HomeMy WebLinkAboutAPPROVED, New Manual J UpdatedCalculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Nov-30 16:49:01
Right-Suite® Universal 2021 21.0.10 RSU29066 Page 1
...tsoft HVAC\TBD Kenwood Rd (lot 11) PSL Prop.rup Calc = MJ8 Front Door faces: N
1561Job:Load Short Form 7/14/2021Date:House Chris BatemanBy:
Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
Project Information
Heath Residence, NisAir Air ConditioningFor:
TBD Kenwood Rd (Lot 11), Port St. Lucie, FL 34951
Design Information
InfiltrationClgHtg
SimplifiedMethod9041Outside db (°F)
AverageConstruction quality7570Inside db (°F)
0Fireplaces1529Design TD (°F)
L-Daily range
5030Inside humidity (%)
572Moisture difference (gr/lb)
HEATING EQUIPMENT COOLING EQUIPMENT
Make Make Lennox
Trade Trade LENNOX
Model Cond ML14XC1S036-230C**
AHRI ref Coil CBA27UHE-036-230*++TDR
AHRI ref 204289057
Efficiency 100 EFF Efficiency 13.0 EER, 16 SEER
Heating input kW7.8 Sensible cooling Btuh24220
Heating output Btuh26551 Latent cooling Btuh10380
Temperature rise °F21 Total cooling Btuh34600
Actual air flow cfm1153 Actual air flow cfm1153
Air flow factor cfm/Btuh0.045 Air flow factor cfm/Btuh0.049
Static pressure in H2O0.70 Static pressure in H2O0.70
Space thermostat Load sensible heat ratio 0.78
ROOM NAME Area Htg load Clg load Htg AVF Clg AVF
(ft²)(Btuh)(Btuh)(cfm)(cfm)
Laundry 72 1056 1010 47 49
Bed 2 172 2660 1671 119 81
Kitchen 220 301 3281 13 159
Hall 28 0 0 0 0
Lin 9 0 0 0 0
Bath 68 1235 830 55 40
Bed 3 237 3895 2877 174 140
Master Bed 306 4443 3553 199 173
Wtr Clst 23 360 141 16 7
His 28 36 53 2 3
Hers 49 1055 385 47 19
Master Bath 130 2635 1600 118 78
Family Room 327 3159 5311 141 258
DR Foyer 147 3434 2500 154 121
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Nov-30 16:49:01
Right-Suite® Universal 2021 21.0.10 RSU29066 Page 2
...tsoft HVAC\TBD Kenwood Rd (lot 11) PSL Prop.rup Calc = MJ8 Front Door faces: N
WIC 2 23 501 182 22 9
WIC 1 27 1026 343 46 17
House 1863 25795 23736 1153 1153
Other equip loads 1550 823
Equip. @ 0.95 RSM 23430
Latent cooling 6891
TOTALS 1863 27345 30320 1153 1153
2021-Nov-30 16:49:01
Right-Suite® Universal 2021 21.0.10 RSU29066 Page 1
...tsoft HVAC\TBD Kenwood Rd (lot 11) PSL Prop.rup Calc = MJ8 Front Door faces: N
1561Job:Building Analysis 7/14/2021Date:House Chris BatemanBy:
Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
Project Information
Heath Residence, NisAir Air ConditioningFor:
TBD Kenwood Rd (Lot 11), Port St. Lucie, FL 34951
Design Conditions
Location: CoolingHeatingIndoor:7570Indoor temperature (°F)St Lucie Co Intl, FL, US
1529Design TD (°F)ft26Elevation:
5030Relative humidity (%)°N28Latitude:
Outdoor:56.92.4Moisture difference (gr/lb)CoolingHeating
Infiltration:9041Dry bulb (°F)
SimplifiedMethod)L(15-Daily range (°F)
AverageConstruction quality77-Wet bulb (°F)
0Fireplaces7.515.0Wind speed (mph)
Heating
Walls
Glazing
Other
Ceilings
Floors
Infiltration
Ducts
Ventilation
% of loadBtuhBtuh/ft²Component
16.444743.1Walls
14.7401017.5Glazing
0.51483.7Doors
6.818471.0Ceilings
21.257943.13.1Floors
12.133192.2Infiltration
22.76203Ducts
00Piping
00Humidification
5.71550Ventilation0Adjustments
100.027345Total
Cooling
Walls
Glazing
Other
Ceilings
Infiltration
Ducts
Internal Gains
Ventilation
% of loadBtuhBtuh/ft²Component
11.327741.9Walls
21.2519922.7Glazing
0.61503.7Doors
11.127251.5Ceilings
000Floors
3.89280.6Infiltration
28.36941Ducts
3.4823Ventilation
20.45020Internal gains
00Blower
0Adjustments
100.024559Total
Latent Cooling Load = 6891 Btuh
Overall U-value = 0.103 Btuh/ft²-°F
Data entries checked.
2021-Nov-30 16:49:02
Right-Suite® Universal 2021 21.0.10 RSU29066 Page 1
...tsoft HVAC\TBD Kenwood Rd (lot 11) PSL Prop.rup Calc = MJ8 Front Door faces: N
1561Job:Component Constructions 7/14/2021Date:House Chris BatemanBy:
Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
Project Information
Heath Residence, NisAir Air ConditioningFor:
TBD Kenwood Rd (Lot 11), Port St. Lucie, FL 34951
Design Conditions
Location: CoolingHeatingIndoor:
7570Indoor temperature (°F)St Lucie Co Intl, FL, US
1529Design TD (°F)ft26Elevation:
5030Relative humidity (%)°N28Latitude:
Outdoor:56.92.4Moisture difference (gr/lb)CoolingHeating
Infiltration:9041Dry bulb (°F)
SimplifiedMethod)L(15-Daily range (°F)
AverageConstruction quality77-Wet bulb (°F)
0Fireplaces7.515.0Wind speed (mph)
Construction descriptions GainLoss Clg HTMHtg HTMInsul RU-valueAreaOr
BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft²
Walls
Blk Wall, Stucco Ext, R-4.1 Ext Bd inI, 8" Thk, 1/2" Gyp Bd Int Fnsh 8853.155.10.109281ne 5662.02
4382.026843.155.10.109217se
7182.0211223.155.10.109356sw
7492.0211713.155.10.109372nw
24712.0238633.155.10.1091226all
Partitions
Frm Wall, 1/2" Gyp Bd Ext, R-11 Cav Ins, 1/2" Gyp Bd Int Fnsh, 2"x4", 16"
OC Stud
3031.466112.9411.00.101208
Windows
Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.24);
50% blinds 45°, medium; 50% outdoor insect screen; foreground = green
grass (0.23); 1 ft overhang (5.2 ft window ht, 1 ft sep.); 6.8 ft head ht
70622.652516.800.58031ne
70622.652516.800.58031nw
141322.6105016.800.58062all
Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.16);
50% blinds 45°, medium; 50% outdoor insect screen; foreground = green
grass (0.23); 1 ft overhang (1.25 ft window ht, 1 ft sep.); 6.8 ft head ht
10714.210714.200.4908se
10714.210714.200.4908se
21314.221314.200.49015all
Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.22);
50% blinds 45°, medium; 50% outdoor insect screen; foreground = green
grass (0.23); 1 ft overhang (5.17 ft window ht, 1 ft sep.); 6.8 ft head ht
47921.440318.000.62022se
Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.22);
50% blinds 45°, medium; 50% outdoor insect screen; foreground = green
grass (0.23); 1 ft overhang (5.2 ft window ht, 1 ft sep.); 6.8 ft head ht
66821.456118.000.62031se
Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.24);
50% blinds 45°, medium; 50% outdoor insect screen; foreground = green
grass (0.23); 1 ft overhang (4.17 ft window ht, 1 ft sep.); 6.8 ft head ht
40421.531516.800.58019sw
2021-Nov-30 16:49:02
Right-Suite® Universal 2021 21.0.10 RSU29066 Page 2
...tsoft HVAC\TBD Kenwood Rd (lot 11) PSL Prop.rup Calc = MJ8 Front Door faces: N
Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.24);
50% blinds 45°, medium; 50% outdoor insect screen; foreground = green
grass (0.23); 10 ft overhang (5.2 ft window ht, 1 ft sep.); 6.8 ft head ht
35322.626216.800.58016nw
Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.21);
50% blinds 45°, medium; 50% outdoor insect screen; foreground = green
grass (0.23); 10 ft overhang (8 ft window ht, 1 ft sep.); 6.8 ft head ht
141022.0120618.800.65064nw
Doors
Fbrgls Door 1503.731483.697.00.12740se
Ceilings
Attic, Shngl Roof, R-30 Ceil Ins, 1/2" Gyp Bd Int Fnsh 0.0341863 27251.4618470.9930.0
Floors
On Grade Depth, Tile Flr Fnsh 00579428.700.989202
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Nov-30 16:49:02
Right-Suite® Universal 2021 21.0.10 RSU29066 Page 1
...tsoft HVAC\TBD Kenwood Rd (lot 11) PSL Prop.rup Calc = MJ8 Front Door faces: N
1561Job:Project Summary 7/14/2021Date:House Chris BatemanBy:
Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
Project Information
Heath Residence, NisAir Air ConditioningFor:TBD Kenwood Rd (Lot 11), Port St. Lucie, FL 34951
Notes:
Design Information
St Lucie Co Intl, FL, USWeather:
Winter Design Conditions Summer Design Conditions
Outside db °F41 Outside db °F90Inside db °F70 Inside db °F75
Design TD °F29 Design TD °F15Daily range L
Relative humidity %50Moisture difference gr/lb57
Heating Summary Sensible Cooling Equipment Load Sizing
Structure Btuh19592 Structure Btuh16796
Ducts Btuh6203 Ducts Btuh6941Central vent (49 cfm) 1550 Btuh Central vent (49 cfm) Btuh823
Outside air Outside airHumidification Btuh0 Blower Btuh0
Piping Btuh0Equipment load Btuh27345 Use manufacturer's data n
Rate/swing multiplier 0.95InfiltrationEquipment sensible load Btuh23430
Method Latent Cooling Equipment Load SizingSimplified
Construction quality Average0Fireplaces Structure Btuh2918
Ducts Btuh2093Central vent (49 cfm) Btuh1879
CoolingHeating Outside air18631863Area (ft²) Equipment latent load Btuh6891
1644416444Volume (ft³)Air changes/hour 0.200.38 Equipment Total Load (Sen+Lat)Btuh30320
Equiv. AVF (cfm) 55104 Req. total capacity at 0.70 SHR ton2.8
Heating Equipment Summary Cooling Equipment Summary
Make Make LennoxTrade Trade LENNOX
Model Cond ML14XC1S036-230C**AHRI ref Coil CBA27UHE-036-230*++TDR
AHRI ref 204289057Efficiency 100 EFF Efficiency 13.0 EER, 16 SEER
Heating input kW7.8 Sensible cooling Btuh24220Heating output Btuh26551 Latent cooling Btuh10380
Temperature rise °F21 Total cooling Btuh34600Actual air flow cfm1153 Actual air flow cfm1153
Air flow factor cfm/Btuh0.045 Air flow factor cfm/Btuh0.049Static pressure in H2O0.70 Static pressure in H2O0.70
Space thermostat Load sensible heat ratio 0.78
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Nov-30 16:49:02Right-Suite® Universal 2021 21.0.10 RSU29066 Page 1...tsoft HVAC\TBD Kenwood Rd (lot 11) PSL Prop.rup Calc = MJ8 Front Door faces: N
1561Job:Right-J® Worksheet 7/14/2021Date:House Chris BatemanBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name House Laundry
2 Exposed wall 202.0 ft 14.0 ft
3 Room height 8.8 ft 8.0 heat/coolft
4 Room dimensions ft9.0x8.0
5 Room area 1863.0 ft²72.0 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 312 281 885 566 0 0 0 0
.GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nene 16.8216.82 22.6422.64 31 0 525 706 0 0 0 0
.WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 326 217 684 438 0 0 0 0
.GG Impact, Clear Low-e 0.490Impact, Clear Low-e 0.490 sese 14.2114.21 14.2214.22 8 4 107 107 0 0 0 0
11 GG Impact, Clear Low-e 0.490Impact, Clear Low-e 0.490 sese 14.2114.21 14.2214.22 8 4 107 107 0 0 0 0
GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 sese 17.9817.98 21.3921.39 22 3 403 479 0 0 0 0
GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 sese 17.9817.98 21.3921.39 31 4 561 668 0 0 0 0
DD Fbrgls DoorFbrgls Door 0.1270.127 sese 3.693.69 3.733.73 40 40 148 150 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 375 356 1122 718 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.5421.54 19 3 315 404 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 483 372 1171 749 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 31 0 525 706 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 16 0 262 353 0 0 0 0
GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nwnw 18.8518.85 22.0422.04 64 0 1206 1410 0 0 0 0
PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 208 208 611 303 112 112 329 163
CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.990.99 1.461.46 1863 1863 1847 2725 72 72 71 105
FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 1863 202 5794 0 72 14 402 0
6 c) AED excursion 258 -54
Envelope loss/gain 16273 10848 802 215
12 a) Infiltration 3319 928 0 0
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 4 920 0 0
Appliances/other 4100 500
Subtotal (lines 6 to 13)19592 16796 802 715
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 0 0 0 0
14 Subtotal 19592 16796 802 715
15 Duct loads 32%41%6203 6941 32%41%254 295
Total room load 25795 23736 1056 1010
Air required (cfm)Air required (cfm)1153 1153 47 49
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Nov-30 16:49:02Right-Suite® Universal 2021 21.0.10 RSU29066 Page 2...tsoft HVAC\TBD Kenwood Rd (lot 11) PSL Prop.rup Calc = MJ8 Front Door faces: N
1561Job:Right-J® Worksheet 7/14/2021Date:House Chris BatemanBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name Bed 2 Kitchen
2 Exposed wall 26.0 ft 0 ft
3 Room height 8.0 heat/coolft 10.0 heat/coolft
4 Room dimensions ft171.5x1.0 ft20.0x11.0
5 Room area 171.5 ft²220.0 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 112 96 304 194 0 0 0 0
.GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nene 16.8216.82 22.6422.64 16 0 262 353 0 0 0 0
.WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 0 0 0 0 0 0 0 0
.GG Impact, Clear Low-e 0.490Impact, Clear Low-e 0.490 sese 14.2114.21 14.2214.22 0 0 0 0 0 0 0 0
11 GG Impact, Clear Low-e 0.490Impact, Clear Low-e 0.490 sese 14.2114.21 14.2214.22 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 sese 17.9817.98 21.3921.39 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 sese 17.9817.98 21.3921.39 0 0 0 0 0 0 0 0
DD Fbrgls DoorFbrgls Door 0.1270.127 sese 3.693.69 3.733.73 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.5421.54 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nwnw 18.8518.85 22.0422.04 0 0 0 0 0 0 0 0
PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 96 96 282 140 0 0 0 0
CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.990.99 1.461.46 172 172 170 251 220 220 218 322
FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 172 26 746 0 220 0 0 0
6 c) AED excursion -87 -175
Envelope loss/gain 1764 852 218 147
12 a) Infiltration 249 69 0 0
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 0 0 2 460
Appliances/other 250 1700
Subtotal (lines 6 to 13)2012 1171 218 2307
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 8 11 11 15
14 Subtotal 2020 1182 229 2322
15 Duct loads 32%41%640 489 32%41%72 959
Total room load 2660 1671 301 3281
Air required (cfm)Air required (cfm)119 81 13 159
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Nov-30 16:49:02Right-Suite® Universal 2021 21.0.10 RSU29066 Page 3...tsoft HVAC\TBD Kenwood Rd (lot 11) PSL Prop.rup Calc = MJ8 Front Door faces: N
1561Job:Right-J® Worksheet 7/14/2021Date:House Chris BatemanBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name Hall Lin
2 Exposed wall 0 ft 0 ft
3 Room height 8.0 heat/coolft 8.0 heat/coolft
4 Room dimensions ft8.0x3.5 ft3.5x2.5
5 Room area 28.0 ft²8.8 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 0 0 0 0 0 0 0 0
.GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nene 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0
.WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 0 0 0 0 0 0 0 0
.GG Impact, Clear Low-e 0.490Impact, Clear Low-e 0.490 sese 14.2114.21 14.2214.22 0 0 0 0 0 0 0 0
11 GG Impact, Clear Low-e 0.490Impact, Clear Low-e 0.490 sese 14.2114.21 14.2214.22 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 sese 17.9817.98 21.3921.39 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 sese 17.9817.98 21.3921.39 0 0 0 0 0 0 0 0
DD Fbrgls DoorFbrgls Door 0.1270.127 sese 3.693.69 3.733.73 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.5421.54 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nwnw 18.8518.85 22.0422.04 0 0 0 0 0 0 0 0
PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0
CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.990.99 1.461.46 28 28 28 41 9 9 9 13
FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 28 0 0 0 9 0 0 0
6 c) AED excursion -3 -1
Envelope loss/gain 28 38 9 12
12 a) Infiltration 0 0 0 0
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 0 0 0 0
Appliances/other 0 0
Subtotal (lines 6 to 13)28 38 9 12
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution -28 -38 -9 -12
14 Subtotal 0 0 0 0
15 Duct loads 32%41%0 0 32%41%0 0
Total room load 0 0 0 0
Air required (cfm)Air required (cfm)0 0 0 0
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Nov-30 16:49:02Right-Suite® Universal 2021 21.0.10 RSU29066 Page 4...tsoft HVAC\TBD Kenwood Rd (lot 11) PSL Prop.rup Calc = MJ8 Front Door faces: N
1561Job:Right-J® Worksheet 7/14/2021Date:House Chris BatemanBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name Bath Bed 3
2 Exposed wall 9.0 ft 32.0 ft
3 Room height 8.0 heat/coolft 8.0 heat/coolft
4 Room dimensions ft67.8x1.0 ft11.0x21.5
5 Room area 67.8 ft²236.5 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 72 56 178 114 0 0 0 0
.GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nene 16.8216.82 22.6422.64 16 0 262 353 0 0 0 0
.WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 0 0 0 0 0 0 0 0
.GG Impact, Clear Low-e 0.490Impact, Clear Low-e 0.490 sese 14.2114.21 14.2214.22 0 0 0 0 0 0 0 0
11 GG Impact, Clear Low-e 0.490Impact, Clear Low-e 0.490 sese 14.2114.21 14.2214.22 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 sese 17.9817.98 21.3921.39 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 sese 17.9817.98 21.3921.39 0 0 0 0 0 0 0 0
DD Fbrgls DoorFbrgls Door 0.1270.127 sese 3.693.69 3.733.73 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 0 0 0 0 84 84 265 169
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.5421.54 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 0 0 0 0 172 141 444 284
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 31 0 525 706
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nwnw 18.8518.85 22.0422.04 0 0 0 0 0 0 0 0
PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0
CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.990.99 1.461.46 68 68 67 99 237 237 234 346
FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 68 9 258 0 237 32 918 0
6 c) AED excursion -41 115
Envelope loss/gain 765 525 2385 1621
12 a) Infiltration 160 45 568 159
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 0 0 0 0
Appliances/other 0 250
Subtotal (lines 6 to 13)925 570 2953 2029
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 13 18 5 7
14 Subtotal 938 587 2958 2036
15 Duct loads 32%41%297 243 32%41%937 841
Total room load 1235 830 3895 2877
Air required (cfm)Air required (cfm)55 40 174 140
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Nov-30 16:49:02Right-Suite® Universal 2021 21.0.10 RSU29066 Page 5...tsoft HVAC\TBD Kenwood Rd (lot 11) PSL Prop.rup Calc = MJ8 Front Door faces: N
1561Job:Right-J® Worksheet 7/14/2021Date:House Chris BatemanBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name Master Bed Wtr Clst
2 Exposed wall 35.0 ft 3.5 ft
3 Room height 8.5 heat/coolft 8.0 heat/coolft
4 Room dimensions ft18.0x17.0 ft3.5x6.5
5 Room area 306.0 ft²22.8 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 0 0 0 0 0 0 0 0
.GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nene 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0
.WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 0 0 0 0 0 0 0 0
.GG Impact, Clear Low-e 0.490Impact, Clear Low-e 0.490 sese 14.2114.21 14.2214.22 0 0 0 0 0 0 0 0
11 GG Impact, Clear Low-e 0.490Impact, Clear Low-e 0.490 sese 14.2114.21 14.2214.22 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 sese 17.9817.98 21.3921.39 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 sese 17.9817.98 21.3921.39 0 0 0 0 0 0 0 0
DD Fbrgls DoorFbrgls Door 0.1270.127 sese 3.693.69 3.733.73 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 153 134 423 271 28 28 88 56
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.5421.54 19 3 315 404 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 145 129 406 260 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 16 0 262 353 0 0 0 0
GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nwnw 18.8518.85 22.0422.04 0 0 0 0 0 0 0 0
PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0
CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.990.99 1.461.46 306 306 303 448 23 23 23 33
FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 306 35 1004 0 23 4 100 0
6 c) AED excursion 94 -8
Envelope loss/gain 2714 1829 211 82
12 a) Infiltration 660 185 62 17
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 0 0 0 0
Appliances/other 500 0
Subtotal (lines 6 to 13)3374 2514 273 100
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 0 0 0 0
14 Subtotal 3374 2514 273 100
15 Duct loads 32%41%1068 1039 32%41%87 41
Total room load 4443 3553 360 141
Air required (cfm)Air required (cfm)199 173 16 7
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Nov-30 16:49:02Right-Suite® Universal 2021 21.0.10 RSU29066 Page 6...tsoft HVAC\TBD Kenwood Rd (lot 11) PSL Prop.rup Calc = MJ8 Front Door faces: N
1561Job:Right-J® Worksheet 7/14/2021Date:House Chris BatemanBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name His Hers
2 Exposed wall 0 ft 10.5 ft
3 Room height 8.0 heat/coolft 8.0 heat/coolft
4 Room dimensions ft5.5x5.0 ft49.3x1.0
5 Room area 27.5 ft²49.3 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 0 0 0 0 40 40 126 81
.GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nene 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0
.WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 0 0 0 0 44 44 139 89
.GG Impact, Clear Low-e 0.490Impact, Clear Low-e 0.490 sese 14.2114.21 14.2214.22 0 0 0 0 0 0 0 0
11 GG Impact, Clear Low-e 0.490Impact, Clear Low-e 0.490 sese 14.2114.21 14.2214.22 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 sese 17.9817.98 21.3921.39 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 sese 17.9817.98 21.3921.39 0 0 0 0 0 0 0 0
DD Fbrgls DoorFbrgls Door 0.1270.127 sese 3.693.69 3.733.73 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.5421.54 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nwnw 18.8518.85 22.0422.04 0 0 0 0 0 0 0 0
PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0
CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.990.99 1.461.46 28 28 27 40 49 49 49 72
FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 28 0 0 0 49 11 301 0
6 c) AED excursion -3 -21
Envelope loss/gain 27 37 615 221
12 a) Infiltration 0 0 186 52
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 0 0 0 0
Appliances/other 0 0
Subtotal (lines 6 to 13)27 37 801 273
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 0 0 0 0
14 Subtotal 27 37 801 273
15 Duct loads 32%41%9 15 32%41%254 113
Total room load 36 53 1055 385
Air required (cfm)Air required (cfm)2 3 47 19
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Nov-30 16:49:02Right-Suite® Universal 2021 21.0.10 RSU29066 Page 7...tsoft HVAC\TBD Kenwood Rd (lot 11) PSL Prop.rup Calc = MJ8 Front Door faces: N
1561Job:Right-J® Worksheet 7/14/2021Date:House Chris BatemanBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name Master Bath Family Room
2 Exposed wall 21.5 ft 13.0 ft
3 Room height 8.0 heat/coolft 10.0 heat/coolft
4 Room dimensions ft130.0x1.0 ft326.5x1.0
5 Room area 130.0 ft²326.5 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 0 0 0 0 0 0 0 0
.GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nene 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0
.WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 92 70 219 140 0 0 0 0
.GG Impact, Clear Low-e 0.490Impact, Clear Low-e 0.490 sese 14.2114.21 14.2214.22 0 0 0 0 0 0 0 0
11 GG Impact, Clear Low-e 0.490Impact, Clear Low-e 0.490 sese 14.2114.21 14.2214.22 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 sese 17.9817.98 21.3921.39 22 3 403 479 0 0 0 0
GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 sese 17.9817.98 21.3921.39 0 0 0 0 0 0 0 0
DD Fbrgls DoorFbrgls Door 0.1270.127 sese 3.693.69 3.733.73 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 80 80 252 161 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.5421.54 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 0 0 0 0 130 66 208 133
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nwnw 18.8518.85 22.0422.04 0 0 0 0 64 0 1206 1410
PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0
CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.990.99 1.461.46 130 130 129 190 327 327 324 478
FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 130 22 617 0 327 13 373 0
6 c) AED excursion 55 296
Envelope loss/gain 1619 1025 2111 2317
12 a) Infiltration 382 107 289 81
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 0 0 2 460
Appliances/other 0 900
Subtotal (lines 6 to 13)2001 1132 2399 3758
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 0 0 0 0
14 Subtotal 2001 1132 2399 3758
15 Duct loads 32%41%634 468 32%41%760 1553
Total room load 2635 1600 3159 5311
Air required (cfm)Air required (cfm)118 78 141 258
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Nov-30 16:49:02Right-Suite® Universal 2021 21.0.10 RSU29066 Page 8...tsoft HVAC\TBD Kenwood Rd (lot 11) PSL Prop.rup Calc = MJ8 Front Door faces: N
1561Job:Right-J® Worksheet 7/14/2021Date:House Chris BatemanBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name DR Foyer WIC 2
2 Exposed wall 22.0 ft 5.0 ft
3 Room height 10.0 heat/coolft 8.0 heat/coolft
4 Room dimensions ft147.0x1.0 ft5.0x4.5
5 Room area 147.0 ft²22.5 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 0 0 0 0 40 40 126 81
.GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nene 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0
.WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 190 104 326 209 0 0 0 0
.GG Impact, Clear Low-e 0.490Impact, Clear Low-e 0.490 sese 14.2114.21 14.2214.22 8 4 107 107 0 0 0 0
11 GG Impact, Clear Low-e 0.490Impact, Clear Low-e 0.490 sese 14.2114.21 14.2214.22 8 4 107 107 0 0 0 0
GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 sese 17.9817.98 21.3921.39 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 sese 17.9817.98 21.3921.39 31 4 561 668 0 0 0 0
DD Fbrgls DoorFbrgls Door 0.1270.127 sese 3.693.69 3.733.73 40 40 148 150 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 30 30 95 60 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.5421.54 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nwnw 18.8518.85 22.0422.04 0 0 0 0 0 0 0 0
PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0
CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.990.99 1.461.46 147 147 146 215 23 23 22 33
FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 147 22 631 0 23 5 143 0
6 c) AED excursion 117 -10
Envelope loss/gain 2120 1632 292 104
12 a) Infiltration 488 136 89 25
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 0 0 0 0
Appliances/other 0 0
Subtotal (lines 6 to 13)2608 1769 381 129
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 0 0 0 0
14 Subtotal 2608 1769 381 129
15 Duct loads 32%41%826 731 32%41%120 53
Total room load 3434 2500 501 182
Air required (cfm)Air required (cfm)154 121 22 9
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Nov-30 16:49:02Right-Suite® Universal 2021 21.0.10 RSU29066 Page 9...tsoft HVAC\TBD Kenwood Rd (lot 11) PSL Prop.rup Calc = MJ8 Front Door faces: N
1561Job:Right-J® Worksheet 7/14/2021Date:House Chris BatemanBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name WIC 1
2 Exposed wall 10.5 ft
3 Room height 8.0 heat/coolft
4 Room dimensions ft6.0x4.5
5 Room area 27.0 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area Load
number (Btuh/ft²-°F)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 W Blk Wall, Stucco Ext 0.109 ne 3.15 2.02 48 48 151 97
.G Impact, Clear Low-e 0.580 ne 16.82 22.64 0 0 0 0
.W Blk Wall, Stucco Ext 0.109 se 3.15 2.02 0 0 0 0
.G Impact, Clear Low-e 0.490 se 14.21 14.22 0 0 0 0
11 G Impact, Clear Low-e 0.490 se 14.21 14.22 0 0 0 0
G Impact, Clear Low-e 0.620 se 17.98 21.39 0 0 0 0
G Impact, Clear Low-e 0.620 se 17.98 21.39 0 0 0 0
D Fbrgls Door 0.127 se 3.69 3.73 0 0 0 0
W Blk Wall, Stucco Ext 0.109 sw 3.15 2.02 0 0 0 0
G Impact, Clear Low-e 0.580 sw 16.82 21.54 0 0 0 0
W Blk Wall, Stucco Ext 0.109 nw 3.15 2.02 36 36 113 73
G Impact, Clear Low-e 0.580 nw 16.82 22.64 0 0 0 0
G Impact, Clear Low-e 0.580 nw 16.82 22.64 0 0 0 0
G Impact, Clear Low-e 0.650 nw 18.85 22.04 0 0 0 0
P Frm Wall, 1/2" Gyp B 0.101 -2.94 1.46 0 0 0 0
C Attic, Shngl Roof, R 0.034 -0.99 1.46 27 27 27 39
F On Grade Depth, Tile 0.989 -28.68 0.00 27 11 301 0
6 c) AED excursion -18
Envelope loss/gain 593 190
12 a) Infiltration 186 52
b) Room ventilation 0 0
13 Internal gains: Occupants @ 230 0 0
Appliances/other 0
Subtotal (lines 6 to 13)779 243
Less external load 0 0
Less transfer 0 0
Redistribution 0 0
14 Subtotal 779 243
15 Duct loads 32%41%247 100
Total room load 1026 343
Air required (cfm)46 17
2021-Nov-30 16:49:03
Right-Suite® Universal 2021 21.0.10 RSU29066 Page 1
...tsoft HVAC\TBD Kenwood Rd (lot 11) PSL Prop.rup Calc = MJ8 Front Door faces: N
1561Job:Duct System Summary 7/14/2021Date:House Chris BatemanBy:
Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
Project Information
Heath Residence, NisAir Air ConditioningFor:
TBD Kenwood Rd (Lot 11), Port St. Lucie, FL 34951
CoolingHeating
External static pressure in H2O0.70in H2O0.70
Pressure losses in H2O0in H2O0
Available static pressure in H2O0.70in H2O0.70
Supply / return available pressure 0.481 / 0.219 in H2O in H2O0.481 / 0.219
Lowest friction rate in/100ft0.273in/100ft0.273
Actual air flow cfm1153cfm1153
Total effective length (TEL) ft256
Supply Branch Detail Table
Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv
Name (Btuh)(cfm) (cfm)FR (in)(in)Matl Ln (ft)Ln (ft) Trunk
st2120.044.8VlFx0x05.00.29248661235hBath
st2120.050.0VlFx0x07.00.283971432660hBed 2
st2120.043.5VlFx0x06.00.294841041947hBed 3-A
st2120.047.5VlFx0x06.00.287841041947hBed 3-B
st1100.032.1VlFx0x05.00.36473921717hDR Foyer
st3120.051.2VlFx0x06.00.28173921717hDR Foyer-A
st1100.030.1VlFx0x07.00.370155852655cFamily Room
st1100.029.0VlFx0x07.00.373155852655cFamily Room-A
st3120.049.9VlFx0x05.00.28322571055hHers
st3120.045.1VlFx0x04.00.2913253cHis
st1100.029.1VlFx0x06.00.3739681641cKitchen
st1100.027.1VlFx0x06.00.3789681641cKitchen-A
75.08.4VlFx0x04.00.57759571010cLaundry
st3120.051.1VlFx0x07.00.281931412635hMaster Bath
st3120.055.9VlFx0x06.00.2731041192221hMaster Bed
st3120.049.4VlFx0x06.00.2841041192221hMaster Bed-A
st2120.048.2VlFx0x05.00.28620551026hWIC 1
st2120.045.0VlFx0x04.00.2921127501hWIC 2
st3120.048.5VlFx0x04.00.285819360hWtr Clst
Bold/italic values have been manually overridden
2021-Nov-30 16:49:03
Right-Suite® Universal 2021 21.0.10 RSU29066 Page 2
...tsoft HVAC\TBD Kenwood Rd (lot 11) PSL Prop.rup Calc = MJ8 Front Door faces: N
Supply Trunk Detail Table
Trunk Htg Clg Design Veloc Diam H x W Duct
Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk
st2 Peak AVF 500 344 0.283 636 12.0 0x0 VinlFlx st1
st3 Peak AVF 550 407 0.273 700 12.0 0x0 VinlFlx st1
st1 Peak AVF 1327 1325 0.273 751 18.0 0x0 VinlFlx
Return Branch Detail Table
Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct
Name Size (in) (cfm)(cfm)(ft)FR (fpm)(in)(in)Opening (in) Matl Trunk
rb4 0x 2910 198 80.1 0.273 533 10.0 x0 0 VlFx rt1
rb3 0x 1430 97 75.5 0.290 534 7.0 x0 0 VlFx rt1
rb2 0x 6540 856 76.6 0.286 484 18.0 x0 0 VlFx rt1
rb5 0x 2970 233 0 0 0 0 x0 0 VlFx
Return Trunk Detail Table
Trunk Htg Clg Design Veloc Diam H x W Duct
Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk
rt1 Peak AVF 1087 1151 0.273 651 18.0 0x0 VinlFlx
2021-Nov-30 16:49:03
Right-Suite® Universal 2021 21.0.10 RSU29066 Page 1
...tsoft HVAC\TBD Kenwood Rd (lot 11) PSL Prop.rup Calc = MJ8 Front Door faces: N
1561Job:Manual S Compliance Report 7/14/2021Date:House Chris BatemanBy:
Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
Project Information
Heath Residence, NisAir Air ConditioningFor:
TBD Kenwood Rd (Lot 11), Port St. Lucie, FL 34951
Cooling Equipment
Design Conditions
°F76.8Entering coil DB:Btuh24559Sensible gain:°F90.4Outdoor design DB:
°F63.9Entering coil WB:Btuh6891Latent gain:°F77.4Outdoor design WB:
Btuh31450Total gain:°F75.0Indoor design DB:
cfm1153Estimated airflow:%50Indoor RH:
Manufacturer's Performance Data at Actual Design Conditions
Split ACEquipment type:
ML14XC1S036-230C**+CBA27UHE-036-230*++TDRModel:LennoxManufacturer:
cfm1153Actual airflow:
% of load99Btuh24220Sensible capacity:
% of load151Btuh10380Latent capacity:
%70SHR:% of load110Btuh34600Total capacity:
Heating Equipment
Design Conditions
°F68.3Entering coil DB:Btuh27345Heat loss:°F41.0Outdoor design DB:
°F70.0Indoor design DB:
Manufacturer's Performance Data at Actual Design Conditions
Elec stripEquipment type:
Model:Manufacturer:
cfm1153Actual airflow:
°F50Temp. rise:% of load97kW7.8Output capacity:
Meets all requirements of ACCA Manual S.