 or Trufast 3” Metal Insulation Plate with Trufast #14 HD. 1 per 2.0 ft2 SBS-SA (Optional) SBS- SA, SBS-TA, APP-TA SBS-SA, APP- SA, SBS-TA, APP-TA -30.0 W-54 Min. 15/32- inch plywood One or more layers, any combination, min. 1-inch, loose laid Min. 0.25-inch SECUROCK Gypsum- Fiber Roof Board optionally primed with POLYBRITE 745 or WB3000 Polygrip #14 with Polygrip Hex Plate or Dekfast #14 with Dekfast Hex (aka, Dekfast PLT-H-2-7/8) or Dekfast Galvalume Steel 3” Round (aka, Dekfast PLT-R-3) or OMG #14 Roofgrip with OMG 3 in. Round Metal Plate, OMG 3 in. Ribbed Galvalume Plate (Flat) or Accutrac Flat Bottom Plate or Trufast #14 HD Fasteners with Trufast 3” Metal Insulation Plate 1 per 2.0 ft2 SBS-SA None SBS-SA -45.0 W-55 Min. 15/32- inch plywood One or more layers, any combination, min. 1-inch, loose laid Min. 0.25-inch DensDeck Prime optionally primed with POLYBRITE 745 or WB3000 Polygrip #14 with Polygrip Hex Plate or Dekfast #14 with Dekfast Hex (aka, Dekfast PLT-H-2-7/8) or OMG #14 Roofgrip with OMG 3 in. Round Metal Plate or Accutrac Flat Bottom Plate or Trufast #14 HD Fasteners with Trufast 3” Metal Insulation Plate 1 per 2.0 ft2 SBS-SA None SBS-SA -45.0 W-56 Min. 15/32- inch plywood One or more layers, any combination, min. 1-inch, loose laid Min. 0.25-inch SECUROCK Gypsum- Fiber Roof Board optionally primed with POLYBRITE 745 or WB3000 Polygrip #14 with Polygrip Hex Plate or Dekfast DF-#14 with Dekfast Hex (aka, Dekfast PLT-H-2- 7/8) or OMG #14 Roofgrip with OMG 3 in. Round Metal Plate or Accutrac Flat Bottom Plate or Trufast #14 HD Fasteners with Trufast 3” Metal Insulation Plate 1 per 1.8 ft2 SBS-SA (Optional when using torch- applied Cap Ply) SBS-TA, APP-TA SBS-SA, APP- SA, SBS-TA or APP-TA -45.0 W-57 Min. 15/32- inch plywood One or more layers, any combination, min. 1-inch, loose laid Min. 0.25-inch DensDeck Prime optionally primed with POLYBRITE 745 or WB3000 OMG #14 Roofgrip with OMG 3 in. Round Metal Plate or Trufast #14 HD Fasteners with Trufast 3” Metal Insulation Plate 1 per 1.8 ft2 SBS-SA (Optional when using torch- applied Cap Ply) SBS-TA, APP-TA SBS-SA, APP- SA, SBS-TA or APP-TA -45.0 W-58 Min. 15/32- inch plywood (Optional) One or more layers, any combination, loose laid Min. 0.25-inch DensDeck Prime, DEXcell FA Glass Mat Roof Board or SECUROCK Gypsum-Fiber Roof Board Dekfast #14 with Dekfast Hex (aka, Dekfast PLT-H- 2-7/8), OMG #14 HD with OMG 3” Galvalume Steel Plates or Trufast #14 HD with Trufast 3-inch Insulation Plates 1 per 1.0 ft2 SBS-SA (Optional) SBS- TA, APP-TA SBS-TA, APP- TA -60.0 NEMO|etc. NEMO ETC, LLC Evaluation Report P9290.02.08-R25 for FL1654-R27 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 25: 09/30/2020 ©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 17 of 94 TABLE 1E: WOOD DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER SYSTEM TYPE C-1: MECHANICALLY ATTACHED INSULATION, BONDED ROOF COVER System No. Deck (Note 1) Base Insulation Layer (Note 13) Top Insulation Layer Roof Cover (Note 15) MDP (psf) Type Fasten (Note 11) Attach Base Ply Ply Cap Ply W-59 APA rated, 19/32 CAT, 0.578 in., Exposure 1 OSB or min. 19/32” APA rated plywood (Optional) One or more layers, any combination, loose laid Min. 1.5-inch ACFoam II, ACFoam III, EnergyGuard Polyiso Insulation, ENRGY 3, ENRGY 3 CGF, H-Shield, H- Shield CG, ISO 95+ GL, Multi-Max FA3, Polytherm or Ultra-Max optionally primed with POLYBRITE 745 or WB3000 Trufast Versa Fasteners (min. ¾” penetration) & Plates; 2 screws per plate installed 180° into the holes of the plate* 1 per 1.3 ft2 SBS-SA (Optional) SBS- SA, SBS-TA, APP-TA SBS-SA, APP- SA, SBS-TA, APP-TA -67.5* Note: *For re-roof or recover construction, field withdrawal resistance testing (Note 11) shall yield minimum 180 lbf. Additional Versa-Fast Fasteners within each Versa-Fast Plate may be utilized to produce minimum withdrawal resistance W-60 Min. 19/32- inch plywood (Optional) One or more layers, any combination, loose laid Min. 1.5-inch ACFoam II, ACFoam III, EnergyGuard Polyiso Insulation, ENRGY 3, ENRGY 3 CGF, H-Shield, H- Shield CG, ISO 95+ GL, Multi-Max FA3, Polytherm or Ultra-Max optionally primed with POLYBRITE 745 or WB3000 Dekfast Hex (aka, Dekfast PLT-H-2-7/8) or Dekfast Galvalume Steel 3” Round Insulation Plate (aka, Dekfast PLT-R-3) with Dekfast #12, OMG 3 in. Galvalume Plate (non-ribbed) or OMG AccuTrac Plate with #12 Roofgrip or Trufast 3” Metal Insulation Plate with Trufast DP 1 per 1.3 ft2 SBS-SA (Optional) SBS- SA, SBS-TA, APP-TA SBS-SA, APP- SA, SBS-TA, APP-TA -67.5* HYBRID SYSTEMS WITH SELF-ADHERING APP BASE PLY: W-61 Min. 15/32- inch plywood (Optional) One or more layers, any combination, loose laid Min. 1.5-inch Polytherm, ACFoam II, H-Shield or Polytherm Dekfast #14 with Dekfast Hex (aka, Dekfast PLT-H- 2-7/8), OMG #14 HD with OMG 3” Galvalume Steel Plates or Trufast #14 HD with Trufast 3-inch Insulation Plates 1 per 2.7 ft2 APP-SA-H (Optional) APP- TA APP-TA -30.0 W-62 Min. 15/32- inch plywood (Optional) One or more layers, any combination, loose laid Min. 0.25-inch DensDeck Prime or SECUROCK Gypsum-Fiber Roof Board Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with Dekfast #14, OMG 3” Round Metal Plate with OMG HD, OMG Flat Bottom Plate (Accutrac) with Roofgrip #14 or Trufast 3” Metal Insulation Plate with Trufast #14 HD. 1 per 2.0 ft2 APP-SA-H (Optional) APP- TA APP-TA -30.0 W-63 Min. 15/32- inch plywood (Optional) One or more layers, any combination, loose laid Min. 0.25-inch DensDeck Prime or SECUROCK Gypsum-Fiber Roof Board Dekfast #14 with Dekfast Hex (aka, Dekfast PLT-H- 2-7/8), OMG #14 HD with OMG 3” Galvalume Steel Plates or Trufast #14 HD with Trufast 3-inch Insulation Plates 1 per 1.8 ft2 APP-SA-H (Optional) APP- TA APP-TA -45.0 HYBRID SYSTEMS WITH SELF-ADHERING SBS BASE PLY: W-64 Min. 15/32- inch plywood (Optional) One or more layers, any combination, loose laid Min. 1.5-inch Polytherm, ACFoam II, H-Shield or Polytherm H Dekfast #14 with Dekfast Hex (aka, Dekfast PLT-H- 2-7/8), OMG #14 HD with OMG 3” Galvalume Steel Plates or Trufast #14 HD with Trufast 3-inch Insulation Plates 1 per 2.7 ft2 SBS-SA-H (Optional) SBS- TA SBS-TA -30.0 NEMO|etc. NEMO ETC, LLC Evaluation Report P9290.02.08-R25 for FL1654-R27 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 25: 09/30/2020 ©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 18 of 94 TABLE 1E: WOOD DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER SYSTEM TYPE C-1: MECHANICALLY ATTACHED INSULATION, BONDED ROOF COVER System No. Deck (Note 1) Base Insulation Layer (Note 13) Top Insulation Layer Roof Cover (Note 15) MDP (psf) Type Fasten (Note 11) Attach Base Ply Ply Cap Ply W-65 Min. 15/32- inch plywood (Optional) One or more layers, any combination, loose laid Min. 0.25-inch DensDeck Prime or SECUROCK Gypsum-Fiber Roof Board Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with Dekfast #14, OMG 3” Round Metal Plate with OMG HD, OMG Flat Bottom Plate (Accutrac) with Roofgrip #14 or Trufast 3” Metal Insulation Plate with Trufast #14 HD. 1 per 2.0 ft2 SBS-SA-H (Optional) SBS- TA SBS-TA -30.0 W-66 Min. 15/32- inch plywood One or more layers, any combination, min. 1-inch, loose laid Min. 0.25-inch SECUROCK Gypsum- Fiber Roof Board optionally primed with POLYBRITE 745 or WB3000 Polygrip #14 with Polygrip Hex Plate or Dekfast #14 with Dekfast Hex (aka, Dekfast PLT-H-2-7/8) or Dekfast Galvalume Steel 3” Round (aka, Dekfast PLT-R-3) or OMG #14 Roofgrip with OMG 3 in. Round Metal Plate, OMG 3 in. Ribbed Galvalume Plate (Flat) or Accutrac Flat Bottom Plate or Trufast #14 HD Fasteners with Trufast 3” Metal Insulation Plate 1 per 2.0 ft2 SBS-SA-H (Optional) SBS- TA SBS-TA -45.0 W-67 Min. 15/32- inch plywood One or more layers, any combination, min. 1-inch, loose laid Min. 0.25-inch DensDeck Prime optionally primed with POLYBRITE 745 or WB3000 Polygrip #14 with Polygrip Hex Plate or Dekfast #14 with Dekfast Hex (aka, Dekfast PLT-H-2-7/8) or OMG #14 Roofgrip with OMG 3 in. Round Metal Plate or Accutrac Flat Bottom Plate or Trufast #14 HD Fasteners with Trufast 3” Metal Insulation Plate 1 per 2.0 ft2 SBS-SA-H (Optional) SBS- TA SBS-TA -45.0 W-68 Min. 15/32- inch plywood (Optional) One or more layers, any combination, loose laid Min. 0.25-inch DensDeck Prime, DEXcell FA Glass Mat Roof Board or SECUROCK Gypsum-Fiber Roof Board Dekfast #14 with Dekfast Hex (aka, Dekfast PLT-H- 2-7/8), OMG #14 HD with OMG 3” Galvalume Steel Plates or Trufast #14 HD with Trufast 3-inch Insulation Plates 1 per 1.0 ft2 SBS-SA-H (Optional) SBS- TA SBS-TA -60.0 W-69 APA rated, 19/32 CAT, 0.578 in., Exposure 1 OSB or min. 19/32” APA rated plywood (Optional) One or more layers, any combination, loose laid Min. 1.5-inch ACFoam II, ACFoam III, EnergyGuard Polyiso Insulation, ENRGY 3, ENRGY 3 CGF, H-Shield, H- Shield CG, ISO 95+ GL, Multi-Max FA3, Polytherm or Ultra-Max optionally primed with POLYBRITE 745 or WB3000 Trufast Versa Fasteners (min. ¾” penetration) & Plates; 2 screws per plate installed 180° into the holes of the plate* 1 per 1.3 ft2 SBS-SA-H (Optional) SBS- TA SBS-TA -67.5* Note: *For re-roof or recover construction, field withdrawal resistance testing (Note 11) shall yield minimum 180 lbf. Additional Versa-Fast Fasteners within each Versa-Fast Plate may be utilized to produce minimum withdrawal resistance NEMO|etc. NEMO ETC, LLC Evaluation Report P9290.02.08-R25 for FL1654-R27 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 25: 09/30/2020 ©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 19 of 94 TABLE 1E: WOOD DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER SYSTEM TYPE C-1: MECHANICALLY ATTACHED INSULATION, BONDED ROOF COVER System No. Deck (Note 1) Base Insulation Layer (Note 13) Top Insulation Layer Roof Cover (Note 15) MDP (psf) Type Fasten (Note 11) Attach Base Ply Ply Cap Ply W-70 Min. 19/32- inch plywood (Optional) One or more layers, any combination, loose laid Min. 1.5-inch ACFoam II, ACFoam III, EnergyGuard Polyiso Insulation, ENRGY 3, ENRGY 3 CGF, H-Shield, H- Shield CG, ISO 95+ GL, Multi-Max FA3, Polytherm or Ultra-Max optionally primed with POLYBRITE 745 or WB3000 Dekfast Hex (aka, Dekfast PLT-H-2-7/8) or Dekfast Galvalume Steel 3” Round Insulation Plate (aka, Dekfast PLT-R-3) with Dekfast #12, OMG 3 in. Galvalume Plate (non-ribbed) or OMG AccuTrac Plate with #12 Roofgrip or Trufast 3” Metal Insulation Plate with Trufast DP 1 per 1.3 ft2 SBS-SA-H (Optional) SBS- TA SBS-TA -67.5* TABLE 1F: WOOD DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER SYSTEM TYPE D-2: INSULATED, MECHANICALLY ATTACHED BASE SHEET, BONDED ROOF COVER System No. Deck (Note 1) Insulation Layer(s) (Note 13) Base Sheet Roof Cover (Note 15) MDP (psf) Type Attach Type Fasten (Note 11) Attach Base Ply Cap Ply ASPHALT-APPLIED OR TORCH-APPLIED BASE PLY: W-71 Min. 19/32-inch plywood One or more layers, any combination Prelim. Attached Elastobase, Elastobase P, Elastovent, Polyglass G2 Base, CertainTeed Glasbase, Firestone MB Base, JM Perma- Ply 28 or GAFGLAS #75 OMG Flat Bottom Plates (square) with Roofgrip #14, Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with Dekfast #14 or Trufast 3” Metal Insulation Plate with Trufast #14 HD 12-inch o.c. at min. 4-inch lap and 12-inch o.c. at two (2), equally spaced, staggered center rows (Optional) BP- AA, SBS-AA, SBS- TA or APP-TA SBS-AA, SBS- TA, APP-TA -52.5 W-72 Min. 19/32-inch plywood One or more layers, any combination Prelim. Attached Elastobase, Elastobase P or Elastovent OMG Flat Bottom Plates (square) with Roofgrip #12 12-inch o.c. at min. 4-inch lap and 12-inch o.c. at two (2), equally spaced, staggered center rows (Optional) BP- AA, SBS-AA, SBS- TA or APP-TA SBS-AA, SBS- TA, APP-TA -60.0 W-73 APA rated, 19/32 CAT, 0.578 in., Exposure 1 OSB or min. 19/32” APA rated plywood One or more layers, any combination Loose-laid Elastobase, Elastobase P or Elastovent Trufast Versa Fasteners (min. ¾” penetration) & Plates; 2 screws per plate installed 180° into the holes of the plate, parallel to the width-direction of the sheet* 12-inch o.c. at min. 4-inch lap and 12-inch o.c. at two (2), equally spaced, staggered center rows BP-AA, SBS-AA, SBS-TA, APP-TA SBS-SA, APP- SA, SBS-AA, SBS-TA, APP- TA -67.5 Note: *For re-roof or recover construction, field withdrawal resistance testing (Note 11) shall yield minimum 199 lbf. Additional Versa-Fast Fasteners within each Versa-Fast Plate may be utilized to produce minimum withdrawal resistance NEMO|etc. NEMO ETC, LLC Evaluation Report P9290.02.08-R25 for FL1654-R27 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 25: 09/30/2020 ©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 20 of 94 TABLE 1F: WOOD DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER SYSTEM TYPE D-2: INSULATED, MECHANICALLY ATTACHED BASE SHEET, BONDED ROOF COVER System No. Deck (Note 1) Insulation Layer(s) (Note 13) Base Sheet Roof Cover (Note 15) MDP (psf) Type Attach Type Fasten (Note 11) Attach Base Ply Cap Ply W-74 APA rated, 19/32 CAT, 0.578 in., Exposure 1 OSB or min. 19/32” APA rated plywood One or more layers, any combination Loose-laid Polyglass Base Trufast Versa Fasteners (min. ¾” penetration) & Plates; 2 screws per plate installed 180° into the holes of the plate, parallel to the width-direction of the sheet* 12-inch o.c. at min. 4-inch lap and 12-inch o.c. at two (2), equally spaced, staggered center rows APP-TA APP-TA -67.5 Note: *For re-roof or recover construction, field withdrawal resistance testing (Note 11) shall yield minimum 199 lbf. Additional Versa-Fast Fasteners within each Versa-Fast Plate may be utilized to produce minimum withdrawal resistance W-75 Min. 15/32-inch plywood One or more layers, any combination Prelim. Attached Polyglass G2 Base, Elastobase, Elastobase P or Elastovent Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with Dekfast #14, OMG 3” Round Metal Plate with OMG HD, OMG Flat Bottom Plate (Accutrac) with Roofgrip #14 or Trufast 3” Metal Insulation Plate with Trufast #14 HD. 10-inch o.c. at min. 4-inch lap and 10-inch o.c. at three (3), equally spaced, staggered center rows (Optional) BP- AA, SBS-AA, SBS- TA or APP-TA SBS-AA, SBS- TA, APP-TA -75.0 W-76 Min. 15/32-inch plywood One or more layers, any combination Prelim. Attached Polyglass Base Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with Dekfast #14, OMG 3” Round Metal Plate with OMG HD, OMG Flat Bottom Plate (Accutrac) with Roofgrip #14 or Trufast 3” Metal Insulation Plate with Trufast #14 HD. 10-inch o.c. at min. 4-inch lap and 10-inch o.c. at three (3), equally spaced, staggered center rows (Optional) APP- TA APP-TA -75.0 W-77 APA rated, 7/16 CAT, 0.418 in., Exposure 1 OSB or min. 15/32” APA rated plywood One or more layers, any combination Loose-laid Elastobase, Elastobase P or Elastovent Trufast Versa Fasteners (min. ¾” penetration) & Plates; 2 screws per plate installed 180° into the holes of the plate, parallel to the width-direction of the sheet* 9-inch o.c. at min. 2-inch lap and 12-inch o.c. at two (2), equally spaced, staggered center rows BP-AA, SBS-AA, SBS-TA, APP-TA SBS-SA, APP- SA, SBS-AA, SBS-TA, APP- TA -90.0 Note: *For re-roof or recover construction, field withdrawal resistance testing (Note 11) shall yield minimum 159 lbf. Additional Versa-Fast Fasteners within each Versa-Fast Plate may be utilized to produce minimum withdrawal resistance W-78 APA rated, 7/16 CAT, 0.418 in., Exposure 1 OSB or min. 15/32” APA rated plywood One or more layers, any combination Loose-laid Polyglass Base Trufast Versa Fasteners (min. ¾” penetration) & Plates; 2 screws per plate installed 180° into the holes of the plate, parallel to the width-direction of the sheet* 9-inch o.c. at min. 2-inch lap and 12-inch o.c. at two (2), equally spaced, staggered center rows APP-TA APP-TA -90.0 Note: *For re-roof or recover construction, field withdrawal resistance testing (Note 11) shall yield minimum 159 lbf. Additional Versa-Fast Fasteners within each Versa-Fast Plate may be utilized to produce minimum withdrawal resistance W-79 Min. 15/32-inch plywood One or more layers, any combination Prelim. Attached Polyglass G2 Base, Elastobase, Elastobase P or Elastovent Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with Dekfast #14, OMG 3” Round Metal Plate with OMG HD, OMG Flat Bottom Plate (Accutrac) with Roofgrip #14 or Trufast 3” Metal Insulation Plate with Trufast #14 HD. 9-inch o.c. at min. 4-inch lap and 9-inch o.c. at four (4), equally spaced, staggered center rows (Optional) BP- AA, SBS-AA, SBS- TA or APP-TA SBS-AA, SBS- TA, APP-TA -90.0 NEMO|etc. NEMO ETC, LLC Evaluation Report P9290.02.08-R25 for FL1654-R27 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 25: 09/30/2020 ©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 21 of 94 TABLE 1F: WOOD DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER SYSTEM TYPE D-2: INSULATED, MECHANICALLY ATTACHED BASE SHEET, BONDED ROOF COVER System No. Deck (Note 1) Insulation Layer(s) (Note 13) Base Sheet Roof Cover (Note 15) MDP (psf) Type Attach Type Fasten (Note 11) Attach Base Ply Cap Ply W-80 Min. 15/32-inch plywood One or more layers, any combination Prelim. Attached Polyglass Base Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with Dekfast #14, OMG 3” Round Metal Plate with OMG HD, OMG Flat Bottom Plate (Accutrac) with Roofgrip #14 or Trufast 3” Metal Insulation Plate with Trufast #14 HD. 9-inch o.c. at min. 4-inch lap and 9-inch o.c. at four (4), equally spaced, staggered center rows (Optional) APP- TA APP-TA -90.0 W-81 Min. 15/32-inch plywood One or more layers, any combination Prelim. Attached Elastobase, Elastobase P or Elastovent Trufast #12 DP or Trufast #14 HD with Trufast 3” Metal Insulation Plates 6-inch o.c. at min. 4-inch lap and 6-inch o.c. at three (3), equally spaced, staggered center rows (Optional) BP-AA or SBS-AA SBS-AA -90.0 W-82 Min. 15/32-inch plywood One or more layers, any combination Prelim. Attached Elastobase, Elastobase P or Elastovent OMG #12 Standard Roofgrip or OMG #14 Heavy Duty with OMG 3” Round Metal Plates or OMG Flat Bottom Metal Plates 6-inch o.c. at min. 4-inch lap and 6-inch o.c. at three (3), equally spaced, staggered center rows (Optional) BP- AA, SBS-AA, SBS- TA, APP-TA SBS-AA, SBS- TA or APP-TA -90.0 W-83 Min. 15/32-inch plywood One or more layers, any combination Prelim. Attached Polyglass Base OMG #12 Standard Roofgrip or OMG #14 Heavy Duty with OMG 3” Round Metal Plates or OMG Flat Bottom Metal Plates 6-inch o.c. at min. 4-inch lap and 6-inch o.c. at three (3), equally spaced, staggered center rows (Optional) APP- TA APP-TA -90.0 W-84 APA rated, 7/16 CAT, 0.418 in., Exposure 1 OSB or min. 15/32” APA rated plywood One or more layers, any combination Loose-laid Elastobase, Elastobase P or Elastovent Trufast Versa Fasteners (min. ¾” penetration) & Plates; 2 screws per plate installed 180° into the holes of the plate, parallel to the width-direction of the sheet* 6-inch o.c. at min. 4-inch lap and 6-inch o.c. at three (3), equally spaced, staggered center rows BP-AA, SBS-AA, SBS-TA, APP-TA SBS-SA, APP- SA, SBS-AA, SBS-TA, APP- TA -105.0 Note: *For re-roof or recover construction, field withdrawal resistance testing (Note 11) shall yield minimum 103 lbf. Additional Versa-Fast Fasteners within each Versa-Fast Plate may be utilized to produce minimum withdrawal resistance W-85 APA rated, 7/16 CAT, 0.418 in., Exposure 1 OSB or min. 15/32” APA rated plywood One or more layers, any combination Loose-laid Polyglass Base Trufast Versa Fasteners (min. ¾” penetration) & Plates; 2 screws per plate installed 180° into the holes of the plate, parallel to the width-direction of the sheet* 6-inch o.c. at min. 4-inch lap and 6-inch o.c. at three (3), equally spaced, staggered center rows APP-TA APP-TA -105.0 Note: *For re-roof or recover construction, field withdrawal resistance testing (Note 11) shall yield minimum 103 lbf. Additional Versa-Fast Fasteners within each Versa-Fast Plate may be utilized to produce minimum withdrawal resistance W-86 Min. 15/32-inch plywood One or more layers, any combination Prelim. Attached Elastobase, Elastobase P or Elastovent Trufast #12 DP or Trufast #14 HD with Trufast 3” Metal Insulation Plates 6-inch o.c. at min. 4-inch lap and 6-inch o.c. at five (5), equally spaced, staggered center rows (Optional) BP-AA or SBS-AA SBS-AA -120.0 W-87 Min. 15/32-inch plywood One or more layers, any combination Prelim. Attached Elastobase, Elastobase P or Elastovent OMG #12 Standard Roofgrip or OMG #14 Heavy Duty with OMG 3” Round Metal Plates or OMG Flat Bottom Metal Plates 6-inch o.c. at min. 4-inch lap and 6-inch o.c. at five (5), equally spaced, staggered center rows (Optional) BP- AA, SBS-AA, SBS- TA, APP-TA SBS-AA, SBS- TA or APP-TA -120.0 NEMO|etc. NEMO ETC, LLC Evaluation Report P9290.02.08-R25 for FL1654-R27 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 25: 09/30/2020 ©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 22 of 94 TABLE 1F: WOOD DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER SYSTEM TYPE D-2: INSULATED, MECHANICALLY ATTACHED BASE SHEET, BONDED ROOF COVER System No. Deck (Note 1) Insulation Layer(s) (Note 13) Base Sheet Roof Cover (Note 15) MDP (psf) Type Attach Type Fasten (Note 11) Attach Base Ply Cap Ply W-88 Min. 15/32-inch plywood One or more layers, any combination Prelim. Attached Polyglass Base OMG #12 Standard Roofgrip or OMG #14 Heavy Duty with OMG 3” Round Metal Plates or OMG Flat Bottom Metal Plates 6-inch o.c. at min. 4-inch lap and 6-inch o.c. at five (5), equally spaced, staggered center rows (Optional) APP- TA APP-TA -120.0 SELF-ADHERING BASE PLY: W-89 Min. 19/32-inch plywood One or more layers, any combination Prelim. Attached Elastobase, Elastobase P (poly- film top) Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with Dekfast #14 or Trufast 3” Metal Insulation Plate with Trufast #14 HD 12-inch o.c. at min. 4-inch lap and 12-inch o.c. at two, equally spaced, staggered center rows SBS-SA SBS-SA, APP- SA, SBS-TA or APP-TA -52.5* W-90 Min. 19/32-inch plywood One or more layers, any combination Prelim. Attached Elastobase, Elastobase P (poly- film top) OMG Flat Bottom Plates (square) with Roofgrip #12 12-inch o.c. at min. 4-inch lap and 12-inch o.c. at two, equally spaced, staggered center rows SBS-SA SBS-SA, APP- SA, SBS-TA or APP-TA -60.0* W-91 APA rated, 19/32 CAT, 0.578 in., Exposure 1 OSB or min. 19/32” APA rated plywood One or more layers, any combination Loose-laid Elastobase, Elastobase P (poly- film top) Trufast Versa Fasteners (min. ¾” penetration) & Plates; 2 screws per plate installed 180° into the holes of the plate, parallel to the width-direction of the sheet* 12-inch o.c. at min. 4-inch lap and 12-inch o.c. at two (2), equally spaced, staggered center rows SBS-SA SBS-SA, APP- SA, SBS-TA, APP-TA -67.5 Note: *For re-roof or recover construction, field withdrawal resistance testing (Note 11) shall yield minimum 199 lbf. Additional Versa-Fast Fasteners within each Versa-Fast Plate may be utilized to produce minimum withdrawal resistance HYBRID SYSTEMS WITH SELF-ADHERING APP BASE PLY: W-92 Min. 19/32-inch plywood One or more layers, any combination Prelim. Attached Elastobase, Elastobase P (poly- film top) Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with Dekfast #14 or Trufast 3” Metal Insulation Plate with Trufast #14 HD 12-inch o.c. at min. 4-inch lap and 12-inch o.c. at two, equally spaced, staggered center rows APP-SA-H APP-TA -52.5* W-93 Min. 19/32-inch plywood One or more layers, any combination Prelim. Attached Elastobase, Elastobase P (poly- film top) OMG Flat Bottom Plates (square) with Roofgrip #12 12-inch o.c. at min. 4-inch lap and 12-inch o.c. at two, equally spaced, staggered center rows APP-SA-H APP-TA -60.0* W-94 APA rated, 19/32 CAT, 0.578 in., Exposure 1 OSB or min. 19/32” APA rated plywood One or more layers, any combination Loose-laid Elastobase, Elastobase P (poly- film top) Trufast Versa Fasteners (min. ¾” penetration) & Plates; 2 screws per plate installed 180° into the holes of the plate, parallel to the width-direction of the sheet* 12-inch o.c. at min. 4-inch lap and 12-inch o.c. at two (2), equally spaced, staggered center rows APP-SA-H APP-TA -67.5 Note: *For re-roof or recover construction, field withdrawal resistance testing (Note 11) shall yield minimum 199 lbf. Additional Versa-Fast Fasteners within each Versa-Fast Plate may be utilized to produce minimum withdrawal resistance HYBRID SYSTEMS WITH SELF-ADHERING SBS BASE PLY: W-95 Min. 19/32-inch plywood One or more layers, any combination Prelim. Attached Elastobase, Elastobase P (poly- film top) Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with Dekfast #14 or Trufast 3” Metal Insulation Plate with Trufast #14 HD 12-inch o.c. at min. 4-inch lap and 12-inch o.c. at two, equally spaced, staggered center rows SBS-SA-H SBS-TA -52.5* NEMO|etc. NEMO ETC, LLC Evaluation Report P9290.02.08-R25 for FL1654-R27 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 25: 09/30/2020 ©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 23 of 94 TABLE 1F: WOOD DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER SYSTEM TYPE D-2: INSULATED, MECHANICALLY ATTACHED BASE SHEET, BONDED ROOF COVER System No. Deck (Note 1) Insulation Layer(s) (Note 13) Base Sheet Roof Cover (Note 15) MDP (psf) Type Attach Type Fasten (Note 11) Attach Base Ply Cap Ply W-96 Min. 19/32-inch plywood One or more layers, any combination Prelim. Attached Elastobase, Elastobase P (poly- film top) OMG Flat Bottom Plates (square) with Roofgrip #12 12-inch o.c. at min. 4-inch lap and 12-inch o.c. at two, equally spaced, staggered center rows SBS-SA-H SBS-TA -60.0* W-97 APA rated, 19/32 CAT, 0.578 in., Exposure 1 OSB or min. 19/32” APA rated plywood One or more layers, any combination Loose-laid Elastobase, Elastobase P (poly- film top) Trufast Versa Fasteners (min. ¾” penetration) & Plates; 2 screws per plate installed 180° into the holes of the plate, parallel to the width-direction of the sheet* 12-inch o.c. at min. 4-inch lap and 12-inch o.c. at two (2), equally spaced, staggered center rows SBS-SA-H SBS-TA -67.5 Note: *For re-roof or recover construction, field withdrawal resistance testing (Note 11) shall yield minimum 199 lbf. Additional Versa-Fast Fasteners within each Versa-Fast Plate may be utilized to produce minimum withdrawal resistance TABLE 1G: WOOD DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF) SYSTEM TYPE E-2: NON-INSULATED, MECHANICALLY ATTACHED BASE SHEET (NAILS), BONDED ROOF COVER System No. Deck (Note 1) Base Sheet Roof Cover (Note 15) MDP (psf) Type Fasten (Note 11) Attach Base Ply Cap Ply NO BASE PLY: W-98 Min. 15/32-inch plywood Elastobase, Elastobase P Simplex MAXX Cap 9-inch o.c. at min. 2-inch lap and 18-inch o.c. at two (2), equally spaced, staggered center rows None SBS-AA, SBS-TA, APP-TA -45.0* W-99 APA rated, 7/16 CAT, 0.418 in., Exposure 1 OSB Elastobase, Elastobase P or Elastovent 32 ga., 1-5/8-inch diameter tin caps with 12 ga. annular ring shank nails 6-inch o.c. at min. 3-inch lap and 6-inch o.c. at four (4), equally spaced, staggered center rows None SBS-AA, SBS-TA, APP-TA -45.0 W-100 APA rated, 7/16 CAT, 0.418 in., Exposure 1 OSB Elastobase, Elastobase P (poly-film top) 32 ga., 1-5/8-inch diameter tin caps with 12 ga. annular ring shank nails 6-inch o.c. at min. 3-inch lap and 6-inch o.c. at four (4), equally spaced, staggered center rows None SBS-SA, APP-SA -45.0 W-101 APA rated, 7/16 CAT, 0.418 in., Exposure 1 OSB Polyglass Base 32 ga., 1-5/8-inch diameter tin caps with 12 ga. annular ring shank nails 6-inch o.c. at min. 3-inch lap and 6-inch o.c. at four (4), equally spaced, staggered center rows None APP-TA -45.0 W-102 Min. 15/32-inch plywood Elastobase, Elastobase P Simplex MAXX Cap 9-inch o.c. at min. 2-inch lap and 12-inch o.c. at two (2), equally spaced, staggered center rows None SBS-AA, SBS-TA, APP-TA -52.5 W-103 Min. 15/32-inch plywood Elastobase, Elastobase P or Elastovent Original Simplex Cap Nails (1-inch metal head diameter, 11 gauge x min. 1.25-inch long annular grooved shank) 6-inch o.c. at min. 3-inch lap and 6-inch o.c. at four (4), equally spaced, staggered center rows None SBS-AA, SBS-TA, APP-TA -52.5 NEMO|etc. NEMO ETC, LLC Evaluation Report P9290.02.08-R25 for FL1654-R27 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 25: 09/30/2020 ©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 24 of 94 TABLE 1G: WOOD DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF) SYSTEM TYPE E-2: NON-INSULATED, MECHANICALLY ATTACHED BASE SHEET (NAILS), BONDED ROOF COVER System No. Deck (Note 1) Base Sheet Roof Cover (Note 15) MDP (psf) Type Fasten (Note 11) Attach Base Ply Cap Ply W-104 Min. 15/32-inch plywood Elastobase, Elastobase P (poly-film top) Original Simplex Cap Nails (1-inch metal head diameter, 11 gauge x min. 1.25-inch long annular grooved shank) 6-inch o.c. at min. 3-inch lap and 6-inch o.c. at four (4), equally spaced, staggered center rows None SBS-SA, APP-SA -52.5 W-105 Min. 15/32-inch plywood Polyglass Base Original Simplex Cap Nails (1-inch metal head diameter, 11 gauge x min. 1.25-inch long annular grooved shank) 6-inch o.c. at min. 3-inch lap and 6-inch o.c. at four (4), equally spaced, staggered center rows None APP-TA -52.5 W-106 APA rated, 7/16 CAT, 0.418 in., Exposure 1 OSB or min. 15/32” APA rated plywood Elastobase (sanded top) Simplex MAXX Cap 8-inch o.c. at min. 3-inch lap and 8-inch o.c. at three (3), equally spaced, staggered center rows None SBS-AA, SBS-TA, APP-TA -60.0 W-107 APA rated, 7/16 CAT, 0.418 in., Exposure 1 OSB or min. 15/32” APA rated plywood Elastobase (poly-film top) Simplex MAXX Cap 8-inch o.c. at min. 3-inch lap and 8-inch o.c. at three (3), equally spaced, staggered center rows None SBS-TA, APP-TA -60.0 W-108 APA rated, 7/16 CAT, 0.418 in., Exposure 1 OSB or min. 15/32” APA rated plywood Polyglass Base Simplex MAXX Cap 8-inch o.c. at min. 3-inch lap and 8-inch o.c. at three (3), equally spaced, staggered center rows None APP-TA -60.0 W-109 APA rated, 7/16 CAT, 0.418 in., Exposure 1 OSB or min. 15/32” APA rated plywood Elastobase (poly-film top) Simplex MAXX Cap Note: MAXX Caps are to be primed with PG100 or ASTM D41 primer 8-inch o.c. at min. 3-inch lap and 8-inch o.c. at three (3), equally spaced, staggered center rows None SBS-SA, APP-SA -60.0 W-110 Min. 19/32-inch plywood Elastobase, Elastobase P, Elastovent, Polyglass G2 Base, CertainTeed Glasbase, Firestone MB Base, JM Perma-Ply 28 or GAFGLAS #75 32 ga., 1-5/8-inch diameter tin caps with 11 ga. annular ring shank nails 8-inch o.c. at min. 4-inch lap and 8-inch o.c. at three (3), equally spaced, staggered center rows None SBS-AA, SBS-TA, APP-TA -60.0 W-111 Min. 19/32-inch plywood Elastobase, Elastobase P (poly-film top) 32 ga., 1-5/8-inch diameter tin caps with 11 ga. annular ring shank nails 8-inch o.c. at min. 4-inch lap and 8-inch o.c. at three (3), equally spaced, staggered center rows None SBS-SA, APP-SA -60.0 NEMO|etc. NEMO ETC, LLC Evaluation Report P9290.02.08-R25 for FL1654-R27 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 25: 09/30/2020 ©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 25 of 94 TABLE 1G: WOOD DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF) SYSTEM TYPE E-2: NON-INSULATED, MECHANICALLY ATTACHED BASE SHEET (NAILS), BONDED ROOF COVER System No. Deck (Note 1) Base Sheet Roof Cover (Note 15) MDP (psf) Type Fasten (Note 11) Attach Base Ply Cap Ply W-112 Min. 15/32-inch plywood Polyglass G2 Base, Elastobase, Elastobase P or Elastovent 32 ga., 1-5/8-inch diameter tin caps with 11 ga. annular ring shank nails 8-inch o.c. at min. 4-inch lap and 8-inch o.c. at four (4), equally spaced, staggered center rows None SBS-AA, SBS-TA, APP-TA -67.5 W-113 Min. 15/32-inch plywood Polyglass Base 32 ga., 1-5/8-inch diameter tin caps with 11 ga. annular ring shank nails 8-inch o.c. at min. 4-inch lap and 8-inch o.c. at four (4), equally spaced, staggered center rows None APP-TA -67.5 W-114 Min. 15/32-inch plywood Polyglass G2 Base, Elastobase, Elastobase P Simplex MAXX Cap 10-inch o.c. at min. 4-inch lap and 10-inch o.c. at three (3), equally spaced, staggered center rows None SBS-AA, SBS-TA, APP-TA -75.0 W-115 Min. 15/32-inch plywood Polyglass Base Simplex MAXX Cap 10-inch o.c. at min. 4-inch lap and 10-inch o.c. at three (3), equally spaced, staggered center rows None APP-TA -75.0 W-116 Min. 15/32-inch plywood Polyglass G2 Base, Elastobase, Elastobase P Simplex MAXX Cap 9-inch o.c. at min. 4-inch lap and 9-inch o.c. at four (4), equally spaced, staggered center rows None SBS-AA, SBS-TA, APP-TA -90.0 W-117 Min. 15/32-inch plywood Polyglass Base Simplex MAXX Cap 9-inch o.c. at min. 4-inch lap and 9-inch o.c. at four (4), equally spaced, staggered center rows None APP-TA -90.0 W-118 Min. 15/32-inch plywood Elastobase, Elastobase P Simplex MAXX Cap 6-inch o.c. at min. 2-inch lap and 6-inch o.c. at two (2), equally spaced, staggered center rows None SBS-AA, SBS-TA, APP-TA -90.0 W-119 Min. 19/32-inch plywood Elastobase, Elastobase P (poly-film top) 32 ga., 1-5/8-inch diameter tin caps with 11 ga. annular ring shank nails. 4-inch o.c. at min. 4-inch lap and 4-inch o.c. at four (4), equally spaced, staggered center rows None SBS-SA, APP-SA -97.5 W-120 Min. 15/32-inch plywood Elastobase, Elastobase P Simplex MAXX Cap 6-inch o.c. at min. 2-inch lap and 6-inch o.c. at three (3), equally spaced, staggered center rows None SBS-AA, SBS-TA, APP-TA -105.0 W-121 Min. 19/32-inch plywood Elastobase, Elastobase P or Elastovent 32 ga., 1-5/8-inch diameter tin caps with 11 ga. annular ring shank nails 6-inch o.c. at min. 4-inch lap and 6-inch o.c. at four (4), equally spaced, staggered center rows None SBS-AA, SBS-TA, APP-TA -112.5 W-122 Min. 19/32-inch plywood Elastobase, Elastobase P (poly-film top) 32 ga., 1-5/8-inch diameter tin caps with 11 ga. annular ring shank nails. Note: Tin caps are to be primed with PG100 or ASTM D41 primer. 6-inch o.c. at min. 4-inch lap and 6-inch o.c. at four (4), equally spaced, staggered center rows None SBS-SA, APP-SA -112.5 ASPHALT-APPLIED OR TORCH-APPLIED BASE PLY: NEMO|etc. NEMO ETC, LLC Evaluation Report P9290.02.08-R25 for FL1654-R27 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 25: 09/30/2020 ©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 26 of 94 TABLE 1G: WOOD DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF) SYSTEM TYPE E-2: NON-INSULATED, MECHANICALLY ATTACHED BASE SHEET (NAILS), BONDED ROOF COVER System No. Deck (Note 1) Base Sheet Roof Cover (Note 15) MDP (psf) Type Fasten (Note 11) Attach Base Ply Cap Ply W-123 Min. 15/32-inch plywood Elastobase, Elastobase P Simplex MAXX Cap 9-inch o.c. at min. 2-inch lap and 18-inch o.c. at two (2), equally spaced, staggered center rows BP-AA, SBS-AA, SBS- TA, APP-TA SBS-SA, APP-SA, SBS-AA, SBS-TA, APP-TA -45.0* W-124 APA rated, 7/16 CAT, 0.418 in., Exposure 1 OSB Elastobase, Elastobase P or Elastovent 32 ga., 1-5/8-inch diameter tin caps with 12 ga. annular ring shank nails 6-inch o.c. at min. 3-inch lap and 6-inch o.c. at four (4), equally spaced, staggered center rows BP-AA, SBS-AA, SBS- TA, APP-TA SBS-SA, APP-SA, SBS-AA, SBS-TA, APP-TA -45.0 W-125 APA rated, 7/16 CAT, 0.418 in., Exposure 1 OSB Polyglass Base 32 ga., 1-5/8-inch diameter tin caps with 12 ga. annular ring shank nails 6-inch o.c. at min. 3-inch lap and 6-inch o.c. at four (4), equally spaced, staggered center rows APP-TA APP-TA -45.0 W-126 Min. 15/32-inch plywood Elastobase, Elastobase P Simplex MAXX Cap 9-inch o.c. at min. 2-inch lap and 12-inch o.c. at two (2), equally spaced, staggered center rows BP-AA, SBS-AA, SBS- TA, APP-TA SBS-SA, APP-SA, SBS-AA, SBS-TA, APP-TA -52.5 W-127 Min. 15/32-inch plywood Elastobase, Elastobase P or Elastovent Original Simplex Cap Nails (1-inch metal head diameter, 11 gauge x min. 1.25-inch long annular grooved shank) 6-inch o.c. at min. 3-inch lap and 6-inch o.c. at four (4), equally spaced, staggered center rows BP-AA, SBS-AA, SBS- TA, APP-TA SBS-SA, APP-SA, SBS-AA, SBS-TA, APP-TA -52.5 W-128 Min. 15/32-inch plywood Polyglass Base Original Simplex Cap Nails (1-inch metal head diameter, 11 gauge x min. 1.25-inch long annular grooved shank) 6-inch o.c. at min. 3-inch lap and 6-inch o.c. at four (4), equally spaced, staggered center rows APP-TA APP-TA -52.5 W-129 APA rated, 7/16 CAT, 0.418 in., Exposure 1 OSB or min. 15/32” APA rated plywood Elastobase (sanded top) Simplex MAXX Cap 8-inch o.c. at min. 3-inch lap and 8-inch o.c. at three (3), equally spaced, staggered center rows BP-AA, SBS-AA, SBS- TA, APP-TA SBS-AA, SBS-TA, APP-TA -60.0 W-130 APA rated, 7/16 CAT, 0.418 in., Exposure 1 OSB or min. 15/32” APA rated plywood Elastobase (poly-film top) Simplex MAXX Cap 8-inch o.c. at min. 3-inch lap and 8-inch o.c. at three (3), equally spaced, staggered center rows SBS-TA SBS-TA, APP-TA -60.0 W-131 APA rated, 7/16 CAT, 0.418 in., Exposure 1 OSB or min. 15/32” APA rated plywood Polyglass Base Simplex MAXX Cap 8-inch o.c. at min. 3-inch lap and 8-inch o.c. at three (3), equally spaced, staggered center rows APP-TA APP-TA -60.0 W-132 Min. 19/32-inch plywood Elastobase, Elastobase P, Elastovent, Polyglass G2 Base, CertainTeed Glasbase, Firestone MB Base, JM Perma- Ply 28 or GAFGLAS #75 32 ga., 1-5/8-inch diameter tin caps with 11 ga. annular ring shank nails 8-inch o.c. at min. 4-inch lap and 8-inch o.c. at three (3), equally spaced, staggered center rows BP-AA, SBS-AA, SBS- TA, APP-TA SBS-SA, APP-SA, SBS-AA, SBS-TA, APP-TA -60.0 NEMO|etc. NEMO ETC, LLC Evaluation Report P9290.02.08-R25 for FL1654-R27 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 25: 09/30/2020 ©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 27 of 94 TABLE 1G: WOOD DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF) SYSTEM TYPE E-2: NON-INSULATED, MECHANICALLY ATTACHED BASE SHEET (NAILS), BONDED ROOF COVER System No. Deck (Note 1) Base Sheet Roof Cover (Note 15) MDP (psf) Type Fasten (Note 11) Attach Base Ply Cap Ply W-133 Min. 15/32-inch plywood Polyglass G2 Base, Elastobase, Elastobase P or Elastovent 32 ga., 1-5/8-inch diameter tin caps with 11 ga. annular ring shank nails 8-inch o.c. at min. 4-inch lap and 8-inch o.c. at four (4), equally spaced, staggered center rows BP-AA, SBS-AA, SBS- TA, APP-TA SBS-SA, APP-SA, SBS-AA, SBS-TA, APP-TA -67.5 W-134 Min. 15/32-inch plywood Polyglass Base 32 ga., 1-5/8-inch diameter tin caps with 11 ga. annular ring shank nails 8-inch o.c. at min. 4-inch lap and 8-inch o.c. at four (4), equally spaced, staggered center rows APP-TA APP-TA -67.5 W-135 Min. 15/32-inch plywood Polyglass G2 Base, Elastobase, Elastobase P Simplex MAXX Cap 10-inch o.c. at min. 4-inch lap and 10-inch o.c. at three (3), equally spaced, staggered center rows BP-AA, SBS-AA, SBS- TA, APP-TA SBS-SA, APP-SA, SBS-AA, SBS-TA, APP-TA -75.0 W-136 Min. 15/32-inch plywood Polyglass Base Simplex MAXX Cap 10-inch o.c. at min. 4-inch lap and 10-inch o.c. at three (3), equally spaced, staggered center rows APP-TA APP-TA -75.0 W-137 Min. 15/32-inch plywood Polyglass G2 Base, Elastobase, Elastobase P Simplex MAXX Cap 9-inch o.c. at min. 4-inch lap and 9-inch o.c. at four (4), equally spaced, staggered center rows BP-AA, SBS-AA, SBS- TA, APP-TA SBS-SA, APP-SA, SBS-AA, SBS-TA, APP-TA -90.0 W-138 Min. 15/32-inch plywood Polyglass Base Simplex MAXX Cap 9-inch o.c. at min. 4-inch lap and 9-inch o.c. at four (4), equally spaced, staggered center rows APP-TA APP-TA -90.0 W-139 Min. 15/32-inch plywood Elastobase, Elastobase P Simplex MAXX Cap 6-inch o.c. at min. 2-inch lap and 6-inch o.c. at two (2), equally spaced, staggered center rows BP-AA, SBS-AA, SBS- TA, APP-TA SBS-SA, APP-SA, SBS-AA, SBS-TA, APP-TA -90.0 W-140 Min. 15/32-inch plywood Elastobase, Elastobase P Simplex MAXX Cap 6-inch o.c. at min. 2-inch lap and 6-inch o.c. at three (3), equally spaced, staggered center rows BP-AA, SBS-AA, SBS- TA, APP-TA SBS-SA, APP-SA, SBS-AA, SBS-TA, APP-TA -105.0 W-141 Min. 19/32-inch plywood Elastobase, Elastobase P or Elastovent 32 ga., 1-5/8-inch diameter tin caps with 11 ga. annular ring shank nails 6-inch o.c. at min. 4-inch lap and 6-inch o.c. at four (3), equally spaced, staggered center rows BP-AA, SBS-AA, SBS- TA, APP-TA SBS-SA, APP-SA, SBS-AA, SBS-TA, APP-TA -112.5 SELF-ADHERING BASE PLY: W-142 APA rated, 7/16 CAT, 0.418 in., Exposure 1 OSB Elastobase, Elastobase P (poly-film top) 32 ga., 1-5/8-inch diameter tin caps with 12 ga. annular ring shank nails 6-inch o.c. at min. 3-inch lap and 6-inch o.c. at four (4), equally spaced, staggered center rows SBS-SA SBS-SA, APP-SA, SBS-TA, APP-TA -45.0 W-143 Min. 15/32-inch plywood Elastobase, Elastobase P (poly-film top) Original Simplex Cap Nails (1-inch metal head diameter, 11 gauge x min. 1.25-inch long annular grooved shank) 6-inch o.c. at min. 3-inch lap and 6-inch o.c. at four (4), equally spaced, staggered center rows SBS-SA SBS-SA, APP-SA, SBS-TA, APP-TA -52.5 NEMO|etc. NEMO ETC, LLC Evaluation Report P9290.02.08-R25 for FL1654-R27 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 25: 09/30/2020 ©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 28 of 94 TABLE 1G: WOOD DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF) SYSTEM TYPE E-2: NON-INSULATED, MECHANICALLY ATTACHED BASE SHEET (NAILS), BONDED ROOF COVER System No. Deck (Note 1) Base Sheet Roof Cover (Note 15) MDP (psf) Type Fasten (Note 11) Attach Base Ply Cap Ply W-144 APA rated, 7/16 CAT, 0.418 in., Exposure 1 OSB or min. 15/32” APA rated plywood Elastobase (poly-film top) Simplex MAXX Cap Note: MAXX Caps are to be primed with PG100 or ASTM D41 primer 8-inch o.c. at min. 3-inch lap and 8-inch o.c. at three (3), equally spaced, staggered center rows SBS-SA SBS-SA, APP-SA, SBS-TA, APP-TA -60.0 W-145 Min. 19/32-inch plywood Elastobase, Elastobase P (poly-film top) 32 ga., 1-5/8-inch diameter tin caps with 11 ga. annular ring shank nails 8-inch o.c. at min. 4-inch lap and 8-inch o.c. at three (3), equally spaced, staggered center rows SBS-SA SBS-SA, APP-SA, SBS-TA, APP-TA -60.0 W-146 Min. 19/32-inch plywood Elastobase, Elastobase P (poly-film top) 32 ga., 1-5/8-inch diameter tin caps with 11 ga. annular ring shank nails. 4-inch o.c. at min. 4-inch lap and 4-inch o.c. at four (4), equally spaced, staggered center rows SBS-SA SBS-SA, APP-SA, SBS-TA, APP-TA -97.5 W-147 Min. 19/32-inch plywood Elastobase, Elastobase P (poly-film top) 32 ga., 1-5/8-inch diameter tin caps with 11 ga. annular ring shank nails. Note: Tin caps are to be primed with PG100 or ASTM D41 primer. 6-inch o.c. at min. 4-inch lap and 6-inch o.c. at four (4), equally spaced, staggered center rows Elastoflex SA V Plus, Elastoflex SA V Plus FR SBS-SA, APP-SA, SBS-TA, APP-TA -112.5 HYBRID SYSTEMS WITH SELF-ADHERING APP BASE PLY: W-148 Min. 15/32-inch plywood Polyglass Base, Elastobase, Elastobase P (poly-film top) Original Simplex Cap Nails (1-inch metal head diameter, 11 gauge x min. 1.25-inch long annular grooved shank) 6-inch o.c. at min. 3-inch lap and 6-inch o.c. at four (4), equally spaced, staggered center rows APP-SA-H APP-TA -52.5 W-149 Min. 19/32-inch plywood Elastobase, Elastobase P (poly-film top) 32 ga., 1-5/8-inch diameter tin caps with 11 ga. annular ring shank nails 8-inch o.c. at min. 4-inch lap and 8-inch o.c. at three (3), equally spaced, staggered center rows APP-SA-H APP-TA -60.0 W-150 Min. 19/32-inch plywood Elastobase, Elastobase P (poly-film top) 32 ga., 1-5/8-inch diameter tin caps with 11 ga. annular ring shank nails. 4-inch o.c. at min. 4-inch lap and 4-inch o.c. at four (4), equally spaced, staggered center rows APP-SA-H APP-TA -97.5 W-151 Min. 19/32-inch plywood Elastobase, Elastobase P (poly-film top) 32 ga., 1-5/8-inch diameter tin caps with 11 ga. annular ring shank nails. Note: Tin caps are to be primed with PG100 or ASTM D41 primer. 6-inch o.c. at min. 4-inch lap and 6-inch o.c. at four (4), equally spaced, staggered center rows APP-SA-H APP-TA -112.5 HYBRID SYSTEMS WITH SELF-ADHERING SBS BASE PLY: W-152 APA rated, 7/16 CAT, 0.418 in., Exposure 1 OSB Elastobase, Elastobase P (poly-film top) 32 ga., 1-5/8-inch diameter tin caps with 12 ga. annular ring shank nails 6-inch o.c. at min. 3-inch lap and 6-inch o.c. at four (4), equally spaced, staggered center rows SBS-SA-H SBS-TA -45.0 W-153 Min. 15/32-inch plywood Elastobase, Elastobase P (poly-film top) Original Simplex Cap Nails (1-inch metal head diameter, 11 gauge x min. 1.25-inch long annular grooved shank) 6-inch o.c. at min. 3-inch lap and 6-inch o.c. at four (4), equally spaced, staggered center rows SBS-SA-H SBS-TA -52.5 NEMO|etc. NEMO ETC, LLC Evaluation Report P9290.02.08-R25 for FL1654-R27 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 25: 09/30/2020 ©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 29 of 94 TABLE 1G: WOOD DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF) SYSTEM TYPE E-2: NON-INSULATED, MECHANICALLY ATTACHED BASE SHEET (NAILS), BONDED ROOF COVER System No. Deck (Note 1) Base Sheet Roof Cover (Note 15) MDP (psf) Type Fasten (Note 11) Attach Base Ply Cap Ply W-154 APA rated, 7/16 CAT, 0.418 in., Exposure 1 OSB or min. 15/32” APA rated plywood Elastobase (poly-film top) Simplex MAXX Cap Note: MAXX Caps are to be primed with PG100 or ASTM D41 primer 8-inch o.c. at min. 3-inch lap and 8-inch o.c. at three (3), equally spaced, staggered center rows SBS-SA-H SBS-TA -60.0 W-155 Min. 19/32-inch plywood Elastobase, Elastobase P (poly-film top) 32 ga., 1-5/8-inch diameter tin caps with 11 ga. annular ring shank nails 8-inch o.c. at min. 4-inch lap and 8-inch o.c. at three (3), equally spaced, staggered center rows SBS-SA-H SBS-TA -60.0 W-156 Min. 19/32-inch plywood Elastobase, Elastobase P (poly-film top) 32 ga., 1-5/8-inch diameter tin caps with 11 ga. annular ring shank nails. 4-inch o.c. at min. 4-inch lap and 4-inch o.c. at four (4), equally spaced, staggered center rows SBS-SA-H SBS-TA -97.5 TABLE 1H: WOOD DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER SYSTEM TYPE E-2: NON-INSULATED, MECHANICALLY ATTACHED BASE SHEET (SCREWS & PLATES), BONDED ROOF COVER System No. Deck (Note 1) Base Sheet Roof Cover (Note 15) MDP (psf) Type Fasten (Note 11) Attach Base Ply Cap NO BASE PLY: W-157 Min. 19/32-inch plywood Elastobase, Elastobase P, Elastovent, Polyglass G2 Base, CertainTeed Glasbase, Firestone MB Base, JM Perma-Ply 28 or GAFGLAS #75 OMG Flat Bottom Plates (square) with Roofgrip #14, Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with Dekfast #14 or Trufast 3” Metal Insulation Plate with Trufast #14 HD 12-inch o.c. at min. 4-inch lap and 12-inch o.c. at two (2), equally spaced, staggered center rows None SBS-AA, SBS-TA, APP-TA -52.5 W-158 Min. 19/32-inch plywood Elastobase, Elastobase P or Elastovent OMG Flat Bottom Plates (square) with Roofgrip #12 12-inch o.c. at min. 4-inch lap and 12-inch o.c. at two (2), equally spaced, staggered center rows None SBS-AA, SBS-TA, APP-TA -60.0 W-159 APA rated, 19/32 CAT, 0.578 in., Exposure 1 OSB or min. 19/32” APA rated plywood Elastobase, Elastobase P or Elastovent Trufast Versa Fasteners (min. ¾” penetration) & Plates; 2 screws per plate installed 180° into the holes of the plate, parallel to the width-direction of the sheet* 12-inch o.c. at min. 4-inch lap and 12-inch o.c. at two (2), equally spaced, staggered center rows None SBS-AA, SBS-TA, APP-TA -67.5 Note: *For re-roof or recover construction, field withdrawal resistance testing (Note 11) shall yield minimum 199 lbf. Additional Versa-Fast Fasteners within each Versa-Fast Plate may be utilized to produce minimum withdrawal resistance NEMO|etc. NEMO ETC, LLC Evaluation Report P9290.02.08-R25 for FL1654-R27 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 25: 09/30/2020 ©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 30 of 94 TABLE 1H: WOOD DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER SYSTEM TYPE E-2: NON-INSULATED, MECHANICALLY ATTACHED BASE SHEET (SCREWS & PLATES), BONDED ROOF COVER System No. Deck (Note 1) Base Sheet Roof Cover (Note 15) MDP (psf) Type Fasten (Note 11) Attach Base Ply Cap W-160 APA rated, 19/32 CAT, 0.578 in., Exposure 1 OSB or min. 19/32” APA rated plywood Elastobase, Elastobase P (poly-film top) Trufast Versa Fasteners (min. ¾” penetration) & Plates; 2 screws per plate installed 180° into the holes of the plate, parallel to the width-direction of the sheet* 12-inch o.c. at min. 4-inch lap and 12-inch o.c. at two (2), equally spaced, staggered center rows None SBS-SA, APP-SA -67.5 Note: *For re-roof or recover construction, field withdrawal resistance testing (Note 11) shall yield minimum 199 lbf. Additional Versa-Fast Fasteners within each Versa-Fast Plate may be utilized to produce minimum withdrawal resistance W-161 APA rated, 19/32 CAT, 0.578 in., Exposure 1 OSB or min. 19/32” APA rated plywood Polyglass Base Trufast Versa Fasteners (min. ¾” penetration) & Plates; 2 screws per plate installed 180° into the holes of the plate, parallel to the width-direction of the sheet* 12-inch o.c. at min. 4-inch lap and 12-inch o.c. at two (2), equally spaced, staggered center rows None APP-TA -67.5 Note: *For re-roof or recover construction, field withdrawal resistance testing (Note 11) shall yield minimum 199 lbf. Additional Versa-Fast Fasteners within each Versa-Fast Plate may be utilized to produce minimum withdrawal resistance W-162 Min. 15/32-inch plywood Polyglass G2 Base, Elastobase, Elastobase P or Elastovent Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with Dekfast #14, OMG 3” Round Metal Plate with OMG HD, OMG Flat Bottom Plate (Accutrac) with Roofgrip #14 or Trufast 3” Metal Insulation Plate with Trufast #14 HD. 10-inch o.c. at min. 4-inch lap and 10-inch o.c. at three (3), equally spaced, staggered center rows None SBS-AA, SBS-TA, APP-TA -75.0 W-163 Min. 15/32-inch plywood Polyglass Base Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with Dekfast #14, OMG 3” Round Metal Plate with OMG HD, OMG Flat Bottom Plate (Accutrac) with Roofgrip #14 or Trufast 3” Metal Insulation Plate with Trufast #14 HD. 10-inch o.c. at min. 4-inch lap and 10-inch o.c. at three (3), equally spaced, staggered center rows None APP-TA -75.0 W-164 APA rated, 7/16 CAT, 0.418 in., Exposure 1 OSB or min. 15/32” APA rated plywood Elastobase, Elastobase P or Elastovent Trufast Versa Fasteners (min. ¾” penetration) & Plates; 2 screws per plate installed 180° into the holes of the plate, parallel to the width-direction of the sheet* 9-inch o.c. at min. 2-inch lap and 12-inch o.c. at two (2), equally spaced, staggered center rows None SBS-AA, SBS-TA, APP-TA -90.0 Note: *For re-roof or recover construction, field withdrawal resistance testing (Note 11) shall yield minimum 159 lbf. Additional Versa-Fast Fasteners within each Versa-Fast Plate may be utilized to produce minimum withdrawal resistance W-165 APA rated, 7/16 CAT, 0.418 in., Exposure 1 OSB or min. 15/32” APA rated plywood Polyglass Base Trufast Versa Fasteners (min. ¾” penetration) & Plates; 2 screws per plate installed 180° into the holes of the plate, parallel to the width-direction of the sheet* 9-inch o.c. at min. 2-inch lap and 12-inch o.c. at two (2), equally spaced, staggered center rows None APP-TA -90.0 Note: *For re-roof or recover construction, field withdrawal resistance testing (Note 11) shall yield minimum 159 lbf. Additional Versa-Fast Fasteners within each Versa-Fast Plate may be utilized to produce minimum withdrawal resistance NEMO|etc. NEMO ETC, LLC Evaluation Report P9290.02.08-R25 for FL1654-R27 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 25: 09/30/2020 ©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 31 of 94 TABLE 1H: WOOD DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER SYSTEM TYPE E-2: NON-INSULATED, MECHANICALLY ATTACHED BASE SHEET (SCREWS & PLATES), BONDED ROOF COVER System No. Deck (Note 1) Base Sheet Roof Cover (Note 15) MDP (psf) Type Fasten (Note 11) Attach Base Ply Cap W-166 Min. 15/32-inch plywood Polyglass G2 Base, Elastobase, Elastobase P or Elastovent Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with Dekfast #14, OMG 3” Round Metal Plate with OMG HD, OMG Flat Bottom Plate (Accutrac) with Roofgrip #14 or Trufast 3” Metal Insulation Plate with Trufast #14 HD. 9-inch o.c. at min. 4-inch lap and 9-inch o.c. at four (4), equally spaced, staggered center rows None SBS-AA, SBS-TA, APP-TA -90.0 W-167 Min. 15/32-inch plywood Polyglass Base Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with Dekfast #14, OMG 3” Round Metal Plate with OMG HD, OMG Flat Bottom Plate (Accutrac) with Roofgrip #14 or Trufast 3” Metal Insulation Plate with Trufast #14 HD. 9-inch o.c. at min. 4-inch lap and 9-inch o.c. at four (4), equally spaced, staggered center rows None APP-TA -90.0 W-168 Min. 15/32-inch plywood Elastobase, Elastobase P or Elastovent Trufast #12 DP or Trufast #14 HD with Trufast 3” Metal Insulation Plates 6-inch o.c. at min. 4-inch lap and 6-inch o.c. at three (3), equally spaced, staggered center rows None SBS-AA -90.0 W-169 Min. 15/32-inch plywood Elastobase, Elastobase P or Elastovent OMG #12 Standard Roofgrip or OMG #14 Heavy Duty with OMG 3” Round Metal Plates or OMG Flat Bottom Metal Plates 6-inch o.c. at min. 4-inch lap and 6-inch o.c. at three (3), equally spaced, staggered center rows None SBS-AA, SBS-TA or APP-TA -90.0 W-170 Min. 15/32-inch plywood Polyglass Base OMG #12 Standard Roofgrip or OMG #14 Heavy Duty with OMG 3” Round Metal Plates or OMG Flat Bottom Metal Plates 6-inch o.c. at min. 4-inch lap and 6-inch o.c. at three (3), equally spaced, staggered center rows None APP-TA -90.0 W-171 APA rated, 7/16 CAT, 0.418 in., Exposure 1 OSB or min. 15/32” APA rated plywood Elastobase, Elastobase P or Elastovent Trufast Versa Fasteners (min. ¾” penetration) & Plates; 2 screws per plate installed 180° into the holes of the plate, parallel to the width-direction of the sheet* 6-inch o.c. at min. 4-inch lap and 6-inch o.c. at three (3), equally spaced, staggered center rows None SBS-AA, SBS-TA, APP-TA -105.0 Note: *For re-roof or recover construction, field withdrawal resistance testing (Note 11) shall yield minimum 103 lbf. Additional Versa-Fast Fasteners within each Versa-Fast Plate may be utilized to produce minimum withdrawal resistance W-172 APA rated, 7/16 CAT, 0.418 in., Exposure 1 OSB or min. 15/32” APA rated plywood Polyglass Base Trufast Versa Fasteners (min. ¾” penetration) & Plates; 2 screws per plate installed 180° into the holes of the plate, parallel to the width-direction of the sheet* 6-inch o.c. at min. 4-inch lap and 6-inch o.c. at three (3), equally spaced, staggered center rows None APP-TA -105.0 Note: *For re-roof or recover construction, field withdrawal resistance testing (Note 11) shall yield minimum 103 lbf. Additional Versa-Fast Fasteners within each Versa-Fast Plate may be utilized to produce minimum withdrawal resistance W-173 Min. 15/32-inch plywood Elastobase, Elastobase P or Elastovent Trufast #12 DP or Trufast #14 HD with Trufast 3” Metal Insulation Plates 6-inch o.c. at min. 4-inch lap and 6-inch o.c. at five (5), equally spaced, staggered center rows None SBS-AA -120.0 W-174 Min. 15/32-inch plywood Elastobase, Elastobase P or Elastovent OMG #12 Standard Roofgrip or OMG #14 Heavy Duty with OMG 3” Round Metal Plates or OMG Flat Bottom Metal Plates 6-inch o.c. at min. 4-inch lap and 6-inch o.c. at five (5), equally spaced, staggered center rows None SBS-AA, SBS-TA or APP-TA -120.0 NEMO|etc. NEMO ETC, LLC Evaluation Report P9290.02.08-R25 for FL1654-R27 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 25: 09/30/2020 ©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 32 of 94 TABLE 1H: WOOD DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER SYSTEM TYPE E-2: NON-INSULATED, MECHANICALLY ATTACHED BASE SHEET (SCREWS & PLATES), BONDED ROOF COVER System No. Deck (Note 1) Base Sheet Roof Cover (Note 15) MDP (psf) Type Fasten (Note 11) Attach Base Ply Cap W-175 Min. 15/32-inch plywood Polyglass Base OMG #12 Standard Roofgrip or OMG #14 Heavy Duty with OMG 3” Round Metal Plates or OMG Flat Bottom Metal Plates 6-inch o.c. at min. 4-inch lap and 6-inch o.c. at five (5), equally spaced, staggered center rows None APP-TA -120.0 ASPHALT-APPLIED OR TORCH-APPLIED BASE PLY: W-176 Min. 19/32-inch plywood Elastobase, Elastobase P, Elastovent, Polyglass G2 Base, CertainTeed Glasbase, Firestone MB Base, JM Perma-Ply 28 or GAFGLAS #75 OMG Flat Bottom Plates (square) with Roofgrip #14, Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with Dekfast #14 or Trufast 3” Metal Insulation Plate with Trufast #14 HD 12-inch o.c. at min. 4-inch lap and 12-inch o.c. at two (2), equally spaced, staggered center rows BP-AA, SBS-AA, SBS- TA, APP-TA SBS-SA, APP-SA, SBS-AA, SBS-TA, APP-TA -52.5 W-177 Min. 19/32-inch plywood Elastobase, Elastobase P or Elastovent OMG Flat Bottom Plates (square) with Roofgrip #12 12-inch o.c. at min. 4-inch lap and 12-inch o.c. at two (2), equally spaced, staggered center rows BP-AA, SBS-AA, SBS- TA, APP-TA SBS-SA, APP-SA, SBS-AA, SBS-TA, APP-TA -60.0 W-178 APA rated, 19/32 CAT, 0.578 in., Exposure 1 OSB or min. 19/32” APA rated plywood Elastobase, Elastobase P or Elastovent Trufast Versa Fasteners (min. ¾” penetration) & Plates; 2 screws per plate installed 180° into the holes of the plate, parallel to the width-direction of the sheet* 12-inch o.c. at min. 4-inch lap and 12-inch o.c. at two (2), equally spaced, staggered center rows BP-AA, SBS-AA, SBS- TA, APP-TA SBS-SA, APP-SA, SBS-AA, SBS-TA, APP-TA -67.5 Note: *For re-roof or recover construction, field withdrawal resistance testing (Note 11) shall yield minimum 199 lbf. Additional Versa-Fast Fasteners within each Versa-Fast Plate may be utilized to produce minimum withdrawal resistance W-179 APA rated, 19/32 CAT, 0.578 in., Exposure 1 OSB or min. 19/32” APA rated plywood Polyglass Base Trufast Versa Fasteners (min. ¾” penetration) & Plates; 2 screws per plate installed 180° into the holes of the plate, parallel to the width-direction of the sheet* 12-inch o.c. at min. 4-inch lap and 12-inch o.c. at two (2), equally spaced, staggered center rows APP-TA APP-TA -67.5 Note: *For re-roof or recover construction, field withdrawal resistance testing (Note 11) shall yield minimum 199 lbf. Additional Versa-Fast Fasteners within each Versa-Fast Plate may be utilized to produce minimum withdrawal resistance W-180 Min. 15/32-inch plywood Polyglass G2 Base, Elastobase, Elastobase P or Elastovent Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with Dekfast #14, OMG 3” Round Metal Plate with OMG HD, OMG Flat Bottom Plate (Accutrac) with Roofgrip #14 or Trufast 3” Metal Insulation Plate with Trufast #14 HD. 10-inch o.c. at min. 4-inch lap and 10-inch o.c. at three (3), equally spaced, staggered center rows BP-AA, SBS-AA, SBS- TA, APP-TA SBS-SA, APP-SA, SBS-AA, SBS-TA, APP-TA -75.0 W-181 Min. 15/32-inch plywood Polyglass Base Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with Dekfast #14, OMG 3” Round Metal Plate with OMG HD, OMG Flat Bottom Plate (Accutrac) with Roofgrip #14 or Trufast 3” Metal Insulation Plate with Trufast #14 HD. 10-inch o.c. at min. 4-inch lap and 10-inch o.c. at three (3), equally spaced, staggered center rows APP-TA APP-TA -75.0 NEMO|etc. NEMO ETC, LLC Evaluation Report P9290.02.08-R25 for FL1654-R27 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 25: 09/30/2020 ©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 33 of 94 TABLE 1H: WOOD DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER SYSTEM TYPE E-2: NON-INSULATED, MECHANICALLY ATTACHED BASE SHEET (SCREWS & PLATES), BONDED ROOF COVER System No. Deck (Note 1) Base Sheet Roof Cover (Note 15) MDP (psf) Type Fasten (Note 11) Attach Base Ply Cap W-182 APA rated, 7/16 CAT, 0.418 in., Exposure 1 OSB or min. 15/32” APA rated plywood Elastobase, Elastobase P or Elastovent Trufast Versa Fasteners (min. ¾” penetration) & Plates; 2 screws per plate installed 180° into the holes of the plate, parallel to the width-direction of the sheet* 9-inch o.c. at min. 2-inch lap and 12-inch o.c. at two (2), equally spaced, staggered center rows BP-AA, SBS-AA, SBS- TA, APP-TA SBS-SA, APP-SA, SBS-AA, SBS-TA, APP-TA -90.0 Note: *For re-roof or recover construction, field withdrawal resistance testing (Note 11) shall yield minimum 159 lbf. Additional Versa-Fast Fasteners within each Versa-Fast Plate may be utilized to produce minimum withdrawal resistance W-183 APA rated, 7/16 CAT, 0.418 in., Exposure 1 OSB or min. 15/32” APA rated plywood Polyglass Base Trufast Versa Fasteners (min. ¾” penetration) & Plates; 2 screws per plate installed 180° into the holes of the plate, parallel to the width-direction of the sheet* 9-inch o.c. at min. 2-inch lap and 12-inch o.c. at two (2), equally spaced, staggered center rows APP-TA APP-TA -90.0 Note: *For re-roof or recover construction, field withdrawal resistance testing (Note 11) shall yield minimum 159 lbf. Additional Versa-Fast Fasteners within each Versa-Fast Plate may be utilized to produce minimum withdrawal resistance W-184 Min. 15/32-inch plywood Polyglass G2 Base, Elastobase, Elastobase P or Elastovent Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with Dekfast #14, OMG 3” Round Metal Plate with OMG HD, OMG Flat Bottom Plate (Accutrac) with Roofgrip #14 or Trufast 3” Metal Insulation Plate with Trufast #14 HD. 9-inch o.c. at min. 4-inch lap and 9-inch o.c. at four (4), equally spaced, staggered center rows BP-AA, SBS-AA, SBS- TA, APP-TA SBS-SA, APP-SA, SBS-AA, SBS-TA, APP-TA -90.0 W-185 Min. 15/32-inch plywood Polyglass Base Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with Dekfast #14, OMG 3” Round Metal Plate with OMG HD, OMG Flat Bottom Plate (Accutrac) with Roofgrip #14 or Trufast 3” Metal Insulation Plate with Trufast #14 HD. 9-inch o.c. at min. 4-inch lap and 9-inch o.c. at four (4), equally spaced, staggered center rows APP-TA APP-TA -90.0 W-186 Min. 15/32-inch plywood Elastobase, Elastobase P or Elastovent Trufast #12 DP or Trufast #14 HD with Trufast 3” Metal Insulation Plates 6-inch o.c. at min. 4-inch lap and 6-inch o.c. at three (3), equally spaced, staggered center rows BP-AA or SBS-AA SBS-AA -90.0 W-187 Min. 15/32-inch plywood Elastobase, Elastobase P or Elastovent OMG #12 Standard Roofgrip or OMG #14 Heavy Duty (min. 1-5/8-inch long) with OMG 3” Round Metal Plates or OMG Flat Bottom Metal Plates 6-inch o.c. at min. 4-inch lap and 6-inch o.c. at three (3), equally spaced, staggered center rows BP-AA, SBS-AA, SBS- TA, APP-TA SBS-SA, APP-SA, SBS-AA, SBS-TA, APP-TA -90.0 W-188 Min. 15/32-inch plywood Polyglass Base OMG #12 Standard Roofgrip or OMG #14 Heavy Duty with OMG 3” Round Metal Plates or OMG Flat Bottom Metal Plates 6-inch o.c. at min. 4-inch lap and 6-inch o.c. at three (3), equally spaced, staggered center rows APP-TA APP-TA -90.0 W-189 APA rated, 7/16 CAT, 0.418 in., Exposure 1 OSB or min. 15/32” APA rated plywood Elastobase, Elastobase P or Elastovent Trufast Versa Fasteners (min. ¾” penetration) & Plates; 2 screws per plate installed 180° into the holes of the plate, parallel to the width-direction of the sheet* 6-inch o.c. at min. 4-inch lap and 6-inch o.c. at three (3), equally spaced, staggered center rows BP-AA, SBS-AA, SBS- TA, APP-TA SBS-SA, APP-SA, SBS-AA, SBS-TA, APP-TA -105.0 Note: *For re-roof or recover construction, field withdrawal resistance testing (Note 11) shall yield minimum 103 lbf. Additional Versa-Fast Fasteners within each Versa-Fast Plate may be utilized to produce minimum withdrawal resistance NEMO|etc. NEMO ETC, LLC Evaluation Report P9290.02.08-R25 for FL1654-R27 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 25: 09/30/2020 ©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 34 of 94 TABLE 1H: WOOD DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER SYSTEM TYPE E-2: NON-INSULATED, MECHANICALLY ATTACHED BASE SHEET (SCREWS & PLATES), BONDED ROOF COVER System No. Deck (Note 1) Base Sheet Roof Cover (Note 15) MDP (psf) Type Fasten (Note 11) Attach Base Ply Cap W-190 APA rated, 7/16 CAT, 0.418 in., Exposure 1 OSB or min. 15/32” APA rated plywood Polyglass Base Trufast Versa Fasteners (min. ¾” penetration) & Plates; 2 screws per plate installed 180° into the holes of the plate, parallel to the width-direction of the sheet* 6-inch o.c. at min. 4-inch lap and 6-inch o.c. at three (3), equally spaced, staggered center rows APP-TA APP-TA -105.0 Note: *For re-roof or recover construction, field withdrawal resistance testing (Note 11) shall yield minimum 103 lbf. Additional Versa-Fast Fasteners within each Versa-Fast Plate may be utilized to produce minimum withdrawal resistance W-191 Min. 15/32-inch plywood Elastobase, Elastobase P or Elastovent Trufast #12 DP or Trufast #14 HD with Trufast 3” Metal Insulation Plates 6-inch o.c. at min. 4-inch lap and 6-inch o.c. at five (5), equally spaced, staggered center rows BP-AA or SBS-AA SBS-AA -120.0 W-192 Min. 15/32-inch plywood Elastobase, Elastobase P or Elastovent OMG #12 Standard Roofgrip or OMG #14 Heavy Duty with OMG 3” Round Metal Plates or OMG Flat Bottom Metal Plates 6-inch o.c. at min. 4-inch lap and 6-inch o.c. at five (5), equally spaced, staggered center rows BP-AA, SBS-AA, SBS- TA, APP-TA SBS-SA, APP-SA, SBS-AA, SBS-TA, APP-TA -120.0 W-193 Min. 15/32-inch plywood Polyglass Base OMG #12 Standard Roofgrip or OMG #14 Heavy Duty with OMG 3” Round Metal Plates or OMG Flat Bottom Metal Plates 6-inch o.c. at min. 4-inch lap and 6-inch o.c. at five (5), equally spaced, staggered center rows APP-TA APP-TA -120.0 W-194 APA rated, 19/32 CAT, 0.578 in., Exposure 1 OSB or min. 19/32” APA rated plywood Elastobase (sanded top) or Elastovent Trufast Versa Fasteners (min. ¾” penetration) & Plates; 1 screws per plate in center hole* 9-inch o.c. at min. 4-inch lap and 9-inch o.c. at four (4), equally spaced center rows BP-AA, SBS-AA, SBS- TA, APP-TA SBS-AA, SBS-TA, APP-TA -127.5 Note: *For re-roof or recover construction, field withdrawal resistance testing (Note 11) shall yield minimum 141 lbf. Additional Versa-Fast Fasteners within each Versa-Fast Plate may be utilized to produce minimum withdrawal resistance W-195 APA rated, 19/32 CAT, 0.578 in., Exposure 1 OSB or min. 19/32” APA rated plywood Elastobase (poly-film top) Trufast Versa Fasteners (min. ¾” penetration) & Plates; 1 screws per plate in center hole* 9-inch o.c. at min. 4-inch lap and 9-inch o.c. at four (4), equally spaced center rows SBS-TA SBS-TA, APP-TA -127.5 Note: *For re-roof or recover construction, field withdrawal resistance testing (Note 11) shall yield minimum 141 lbf. Additional Versa-Fast Fasteners within each Versa-Fast Plate may be utilized to produce minimum withdrawal resistance W-196 APA rated, 19/32 CAT, 0.578 in., Exposure 1 OSB or min. 19/32” APA rated plywood Polyglass Base Trufast Versa Fasteners (min. ¾” penetration) & Plates; 1 screws per plate in center hole* 9-inch o.c. at min. 4-inch lap and 9-inch o.c. at four (4), equally spaced center rows APP-TA APP-TA -127.5 Note: *For re-roof or recover construction, field withdrawal resistance testing (Note 11) shall yield minimum 141 lbf. Additional Versa-Fast Fasteners within each Versa-Fast Plate may be utilized to produce minimum withdrawal resistance SELF-ADHERING BASE PLY: NEMO|etc. NEMO ETC, LLC Evaluation Report P9290.02.08-R25 for FL1654-R27 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 25: 09/30/2020 ©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 35 of 94 TABLE 1H: WOOD DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER SYSTEM TYPE E-2: NON-INSULATED, MECHANICALLY ATTACHED BASE SHEET (SCREWS & PLATES), BONDED ROOF COVER System No. Deck (Note 1) Base Sheet Roof Cover (Note 15) MDP (psf) Type Fasten (Note 11) Attach Base Ply Cap W-197 Min. 19/32-inch plywood Elastobase, Elastobase P (poly-film top) Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with Dekfast #14 or Trufast 3” Metal Insulation Plate with Trufast #14 HD 12-inch o.c. at min. 4-inch lap and 12-inch o.c. at two (2), equally spaced, staggered center rows SBS-SA SBS-SA, APP-SA, SBS-TA, APP-TA -52.5* W-198 Min. 19/32-inch plywood Elastobase, Elastobase P (poly-film top) OMG Flat Bottom Plates (square) with Roofgrip #12 12-inch o.c. at min. 4-inch lap and 12-inch o.c. at two (2), equally spaced, staggered center rows SBS-SA SBS-SA, APP-SA, SBS-TA, APP-TA -60.0* W-199 APA rated, 19/32 CAT, 0.578 in., Exposure 1 OSB or min. 19/32” APA rated plywood Elastobase, Elastobase P (poly-film top) Trufast Versa Fasteners (min. ¾” penetration) & Plates; 2 screws per plate installed 180° into the holes of the plate, parallel to the width-direction of the sheet* 12-inch o.c. at min. 4-inch lap and 12-inch o.c. at two (2), equally spaced, staggered center rows SBS-SA SBS-SA, APP-SA, SBS-TA, APP-TA -67.5 Note: *For re-roof or recover construction, field withdrawal resistance testing (Note 11) shall yield minimum 199 lbf. Additional Versa-Fast Fasteners within each Versa-Fast Plate may be utilized to produce minimum withdrawal resistance W-200 APA rated, 19/32 CAT, 0.578 in., Exposure 1 OSB or min. 19/32” APA rated plywood Elastobase (poly-film top) Trufast Versa Fasteners (min. ¾” penetration) & Plates; 1 screws per plate in center hole* Note: Versa-Fast Plates shall be primed with PG100 or ASTM D41 primer. 9-inch o.c. at min. 4-inch lap and 9-inch o.c. at four (4), equally spaced center rows SBS-SA SBS-SA, APP-SA, SBS-TA, APP-TA -127.5 Note: *For re-roof or recover construction, field withdrawal resistance testing (Note 11) shall yield minimum 141 lbf. Additional Versa-Fast Fasteners within each Versa-Fast Plate may be utilized to produce minimum withdrawal resistance HYBRID SYSTEMS WITH SELF-ADHERING APP BASE PLY: W-201 Min. 19/32-inch plywood Elastobase, Elastobase P (poly-film top) Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with Dekfast #14 or Trufast 3” Metal Insulation Plate with Trufast #14 HD 12-inch o.c. at min. 4-inch lap and 12-inch o.c. at two (2), equally spaced, staggered center rows APP-SA-H APP-TA -52.5* W-202 Min. 19/32-inch plywood Elastobase, Elastobase P (poly-film top) OMG Flat Bottom Plates (square) with Roofgrip #12 12-inch o.c. at min. 4-inch lap and 12-inch o.c. at two (2), equally spaced, staggered center rows APP-SA-H APP-TA -60.0* W-203 APA rated, 19/32 CAT, 0.578 in., Exposure 1 OSB or min. 19/32” APA rated plywood Elastobase, Elastobase P (poly-film top) Trufast Versa Fasteners (min. ¾” penetration) & Plates; 2 screws per plate installed 180° into the holes of the plate, parallel to the width-direction of the sheet* 12-inch o.c. at min. 4-inch lap and 12-inch o.c. at two (2), equally spaced, staggered center rows APP-SA-H APP-TA -67.5 Note: *For re-roof or recover construction, field withdrawal resistance testing (Note 11) shall yield minimum 199 lbf. Additional Versa-Fast Fasteners within each Versa-Fast Plate may be utilized to produce minimum withdrawal resistance HYBRID SYSTEMS WITH SELF-ADHERING SBS BASE PLY: NEMO|etc. NEMO ETC, LLC Evaluation Report P9290.02.08-R25 for FL1654-R27 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 25: 09/30/2020 ©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 36 of 94 TABLE 1H: WOOD DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER SYSTEM TYPE E-2: NON-INSULATED, MECHANICALLY ATTACHED BASE SHEET (SCREWS & PLATES), BONDED ROOF COVER System No. Deck (Note 1) Base Sheet Roof Cover (Note 15) MDP (psf) Type Fasten (Note 11) Attach Base Ply Cap W-204 Min. 19/32-inch plywood Elastobase, Elastobase P (poly-film top) Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with Dekfast #14 or Trufast 3” Metal Insulation Plate with Trufast #14 HD 12-inch o.c. at min. 4-inch lap and 12-inch o.c. at two (2), equally spaced, staggered center rows SBS-SA-H SBS-TA -52.5* W-205 Min. 19/32-inch plywood Elastobase, Elastobase P (poly-film top) OMG Flat Bottom Plates (square) with Roofgrip #12 12-inch o.c. at min. 4-inch lap and 12-inch o.c. at two (2), equally spaced, staggered center rows SBS-SA-H SBS-TA -60.0* W-206 APA rated, 19/32 CAT, 0.578 in., Exposure 1 OSB or min. 19/32” APA rated plywood Elastobase, Elastobase P (poly-film top) Trufast Versa Fasteners (min. ¾” penetration) & Plates; 2 screws per plate installed 180° into the holes of the plate, parallel to the width-direction of the sheet* 12-inch o.c. at min. 4-inch lap and 12-inch o.c. at two (2), equally spaced, staggered center rows SBS-SA-H SBS-TA -67.5 Note: *For re-roof or recover construction, field withdrawal resistance testing (Note 11) shall yield minimum 199 lbf. Additional Versa-Fast Fasteners within each Versa-Fast Plate may be utilized to produce minimum withdrawal resistance W-207 APA rated, 19/32 CAT, 0.578 in., Exposure 1 OSB or min. 19/32” APA rated plywood Elastobase (poly-film top) Trufast Versa Fasteners (min. ¾” penetration) & Plates; 1 screws per plate in center hole* Note: Versa-Fast Plates shall be primed with PG100 or ASTM D41 primer. 9-inch o.c. at min. 4-inch lap and 9-inch o.c. at four (4), equally spaced center rows SBS-SA-H SBS-TA -127.5 Note: *For re-roof or recover construction, field withdrawal resistance testing (Note 11) shall yield minimum 141 lbf. Additional Versa-Fast Fasteners within each Versa-Fast Plate may be utilized to produce minimum withdrawal resistance NEMO|etc. NEMO ETC, LLC Evaluation Report P9290.02.08-R25 for FL1654-R27 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 25: 09/30/2020 ©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 37 of 94 TABLE 1I: WOOD DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF) SYSTEM TYPE F: NON-INSULATED, BONDED ROOF COVER System No. Deck (Note 1) Primer Roof Cover (Note 15) MDP (psf) Joint Treatment Base Ply Ply Cap Ply SELF-ADHERING BASE PLY: W-208 APA rated, 7/16 CAT, 0.418 in., Exposure 1 OSB None OSB joints are covered with 4-inch wide strips of Elastoflex SA V, rolled into place to create continuous bond. Elastoflex SA V Plus or Elastoflex SA V Plus FR (Optional) SBS-SA, SBS- TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -52.5 W-209 Min. 15/32- inch plywood None None SBS-SA (Optional) SBS-SA, SBS- TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -90.0 W-210 Min. 15/32- inch plywood PG100 None SBS-SA (Optional) SBS-SA, SBS- TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -97.5 W-211 Min. 15/32- inch plywood (Optional) PG100 Plywood joints are covered with 4-inch wide strips of Elastoflex SA V Plus, rolled into place to create continuous bond. Elastoflex SA V or Elastoflex SA V FR (Optional) SBS-SA, SBS- TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -97.5 W-212 Min. 15/32- inch plywood POLYBRITE 745 or WB3000 None SBS-SA (Optional) SBS-SA, SBS- TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -105.0 W-213 Min. 15/32- inch plywood (Optional) PG100 Plywood joints are covered with 4-inch wide strips of Elastoflex SA V Plus, rolled into place to create continuous bond. Elastoflex SA V Plus or Elastoflex SA V Plus FR (Optional) SBS-SA, SBS- TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -135.0 HYBRID SYSTEMS WITH SELF-ADHERING APP BASE PLY: W-214 Min. 15/32- inch plywood (Optional) PG100 None APP-SA-H (Optional) APP-TA APP-TA -90.0 W-215 Min. 15/32- inch plywood (Optional) PG100 Plywood joints are covered with 4-inch wide strips of Elastoflex SA V Plus, rolled into place to create continuous bond. APP-SA-H (Optional) APP-TA APP-TA -135.0 HYBRID SYSTEMS WITH SELF-ADHERING SBS BASE PLY: W-216 Min. 15/32- inch plywood None None SBS-SA-H (Optional) SBS-TA SBS-TA -90.0 W-217 Min. 15/32- inch plywood PG100 None SBS-SA-H (Optional) SBS-TA SBS-TA -97.5 W-218 Min. 15/32- inch plywood (Optional) PG100 Plywood joints are covered with 4-inch wide strips of Elastoflex SA V Plus, rolled into place to create continuous bond. SBS-SA-H (Optional) SBS-TA SBS-TA -97.5 W-219 Min. 15/32- inch plywood POLYBRITE 745 or WB3000 None SBS-SA-H (Optional) SBS-TA SBS-TA -105.0 NEMO|etc. NEMO ETC, LLC Evaluation Report P9290.02.08-R25 for FL1654-R27 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 25: 09/30/2020 ©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 38 of 94 TABLE 2A: STEEL OR STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER SYSTEM TYPE B-1: MECHANICALLY ATTACHED BASE INSULATION, BONDED TOP INSULATION, BONDED ROOF COVER System No. Deck (Note 1) Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP (psf) Type Fasten (Note 11) Attach Type Attach (Notes 6,7,8) Base Ply Ply Cap Ply ASPHALT- OR TORCH-APPLIED BASE PLY: S-1. Min. 22 ga., type B, Grade 33 steel or min. 2,500 psi structural concrete Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3, H- Shield or Polytherm Dekfast Hex (aka, Dekfast PLT-H-2- 7/8) with Dekfast #14, Trufast 3” Metal Insulation Plate with Trufast #14 HD or OMG 3-inch Galv Plate with OMD HD 1 per 2.0 ft2 Min. 0.75-inch Fesco Board (homogeneous) or min. 0.5-inch Structodek High Density Fiberboard Roof Insulation Hot asphalt (Optional if using AA Ply) BP-AA, SBS-AA (Optional if using AA Base) BP-AA, SBS-AA, SBS-TA or APP-TA SBS-AA, SBS-TA, APP-TA -45.0* S-2. Min. 22 ga., type B, Grade 33 steel or min. 2,500 psi structural concrete Min. 2-inch Polytherm, ACFoam II, ENRGY 3, H- Shield or Polytherm Dekfast Hex (aka, Dekfast PLT-H-2- 7/8) with Dekfast #14, Trufast 3” Metal Insulation Plate with Trufast #14 HD or OMG 3-inch Galv Plate with OMD HD 1 per 4.0 ft2 Min. 0.75-inch Fesco Board (homogeneous) or min. 0.5-inch Structodek High Density Fiberboard Roof Insulation Hot asphalt (Optional if using AA Ply) BP-AA, SBS-AA (Optional if using AA Base) BP-AA, SBS-AA, SBS-TA or APP-TA SBS-AA, SBS-TA, APP-TA -45.0* S-3. Min. 22 ga., type B, Grade 33 steel or min. 2,500 psi structural concrete Min. 1.5-inch ENRGY 3, H-Shield or Polytherm Dekfast Hex (aka, Dekfast PLT-H-2- 7/8) with Dekfast #14 or Trufast 3” Metal Insulation Plate with Trufast #14 HD 1 per 1.3 ft2 Min. 0.75-inch Fesco Board (homogeneous) or min. 0.5-inch Structodek High Density Fiberboard Roof Insulation Hot asphalt (Optional if using AA Ply) BP-AA, SBS-AA (Optional if using AA Base) BP-AA, SBS-AA, SBS-TA or APP-TA SBS-AA, SBS-TA, APP-TA -90.0 S-4. Min. 22 ga., type B, Grade 33 steel or min. 2,500 psi structural concrete Min. 1.5-inch ENRGY 3, H-Shield or Polytherm Dekfast Hex (aka, Dekfast PLT-H-2- 7/8) with Dekfast #14 or Trufast 3” Metal Insulation Plate with Trufast #14 HD 1 per 1.3 ft2 Min. 0.75-inch Fesco Board (homogeneous) or min. 0.5-inch Structodek High Density Fiberboard Roof Insulation Hot asphalt BP-AA, SBS- AA (Top surface primed with PG100 primer) SBS-SA, SBS-TA or APP-TA SBS-SA, APP-SA, SBS-TA or APP-TA -90.0 S-5. Min. 22 ga., type B, Grade 40 steel or min. 2,500 psi structural concrete Min. 2-inch Polytherm, ACFoam II, ENRGY 3, EnergyGuard Polyiso Insulation, Polytherm H, H-Shield or Multi-Max FA3 Dekfast Hex (aka, Dekfast PLT-H-2- 7/8) with Dekfast #14, OMG 3” Galvalume Ribbons Plates with OMG #14 Roofgrip or Trufast 3” Metal Insulation Plate with Trufast #14 HD 1 per 4.0 ft2 Min. 0.25-inch DensDeck Prime, DEXcell FA Glass Mat Roof Board or SECUROCK Gypsum- Fiber Roof Board D-IS SBS-AA, SBS-TA, APP-TA (Optional) SBS-AA, SBS-TA, APP-TA SBS-AA, SBS-TA, APP-TA -30.0* S-6. Min. 22 ga., type B, Grade 40 steel or min. 2,500 psi structural concrete Min. 2-inch Polytherm, ACFoam II, ENRGY 3, EnergyGuard Polyiso Insulation, Polytherm H, H-Shield or Multi-Max FA3 Dekfast Hex (aka, Dekfast PLT-H-2- 7/8) with Dekfast #14, OMG 3” Galvalume Ribbons Plates with OMG #14 Roofgrip or Trufast 3” Metal Insulation Plate with Trufast #14 HD 1 per 1.6 ft2 Min. 0.25-inch DensDeck Prime, DEXcell FA Glass Mat Roof Board or SECUROCK Gypsum- Fiber Roof Board D-IS SBS-AA, SBS-TA, APP-TA (Optional) SBS-AA, SBS-TA, APP-TA SBS-AA, SBS-TA, APP-TA -45.0 NEMO|etc. NEMO ETC, LLC Evaluation Report P9290.02.08-R25 for FL1654-R27 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 25: 09/30/2020 ©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 39 of 94 TABLE 2A: STEEL OR STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER SYSTEM TYPE B-1: MECHANICALLY ATTACHED BASE INSULATION, BONDED TOP INSULATION, BONDED ROOF COVER System No. Deck (Note 1) Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP (psf) Type Fasten (Note 11) Attach Type Attach (Notes 6,7,8) Base Ply Ply Cap Ply S-7. Min. 22 ga., type B, Grade 40 steel or min. 2,500 psi structural concrete Min. 2-inch Polytherm, ACFoam II, ENRGY 3, EnergyGuard Polyiso Insulation, Polytherm H, H-Shield or Multi-Max FA3 Dekfast Hex (aka, Dekfast PLT-H-2- 7/8) with Dekfast #14, OMG 3” Galvalume Ribbons Plates with OMG #14 Roofgrip or Trufast 3” Metal Insulation Plate with Trufast #14 HD 1 per 4.0 ft2 Min. 0.25-inch DensDeck Prime, DEXcell FA Glass Mat Roof Board, SECUROCK Gypsum- Fiber Roof Board or SECUROCK Glass-Mat Roof Board, min. 7/16-inch DEXcell Cement Roof Board or min. 0.5-inch SECUROCK Cement Roof Board M-OSFA or M-PG1 SBS-AA, SBS-TA, APP-TA (Optional) SBS-AA, SBS-TA, APP-TA SBS-AA, SBS-TA, APP-TA -30.0* S-8. Min. 22 ga., type B, Grade 40 steel or min. 2,500 psi structural concrete Min. 2-inch Polytherm, ACFoam II, ENRGY 3, EnergyGuard Polyiso Insulation, Polytherm H, H-Shield or Multi-Max FA3 Dekfast Hex (aka, Dekfast PLT-H-2- 7/8) with Dekfast #14, OMG 3” Galvalume Ribbons Plates with OMG #14 Roofgrip or Trufast 3” Metal Insulation Plate with Trufast #14 HD 1 per 1.6 ft2 Min. 0.25-inch DensDeck Prime, DEXcell FA Glass Mat Roof Board, SECUROCK Gypsum- Fiber Roof Board or SECUROCK Glass-Mat Roof Board, min. 7/16-inch DEXcell Cement Roof Board or min. 0.5-inch SECUROCK Cement Roof Board M-OSFA or M-PG1 SBS-AA, SBS-TA, APP-TA (Optional) SBS-AA, SBS-TA, APP-TA SBS-AA, SBS-TA, APP-TA -45.0 S-9. Min. 22 ga., type B, Grade 40 steel or min. 2,500 psi structural concrete Min. 2-inch Polytherm, ACFoam II, ENRGY 3, EnergyGuard Polyiso Insulation, Polytherm H, H-Shield or Multi-Max FA3 Dekfast Hex (aka, Dekfast PLT-H-2- 7/8) with Dekfast #14, OMG 3” Galvalume Ribbons Plates with OMG #14 Roofgrip or Trufast 3” Metal Insulation Plate with Trufast #14 HD 1 per 4.0 ft2 Min. 0.25-inch DensDeck Prime, DEXcell FA Glass Matg Roof Board or SECUROCK Gypsum- Fiber Roof Board OB500 SBS-AA, SBS-TA, APP-TA (Optional) SBS-AA, SBS-TA, APP-TA SBS-AA, SBS-TA, APP-TA -30.0* S-10. Min. 22 ga., type B, Grade 40 steel or min. 2,500 psi structural concrete Min. 2-inch Polytherm, ACFoam II, ENRGY 3, EnergyGuard Polyiso Insulation, Polytherm H, H-Shield or Multi-Max FA3 Dekfast Hex (aka, Dekfast PLT-H-2- 7/8) with Dekfast #14, OMG 3” Galvalume Ribbons Plates with OMG #14 Roofgrip or Trufast 3” Metal Insulation Plate with Trufast #14 HD 1 per 1.6 ft2 Min. 0.25-inch DensDeck Prime, DEXcell FA Glass Mat Roof Board or SECUROCK Gypsum- Fiber Roof Board OB500 SBS-AA, SBS-TA, APP-TA (Optional) SBS-AA, SBS-TA, APP-TA SBS-AA, SBS-TA, APP-TA -45.0 S-11. Min. 22 ga., type B, Grade 40 steel or min. 2,500 psi structural concrete Min. 2-inch Polytherm, ACFoam II, ENRGY 3, EnergyGuard Polyiso Insulation, Polytherm H, H-Shield or Multi-Max FA3 Dekfast Hex (aka, Dekfast PLT-H-2- 7/8) with Dekfast #14, OMG 3” Galvalume Ribbons Plates with OMG #14 Roofgrip or Trufast 3” Metal Insulation Plate with Trufast #14 HD 1 per 4.0 ft2 Min. 0.25-inch DensDeck Prime or SECUROCK Gypsum-Fiber Roof Board CR-20 SBS-AA, SBS-TA, APP-TA (Optional) SBS-AA, SBS-TA, APP-TA SBS-AA, SBS-TA, APP-TA -30.0* NEMO|etc. NEMO ETC, LLC Evaluation Report P9290.02.08-R25 for FL1654-R27 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 25: 09/30/2020 ©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 40 of 94 TABLE 2A: STEEL OR STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER SYSTEM TYPE B-1: MECHANICALLY ATTACHED BASE INSULATION, BONDED TOP INSULATION, BONDED ROOF COVER System No. Deck (Note 1) Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP (psf) Type Fasten (Note 11) Attach Type Attach (Notes 6,7,8) Base Ply Ply Cap Ply S-12. Min. 22 ga., type B, Grade 40 steel or min. 2,500 psi structural concrete Min. 2-inch Polytherm, ACFoam II, ENRGY 3, EnergyGuard Polyiso Insulation, Polytherm H, H-Shield or Multi-Max FA3 Dekfast Hex (aka, Dekfast PLT-H-2- 7/8) with Dekfast #14, OMG 3” Galvalume Ribbons Plates with OMG #14 Roofgrip or Trufast 3” Metal Insulation Plate with Trufast #14 HD 1 per 1.6 ft2 Min. 0.25-inch DensDeck Prime or SECUROCK Gypsum-Fiber Roof Board CR-20 SBS-AA, SBS-TA, APP-TA (Optional) SBS-AA, SBS-TA, APP-TA SBS-AA, SBS-TA, APP-TA -45.0 SELF-ADHERING BASE PLY: S-13. Min. 22 ga., type B, Grade 40 steel or min. 2,500 psi structural concrete Min. 2-inch Polytherm, ACFoam II, ENRGY 3, EnergyGuard Polyiso Insulation, Polytherm H, H-Shield or Multi-Max FA3 Dekfast Hex (aka, Dekfast PLT-H-2- 7/8) with Dekfast #14, OMG 3” Galvalume Ribbons Plates with OMG #14 Roofgrip or Trufast 3” Metal Insulation Plate with Trufast #14 HD 1 per 4.0 ft2 Min. 0.25-inch DensDeck Prime or SECUROCK Gypsum-Fiber Roof Board PRIMER: POLYBRITE 745 or WB3000 D-IS SBS-SA None SBS-CA1, SBS-CA2, APP-CA1 -30.0* S-14. Min. 22 ga., type B, Grade 40 steel or min. 2,500 psi structural concrete Min. 2-inch Polytherm, ACFoam II, ENRGY 3, EnergyGuard Polyiso Insulation, Polytherm H, H-Shield or Multi-Max FA3 Dekfast Hex (aka, Dekfast PLT-H-2- 7/8) with Dekfast #14, OMG 3” Galvalume Ribbons Plates with OMG #14 Roofgrip or Trufast 3” Metal Insulation Plate with Trufast #14 HD 1 per 1.6 ft2 Min. 0.25-inch DensDeck Prime or SECUROCK Gypsum-Fiber Roof Board PRIMER: POLYBRITE 745 or WB3000 D-IS SBS-SA None SBS-CA1, SBS-CA2, APP-CA1 -45.0 S-15. Min. 22 ga., type B, Grade 40 steel or min. 2,500 psi structural concrete Min. 2-inch Polytherm, ACFoam II, ENRGY 3, EnergyGuard Polyiso Insulation, Polytherm H, H-Shield or Multi-Max FA3 Dekfast Hex (aka, Dekfast PLT-H-2- 7/8) with Dekfast #14, OMG 3” Galvalume Ribbons Plates with OMG #14 Roofgrip or Trufast 3” Metal Insulation Plate with Trufast #14 HD 1 per 4.0 ft2 Min. 0.25-inch DensDeck, DensDeck Prime, SECUROCK Gypsum-Fiber Roof Board or SECUROCK Glass-Mat Roof Board, min. 7/16-inch DEXcell Cement Roof Board or min. 0.5- inch SECUROCK Cement Roof Board PRIMER: POLYBRITE 745 or WB3000 M-OSFA or M-PG1 SBS-SA None SBS-CA1, SBS-CA2, APP-CA1 -30.0* NEMO|etc. NEMO ETC, LLC Evaluation Report P9290.02.08-R25 for FL1654-R27 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 25: 09/30/2020 ©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 41 of 94 TABLE 2A: STEEL OR STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER SYSTEM TYPE B-1: MECHANICALLY ATTACHED BASE INSULATION, BONDED TOP INSULATION, BONDED ROOF COVER System No. Deck (Note 1) Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP (psf) Type Fasten (Note 11) Attach Type Attach (Notes 6,7,8) Base Ply Ply Cap Ply S-16. Min. 22 ga., type B, Grade 40 steel or min. 2,500 psi structural concrete Min. 2-inch Polytherm, ACFoam II, ENRGY 3, EnergyGuard Polyiso Insulation, Polytherm H, H-Shield or Multi-Max FA3 Dekfast Hex (aka, Dekfast PLT-H-2- 7/8) with Dekfast #14, OMG 3” Galvalume Ribbons Plates with OMG #14 Roofgrip or Trufast 3” Metal Insulation Plate with Trufast #14 HD 1 per 1.6 ft2 Min. 0.25-inch DensDeck, DensDeck Prime, SECUROCK Gypsum-Fiber Roof Board or SECUROCK Glass-Mat Roof Board, min. 7/16-inch DEXcell Cement Roof Board or min. 0.5- inch SECUROCK Cement Roof Board PRIMER: POLYBRITE 745 or WB3000 M-OSFA or M-PG1 SBS-SA None SBS-CA1, SBS-CA2, APP-CA1 -45.0 S-17. Min. 22 ga., type B, Grade 40 steel or min. 2,500 psi structural concrete Min. 2-inch Polytherm, ACFoam II, ENRGY 3, EnergyGuard Polyiso Insulation, Polytherm H, H-Shield or Multi-Max FA3 Dekfast Hex (aka, Dekfast PLT-H-2- 7/8) with Dekfast #14, OMG 3” Galvalume Ribbons Plates with OMG #14 Roofgrip or Trufast 3” Metal Insulation Plate with Trufast #14 HD 1 per 4.0 ft2 Min. 0.25-inch DensDeck Prime or SECUROCK Gypsum-Fiber Roof Board PRIMER: POLYBRITE 745 or WB3000 OB500 SBS-SA None SBS-CA1, SBS-CA2, APP-CA1 -30.0* S-18. Min. 22 ga., type B, Grade 40 steel or min. 2,500 psi structural concrete Min. 2-inch Polytherm, ACFoam II, ENRGY 3, EnergyGuard Polyiso Insulation, Polytherm H, H-Shield or Multi-Max FA3 Dekfast Hex (aka, Dekfast PLT-H-2- 7/8) with Dekfast #14, OMG 3” Galvalume Ribbons Plates with OMG #14 Roofgrip or Trufast 3” Metal Insulation Plate with Trufast #14 HD 1 per 1.6 ft2 Min. 0.25-inch DensDeck Prime or SECUROCK Gypsum-Fiber Roof Board PRIMER: POLYBRITE 745 or WB3000 OB500 SBS-SA None SBS-CA1, SBS-CA2, APP-CA1 -45.0 S-19. Min. 22 ga., type B, Grade 40 steel or min. 2,500 psi structural concrete Min. 2-inch Polytherm, ACFoam II, ENRGY 3, EnergyGuard Polyiso Insulation, Polytherm H, H-Shield or Multi-Max FA3 Dekfast Hex (aka, Dekfast PLT-H-2- 7/8) with Dekfast #14, OMG 3” Galvalume Ribbons Plates with OMG #14 Roofgrip or Trufast 3” Metal Insulation Plate with Trufast #14 HD 1 per 4.0 ft2 Min. 0.25-inch DensDeck Prime or SECUROCK Gypsum-Fiber Roof Board PRIMER: POLYBRITE 745 or WB3000 CR-20 SBS-SA None SBS-CA1, SBS-CA2, APP-CA1 -30.0* S-20. Min. 22 ga., type B, Grade 40 steel or min. 2,500 psi structural concrete Min. 2-inch Polytherm, ACFoam II, ENRGY 3, EnergyGuard Polyiso Insulation, Polytherm H, H-Shield or Multi-Max FA3 Dekfast Hex (aka, Dekfast PLT-H-2- 7/8) with Dekfast #14, OMG 3” Galvalume Ribbons Plates with OMG #14 Roofgrip or Trufast 3” Metal Insulation Plate with Trufast #14 HD 1 per 1.6 ft2 Min. 0.25-inch DensDeck Prime or SECUROCK Gypsum-Fiber Roof Board PRIMER: POLYBRITE 745 or WB3000 CR-20 SBS-SA None SBS-CA1, SBS-CA2, APP-CA1 -45.0 COLD-APPLIED BASE PLY: NEMO|etc. NEMO ETC, LLC Evaluation Report P9290.02.08-R25 for FL1654-R27 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 25: 09/30/2020 ©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 42 of 94 TABLE 2A: STEEL OR STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER SYSTEM TYPE B-1: MECHANICALLY ATTACHED BASE INSULATION, BONDED TOP INSULATION, BONDED ROOF COVER System No. Deck (Note 1) Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP (psf) Type Fasten (Note 11) Attach Type Attach (Notes 6,7,8) Base Ply Ply Cap Ply S-21. Min. 22 ga., type B, Grade 40 steel or min. 2,500 psi structural concrete Min. 2-inch Polytherm, ACFoam II, ENRGY 3, EnergyGuard Polyiso Insulation, Polytherm H, H-Shield or Multi-Max FA3 Dekfast Hex (aka, Dekfast PLT-H-2- 7/8) with Dekfast #14, OMG 3” Galvalume Ribbons Plates with OMG #14 Roofgrip or Trufast 3” Metal Insulation Plate with Trufast #14 HD 1 per 4.0 ft2 Min. 0.25-inch DensDeck Prime, DEXcell FA Glass Mat Roof Board or SECUROCK Gypsum- Fiber Roof Board D-IS SBS-CA1, SBS-CA2 (Optional) SBS- CA1, SBS-CA2 SBS-CA1, SBS-CA2, APP-CA1 -30.0* S-22. Min. 22 ga., type B, Grade 40 steel or min. 2,500 psi structural concrete Min. 2-inch Polytherm, ACFoam II, ENRGY 3, EnergyGuard Polyiso Insulation, Polytherm H, H-Shield or Multi-Max FA3 Dekfast Hex (aka, Dekfast PLT-H-2- 7/8) with Dekfast #14, OMG 3” Galvalume Ribbons Plates with OMG #14 Roofgrip or Trufast 3” Metal Insulation Plate with Trufast #14 HD 1 per 1.6 ft2 Min. 0.25-inch DensDeck Prime, DEXcell FA Glass Mat Roof Board or SECUROCK Gypsum- Fiber Roof Board D-IS SBS-CA1, SBS-CA2 (Optional) SBS- CA1, SBS-CA2 SBS-CA1, SBS-CA2, APP-CA1 -45.0 S-23. Min. 22 ga., type B, Grade 40 steel or min. 2,500 psi structural concrete Min. 2-inch Polytherm, ACFoam II, ENRGY 3, EnergyGuard Polyiso Insulation, Polytherm H, H-Shield or Multi-Max FA3 Dekfast Hex (aka, Dekfast PLT-H-2- 7/8) with Dekfast #14, OMG 3” Galvalume Ribbons Plates with OMG #14 Roofgrip or Trufast 3” Metal Insulation Plate with Trufast #14 HD 1 per 4.0 ft2 Min. 0.25-inch DensDeck, DensDeck Prime, DEXcell FA Glass Mat Roof Board, SECUROCK Gypsum-Fiber Roof Board or SECUROCK Glass-Mat Roof Board, min. 7/16-inch DEXcell Cement Roof Board or min. 0.5-inch SECUROCK Cement Roof Board M-OSFA or M-PG1 SBS-CA1, SBS-CA2 (Optional) SBS- CA1, SBS-CA2 SBS-CA1, SBS-CA2, APP-CA1 -30.0* S-24. Min. 22 ga., type B, Grade 40 steel or min. 2,500 psi structural concrete Min. 2-inch Polytherm, ACFoam II, ENRGY 3, EnergyGuard Polyiso Insulation, Polytherm H, H-Shield or Multi-Max FA3 Dekfast Hex (aka, Dekfast PLT-H-2- 7/8) with Dekfast #14, OMG 3” Galvalume Ribbons Plates with OMG #14 Roofgrip or Trufast 3” Metal Insulation Plate with Trufast #14 HD 1 per 1.6 ft2 Min. 0.25-inch DensDeck, DensDeck Prime, DEXcell FA Glass Mat Roof Board, SECUROCK Gypsum-Fiber Roof Board or SECUROCK Glass-Mat Roof Board, min. 7/16-inch DEXcell Cement Roof Board or min. 0.5-inch SECUROCK Cement Roof Board M-OSFA or M-PG1 SBS-CA1, SBS-CA2 (Optional) SBS- CA1, SBS-CA2 SBS-CA1, SBS-CA2, APP-CA1 -45.0 S-25. Min. 22 ga., type B, Grade 40 steel or min. 2,500 psi structural concrete Min. 2-inch Polytherm, ACFoam II, ENRGY 3, EnergyGuard Polyiso Insulation, Polytherm H, H-Shield or Multi-Max FA3 Dekfast Hex (aka, Dekfast PLT-H-2- 7/8) with Dekfast #14, OMG 3” Galvalume Ribbons Plates with OMG #14 Roofgrip or Trufast 3” Metal Insulation Plate with Trufast #14 HD 1 per 4.0 ft2 Min. 0.25-inch DensDeck Prime, DEXcell FA Glass Matg Roof Board or SECUROCK Gypsum- Fiber Roof Board OB500 SBS-CA1, SBS-CA2 (Optional) SBS- CA1, SBS-CA2 SBS-CA1, SBS-CA2, APP-CA1 -30.0* NEMO|etc. NEMO ETC, LLC Evaluation Report P9290.02.08-R25 for FL1654-R27 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 25: 09/30/2020 ©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 43 of 94 TABLE 2A: STEEL OR STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER SYSTEM TYPE B-1: MECHANICALLY ATTACHED BASE INSULATION, BONDED TOP INSULATION, BONDED ROOF COVER System No. Deck (Note 1) Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP (psf) Type Fasten (Note 11) Attach Type Attach (Notes 6,7,8) Base Ply Ply Cap Ply S-26. Min. 22 ga., type B, Grade 40 steel or min. 2,500 psi structural concrete Min. 2-inch Polytherm, ACFoam II, ENRGY 3, EnergyGuard Polyiso Insulation, Polytherm H, H-Shield or Multi-Max FA3 Dekfast Hex (aka, Dekfast PLT-H-2- 7/8) with Dekfast #14, OMG 3” Galvalume Ribbons Plates with OMG #14 Roofgrip or Trufast 3” Metal Insulation Plate with Trufast #14 HD 1 per 1.6 ft2 Min. 0.25-inch DensDeck Prime, DEXcell FA Glass Matg Roof Board or SECUROCK Gypsum- Fiber Roof Board OB500 SBS-CA1, SBS-CA2 (Optional) SBS- CA1, SBS-CA2 SBS-CA1, SBS-CA2, APP-CA1 -45.0 S-27. Min. 22 ga., type B, Grade 40 steel or min. 2,500 psi structural concrete Min. 2-inch Polytherm, ACFoam II, ENRGY 3, EnergyGuard Polyiso Insulation, Polytherm H, H-Shield or Multi-Max FA3 Dekfast Hex (aka, Dekfast PLT-H-2- 7/8) with Dekfast #14, OMG 3” Galvalume Ribbons Plates with OMG #14 Roofgrip or Trufast 3” Metal Insulation Plate with Trufast #14 HD 1 per 4.0 ft2 Min. 0.25-inch DensDeck Prime or SECUROCK Gypsum-Fiber Roof Board CR-20 SBS-CA1, SBS-CA2 (Optional) SBS- CA1, SBS-CA2 SBS-CA1, SBS-CA2, APP-CA1 -30.0* S-28. Min. 22 ga., type B, Grade 40 steel or min. 2,500 psi structural concrete Min. 2-inch Polytherm, ACFoam II, ENRGY 3, EnergyGuard Polyiso Insulation, Polytherm H, H-Shield or Multi-Max FA3 Dekfast Hex (aka, Dekfast PLT-H-2- 7/8) with Dekfast #14, OMG 3” Galvalume Ribbons Plates with OMG #14 Roofgrip or Trufast 3” Metal Insulation Plate with Trufast #14 HD 1 per 1.6 ft2 Min. 0.25-inch DensDeck Prime or SECUROCK Gypsum-Fiber Roof Board CR-20 SBS-CA1, SBS-CA2 (Optional) SBS- CA1, SBS-CA2 SBS-CA1, SBS-CA2, APP-CA1 -45.0 NEMO|etc. NEMO ETC, LLC Evaluation Report P9290.02.08-R25 for FL1654-R27 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 25: 09/30/2020 ©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 44 of 94 TABLE 2B: STEEL OR STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER SYSTEM TYPE C-1: MECHANICALLY ATTACHED INSULATION, BONDED ROOF COVER System No. Deck (Note 1) Base Insulation Layer (Note 13) Top Insulation Layer Roof Cover (Note 15) MDP (psf) Type Fasten (Note 11) Attach Base Ply Ply Cap Ply ASPHALT- OR TORCH-APPLIED BASE PLY: S-29. Min. 22 ga., type B, Grade 33 steel or min. 2,500 psi structural concrete One or more layers, any combination, loose laid Min. 0.75-inch JM Fesco Board (homogeneous) or min. 1.5-inch JM Fesco Board (laminated) OMG AccuTrac Plate or OMG 3 in. Ribbed Galvalume Plate with #12 Roofgrip (steel only) or OMG #14 Heavy Duty, Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with Dekfast #12 DP (steel only) or Dekfast #14, Trufast 3” Metal Insulation Plate with Trufast #12 DP (steel only) or Trufast #14 HD 1 per 2.0 ft2 (Optional if using AA Ply) BP-AA, SBS- AA (Optional if using AA Base) BP-AA, SBS-AA, SBS-TA or APP-TA SBS-AA, SBS-TA, APP-TA -45.0* S-30. Min. 22 ga., type B, Grade 33 steel or min. 2,500 psi structural concrete One or more layers, any combination, loose laid Min. 0.5-inch Structodek High Density Fiberboard Roof Insulation or G-P FiberBase HD or HD Excel OMG AccuTrac Plate or OMG 3 in. Ribbed Galvalume Plate with #12 Roofgrip (steel only) or OMG #14 Heavy Duty, Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with Dekfast #12 DP (steel only) or Dekfast #14, Trufast 3” Metal Insulation Plate with Trufast #12 DP (steel only) or Trufast #14 HD 1 per 4.0 ft2 (Optional if using AA Ply) BP-AA, SBS- AA (Optional if using AA Base) BP-AA, SBS-AA, SBS-TA or APP-TA SBS-AA, SBS-TA, APP-TA -45.0* S-31. Min. 22 ga., type B, Grade 33 steel or min. 2,500 psi structural concrete One or more layers, any combination, loose laid Min. 0.25-inch DensDeck Prime or SECUROCK Gypsum-Fiber Roof Board OMG AccuTrac Plate or OMG 3 in. Ribbed Galvalume Plate with #12 Roofgrip (steel only) or OMG #14 Heavy Duty, Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with Dekfast #12 DP (steel only) or Dekfast #14, Trufast 3” Metal Insulation Plate with Trufast #12 DP (steel only) or Trufast #14 HD 1 per 4.0 ft2 (Optional if using AA Ply) BP-AA, SBS- AA (Optional if using AA Base) BP-AA, SBS-AA, SBS-TA or APP-TA SBS-AA, SBS-TA, APP-TA -45.0* S-32. Min. 22 ga., type B, Grade 33 steel or min. 2,500 psi structural concrete (Optional) One or more layers, any combination, loose laid Min. 2-inch H-Shield WF OMG AccuTrac Plate or OMG 3 in. Ribbed Galvalume Plate with #12 Roofgrip (steel only) or OMG #14 Heavy Duty, Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with Dekfast #12 DP (steel only) or Dekfast #14, Trufast 3” Metal Insulation Plate with Trufast #12 DP (steel only) or Trufast #14 HD 1 per 4.0 ft2 (Optional if using AA Ply) BP-AA, SBS- AA (Optional if using AA Base) BP-AA, SBS-AA, SBS-TA or APP-TA SBS-AA, SBS-TA, APP-TA -45.0* S-33. Min. 22 ga., type B, Grade 40 steel; 6 ft span; 5/8” puddle welds, 6” o.c. One or more layers, any combination, min. 1.5” thick, loose laid Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board Dekfast PLT-H-2-7/8 or PTL-R-3 plates with Dekfast DF- #12-PH3, DF-#14-PH3 or DF-#15-PH3 fasteners or OMG 3 in. Galvalume Steel Plate, 3 in. Ribbed Galvalume Plate (Flat) or AccuTrac Flat Bottom Plate with OMG #12 Roofgrip, #14 Roofgrip or OMG #15 Roofgrip fasteners or Trufast 3” Metal Insulation Plate with Trufast #12 DP, Trufast #14 HD or Trufast #15 EHD fasteners 1 per 2.0 ft2 SBS-TA or APP-TA (Optional) SBS-TA or APP-TA SBS-TA or APP-TA -52.5 S-34. Min. 22 ga., type B, Grade 40 steel; 6 ft span; 5/8” puddle welds, 6” o.c. One or more layers, any combination, min. 1.5” thick, loose laid Min. 0.25-inch DensDeck Prime Dekfast PLT-H-2-7/8 or PTL-R-3 plates with Dekfast DF- #12-PH3, DF-#14-PH3 or DF-#15-PH3 fasteners or OMG 3 in. Galvalume Steel Plate, 3 in. Ribbed Galvalume Plate (Flat) or AccuTrac Flat Bottom Plate with OMG #12 Roofgrip, #14 Roofgrip or OMG #15 Roofgrip fasteners or Trufast 3” Metal Insulation Plate with Trufast #12 DP, Trufast #14 HD or Trufast #15 EHD fasteners 1 per 2.0 ft2 SBS-TA or APP-TA (Optional) SBS-TA or APP-TA SBS-TA or APP-TA -60.0 S-35. Min. 22 ga., type B, Grade 40 steel; 6 ft span; 5/8” puddle welds, 6” o.c. One or more layers, any combination, min. 1.5” thick, loose laid Min. 0.25-inch DensDeck Prime or SECUROCK Gypsum-Fiber Roof Board Dekfast PLT-H-2-7/8 or PTL-R-3 plates with Dekfast DF- #12-PH3, DF-#14-PH3 or DF-#15-PH3 fasteners or OMG 3 in. Galvalume Steel Plate, 3 in. Ribbed Galvalume Plate (Flat) or AccuTrac Flat Bottom Plate with OMG #12 Roofgrip, #14 Roofgrip or OMG #15 Roofgrip fasteners or Trufast 3” Metal Insulation Plate with Trufast #12 DP, Trufast #14 HD or Trufast #15 EHD fasteners 1 per 1.6 ft2 SBS-TA or APP-TA (Optional) SBS-TA or APP-TA SBS-TA or APP-TA -67.5 NEMO|etc. NEMO ETC, LLC Evaluation Report P9290.02.08-R25 for FL1654-R27 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 25: 09/30/2020 ©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 45 of 94 TABLE 2B: STEEL OR STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER SYSTEM TYPE C-1: MECHANICALLY ATTACHED INSULATION, BONDED ROOF COVER System No. Deck (Note 1) Base Insulation Layer (Note 13) Top Insulation Layer Roof Cover (Note 15) MDP (psf) Type Fasten (Note 11) Attach Base Ply Ply Cap Ply S-36. Min. 22 ga., type B, Grade 33 steel or min. 2,500 psi structural concrete (Optional) One or more layers, any combination, loose laid Min. 0.5-inch SECUROCK Gypsum-Fiber Roof Board OMG 3-inch Galvalume Steel Plate with OMG #14 HD 1 per 1.8 ft2 (Optional if using AA Ply) BP-AA, SBS- AA (Optional if using AA Base) BP-AA, SBS-AA, SBS-TA or APP-TA SBS-AA, SBS-TA, APP-TA -75.0 S-37. Min. 22 ga., type B, Grade 33 steel or min. 2,500 psi structural concrete One or more layers, any combination, loose laid Min. 0.5-inch Structodek High Density Fiberboard Roof Insulation or min. 0.25-inch DensDeck, DensDeck Prime or SECUROCK Gypsum-Fiber Roof Board Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with Dekfast #12 (steel only) or #14 or Trufast 3” Metal Insulation Plate with Trufast DP (steel only) or HD 1 per 1.3 ft2 (Optional if using AA Ply) BP-AA, SBS- AA (Optional if using AA Base) BP-AA, SBS-AA, SBS-TA or APP-TA SBS-AA, SBS-TA, APP-TA -82.5 SELF-ADHERING BASE PLY: S-38. Min. 22 ga., type B, Grade 33 steel or min. 2,500 psi structural concrete (Optional) One or more layers, any combination, loose laid Min. 1.5-inch Polytherm, ACFoam II, H-Shield or Polytherm Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with Dekfast #12 DP (steel only) or Dekfast #14, OMG AccuTrac Flat Bottom Plate with #12 Roofgrip (steel only) or OMG #14 Heavy Duty, Trufast 3” Metal Insulation Plate with Trufast #12 DP (steel only) or Trufast #14 HD 1 per 2.7 ft2 SBS-SA (Optional) SBS-SA, SBS-TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -30.0 S-39. Min. 22 ga., type B, Grade 40 steel or min. 2,500 psi structural concrete One or more layers, any combination, min. 1-inch, loose laid Min. 0.25-inch DensDeck Prime optionally primed with POLYBRITE 745 or WB3000 Polygrip #14 or Polygrip #15 with Polygrip Hex Plate or Dekfast DF-#14 or DF-#15 with Dekfast Hex (aka, Dekfast PLT-H-2-7/8) or OMG #14 Roofgrip or #15 Roofgrip with OMG 3 in. Round Metal Plate or Trufast #14 HD or Trufast #15 EHD Fasteners with Trufast 3” Metal Insulation Plate 1 per 2.7 ft2 SBS-SA (Optional) SBS-SA, SBS-TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -37.5* S-40. Min. 22 ga., type B, Grade 40 steel or min. 2,500 psi structural concrete One or more layers, any combination, min. 1-inch, loose laid Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board optionally primed with POLYBRITE 745 or WB3000 Polygrip #14 or Polygrip #15 with Polygrip Hex Plate or Dekfast DF-#14 or DF-#15 with Dekfast Hex (aka, Dekfast PLT-H-2-7/8) or OMG #14 Roofgrip or #15 Roofgrip with OMG 3 in. Round Metal Plate or Accutrac Flat Bottom Plate or Trufast #14 HD or Trufast #15 EHD Fasteners with Trufast 3” Metal Insulation Plate 1 per 2.7 ft2 SBS-SA (Optional) SBS-SA, SBS-TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -37.5* S-41. Min. 22 ga., type B, Grade 40 steel or min. 2,500 psi structural concrete One or more layers, any combination, min. 1-inch, loose laid Min. 0.25-inch DEXcell FA Glass Mat Roof Board Polygrip #14 or Polygrip #15 with Polygrip Hex Plate or Dekfast DF-#14 or DF-#15 with Dekfast Hex (aka, Dekfast PLT-H-2-7/8), isofast PLT-S-2-3/4X2-3/4 or Dekfast Galvalume Steel 3” Round (aka, Dekfast PLT-R-3) or OMG #14 Roofgrip or #15 Roofgrip with OMG 3 in. Round Metal Plate or Accutrac Flat Bottom Plate or Trufast #14 HD or Trufast #15 EHD Fasteners with Trufast 3” Metal Insulation Plate 1 per 2.7 ft2 SBS-SA (Optional) SBS-SA, SBS-TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -37.5* S-42. Min. 22 ga., type B, Grade 33 steel or min. 2,500 psi structural concrete (Optional) One or more layers, any combination, loose laid Min. 1.5-inch H-Shield or Polytherm OMG AccuTrac Flat Bottom Plate with #12 Roofgrip (steel only) or OMG #14 Heavy Duty, Trufast 3” Metal Insulation Plate with Trufast #12 DP (steel only) or Trufast #14 HD 1 per 2.0 ft2 SBS-SA (Optional) SBS-SA, SBS-TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -45.0* NEMO|etc. NEMO ETC, LLC Evaluation Report P9290.02.08-R25 for FL1654-R27 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 25: 09/30/2020 ©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 46 of 94 TABLE 2B: STEEL OR STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER SYSTEM TYPE C-1: MECHANICALLY ATTACHED INSULATION, BONDED ROOF COVER System No. Deck (Note 1) Base Insulation Layer (Note 13) Top Insulation Layer Roof Cover (Note 15) MDP (psf) Type Fasten (Note 11) Attach Base Ply Ply Cap Ply S-43. Min. 22 ga., type B, Grade 33 steel or min. 2,500 psi structural concrete One or more layers, any combination, loose laid Min. 0.25-inch DensDeck Prime or SECUROCK Gypsum-Fiber Roof Board optionally primed with POLYBRITE 745 or WB3000 Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with Dekfast #14, OMG 3” Galvalume Ribbed Plates with OMG #14 RoofGrip or Trufast 3” Metal Insulation Plates with Trufast #14 HD Fasteners 1 per 2.0 ft2 SBS-SA None SBS-CA1, SBS-CA2, APP-CA1 -45.0* S-44. Min. 22 ga., type B, Grade 33 steel or min. 2,500 psi structural concrete One or more layers, any combination, loose laid Min. 0.25-inch DensDeck Prime or SECUROCK Gypsum-Fiber Roof Board optionally primed with POLYBRITE 745 or WB3000 OMG 3 in. Galvalume Plate (non-ribbed) with #12 Roofgrip (steel only) or OMG #14 Heavy Duty, Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with Dekfast #12 DP (steel only) or Dekfast #14, Trufast 3” Metal Insulation Plate with Trufast #12 DP (steel only) or Trufast #14 HD 1 per 2.0 ft2 SBS-SA (Optional) SBS-SA, SBS-TA or APP-TA SBS-SA, APP-SA, SBS-TA or APP-TA -45.0* S-45. Min. 22 ga., type B, Grade 40 steel or min. 2,500 psi structural concrete One or more layers, any combination, min. 1-inch, loose laid Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board optionally primed with POLYBRITE 745 or WB3000 Polygrip #14 with Polygrip Hex Plate or Dekfast #14 with Dekfast Hex (aka, Dekfast PLT-H-2-7/8) or Dekfast Galvalume Steel 3” Round (aka, Dekfast PLT-R-3) or OMG #14 Roofgrip with OMG 3 in. Round Metal Plate, OMG 3 in. Ribbed Galvalume Plate (Flat) or Accutrac Flat Bottom Plate or Trufast #14 HD Fasteners with Trufast 3” Metal Insulation Plate 1 per 2.0 ft2 SBS-SA None SBS-SA -45.0 S-46. Min. 22 ga., type B, Grade 40 steel or min. 2,500 psi structural concrete One or more layers, any combination, min. 1-inch, loose laid Min. 0.25-inch DensDeck Prime optionally primed with POLYBRITE 745 or WB3000 Polygrip #14 with Polygrip Hex Plate or Dekfast #14 with Dekfast Hex (aka, Dekfast PLT-H-2-7/8) or OMG #14 Roofgrip with OMG 3 in. Round Metal Plate or Accutrac Flat Bottom Plate or Trufast #14 HD Fasteners with Trufast 3” Metal Insulation Plate 1 per 2.0 ft2 SBS-SA None SBS-SA -45.0 S-47. Min. 22 ga., type B, Grade 40 steel or min. 2,500 psi structural concrete One or more layers, any combination, min. 1-inch, loose laid Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board optionally primed with POLYBRITE 745 or WB3000 Polygrip #14 or Polygrip #15 with Polygrip Hex Plate or Dekfast DF-#14 or DF-#15 with Dekfast Hex (aka, Dekfast PLT-H-2-7/8) or OMG #14 Roofgrip or #15 Roofgrip with OMG 3 in. Round Metal Plate or Accutrac Flat Bottom Plate or Trufast #14 HD or Trufast #15 EHD Fasteners with Trufast 3” Metal Insulation Plate 1 per 1.8 ft2 SBS-SA (Optional when using torch- applied Cap Ply) SBS-TA, APP-TA SBS-SA, APP-SA, SBS-TA or APP-TA -45.0 S-48. Min. 22 ga., type B, Grade 40 steel or min. 2,500 psi structural concrete One or more layers, any combination, min. 1-inch, loose laid Min. 0.25-inch DensDeck Prime optionally primed with POLYBRITE 745 or WB3000 OMG #14 Roofgrip or #15 Roofgrip with OMG 3 in. Round Metal Plate or Trufast #14 HD or Trufast #15 EHD Fasteners with Trufast 3” Metal Insulation Plate 1 per 1.8 ft2 SBS-SA (Optional when using torch- applied Cap Ply) SBS-TA, APP-TA SBS-SA, APP-SA, SBS-TA or APP-TA -45.0 S-49. Min. 22 ga., type B, Grade 33 steel or min. 2,500 psi structural concrete (Optional) One or more layers, any combination, loose laid Min. 1.5-inch H-Shield or Polytherm optionally primed with POLYBRITE 745 or WB3000 Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with Dekfast #12 DP (steel only) or Dekfast #14 1 per 2.0 ft2 SBS-SA (Optional) SBS-SA, SBS-TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -60.0 S-50. Min. 22 ga., type B, Grade 40 steel or min. 2,500 psi structural concrete One or more layers, any combination, loose laid Min. 0.25-inch DensDeck Prime or SECUROCK Gypsum-Fiber Roof Board optionally primed with POLYBRITE 745 or WB3000 OMG 3 in. Galvalume Plate (non-ribbed) with #12 Roofgrip (steel only) or OMG #14 Heavy Duty, Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with Dekfast #12 DP (steel only) or Dekfast #14, Trufast 3” Metal Insulation Plate with Trufast #12 DP (steel only) or Trufast #14 HD 1 per 1.6 ft2 SBS-SA (Optional) SBS-TA or APP-TA SBS-TA or APP-TA -60.0 NEMO|etc. NEMO ETC, LLC Evaluation Report P9290.02.08-R25 for FL1654-R27 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 25: 09/30/2020 ©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 47 of 94 TABLE 2B: STEEL OR STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER SYSTEM TYPE C-1: MECHANICALLY ATTACHED INSULATION, BONDED ROOF COVER System No. Deck (Note 1) Base Insulation Layer (Note 13) Top Insulation Layer Roof Cover (Note 15) MDP (psf) Type Fasten (Note 11) Attach Base Ply Ply Cap Ply S-51. Min. 22 ga., type B, Grade 33 steel or min. 2,500 psi structural concrete (Optional) One or more layers, any combination, loose laid Min. 1.5-inch ACFoam II, ACFoam III, EnergyGuard Polyiso Insulation, ENRGY 3, ENRGY 3 CGF, H-Shield, H-Shield CG, ISO 95+ GL, Multi-Max FA3, Polytherm or Ultra-Max optionally primed with POLYBRITE 745 or WB3000 Dekfast Hex (aka, Dekfast PLT-H-2-7/8) or Dekfast Galvalume Steel 3” Round Insulation Plate (aka, Dekfast PLT-R-3) with Dekfast #12 (steel only) or Dekfast #14, OMG 3 in. Galvalume Plate (non-ribbed) or OMG AccuTrac Plate with #12 Roofgrip (steel only) or OMG #14 Heavy Duty or Trufast 3” Metal Insulation Plate with Trufast #12 DP (steel only) or Trufast #14 HD 1 per 1.3 ft2 SBS-SA (Optional) SBS-SA, SBS-TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -67.5* S-52. Min. 22 ga., type B, Grade 40 steel or min. 2,500 psi structural concrete One or more layers, any combination, loose laid Min. 0.25-inch DensDeck Prime or SECUROCK Gypsum-Fiber Roof Board optionally primed with POLYBRITE 745 or WB3000 OMG 3 in. Galvalume Plate (non-ribbed) with #12 Roofgrip (steel only) or OMG #14 Heavy Duty, Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with Dekfast #12 DP (steel only) or Dekfast #14, Trufast 3” Metal Insulation Plate with Trufast #12 DP (steel only) or Trufast #14 HD 1 per 1.3 ft2 SBS-SA (Optional) SBS-TA or APP-TA SBS-TA or APP-TA -72.5 S-53. Min. 22 ga., type B, Grade 33 steel or min. 2,500 psi structural concrete (Optional) One or more layers, any combination, loose laid Min. 0.5-inch SECUROCK Gypsum-Fiber Roof Board OMG 3-inch Galvalume Steel Plate with OMG #14 HD 1 per 1.8 ft2 SBS-SA (Optional) SBS-TA SBS-TA -75.0 S-54. Min. 22 ga., type B, Grade 40 steel or min. 2,500 psi structural concrete One or more layers, any combination, min. 1-inch, loose laid Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board optionally primed with POLYBRITE 745 or WB3000 Polygrip #14 or Polygrip #15 with Polygrip Hex Plate or Dekfast DF-#14 or DF-#15 with Dekfast Hex (aka, Dekfast PLT-H-2-7/8) or OMG #14 Roofgrip or #15 Roofgrip with OMG 3 in. Round Metal Plate or Accutrac Flat Bottom Plate or Trufast #14 HD or Trufast #15 EHD Fasteners with Trufast 3” Metal Insulation Plate 1 per 1.0 ft2 SBS-SA (Optional) SBS-TA, APP-TA SBS-TA, APP-TA -90.0 S-55. Min. 22 ga., type B, Grade 40 steel or min. 2,500 psi structural concrete One or more layers, any combination, min. 1-inch, loose laid Min. 0.25-inch DensDeck Prime optionally primed with POLYBRITE 745 or WB3000 Polygrip #14 or Polygrip #15 with Polygrip Hex Plate or Dekfast DF-#14 or DF-#15 with Dekfast Hex (aka, Dekfast PLT-H-2-7/8) or OMG #14 Roofgrip or #15 Roofgrip with OMG 3 in. Round Metal Plate or Trufast #14 HD or Trufast #15 EHD Fasteners with Trufast 3” Metal Insulation Plate 1 per 1.0 ft2 SBS-SA (Optional) SBS-TA, APP-TA SBS-TA, APP-TA -97.5 HYBRID SYSTEMS WITH SELF-ADHERING APP BASE PLY: S-56. Min. 22 ga., type B, Grade 33 steel or min. 2,500 psi structural concrete (Optional) One or more layers, any combination, loose laid Min. 1.5-inch Polytherm, ACFoam II, H-Shield or Polytherm Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with Dekfast #12 DP (steel only) or Dekfast #14, OMG AccuTrac Flat Bottom Plate with #12 Roofgrip (steel only) or OMG #14 Heavy Duty, Trufast 3” Metal Insulation Plate with Trufast #12 DP (steel only) or Trufast #14 HD 1 per 2.7 ft2 APP-SA-H (Optional) APP-TA APP-TA -30.0 S-57. Min. 22 ga., type B, Grade 40 steel or min. 2,500 psi structural concrete One or more layers, any combination, min. 1-inch, loose laid Min. 0.25-inch DensDeck Prime optionally primed with POLYBRITE 745 or WB3000 Polygrip #14 or Polygrip #15 with Polygrip Hex Plate or Dekfast DF-#14 or DF-#15 with Dekfast Hex (aka, Dekfast PLT-H-2-7/8) or OMG #14 Roofgrip or #15 Roofgrip with OMG 3 in. Round Metal Plate or Trufast #14 HD or Trufast #15 EHD Fasteners with Trufast 3” Metal Insulation Plate 1 per 2.7 ft2 APP-SA-H (Optional) APP-TA APP-TA -37.5* NEMO|etc. NEMO ETC, LLC Evaluation Report P9290.02.08-R25 for FL1654-R27 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 25: 09/30/2020 ©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 48 of 94 TABLE 2B: STEEL OR STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER SYSTEM TYPE C-1: MECHANICALLY ATTACHED INSULATION, BONDED ROOF COVER System No. Deck (Note 1) Base Insulation Layer (Note 13) Top Insulation Layer Roof Cover (Note 15) MDP (psf) Type Fasten (Note 11) Attach Base Ply Ply Cap Ply S-58. Min. 22 ga., type B, Grade 40 steel or min. 2,500 psi structural concrete One or more layers, any combination, min. 1-inch, loose laid Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board optionally primed with POLYBRITE 745 or WB3000 Polygrip #14 or Polygrip #15 with Polygrip Hex Plate or Dekfast DF-#14 or DF-#15 with Dekfast Hex (aka, Dekfast PLT-H-2-7/8) or OMG #14 Roofgrip or #15 Roofgrip with OMG 3 in. Round Metal Plate or Accutrac Flat Bottom Plate or Trufast #14 HD or Trufast #15 EHD Fasteners with Trufast 3” Metal Insulation Plate 1 per 2.7 ft2 APP-SA-H (Optional) APP-TA APP-TA -37.5* S-59. Min. 22 ga., type B, Grade 40 steel or min. 2,500 psi structural concrete One or more layers, any combination, min. 1-inch, loose laid Min. 0.25-inch DEXcell FA Glass Mat Roof Board Polygrip #14 or Polygrip #15 with Polygrip Hex Plate or Dekfast DF-#14 or DF-#15 with Dekfast Hex (aka, Dekfast PLT-H-2-7/8), isofast PLT-S-2-3/4X2-3/4 or Dekfast Galvalume Steel 3” Round (aka, Dekfast PLT-R-3) or OMG #14 Roofgrip or #15 Roofgrip with OMG 3 in. Round Metal Plate or Accutrac Flat Bottom Plate or Trufast #14 HD or Trufast #15 EHD Fasteners with Trufast 3” Metal Insulation Plate 1 per 2.7 ft2 APP-SA-H (Optional) APP-TA APP-TA -37.5* S-60. Min. 22 ga., type B, Grade 33 steel or min. 2,500 psi structural concrete (Optional) One or more layers, any combination, loose laid Min. 1.5-inch H-Shield or Polytherm OMG AccuTrac Flat Bottom Plate with #12 Roofgrip (steel only) or OMG #14 Heavy Duty, Trufast 3” Metal Insulation Plate with Trufast #12 DP (steel only) or Trufast #14 HD 1 per 2.0 ft2 APP-SA-H (Optional) APP-TA APP-TA -45.0* HYBRID SYSTEMS WITH SELF-ADHERING SBS BASE PLY: S-61. Min. 22 ga., type B, Grade 33 steel or min. 2,500 psi structural concrete (Optional) One or more layers, any combination, loose laid Min. 1.5-inch Polytherm, ACFoam II, H-Shield or Polytherm H Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with Dekfast #12 DP (steel only) or Dekfast #14, OMG AccuTrac Flat Bottom Plate with #12 Roofgrip (steel only) or OMG #14 Heavy Duty, Trufast 3” Metal Insulation Plate with Trufast #12 DP (steel only) or Trufast #14 HD 1 per 2.7 ft2 SBS-SA-H (Optional) SBS-TA SBS-TA -30.0 S-62. Min. 22 ga., type B, Grade 40 steel or min. 2,500 psi structural concrete One or more layers, any combination, min. 1-inch, loose laid Min. 0.25-inch DensDeck Prime optionally primed with POLYBRITE 745 or WB3000 Polygrip #14 or Polygrip #15 with Polygrip Hex Plate or Dekfast DF-#14 or DF-#15 with Dekfast Hex (aka, Dekfast PLT-H-2-7/8) or OMG #14 Roofgrip or #15 Roofgrip with OMG 3 in. Round Metal Plate or Trufast #14 HD or Trufast #15 EHD Fasteners with Trufast 3” Metal Insulation Plate 1 per 2.7 ft2 SBS-SA-H (Optional) SBS-TA SBS-TA -37.5* S-63. Min. 22 ga., type B, Grade 40 steel or min. 2,500 psi structural concrete One or more layers, any combination, min. 1-inch, loose laid Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board optionally primed with POLYBRITE 745 or WB3000 Polygrip #14 or Polygrip #15 with Polygrip Hex Plate or Dekfast DF-#14 or DF-#15 with Dekfast Hex (aka, Dekfast PLT-H-2-7/8) or OMG #14 Roofgrip or #15 Roofgrip with OMG 3 in. Round Metal Plate or Accutrac Flat Bottom Plate or Trufast #14 HD or Trufast #15 EHD Fasteners with Trufast 3” Metal Insulation Plate 1 per 2.7 ft2 SBS-SA-H (Optional) SBS-TA SBS-TA -37.5* NEMO|etc. NEMO ETC, LLC Evaluation Report P9290.02.08-R25 for FL1654-R27 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 25: 09/30/2020 ©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 49 of 94 TABLE 2B: STEEL OR STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER SYSTEM TYPE C-1: MECHANICALLY ATTACHED INSULATION, BONDED ROOF COVER System No. Deck (Note 1) Base Insulation Layer (Note 13) Top Insulation Layer Roof Cover (Note 15) MDP (psf) Type Fasten (Note 11) Attach Base Ply Ply Cap Ply S-64. Min. 22 ga., type B, Grade 40 steel or min. 2,500 psi structural concrete One or more layers, any combination, min. 1-inch, loose laid Min. 0.25-inch DEXcell FA Glass Mat Roof Board Polygrip #14 or Polygrip #15 with Polygrip Hex Plate or Dekfast DF-#14 or DF-#15 with Dekfast Hex (aka, Dekfast PLT-H-2-7/8), isofast PLT-S-2-3/4X2-3/4 or Dekfast Galvalume Steel 3” Round (aka, Dekfast PLT-R-3) or OMG #14 Roofgrip or #15 Roofgrip with OMG 3 in. Round Metal Plate or Accutrac Flat Bottom Plate or Trufast #14 HD or Trufast #15 EHD Fasteners with Trufast 3” Metal Insulation Plate 1 per 2.7 ft2 SBS-SA-H (Optional) SBS-TA SBS-TA -37.5* S-65. Min. 22 ga., type B, Grade 33 steel or min. 2,500 psi structural concrete (Optional) One or more layers, any combination, loose laid Min. 1.5-inch H-Shield or Polytherm H OMG AccuTrac Flat Bottom Plate with #12 Roofgrip (steel only) or OMG #14 Heavy Duty, Trufast 3” Metal Insulation Plate with Trufast #12 DP (steel only) or Trufast #14 HD 1 per 2.0 ft2 SBS-SA-H (Optional) SBS-TA SBS-TA -45.0* S-66. Min. 22 ga., type B, Grade 40 steel or min. 2,500 psi structural concrete One or more layers, any combination, min. 1-inch, loose laid Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board optionally primed with POLYBRITE 745 or WB3000 Polygrip #14 with Polygrip Hex Plate or Dekfast #14 with Dekfast Hex (aka, Dekfast PLT-H-2-7/8) or Dekfast Galvalume Steel 3” Round (aka, Dekfast PLT-R-3) or OMG #14 Roofgrip with OMG 3 in. Round Metal Plate, OMG 3 in. Ribbed Galvalume Plate (Flat) or Accutrac Flat Bottom Plate or Trufast #14 HD Fasteners with Trufast 3” Metal Insulation Plate 1 per 2.0 ft2 SBS-SA-H (Optional) SBS-TA SBS-TA -45.0 S-67. Min. 22 ga., type B, Grade 40 steel or min. 2,500 psi structural concrete One or more layers, any combination, min. 1-inch, loose laid Min. 0.25-inch DensDeck Prime optionally primed with POLYBRITE 745 or WB3000 Polygrip #14 with Polygrip Hex Plate or Dekfast #14 with Dekfast Hex (aka, Dekfast PLT-H-2-7/8) or OMG #14 Roofgrip with OMG 3 in. Round Metal Plate or Accutrac Flat Bottom Plate or Trufast #14 HD Fasteners with Trufast 3” Metal Insulation Plate 1 per 2.0 ft2 SBS-SA-H (Optional) SBS-TA SBS-TA -45.0 S-68. Min. 22 ga., type B, Grade 33 steel or min. 2,500 psi structural concrete (Optional) One or more layers, any combination, loose laid Min. 1.5-inch H-Shield or Polytherm optionally primed with POLYBRITE 745 or WB3000 Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with Dekfast #12 DP (steel only) or Dekfast #14 1 per 2.0 ft2 SBS-SA-H (Optional) SBS-TA SBS-TA -60.0 S-69. Min. 22 ga., type B, Grade 40 steel or min. 2,500 psi structural concrete One or more layers, any combination, loose laid Min. 0.25-inch DensDeck Prime or SECUROCK Gypsum-Fiber Roof Board optionally primed with POLYBRITE 745 or WB3000 OMG 3 in. Galvalume Plate (non-ribbed) with #12 Roofgrip (steel only) or OMG #14 Heavy Duty, Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with Dekfast #12 DP (steel only) or Dekfast #14, Trufast 3” Metal Insulation Plate with Trufast #12 DP (steel only) or Trufast #14 HD 1 per 1.6 ft2 SBS-SA-H (Optional) SBS-TA SBS-TA -60.0 S-70. Min. 22 ga., type B, Grade 33 steel or min. 2,500 psi structural concrete (Optional) One or more layers, any combination, loose laid Min. 1.5-inch ACFoam II, ACFoam III, EnergyGuard Polyiso Insulation, ENRGY 3, ENRGY 3 CGF, H-Shield, H-Shield CG, ISO 95+ GL, Multi-Max FA3, Polytherm or Ultra-Max optionally primed with POLYBRITE 745 or WB3000 Dekfast Hex (aka, Dekfast PLT-H-2-7/8) or Dekfast Galvalume Steel 3” Round Insulation Plate (aka, Dekfast PLT-R-3) with Dekfast #12 (steel only) or Dekfast #14, OMG 3 in. Galvalume Plate (non-ribbed) or OMG AccuTrac Plate with #12 Roofgrip (steel only) or OMG #14 Heavy Duty or Trufast 3” Metal Insulation Plate with Trufast #12 DP (steel only) or Trufast #14 HD 1 per 1.3 ft2 SBS-SA-H (Optional) SBS-TA SBS-TA -67.5* NEMO|etc. NEMO ETC, LLC Evaluation Report P9290.02.08-R25 for FL1654-R27 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 25: 09/30/2020 ©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 50 of 94 TABLE 2B: STEEL OR STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER SYSTEM TYPE C-1: MECHANICALLY ATTACHED INSULATION, BONDED ROOF COVER System No. Deck (Note 1) Base Insulation Layer (Note 13) Top Insulation Layer Roof Cover (Note 15) MDP (psf) Type Fasten (Note 11) Attach Base Ply Ply Cap Ply S-71. Min. 22 ga., type B, Grade 40 steel or min. 2,500 psi structural concrete One or more layers, any combination, loose laid Min. 0.25-inch DensDeck Prime or SECUROCK Gypsum-Fiber Roof Board optionally primed with POLYBRITE 745 or WB3000 OMG 3 in. Galvalume Plate (non-ribbed) with #12 Roofgrip (steel only) or OMG #14 Heavy Duty, Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with Dekfast #12 DP (steel only) or Dekfast #14, Trufast 3” Metal Insulation Plate with Trufast #12 DP (steel only) or Trufast #14 HD 1 per 1.3 ft2 SBS-SA-H (Optional) SBS-TA SBS-TA -72.5 S-72. Min. 22 ga., type B, Grade 33 steel or min. 2,500 psi structural concrete (Optional) One or more layers, any combination, loose laid Min. 0.5-inch SECUROCK Gypsum-Fiber Roof Board OMG 3-inch Galvalume Steel Plate with OMG #14 HD 1 per 1.8 ft2 SBS-SA-H (Optional) SBS-TA SBS-TA -75.0 S-73. Min. 22 ga., type B, Grade 40 steel or min. 2,500 psi structural concrete One or more layers, any combination, min. 1-inch, loose laid Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board optionally primed with POLYBRITE 745 or WB3000 Polygrip #14 or Polygrip #15 with Polygrip Hex Plate or Dekfast DF-#14 or DF-#15 with Dekfast Hex (aka, Dekfast PLT-H-2-7/8) or OMG #14 Roofgrip or #15 Roofgrip with OMG 3 in. Round Metal Plate or Accutrac Flat Bottom Plate or Trufast #14 HD or Trufast #15 EHD Fasteners with Trufast 3” Metal Insulation Plate 1 per 1.0 ft2 SBS-SA-H (Optional) SBS-TA SBS-TA -90.0 S-74. Min. 22 ga., type B, Grade 40 steel or min. 2,500 psi structural concrete One or more layers, any combination, min. 1-inch, loose laid Min. 0.25-inch DensDeck Prime optionally primed with POLYBRITE 745 or WB3000 Polygrip #14 or Polygrip #15 with Polygrip Hex Plate or Dekfast DF-#14 or DF-#15 with Dekfast Hex (aka, Dekfast PLT-H-2-7/8) or OMG #14 Roofgrip or #15 Roofgrip with OMG 3 in. Round Metal Plate or Trufast #14 HD or Trufast #15 EHD Fasteners with Trufast 3” Metal Insulation Plate 1 per 1.0 ft2 SBS-SA-H (Optional) SBS-TA SBS-TA -97.5 COLD-APPLIED BASE PLY: S-75. Min. 22 ga., type B, Grade 33 steel or min. 2,500 psi structural concrete One or more layers, any combination, loose laid Min. 0.25-inch DensDeck Prime or SECUROCK Gypsum-Fiber Roof Board Dekfast Galvalume Steel Hex with Dekfast #14, OMG 3” Galvalume Ribbed Plates with OMG #14 RoofGrip or Trufast 3” Metal Insulation Plates with Trufast #14 HD Fasteners 1 per 2.0 ft2 SBS-CA1, SBS-CA2 (Optional) SBS- CA1, SBS-CA2 SBS-CA1, SBS-CA2, APP-CA1 -45.0* NEMO|etc. NEMO ETC, LLC Evaluation Report P9290.02.08-R25 for FL1654-R27 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 25: 09/30/2020 ©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 51 of 94 TABLE 2C: STEEL OR STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER SYSTEM TYPE D-2: INSULATED, MECHANICALLY ATTACHED BASE SHEET, BONDED ROOF COVER System No. Deck (Note 1) Insulation Layer(s) (Note 13) Base Sheet Roof Cover (Note 15) MDP (psf) Type Attach Type Fasten (Note 11) Attach Base Ply Cap Ply ASPHALT- OR TORCH-APPLIED BASE PLY: S-76. Min. 22 ga., type B, Grade 33 steel or min. 2,500 psi structural concrete One or more layers, any combination Prelim. Attached Elastobase, Elastobase P, Elastovent or JM Perma-Ply 28 Roofgrip #14 with OMG Flat Bottom Plates (square), Dekfast #14 with Dekfast Hex (aka, Dekfast PLT-H-2-7/8) or Trufast #14 HD with Trufast 3” Metal Insulation Plate 12-inch o.c. at min. 4-inch lap and 18-inch o.c. at two, equally spaced, staggered center rows (Optional) BP- AA, SBS-AA, SBS-TA or APP-TA SBS-AA, SBS- TA, APP-TA -45.0* S-77. Min. 22 ga., type B, Grade 33 steel or min. 2,500 psi structural concrete One or more layers, any combination Prelim. Attached Elastobase, Elastobase P, Elastovent, Polyglass G2 Base, CertainTeed Glasbase, Firestone MB Base, JM Perma-Ply 28 or GAFGLAS #75 Roofgrip #14 with OMG Flat Bottom Plates (square), Dekfast #14 with Dekfast Hex (aka, Dekfast PLT-H-2-7/8) or Trufast #14 HD with Trufast 3” Metal Insulation Plate 12-inch o.c. at min. 4-inch lap and 12-inch o.c. at two, equally spaced, staggered center rows (Optional) BP- AA, SBS-AA, SBS-TA or APP-TA SBS-AA, SBS- TA, APP-TA -52.5 S-78. Min. 22 ga., type B, Grade 33 steel or min. 2,500 psi structural concrete One or more layers, any combination Prelim. Attached Elastobase, Elastobase P or Elastovent Roofgrip #12 (steel only) or #14 with OMG Flat Bottom Plates (square) 12-inch o.c. at min. 4-inch lap and 12-inch o.c. at two, equally spaced, staggered center rows (Optional) BP- AA, SBS-AA, SBS-TA or APP-TA SBS-AA, SBS- TA, APP-TA -60.0 S-79. Min. 22 ga., type B, Grade 33 steel or min. 2,500 psi structural concrete One or more layers, any combination Prelim. Attached Polybond, Polyflex Dekfast #14 with Dekfast Hex (aka, Dekfast PLT-H- 2-7/8) or OMG Roofgrip #14 OMG Flat Bottom Plates 12-inch o.c. at the min. 4-inch lap and 18-inch o.c. at two, equally spaced, staggered center rows (Optional) BP- AA, SBS-AA, SBS-TA or APP-TA SBS-AA, SBS- TA, APP-TA -112.5 SELF-ADHERING BASE PLY: S-80. Min. 22 ga., type B, Grade 33 steel or min. 2,500 psi structural concrete One or more layers, any combination Prelim. Attached Elastobase or Elastobase P with poly top surface Roofgrip #14 with OMG Flat Bottom Plates (square), Dekfast #14 with Dekfast Hex (aka, Dekfast PLT-H-2-7/8) or Trufast #14 HD with Trufast 3” Metal Insulation Plate 12-inch o.c. at min. 4-inch lap and 12-inch o.c. at two, equally spaced, staggered center rows SBS-SA SBS-SA, APP- SA, SBS-TA or APP-TA -52.5* S-81. Min. 22 ga., type B, Grade 33 steel or min. 2,500 psi structural concrete One or more layers, any combination Prelim. Attached Elastobase or Elastobase P with poly top surface Roofgrip #12 (steel only) or #14 with OMG Flat Bottom Plates (square) 12-inch o.c. at min. 4-inch lap and 12-inch o.c. at two, equally spaced, staggered center rows SBS-SA SBS-SA, APP- SA, SBS-TA or APP-TA -60.0* HYBRID SYSTEMS WITH SELF-ADHERING APP BASE PLY: S-82. Min. 22 ga., type B, Grade 33 steel or min. 2,500 psi structural concrete One or more layers, any combination Prelim. Attached Elastobase or Elastobase P with poly top surface Roofgrip #14 with OMG Flat Bottom Plates (square), Dekfast #14 with Dekfast Hex (aka, Dekfast PLT-H-2-7/8) or Trufast #14 HD with Trufast 3” Metal Insulation Plate 12-inch o.c. at min. 4-inch lap and 12-inch o.c. at two, equally spaced, staggered center rows APP-SA-H APP-TA -52.5* NEMO|etc. NEMO ETC, LLC Evaluation Report P9290.02.08-R25 for FL1654-R27 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 25: 09/30/2020 ©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 52 of 94 TABLE 2C: STEEL OR STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER SYSTEM TYPE D-2: INSULATED, MECHANICALLY ATTACHED BASE SHEET, BONDED ROOF COVER System No. Deck (Note 1) Insulation Layer(s) (Note 13) Base Sheet Roof Cover (Note 15) MDP (psf) Type Attach Type Fasten (Note 11) Attach Base Ply Cap Ply S-83. Min. 22 ga., type B, Grade 33 steel or min. 2,500 psi structural concrete One or more layers, any combination Prelim. Attached Elastobase or Elastobase P with poly top surface Roofgrip #12 (steel only) or #14 with OMG Flat Bottom Plates (square) 12-inch o.c. at min. 4-inch lap and 12-inch o.c. at two, equally spaced, staggered center rows APP-SA-H APP-TA -60.0* HYBRID SYSTEMS WITH SELF-ADHERING SBS BASE PLY: S-84. Min. 22 ga., type B, Grade 33 steel or min. 2,500 psi structural concrete One or more layers, any combination Prelim. Attached Elastobase or Elastobase P with poly top surface Roofgrip #14 with OMG Flat Bottom Plates (square), Dekfast #14 with Dekfast Hex (aka, Dekfast PLT-H-2-7/8) or Trufast #14 HD with Trufast 3” Metal Insulation Plate 12-inch o.c. at min. 4-inch lap and 12-inch o.c. at two, equally spaced, staggered center rows SBS-SA-H SBS-TA -52.5* S-85. Min. 22 ga., type B, Grade 33 steel or min. 2,500 psi structural concrete One or more layers, any combination Prelim. Attached Elastobase or Elastobase P with poly top surface Roofgrip #12 (steel only) or #14 with OMG Flat Bottom Plates (square) 12-inch o.c. at min. 4-inch lap and 12-inch o.c. at two, equally spaced, staggered center rows SBS-SA-H SBS-TA -60.0* COLD-APPLIED BASE PLY: S-86. Min. 22 ga., type B, Grade 33 steel or min. 2,500 psi structural concrete One or more layers, any combination Loose laid Elastobase Trufast #12 DP (steel only), #14 HD or #15 EHD with Trufast 3” Metal Insulation Plate 12-inch o.c. at min. 4-inch lap and 12-inch o.c. at one staggered center row (Optional) SBS-CA1, SBS- CA2 SBS-CA1, SBS-CA2, APP-CA1 -45.0* S-87. Min. 22 ga., type B, Grade 33 steel or min. 2,500 psi structural concrete One or more layers, any combination Loose laid Elastovent Trufast #12 DP (steel only), #14 HD or #15 EHD with Trufast 3” Metal Insulation Plate 12-inch o.c. at min. 4-inch lap and 12-inch o.c. at one staggered center row (Optional) SBS-CA1 SBS-CA1, APP-CA1 -45.0* S-88. Min. 22 ga., type B, Grade 33 steel or min. 2,500 psi structural concrete One or more layers, any combination Loose laid Elastobase Trufast #12 DP (steel only), #14 HD or #15 EHD with Trufast 3” Metal Insulation Plate 12-inch o.c. at min. 4-inch lap and 12-inch o.c. at two, equally spaced, staggered center rows (Optional) SBS-CA1, SBS- CA2 SBS-CA1, SBS-CA2, APP-CA1 -67.5 S-89. Min. 22 ga., type B, Grade 33 steel or min. 2,500 psi structural concrete One or more layers, any combination Loose laid Elastovent Trufast #12 DP (steel only), #14 HD or #15 EHD with Trufast 3” Metal Insulation Plate 12-inch o.c. at min. 4-inch lap and 12-inch o.c. at two, equally spaced, staggered center rows (Optional) SBS-CA1 SBS-CA1, APP-CA1 -67.5 S-90. Min. 22 ga., type B, Grade 40 steel or min. 2,500 psi structural concrete One or more layers, any combination Loose- laid Elastoflex S6 Trufast #12 DP (steel only) or Trufast #14 HD (steel or concrete) with Trufast 3” Metal Insulation Plate 6-inch o.c. at min. 4-inch lap and 6-inch o.c. at one staggered center row (Optional) Elastoflex S6 applied in PG350 at 1.5- 2.0 gal/square SBS-CA1 -75.0* NEMO|etc. NEMO ETC, LLC Evaluation Report P9290.02.08-R25 for FL1654-R27 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 25: 09/30/2020 ©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 53 of 94 TABLE 2C: STEEL OR STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER SYSTEM TYPE D-2: INSULATED, MECHANICALLY ATTACHED BASE SHEET, BONDED ROOF COVER System No. Deck (Note 1) Insulation Layer(s) (Note 13) Base Sheet Roof Cover (Note 15) MDP (psf) Type Attach Type Fasten (Note 11) Attach Base Ply Cap Ply S-91. Min. 22 ga., type B, Grade 40 steel or min. 2,500 psi structural concrete One or more layers, any combination Loose- laid Elastoflex S6 Trufast #12 DP (steel only) or Trufast #14 HD (steel or concrete) with Trufast 3” Metal Insulation Plate 12-inch o.c. at min. 4-inch lap and 12-inch o.c. at two, equally spaced, staggered center rows (Optional) Elastoflex S6 applied in PG350 at 1.5- 2.0 gal/square SBS-CA1 -90.0* TABLE 2D: STEEL OR STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER SYSTEM TYPE D-2: INSULATED, MECHANICALLY ATTACHED VELOCIFLEX, BONDED ROOF COVER System No. Deck (Note 1) Insulation Layer(s) (Note 13) Base Sheet Roof Cover (Note 15) MDP (psf) Type Attach Type Fasten (Note 11) Attach Base Ply Cap Ply ASPHALT- OR TORCH-APPLIED BASE PLY: S-92. Min. 22 ga., type B, 40 ksi steel or min. 2,500 psi structural concrete One or more layers, any combination Prelim. Attached Elastoflex S6 Trufast #14 HD with Trufast 2” Barbed Seam Plates 18-inch o.c. within the 4-inch wide, torch-sealed or heat- welded side laps (Optional) SBS-TA SBS-TA -30.0 S-93. Min. 22 ga., type B, Grade 40 steel or min. 2,500 psi structural concrete One or more layers, any combination Prelim. Attached Elastoshield HT Trufast #15 EHD (steel only) or Trufast #14 HD (concrete only) with Trufast 2.4” Barbed Metal Seam Plates, Trufast 2.4” Scoop Seam Plates or Trufast 2.75” Barbed Metal Seam Plates or Dekfast #15 with Dekfast Galvalume Steel 1-1/2” x 2-3/4” Oval Barbed Plate (aka, Dekfast PLT-O2- 3/4-12B) or Dekfast Galvalume Steel 2-3/8” Round Barbed Plate (aka, Dekfast PLT-R-2-3/8-6B) 18-inch o.c. within the 5-inch wide, torch-sealed or heat- welded side laps (Optional) SBS-TA SBS-TA -37.5 S-94. Min. 22 ga., type B, 33 ksi steel or min. 2,500 psi structural concrete One or more layers, any combination Prelim. Attached Elastoflex S6 Trufast #15 EHD (steel only) or Trufast #14 HD (concrete only) with Trufast 2.4” Scoop Seam Plates or Trufast 2.75” Barbed Metal Seam Plates 12-inch o.c. within the 5-inch wide, torch-sealed or heat- welded side laps (Optional) SBS-TA SBS-TA -45.0 S-95. Min. 22 ga., type B, 33 ksi steel or min. 2,500 psi structural concrete One or more layers, any combination Prelim. Attached Elastoflex S6 Trufast #15 EHD (steel only) or Trufast #14 HD (concrete only) with Trufast 2.75” Barbed Metal Seam Plates 6-inch o.c. within the 5-inch wide, torch-sealed or heat- welded side laps (Optional) SBS-TA SBS-TA -60.0 S-96. Min. 22 ga., type B, Grade 40 steel or min. 2,500 psi structural concrete One or more layers, any combination Prelim. Attached Elastoflex S6 HP Trufast #15 EHD (steel only) or Trufast #14 HD (concrete only) with Trufast 2.75” Barbed Metal Seam Plates 18-inch o.c. within the 5-inch wide, torch-sealed or heat- welded side laps (Optional) SBS-TA SBS-TA (D6164 only) -60.0 S-97. Min. 22 ga., type B, 33 ksi steel or min. 2,500 psi structural concrete One or more layers, any combination Prelim. Attached Elastoflex S6 HP Trufast #15 EHD (steel only) or Trufast #14 HD (concrete only) with Trufast 2.75” Barbed Metal Seam Plates 12-inch o.c. within the 5-inch wide, torch-sealed or heat- welded side laps (Optional) SBS-TA SBS-TA (D6164 only) -82.5 NEMO|etc. NEMO ETC, LLC Evaluation Report P9290.02.08-R25 for FL1654-R27 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 25: 09/30/2020 ©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 54 of 94 TABLE 2D: STEEL OR STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER SYSTEM TYPE D-2: INSULATED, MECHANICALLY ATTACHED VELOCIFLEX, BONDED ROOF COVER System No. Deck (Note 1) Insulation Layer(s) (Note 13) Base Sheet Roof Cover (Note 15) MDP (psf) Type Attach Type Fasten (Note 11) Attach Base Ply Cap Ply S-98. Min. 22 ga., type B, 33 ksi steel or min. 2,500 psi structural concrete One or more layers, any combination Prelim. Attached Elastoshield HT Trufast #15 EHD (steel only) or Trufast #14 HD (concrete only) with Trufast 2.4” Barbed Metal Seam Plates, Trufast 2.4” Scoop Seam Plates or Trufast 2.75” Barbed Metal Seam Plates or Dekfast #15 with Dekfast Galvalume Steel 1-1/2” x 2-3/4” Oval Barbed Plate (aka, Dekfast PLT-O2- 3/4-12B) or Dekfast Galvalume Steel 2-3/8” Round Barbed Plate (aka, Dekfast PLT-R-2-3/8-6B) 12-inch o.c. within the 5-inch wide, torch-sealed or heat- welded side laps (Optional) SBS-TA SBS-TA (D6164 only) -82.5 S-99. Min. 22 ga., type B, Grade 80 steel One or more layers, any combination Prelim. Attached Polyflex Dekfast #15 HS with Dekfast Galvalume Steel 2- 3/8” Round Barbed Plate (aka, Dekfast PLT-R-2- 3/8-6B) 12-inch o.c. within the 5-inch wide, torch-sealed side lap (Optional) APP-TA SBS-TA, APP- TA -82.5 S-100. Min. 22 ga., type B, Grade 80 steel or min. 2,500 psi structural concrete One or more layers, any combination Prelim. Attached Polybond or Polyflex Trufast #15 EHD (steel only) or Trufast #14 HD (concrete only) with Trufast 2.4 in. Barbed Seam Plates 12-inch o.c. within the 6-inch wide, torch-sealed side lap (Optional) APP-TA SBS-TA, APP- TA -82.5 S-101. Min. 22 ga., type B, 40 ksi steel or min. 2,500 psi structural concrete One or more layers, any combination Prelim. Attached Elastoshield HT Trufast #15 EHD (steel only) or Trufast #14 HD (concrete only) with Trufast 2.4” Barbed Metal Seam Plates, Trufast 2.4” Scoop Seam Plates or Trufast 2.75” Barbed Metal Seam Plates or Dekfast #15 with Dekfast Galvalume Steel 1-1/2” x 2-3/4” Oval Barbed Plate (aka, Dekfast PLT-O2- 3/4-12B) or Dekfast Galvalume Steel 2-3/8” Round Barbed Plate (aka, Dekfast PLT-R-2-3/8-6B) 6-inch o.c. within the 5-inch wide, torch-sealed or heat- welded side laps (Optional) SBS-TA SBS-TA (D6164 only) -97.5 S-102. Min. 22 ga., type B, Grade 40 steel or min. 2,500 psi structural concrete One or more layers, any combination Prelim. Attached Elastoflex S6 HP Trufast #15 EHD (steel only) or Trufast #14 HD (concrete only) with Trufast 2.75” Barbed Metal Seam Plates 6-inch o.c. within the 5-inch wide, torch-sealed or heat- welded side laps (Optional) SBS-TA SBS-TA (D6164 only) -135.0 COLD-APPLIED BASE PLY: S-103. Min. 22 ga., type B, 40 ksi steel or min. 2,500 psi structural concrete One or more layers, any combination Prelim. Attached Elastoflex S6 HP Trufast #15 EHD (steel only) or Trufast #14 HD (concrete only) with Trufast 2.75” Barbed Metal Seam Plates 18-inch o.c. within the 5-inch wide, torch-sealed or heat- welded side laps (Optional) Elastoflex S6 applied in PG350 at 1.5- 2.0 gal/square SBS-CA1 -60.0 Note: When extrapolating base sheet attachment for this system for elevated pressure zones, any additional fastener rows installed in the center of the sheet shall be stripped-in with minimum 6-inch wide strips of torch-applied, sand-top-surfaced, Polyglass SBS modified bitumen membrane prior to placement of subsequent Base Ply or Cap Ply membranes in PG350 adhesive. NEMO|etc. NEMO ETC, LLC Evaluation Report P9290.02.08-R25 for FL1654-R27 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 25: 09/30/2020 ©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 55 of 94 TABLE 2D: STEEL OR STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER SYSTEM TYPE D-2: INSULATED, MECHANICALLY ATTACHED VELOCIFLEX, BONDED ROOF COVER System No. Deck (Note 1) Insulation Layer(s) (Note 13) Base Sheet Roof Cover (Note 15) MDP (psf) Type Attach Type Fasten (Note 11) Attach Base Ply Cap Ply S-104. Min. 22 ga., type B, 40 ksi steel or min. 2,500 psi structural concrete One or more layers, any combination Prelim. Attached Elastoflex S6 HP Trufast #15 EHD (steel only) or Trufast #14 HD (concrete only) with Trufast 2.75” Barbed Metal Seam Plates 12-inch o.c. within the 5-inch wide, torch-sealed or heat- welded side laps (Optional) Elastoflex S6 applied in PG350 at 1.5- 2.0 gal/square SBS-CA1 -82.5 Note: When extrapolating base sheet attachment for this system for elevated pressure zones, any additional fastener rows installed in the center of the sheet shall be stripped-in with minimum 6-inch wide strips of torch-applied, sand-top-surfaced, Polyglass SBS modified bitumen membrane prior to placement of subsequent Base Ply or Cap Ply membranes in PG350 adhesive. NEMO|etc. NEMO ETC, LLC Evaluation Report P9290.02.08-R25 for FL1654-R27 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 25: 09/30/2020 ©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 56 of 94 TABLE 3A: STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF) SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER NOTE: FOR VAPOR BARRIER OPTIONS REFER TO NOTE 16 System No. Deck (Note 1) Primer Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP (psf) Type Attach (Notes 6,7,8) Type Attach (Notes 6,7,8) Base Ply Ply Cap Ply ASPHALT OR TORCH APPLIED BASE PLY: C-1 Structural concrete None Min. 2-inch Polytherm, ACFoam II, Polytherm H or H-Shield D-IS Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board D-IS BP-AA, SBS-AA (Optional) BP-AA, SBS-AA SBS-AA -225.0 C-2 Structural concrete None (Optional) Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, Polytherm H, H-Shield D-IS Min. 0.25-inch DensDeck Prime D-IS SBS-TA, APP- TA (Optional) SBS-TA, APP-TA SBS-TA, APP-TA -282.5 C-3 Structural concrete None (Optional) Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, Polytherm H, H-Shield D-IS Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board or DEXcell FA Glass Mat Roof Board D-IS SBS-TA, APP- TA (Optional) SBS-TA, APP-TA SBS-TA, APP-TA -322.5 C-4 Structural concrete None Min. 2-inch Polytherm, ACFoam II, Polytherm H or H-Shield OB500 Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board OB500 BP-AA, SBS-AA (Optional) BP-AA, SBS-AA SBS-AA -225.0 C-5 Structural concrete None (Optional) Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, Polytherm H, H-Shield OB500 Min. 0.25-inch DensDeck Prime OB500 SBS-TA, APP- TA (Optional) SBS-TA, APP-TA SBS-TA, APP-TA -282.5 C-6 Structural concrete None (Optional) Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, Polytherm H, H-Shield OB500 Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board or DEXcell FA Glass Mat Roof Board OB500 SBS-TA, APP- TA (Optional) SBS-TA, APP-TA SBS-TA, APP-TA -322.5 C-7 Structural concrete None Min. 2-inch Polytherm, ACFoam II, Polytherm H or H-Shield M-OSFA or M-PG1 Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board M-OSFA or M-PG1 BP-AA, SBS-AA (Optional) BP-AA, SBS-AA SBS-AA -225.0 C-8 Structural concrete None (Optional) Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, Polytherm H, H-Shield M-OSFA or M-PG1 Min. 0.25-inch DensDeck Prime M-OSFA or M-PG1 SBS-TA, APP- TA (Optional) SBS-TA, APP-TA SBS-TA, APP-TA -282.5 C-9 Structural concrete None (Optional) Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, Polytherm H, H-Shield M-OSFA or M-PG1 Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board or DEXcell FA Glass Mat Roof Board M-OSFA or M-PG1 SBS-TA, APP- TA (Optional) SBS-TA, APP-TA SBS-TA, APP-TA -322.5 C-10 Structural concrete None Min. 1.5-inch Ultra-Max or Multi-Max FA-3, min. 1.3-inch Polytherm G, ACFoam III or min. 1.0-inch ISO 95+GL, Polytherm H, H- Shield, H-Shield CG or ENRGY 3 CR-20 Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board CR-20 BP-AA, SBS-AA (Optional) BP-AA, SBS-AA SBS-AA -225.0 C-11 Structural concrete None Min. 1.5-inch Ultra-Max or Multi-Max FA-3, min. 1.3-inch Polytherm G, ACFoam III or min. 1.0-inch ISO 95+GL, Polytherm H, H- Shield, H-Shield CG or ENRGY 3 CR-20 Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board CR-20 APP-TA (Optional) APP-TA APP-TA -232.5 NEMO|etc. NEMO ETC, LLC Evaluation Report P9290.02.08-R25 for FL1654-R27 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 25: 09/30/2020 ©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 57 of 94 TABLE 3A: STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF) SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER NOTE: FOR VAPOR BARRIER OPTIONS REFER TO NOTE 16 System No. Deck (Note 1) Primer Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP (psf) Type Attach (Notes 6,7,8) Type Attach (Notes 6,7,8) Base Ply Ply Cap Ply C-12 Structural concrete None (Optional) Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, Polytherm H, H-Shield CR-20 Min. 0.25-inch DensDeck Prime CR-20 SBS-TA, APP- TA (Optional) SBS-TA, APP-TA SBS-TA, APP-TA -282.5 C-13 Structural concrete None (Optional) Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, Polytherm H, H-Shield CR-20 Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board or DEXcell FA Glass Mat Roof Board CR-20 SBS-TA, APP- TA (Optional) SBS-TA, APP-TA SBS-TA, APP-TA -322.5 C-14 Structural concrete None (Optional) Min. 2-inch Polytherm, ACFoam II, Polytherm H or H-Shield OB Classic (full- coverage) Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board OB Classic (full- coverage) BP-AA, SBS-AA (Optional) BP-AA, SBS-AA SBS-AA -225.0 C-15 Structural concrete None (Optional) Min. 2-inch Polytherm, ACFoam II, Polytherm H or H-Shield OB Classic (full- coverage) Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board OB Classic (full- coverage) APP-TA (Optional) APP-TA APP-TA -232.5 C-16 Structural concrete PG100 Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY 3, Polytherm H, H-Shield, H-Shield CG or Multi-Max FA3 Hot asphalt Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board Hot asphalt BP-AA, SBS-AA (Optional) BP-AA, SBS-AA SBS-AA -225.0 C-17 Structural concrete PG100 Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY 3, Polytherm H, H-Shield, H-Shield CG or Multi-Max FA3 Hot asphalt Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board Hot asphalt APP-TA (Optional) APP-TA APP-TA -232.5 C-18 Structural concrete PG100 Min. 0.75-inch Fesco Board (homogeneous) Hot asphalt None N/A (Optional if using AA Ply) BP-AA, SBS-AA (Optional if using AA Base) BP-AA, SBS-AA, SBS-TA or APP-TA SBS-AA, SBS-TA, APP-TA -277.5 C-19 Structural concrete PG100 Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY 3, Polytherm H, H-Shield, H-Shield CG or Multi-Max FA3 Hot asphalt Min. 0.75-inch Fesco Board (homogeneous) Hot asphalt (Optional if using AA Ply) BP-AA, SBS-AA (Optional if using AA Base) BP-AA, SBS-AA, SBS-TA or APP-TA SBS-AA, SBS-TA, APP-TA -290.0 C-20 Structural concrete PG100 Min. 0.5-inch Structodek High Density Fiberboard Roof Insulation Hot asphalt None N/A (Optional if using AA Ply) BP-AA, SBS-AA (Optional if using AA Base) BP-AA, SBS-AA, SBS-TA or APP-TA SBS-AA, SBS-TA, APP-TA -285.0 C-21 Structural concrete PG100 Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY 3, Polytherm H, H-Shield, H-Shield CG or Multi-Max FA3 Hot asphalt Min. 0.5-inch Structodek High Density Fiberboard Roof Insulation Hot asphalt (Optional if using AA Ply) BP-AA, SBS-AA (Optional if using AA Base) BP-AA, SBS-AA, SBS-TA or APP-TA SBS-AA, SBS-TA, APP-TA -480.0 NEMO|etc. NEMO ETC, LLC Evaluation Report P9290.02.08-R25 for FL1654-R27 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 25: 09/30/2020 ©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 58 of 94 TABLE 3A: STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF) SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER NOTE: FOR VAPOR BARRIER OPTIONS REFER TO NOTE 16 System No. Deck (Note 1) Primer Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP (psf) Type Attach (Notes 6,7,8) Type Attach (Notes 6,7,8) Base Ply Ply Cap Ply C-22 Structural concrete PG100 Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY 3, Polytherm H, H-Shield, H-Shield CG or Multi-Max FA3 Hot asphalt Min. 0.25-inch DensDeck Prime Hot asphalt (Optional if using AA Ply) BP-AA, SBS-AA (Optional if using AA Base) BP-AA, SBS-AA, SBS-TA or APP-TA SBS-AA, SBS-TA, APP-TA -480.0 C-23 Structural concrete PG100 Min. 0.25-inch DensDeck Prime Hot asphalt None N/A (Optional if using AA Ply) BP-AA, SBS-AA (Optional if using AA Base) BP-AA, SBS-AA, SBS-TA or APP-TA SBS-AA, SBS-TA, APP-TA -510.0 SELF-ADHERING BASE PLY TO INSULATION: C-24 Structural concrete (Optiona l) PG100 Min. 1.5-inch H-Shield or Multi-Max FA3 D-IS (Optional) additional layers(s) of base insulation D-IS SBS-SA (Optional) SBS-SA, SBS-TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -67.5 C-25 Structural concrete None Min. 1.5-inch Polytherm H, H-Shield D-IS (Optional) additional layers(s) of base insulation D-IS SBS-SA (Optional) SBS-TA, APP-TA SBS-TA, APP-TA -122.5 C-26 Structural concrete (Optiona l) PG100 Min. 1.5-inch Polytherm, ACFoam II or ENRGY 3 D-IS (Optional) additional layers(s) of base insulation D-IS SBS-SA (Optional) SBS-SA, SBS-TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -135.0 C-27 Structural concrete None Min. 1.5-inch, min. 1.5 pcf Insulfoam D-IS (Optional) additional layers of base insulation D-IS SBS-SA (Optional) SBS-SA SBS-SA, APP-SA -157.5 C-28 Structural concrete None Min. 1.5-inch, min. 2.0 pcf Insulfoam OB500 (Optional) additional layers of base insulation OB500 SBS-SA (Optional) SBS-SA SBS-SA, APP-SA -120.0 C-29 Structural concrete None Min. 1.5-inch Polytherm, ACFoam II OB500 (Optional) additional layers(s) of base insulation OB500 SBS-SA (Optional) SBS-TA, APP-TA SBS-TA, APP-TA -122.5 C-30 Structural concrete None Min. 1.5-inch ENRGY 3 OB500 (Optional) additional layers(s) of base insulation OB500 SBS-SA (Optional) SBS-SA, SBS-TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -127.5 C-31 Structural concrete None Min. 1.5-inch Polytherm H or H-Shield OB500 (Optional) additional layers(s) of base insulation OB500 SBS-SA (Optional) SBS-SA, SBS-TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -150.0 C-32 Structural concrete None Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, Polytherm H, H- Shield M-OSFA or M-PG1 (Optional) additional layers(s) of base insulation M-OSFA or M-PG1 SBS-SA (Optional) SBS-TA, APP-TA SBS-TA, APP-TA -122.5 C-33 Structural concrete None Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3, H-Shield or Multi-Max FA3 M-OSFA (Optional) additional layers(s) of base insulation M-OSFA SBS-SA (Optional) SBS-SA, SBS-TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -232.5 C-34 Structural concrete None Min. 1-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, EnergyGuard Polyiso Insulation, ENRGY 3, Polytherm H, H-Shield, ISO 95+ GL, Multi-Max FA3, RESISTA or UltraMax. M-OSFA or M-PG1 (Optional) additional layers(s) of base insulation, optionally primed with POLYBRITE 745 or WB3000 M-OSFA or M-PG1 SBS-SA None SBS-CA1, SBS- CA2 -290.0 NEMO|etc. NEMO ETC, LLC Evaluation Report P9290.02.08-R25 for FL1654-R27 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 25: 09/30/2020 ©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 59 of 94 TABLE 3A: STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF) SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER NOTE: FOR VAPOR BARRIER OPTIONS REFER TO NOTE 16 System No. Deck (Note 1) Primer Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP (psf) Type Attach (Notes 6,7,8) Type Attach (Notes 6,7,8) Base Ply Ply Cap Ply C-35 Structural concrete None Min. 1.5-inch Polytherm, ACFoam II, Polytherm H, H-Shield CR-20 (Optional) additional layers(s) of base insulation CR-20 SBS-SA (Optional) SBS-TA, APP-TA SBS-TA, APP-TA -122.5 C-36 Structural concrete None Min. 1.5-inch, min. 2.0 pcf Insulfoam CR-20 (Optional) additional layers of base insulation CR-20 SBS-SA (Optional) SBS-SA SBS-SA, APP-SA -240.0 C-37 Structural concrete None Min. 2-inch Polytherm, ACFoam II, Polytherm H or H-Shield OB Classic (full- coverage) (Optional) additional layers(s) of base insulation OB Classic (full- coverage) SBS-SA (Optional) SBS-SA, SBS-TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -270.0 C-38 Structural concrete PG100 Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY 3, Polytherm H, H-Shield, H-Shield CG or Multi-Max FA3 Hot asphalt (Optional) additional layers(s) of base insulation Hot asphalt SBS-SA (Optional) SBS-SA, SBS-TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -480.0 HYBRID SYSTEMS WITH SELF-ADHERING APP BASE PLY TO INSULATION: C-39 Structural concrete (Optiona l) PG100 Min. 1.5-inch H-Shield or Multi-Max FA3 D-IS (Optional) additional layers(s) of base insulation D-IS APP-SA-H (Optional) APP-TA APP-TA -67.5 C-40 Structural concrete None Min. 1.5-inch Polytherm H, H-Shield D-IS (Optional) additional layers(s) of base insulation D-IS APP-SA-H (Optional) APP-TA APP-TA -122.5 C-41 Structural concrete (Optiona l) PG100 Min. 1.5-inch Polytherm, ACFoam II or ENRGY 3 D-IS (Optional) additional layers(s) of base insulation D-IS APP-SA-H (Optional) APP-TA APP-TA -135.0 C-42 Structural concrete None Min. 1.5-inch Polytherm, ACFoam II OB500 (Optional) additional layers(s) of base insulation OB500 APP-SA-H (Optional) APP-TA APP-TA -122.5 C-43 Structural concrete None Min. 1.5-inch ENRGY 3 OB500 (Optional) additional layers(s) of base insulation OB500 APP-SA-H (Optional) APP-TA APP-TA -127.5 C-44 Structural concrete None Min. 1.5-inch Polytherm H or H-Shield OB500 (Optional) additional layers(s) of base insulation OB500 APP-SA-H (Optional) APP-TA APP-TA -150.0 C-45 Structural concrete None Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, Polytherm H, H- Shield M-OSFA or M-PG1 (Optional) additional layers(s) of base insulation M-OSFA or M-PG1 APP-SA-H (Optional) APP-TA APP-TA -122.5 C-46 Structural concrete None Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3, H-Shield or Multi-Max FA3 M-OSFA (Optional) additional layers(s) of base insulation M-OSFA APP-SA-H (Optional) APP-TA APP-TA -232.5 C-47 Structural concrete None Min. 1.5-inch Polytherm, ACFoam II, Polytherm H, H-Shield CR-20 (Optional) additional layers(s) of base insulation CR-20 APP-SA-H (Optional) APP-TA APP-TA -122.5 C-48 Structural concrete None Min. 2-inch Polytherm, ACFoam II, Polytherm H or H-Shield OB Classic (full- coverage) (Optional) additional layers(s) of base insulation OB Classic (full- coverage) APP-SA-H (Optional) APP-TA APP-TA -270.0 NEMO|etc. NEMO ETC, LLC Evaluation Report P9290.02.08-R25 for FL1654-R27 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 25: 09/30/2020 ©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 60 of 94 TABLE 3A: STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF) SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER NOTE: FOR VAPOR BARRIER OPTIONS REFER TO NOTE 16 System No. Deck (Note 1) Primer Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP (psf) Type Attach (Notes 6,7,8) Type Attach (Notes 6,7,8) Base Ply Ply Cap Ply C-49 Structural concrete PG100 Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY 3, Polytherm H, H-Shield, H-Shield CG or Multi-Max FA3 Hot asphalt (Optional) additional layers(s) of base insulation Hot asphalt APP-SA-H (Optional) APP-TA APP-TA -480.0 HYBRID SYSTEMS WITH SELF-ADHERING SBS BASE PLY TO INSULATION: C-50 Structural concrete (Optiona l) PG100 Min. 1.5-inch H-Shield or Multi-Max FA3 D-IS (Optional) additional layers(s) of base insulation D-IS SBS-SA-H (Optional) SBS-TA SBS-TA -67.5 C-51 Structural concrete None Min. 1.5-inch Polytherm H, H-Shield D-IS (Optional) additional layers(s) of base insulation D-IS SBS-SA-H (Optional) SBS-TA SBS-TA -122.5 C-52 Structural concrete (Optiona l) PG100 Min. 1.5-inch Polytherm, ACFoam II or ENRGY 3 D-IS (Optional) additional layers(s) of base insulation D-IS SBS-SA-H (Optional) SBS-TA SBS-TA -135.0 C-53 Structural concrete None Min. 1.5-inch Polytherm, ACFoam II OB500 (Optional) additional layers(s) of base insulation OB500 SBS-SA-H (Optional) SBS-TA SBS-TA -122.5 C-54 Structural concrete None Min. 1.5-inch ENRGY 3 OB500 (Optional) additional layers(s) of base insulation OB500 SBS-SA-H (Optional) SBS-TA SBS-TA -127.5 C-55 Structural concrete None Min. 1.5-inch Polytherm H or H-Shield OB500 (Optional) additional layers(s) of base insulation OB500 SBS-SA-H (Optional) SBS-TA SBS-TA -150.0 C-56 Structural concrete None Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, Polytherm H, H- Shield M-OSFA or M-PG1 (Optional) additional layers(s) of base insulation M-OSFA or M-PG1 SBS-SA-H (Optional) SBS-TA SBS-TA -122.5 C-57 Structural concrete None Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3, H-Shield or Multi-Max FA3 M-OSFA (Optional) additional layers(s) of base insulation M-OSFA SBS-SA-H (Optional) SBS-TA SBS-TA -232.5 C-58 Structural concrete None Min. 1.5-inch Polytherm, ACFoam II, Polytherm H, H-Shield CR-20 (Optional) additional layers(s) of base insulation CR-20 SBS-SA-H (Optional) SBS-TA SBS-TA -122.5 C-59 Structural concrete None Min. 2-inch Polytherm, ACFoam II, Polytherm H or H-Shield OB Classic (full- coverage) (Optional) additional layers(s) of base insulation OB Classic (full- coverage) SBS-SA-H (Optional) SBS-TA SBS-TA -270.0 C-60 Structural concrete PG100 Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY 3, Polytherm H, H-Shield, H-Shield CG or Multi-Max FA3 Hot asphalt (Optional) additional layers(s) of base insulation Hot asphalt SBS-SA-H (Optional) SBS-TA SBS-TA -480.0 SELF-ADHERING BASE PLY TO COVERBOARD: NEMO|etc. NEMO ETC, LLC Evaluation Report P9290.02.08-R25 for FL1654-R27 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 25: 09/30/2020 ©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 61 of 94 TABLE 3A: STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF) SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER NOTE: FOR VAPOR BARRIER OPTIONS REFER TO NOTE 16 System No. Deck (Note 1) Primer Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP (psf) Type Attach (Notes 6,7,8) Type Attach (Notes 6,7,8) Base Ply Ply Cap Ply C-61 Structural concrete None Min. 1.5-inch Multi-Max FA3 D-IS Min. 0.25-inch DensDeck Prime or SECUROCK Gypsum-Fiber Roof Board D-IS SBS-SA (Optional) SBS-SA, SBS-TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -67.5 C-62 Structural concrete None Min. 1.5-inch, min. 2.0 pcf Insulfoam, Polytherm, ACFoam II, ENRGY 3, Polytherm H or H-Shield D-IS Min. 0.25-inch DensDeck Prime D-IS SBS-SA (Optional) SBS-SA SBS-SA, APP-SA -72.5 C-63 Structural concrete None Min. 1.5-inch, min. 2.0 pcf Insulfoam D-IS Min. 0.25-inch DensDeck, DensDeck Prime D-IS SBS-SA (Optional) SBS-TA, APP-TA SBS-TA, APP-TA -120.0 C-64 Structural concrete None (Optional) Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, Polytherm H, H-Shield D-IS Min. 0.25-inch DensDeck Prime optionally primed with POLYBRITE 745 or WB3000 D-IS SBS-SA (Optional) SBS-TA, APP-TA SBS-TA, APP-TA -282.5 C-65 Structural concrete None (Optional) Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, Polytherm H, H-Shield D-IS Min. 0.25-inch DEXcell FA Glass Mat Roof Board D-IS SBS-SA (Optional) SBS-TA, APP-TA SBS-TA, APP-TA -322.5 C-66 Structural concrete None (Optional) Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, Polytherm H, H-Shield D-IS Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board optionally primed with POLYBRITE 745 or WB3000 D-IS SBS-SA (Optional) SBS-SA, SBS-TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -322.5 C-67 Structural concrete None Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3, H-Shield or ISO 95+GL OB500 Min. 0.25-inch DensDeck Prime OB500 SBS-SA (Optional) SBS-SA SBS-SA, APP-SA -72.5 C-68 Structural concrete None Min. 1.5-inch ENRGY 3 OB500 Min. 0.25-inch DensDeck, DensDeck Prime OB500 SBS-SA (Optional) SBS-TA, APP-TA SBS-TA, APP-TA -127.5 C-69 Structural concrete None Min. 1.5-inch Polytherm, ACFoam II, H- Shield or ISO 95+GL OB500 Min. 0.25-inch DensDeck, DensDeck Prime OB500 SBS-SA (Optional) SBS-TA, APP-TA SBS-TA, APP-TA -150.0 C-70 Structural concrete None (Optional) Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, Polytherm H, H-Shield OB500 Min. 0.25-inch DensDeck Prime OB500 SBS-SA (Optional) SBS-TA, APP-TA SBS-TA, APP-TA -282.5 C-71 Structural concrete None (Optional) Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, Polytherm H, H-Shield OB500 Min. 0.25-inch DEXcell FA Glass Mat Roof Board OB500 SBS-SA (Optional) SBS-TA, APP-TA SBS-TA, APP-TA -322.5 C-72 Structural concrete None (Optional) Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, Polytherm H, H-Shield OB500 Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board optionally primed with POLYBRITE 745 or WB3000 OB500 SBS-SA (Optional) SBS-SA, SBS-TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -322.5 NEMO|etc. NEMO ETC, LLC Evaluation Report P9290.02.08-R25 for FL1654-R27 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 25: 09/30/2020 ©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 62 of 94 TABLE 3A: STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF) SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER NOTE: FOR VAPOR BARRIER OPTIONS REFER TO NOTE 16 System No. Deck (Note 1) Primer Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP (psf) Type Attach (Notes 6,7,8) Type Attach (Notes 6,7,8) Base Ply Ply Cap Ply C-73 Structural concrete None Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3, H-Shield or Multi-Max FA3 M-OSFA Min. 0.25-inch DensDeck Prime M-OSFA SBS-SA (Optional) SBS-SA SBS-SA, APP-SA -72.5 C-74 Structural concrete None Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3, H-Shield or Multi-Max FA3 M-OSFA Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board M-OSFA SBS-SA (Optional) SBS-SA, SBS-TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -232.5 C-75 Structural concrete None (Optional) Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, Polytherm H, H-Shield M-OSFA or M-PG1 Min. 0.25-inch DensDeck Prime M-OSFA or M-PG1 SBS-SA (Optional) SBS-TA, APP-TA SBS-TA, APP-TA -282.5 C-76 Structural concrete None (Optional) Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, Polytherm H, H-Shield M-OSFA or M-PG1 Min. 0.25-inch DEXcell FA Glass Mat Roof Board M-OSFA or M-PG1 SBS-SA (Optional) SBS-TA, APP-TA SBS-TA, APP-TA -322.5 C-77 Structural concrete None (Optional) Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, Polytherm H, H-Shield M-OSFA or M-PG1 Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board optionally primed with POLYBRITE 745 or WB3000 M-OSFA or M-PG1 SBS-SA (Optional) SBS-SA, SBS-TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -322.5 C-78 Structural concrete None Min. 1.5-inch, min. 2.0 pcf Insulfoam, Min. 2-inch Polytherm, ACFoam II, min. 1.5-inch Ultra-Max or Multi-Max FA-3, min. 1.3-inch Polytherm G, ACFoam III or min. 1.0-inch ISO 95+GL, Polytherm H, H-Shield, H-Shield CG or ENRGY 3 CR-20 Min. 0.25-inch DensDeck, DensDeck Prime CR-20 SBS-SA (Optional) SBS-SA SBS-SA, APP-SA -72.5 C-79 Structural concrete None Min. 1.5-inch, min. 2.0 pcf Insulfoam, Min. 1.5-inch Ultra-Max or Multi-Max FA-3, min. 1.3-inch Polytherm G, ACFoam III or min. 1.0-inch ISO 95+GL, Polytherm H, H-Shield, H-Shield CG or ENRGY 3 CR-20 Min. 0.25-inch DensDeck, DensDeck Prime CR-20 SBS-SA (Optional) SBS-TA, APP-TA SBS-TA, APP-TA -240.0 C-80 Structural concrete None Min. 1.5-inch Ultra-Max or Multi-Max FA-3, min. 1.3-inch Polytherm G, ACFoam III or min. 1.0-inch ISO 95+GL, Polytherm H, H- Shield, H-Shield CG or ENRGY 3 CR-20 Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board CR-20 SBS-SA (Optional) SBS-SA, SBS-TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -240.0 C-81 Structural concrete None (Optional) Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, Polytherm H, H-Shield CR-20 Min. 0.25-inch DensDeck Prime CR-20 SBS-SA (Optional) SBS-TA, APP-TA SBS-TA, APP-TA -282.5 C-82 Structural concrete None (Optional) Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, Polytherm H, H-Shield CR-20 Min. 0.25-inch DEXcell FA Glass Mat Roof Board CR-20 SBS-SA (Optional) SBS-TA, APP-TA SBS-TA, APP-TA -322.5 NEMO|etc. NEMO ETC, LLC Evaluation Report P9290.02.08-R25 for FL1654-R27 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 25: 09/30/2020 ©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 63 of 94 TABLE 3A: STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF) SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER NOTE: FOR VAPOR BARRIER OPTIONS REFER TO NOTE 16 System No. Deck (Note 1) Primer Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP (psf) Type Attach (Notes 6,7,8) Type Attach (Notes 6,7,8) Base Ply Ply Cap Ply C-83 Structural concrete None (Optional) Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, Polytherm H, H-Shield CR-20 Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board optionally primed with POLYBRITE 745 or WB3000 CR-20 SBS-SA (Optional) SBS-SA, SBS-TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -322.5 C-84 Structural concrete None Min. 2-inch Polytherm, ACFoam II, Polytherm H or H-Shield OB Classic (full- coverage) Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board OB Classic (full- coverage) SBS-SA (Optional) SBS-SA, SBS-TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -350.0 C-85 Structural concrete PG100 Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY 3, Polytherm H, H-Shield, H-Shield CG or Multi-Max FA3 Hot asphalt Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board Hot asphalt SBS-SA (Optional) SBS-SA, SBS-TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -350.0 HYBRID SYSTEMS WITH SELF-ADHERING APP BASE PLY TO COVERBOARD: C-86 Structural concrete None Min. 1.5-inch Multi-Max FA3 D-IS Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board D-IS APP-SA-H (Optional) APP-TA APP-TA -67.5 C-87 Structural concrete None Min. 1.5-inch, min. 2.0 pcf Insulfoam D-IS Min. 0.25-inch DensDeck, DensDeck Prime D-IS APP-SA-H (Optional) APP-TA APP-TA -120.0 C-88 Structural concrete None (Optional) Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, Polytherm H, H-Shield D-IS Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board optionally primed with POLYBRITE 745 or WB3000 or DEXcell FA Glass Mat Roof Board D-IS APP-SA-H (Optional) APP-TA APP-TA -322.5 C-89 Structural concrete None Min. 1.5-inch ENRGY 3 OB500 Min. 0.25-inch DensDeck, DensDeck Prime OB500 APP-SA-H (Optional) APP-TA APP-TA -127.5 C-90 Structural concrete None Min. 1.5-inch Polytherm, ACFoam II, H- Shield or ISO 95+GL OB500 Min. 0.25-inch DensDeck, DensDeck Prime OB500 APP-SA-H (Optional) APP-TA APP-TA -150.0 C-91 Structural concrete None (Optional) Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, Polytherm H, H-Shield OB500 Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board or DEXcell FA Glass Mat Roof Board OB500 APP-SA-H (Optional) APP-TA APP-TA -322.5 C-92 Structural concrete None (Optional) Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, Polytherm H, H-Shield M-OSFA or M-PG1 Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board or DEXcell FA Glass Mat Roof Board M-OSFA or M-PG1 APP-SA-H (Optional) APP-TA APP-TA -322.5 NEMO|etc. NEMO ETC, LLC Evaluation Report P9290.02.08-R25 for FL1654-R27 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 25: 09/30/2020 ©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 64 of 94 TABLE 3A: STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF) SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER NOTE: FOR VAPOR BARRIER OPTIONS REFER TO NOTE 16 System No. Deck (Note 1) Primer Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP (psf) Type Attach (Notes 6,7,8) Type Attach (Notes 6,7,8) Base Ply Ply Cap Ply C-93 Structural concrete None Min. 1.5-inch, min. 2.0 pcf Insulfoam, Min. 1.5-inch Ultra-Max or Multi-Max FA-3, min. 1.3-inch Polytherm G, ACFoam III or min. 1.0-inch ISO 95+GL, Polytherm H, H-Shield, H-Shield CG or ENRGY 3 CR-20 Min. 0.25-inch DensDeck, DensDeck Prime CR-20 APP-SA-H (Optional) APP-TA APP-TA -240.0 C-94 Structural concrete None Min. 1.5-inch Ultra-Max or Multi-Max FA-3, min. 1.3-inch Polytherm G, ACFoam III or min. 1.0-inch ISO 95+GL, Polytherm H, H- Shield, H-Shield CG or ENRGY 3 CR-20 Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board CR-20 APP-SA-H (Optional) APP-TA APP-TA -240.0 C-95 Structural concrete None (Optional) Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, Polytherm H, H-Shield CR-20 Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board or DEXcell FA Glass Mat Roof Board CR-20 APP-SA-H (Optional) APP-TA APP-TA -322.5 C-96 Structural concrete None Min. 2-inch Polytherm, ACFoam II, Polytherm H or H-Shield OB Classic (full- coverage) Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board OB Classic (full- coverage) APP-SA-H (Optional) APP-TA APP-TA -350.0 C-97 Structural concrete PG100 Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY 3, Polytherm H, H-Shield, H-Shield CG or Multi-Max FA3 Hot asphalt Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board Hot asphalt APP-SA-H (Optional) APP-TA APP-TA -350.0 HYBRID SYSTEMS WITH SELF-ADHERING SBS BASE PLY TO COVERBOARD: C-98 Structural concrete None Min. 1.5-inch Multi-Max FA3 D-IS Min. 0.25-inch DensDeck Prime or SECUROCK Gypsum-Fiber Roof Board D-IS SBS-SA-H (Optional) SBS-TA SBS-TA -67.5 C-99 Structural concrete None Min. 1.5-inch, min. 2.0 pcf Insulfoam D-IS Min. 0.25-inch DensDeck, DensDeck Prime D-IS SBS-SA-H (Optional) SBS-TA SBS-TA -120.0 C-100 Structural concrete None Min. 2-inch Polytherm, ACFoam II, ENRGY- 3, Polytherm H or H-Shield D-IS Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board D-IS SBS-SA-H (Optional) SBS-TA SBS-TA -247.5 C-101 Structural concrete None (Optional) Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, Polytherm H, H-Shield D-IS Min. 0.25-inch DensDeck Prime optionally primed with POLYBRITE 745 or WB3000 D-IS SBS-SA-H (Optional) SBS-TA SBS-TA -282.5 C-102 Structural concrete None (Optional) Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, Polytherm H, H-Shield D-IS Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board optionally primed with POLYBRITE 745 or WB3000 or DEXcell FA Glass Mat Roof Board D-IS SBS-SA-H (Optional) SBS-TA SBS-TA -322.5 NEMO|etc. NEMO ETC, LLC Evaluation Report P9290.02.08-R25 for FL1654-R27 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 25: 09/30/2020 ©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 65 of 94 TABLE 3A: STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF) SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER NOTE: FOR VAPOR BARRIER OPTIONS REFER TO NOTE 16 System No. Deck (Note 1) Primer Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP (psf) Type Attach (Notes 6,7,8) Type Attach (Notes 6,7,8) Base Ply Ply Cap Ply C-103 Structural concrete None Min. 1.5-inch ENRGY 3 OB500 Min. 0.25-inch DensDeck, DensDeck Prime OB500 SBS-SA-H (Optional) SBS-TA SBS-TA -127.5 C-104 Structural concrete None Min. 1.5-inch Polytherm, ACFoam II, H- Shield or ISO 95+GL OB500 Min. 0.25-inch DensDeck, DensDeck Prime OB500 SBS-SA-H (Optional) SBS-TA SBS-TA -150.0 C-105 Structural concrete None Min. 2-inch Polytherm, ACFoam II, ENRGY- 3, Polytherm H or H-Shield OB500 Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board OB500 SBS-SA-H (Optional) SBS-TA SBS-TA -247.5 C-106 Structural concrete None (Optional) Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, Polytherm H, H-Shield OB500 Min. 0.25-inch DensDeck Prime OB500 SBS-SA-H (Optional) SBS-TA SBS-TA -282.5 C-107 Structural concrete None (Optional) Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, Polytherm H, H-Shield OB500 Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board or DEXcell FA Glass Mat Roof Board OB500 SBS-SA-H (Optional) SBS-TA SBS-TA -322.5 C-108 Structural concrete None Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3, H-Shield or Multi-Max FA3 M-OSFA Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board M-OSFA SBS-SA-H (Optional) SBS-TA SBS-TA -232.5 C-109 Structural concrete None Min. 2-inch Polytherm, ACFoam II, ENRGY- 3, Polytherm H or H-Shield M-OSFA Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board M-OSFA SBS-SA-H (Optional) SBS-TA SBS-TA -247.5 C-110 Structural concrete None (Optional) Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, Polytherm H, H-Shield M-OSFA or M-PG1 Min. 0.25-inch DensDeck Prime M-OSFA or M-PG1 SBS-SA-H (Optional) SBS-TA SBS-TA -282.5 C-111 Structural concrete None (Optional) Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, Polytherm H, H-Shield M-OSFA or M-PG1 Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board or DEXcell FA Glass Mat Roof Board M-OSFA or M-PG1 SBS-SA-H (Optional) SBS-TA SBS-TA -322.5 C-112 Structural concrete None Min. 1.5-inch, min. 2.0 pcf Insulfoam, Min. 1.5-inch Ultra-Max or Multi-Max FA-3, min. 1.3-inch Polytherm G, ACFoam III or min. 1.0-inch ISO 95+GL, Polytherm H, H-Shield, H-Shield CG or ENRGY 3 CR-20 Min. 0.25-inch DensDeck, DensDeck Prime CR-20 SBS-SA-H (Optional) SBS-TA SBS-TA -240.0 C-113 Structural concrete None Min. 1.5-inch Ultra-Max or Multi-Max FA-3, min. 1.3-inch Polytherm G, ACFoam III or min. 1.0-inch ISO 95+GL, Polytherm H, H- Shield, H-Shield CG or ENRGY 3 CR-20 Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board CR-20 SBS-SA-H (Optional) SBS-TA SBS-TA -240.0 C-114 Structural concrete None Min. 2-inch Polytherm, ACFoam II, ENRGY- 3, Polytherm H or H-Shield CR-20 Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board CR-20 SBS-SA-H (Optional) SBS-TA SBS-TA -247.5 NEMO|etc. NEMO ETC, LLC Evaluation Report P9290.02.08-R25 for FL1654-R27 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 25: 09/30/2020 ©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 66 of 94 TABLE 3A: STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF) SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER NOTE: FOR VAPOR BARRIER OPTIONS REFER TO NOTE 16 System No. Deck (Note 1) Primer Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP (psf) Type Attach (Notes 6,7,8) Type Attach (Notes 6,7,8) Base Ply Ply Cap Ply C-115 Structural concrete None (Optional) Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, Polytherm H, H-Shield CR-20 Min. 0.25-inch DensDeck Prime CR-20 SBS-SA-H (Optional) SBS-TA SBS-TA -282.5 C-116 Structural concrete None (Optional) Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, Polytherm H, H-Shield CR-20 Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board or DEXcell FA Glass Mat Roof Board CR-20 SBS-SA-H (Optional) SBS-TA SBS-TA -322.5 C-117 Structural concrete None Min. 2-inch Polytherm, ACFoam II, Polytherm H or H-Shield OB Classic (full- coverage) Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board OB Classic (full- coverage) SBS-SA-H (Optional) SBS-TA SBS-TA -350.0 C-118 Structural concrete PG100 Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY 3, Polytherm H, H-Shield, H-Shield CG or Multi-Max FA3 Hot asphalt Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board Hot asphalt SBS-SA-H (Optional) SBS-TA SBS-TA -350.0 COLD-APPLIED BASE PLY: C-119 Structural concrete None Min. 1-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY 3, Polytherm H or H-Shield D-IS Min. 0.25-inch DensDeck Prime, DEXcell FA Glass Mat Roof Board or SECUROCK Gypsum-Fiber Roof Board D-IS SBS-CA1, SBS- CA2 (Optional) SBS-CA1, SBS-CA2 SBS-CA1, SBS- CA2, APP-CA1 -120.0 C-120 Structural concrete None Min. 1-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, Polytherm H or H-Shield D-IS Min. 0.25-inch DensDeck Prime or DEXcell FA Glass Mat Roof Board D-IS SBS-CA1 None SBS-CA1, SBS- CA2, APP-CA1 -127.5 C-121 Structural concrete None Min. 1-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, Polytherm H or H-Shield D-IS Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board D-IS SBS-CA1, SBS- CA2 None SBS-CA1, SBS- CA2, APP-CA1 -127.5 C-122 Structural concrete None Min. 1-inch ENRGY 3, Polytherm H or H- Shield D-IS Min. 0.25-inch DensDeck Prime or SECUROCK Gypsum-Fiber Roof Board D-IS SBS-CA1, SBS- CA2 None SBS-CA1, SBS- CA2 -232.5 C-123 Structural concrete None Min. 1-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, EnergyGuard Polyiso Insulation, ENRGY 3, Polytherm H, H-Shield ISO 95+ GL, Multi-Max FA3, RESISTA or UltraMax or min. 2-inch DECKMATE Plus or DECKMATE Plus FA M-OSFA, M-PG1 Min. 0.25-inch DensDeck, DensDeck Prime, DEXcell FA Glass Mat Roof Board, SECUROCK Gypsum-Fiber Roof Board or SECUROCK Glass-Mat Roof Board, min. 7/16-inch DEXcell Cement Roof Board or min. 0.5-inch SECUROCK Cement Roof Board M-OSFA or M-PG1 SBS-CA1, SBS- CA2 (Optional) SBS-CA1, SBS-CA2 SBS-CA1, SBS- CA2, APP-CA1 -120.0 NEMO|etc. NEMO ETC, LLC Evaluation Report P9290.02.08-R25 for FL1654-R27 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 25: 09/30/2020 ©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 67 of 94 TABLE 3A: STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF) SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER NOTE: FOR VAPOR BARRIER OPTIONS REFER TO NOTE 16 System No. Deck (Note 1) Primer Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP (psf) Type Attach (Notes 6,7,8) Type Attach (Notes 6,7,8) Base Ply Ply Cap Ply C-124 Structural concrete None Min. 1-inch Polytherm or ACFoam II, Polytherm G, ACFoam III, EnergyGuard Polyiso Insulation, ENRGY 3, Polytherm H, H-Shield, ISO 95+ GL, Multi-Max FA3, RESISTA or UltraMax or min. 2-inch DECKMATE Plus or DECKMATE Plus FA M-OSFA, M-PG1 Min. 0.25-inch DensDeck Prime or DEXcell FA Glass Mat Roof Board, min. 7/16-inch DEXcell Cement Roof Board or min. 0.5- inch SECUROCK Cement Roof Board M-OSFA, M-PG1 SBS-CA1 None SBS-CA1, SBS- CA2, APP-CA1 -127.5 C-125 Structural concrete None Min. 1-inch Polytherm or ACFoam II, Polytherm G, ACFoam III, EnergyGuard Polyiso Insulation, ENRGY 3, Polytherm H, H-Shield, ISO 95+ GL, Multi-Max FA3, RESISTA or UltraMax or min. 2-inch DECKMATE Plus or DECKMATE Plus FA M-OSFA, M-PG1 Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board M-OSFA, M-PG1 SBS-CA1, SBS- CA2 None SBS-CA1, SBS- CA2, APP-CA1 -127.5 C-126 Structural concrete None Min. 1-inch Polytherm or ACFoam II, Polytherm G, ACFoam III, EnergyGuard Polyiso Insulation, ENRGY 3, Polytherm H, H-Shield, ISO 95+ GL, Multi-Max FA3, RESISTA or UltraMax or min. 2-inch DECKMATE Plus or DECKMATE Plus FA M-OSFA, M-PG1 Min. 0.25-inch DensDeck, DensDeck Prime, DEXcell FA Glass Mat Roof Board, SECUROCK Gypsum-Fiber Roof Board or SECUROCK Glass-Mat Roof Board, min. 7/16-inch DEXcell Cement Roof Board or min. 0.5-inch SECUROCK Cement Roof Board M-OSFA, M-PG1 SBS-CA1, SBS- CA2 None SBS-CA1, SBS- CA2 -232.5 C-127 Structural concrete None Min. 1-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY 3, Polytherm H, H-Shield or Multi-Max FA3 OB500 Min. 0.25-inch DensDeck Prime, DEXcell FA Glass Mat Roof Board or SECUROCK Gypsum-Fiber Roof Board OB500 SBS-CA1, SBS- CA2 (Optional) SBS-CA1, SBS-CA2 SBS-CA1, SBS- CA2, APP-CA1 -120.0 C-128 Structural concrete None Min. 1-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY 3, Polytherm H, H-Shield or Multi-Max FA3 OB500 Min. 0.25-inch DensDeck Prime or DEXcell FA Glass Mat Roof Board OB500 SBS-CA1 None SBS-CA1, SBS- CA2, APP-CA1 -127.5 C-129 Structural concrete None Min. 1-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY 3, Polytherm H, H-Shield or Multi-Max FA3 OB500 Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board OB500 SBS-CA1, SBS- CA2 None SBS-CA1, SBS- CA2, APP-CA1 -127.5 C-130 Structural concrete None Min. 1-inch Polytherm, ACFoam II, ENRGY 3 or Multi-Max FA3 OB500 Min. 0.25-inch DensDeck Prime, DEXcell FA Glass Mat Roof Board or SECUROCK Gypsum-Fiber Roof Board OB500 SBS-CA1, SBS- CA2 None SBS-CA1, SBS- CA2 -232.5 NEMO|etc. NEMO ETC, LLC Evaluation Report P9290.02.08-R25 for FL1654-R27 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 25: 09/30/2020 ©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 68 of 94 TABLE 3A: STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF) SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER NOTE: FOR VAPOR BARRIER OPTIONS REFER TO NOTE 16 System No. Deck (Note 1) Primer Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP (psf) Type Attach (Notes 6,7,8) Type Attach (Notes 6,7,8) Base Ply Ply Cap Ply C-131 Structural concrete None Min. 1-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY 3, Polytherm H, H-Shield or Multi-Max FA3 CR-20 Min. 0.25-inch DensDeck Prime or SECUROCK Gypsum-Fiber Roof Board CR-20 SBS-CA1, SBS- CA2 (Optional) SBS-CA1, SBS-CA2 SBS-CA1, SBS- CA2, APP-CA1 -120.0 C-132 Structural concrete None Min. 1-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY 3, Polytherm H, H-Shield or Multi-Max FA3 CR-20 Min. 0.25-inch DensDeck Prime or DEXcell FA Glass Mat Roof Board CR-20 SBS-CA1 None SBS-CA1, SBS- CA2, APP-CA1 -127.5 C-133 Structural concrete None Min. 1-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY 3, Polytherm H, H-Shield or Multi-Max FA3 CR-20 Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board CR-20 SBS-CA1, SBS- CA2 None SBS-CA1, SBS- CA2, APP-CA1 -127.5 C-134 Structural concrete None Min. 1-inch ENRGY 3, Polytherm H, H- Shield, Multi-Max FA3 CR-20 Min. 0.25-inch DensDeck Prime or SECUROCK Gypsum-Fiber Roof Board CR-20 SBS-CA1, SBS- CA2 None SBS-CA1, SBS- CA2 -232.5 TABLE 3B: STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF) SYSTEM TYPE F: NON-INSULATED, BONDED BASE SHEET, BONDED ROOF COVER System No. Deck (Note 1) Primer Roof Cover (Note 15) MDP (psf) Base Ply Ply Cap Ply ASPHALT- OR TORCH-APPLIED BASE PLY: C-135 Structural concrete PG100 (Optional) SBS-TA (Optional) SBS-TA SBS-TA -495.0 C-136 Structural concrete PG100 BP-AA (Optional if using asphalt applied Ply) (Optional if using asphalt applied Base) BP-AA, SBS-AA, SBS-TA or APP-TA SBS-AA, SBS-TA, APP-TA -622.5 SELF-ADHERING BASE PLY: C-137 Structural concrete PG100 SBS-SA (Optional) SBS-SA, SBS-TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -315.0 HYBRID SYSTEMS WITH SELF-ADHERING APP BASE PLY: C-138 Structural concrete PG100 APP-SA-H (Optional) APP-TA APP-TA -315.0 HYBRID SYSTEMS WITH SELF-ADHERING SBS BASE PLY: C-139 Structural concrete PG100 SBS-SA-H (Optional) SBS-TA SBS-TA -315.0 COLD-APPLIED BASE PLY: C-140 Structural concrete None SBS-CA1 None SBS-CA1, SBS-CA2, APP-CA1 -105.0 NEMO|etc. NEMO ETC, LLC Evaluation Report P9290.02.08-R25 for FL1654-R27 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 25: 09/30/2020 ©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 69 of 94 TABLE 4A: LIGHTWEIGHT CONCRETE DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF) SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER System No. Deck (Note 1) Lightweight Concrete (Note 14) Base Insulation Layer Coverboard Roof Cover (Note 15) MDP (psf) Type Attach (Notes 6,7,8) Type Attach (Notes 6,7,8) Base Ply Ply Cap Ply CELCORE (FL2037): ASPHALT OR TORCH APPLIED BASE PLY: LWC-1 Structural concrete Min. 200 psi, min. 2-inch Celcore Cellular Concrete Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY 3, ISO 95+ GL, Polytherm H, H-Shield, H-Shield CG, Multi- Max FA3 or min. 2.0 pcf Insulfoam CR-20 Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board CR-20 BP-AA, SBS- AA, APP-TA (Optional) BP- AA, SBS-AA, SBS-TA or APP- TA SBS-AA, SBS- TA, APP-TA -222.5 SELF-ADHERING BASE PLY: LWC-2 Structural concrete Min. 200 psi, min. 2-inch Celcore Cellular Concrete Min. 1.5-inch, min. 2.0 pcf Insulfoam CR-20 (Optional) Additional layers of base insulation CR-20 SBS-SA (Optional) SBS- SA SBS-SA, APP- SA -222.5 LWC-3 Structural concrete Min. 200 psi, min. 2-inch Celcore Cellular Concrete Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY 3, ISO 95+ GL, Polytherm H, H-Shield, H-Shield CG, Multi- Max FA3 CR-20 (Optional) Additional layers of base insulation CR-20 SBS-SA (Optional) SBS- SA, SBS-TA, APP-TA SBS-SA, APP- SA, SBS-TA, APP-TA -222.5 LWC-4 Structural concrete Min. 200 psi, min. 2-inch Celcore Cellular Concrete Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY 3, ISO 95+ GL, Polytherm H, H-Shield, H-Shield CG, Multi- Max FA3 or min. 2.0 pcf Insulfoam CR-20 Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board CR-20 SBS-SA (Optional) SBS- SA, SBS-TA, APP-TA SBS-SA, APP- SA, SBS-TA, APP-TA -222.5 HYBRID SYSTEMS WITH SELF-ADHERING APP BASE PLY: LWC-5 Structural concrete Min. 200 psi, min. 2-inch Celcore Cellular Concrete Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY 3, ISO 95+ GL, Polytherm H, H-Shield, H-Shield CG, Multi- Max FA3 CR-20 (Optional) Additional layers of base insulation CR-20 APP-SA-H (Optional) APP- TA APP-TA -222.5 LWC-6 Structural concrete Min. 200 psi, min. 2-inch Celcore Cellular Concrete Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY 3, ISO 95+ GL, Polytherm H, H-Shield, H-Shield CG, Multi- Max FA3 or min. 2.0 pcf Insulfoam CR-20 Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board CR-20 APP-SA-H (Optional) APP- TA APP-TA -222.5 HYBRID SYSTEMS WITH SELF-ADHERING SBS BASE PLY: LWC-7 Structural concrete Min. 200 psi, min. 2-inch Celcore Cellular Concrete Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY 3, ISO 95+ GL, Polytherm H, H-Shield, H-Shield CG, Multi- Max FA3 CR-20 (Optional) Additional layers of base insulation CR-20 SBS-SA-H (Optional) SBS- TA SBS-TA -222.5 LWC-8 Structural concrete Min. 200 psi, min. 2-inch Celcore Cellular Concrete Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY 3, ISO 95+ GL, Polytherm H, H-Shield, H-Shield CG, Multi- Max FA3 or min. 2.0 pcf Insulfoam CR-20 Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board CR-20 SBS-SA-H (Optional) SBS- TA SBS-TA -222.5 NEMO|etc. NEMO ETC, LLC Evaluation Report P9290.02.08-R25 for FL1654-R27 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 25: 09/30/2020 ©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 70 of 94 TABLE 4A: LIGHTWEIGHT CONCRETE DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF) SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER System No. Deck (Note 1) Lightweight Concrete (Note 14) Base Insulation Layer Coverboard Roof Cover (Note 15) MDP (psf) Type Attach (Notes 6,7,8) Type Attach (Notes 6,7,8) Base Ply Ply Cap Ply ELASTIZELL (FL4994): ASPHALT OR TORCH APPLIED BASE PLY: LWC-9 Structural concrete Min. 200 psi, min 2-inch Range II Elastizell Lightweight Insulating Concrete. Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3, ISO 95+ GL, Polytherm H or H-Shield OB500 Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board OB500 BP-AA, SBS- AA, APP-TA (Optional) BP- AA, SBS-AA, SBS-TA or APP- TA SBS-AA, SBS- TA, APP-TA -225.0 LWC-10 Structural concrete Min. 200 psi, min 2-inch Range II Elastizell Lightweight Insulating Concrete. Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY 3, ISO 95+ GL, Polytherm H, H-Shield, H-Shield CG, Multi- Max FA3 or min. 2.0 pcf Insulfoam CR-20 Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board CR-20 BP-AA, SBS- AA, APP-TA (Optional) BP- AA, SBS-AA, SBS-TA or APP- TA SBS-AA, SBS- TA, APP-TA -180.0 SELF-ADHERING BASE PLY: LWC-11 Structural concrete Min. 200 psi, min 2-inch Range II Elastizell Lightweight Insulating Concrete. Min. 1.5-inch, min. 2.0 pcf Insulfoam OB500 (Optional) Additional layers of base insulation OB500 SBS-SA (Optional) SBS- SA SBS-SA, APP- SA -120.0 LWC-12 Structural concrete Min. 200 psi, min 2-inch Range II Elastizell Lightweight Insulating Concrete. Min. 1.5-inch, min. 2.0 pcf Insulfoam OB500 Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board OB500 SBS-SA (Optional) SBS- SA, SBS-TA, APP-TA SBS-SA, APP- SA, SBS-TA, APP-TA -120.0 LWC-13 Structural concrete Min. 200 psi, min 2-inch Range II Elastizell Lightweight Insulating Concrete. Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3, ISO 95+ GL, Polytherm H or H-Shield OB500 (Optional) Additional layers of base insulation OB500 SBS-SA (Optional) SBS- SA, SBS-TA, APP-TA SBS-SA, APP- SA, SBS-TA, APP-TA -225.0 LWC-14 Structural concrete Min. 200 psi, min 2-inch Range II Elastizell Lightweight Insulating Concrete. Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3, ISO 95+ GL, Polytherm H or H-Shield OB500 Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board OB500 SBS-SA (Optional) SBS- SA, SBS-TA, APP-TA SBS-SA, APP- SA, SBS-TA, APP-TA -225.0 LWC-15 Structural concrete Min. 200 psi, min 2-inch Range II Elastizell Lightweight Insulating Concrete. Min. 1.5-inch, min. 2.0 pcf Insulfoam CR-20 (Optional) Additional layers of base insulation CR-20 SBS-SA (Optional) SBS- SA SBS-SA, APP- SA -180.0 LWC-16 Structural concrete Min. 200 psi, min 2-inch Range II Elastizell Lightweight Insulating Concrete. Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY 3, ISO 95+ GL, Polytherm H, H-Shield, H-Shield CG, Multi- Max FA3 CR-20 (Optional) Additional layers of base insulation CR-20 SBS-SA (Optional) SBS- SA, SBS-TA, APP-TA SBS-SA, APP- SA, SBS-TA, APP-TA -180.0 NEMO|etc. NEMO ETC, LLC Evaluation Report P9290.02.08-R25 for FL1654-R27 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 25: 09/30/2020 ©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 71 of 94 TABLE 4A: LIGHTWEIGHT CONCRETE DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF) SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER System No. Deck (Note 1) Lightweight Concrete (Note 14) Base Insulation Layer Coverboard Roof Cover (Note 15) MDP (psf) Type Attach (Notes 6,7,8) Type Attach (Notes 6,7,8) Base Ply Ply Cap Ply LWC-17 Structural concrete Min. 200 psi, min 2-inch Range II Elastizell Lightweight Insulating Concrete. Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY 3, ISO 95+ GL, Polytherm H, H-Shield, H-Shield CG, Multi- Max FA3 or min. 2.0 pcf Insulfoam CR-20 Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board CR-20 SBS-SA (Optional) SBS- SA, SBS-TA, APP-TA SBS-SA, APP- SA, SBS-TA, APP-TA -180.0 HYBRID SYSTEMS WITH SELF-ADHERING APP BASE PLY: LWC-18 Structural concrete Min. 200 psi, min 2-inch Range II Elastizell Lightweight Insulating Concrete. Min. 1.5-inch, min. 2.0 pcf Insulfoam OB500 Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board OB500 APP-SA-H (Optional) APP- TA APP-TA -120.0 LWC-19 Structural concrete Min. 200 psi, min 2-inch Range II Elastizell Lightweight Insulating Concrete. Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3, ISO 95+ GL, Polytherm H or H-Shield OB500 (Optional) Additional layers of base insulation OB500 APP-SA-H (Optional) APP- TA APP-TA -225.0 LWC-20 Structural concrete Min. 200 psi, min 2-inch Range II Elastizell Lightweight Insulating Concrete. Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3, ISO 95+ GL, Polytherm H or H-Shield OB500 Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board OB500 APP-SA-H (Optional) APP- TA APP-TA -225.0 LWC-21 Structural concrete Min. 200 psi, min 2-inch Range II Elastizell Lightweight Insulating Concrete. Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY 3, ISO 95+ GL, Polytherm H, H-Shield, H-Shield CG, Multi- Max FA3 CR-20 (Optional) Additional layers of base insulation CR-20 APP-SA-H (Optional) APP- TA APP-TA -180.0 LWC-22 Structural concrete Min. 200 psi, min 2-inch Range II Elastizell Lightweight Insulating Concrete. Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY 3, ISO 95+ GL, Polytherm H, H-Shield, H-Shield CG, Multi- Max FA3 or min. 2.0 pcf Insulfoam CR-20 Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board CR-20 APP-SA-H (Optional) APP- TA APP-TA -180.0 HYBRID SYSTEMS WITH SELF-ADHERING SBS BASE PLY: LWC-23 Structural concrete Min. 200 psi, min 2-inch Range II Elastizell Lightweight Insulating Concrete. Min. 1.5-inch, min. 2.0 pcf Insulfoam OB500 Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board OB500 SBS-SA-H (Optional) SBS- TA SBS-TA -120.0 LWC-24 Structural concrete Min. 200 psi, min 2-inch Range II Elastizell Lightweight Insulating Concrete. Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3, ISO 95+ GL, Polytherm H or H-Shield OB500 (Optional) Additional layers of base insulation OB500 SBS-SA-H (Optional) SBS- TA SBS-TA -225.0 NEMO|etc. NEMO ETC, LLC Evaluation Report P9290.02.08-R25 for FL1654-R27 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 25: 09/30/2020 ©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 72 of 94 TABLE 4A: LIGHTWEIGHT CONCRETE DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF) SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER System No. Deck (Note 1) Lightweight Concrete (Note 14) Base Insulation Layer Coverboard Roof Cover (Note 15) MDP (psf) Type Attach (Notes 6,7,8) Type Attach (Notes 6,7,8) Base Ply Ply Cap Ply LWC-25 Structural concrete Min. 200 psi, min 2-inch Range II Elastizell Lightweight Insulating Concrete. Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3, ISO 95+ GL, Polytherm H or H-Shield OB500 Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board OB500 SBS-SA-H (Optional) SBS- TA SBS-TA -225.0 LWC-26 Structural concrete Min. 200 psi, min 2-inch Range II Elastizell Lightweight Insulating Concrete. Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY 3, ISO 95+ GL, Polytherm H, H-Shield, H-Shield CG, Multi- Max FA3 CR-20 (Optional) Additional layers of base insulation CR-20 SBS-SA-H (Optional) SBS- TA SBS-TA -180.0 LWC-27 Structural concrete Min. 200 psi, min 2-inch Range II Elastizell Lightweight Insulating Concrete. Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY 3, ISO 95+ GL, Polytherm H, H-Shield, H-Shield CG, Multi- Max FA3 or min. 2.0 pcf Insulfoam CR-20 Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board CR-20 SBS-SA-H (Optional) SBS- TA SBS-TA -180.0 MEARLCRETE (FL13492): ASPHALT OR TORCH APPLIED BASE PLY: LWC-28 Structural concrete Min. 200 psi, min. 2-inch Mearlcrete Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY 3, ISO 95+ GL, Polytherm H, H-Shield, H-Shield CG, Multi- Max FA3 or min. 2.0 pcf Insulfoam CR-20 Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board CR-20 BP-AA, SBS- AA, APP-TA (Optional) BP- AA, SBS-AA, SBS-TA or APP- TA SBS-AA, SBS- TA, APP-TA -222.5 SELF-ADHERING BASE PLY: LWC-29 Structural concrete Min. 200 psi, min. 2-inch Mearlcrete Min. 1.5-inch, min. 2.0 pcf Insulfoam CR-20 (Optional) Additional layers of base insulation CR-20 SBS-SA (Optional) SBS- SA SBS-SA, APP- SA -222.5 LWC-30 Structural concrete Min. 200 psi, min. 2-inch Mearlcrete Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY 3, ISO 95+ GL, Polytherm H, H-Shield, H-Shield CG, Multi- Max FA3 CR-20 (Optional) Additional layers of base insulation CR-20 SBS-SA (Optional) SBS- SA, SBS-TA, APP-TA SBS-SA, APP- SA, SBS-TA, APP-TA -222.5 LWC-31 Structural concrete Min. 200 psi, min. 2-inch Mearlcrete Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY 3, ISO 95+ GL, Polytherm H, H-Shield, H-Shield CG, Multi- Max FA3 or min. 2.0 pcf Insulfoam CR-20 Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board CR-20 SBS-SA (Optional) SBS- SA, SBS-TA, APP-TA SBS-SA, APP- SA, SBS-TA, APP-TA -222.5 HYBRID SYSTEMS WITH SELF-ADHERING APP BASE PLY: LWC-32 Structural concrete Min. 200 psi, min. 2-inch Mearlcrete Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY 3, ISO 95+ GL, Polytherm H, H-Shield, H-Shield CG, Multi- Max FA3 CR-20 (Optional) Additional layers of base insulation CR-20 APP-SA-H (Optional) APP- TA APP-TA -222.5 NEMO|etc. NEMO ETC, LLC Evaluation Report P9290.02.08-R25 for FL1654-R27 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 25: 09/30/2020 ©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 73 of 94 TABLE 4A: LIGHTWEIGHT CONCRETE DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF) SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER System No. Deck (Note 1) Lightweight Concrete (Note 14) Base Insulation Layer Coverboard Roof Cover (Note 15) MDP (psf) Type Attach (Notes 6,7,8) Type Attach (Notes 6,7,8) Base Ply Ply Cap Ply LWC-33 Structural concrete Min. 200 psi, min. 2-inch Mearlcrete Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY 3, ISO 95+ GL, Polytherm H, H-Shield, H-Shield CG, Multi- Max FA3 or min. 2.0 pcf Insulfoam CR-20 Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board CR-20 APP-SA-H (Optional) APP- TA APP-TA -222.5 HYBRID SYSTEMS WITH SELF-ADHERING SBS BASE PLY: LWC-34 Structural concrete Min. 200 psi, min. 2-inch Mearlcrete Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY 3, ISO 95+ GL, Polytherm H, H-Shield, H-Shield CG, Multi- Max FA3 CR-20 (Optional) Additional layers of base insulation CR-20 SBS-SA-H (Optional) SBS- TA SBS-TA -222.5 LWC-35 Structural concrete Min. 200 psi, min. 2-inch Mearlcrete Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY 3, ISO 95+ GL, Polytherm H, H-Shield, H-Shield CG, Multi- Max FA3 or min. 2.0 pcf Insulfoam CR-20 Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board CR-20 SBS-SA-H (Optional) SBS- TA SBS-TA -222.5 TABLE 4B: LIGHTWEIGHT CONCRETE DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF) SYSTEM TYPE A-2: MECHANICALLY ATTACHED ANCHOR SHEET, BONDED INSULATION, BONDED ROOF COVER System No. Deck (Note 1) Lightweight Concrete (Note 14) Anchor Sheet Base Insulation Top Insulation Roof Cover (Note 15) MDP (psf) Type Fasten (Note 11) Attach Type Attach (Notes 6,7,8) Type Attach (Notes 6,7,8) Base Ply Ply Cap Ply LWC-36 Min. 22 ga., Type B, vented steel at max. 5 ft spans Min. 300 psi, min. 2- inch Celcore Cellular Concrete, Elastizell Lightweight Insulating Concrete or Mearlcrete GAFGLAS #75 or Elastovent OMG CR BSF 7-inch o.c. at min. 4-inch lap and 7-inch o.c. at two, equally spaced center rows (Optional) Min. 1.5-inch Polytherm, ACFoam II, Polytherm H, H- Shield, Multi-Max FA3 or Polytherm HA Min. 1.5-inch Thermaroof Composite, Polytherm Composite, or min. 0.5- inch Structodek High Density Fiberboard Roof Insulation or min. 0.75- inch Fesco Board (homogeneous) HA (Optional if using AA Ply) BP-AA, SBS-AA (Optional if using AA Base) BP- AA, SBS-AA, SBS-TA or APP-TA SBS-AA, SBS-TA, APP-TA -45.0 LWC-37 Min. 22 ga., Type B, vented steel at max. 5 ft spans Min. 300 psi, min. 2- inch Celcore Cellular Concrete, Elastizell Lightweight Insulating Concrete or Mearlcrete GAFGLAS #75 or Elastovent OMG CR BSF 7-inch o.c. at min. 4-inch lap and 7-inch o.c. at two, equally spaced center rows Min. 1.5-inch Polytherm, ACFoam II, Polytherm H, H- Shield, Multi-Max FA3 or Polytherm HA None N/A SBS-SA (Optional) SBS-SA, SBS-TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -45.0 NEMO|etc. NEMO ETC, LLC Evaluation Report P9290.02.08-R25 for FL1654-R27 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 25: 09/30/2020 ©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 74 of 94 TABLE 4B: LIGHTWEIGHT CONCRETE DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF) SYSTEM TYPE A-2: MECHANICALLY ATTACHED ANCHOR SHEET, BONDED INSULATION, BONDED ROOF COVER System No. Deck (Note 1) Lightweight Concrete (Note 14) Anchor Sheet Base Insulation Top Insulation Roof Cover (Note 15) MDP (psf) Type Fasten (Note 11) Attach Type Attach (Notes 6,7,8) Type Attach (Notes 6,7,8) Base Ply Ply Cap Ply LWC-38 Min. 22 ga., Type B, vented steel at max. 5 ft spans Min. 300 psi, min. 2- inch Celcore Cellular Concrete, Elastizell Lightweight Insulating Concrete or Mearlcrete GAFGLAS #75 or Elastovent OMG CR BSF 7-inch o.c. at min. 4-inch lap and 7-inch o.c. at two, equally spaced center rows Min. 1.5-inch Polytherm, ACFoam II, Polytherm H, H- Shield, Multi-Max FA3 or Polytherm HA None N/A APP-SA-H (Optional) APP-TA APP-TA -45.0 LWC-39 Min. 22 ga., Type B, vented steel at max. 5 ft spans Min. 300 psi, min. 2- inch Celcore Cellular Concrete, Elastizell Lightweight Insulating Concrete or Mearlcrete GAFGLAS #75 or Elastovent OMG CR BSF 7-inch o.c. at min. 4-inch lap and 7-inch o.c. at two, equally spaced center rows Min. 1.5-inch Polytherm, ACFoam II, Polytherm H, H- Shield, Multi-Max FA3 or Polytherm HA None N/A SBS-SA-H (Optional) SBS-TA SBS-TA -45.0 TABLE 4C: LIGHTWEIGHT CONCRETE DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF) SYSTEM TYPE E-2: MECHANICALLY ATTACHED BASE SHEET, BONDED ROOF COVER System No. Deck (Note 1) Lightweight Concrete (Note 14) Base Sheet (Note A below) Roof Cover (Note 15) MDP (psf) Type Fasten (Note 11) Attach Base Ply Cap Ply PRE-EXISTENT CELLULAR LWC: LWC-40 Min. 22 ga., type B steel at max 5 ft spans or structural concrete Min. 300 psi, min. 2-inch thick pre-existent cellular lightweight concrete. Note: To qualify the LWIC under this assembly, an OMG CR BPF shall achieve an average withdrawal of 53 lbf when tested per TAS 105 or ANSI/SPRI FX-1 B3 or B11 OMG CR BPF 7-inch o.c. at a min. 3-inch lap and 7-inch o.c. at two, equally spaced, staggered rows in the field of the sheet (Optional) BP-AA, SBS-AA SBS-AA, APP- TA -45.0 CELCORE (FL2037): ASPHALT OR TORCH APPLIED BASE PLY: LWC-41 Min. 0.0179-inch Tensilform S- 75 or min. 0.0205-inch Tensilform 75 at max. 5 ft spans or structural concrete Min. 200 psi, min. 2-inch thick Celcore Cellular Concrete B1, B2, B3, B7 or B11 Trufast FM-90 or OMG CR BPF 8-inch o.c. at a min. 3-inch lap and 16-inch o.c. at two, equally spaced, staggered rows in the field of the sheet BP-AA, SBS-AA SBS-AA -37.5 LWC-42 Min. 22 ga., type B steel at max 5 ft spans or structural concrete Min. 200 psi, min. 2-inch thick Celcore Cellular Concrete B1 through B11 Trufast FM-90 or OMG CR BPF 7-inch o.c. at a min. 3-inch lap and 7-inch o.c. at two, equally spaced, staggered rows in the field of the sheet BP-AA, SBS-AA SBS-AA -45.0 NEMO|etc. NEMO ETC, LLC Evaluation Report P9290.02.08-R25 for FL1654-R27 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 25: 09/30/2020 ©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 75 of 94 TABLE 4C: LIGHTWEIGHT CONCRETE DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF) SYSTEM TYPE E-2: MECHANICALLY ATTACHED BASE SHEET, BONDED ROOF COVER System No. Deck (Note 1) Lightweight Concrete (Note 14) Base Sheet (Note A below) Roof Cover (Note 15) MDP (psf) Type Fasten (Note 11) Attach Base Ply Cap Ply LWC-43 Min. 26 ga., type HF steel at max 5 ft spans or structural concrete Min. 225 psi, min. 2-inch thick Celcore MF Cellular Concrete with Celcore HS Rheology Modifying Admixture B1, B2, B3, B4, B7, B8, B10 or B11 OMG CR BPF 9-inch o.c. at a min. 3-inch lap and 9-inch o.c. at two, equally spaced, staggered rows in the field of the sheet BP-AA, SBS-AA SBS-AA -45.0 LWC-44 Min. 22 ga., type B steel at max 6 ft spans or structural concrete Min. 225 psi, min. 2-inch thick Celcore MF Cellular Concrete with Celcore HS Rheology Modifying Admixture B1, B2, B3, B4, B7, B8, B10 or B11 OMG CR BPF 7-inch o.c. at a min. 3-inch lap and 14-inch o.c. at two, equally spaced, staggered rows in the field of the sheet BP-AA, SBS-AA SBS-AA -45.0 LWC-45 Min. 22 ga., type B steel at max 6 ft spans or structural concrete Min. 225 psi, min. 2-inch thick Celcore MF Cellular Concrete with Celcore HS Rheology Modifying Admixture B1, B2, B3, B4, B7, B8, B10 or B11 OMG CR BPF 9-inch o.c. at a min. 3-inch lap and 9-inch o.c. at two, equally spaced, staggered rows in the field of the sheet BP-AA, SBS-AA SBS-AA -45.0 LWC-46 Min. 22 ga., type B steel at max 5 ft spans or structural concrete Min. 225 psi, min. 2-inch thick Celcore MF Cellular Concrete with Celcore HS Rheology Modifying Admixture B1, B2 or B11 Trufast Twin Loc- Nail 9-inch o.c. at a min. 4-inch lap and 18-inch o.c. at two, equally spaced, staggered rows in the field of the sheet BP-AA, SBS-AA, SBS-TA or APP-TA SBS-AA, SBS- TA, or APP- TA -45.0 LWC-47 Min. 22 ga., type B steel at max 5 ft spans or structural concrete Min. 225 psi, min. 2-inch thick Celcore MF Cellular Concrete with Celcore HS Rheology Modifying Admixture B2 (with poly- film top surface) Trufast Twin Loc- Nail 9-inch o.c. at a min. 4-inch lap and 18-inch o.c. at two, equally spaced, staggered rows in the field of the sheet SBS-TA or APP-TA SBS-TA or APP-TA -45.0 LWC-48 Min. 22 ga., type B steel at max 5 ft spans or structural concrete Min. 300 psi, min. 2-inch thick Celcore MF Cellular Concrete with Celcore HS Rheology Modifying Admixture B2 or B11 Trufast FM-90 8-inch o.c. at a min. 4-inch lap and 8-inch o.c. at three equally spaced, staggered center rows BP-AA, SBS-AA, SBS-TA or APP-TA SBS-AA, SBS- TA, or APP- TA -60.0 LWC-49 Min. 22 ga., type B steel at max 5 ft spans or structural concrete Min. 300 psi, min. 2-inch thick Celcore MF Cellular Concrete with Celcore HS Rheology Modifying Admixture B2 (with poly- film top surface) Trufast FM-90 8-inch o.c. at a min. 4-inch lap and 8-inch o.c. at three equally spaced, staggered center rows SBS-TA or APP-TA SBS-TA or APP-TA -60.0 LWC-50 Min. 22 ga., type B steel at max 5 ft spans or structural concrete Min. 300 psi, min. 2-inch thick Celcore Cellular Concrete B1 through B11 Trufast FM-90 or OMG CR BPF 7-inch o.c. at a min. 3-inch lap and 7-inch o.c. at two, equally spaced, staggered rows in the field of the sheet BP-AA, SBS-AA, SBS-TA, APP-TA SBS-AA, APP- TA -75.0 LWC-51 Min. 22 ga., type B steel at max 5 ft spans or structural concrete Min. 300 psi, min. 2-inch thick Celcore MF Cellular Concrete with Celcore HS Rheology Modifying Admixture Elastobase P Trufast FM-290 10-inch o.c. at a min. 4-inch lap and 10-inch o.c. at three equally spaced, staggered center rows (Optional) BP-AA, SBS-AA, SBS-TA or APP-TA SBS-AA, SBS- TA, APP-TA -90.0 SELF-ADHERING BASE PLY: LWC-52 Min. 22 ga., type B steel at max 5 ft spans or structural concrete Min. 225 psi, min. 2-inch thick Celcore MF Cellular Concrete with Celcore HS Rheology Modifying Admixture B2 (with poly- film top surface) Trufast Twin Loc- Nail 9-inch o.c. at a min. 4-inch lap and 18-inch o.c. at two, equally spaced, staggered rows in the field of the sheet SBS-SA SBS-SA, APP- SA, SBS-TA or APP-TA -45.0 NEMO|etc. NEMO ETC, LLC Evaluation Report P9290.02.08-R25 for FL1654-R27 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 25: 09/30/2020 ©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 76 of 94 TABLE 4C: LIGHTWEIGHT CONCRETE DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF) SYSTEM TYPE E-2: MECHANICALLY ATTACHED BASE SHEET, BONDED ROOF COVER System No. Deck (Note 1) Lightweight Concrete (Note 14) Base Sheet (Note A below) Roof Cover (Note 15) MDP (psf) Type Fasten (Note 11) Attach Base Ply Cap Ply LWC-53 Min. 22 ga., type B steel at max 5 ft spans or structural concrete Min. 300 psi, min. 2-inch thick Celcore MF Cellular Concrete with Celcore HS Rheology Modifying Admixture B2 (with poly- film top surface) Trufast FM-90 8-inch o.c. at a min. 4-inch lap and 8-inch o.c. at three equally spaced, staggered center rows SBS-SA SBS-SA, APP- SA, SBS-TA or APP-TA -60.0 HYBRID SYSTEMS WITH SELF-ADHERING APP BASE PLY: LWC-54 Min. 22 ga., type B steel at max 5 ft spans or structural concrete Min. 225 psi, min. 2-inch thick Celcore MF Cellular Concrete with Celcore HS Rheology Modifying Admixture B2 (with poly- film top surface) Trufast Twin Loc- Nail 9-inch o.c. at a min. 4-inch lap and 18-inch o.c. at two, equally spaced, staggered rows in the field of the sheet APP-SA-H APP-TA -45.0 LWC-55 Min. 22 ga., type B steel at max 5 ft spans or structural concrete Min. 300 psi, min. 2-inch thick Celcore MF Cellular Concrete with Celcore HS Rheology Modifying Admixture B2 (with poly- film top surface) Trufast FM-90 8-inch o.c. at a min. 4-inch lap and 8-inch o.c. at three equally spaced, staggered center rows APP-SA-H APP-TA -60.0 HYBRID SYSTEMS WITH SELF-ADHERING SBS BASE PLY: LWC-56 Min. 22 ga., type B steel at max 5 ft spans or structural concrete Min. 225 psi, min. 2-inch thick Celcore MF Cellular Concrete with Celcore HS Rheology Modifying Admixture B2 (with poly- film top surface) Trufast Twin Loc- Nail 9-inch o.c. at a min. 4-inch lap and 18-inch o.c. at two, equally spaced, staggered rows in the field of the sheet SBS-SA-H SBS-TA -45.0 LWC-57 Min. 22 ga., type B steel at max 5 ft spans or structural concrete Min. 300 psi, min. 2-inch thick Celcore MF Cellular Concrete with Celcore HS Rheology Modifying Admixture B2 (with poly- film top surface) Trufast FM-90 8-inch o.c. at a min. 4-inch lap and 8-inch o.c. at three equally spaced, staggered center rows SBS-SA-H SBS-TA -60.0 ELASTIZELL (FL4994): ASPHALT OR TORCH APPLIED BASE PLY: LWC-58 Min. 0.0179-inch Tensilform S- 75 or min. 0.0205-inch Tensilform 75 at max. 5 ft spans or structural concrete Min. 200 psi, min. 2-inch thick Range II Elastizell Lightweight Insulating Concrete B1 through B11 Trufast FM-90 or OMG CR BPF 7.5-inch o.c. at a min. 3-inch lap and 7.5-inch o.c. at two, equally spaced, staggered rows in the field of the sheet BP-AA, SBS-AA, SBS-TA, or APP-TA SBS-AA, SBS- TA, or APP- TA -30.0 LWC-59 Min. 0.0179-inch Tensilform S- 75 or min. 0.0205-inch Tensilform 75 at max. 5 ft spans or structural concrete Min. 200 psi, min. 2-inch thick Range II Elastizell Lightweight Insulating Concrete B2 (with poly- film top surface) Trufast FM-90 or OMG CR BPF 7.5-inch o.c. at a min. 3-inch lap and 7.5-inch o.c. at two, equally spaced, staggered rows in the field of the sheet SBS-TA or APP-TA SBS-TA or APP-TA -30.0 LWC-60 Min. 22 ga., type B steel at max 5 ft spans or structural concrete Min. 200 psi, min. 2-inch thick Range II Elastizell Lightweight Insulating Concrete B1 through B11 Trufast FM-90 or OMG CR BPF 7-inch o.c. at a min. 3-inch lap and 7-inch o.c. at two, equally spaced, staggered rows in the field of the sheet BP-AA, SBS-AA, SBS-TA, or APP-TA SBS-AA, SBS- TA, or APP- TA -45.0 LWC-61 Min. 22 ga., type B steel at max 5 ft spans or structural concrete Min. 200 psi, min. 2-inch thick Range II Elastizell Lightweight Insulating Concrete B2 (with poly- film top surface) Trufast FM-90 or OMG CR BPF 7-inch o.c. at a min. 3-inch lap and 7-inch o.c. at two, equally spaced, staggered rows in the field of the sheet SBS-TA or APP-TA SBS-TA or APP-TA -45.0 NEMO|etc. NEMO ETC, LLC Evaluation Report P9290.02.08-R25 for FL1654-R27 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 25: 09/30/2020 ©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 77 of 94 TABLE 4C: LIGHTWEIGHT CONCRETE DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF) SYSTEM TYPE E-2: MECHANICALLY ATTACHED BASE SHEET, BONDED ROOF COVER System No. Deck (Note 1) Lightweight Concrete (Note 14) Base Sheet (Note A below) Roof Cover (Note 15) MDP (psf) Type Fasten (Note 11) Attach Base Ply Cap Ply LWC-62 Min. 22 ga., type B vented steel at max 5 ft spans or structural concrete Min. 350 psi, min. 2-inch thick Elastizell with Zell-Crete Fibers, supplemental attached with Roofgrip #21 and 3-inch plates at 1 per 8 ft2 Elastobase P (with poly-film top surface) Trufast FM-290 8-inch o.c. at a min. 4-inch lap and 8-inch o.c. at three, equally spaced, staggered rows in the field of the sheet (Optional) BP-AA, SBS-AA, SBS-TA, or APP-TA SBS-AA, SBS- TA, or APP- TA -52.5 LWC-63 Min. 22 ga., type B steel at max 5 ft spans or structural concrete Min. 350 psi, min. 2-inch thick Elastizell with Zell-Crete Fibers, supplemental attached with Roofgrip #21 and 3-inch plates at 1 per 8 ft2 B2 or B11 Trufast Twin Loc- Nails (min. 1.8- inch) 6-inch o.c. at a min. 4-inch lap and 6-inch o.c. at three, equally spaced, staggered rows in the field of the sheet BP-AA or SBS-AA SBS-AA, SBS- TA, SBS-SA, APP-TA or APP-SA -60.0 LWC-64 Min. 22 ga., type B steel at max 5 ft spans or structural concrete Min. 350 psi, min. 2-inch thick Elastizell with Zell-Crete Fibers, supplemental attached with Roofgrip #21 and 3-inch plates at 1 per 8 ft2 B2 (with poly- film top surface) Trufast Twin Loc- Nails (min. 1.8- inch) 6-inch o.c. at a min. 4-inch lap and 6-inch o.c. at three, equally spaced, staggered rows in the field of the sheet SBS-TA or APP-TA SBS-TA or APP-TA -60.0 SELF-ADHERING BASE PLY: LWC-65 Min. 0.0179-inch Tensilform S- 75 or min. 0.0205-inch Tensilform 75 at max. 5 ft spans or structural concrete Min. 200 psi, min. 2-inch thick Range II Elastizell Lightweight Insulating Concrete B2 (with poly- film top surface) Trufast FM-90 or OMG CR BPF 7.5-inch o.c. at a min. 3-inch lap and 7.5-inch o.c. at two, equally spaced, staggered rows in the field of the sheet SBS-SA SBS-SA, APP- SA, SBS-TA or APP-TA -30.0 LWC-66 Min. 22 ga., type B steel at max 5 ft spans or structural concrete Min. 200 psi, min. 2-inch thick Range II Elastizell Lightweight Insulating Concrete B2 (with poly- film top surface) Trufast FM-90 or OMG CR BPF 7-inch o.c. at a min. 3-inch lap and 7-inch o.c. at two, equally spaced, staggered rows in the field of the sheet SBS-SA SBS-SA, APP- SA, SBS-TA or APP-TA -45.0 LWC-67 Min. 22 ga., type B steel at max 5 ft spans or structural concrete Min. 350 psi, min. 2-inch thick Elastizell with Zell-Crete Fibers, supplemental attached with Roofgrip #21 and 3-inch plates at 1 per 8 ft2 B2 (with poly- film top surface) Trufast Twin Loc- Nails (min. 1.8- inch) 6-inch o.c. at a min. 4-inch lap and 6-inch o.c. at three, equally spaced, staggered rows in the field of the sheet SBS-SA SBS-SA, APP- SA, SBS-TA or APP-TA -60.0 HYBRID SYSTEMS WITH SELF-ADHERING APP BASE PLY: LWC-68 Min. 22 ga., type B steel at max 5 ft spans or structural concrete Min. 200 psi, min. 2-inch thick Range II Elastizell Lightweight Insulating Concrete B2 (with poly- film top surface) Trufast FM-90 or OMG CR BPF 7-inch o.c. at a min. 3-inch lap and 7-inch o.c. at two, equally spaced, staggered rows in the field of the sheet APP-SA-H APP-TA -45.0 LWC-69 Min. 22 ga., type B steel at max 5 ft spans or structural concrete Min. 350 psi, min. 2-inch thick Elastizell with Zell-Crete Fibers, supplemental attached with Roofgrip #21 and 3-inch plates at 1 per 8 ft2 B2 (with poly- film top surface) Trufast Twin Loc- Nails (min. 1.8- inch) 6-inch o.c. at a min. 4-inch lap and 6-inch o.c. at three, equally spaced, staggered rows in the field of the sheet APP-SA-H APP-TA -60.0 HYBRID SYSTEMS WITH SELF-ADHERING SBS BASE PLY: LWC-70 Min. 22 ga., type B steel at max 5 ft spans or structural concrete Min. 200 psi, min. 2-inch thick Range II Elastizell Lightweight Insulating Concrete B2 (with poly- film top surface) Trufast FM-90 or OMG CR BPF 7-inch o.c. at a min. 3-inch lap and 7-inch o.c. at two, equally spaced, staggered rows in the field of the sheet SBS-SA-H SBS-TA -45.0 NEMO|etc. NEMO ETC, LLC Evaluation Report P9290.02.08-R25 for FL1654-R27 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 25: 09/30/2020 ©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 78 of 94 TABLE 4C: LIGHTWEIGHT CONCRETE DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF) SYSTEM TYPE E-2: MECHANICALLY ATTACHED BASE SHEET, BONDED ROOF COVER System No. Deck (Note 1) Lightweight Concrete (Note 14) Base Sheet (Note A below) Roof Cover (Note 15) MDP (psf) Type Fasten (Note 11) Attach Base Ply Cap Ply LWC-71 Min. 22 ga., type B steel at max 5 ft spans or structural concrete Min. 350 psi, min. 2-inch thick Elastizell with Zell-Crete Fibers, supplemental attached with Roofgrip #21 and 3-inch plates at 1 per 8 ft2 B2 (with poly- film top surface) Trufast Twin Loc- Nails (min. 1.8- inch) 6-inch o.c. at a min. 4-inch lap and 6-inch o.c. at three, equally spaced, staggered rows in the field of the sheet SBS-SA-H SBS-TA -60.0 MEARLCRETE (FL13492): ASPHALT OR TORCH APPLIED BASE PLY: LWC-72 Min. 24 ga., type B steel at max 5 ft spans or structural concrete Min. 200 psi, min. 2-inch thick Mearlcrete B1 through B11 Trufast FM-90 or OMG CR BPF 7.5-inch o.c. at a min. 3-inch lap and 10-inch o.c. at two, equally spaced, staggered rows in the field of the sheet BP-AA, SBS-AA SBS-AA -30.0 LWC-73 Min. 22 ga., type B steel at max 5 ft spans or structural concrete Min. 300 psi, min. 2-inch thick Mearlcrete B1, B2, B3, B7 or B11 Trufast FM-90 or OMG CR BPF 7-inch o.c. at a min. 4-inch lap and 7-inch o.c. at two, equally spaced, staggered rows in the field of the sheet BP-AA, SBS-AA, SBS-TA, or APP-TA SBS-AA, SBS- TA, or APP- TA -52.5 LWC-74 Min. 22 ga., type B steel at max 5 ft spans or structural concrete Min. 300 psi, min. 2-inch thick Mearlcrete B2 (with poly- film top surface) Trufast FM-90 or OMG CR BPF 7-inch o.c. at a min. 4-inch lap and 7-inch o.c. at two, equally spaced, staggered rows in the field of the sheet SBS-TA or APP-TA SBS-TA or APP-TA -52.5 SELF-ADHERING BASE PLY: LWC-75 Min. 22 ga., type B steel at max 5 ft spans or structural concrete Min. 300 psi, min. 2-inch thick Mearlcrete B2 (with poly- film top surface) Trufast FM-90 or OMG CR BPF 7-inch o.c. at a min. 4-inch lap and 7-inch o.c. at two, equally spaced, staggered rows in the field of the sheet SBS-SA SBS-SA, APP- SA, SBS-TA or APP-TA -52.5 HYBRID SYSTEMS WITH SELF-ADHERING APP BASE PLY: LWC-76 Min. 22 ga., type B steel at max 5 ft spans or structural concrete Min. 300 psi, min. 2-inch thick Mearlcrete B2 (with poly- film top surface) Trufast FM-90 or OMG CR BPF 7-inch o.c. at a min. 4-inch lap and 7-inch o.c. at two, equally spaced, staggered rows in the field of the sheet APP-SA-H APP-TA -52.5 HYBRID SYSTEMS WITH SELF-ADHERING SBS BASE PLY: LWC-77 Min. 22 ga., type B steel at max 5 ft spans or structural concrete Min. 300 psi, min. 2-inch thick Mearlcrete B2 (with poly- film top surface) Trufast FM-90 or OMG CR BPF 7-inch o.c. at a min. 4-inch lap and 7-inch o.c. at two, equally spaced, staggered rows in the field of the sheet SBS-SA-H SBS-TA -52.5 A. Base Sheets options in Table 4C are coded as follows: ➢ B1: Polyglass G2 Base; B2: Elastobase or Elastobase P; B3: GAFGLAS #75; B4: GAFGLAS Stratavent Nailable Venting Base Sheet; B5: GAFGLAS Ply 4; B6: GAFGLAS FlexPly 6; B7: JM Perma Ply No. 28; B8: JM Vensulation; B9: JM GlasPly IV; B10: JM GlasPly Premier; B11: Elastovent NEMO|etc. NEMO ETC, LLC Evaluation Report P9290.02.08-R25 for FL1654-R27 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 25: 09/30/2020 ©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 79 of 94 TABLE 5A: CEMENTITIOUS WOOD FIBER DECKS – REROOF (TEAR-OFF) SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER System No. Deck (Notes 1 & 12) Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP (psf) Type Attach (Notes 6,7,8) Type Attach (Notes 6,7,8) Base Ply Ply Cap Ply ASPHALT OR TORCH APPLIED BASE PLY: CWF-1 Existing Min. 2.5-inch Tectum Plank or Tectum LS Plank Min. 1.5-inch Polytherm, ACFoam II, ISO 95+GL, Polytherm H, H-Shield, ENRGY-3 D-IS or OB500 Min. 0.25-inch DensDeck, DensDeck Prime, SECUROCK Gypsum-Fiber Roof Board or min. 0.5-inch Structodek High Density Fiberboard Roof Insulation D-IS or OB500 BP-AA, SBS-AA (Optional) BP-AA, SBS-AA, SBS-TA or APP-TA SBS-AA, SBS- TA, APP-TA -45.0 CWF-2 Existing Min. 2.5-inch Tectum Plank or Tectum LS Plank Min. 1.5-inch Polytherm, ACFoam II, ISO 95+GL, Polytherm H, H-Shield, ENRGY-3 D-IS or OB500 Min. 0.25-inch DensDeck, DensDeck Prime, SECUROCK Gypsum-Fiber Roof Board D-IS or OB500 SBS-TA or APP- TA (Optional) SBS-TA or APP-TA SBS-TA, APP-TA -45.0 CWF-3 Existing Min. 2.5-inch Tectum Plank or Tectum LS Plank Min. 1.5-inch Polytherm, ACFoam II, ISO 95+GL, Polytherm H, H-Shield, ENRGY-3 CR-20 Min. 0.25-inch DensDeck, DensDeck Prime, SECUROCK Gypsum-Fiber Roof Board or min. 0.5-inch Structodek High Density Fiberboard Roof Insulation CR-20 BP-AA, SBS-AA (Optional) BP-AA, SBS-AA, SBS-TA or APP-TA SBS-AA, SBS- TA, APP-TA -52.5 CWF-4 Existing Min. 2.5-inch Tectum Plank or Tectum LS Plank Min. 1.5-inch Polytherm, ACFoam II, ISO 95+GL, Polytherm H, H-Shield, ENRGY-3 CR-20 Min. 0.25-inch DensDeck, DensDeck Prime, SECUROCK Gypsum-Fiber Roof Board CR-20 SBS-TA or APP- TA (Optional) SBS-TA or APP-TA SBS-TA, APP-TA -52.5 SELF-ADHERING BASE PLY: CWF-5 Existing Min. 2.5-inch Tectum Plank or Tectum LS Plank Min. 1.5-inch Polytherm, ACFoam II, ISO 95+GL, Polytherm H, H-Shield, ENRGY-3 D-IS or OB500 Min. 0.25-inch DensDeck, DensDeck Prime, SECUROCK Gypsum-Fiber Roof Board D-IS or OB500 SBS-SA (Optional) SBS-SA, SBS-TA or APP-TA SBS-SA, APP- SA, SBS-TA, APP-TA -45.0 CWF-6 Existing Min. 2.5-inch Tectum Plank or Tectum LS Plank Min. 1.5-inch Polytherm, ACFoam II, ISO 95+GL, Polytherm H, H-Shield, ENRGY-3 CR-20 Min. 0.25-inch DensDeck, DensDeck Prime, SECUROCK Gypsum-Fiber Roof Board CR-20 SBS-SA (Optional) SBS-SA, SBS-TA or APP-TA SBS-SA, APP- SA, SBS-TA, APP-TA -52.5 HYBRID SYSTEMS WITH SELF-ADHERING APP BASE PLY: CWF-7 Existing Min. 2.5-inch Tectum Plank or Tectum LS Plank Min. 1.5-inch Polytherm, ACFoam II, ISO 95+GL, Polytherm H, H-Shield, ENRGY-3 D-IS or OB500 Min. 0.25-inch DensDeck, DensDeck Prime, SECUROCK Gypsum-Fiber Roof Board D-IS or OB500 APP-SA-H (Optional) APP-TA APP-TA -45.0 CWF-8 Existing Min. 2.5-inch Tectum Plank or Tectum LS Plank Min. 1.5-inch Polytherm, ACFoam II, ISO 95+GL, Polytherm H, H-Shield, ENRGY-3 CR-20 Min. 0.25-inch DensDeck, DensDeck Prime, SECUROCK Gypsum-Fiber Roof Board CR-20 APP-SA-H (Optional) APP-TA APP-TA -52.5 HYBRID SYSTEMS WITH SELF-ADHERING SBS BASE PLY: CWF-9 Existing Min. 2.5-inch Tectum Plank or Tectum LS Plank Min. 1.5-inch Polytherm, ACFoam II, ISO 95+GL, Polytherm H, H-Shield, ENRGY-3 D-IS or OB500 Min. 0.25-inch DensDeck, DensDeck Prime, SECUROCK Gypsum-Fiber Roof Board D-IS or OB500 SBS-SA-H (Optional) SBS-TA SBS-TA -45.0 NEMO|etc. NEMO ETC, LLC Evaluation Report P9290.02.08-R25 for FL1654-R27 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 25: 09/30/2020 ©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 80 of 94 TABLE 5A: CEMENTITIOUS WOOD FIBER DECKS – REROOF (TEAR-OFF) SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER System No. Deck (Notes 1 & 12) Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP (psf) Type Attach (Notes 6,7,8) Type Attach (Notes 6,7,8) Base Ply Ply Cap Ply CWF-10 Existing Min. 2.5-inch Tectum Plank or Tectum LS Plank Min. 1.5-inch Polytherm, ACFoam II, ISO 95+GL, Polytherm H, H-Shield, ENRGY-3 CR-20 Min. 0.25-inch DensDeck, DensDeck Prime, SECUROCK Gypsum-Fiber Roof Board CR-20 SBS-SA-H (Optional) SBS-TA SBS-TA -52.5 TABLE 5B: CEMENTITIOUS WOOD FIBER DECKS – REROOF (TEAR-OFF) OR RECOVER SYSTEM TYPE A-2: MECHANICALLY ATTACHED ANCHOR SHEET, BONDED INSULATION, BONDED ROOF COVER System No. Deck (Note 1) Anchor Sheet Base Insulation Top Insulation Roof Cover (Note 15) MDP (psf) Type Fasten (Note 11) Attach Type Attach (Notes 6,7,8) Type Attach (Notes 6,7,8) Base Ply Ply Cap Ply ASPHALT OR TORCH APPLIED BASE PLY: CWF-11 Existing Min. 2.5-inch Tectum Plank or Tectum LS Plank Elastobase, Elastobase P, Elastovent or Polyglass G2 Base Trufast Inuldek Loc-Nail (reroof only) 9-inch o.c. at min. 4-inch lap and 12- inch o.c. at two, equally spaced, staggered center rows Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ISO95+GL, Polytherm H, H- Shield, ENRGY 3 or Multi-Max FA3, Hot asphalt Min. 0.25-inch DensDeck, DensDeck Prime, SECUROCK Gypsum-Fiber Roof Board, Min. 0.75- inch Fesco Board (homogeneous) or min. 0.5-inch Structodek High Density Fiberboard Roof Insulation Hot asphalt BP-AA, SBS-AA (Optional) BP- AA, SBS-AA, SBS-TA or APP- TA SBS-AA, SBS-TA, APP-TA -30.0* CWF-12 Existing Min. 2.5-inch Tectum Plank or Tectum LS Plank Elastobase, Elastobase P, Elastovent or Polyglass G2 Base Trufast Inuldek Loc-Nail (reroof only) 9-inch o.c. at min. 4-inch lap and 12- inch o.c. at two, equally spaced, staggered center rows Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ISO95+GL, Polytherm H, H- Shield, ENRGY 3 or Multi-Max FA3, Hot asphalt Min. 0.25-inch DensDeck, DensDeck Prime, SECUROCK Gypsum-Fiber Roof Board Hot asphalt SBS-TA or APP- TA (Optional) SBS- TA or APP-TA SBS-TA, APP-TA -30.0* CWF-13 Existing Min. 2.5-inch Tectum Plank or Tectum LS Plank Elastobase, Elastobase P, Elastovent or Polyglass G2 Base Trufast Twin Loc-Nail 9-inch o.c. at min. 4-inch lap and 18- inch o.c. at two, equally spaced, staggered center rows Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ISO95+GL, Polytherm H, H- Shield, ENRGY 3 or Multi-Max FA3, Hot asphalt Min. 0.25-inch DensDeck, DensDeck Prime, SECUROCK Gypsum-Fiber Roof Board, Min. 0.75- inch Fesco Board (homogeneous) or min. 0.5-inch Structodek High Density Fiberboard Roof Insulation Hot asphalt BP-AA, SBS-AA (Optional) BP- AA, SBS-AA, SBS-TA or APP- TA SBS-AA, SBS-TA, APP-TA -45.0* NEMO|etc. NEMO ETC, LLC Evaluation Report P9290.02.08-R25 for FL1654-R27 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 25: 09/30/2020 ©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 81 of 94 TABLE 5B: CEMENTITIOUS WOOD FIBER DECKS – REROOF (TEAR-OFF) OR RECOVER SYSTEM TYPE A-2: MECHANICALLY ATTACHED ANCHOR SHEET, BONDED INSULATION, BONDED ROOF COVER System No. Deck (Note 1) Anchor Sheet Base Insulation Top Insulation Roof Cover (Note 15) MDP (psf) Type Fasten (Note 11) Attach Type Attach (Notes 6,7,8) Type Attach (Notes 6,7,8) Base Ply Ply Cap Ply CWF-14 Existing Min. 2.5-inch Tectum Plank or Tectum LS Plank Elastobase, Elastobase P, Elastovent or Polyglass G2 Base Trufast Twin Loc-Nail 9-inch o.c. at min. 4-inch lap and 18- inch o.c. at two, equally spaced, staggered center rows Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ISO95+GL, Polytherm H, H-Shield, ENRGY 3 or Multi-Max FA3, Hot asphalt Min. 0.25-inch DensDeck, DensDeck Prime, SECUROCK Gypsum-Fiber Roof Board Hot asphalt SBS-TA or APP- TA (Optional) SBS- TA or APP-TA SBS-TA, APP-TA -45.0* SELF-ADHERING BASE PLY: CWF-15 Existing Min. 2.5-inch Tectum Plank or Tectum LS Plank Elastobase, Elastobase P, Elastovent or Polyglass G2 Base Trufast Inuldek Loc-Nail (reroof only) 9-inch o.c. at min. 4-inch lap and 12- inch o.c. at two, equally spaced, staggered center rows Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ISO95+GL, Polytherm H, H-Shield, ENRGY 3 or Multi-Max FA3, Hot asphalt Min. 0.25-inch DensDeck, DensDeck Prime, SECUROCK Gypsum-Fiber Roof Board Hot asphalt SBS-SA (Optional) SBS- TA, SBS-SA or APP-TA SBS-TA, SBS-SA, APP-TA, APP-SA -30.0* CWF-16 Existing Min. 2.5-inch Tectum Plank or Tectum LS Plank Elastobase, Elastobase P, Elastovent or Polyglass G2 Base Trufast Twin Loc-Nail 9-inch o.c. at min. 4-inch lap and 18- inch o.c. at two, equally spaced, staggered center rows Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ISO95+GL, Polytherm H, H-Shield, ENRGY 3 or Multi-Max FA3, Hot asphalt Min. 0.25-inch DensDeck, DensDeck Prime, SECUROCK Gypsum-Fiber Roof Board Hot asphalt SBS-SA (Optional) SBS- TA, SBS-SA or APP-TA SBS-TA, SBS-SA, APP-TA, APP-SA -45.0* HYBRID SYSTEMS WITH SELF-ADHERING APP BASE PLY: CWF-17 Existing Min. 2.5-inch Tectum Plank or Tectum LS Plank Elastobase, Elastobase P, Elastovent or Polyglass G2 Base Trufast Inuldek Loc-Nail (reroof only) 9-inch o.c. at min. 4-inch lap and 12- inch o.c. at two, equally spaced, staggered center rows Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ISO95+GL, Polytherm H, H-Shield, ENRGY 3 or Multi-Max FA3, Hot asphalt Min. 0.25-inch DensDeck, DensDeck Prime, SECUROCK Gypsum-Fiber Roof Board Hot asphalt APP-SA- H (Optional) APP- TA APP-TA -30.0* CWF-18 Existing Min. 2.5-inch Tectum Plank or Tectum LS Plank Elastobase, Elastobase P, Elastovent or Polyglass G2 Base Trufast Twin Loc-Nail 9-inch o.c. at min. 4-inch lap and 18- inch o.c. at two, equally spaced, staggered center rows Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ISO95+GL, Polytherm H, H-Shield, ENRGY 3 or Multi-Max FA3, Hot asphalt Min. 0.25-inch DensDeck, DensDeck Prime, SECUROCK Gypsum-Fiber Roof Board Hot asphalt APP-SA- H (Optional) APP- TA APP-TA -45.0* HYBRID SYSTEMS WITH SELF-ADHERING SBS BASE PLY: NEMO|etc. NEMO ETC, LLC Evaluation Report P9290.02.08-R25 for FL1654-R27 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 25: 09/30/2020 ©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 82 of 94 TABLE 5B: CEMENTITIOUS WOOD FIBER DECKS – REROOF (TEAR-OFF) OR RECOVER SYSTEM TYPE A-2: MECHANICALLY ATTACHED ANCHOR SHEET, BONDED INSULATION, BONDED ROOF COVER System No. Deck (Note 1) Anchor Sheet Base Insulation Top Insulation Roof Cover (Note 15) MDP (psf) Type Fasten (Note 11) Attach Type Attach (Notes 6,7,8) Type Attach (Notes 6,7,8) Base Ply Ply Cap Ply CWF-19 Existing Min. 2.5-inch Tectum Plank or Tectum LS Plank Elastobase, Elastobase P, Elastovent or Polyglass G2 Base Trufast Inuldek Loc-Nail (reroof only) 9-inch o.c. at min. 4-inch lap and 12- inch o.c. at two, equally spaced, staggered center rows Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ISO95+GL, Polytherm H, H-Shield, ENRGY 3 or Multi-Max FA3, Hot asphalt Min. 0.25-inch DensDeck, DensDeck Prime, SECUROCK Gypsum-Fiber Roof Board Hot asphalt SBS-SA- H (Optional) SBS- TA SBS-TA -30.0* CWF-20 Existing Min. 2.5-inch Tectum Plank or Tectum LS Plank Elastobase, Elastobase P, Elastovent or Polyglass G2 Base Trufast Twin Loc-Nail 9-inch o.c. at min. 4-inch lap and 18- inch o.c. at two, equally spaced, staggered center rows Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ISO95+GL, Polytherm H, H-Shield, ENRGY 3 or Multi-Max FA3, Hot asphalt Min. 0.25-inch DensDeck, DensDeck Prime, SECUROCK Gypsum-Fiber Roof Board Hot asphalt SBS-SA- H (Optional) SBS- TA SBS-TA -45.0* TABLE 5C: CEMENTITIOUS WOOD FIBER DECKS – REROOF (TEAR-OFF) OR RECOVER SYSTEM TYPE B-1: MECHANICALLY ATTACHED BASE INSULATION, BONDED TOP INSULATION, BONDED ROOF COVER System No. Deck (Note 1) Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP (psf) Type Fasten (Note 11) Attach Type Attach (Notes 6,7,8) Base Ply Ply Cap Ply CWF-21 Existing Min. 2.5-inch Tectum Plank or Tectum LS Plank Min. 2-inch H- Shield or Polytherm H OMG Polymer GypTec Plate with Polymer GypTec or Trufast TL 3 in. Plate with TL Fastener 1 per 4.0 ft2 Min. 0.5-inch Structodek High Density Fiberboard Roof Insulation Hot asphalt (Optional if using AA Ply) BP-AA, SBS-AA (Optional if using AA Base) BP-AA, SBS-AA, SBS-TA or APP-TA SBS-AA, SBS-TA, APP-TA -45.0* NEMO|etc. NEMO ETC, LLC Evaluation Report P9290.02.08-R25 for FL1654-R27 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 25: 09/30/2020 ©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 83 of 94 TABLE 5D: CEMENTITIOUS WOOD FIBER DECKS – REROOF (TEAR-OFF) OR RECOVER SYSTEM TYPE C-1: MECHANICALLY ATTACHED INSULATION, BONDED ROOF COVER System No. Deck (Note 1) Base Insulation Layer (Note 13) Top Insulation Layer Roof Cover (Note 15) MDP (psf) Type Fasten (Note 11) Attach Base Ply Ply Cap Ply CWF-22 Existing Min. 2.5- inch Tectum Plank or Tectum LS Plank (Optional) One or more layers, any combination, loose laid Min. 0.25-inch DensDeck, DensDeck Prime or SECUROCK Gypsum-Fiber Roof Board or min. 0.5- inch Structodek High Density Fiberboard Roof Insulation Trufast Twin Loc- Nails (min. 1-inch embedment) 1 per 2.0 ft2 (Optional if using AA Ply) BP-AA, SBS-AA (Optional if using AA Base) BP-AA, SBS-AA, SBS-TA or APP-TA SBS-AA, SBS-TA, APP-TA -45.0* TABLE 5E: CEMENTITIOUS WOOD FIBER DECKS – REROOF (TEAR-OFF) OR RECOVER SYSTEM TYPE E-2: NON-INSULATED, MECHANICALLY ATTACHED BASE SHEET, BONDED ROOF COVER System No. Deck (Note 1) Base Sheet Roof Cover (Note 15) MDP (psf) Type Fasten (Note 11) Attach Base Ply Cap Ply CWF-23 Existing Min. 2.5- inch Tectum Plank or Tectum LS Plank Elastobase, Elastobase P, Elastovent or Polyglass G2 Base Trufast Insuldek Loc-Nail (reroof only) 9-inch o.c. at min. 4-inch lap and 12-inch o.c. at two, equally spaced, staggered center rows (Optional) BP-AA, SBS-AA, SBS-TA or APP-TA SBS-AA, SBS-TA, APP-TA -30.0* CWF-24 Existing Min. 2.5- inch Tectum Plank or Tectum LS Plank Elastobase, Elastobase P, Elastovent or Polyglass G2 Base Trufast Twin Loc-Nails 9-inch o.c. at min. 4-inch lap and 18-inch o.c. at two, equally spaced, staggered center rows (Optional) BP-AA, SBS-AA, SBS-TA or APP-TA SBS-AA, SBS-TA, APP-TA -45.0* NEMO|etc. NEMO ETC, LLC Evaluation Report P9290.02.08-R25 for FL1654-R27 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 25: 09/30/2020 ©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 84 of 94 TABLE 6A: GYPSUM DECKS – REROOF (TEAR-OFF) SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER System No. Deck (Notes 1 & 12) Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP (psf) Type Attach (Notes 6,7,8) Type Attach (Notes 6,7,8) Base Ply Ply Cap Ply ASPHALT-APPLIED BASE PLY: G-1 Existing, sound poured gypsum or gypsum plank Min. 0.25-inch DensDeck, DensDeck Prime or SECUROCK Gypsum-Fiber Roof Board CR-20 None N/A (Optional if using AA Ply) BP-AA, SBS-AA (Optional if using AA Base) BP-AA, SBS-AA, SBS-TA or APP-TA SBS-AA, SBS-TA, APP-TA -245.0 SELF-ADHERING BASE PLY: G-2 Existing, sound poured gypsum or gypsum plank Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3, Polytherm H or H-Shield or min. 2.0 pcf, Insulfoam OB500 Min. 0.25-inch DensDeck Prime OB500 SBS-SA (Optional) SBS- SA, SBS-TA, APP- TA SBS-SA, APP-SA, SBS-TA, APP-TA -72.5 G-3 Existing, sound poured gypsum or gypsum plank Min. 0.25-inch DensDeck Prime OB500 None N/A SBS-SA (Optional) SBS- SA, SBS-TA, APP- TA SBS-SA, APP-SA, SBS-TA, APP-TA -72.5 G-4 Existing, sound poured gypsum or gypsum plank Min. 1.5-inch min. 2.0 pcf, Insulfoam OB500 (Optional) additional layers(s) of base insulation OB500 SBS-SA (Optional) SBS-SA SBS-SA, APP-SA -112.5 G-5 Existing, sound poured gypsum or gypsum plank Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3, Polytherm H or H-Shield OB500 (Optional) additional layers(s) of base insulation OB500 SBS-SA (Optional) SBS- SA, SBS-TA, APP- TA SBS-SA, APP-SA, SBS-TA, APP-TA -112.5 G-6 Existing, sound poured gypsum or gypsum plank Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3, Polytherm H or H-Shield or min. 2.0 pcf, Insulfoam OB500 Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board OB500 SBS-SA (Optional) SBS- SA, SBS-TA, APP- TA SBS-SA, APP-SA, SBS-TA, APP-TA -112.5 G-7 Existing, sound poured gypsum or gypsum plank Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board OB500 None N/A SBS-SA (Optional) SBS- SA, SBS-TA, APP- TA SBS-SA, APP-SA, SBS-TA, APP-TA -112.5 G-8 Existing, sound poured gypsum or gypsum plank Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3, H- Shield or Multi-Max FA3 M-OSFA Min. 0.25-inch DensDeck Prime M-OSFA SBS-SA (Optional) SBS- SA, SBS-TA, APP- TA SBS-SA, APP-SA, SBS-TA, APP-TA -72.5 G-9 Existing, sound poured gypsum or gypsum plank Min. 0.25-inch DensDeck Prime M-OSFA None N/A SBS-SA (Optional) SBS- SA, SBS-TA, APP- TA SBS-SA, APP-SA, SBS-TA, APP-TA -72.5 G-10 Existing, sound poured gypsum or gypsum plank Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3, H- Shield or Multi-Max FA3 M-OSFA (Optional) additional layers(s) of base insulation and/or min. 0.25-inch SECUROCK Gypsum- Fiber Roof Board M-OSFA SBS-SA (Optional) SBS- SA, SBS-TA, APP- TA SBS-SA, APP-SA, SBS-TA, APP-TA -202.5 NEMO|etc. NEMO ETC, LLC Evaluation Report P9290.02.08-R25 for FL1654-R27 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 25: 09/30/2020 ©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 85 of 94 TABLE 6A: GYPSUM DECKS – REROOF (TEAR-OFF) SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER System No. Deck (Notes 1 & 12) Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP (psf) Type Attach (Notes 6,7,8) Type Attach (Notes 6,7,8) Base Ply Ply Cap Ply G-11 Existing, sound poured gypsum or gypsum plank Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board M-OSFA None N/A SBS-SA (Optional) SBS- SA, SBS-TA, APP- TA SBS-SA, APP-SA, SBS-TA, APP-TA -202.5 G-12 Existing, sound poured gypsum or gypsum plank Min. 1.5-inch, min. 2.0 pcf EPS insulation board, Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY 3, Polytherm H, H-Shield, H-Shield CG or Multi-Max FA3 CR-20 Min. 0.25-inch DensDeck Prime CR-20 SBS-SA (Optional) SBS- SA, SBS-TA, APP- TA SBS-SA, APP-SA, SBS-TA, APP-TA -72.5 G-13 Existing, sound poured gypsum or gypsum plank Min. 0.25-inch DensDeck Prime CR-20 None N/A SBS-SA (Optional) SBS- SA, SBS-TA, APP- TA SBS-SA, APP-SA, SBS-TA, APP-TA -72.5 G-14 Existing, sound poured gypsum or gypsum plank Min. 1.5-inch, min. 2.0 pcf Insulfoam CR-20 (Optional) additional layers of base insulation CR-20 SBS-SA (Optional) SBS-SA SBS-SA -240.0 G-15 Existing, sound poured gypsum or gypsum plank Min. 1.5-inch, min. 2.0 pcf Insulfoam CR-20 Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board CR-20 SBS-SA (Optional) SBS- SA, SBS-TA, APP- TA SBS-SA, APP-SA, SBS-TA, APP-TA -240.0 G-16 Existing, sound poured gypsum or gypsum plank Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board CR-20 None N/A SBS-SA (Optional) SBS- SA, SBS-TA, APP- TA SBS-SA, APP-SA, SBS-TA, APP-TA -240.0 G-17 Existing, sound poured gypsum or gypsum plank Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY 3, Polytherm H, H-Shield, H- Shield CG or Multi-Max FA3 CR-20 (Optional) additional layers(s) of base insulation and/or min. 0.25-inch SECUROCK Gypsum- Fiber Roof Board CR-20 SBS-SA (Optional) SBS- SA, SBS-TA, APP- TA SBS-SA, APP-SA, SBS-TA, APP-TA -257.5 HYBRID SYSTEMS WITH SELF-ADHERING APP BASE PLY: G-18 Existing, sound poured gypsum or gypsum plank Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3, Polytherm H or H-Shield OB500 (Optional) additional layers(s) of base insulation OB500 APP-SA-H (Optional) APP- TA APP-TA -112.5 G-19 Existing, sound poured gypsum or gypsum plank Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3, Polytherm H or H-Shield or min. 2.0 pcf, Insulfoam OB500 Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board OB500 APP-SA-H (Optional) APP- TA APP-TA -112.5 G-20 Existing, sound poured gypsum or gypsum plank Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3, H- Shield or Multi-Max FA3 M-OSFA (Optional) additional layers(s) of base insulation and/or min. 0.25-inch SECUROCK Gypsum- Fiber Roof Board M-OSFA APP-SA-H (Optional) APP- TA APP-TA -202.5 NEMO|etc. NEMO ETC, LLC Evaluation Report P9290.02.08-R25 for FL1654-R27 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 25: 09/30/2020 ©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 86 of 94 TABLE 6A: GYPSUM DECKS – REROOF (TEAR-OFF) SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER System No. Deck (Notes 1 & 12) Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP (psf) Type Attach (Notes 6,7,8) Type Attach (Notes 6,7,8) Base Ply Ply Cap Ply G-21 Existing, sound poured gypsum or gypsum plank Min. 1.5-inch, min. 2.0 pcf Insulfoam CR-20 Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board CR-20 APP-SA-H (Optional) APP- TA APP-TA -240.0 G-22 Existing, sound poured gypsum or gypsum plank Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY 3, Polytherm H, H-Shield, H- Shield CG or Multi-Max FA3 CR-20 (Optional) additional layers(s) of base insulation and/or min. 0.25-inch SECUROCK Gypsum- Fiber Roof Board CR-20 APP-SA-H (Optional) APP- TA APP-TA -257.5 HYBRID SYSTEMS WITH SELF-ADHERING SBS BASE PLY: G-23 Existing, sound poured gypsum or gypsum plank Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3, Polytherm H or H-Shield or min. 2.0 pcf, Insulfoam OB500 Min. 0.25-inch DensDeck Prime OB500 SBS-SA-H (Optional) SBS-TA SBS-TA -72.5 G-24 Existing, sound poured gypsum or gypsum plank Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3, Polytherm H or H-Shield OB500 (Optional) additional layers(s) of base insulation OB500 SBS-SA-H (Optional) SBS-TA SBS-TA -112.5 G-25 Existing, sound poured gypsum or gypsum plank Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3, Polytherm H or H-Shield or min. 2.0 pcf, Insulfoam OB500 Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board OB500 SBS-SA-H (Optional) SBS-TA SBS-TA -112.5 G-26 Existing, sound poured gypsum or gypsum plank Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3, H- Shield or Multi-Max FA3 M-OSFA Min. 0.25-inch DensDeck Prime M-OSFA SBS-SA-H (Optional) SBS-TA SBS-TA -72.5 G-27 Existing, sound poured gypsum or gypsum plank Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3, H- Shield or Multi-Max FA3 M-OSFA (Optional) additional layers(s) of base insulation and/or min. 0.25-inch SECUROCK Gypsum- Fiber Roof Board M-OSFA SBS-SA-H (Optional) SBS-TA SBS-TA -202.5 G-28 Existing, sound poured gypsum or gypsum plank Min. 1.5-inch, min. 2.0 pcf EPS insulation board, Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY 3, Polytherm H, H-Shield, H-Shield CG or Multi-Max FA3 CR-20 Min. 0.25-inch DensDeck Prime CR-20 SBS-SA-H (Optional) SBS-TA SBS-TA -72.5 G-29 Existing, sound poured gypsum or gypsum plank Min. 1.5-inch, min. 2.0 pcf Insulfoam CR-20 Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board CR-20 SBS-SA-H (Optional) SBS-TA SBS-TA -240.0 G-30 Existing, sound poured gypsum or gypsum plank Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY 3, Polytherm H, H-Shield, H- Shield CG or Multi-Max FA3 CR-20 (Optional) additional layers(s) of base insulation and/or min. 0.25-inch SECUROCK Gypsum- Fiber Roof Board CR-20 SBS-SA-H (Optional) SBS-TA SBS-TA -257.5 COLD APPLIED BASE PLY: NEMO|etc. NEMO ETC, LLC Evaluation Report P9290.02.08-R25 for FL1654-R27 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 25: 09/30/2020 ©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 87 of 94 TABLE 6A: GYPSUM DECKS – REROOF (TEAR-OFF) SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER System No. Deck (Notes 1 & 12) Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP (psf) Type Attach (Notes 6,7,8) Type Attach (Notes 6,7,8) Base Ply Ply Cap Ply G-31 Existing, sound poured gypsum or gypsum plank Min. 1-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, EnergyGuard Polyiso Insulation, ENRGY 3, Polytherm H, H-Shield ISO 95+ GL, Multi- Max FA3, RESISTA or UltraMax or min. 2-inch DECKMATE Plus or DECKMATE Plus FA M-OSFA Min. 0.25-inch DensDeck, DensDeck Prime, DEXcell FA Glass Mat Roof Board, SECUROCK Gypsum-Fiber Roof Board or SECUROCK Glass-Mat Roof Board, min. 7/16-inch DEXcell Cement Roof Board or min. 0.5-inch SECUROCK Cement Roof Board M-OSFA SBS-CA1, SBS-CA2 (Optional) SBS- CA1, SBS-CA2 SBS-CA1, SBS- CA2, APP-CA1 -120.0 G-32 Existing, sound poured gypsum or gypsum plank Min. 1-inch Polytherm or ACFoam II, Polytherm G, ACFoam III, EnergyGuard Polyiso Insulation, ENRGY 3, Polytherm H, H-Shield, ISO 95+ GL, Multi-Max FA3, RESISTA or UltraMax or min. 2- inch DECKMATE Plus or DECKMATE Plus FA M-OSFA Min. 0.25-inch DensDeck Prime or DEXcell FA Glass Mat Roof Board, min. 7/16-inch DEXcell Cement Roof Board or min. 0.5- inch SECUROCK Cement Roof Board M-OSFA SBS-CA1 None SBS-CA1, SBS- CA2, APP-CA1 -127.5 G-33 Existing, sound poured gypsum or gypsum plank Min. 1-inch Polytherm or ACFoam II, Polytherm G, ACFoam III, EnergyGuard Polyiso Insulation, ENRGY 3, Polytherm H, H-Shield, ISO 95+ GL, Multi-Max FA3, RESISTA or UltraMax or min. 2- inch DECKMATE Plus or DECKMATE Plus FA M-OSFA Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board M-OSFA SBS-CA1, SBS-CA2 None SBS-CA1, SBS- CA2, APP-CA1 -127.5 G-34 Existing, sound poured gypsum or gypsum plank Min. 1-inch Polytherm or ACFoam II, Polytherm G, ACFoam III, EnergyGuard Polyiso Insulation, ENRGY 3, Polytherm H, H-Shield, ISO 95+ GL, Multi-Max FA3, RESISTA or UltraMax or min. 2- inch DECKMATE Plus or DECKMATE Plus FA M-OSFA Min. 0.25-inch DensDeck, DensDeck Prime, DEXcell FA Glass Mat Roof Board, SECUROCK Gypsum-Fiber Roof Board or SECUROCK Glass-Mat Roof Board, min. 7/16-inch DEXcell Cement Roof Board or min. 0.5-inch SECUROCK Cement Roof Board M-OSFA SBS-CA1, SBS-CA2 None SBS-CA1, SBS- CA2 -202.5 G-35 Existing, sound poured gypsum or gypsum plank Min. 1-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY 3, Polytherm H, H-Shield or Multi-Max FA3 OB500 Min. 0.25-inch DensDeck Prime, DEXcell FA Glass Mat Roof Board or SECUROCK Gypsum-Fiber Roof Board OB500 SBS-CA1, SBS-CA2 (Optional) SBS- CA1, SBS-CA2 SBS-CA1, SBS- CA2, APP-CA1 -112.5 G-36 Existing, sound poured gypsum or gypsum plank Min. 1-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY 3, Polytherm H, H-Shield or Multi-Max FA3 CR-20 Min. 0.25-inch DensDeck Prime or SECUROCK Gypsum-Fiber Roof Board CR-20 SBS-CA1, SBS-CA2 (Optional) SBS- CA1, SBS-CA2 SBS-CA1, SBS- CA2, APP-CA1 -120.0 G-37 Existing, sound poured gypsum or gypsum plank Min. 1-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY 3, Polytherm H, H-Shield or Multi-Max FA3 CR-20 Min. 0.25-inch DensDeck Prime or DEXcell FA Glass Mat Roof Board CR-20 SBS-CA1 None SBS-CA1, SBS- CA2, APP-CA1 -127.5 G-38 Existing, sound poured gypsum or gypsum plank Min. 1-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY 3, Polytherm H, H-Shield or Multi-Max FA3 CR-20 Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board CR-20 SBS-CA1, SBS-CA2 None SBS-CA1, SBS- CA2, APP-CA1 -127.5 NEMO|etc. NEMO ETC, LLC Evaluation Report P9290.02.08-R25 for FL1654-R27 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 25: 09/30/2020 ©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 88 of 94 TABLE 6A: GYPSUM DECKS – REROOF (TEAR-OFF) SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER System No. Deck (Notes 1 & 12) Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP (psf) Type Attach (Notes 6,7,8) Type Attach (Notes 6,7,8) Base Ply Ply Cap Ply G-39 Existing, sound poured gypsum or gypsum plank Min. 1-inch ENRGY 3, Polytherm H, H-Shield, Multi-Max FA3 CR-20 Min. 0.25-inch DensDeck Prime or SECUROCK Gypsum-Fiber Roof Board CR-20 SBS-CA1, SBS-CA2 None SBS-CA1, SBS- CA2 -232.5 TABLE 6B: GYPSUM DECKS – REROOF (TEAR-OFF) SYSTEM TYPE A-2: MECHANICALLY ATTACHED ANCHOR SHEET, BONDED INSULATION, BONDED ROOF COVER System No. Deck (Note 1) Anchor Sheet Base Insulation Top Insulation Roof Cover (Note 15) MDP (psf) Type Fasten (Note 11) Attach Type Attach (Notes 6,7,8) Type Attach (Notes 6,7,8) Base Ply Ply Cap Ply G-40 Existing, sound poured gypsum or gypsum plank Elastobase, Elastobase P, Elastovent or Polyglass G2 Base Trufast FM-75 or FM-90 or Twin Loc- Nails 9-inch o.c. at min. 4-inch lap and 18- inch o.c. at two, equally spaced, staggered center rows Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ISO95+GL, Polytherm H, H-Shield, ENRGY 3 or Multi-Max FA3 Hot asphalt Min. 0.25-inch DensDeck, DensDeck Prime, SECUROCK Gypsum-Fiber Roof Board, Min. 0.75-inch Fesco Board (homogeneous) or min. 0.5-inch Structodek High Density Fiberboard Roof Insulation Hot asphalt BP-AA, SBS-AA (Optional) BP-AA, SBS- AA, SBS-TA or APP-TA SBS-AA, SBS-TA, APP-TA -45.0* TABLE 6C: GYPSUM DECKS – REROOF (TEAR-OFF) OR RECOVER SYSTEM TYPE C-1: MECHANICALLY ATTACHED INSULATION, BONDED ROOF COVER System No. Deck (Note 1) Base Insulation Layer (Note 13) Top Insulation Layer Roof Cover (Note 15) MDP (psf) Type Fasten (Note 11) Attach Base Ply Ply Cap Ply G-41 Existing sound poured gypsum or gypsum plank (Optional) One or more layers, any combination, loose laid Min. 0.25-inch DensDeck, DensDeck Prime or SECUROCK Gypsum-Fiber Roof Board or min. 0.5- inch Structodek High Density Fiberboard Roof Insulation Trufast Twin Loc- Nails (min. 1-inch embedment) 1 per 2.0 ft2 (Optional if using AA Ply) BP-AA, SBS-AA (Optional if using AA Base) BP-AA, SBS-AA, SBS-TA or APP-TA SBS-AA, SBS-TA, APP-TA -45.0* TABLE 6D: GYPSUM DECKS – REROOF (TEAR-OFF) SYSTEM TYPE E: NON-INSULATED, MECHANICALLY ATTACHED BASE SHEET, BONDED ROOF COVER System No. Deck (Note 1) Base Sheet Roof Cover (Note 15) MDP (psf) Type Fasten (Note 11) Attach Base Ply Cap Ply G-42 Existing sound poured gypsum or gypsum plank Elastobase, Elastobase P, Elastovent or Polyglass G2 Base Trufast FM-75 or FM- 90 or Twin Loc-Nails 9-inch o.c. at min. 4-inch lap and 18-inch o.c. at two, equally spaced, staggered center rows (Optional) BP-AA, SBS-AA, SBS- TA or APP-TA SBS-AA, SBS-TA, APP-TA -45.0* NEMO|etc. NEMO ETC, LLC Evaluation Report P9290.02.08-R25 for FL1654-R27 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 25: 09/30/2020 ©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 89 of 94 TABLE 7A: RECOVER APPLICATIONS SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER System No. Substrate (Notes 1 & 12) Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP (psf) Type Attach (Notes 6,7,8) Type Attach (Notes 6,7,8) Base Ply Ply Cap Ply ASPHALT OR TORCH APPLIED BASE PLY: R-1 Existing asphaltic roof Min. 1.5-inch Multi-Max FA3 D-IS Min. 0.25-inch DensDeck, DensDeck Prime or SECUROCK Gypsum-Fiber Roof Board D-IS BP-AA, SBS- AA, SBS-TA, APP-TA (Optional) BP-AA, SBS- AA, SBS-TA or APP-TA SBS-AA, SBS-TA or APP-TA -67.5 R-2 Existing asphaltic roof Min. 1.5-inch Polytherm, ACFoam II or ENRGY 3 or min. 2.0 pcf Insulfoam D-IS Min. 0.25-inch DensDeck, DensDeck Prime or SECUROCK Gypsum-Fiber Roof Board D-IS BP-AA, SBS- AA, SBS-TA, APP-TA (Optional) BP-AA, SBS- AA, SBS-TA or APP-TA SBS-AA, SBS-TA, or APP-TA -90.0 R-3 Existing asphaltic roof Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3, H-Shield or ISO 95+GL OB500 Min. 0.25-inch DensDeck, DensDeck Prime or SECUROCK Gypsum-Fiber Roof Board OB500 BP-AA, SBS- AA, SBS-TA, APP-TA (Optional) BP-AA, SBS- AA, SBS-TA or APP-TA SBS-AA, SBS-TA, or APP-TA -127.5 R-4 Existing asphaltic roof Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3, H-Shield or Multi-Max FA3 M-OSFA Min. 0.25-inch SECUROCK Gypsum- Fiber Roof Board M-OSFA BP-AA, SBS- AA, SBS-TA, APP-TA (Optional) BP-AA, SBS- AA, SBS-TA or APP-TA SBS-AA, SBS-TA, or APP-TA -157.5 R-5 Existing asphaltic roof Min. 1.5-inch Ultra-Max or Multi-Max FA-3, min. 1.3-inch Polytherm G, ACFoam III or min. 1.0-inch ISO 95+GL, Polytherm H, H-Shield, H- Shield CG or ENRGY 3 or min. 2.0 pcf Insulfoam CR-20 Min. 0.25-inch SECUROCK Gypsum- Fiber Roof Board CR-20 BP-AA, SBS- AA (Optional) BP-AA, SBS- AA SBS-AA -225.0 R-6 Existing asphaltic roof Min. 1.5-inch Ultra-Max or Multi-Max FA-3, min. 1.3-inch Polytherm G, ACFoam III or min. 1.0-inch ISO 95+GL, Polytherm H, H-Shield, H- Shield CG or ENRGY 3 or min. 2.0 pcf Insulfoam CR-20 Min. 0.25-inch SECUROCK Gypsum- Fiber Roof Board CR-20 APP-TA (Optional) APP-TA APP-TA -232.5 SELF-ADHERING BASE PLY: R-7 Existing asphaltic roof Min. 1.5-inch Multi-Max FA3 D-IS (Optional) additional layers(s) of base insulation and/or min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board or DensDeck Prime D-IS SBS-SA (Optional) SBS-SA, SBS-TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -67.5 R-8 Existing asphaltic roof Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3 or Multi-Max FA3 or min. 2.0 pcf Insulfoam D-IS Min. 0.25-inch DensDeck Prime D-IS SBS-SA (Optional) SBS-SA, SBS-TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -72.5 R-9 Existing asphaltic roof Min. 1.5-inch min. 2.0 pcf Insulfoam D-IS (Optional) additional layers(s) of base insulation D-IS SBS-SA (Optional) SBS-SA SBS-SA -90.0 R-10 Existing asphaltic roof Min. 1.5-inch min. 2.0 pcf Insulfoam D-IS Min. 0.25-inch SECUROCK Gypsum- Fiber Roof Board D-IS SBS-SA (Optional) SBS-SA, SBS-TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -90.0 R-11 Existing asphaltic roof Min. 1.5-inch Polytherm, ACFoam II or ENRGY 3 D-IS (Optional) additional layers(s) of base insulation and/or min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board D-IS SBS-SA (Optional) SBS-SA, SBS-TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -90.0 NEMO|etc. NEMO ETC, LLC Evaluation Report P9290.02.08-R25 for FL1654-R27 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 25: 09/30/2020 ©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 90 of 94 TABLE 7A: RECOVER APPLICATIONS SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER System No. Substrate (Notes 1 & 12) Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP (psf) Type Attach (Notes 6,7,8) Type Attach (Notes 6,7,8) Base Ply Ply Cap Ply R-12 Existing asphaltic roof Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3, Polytherm H or H-Shield or min. 2.0 pcf Insulfoam OB500 Min. 0.25-inch DensDeck Prime OB500 SBS-SA (Optional) SBS-SA, SBS-TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -72.5 R-13 Existing asphaltic roof Min. 1.5-inch, min. 2.0 pcf Insulfoam OB500 (Optional) additional layers of base insulation OB500 SBS-SA (Optional) SBS-SA SBS-SA -120.0 R-14 Existing asphaltic roof Min. 1.5-inch, min. 2.0 pcf Insulfoam OB500 Min. 0.25-inch SECUROCK Gypsum- Fiber Roof Board OB500 SBS-SA (Optional) SBS-SA, SBS-TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -120.0 R-15 Existing asphaltic roof Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3, Polytherm H or H-Shield OB500 (Optional) additional layers(s) of base insulation and/or min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board OB500 SBS-SA (Optional) SBS-SA, SBS-TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -127.5 R-16 Existing asphaltic roof Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3, H-Shield or Multi-Max FA3 M-OSFA Min. 0.25-inch DensDeck Prime M-OSFA SBS-SA (Optional) SBS-SA, SBS-TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -72.5 R-17 Existing asphaltic roof Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3, H-Shield or Multi-Max FA3 M-OSFA (Optional) additional layers(s) of base insulation and/or min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board M-OSFA SBS-SA (Optional) SBS-SA, SBS-TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -157.5 R-18 Existing asphaltic roof Min. 1.5-inch min. 2.0 pcf Insulfoam, Min. 2- inch Polytherm, ACFoam II, min. 1.5-inch Ultra-Max or Multi-Max FA-3, min. 1.3-inch Polytherm G, ACFoam III or min. 1.0-inch ISO 95+GL, Polytherm H, H-Shield, H-Shield CG or ENRGY 3 CR-20 Min. 0.25-inch DensDeck Prime CR-20 SBS-SA (Optional) SBS-SA, SBS-TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -72.5 R-19 Existing asphaltic roof Min. 1.5-inch min. 2.0 pcf Insulfoam CR-20 (Optional) additional layers(s) of base insulation CR-20 SBS-SA (Optional) SBS-SA SBS-SA -240.0 R-20 Existing asphaltic roof Min. 1.5-inch min. 2.0 pcf Insulfoam CR-20 Min. 0.25-inch SECUROCK Gypsum- Fiber Roof Board CR-20 SBS-SA (Optional) SBS-SA, SBS-TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -240.0 R-21 Existing asphaltic roof (Optional if Top Layer Insulation installed) Min. 1.5-inch Ultra-Max or Multi-Max FA-3, min. 1.3-inch Polytherm G, ACFoam III or min. 1.0-inch ISO 95+GL, Polytherm H, H-Shield, H- Shield CG or ENRGY 3 CR-20 (Optional if Base Layer Insulation installed) additional layers(s) of base insulation and/or min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board CR-20 SBS-SA (Optional) SBS-SA, SBS-TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -240.0 R-22 Existing asphaltic roof (Optional if Top Layer Insulation installed) Min. 2-inch Polytherm, ACFoam II, ENRGY-3, Polytherm H or H-Shield CR-20 (Optional if Base Layer Insulation installed) additional layers(s) of base insulation and/or min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board CR-20 SBS-SA (Optional) SBS-SA, SBS-TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -247.5 HYBRID SYSTEMS WITH SELF-ADHERING APP BASE PLY: NEMO|etc. NEMO ETC, LLC Evaluation Report P9290.02.08-R25 for FL1654-R27 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 25: 09/30/2020 ©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 91 of 94 TABLE 7A: RECOVER APPLICATIONS SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER System No. Substrate (Notes 1 & 12) Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP (psf) Type Attach (Notes 6,7,8) Type Attach (Notes 6,7,8) Base Ply Ply Cap Ply R-23 Existing asphaltic roof Min. 1.5-inch Multi-Max FA3 D-IS (Optional) additional layers(s) of base insulation and/or min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board or DensDeck Prime D-IS APP-SA-H (Optional) APP-TA APP-TA -67.5 R-24 Existing asphaltic roof Min. 1.5-inch min. 2.0 pcf Insulfoam D-IS Min. 0.25-inch SECUROCK Gypsum- Fiber Roof Board D-IS APP-SA-H (Optional) APP-TA APP-TA -90.0 R-25 Existing asphaltic roof Min. 1.5-inch Polytherm, ACFoam II or ENRGY 3 D-IS (Optional) additional layers(s) of base insulation and/or min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board D-IS APP-SA-H (Optional) APP-TA APP-TA -90.0 R-26 Existing asphaltic roof Min. 1.5-inch, min. 2.0 pcf Insulfoam OB500 Min. 0.25-inch SECUROCK Gypsum- Fiber Roof Board OB500 APP-SA-H (Optional) APP-TA APP-TA -120.0 R-27 Existing asphaltic roof Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3, Polytherm H or H-Shield OB500 (Optional) additional layers(s) of base insulation and/or min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board OB500 APP-SA-H (Optional) APP-TA APP-TA -127.5 R-28 Existing asphaltic roof Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3, H-Shield or Multi-Max FA3 M-OSFA (Optional) additional layers(s) of base insulation and/or min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board M-OSFA APP-SA-H (Optional) APP-TA APP-TA -157.5 R-29 Existing asphaltic roof Min. 1.5-inch Ultra-Max or Multi-Max FA-3, min. 1.3-inch Polytherm G, ACFoam III or min. 1.0-inch ISO 95+GL, Polytherm H, H-Shield, H- Shield CG or ENRGY 3 CR-20 (Optional) additional layers(s) of base insulation and/or min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board CR-20 APP-SA-H (Optional) APP-TA APP-TA -240.0 R-30 Existing asphaltic roof Min. 2-inch Polytherm, ACFoam II, ENRGY-3, Polytherm H or H-Shield CR-20 (Optional) additional layers(s) of base insulation and/or min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board CR-20 APP-SA-H (Optional) APP-TA APP-TA -247.5 HYBRID SYSTEMS WITH SELF-ADHERING SBS BASE PLY: R-31 Existing asphaltic roof Min. 1.5-inch Multi-Max FA3 D-IS (Optional) additional layers(s) of base insulation and/or min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board or DensDeck Prime D-IS SBS-SA-H (Optional) SBS-TA SBS-TA -67.5 R-32 Existing asphaltic roof Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3 or Multi-Max FA3 or min. 2.0 pcf Insulfoam D-IS Min. 0.25-inch DensDeck Prime D-IS SBS-SA-H (Optional) SBS-TA SBS-TA -72.5 R-33 Existing asphaltic roof Min. 1.5-inch min. 2.0 pcf Insulfoam D-IS Min. 0.25-inch SECUROCK Gypsum- Fiber Roof Board D-IS SBS-SA-H (Optional) SBS-TA SBS-TA -90.0 R-34 Existing asphaltic roof Min. 1.5-inch Polytherm, ACFoam II or ENRGY 3 D-IS (Optional) additional layers(s) of base insulation and/or min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board D-IS SBS-SA-H (Optional) SBS-TA SBS-TA -90.0 NEMO|etc. NEMO ETC, LLC Evaluation Report P9290.02.08-R25 for FL1654-R27 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 25: 09/30/2020 ©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 92 of 94 TABLE 7A: RECOVER APPLICATIONS SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER System No. Substrate (Notes 1 & 12) Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP (psf) Type Attach (Notes 6,7,8) Type Attach (Notes 6,7,8) Base Ply Ply Cap Ply R-35 Existing asphaltic roof Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3, Polytherm H or H-Shield or min. 2.0 pcf Insulfoam OB500 Min. 0.25-inch DensDeck Prime OB500 SBS-SA-H (Optional) SBS-TA SBS-TA -72.5 R-36 Existing asphaltic roof Min. 1.5-inch, min. 2.0 pcf Insulfoam OB500 Min. 0.25-inch SECUROCK Gypsum- Fiber Roof Board OB500 SBS-SA-H (Optional) SBS-TA SBS-TA -120.0 R-37 Existing asphaltic roof Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3, Polytherm H or H-Shield OB500 (Optional) additional layers(s) of base insulation and/or min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board OB500 SBS-SA-H (Optional) SBS-TA SBS-TA -127.5 R-38 Existing asphaltic roof Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3, H-Shield or Multi-Max FA3 M-OSFA Min. 0.25-inch DensDeck Prime M-OSFA SBS-SA-H (Optional) SBS-TA SBS-TA -72.5 R-39 Existing asphaltic roof Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3, H-Shield or Multi-Max FA3 M-OSFA (Optional) additional layers(s) of base insulation and/or min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board M-OSFA SBS-SA-H (Optional) SBS-TA SBS-TA -157.5 R-40 Existing asphaltic roof Min. 1.5-inch min. 2.0 pcf Insulfoam, Min. 2- inch Polytherm, ACFoam II, min. 1.5-inch Ultra-Max or Multi-Max FA-3, min. 1.3-inch Polytherm G, ACFoam III or min. 1.0-inch ISO 95+GL, Polytherm H, H-Shield, H-Shield CG or ENRGY 3 CR-20 Min. 0.25-inch DensDeck Prime CR-20 SBS-SA-H (Optional) SBS-TA SBS-TA -72.5 R-41 Existing asphaltic roof Min. 1.5-inch min. 2.0 pcf Insulfoam CR-20 Min. 0.25-inch SECUROCK Gypsum- Fiber Roof Board CR-20 SBS-SA-H (Optional) SBS-TA SBS-TA -240.0 R-42 Existing asphaltic roof Min. 1.5-inch Ultra-Max or Multi-Max FA-3, min. 1.3-inch Polytherm G, ACFoam III or min. 1.0-inch ISO 95+GL, Polytherm H, H-Shield, H- Shield CG or ENRGY 3 CR-20 (Optional) additional layers(s) of base insulation and/or min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board CR-20 SBS-SA-H (Optional) SBS-TA SBS-TA -240.0 R-43 Existing asphaltic roof Min. 2-inch Polytherm, ACFoam II, ENRGY-3, Polytherm H or H-Shield CR-20 (Optional) additional layers(s) of base insulation and/or min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board CR-20 SBS-SA-H (Optional) SBS-TA SBS-TA -247.5 COLD APPLIED BASE PLY: R-44 Existing asphaltic roof (Optional) Min. 1-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY 3, Polytherm H or H-Shield D-IS Min. 0.25-inch DensDeck Prime, DEXcell FA Glass Mat Roof Board or SECUROCK Gypsum-Fiber Roof Board D-IS SBS-CA1, SBS-CA2 (Optional) SBS-CA1, SBS-CA2 SBS-CA1, SBS- CA2, APP-CA1 -90.0 NEMO|etc. NEMO ETC, LLC Evaluation Report P9290.02.08-R25 for FL1654-R27 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 25: 09/30/2020 ©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 93 of 94 TABLE 7A: RECOVER APPLICATIONS SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER System No. Substrate (Notes 1 & 12) Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP (psf) Type Attach (Notes 6,7,8) Type Attach (Notes 6,7,8) Base Ply Ply Cap Ply R-45 Existing asphaltic roof (Optional) Min. 1-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, EnergyGuard Polyiso Insulation, ENRGY 3, Polytherm H, H-Shield ISO 95+ GL, Multi-Max FA3, RESISTA or UltraMax or min. 2-inch DECKMATE Plus or DECKMATE Plus FA M-OSFA, M-PG1 Min. 0.25-inch DensDeck, DensDeck Prime, DEXcell FA Glass Mat Roof Board, SECUROCK Gypsum-Fiber Roof Board or SECUROCK Glass-Mat Roof Board, min. 7/16-inch DEXcell Cement Roof Board or min. 0.5-inch SECUROCK Cement Roof Board M-OSFA or M-PG1 SBS-CA1, SBS-CA2 (Optional) SBS-CA1, SBS-CA2 SBS-CA1, SBS- CA2, APP-CA1 -120.0 R-46 Existing asphaltic roof (Optional) Min. 1-inch Polytherm or ACFoam II, Polytherm G, ACFoam III, EnergyGuard Polyiso Insulation, ENRGY 3, Polytherm H, H- Shield, ISO 95+ GL, Multi-Max FA3, RESISTA or UltraMax or min. 2-inch DECKMATE Plus or DECKMATE Plus FA M-OSFA, M-PG1 Min. 0.25-inch DensDeck Prime or DEXcell FA Glass Mat Roof Board, min. 7/16-inch DEXcell Cement Roof Board or min. 0.5-inch SECUROCK Cement Roof Board M-OSFA, M- PG1 SBS-CA1 None SBS-CA1, SBS- CA2, APP-CA1 -127.5 R-47 Existing asphaltic roof (Optional) Min. 1-inch Polytherm or ACFoam II, Polytherm G, ACFoam III, EnergyGuard Polyiso Insulation, ENRGY 3, Polytherm H, H- Shield, ISO 95+ GL, Multi-Max FA3, RESISTA or UltraMax or min. 2-inch DECKMATE Plus or DECKMATE Plus FA M-OSFA, M-PG1 Min. 0.25-inch SECUROCK Gypsum- Fiber Roof Board M-OSFA, M- PG1 SBS-CA1, SBS-CA2 None SBS-CA1, SBS- CA2, APP-CA1 -127.5 R-48 Existing asphaltic roof (Optional) Min. 1-inch Polytherm or ACFoam II, Polytherm G, ACFoam III, EnergyGuard Polyiso Insulation, ENRGY 3, Polytherm H, H- Shield, ISO 95+ GL, Multi-Max FA3, RESISTA or UltraMax or min. 2-inch DECKMATE Plus or DECKMATE Plus FA M-OSFA, M-PG1 Min. 0.25-inch DensDeck, DensDeck Prime, DEXcell FA Glass Mat Roof Board, SECUROCK Gypsum-Fiber Roof Board or SECUROCK Glass-Mat Roof Board, min. 7/16-inch DEXcell Cement Roof Board or min. 0.5-inch SECUROCK Cement Roof Board M-OSFA, M- PG1 SBS-CA1, SBS-CA2 None SBS-CA1, SBS- CA2 -157.5 R-49 Existing asphaltic roof (Optional) Min. 1-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY 3, Polytherm H, H-Shield or Multi-Max FA3 OB500 Min. 0.25-inch DensDeck Prime, DEXcell FA Glass Mat Roof Board or SECUROCK Gypsum-Fiber Roof Board OB500 SBS-CA1, SBS-CA2 (Optional) SBS-CA1, SBS-CA2 SBS-CA1, SBS- CA2, APP-CA1 -120.0 R-50 Existing asphaltic roof (Optional) Min. 1-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY 3, Polytherm H, H-Shield or Multi-Max FA3 OB500 Min. 0.25-inch DensDeck Prime or DEXcell FA Glass Mat Roof Board OB500 SBS-CA1 None SBS-CA1, SBS- CA2, APP-CA1 -127.5 R-51 Existing asphaltic roof (Optional) Min. 1-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY 3, Polytherm H, H-Shield or Multi-Max FA3 OB500 Min. 0.25-inch SECUROCK Gypsum- Fiber Roof Board OB500 SBS-CA1, SBS-CA2 None SBS-CA1, SBS- CA2, APP-CA1 -127.5 R-52 Existing asphaltic roof (Optional) Min. 1-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY 3, Polytherm H, H-Shield or Multi-Max FA3 CR-20 Min. 0.25-inch DensDeck Prime or SECUROCK Gypsum-Fiber Roof Board CR-20 SBS-CA1, SBS-CA2 (Optional) SBS-CA1, SBS-CA2 SBS-CA1, SBS- CA2, APP-CA1 -120.0 NEMO|etc. NEMO ETC, LLC Evaluation Report P9290.02.08-R25 for FL1654-R27 Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 25: 09/30/2020 ©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 94 of 94 TABLE 7A: RECOVER APPLICATIONS SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER System No. Substrate (Notes 1 & 12) Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP (psf) Type Attach (Notes 6,7,8) Type Attach (Notes 6,7,8) Base Ply Ply Cap Ply R-53 Existing asphaltic roof (Optional) Min. 1-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY 3, Polytherm H, H-Shield or Multi-Max FA3 CR-20 Min. 0.25-inch DensDeck Prime or DEXcell FA Glass Mat Roof Board CR-20 SBS-CA1 None SBS-CA1, SBS- CA2, APP-CA1 -127.5 R-54 Existing asphaltic roof (Optional) Min. 1-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY 3, Polytherm H, H-Shield or Multi-Max FA3 CR-20 Min. 0.25-inch SECUROCK Gypsum- Fiber Roof Board CR-20 SBS-CA1, SBS-CA2 None SBS-CA1, SBS- CA2, APP-CA1 -127.5 R-55 Existing asphaltic roof (Optional) Min. 1-inch ENRGY 3, Polytherm H, H-Shield, Multi-Max FA3 CR-20 Min. 0.25-inch DensDeck Prime or SECUROCK Gypsum-Fiber Roof Board CR-20 SBS-CA1, SBS-CA2 None SBS-CA1, SBS- CA2 -232.5 TABLE 7B: RECOVER APPLICATIONS SYSTEM TYPE F: NON-INSULATED, BONDED ROOF COVER System No. Substrate (Notes 1 & 12) Primer Roof Cover (Note 15) MDP (psf) Base Ply Ply Cap Ply R-56 Existing asphaltic roof PG100 BP-AA (Optional if using asphalt applied Ply) (Optional if using asphalt applied Base) BP-AA, SBS- AA, SBS-TA or APP-TA SBS-AA, SBS-TA, APP-TA -45.0 R-57 Existing fully-adhered, granule- surfaced modified bitumen None Polyflex, torch-applied (Optional) Polyflex, torch-applied APP-TA -362.5 R-58 Existing fully-adhered, granule- surfaced modified bitumen PG100 Polyflex, torch-applied (Optional) Polyflex, torch-applied APP-TA -445.0