Loading...
HomeMy WebLinkAboutLighting Controls ComplianceProject: BUH PRIMA VISTA Title: BANK UNITED PRIMA VISTA Type: Office (Business) Location: PORT ST LUCIE, ST LUCIE COUNTY, FL (661200) (WEA File: D Lighting Controls Compliance Acronym Ashrae Description Area No. of Design Min Compli- ID (sq.ft) Tasks CP CP ance FIRST FLR 101 Retail Establishments 1,838 14 15 15 PASSES (Merchandising & Circulation Area) Applicable to all lighting, including accen PASSES Project: BUH PRIMA VISTA Title: BANK UNITED PRIMA VISTA Type: Office (Business) Location: PORT ST LUCIE, ST LUCIE COUNTY, FL (661200) (WEA File: D System Report Compliance PrOSyl System 1 Constant Volume Packaged No. of Units System 1 Component Category Capacity Design Eff Design IPLV Comp- Eff Criteria IPLV Criteria liance Cooling System Air Cooled 65000 to 135000 11.10 8.90 8.30 8.30 PASSES Btu/h Cooling Capacity Air Handling Air Handler (Supply) - 0.80 0.80 PASSES System -Supply Constant Volume PASSES Project: BUH PRIMA VISTA Title: BANK UNITED PRIMA VISTA Type: Office (Business) Location: PORT ST LUCIE, ST LUCIE COUNTY, FL (661200) (WEA File: D Water Heater Compliance Design Min Design Max Comp Description Type Category Eff Eff Loss Loss liance Water Heater 1 Instantaneous Water All ratings PASSES heaters - Electric PASSES 4/10/2005 EnergyGauge FlaCom FLCCSB v1.22 Project: BUH PRIMA VISTA Title: BANK UNITED PRIMA VISTA Type: Office (Business) Location: PORT ST Piping System Compliance Category Pipe Dia Is Operating Ins Cond Ins Req Ins Compliance [inches] Runout? Temp [Btu-in/hr Thick [in] Thick [in] [F] .SF.F] Heating System (Steam, Steam 0.37 True 105.00 0.28 0.75 0.67 PASSES Condensate, & Hot Water) PASSES 4/10/2005 EnergyGauge FlaCom FLCCSB 0.22