HomeMy WebLinkAboutAir System Sizing SummaryAir System Sizing Summary for Default System
Project Name: PRIMA VISTA 04/10/2005
Prepared by: ROBERT A SALSBURY, PE, LLC 07:28PU
Air System Information
Air System Name ........................................ Default System Number of zones.................—.....................-.................................1
Equipment Class --------------------------------------------------- SPLT AHU Floor Area .. - - -................------.............. --............_-------1770.0 ftz
Air System Type ........_..._ .............._....................-.-.-... SZCAV Location ........................................ West Palm Beach, Florida
Sizing Calculation Information
Zone and Space Sizing Method:
Zone CFM.................................. Peak zone sensible load Calculation Months -------------------------------------------- ........ Jan to Dec
Space CFM ........................ Individual peak space loads Sizing Data........................................................... User -Modified
Central Cooling Coil Sizing Data
- Total coil load ............................................
............ 6.5
Tons
Load occurs at...............................................................
Aug 1600
Total coil load...........................................................
.. ........78.4
MBH
OA DB / WB ....................................................................................
91.0 / 78.0
°F
Sensible coil load .. ............................................—..........
59.0
MBH
Entering DB / WB------.........----- ---...........
- ...........80.1 / 66.6
°F
Coil CFM at Aug 1500.....................................................
2341
CFM
Leaving DB / WB-------------------------------------------
56.7 / 55.5
°F
Max block CFM ... .................. ..............................
2400
CFM
Coil ADP ----- ---- --- ---.. ----- - -----...--- ...... ... .............................
64.1
°F
Sum of peak zone CFM...........................................
..... 2400
CFM
Bypass Factor ............................................. .............................................
0.100
Sensible heat ratio ..- .....................................................
0.763
Resulting RH . --- .... -- ................. -
..................- ....... 47
%
ft2/Ton ------------------------------------------------------------------------
- 270.9
Design supply temp .---------------------------------------------------------------
68.0
°F
BTU/(hr-ft2) ................. ............................
..................44.3
Zone T-stat Check . -- ..................
......................1 of 1
OK
Water flow @ 10.0 °F rise ................................................
N/A
Max zone temperature deviation ..........................................
0.0
°F
Central Heating Coil Sizing Data
Max coil load-------------------------------------------------------------------------- 9.5 MBH Load occurs at .............................. ......... Des Htg
Coil CFM at Des Htg------------------------------------------------------198 CFM BTU/(hr-ftz)............................ ....................................... .---------.... 5.4
Max coil CFM--------- --------------------------------- -- -------- ----- ----- 2400 CFM Ent. DB / Lvg DB ................... ...................... -- .......65.3 / 109.8 °F
Water flow @ 20.0 °F drop ----- ----- --- -- -- ------ - -------------- N/A
Supply Fan Sizing Data
Actual max CFM----------------------------------------
2400
CFM
Fan motor BHP ...................-............
..................... 0.41
BHP
Standard CFM ---- -- - - ------ - -----------------
----- 2398
CFM
Fan motor kW - .........................................................................
0.30
kW
Actual max CFM/ftz................................................1.36
CFM/ftz
Fan static --------------------- ---- ---- ----........:------------------------------------
0.70
in wg
Outdoor Ventilation Air Data
Design airflow CFM.............................................................400
CFM
CFM/person........................................................................
20.00
CFM/person
CFM/ftz ---- ------------ ----------- - ----------------------------------------
------- 0.23
CFM/ftz
LJ.....I.. A....I.... i., n.............. A n n--- 4 ..i 4
" Zone Sizing Summary for Default System
'reject Name: PRIMA VISTA 04/10/200
'repared by: ROBERT A SALSBURY, PE, LLC 07:28PA
Air System Information
Air System Name... ------------------------------------- Default System
Number of zones .......
Equipment Class ................................................... SPLT AHU
Floor Area ....................
Air System Type ................................. ............. SZCAV
Location .....................
Sizing Calculation Information
Zone and Space Sizing Method:
• Zone CFM---------------------------------- Peak zone sensible load
Calculation Months ---
Space CFM ........................ Individual peak space loads
Sizing Data ..................
Zone Sizing Data
..............................................................1
.-----.._............................1770.0 ft2
......... West Palm Beach, Florida
...................................Jan to Dec
........................... User -Modified
Maximum
Design
Minimum
Time
Maximum
Zone
Cooling
Air
Air
of
Heating
Floor
Sensible
Flow
Flow
Peak
Load
Area
Zone
Zone Name
(MBH)
(CFM)
(CFM)
Load
(MBH)
(ft2)
CFMIft2
Zone 1
46.2
2400
2400
Oct 1500
8.7
1770.0
1.36
Zone Terminal Sizing Data
No Zone Terminal Sizing Data required for this system.
Space Loads and Airflows
Cooling
Time
Air
Heating
Floor
Zone Name /
Sensible
of
Flow
Load
Area
Space
Space Name
Mult.
(MBH)
Load
(CFM)
(MBH)
(ft2)
CFM/ft2
Zone 1
PRIMA VISTA BANK UNITED
1
46.2
Oct 1500
2517
8.7
1770.0
1.42
LJ.. A.. A A 7 r)-- , 4 -9 4
Air System Design Load Summary for Default System
Project Name: PRIMA VISTA 04/10/2005
Prepared by: ROBERT A SALSBURY, PE, LLC 07:28PM
DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Aug 1500
COOLING OA DB / WB 91.0 °F / 78.0 °F
HEATING DATA AT DES HTG
HEATING OA DB / WB '43.0 °F / 36.1 °F
ZONE LOADS
Details
Sensible
(BTU/hr)
Latent
(BTU/hr)
Details
Sensible
(BTU/hr)
Latent
(BTU/hr)
Window &.Skylight Solar Loads
128 ft2
6369
-
128 ft2
-
-
Wall Transmission
430 ftZ
1236
-
430 ft2
1708
-
Roof Transmission
1770 ft2
5697
-
1770 ft2
2378
-
Window Transmission
128 ft2
1132
-
128 ft2
2239
-
Skylight Transmission
0 ft2
0
-
0 ft2
0
-
Door Loads
42 ft2
1519
-
42 ft2
709
-
Floor Transmission
1770 ft2
0
-
1770 ft2
853
-
Partitions
0 ft2
0
-
0 ft2
0
-
Ceiling
564 ft2
119
-
564 ft2
769
-
Overhead Lighting
3823 W
11028
-
0
0
-
Task Lighting
0 W
0
-
0
0
-
Electric Equipment
4500 W
14295
-
0
0
-
People
20
3954
4100
0
0
0
Infiltration
-
0
0
-
0
0
Miscellaneous
-
0
0
0
0
Safety Factor
0%/0%
0
0
0%
0
0
>> Total Zone Loads
45347
4100
8656
0
Zone Conditioning
-
50311
4100
-
8583
0
Plenum Wall Load
0%
0
-
0
0
-
Plenum Roof Load
0%
0
-
0
0
-
Plenum Lighting Load
0%
0
-
0
0
-
Return Fan Load
2400 CFM
0
-
2400 CFM
0
-
Ventilation Load
390 CFM
5510
15254
33 CFM
952
0
Supply Fan Load
2341 CFM
1009
-
198 CFM
-85
-
Space Fan Coil Fans
-
. 0
-
-
0
-
Duct Heat Gain / Loss
5%
2212
-
5%
36
-
>> Total System Loads
59042
19364
94851
0
Central Cooling Coil
-
59042
19363
-
0
0
Central Heating Coil
-
0
-
-
9485
' -
>> Total Conditioning
59042
19363
9485
0
Key:
Positive values are clg loads
Negative values are htg loads
Positive values are htg loads
Negative values are cig loads
U-...1.. A--[..-;- n......,...... A 7 rl--. 4 ..0 4