HomeMy WebLinkAboutNew Signed Energy CodeFORM R405-2020
RESIDENTIAL ENERGY CONSERVATION CODE DOCUMENTATION CHECKLIST
Florida Department of Business and Professional Regulation
Simulated Performance Alternative (Performance) Method
Applications for compliance with the 2020 Florida Building Code, Energy Conservation via the
Residential Simulated Performance Alternative shall include:
❑ This checklist
❑ Form R405-2020 report
❑ Input summary checklist that can be used for field verification (usually four pages/may be greater)
❑ Energy Performance Level (EPL) Display Card (one page)
❑ HVAC system sizing and selection based on ACCA Manual S or per exceptions provided in Section R403.7
❑ Mandatory Requirements (five pages)
Required prior to CO:
❑ Air Barrier and Insulation Inspection Component Criteria checklist (Table R402.4.1.1 - one page)
❑ A completed 2020 Envelope Leakage Test Report (usually one page); exception in R402.4
allows dwelling units of R-2 Occupancies and multiple attached single family dwellings to
comply with Section C402.5
❑ If Form R405 duct leakage type indicates anything other than "default leakage", then a completed
2020 Duct Leakage Test Report - Performance Method (usually one page)
11/1212021 10:43:22 AM EnergyGaugeO USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 1 of 1
FORM R405-2020
FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION
Florida Department of Business and Professional Regulation - Residential Performance Method
Project Name: TBD Carlton PSL Prop
Street: TBD Carlton
City, State, Zip: Fort Pierce , FL , 34983
Owner: Chhay Residence
Design Location: FL, ST_LUCIE_CO_INTL
Builder Name: PSL Prop
Permit Office:
Permit Number:
Jurisdiction: St. Lucie
County: St. Lucie (Florida Climate Zone 2 )
1. New construction or existing New (From Plans) 10. Wall Type$2470.0 sgft.) Insulation Area
2. Single family or multiple family Detached a. Concrete Block - Exl Insul, Exterior R=4.1 2115.00 ft2
b. Interior Frame - Wood, Interior R=11.0 355.00 ft2
3. Number of units, if multiple family 1 c. N/A R= ft2
4. Number of Bedrooms 4 d. N/A R= ft2
5. Is this a worst case? Yes 11. Ceiling Types (2155.0 sqft.) Insulation Area
a. Under Attic (Vented) R=30.0 2155.00 ft2
6. Conditioned floor area above grade (ft2) 2155 b. N/A R= ft2
Conditioned floor area below grade (ft2) 0 c. N/A R= ft2
7, Windows 167.6 sgft.) Description Area tion A12. Ducts R
( a. Sup: Attic, Ret: Attic, AH: Garage 6 85959
a. U-Factor: Sgl, U=0.65 63.50 ft2
SHGC: SHGC=0.21
b. U-Factor: Sgl, U=0.58 59.36 ft2 13. Cooling systems kBtu/hr Efficiency
SHGC: SHGC=0.24 a. Central Unit 47.0 SEER:16.00
c. U-Factor: Sgl, U=0.62 44.78 ft2
SHGC: SHGC=0.22 14. Heating systems k8tu/hr Efficiency
Area Weighted Average Overhang Depth: 3.995 ft.
a. Electric Strip Heal 31.4 COP:1.00
Area Weighted Average SHGC: 0.223
8. Skylights Area
c. U-Factoc(AVG) N/A ft2 15. Hot water systems
SHGC(AVG): N/A a. Electric Cap: 50 gallons
9. Floor Types (2153.7 sgft.) Insulation Area EF: 0.960
a. Slab -On -Grade Edge Insulation R=0.0 2153.70 ft2 b. Conservation features
b. N/A R= ft2 None
c. N/A R= ft2 16. Credits Pstat
Glass/Floor Area: 0.078 Total Proposed Modified Loads: 65.56 rF1�7�7
p /� SS
Total Baseline Loads: 67,42
I hereby certify that the plans and specifications covered by
this calculation are in compliance with the Florida Energy
Code. PREPARED BY: CAZ�acf�
DATE: 11 /12/2021
I hereby certify that this building, as a ne in co nce
with the Florida Energy Code.
OWNER/AGEN :
DATE:
Review of the plans and
specifications covered by this
calculation indicates compliance
with the Florida Energy Code.
Before construction is completed
this building will be inspected for
compliance with Section 553.908
Florida Statutes.
BUILDING OFFICIAL:
DATE:
- Compliance requires certification by the air handler unit manufacturer that the air handler enclosure qualifies as
certified factory -sealed in accordance with R403.3.2.1.
- Compliance requires an Air Barrier and Insulation Inspection Checklist in accordance with R402.4.1.1 and this project requires an
envelope leakage test report with envelope leakage no greater than 6.00 ACH50 (R402.4.1.2).
11/12/2021 10:43 AM 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 1 of 7
FORM R405 2020 INPUT SUMMARY CHECKLIST REPORT
PROJECT
Title:
TBD Carlton PSL Prop
Bedrooms:
4
Address Type: Street Address
Building Type:
User
Conditioned Area:
2155
Lot #
Owner Name:
Chhay Residence
Total Stories:
1
Block/Subdivision:
# of Units:
1
Worst Case:
Yes
PlatBook:
Builder Name:
PSL Prop
Rotate Angle:
180
Street:
TBD
Carlton
Permit Office:
Cross Ventilation:
No
County:
St. Lucie
Jurisdiction:
St. Lucie
Whole House Fan:
No
City, State,
Zip: Fort
Pierce ,
Family Type:
Detached
FL ,
34983
New/Existing:
New (From Plans)
Comment:
CLIMATE
Design
Temp
mt Design Temp
Healing
Design Daily Temp
Design Location
TMY Site
97.5 %
2.5 %
Winter
Summer Degree Days
Moisture
Range
FL, ST_LUCIE_CO_INTL
FL_VERO_BEACH_MUNI
39
90
70
75
299
58
Medium
BLOCKS
Number
Name
Area
Volume
1
Entire House
2155
21550
SPACES
Number
Name
Area
Volume Kitchen
Occupants
Bedrooms
Infil ID
Finished
Cooled
Heated
1
Tackle Room
36
360 No
0
1
Yes
Yes
Yes
2
Master Bed
236
2360 No
0
1
1
Yes
Yes
Yes
3
M Hall
26
260 No
0
1
Yes
Yes
Yes
4
M Bath
75
750 No
0
1
Yes
Yes
Yes
5
WIC 2
49
490 No
0
1
Yes
Yes
Yes
6
Master Bed 2
203
2030 No
0
1
1
Yes
Yes
Yes
7
Bath 2
56
560 No
0
1
Yes
Yes
Yes
8
Family Room
285
2860 No
2
1
Yes
Yes
Yes
9
Pantry
15
150 No
0
1
Yes
Yes
Yes
10
Lin
15
150 No
0
1
Yes
Yes
Yes
11
Bath
47
470 No
0
1
Yes
Yes
Yes
12
Bed 3
149
1490 No
0
i
1
Yes
Yes
Yes
13
Bed 2
142
1420 No
0
1
1
Yes
Yes
Yes
14
M Hall
32
320 No
0
1
Yes
Yes
Yes
15
Kitchen
145
1450 Yes
2
1
Yes
Yes
Yes
16
Hall
106
1060 No
0
1
Yes
Yes
Yes
17
Foyer
225
2250 No
0
1
Yes
Yes
Yes
18
Living Room
266
2660 No
2
1
Yes
Yes
Yes
19
WIC
47
470 No
0
1
Yes
Yes
Yes
11/12/2021 10:43 AM 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 2 of 7
rnonn onnr;--onon IMPI ITME, 0 CI IMMARY11�. CHFCKI.IRT REPORT
�Ixlvl
FLOORS
# Floor Type
Space
Perimeter Perimeter R-Value
Area
Joist R-Value7Wood
1 Slab -On -Grade
Edge
Insulatio
Tackle Room
6.5 ft
0
35.8 ft2
____
2 Slab -On -Grade
Edge
Insulatio
Master Bed
31 ft
0
236.3 ft2
----
3Slab-On-Grade
Edge
Insulatio
M Hall
1 ft
0
26 ft2
4 Slab -On -Grade
Edge
Insulatio
M Bath
14.5 ft
0
74.8 ft2
____
5Slab-On-Grade
Edge
Insulatio
WIC 2
14 ft
0
48.8 ft2
____
6 Slab -On -Grade
Edge
Insulatio
Master Bed 2
28.5 ft
0
203 ft2
____ 1
0
0
7 Slab -On -Grade
Edge
Insulatio
Bath 2
7.5 ft
0
56.3 ft2
____ 1
0
0
8 Slab -On -Grade
Edge
Insulatio
Family Room
19 it
0
285 ft2
____ 1
0
0
9Slab-On-Grade
Edge
Insulatio
Pantry
1 ft
0
15 ft2
1
0
0
10SIab-On-Grade
Edge
Insulatio
Lin
1 ft
0
15 ft2
____ 1
0
0
11Slab-On-Grade
Edge
Insulatio
Bath
8.5 ft
0
46.8 ft2
---- 1
0
0
12SIab-On-Grade
Edge
Insulatio
Bed 3
24.5 ft
0
148.5 ft2
---- 1
0
0
13Slab-On-Grade
Edge
Insulatio
Bed 2
18.5 it
0
141.8 ft2
____ 1
0
0
14SIab-On-Grade
Edge
Insulatio
M Hall 2
4.5 ft
0
31.5 ft2
____ 1
0
0
15SIab-On-Grade
Edge
Insulatio
Kitchen
3 ft
0
145 ft2
1
0
0
16Slab-On-Grade
Edge
Insulatio
Hall
t ft
0
106 f12
1
0
0
17SIab-On-Grade
Edge
Insulatio
Foyer
30 It
0
224.8 ft2
____ 1
0
0
18SIab-On-Grade
Edge
Insulatio
Living Room
20 ft
0
266 ft2
____ 1
0
0
igSlab-On-Grade
Edge
Insulatio
WIC
17ft
0
47.3 ft2
____ 1
0
0
ROOF
Roof
Gable
Roof
Red
Solar
SA Emitt
Emitt
Deck
Pitch
# Type
Materials
Area
Area
Color
Barr
Absor.
Tested Tested
Insul.
(deg)
1 Hip
Composition shingles 2409 ft2
0 ft2
Medium
N
0.8
No 0.9
No
0
26.57
ATTIC
WIN
J#
Type
Ventilation
Vent Ratio (1
in)
Area
RBS
IRCC
1 Full attic
Vented
300
2155 ft2
N
N
11/12/2021 10:43 AM 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 3 of 7
non IAIDI IT SI IMMARV CWFRKI IST RFPCIRT
CEILING
#
Ceiling Type
Space
R-Value
Ins Type
Area
Framing Free Truss Type
1
Under Attic (Vented)
Tackle Room
30
Blown
36 ft'
0.1
Wood
2
Under Attic (Vented)
Master Bed
30
Blown
236 ft'
0.1
Wood
3
Under Attic (Vented)
M Hall
30
Blown
26 IN
0.1
Wood
4
Under Attic (Vented)
M Bath
30
Blown
75 ft'
0.1
Wood
5
Under Attic (Vented)
WIG
30
Blown
49 ft'
0.1
Wood
6
Under Attie (Vented)
Master Bed 2
30
Blown
203 ft'
0.1
Wood
7
Under Attic (Vented)
Bath 2
30
Blown
56 ft°
0.1
Wood
8
Under Attic (Vented)
Family Room
30
Blown
285 ft'
0.1
Wood
9
Under Attie (Vented)
Pantry
30
Blown
15 ft'
0.1
Wood
10
Under Attic (Vented)
Lin
30
Blown
15 ft'
0.1
Wood
11
Under Attic (Vented)
Bath
30
Blown
47 ft'
0.1
Wood
12
Under Attic (Vented)
Bed 3
30
Blown
149 ft'
0.1
Wood
13
Under Attic (Vented)
Bed 2
30
Blown
142 ft'
0.1
Wood
14
Under Attic (Vented)
M Hall 2
30
Blown
32 ft'
0.1
Wood
15
Under Attic (Vented)
Kitchen
30
Blown
145 ft'
0.1
Wood
16
Under Attic (Vented)
Hall
30
Blown
106 W
0.1
Wood
17
Under Attic (Vented)
Foyer
30
Blown
225 ft'
0.1
Wood
18
Under Attic (Vented)
Living Room
30
Blown
266 ft'
0.1
Wood
19
Under Attic (Vented)
WIC
30
Blown
47 ft'
0.1
Wood
WALLS
Adjacent
Cavity
Width
Height
Sheathing
Framing
Solar
Below
Space
Ff
Ft
AraA
R-\/ I
Ff rf'nn
Absor
Gra
I TTp
R=V/ hle
In
In
e
1
E=>W
Tackle R Interior Frame - Wood Tackle Room
11
6
6 10
0
65.0 ft'
0
0.25
0.8
0
2
S=>N
Exterior Concrete
Block -
Ext
InstMaster Bed
4.1
17
6 10
0
175.0 ft'
0
0
0.3
0
3
W=>E
Exterior Concrete
Block -
Ext
InsMaster Bed
4.1
13
6 10
0
135.0 ft'
0
0
0.3
0
_ 4
N=>S
Exterior Concrete
Block -
Ext
Insul M Bath
4.1
8
0 10
0
80.0 fP
0
0
0.3
0
_ 5
W=>E
Exterior Concrete
Block -
Ext
Insul M Bath
4.1
6
6 10
0
65.0 ft'
0
0
0.3
0
6
N=>S
Exterior Concrete
Block -
Ext
Insul WIC 2
4.1
6
6 10
0
65.0 W
0
0
0.3
0
7
E=>W
Exterior Concrete
Block -
Ext
Insul WIC 2
4.1
7
6 10
0
75.0 ft°
0
0
0.3
0
8
E=>W
Exterior Concrete
Block -
Ext
In9dhsler Bed 2
4A
14
6 10
0
145.0 W
0
0
0.3
0
_ 9
S=>N
Exterior Concrete
Block -
Ext
In3dhster Bed 2
4.1
14
0 10
0
140.0 ft'
0
0
0.3
0
10
N=>S
Exterior Concrete
Block -
Ext
Insul Bath 2
4.1
7
6 10
0
75.0 ft'
0
0
0.3
0
_ 11
N=>S
Exterior Concrete
Block -
Ext
InffAmily Room
4.1
19
0 10
0
190.0 ft'
0
0
0.3
0
12
N=>S
Exterior Concrete
Block -
Ext
Insul Bath
4.1
8
6 10
0
85.0 ft'
0
0
0.3
0
_ 13
N=>S
Exterior Concrete
Block -
Ext
Insul Bed 3
4.1
13
6 10
0
135.0 ft'
0
0
0.3
0
14
W=>E
Exterior Concrete
Block -
Ext
Insul Bed 3
4.1
11
0 10
0
110.0 ft'
0
0
0.3
0
15
S=>N
Exterior Concrete
Block -
Ext
Insul Bed 2
4.1
8
0 10
0
80.0 ftz
0
0
0.3
0
16
W=>E
Exterior Concrete
Block -
Ext
Insul Bed 2
4A
10
6 10
0
105.0 W
0
0
0.3
0
_ 17
S=>N
Exterior Concrete
Block -
Ext
InsulM Hall 2
4.1
4
6 10
0
45.0 ft'
0
0
0.3
0
_ 18
E=>W
Exterior Concrete
Block -
Ext
Insul Kitchen
4.1
3
0 10
0
30.0 ft'
0
0
0.3
0
19
E=>W
Exterior Concrete
Block-
Ext
Insul Foyer
4.1
15
6 10
0
155.0 ft'
0
0
0.3
0
20
S=>N
Tackle R Interior Frame
- Wood Foyer
11
14
6 10
0
145.0 Itz
0
0.25
0.8
0
21
W=>E
Exterior Concrete
Block -
Ext
InsUNing Room
4.1
19
0 10
0
190.0 ft'
0
0
0.3
0
11/12/2021 10:43 AM 7.0.00 - FlaRes2020 FBC 7th Edifion (2020) Compliant Software Page 4 of 7
INPUT SUMMARY CHECKLIST REPORT
FORM R405-2020
INPUT SUMMARY CHECKLIST REPORT
WALLS
Adjacent Cavity Width Height Sheathing Framing Solar Below
SIt Ornt TO lAtnfl Typepace _ I FL- Et In Area a u i Pmreon--A
22 S=>N Tackle R Interior Frame - Wood Living Room 11 1 0 10 0 10.0 ft' 0 0.25 0.8 0
23 S=>N Exterior Concrete Block- Ext Insul WIC 4.1 3 6 10 0 35.0 ft' 0 0 0.5 0
24 E=>W Tackle R Interior Frame - Wood WIC 11 13 6 10 0 135.0 ft' 0 0.25 0.8 0
DOORS
# Ornt Door Type Space Storms LI-Value Width Height Area
Ft In Ft In
_ 1 S=>N Insulated M Hall 2 None A3 2 8 8 21.3 ft'
2 E=>W Insulated Foyer None .13 6 8 48 ft'
WINDOWS
Orientation shown is the entered orientation => changed to Worst Case.
/ Wall Overhang
V # Ornl ID Frame Panes NFRC LI-Factor SHGC Imp Area Depth Separation Int Shade Screening
1 W=>E 3 Metal Low-E Single Yes 0.58 0.24 Y 15.5 ft° 1 It 0 in 1 ft 0 in Drapes/blinds Exterior 5
2 W=>E 5 Metal Low-E Single Yes 0.58 0.24 Y 6.0 ft' 1 ft 0 in 1 ft 0 in Drapes/blinds Exterior 5
3 E=>W 8 Metal Low-E Single Yes 0.62 0.22 Y 22A ft' 1 ft 0 in 1 ft 0 in Drapes/blinds Exterior 5
4 N=>S 11 Metal Low-E Single Yes 0.65 0.21 Y 15.5 ft' 1 ft 0 in 1 ft 0 in None None
5 N=>S 12 Metal Low-E Single Yes 0.58 0.24 Y 6.9 ft' 1 ft 0 in 1 ft 0 in Drapes/blinds Exterior 5
6 W=>E 14 Metal Low-E Single Yes 0.58 0.24 Y 15.5 ft' 1 It 0 in 1 ft 0 in Drapes/blinds Exterior 5
7 W=>E 16 Metal Low-E Single Yes 0.68 0.24 Y 15.5 R' 1 ft 0 in 1 ft 0 in Drapes/blinds Exterior 5
8 E=>W 19 Metal Low-E Single Yes 0.62 0.22 Y 22.4 ft' 8 ft 5 in 1 ft 0 in Drapes/blinds Exterior 5
9 W=>E 21 Metal Low-E Single Yes 0.65 0.21 Y 48.0 ft' 8 it 0 in 1 ft 0 in None None
GARAGE
# Floor Area Ceiling Area Exposed Wall Perimeter Avg. Wall Height Exposed Wall Insulation
1 382.8 ft' 382.8 ft' 64 It 8 It 1
INFILTRATION
# Scope Method SLA CFM 50 ELA EgLA ACH ACH 50
1 Wholehouse Proposed ACH(50) .000381 2155 118.23 221.96 .1184 6
HEATING SYSTEM
# System Type Subtype Speed Efficiency Capacity Block Ducts
1 Electric Strip Heat/ None COPA 31.37 kBtu/hr 1 sys#1
11/12/2021 10:43 AM 7.0.00 - FlaRes2020 FBC 7lh Edition (2020) Compliant Software Page 5 of 7
11/12/2021 10:43 AM 7.0.00 - FlaRes2020 FBC 7lh Edition (2020) Compliant Software Page 5 of 7
FORM R405-2020 INPUT SUMMARY CHECKLIST REPORT
COOLING SYSTEM
# System Type
Subtype
Subtype Efficiency
Capacity
Air Flow
SHR Block
Ducts
1 Central Unit/
Split
Singl
SEER: 16
47 kBtu/hr
1410
cfm
0.85
1
sys#1
HOT WATER SYSTEM
# System Type
Sub -Type
Location
EF
Cap
Use
SetPnt
Conservation
1 Electric
None
Garage
0.96
50 gal 60.9 gal
120 deg
None
SOLAR HOT
WATER SYSTEM
FSEC
Collector
Storage
Cart # Company Name
System Model # Collector Model
# Area
Volume
FEF
None None
ft'
DUCTS
/ ---- Supply ----
---- Return ----
Air
CFM 25
CFM25
HVAC #
v # Location R-Value
Area
Location
Area
Leakage Type
Handler
TOT
OUT QN
RLF
Heat Cool
1 Attic
6 859 ft'
Attie
859 ft'
Default Leakage
Garage
(Default)
(Default)
1 1
TEMPERATURES
Programablee Thermostat:
Cr[eij]ling Fans:Jan
]]Y
Heating [X� Jan [X1 Feb
jj ]]
[X] Mar
Apr
May
((]]
Jun [X] Jul
[[ ]]
[X] Aug
[[ ]]
[X1 Sep
Cottrj
NovrDee
Nov
Dec
Venting ll 1111 Jan [( 11 Feb
[[X1l Mar
[ ]May
LXl Jun ll 11 Jul
[[ ]] Aug
[( ]] Sep
[X1
[
Thermostat Schedule: HERS 2006 Reference
Hours
Schedule Type
1
2 3
4
5 6
7
8
9
10
11
12
Cooling (WD) PM
80
80 78
78
78
78
78
78
78
78 78
78
Cooling (WEH) PM
78
78 78
78
78 78
78
78
78
78
78
78
Heating (WD) PM
68
68 68
68
68 68
68
68
68
68
66
66
Healing (WEH) PM
68
68 68
68
68 68
68
68
68
68
66
66
MASS
Mass Type
Area
Thickness
Furniture Fraction
Space
Default(8 Ibs/sq.ft.
0 ft'
0 ft
0.3
Tackle Room
Default(8 Ibs/sq.ft.
ft'
ft
0.3
Master Bed
Default(8 Ibs/sq.ft.
112
ft
0.3
M Hall
Default(8 Ibs/sq.ft.
ft'
It
0.3
M Bath
Default(8 lbs/sq.ft.
ft'
ft
0.3
WIC 2
Default(8 Ibs/sq.ft.
ft'
ft
0.3
Master Bed 2
Default(8 Ibs/sq.ft.
ft'
ft
0.3
Bath 2
Default(8 Ibs/sq.ft.
ft'
ft
0.3
Family Room
Default(8 lbs/sq.ft.
ft'
ft
0.3
Pantry
Default(8 lbs/sq.ft.
ft'
it
0.3
Lin
Default(8 lbs/sq.ft.
ft'
ft
0.3
Bath
nefM1 affa ihcl�n ft
ft'
ft
0.3
Bed 3
11/12/2021 10:43 AM 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 6 of 7
FORM R405-2020
INPUT SUMMARY
CHECKLIST
REPORT
MASS
Mass Type
Area
Thickness
Furniture Fraction
Space
Default(8 Ibs/sq.ft.
ft2
ft
0.3
Bed 2
Default(8 Ibs/sq.ft.
ft2
ft
0.3
M Hall 2
Default(8 lbs/sq.ft.
ft2
ft
0.3
Kitchen
Default(8 lbs/sq.ft.
ft2
ft
0.3
Hall
Default(8 lbs/sq.ft,
ft2
ft
0.3
Foyer
Default(8 Ibs/sq.ft.
ft2
ft
0.3
Living Room
nafaiilfrA Ihgfgn ft
ft2
ft
0.3
WIC
11/12/2021 10:43 AM 7.0.00 - FlaRes2020 FBC 7lh Edition (2020) Compliant Software Page 7 of 7
FORM R405-2020
ENERGY PERFORMANCE LEVEL (EPL) DISPLAY L AAKU
ESTIMATED ENERGY PERFORMANCE INDEX* = 97
The lower the EnergyPerformance Index, the more efficient the home.
TBD Carlton, Fort Pierce, FL, 34983
1.
New construction or existing
New (From Plans)
10. Wall Type and Insulation
Insulation
Area
a. Concrete Block - In , Exterior
R=4.1
25.00
2.
Single family or multiple family
Detached
Interior
b. Interior Frame -W0000 Interior
R=11.0
55.00
3 Wd,
3.
Number of units, if multiple family
i
c. NIA
R=
ft2
4
d. N/A
R=
112
4.
Number of Bedrooms
11. Ceiling Type and insulation level
Insulation
Area
5.
Is this a worst case?
Yes
a. Under Attic (Vented)
R=30.0
2155.00 ft2
6.
Conditioned Floor area (ft2)
2155
b. NIA
R=
ft2
c. N/A
R=
ft2
7.
Windows" Description
Area
12, Ducts, location & insulation level
R ft2
a. U-Factor: Sgl, U=0.65
63.50 ft2
a. Sup: Attic, Rel: Attic, AH: Garage
6 859
SHGC: SHGC=0.21
b. U-Factor: Sgl, U=0.58
59.36 ft2
SHGC: SHGC=0.24
13. Cooling systems
kBtu/hr
Efficiency
c. U-Factor: Sgl, U=0.62
44.78 ft2
a. Central Unit
47.0 SEERA6.00
SHGC: SHGC=0.22
d. U-Factor: N/A
ft2
14. Heating systems
kBtu/hr
Efficiency
SHGC:
a. Electric Strip Heat
31.4
COP:1.00
Area Weighted Average Overhang Depth:
3.995 ft.
Area Weighted Average SHGC:
0.223
8. Skylights Description
Area
15. Hot water systems
Cap: 50 gallons
a. U-Factor(AVG): NIA
ft2
a. Electric
EF: 0.96
SHGC(AVG): NIA
b. Conservation features
9. Floor Types
Insulation
Area
None
a. Slab -On -Grade Edge Insulation
R=0.0
2153.70 ft2
Credits (Performance method)
Pstat
b. NIA
R=
ft2
c. NIA
R=
ft'
I certify that this home has complied with the Florida Energy Efficiency Code for Building
Construction through the above energy saving features which will be installed (or exceeded)
in this home before final inspection. O rwise, a new E - Display Card will be completed
based on installed Code complian t s.
Builder Signature: t/� ' we�o Date:
�r
Address of New Home: CQ(14i6l City/FL Zip:r
3C/4?a
*Note: This is not a Building Energy Rating. If your Index is below 70, your home may qualify for energy efficient
mortgage (EEM) incentives if you obtain a Florida Energy Rating. For information about the Florida Building Code,
Energy Conservation, contact the Florida Building Commission's support staff.
**Label required by Section R303.1.3 of the Florida Building Code, Energy Conservation, if not DEFAULT.
11/12/2021 10:43 AM 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 1 of 1
Florida Building Code, Energy Conservation, 7th Edition (2020)
atory Requirements for Residential Performance, Prescriptive and ERI Methods
ADDRESS: TBD Carlton Permit Number:
Fort Pierce , FL , 34983
MANDATORY REQUIREMENTS - See individual code sections for full details.
J
SECTION R401 GENERAL
R401.3 Energy Performance Level (EPL) display card (Mandatory).The building official she require that an energy performance level (EPL)
display card be completed and certified by the builder to be accurate and correct before final approval of the building for occupancy. Florida law
(Section 553.9085, Florida Statutes) requires the EPL display card to be included as an addendum to each sales contract for both presold and
nonpresold residential buildings. The EPL display card contains information indicating the energy performance level and efficiencies of components
installed in a dwelling unit. The building official shall verify that the EPL display card completed and signed by the builder accurately reflects the plans
and specifications submitted to demonstrate code compliance for the building. A copy of the EPL display card can be found in Appendix RD.
SECTION R402 BUILDING THERMAL ENVELOPE
❑ R402.4 Air leakage (Mandatory). The building thermal envelope shall be constructed to limit air leakage in accordance with the requirements of
Sections R402.4.1 through R402.4.5.
Exception: Dwelling units of R-2 Occupancies and multiple attached single family dwellings shall be permitted to
comply with Section C402.5.
R402.4.1
Building thermal envelopeThe building thermal envelope
shall comply with Sections R402.4.1.1 and
❑
R402.4.1.2.
The sealing methods between dissimilar materials shall
allow for differential expansion and contraction.
❑ R402.4.1.1 Installation. The components of the building thermal envelope as listed in Table R402.4.1.1 shall be installed in accordance
with the manufacturer's instructions and the criteria listed in Table R402.4.1.1, as applicable to the method of construction. Where required
by the code official, an approved third party shall inspect all components and verify compliance.
❑ R402.4.1.2 Testing. The building or dwelling unit shall be tested and verified as having an air leakage rate not exceeding seven air
changes per hour in Climate Zones 1 and 2, and three air changes per hour in Climate Zones 3 through 8. Testing shall be conducted in
accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g. (50 pascals). Testing shall be conducted by either
individuals as defined in Section 553.993(5) or (7), Florida Statutes, or individuals licensed as set forth In Section 489.105(3)(f), (g) or (i) or
an approved third party. A written report of the results of the test shall be signed by the party conducting the test and provided to the code
official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope.
Exception: Testing is not required for additions, alterations, renovations, or repairs, of the building thermal envelope of existing
buildings in which the new construction is less than 85 percent of the building thermal envelope.
During testing:
1. Exterior windows and doors, freplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or
other infiltration control measures.
2. Dampers including exhaust, intake, makeup air, backdraf and flue dampers shall be closed, but not sealed beyond intended
infiltration control measures.
3. Interior doors, if installed at the time of the test, shall be open.
4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed.
5. Heating and cooling systems, if installed at the time of the test, shall be turned off.
6. Supply and return registers, if installed at the time of the test, shall be fully open.
❑ R402.4.2 Fireplaces. New wood -burning fireplaces shall have tight -fitting flue dampers or doors, and outdoor combustion air. Where
using tight -fitting doors on factory -built fireplaces listed and labeled in accordance with UL 127, the doors shall be tested and listed for the
fireplace. Where using tight -filling doors on masonry fireplaces, the doors shall be listed and labeled in accordance with UL 907.
❑ R402.4.3 Fenestration air leakage. Windows, skylights and sliding glass doors shall have an air Infiltration rate of no more than 0.3 cfm
per square foot (1.5 L/s/m2), and swinging doors no more than 0.5 cfm per square foot (2.6 L/s/m2), when tested according to NFRC 400 or
AAMA/ WDMA/CSA 101/I.S.2/A440 by an accredited, independent laboratory and listed and labeled by the manufacturer.
Exception: Site -built windows, skylights and doors.
11/12/2021 10:43 AM EnergyGaugeO USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 1 of 5
MANDATORY REQUIREMENTS - (Continued)
❑R402AA Rooms containing fuel -burning appliances. In Climate Zones 3 through 8, where open combustion air ducts provide combustion air to
open combustion fuel burning appliances, the appliances and combustion air opening shall be located outside the building thermal envelope or
enclosed in a room, isolated from Inside the thermal envelope. Such rooms shall be sealed and insulated in accordance with the envelope requirements
of Table R402.1.2, where the walls, floors and ceilings shall meet not less than the basement wall R-value requirement. The door into the room shall be
fully gasketed and any water lines and ducts in the room insulated in accordance with Section R403. The combustion air duct shall be Insulated where it
passes through conditioned space to a minimum of R-8.
Exceptions:
1. Direct vent appliances with both intake and exhaust pipes installed continuous to the outside.
2. Fireplaces and stoves complying with Section R402.4.2 and Section R1006 of the Florida Building Code, Residential.
❑R402.4.5 Recessed lighting. Recessed luminaires installed in the building thermal envelope shall be sealed to limit air leakage
between conditioned and unconditioned spaces. All recessed luminaires shall be IC -rated and labeled as having an air leakage rate not
more than 2.0 cfm (0.944 Us) when tested in accordance with ASTM E283 at a 1.57 pat (75 Pa) pressure differential. All recessed
luminaires shall be sealed with a gasket or caulk between the housing and the interior wall or ceiling covering.
SECTION R403 SYSTEMS
R403.1 Controls.
R403.1.1 Thermostat provision (Mandatory). At least one thermostat shall be provided for each separate heating and cooling system.
R403.1.3 Heat pump supplementary heat (Mandatory). Heat pumps having supplementary electric -resistance heat shall have controls
that, except during defrost, prevent supplemental heat operation when the heal pump compressor can meet the heating load.
R403.3.2 Sealing (Mandatory) All ducts, air handlers, filter boxes and building cavities that form the primary air containment passageways
for air distribution systems shall be considered ducts or plenum chambers, shall be constructed and sealed in accordance with Section
C403.2.9.2 of the Commercial Provisions of this code and shall be shown to meet duct tightness criteria below.
Duct tightness shall be verified by testing in accordance with ANSI/RESNET/ICC 380 by either individuals as defined in Section 553.993(5) or
(7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(0, (g) or (i), Florida Statutes, to be "substantially leak free" in
accordance with Section R403.3.3.
R403.3.2.1 Sealed air handler. Air handlers shall have a manufacturer's designation for an air leakage of no more than 2 percent
of the design airflow rate when tested in accordance with ASHRAE 193.
❑ R403.3.3 Duct testing (Mandatory). Ducts shall be pressure tested to determine air leakage by one of the following methods:
1. Rough -in test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the system,
including the manufacturers air handler enclosure if installed at the time of the test. All registers shall be taped or otherwise
sealed during the test.
2. Postconslruction lest: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the entire
system, including the manufacturer's air handler enclosure. Registers shall be taped or otherwise sealed during the lest.
Exceptions:
1. A duct air leakage test shall not be required where the ducts and air handlers are located entirely within the building
thermal envelope.
2. Duct testing is not mandatory for buildings complying by Section 405 of this code. Duct leakage testing is required for Section
R405 compliance where credit is taken for leakage, and a duct air leakage Qn to the outside of less than 0.080 (where Qn =
duct leakage to the outside in cfm per 100 square feet of conditioned floor area tested at 25 Pascals) is indicated in the
compliance report for the proposed design.
A written report of the results of the lest shall be signed by the party conducting the test and provided to the code official.
R403.3.5 Building cavities (Mandatory). Building framing cavities shall not be used as ducts or plenums.
❑R403A Mechanical system piping insulation (Mandatory). Mechanical system piping capable of carrying fluids above t05017 (410C)
or below S50F (130C) shall be insulated to a minimum of R-3.
❑ R403.4.1 Protection of piping Insulation. Piping insulation exposed to weather shall be protected from damage, including that
caused by sunlight, moisture, equipment maintenance and wind, and shall provide shielding from solar radiation that can cause
degradation of the material. Adhesive tape shall not be permitted.
❑ R403.5.1 Heated water circulation and temperature maintenance systems (Mandatory). If healed water circulation systems are
installed, they shall be in accordance with Section R403.5.1 A, Heat trace temperature maintenance systems shall be in accordance with
Section R403.5.1.2. Automatic controls, temperature sensors and pumps shall be accessible. Manual controls shall be readily accessible.
R403.5.1.1 Circulation systems. Heated water circulation systems shall be provided with a circulation pump. The system return pipe shall
❑
be a dedicated return pipe or a cold water supply pipe. Gravity and thermosiphon circulation systems shall be prohibited. Controls for
circulating hot water system pumps shall start the pump based on the identification of a demand for hot water within the occupancy. The
controls shall automatically turn off the pump when the water in the circulation loop is at the desired temperature and when there is no
demand for hot water.
R403.5.1.2 Heat trace systems. Electric heat trace systems shall comply with IEEE 515.1 or UL 515. Controls for such systems shall
automatically adjust the energy input to the heat tracing to maintain the desired water temperature in the piping in accordance with the
times when heated water is used in the occupancy.
11/12/2021 10:43 AM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition 120201 Compliant Software Page 2 of 5
MANDATORY REQUIREMENTS In (Continued)
R403.5.5 Heat traps (Mandatory). Storage water heaters not equipped with integral heal traps and having vertical pipe risers shall have
heat traps installed on both the inlets and outlets. External heat traps shall consist of either a commercially available heat trap or a
downward and upward bend of at least 3 % inches (89 mm) in the hot water distribution line and cold water line located as close as possible
to the storage tank.
R403.5.6 Water heater efficiencies (Mandatory).
❑ R403.5.6.1.1 Automatic controls. Service water -heating systems shall be equipped with automatic temperature controls capable
of adjustment from the lowest to the highest acceptable temperature settings for the intended use. The minimum temperature
setting range shall be from 100°F to 140°F (38"C to 600C).
❑ R403.5.6.1.2 Shut down. A separate switch or a clearly marked circuit breaker shall be provided to permit the power supplied to
electric service systems to be turned off. A separate valve shall be provided to permit the energy supplied to the main burner(s) of
combustion types of service water -heating systems to be turned off.
❑ R403.5.6.2 Water•heating equipment. Water -heating equipment Installed in residential units shall meet the minimum efficiencies of
Table C404.2 in Chapter 4 of the Florida Building Code, Energy Conservation, Commercial Provisions, for the type of equipment installed.
Equipment used to provide healing functions as part of a combination system shall satisfy all stated requirements for the appropriate
water -healing category. Solar water heaters shall meet the criteria of Section R403.5.6.2.1.
❑ R403.5.6.2.1 Solar water -heating systems. Solar systems for domestic hot water production are rated by the annual solar energy
factor of the system. The solar energy factor of a system shall be determined from the Florida Solar Energy Center Directory of
Certified Solar Systems. Solar collectors shall be tested in accordance with ISO Standard 9806, Test Methods for Solar Collectors,
and SRCC Standard TM-1, Solar Domestic Hot Water System and Component Test Protocol. Collectors in installed solar
water -heating systems should meet the following criteria:
1. Be installed with a till angle between 10 degrees and 40 degrees of the horizontal; and
2. Be installed at an orientation within 45 degrees of true south.
R403.6 Mechanical ventilation (Mandatory). The building shall be provided with ventilation that meets the requirements of the
Florida Building Code, Residential, or Florida Building Code, Mechanical, as applicable, or with other approved means of ventilation
including: Natural, Infiltration or Mechanical means. Outdoor air intakes and exhausts shall have automatic or gravity dampers that
close when the ventilation system is not operating.
❑ R403.6.1 Whole house mechanical ventilation system fan efficacy. When installed to function as a whole -house mechanical
ventilation system, fans shall meet the efficacy requirements of Table R403.6.1.
Exception: Where an air handler that is integral to tested and listed HVAC equipment is used to provide whole -house mechanical
ventilation, the air handler shall be powered by an electronically commutated motor.
❑ R403.6.2 Ventilation air. Residential buildings designed to be operated at a positive indoor pressure or for mechanical ventilation
shall meet the following criteria:
1. The design air change per hour minimums for residential buildings in ASHRAE 62.2, Ventilation for Acceptable
Indoor Air Quality, shall be the maximum rates allowed for residential applications.
2. No ventilation or air-conditioning system make-up air shall be provided to conditioned space from attics,
crawispaces, attached enclosed garages or outdoor spaces adjacent to swimming pools or spas.
3. If ventilation air is drawn from enclosed space(s), then the walls of the space(s) from which air is drawn shall be
insulated to a minimum of R-11 and the ceiling shall be insulated to a minimum of R-19, space permitting, or R-10
otherwise.
R403.7 Heating and cooling equipment.
R403.7.1 Equipment sizing (Mandatory). Healing and cooling equipment shall be sized in accordance with ACCA Manual S based
❑
on the equipment loads calculated in accordance with ACCA Manual J or other approved healing and cooling calculation
methodologies, based on building loads for the directional orientation of the building. The manufacturer and model number of the
outdoor and indoor units (if split system) shall be submitted along with the sensible and total cooling capacities at the design
conditions described in Section R302.1. This Code does not allow designer safely factors, provisions for future expansion or other
factors that affect equipment sizing. System sizing calculations shall not Include loads created by local Intermittent mechanical
ventilation such as standard kitchen and bathroom exhaust systems. New or replacement heating and cooling equipment shall have
an efficiency rating equal to or greater than the minimum required by federal law for the geographic location where the equipment is
installed. TABLE R403.6.1
ni o uni1QP MFCHANICGI_ VENTILATION SYSTEM FAN EFFICACY
WWI 1
FAN LOCATION
V`AIRFLOW RATE MINIMUM
(CFM)
MINIMUM EFFICACY a
(CFM/WATT)
AIRFLOW RATE MAXIMU
HRV or ERV
Any
1.2 cfm/watt
Any
Range hoods
Any
2.8 cfm/wall
Any
In -line fan
Any
2.8 cfm/watt
Any
Bathroom, utility room
10
1.4 cm/watt
`90
Bathroom, utility room
g0
2.8 cfm/watt
Any
For SI: 1 cfm = 28.3 Umin. a. When tested in accordance with HVI Standard 916
11/12/2021 10:43 AM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7lh Edition (2020) Compliant Software Page 3 of 5
MANDATORY REQUIREMENTS - (Continued)
R403.7.1.1 Cooling equipment capacity. Cooling only equipment shall be selected so that its total capacity is not less
❑
than the calculated total load but not more than 1.15 limes greater than the total load calculated according to the procedure selected in
Section R403.7, or the closest available size provided by the manufacturer's product lines. The corresponding latent capacity of the
equipment shall not be less than the calculated latent load.
The published value for AHRI total capacity is a nominal, rating -test value and shall not be used for equipment sizing. Manufacturer's
expanded performance data shall be used to select cooling -only equipment. This selection shall be based on the outdoor design dry-bulb
temperature for the load calculation (or entering water temperature for water -source equipment), the blower CFM provided by the expanded
performance data, the design value for entering wet -bulb temperature and the design value for entering dry-bulb temperature.
Design values for entering wet -bulb and dry-bulb temperatures shall be for the indoor dry bulb and relative humidity used for the load
calculation and shall be adjusted for return side gains if the return duct(s) is installed in an unconditioned space.
Exceptions:
1. Attached single- and multiple -family residential equipment sizing may be selected so that its cooling capacity is less than the
calculated total sensible load but not less than 80 percent of that load.
2.
When signed and sealed by aFlorida-registered engineer, in attached single- and multiple -family units, the capacity o
equipment may be sized in accordance with good design practice.
R403.7.1.2 Heating equipment capacity.
❑ R403.7.1.2.1 Heat pumps. Heat pump sizing shall be based on the cooling requirements as calculated according to Section
R403.7.1.1, and the heat pump total cooling capacity shall not be more than 1.15 times greater than the design cooling load even if
the design heating load is 1.15 times greater than the design cooling load.
❑ R403.7.1.2.2 Electric resistance furnaces. Electric resistance furnaces shall be sized within 4 kW of the design
requirements calculated according to the procedure selected in Section R403.7.1.
❑ R403.7.1.2.3 Fossil fuel heating equipment. The capacity of fossil fuel heating equipment with natural draft atmospheric burners
shall not be less than the design load calculated in accordance with Section R403.7.1.
❑ R403.7.1.3 Extra capacity required for special occasions. Residences requiring excess cooling or heating equipment capacity on an
intermittent basis, such as anticipated additional loads caused by major entertainment events, shall have equipment sized or controlled to
prevent continuous space cooling or heating within that space by one or more of the following options:
1. A separate cooling or heating system is utilized to provide cooling or heating to the major entertainment areas.
2. A variable capacity system sized for optimum performance during base load periods is utilized.
R403.8 Systems serving multiple dwelling units (Mandatory). Systems serving multiple dwelling units shall comply with Sections
❑ C403 and C404 of the Florida Building Code, Energy Conservation —Commercial Provisions in lieu of Section R403.
❑ R403.9 Snow melt and ice system controls (Mandatory) Snow- and ice -melting systems, supplied through energy service to the building,
shall include automatic controls capable of shutting off the system when the pavement temperature is above 50OF (10°C), and no
precipitation is falling and an automatic or manual control that will allow shutoff when the outdoor temperature is above 40°F (4.8°C).
❑ R403.10 Pools and permanent spa energy consumption (Mandatory). The energy consumption of pools and permanent spas
shall be in accordance with Sections R403.10.1 through R403.10.5.
❑ R403.10.1 Heaters. The electric power to heaters shall be controlled by a readily accessible on -off switch that is an
integral part of the heater mounted on the exterior of the heater, or external to and within 3 feet (914 mm) of the heater. Operation
of such switch shall not change the setting of the heater thermostat. Such switches shall be in addition to a circuit breaker for the
power to the heater. Gas -Fred heaters shall not be equipped with continuously burning ignition pilots.
R403.10.2 Time switches. Time switches or other control methods that can automatically turn off and on according to a preset schedule
❑ shall be installed for heaters and pump motors. Heaters and pump motors that have built-in time switches shall be in compliance with this
section.
Exceptions:
1. Where public health standards require 24-hour pump operation.
2. Pumps that operate solar- and waste -heat -recovery pool healing systems.
3. Where pumps are powered exclusively from on -site renewable generation.
11/12/2021 10:43 AM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 4 of 5
R403.10.3 Covers. Outdoor heated swimming pools and outdoor permanent spas shall be equipped with a vapor -retardant cover on or at
❑ the water surface or a liquid cover or other means proven to reduce heat loss.
Exception: Where more than 70 percent of the energy for heating, computed over an operation season, is from site -recovered
energy, such as from a heat pump or solar energy source, covers or other vapor -retardant means shall not be required.
R403A0.4 Gas- and oil -fired pool and spa heaters. All gas- and oil -fired pool and spa healers shall have a minimum thermal
❑ efficiency of 82 percent for heaters manufactured on or after April 16, 2013, when tested in accordance with ANSI Z 21.56. Pool
heaters fired by natural or LP gas shall not have continuously burning pilot lights.
❑R403.10.5 Heat pump pool heaters. Heal pump pool healers shall have a minimum COP of 4.0 when tested in accordance
with AHRI 1160, Table 2, Standard Rating Conditions -Low Air Temperature. A lest report from an independent laboratory is
required to verify procedure compliance. Geothermal swimming pool heat pumps are not required to meet this standard.
❑R403.11 Portable spas (Mandatory). The energy consumption of electric -powered portable spas shall be controlled by the
requirements of APSP-14.
R403.13 Dehumidifiers (Mandatory If installed, a dehumidifier shall conform to the following requirements:
1. The minimum rated efficiency of the dehumidifier shall be greater than 1.7 liters/ kWh if the total dehumidifier capacity for the house
is less than 75 pints/day and greater than 2.38 liters/kWh if the total dehumidifier capacity for the house is greater than or equal to 75 pints/day.
2. The dehumidifier shall be controlled by a sensor that is installed in a location where it is exposed to mixed house air.
3. Any dehumidifier unit located in unconditioned space that treats air from conditioned space shall be insulated to a minimum of R-2.
4. Condensate disposal shall be in accordance with Section M1411.3.1 of the Florida Building Code, Residential.
R403.13.1 Ducted dehumidifiers. Ducted dehumidifiers shall, In addition to conforming to the requirements of Section R403.13,
conform to the following requirements:
1. If a ducted dehumidifier is configured with return and supply ducts both connected into the supply side of the cooling system, a backdraft
damper shall be installed in the supply air duct between the dehumidifier inlet and outlet duct.
2. If a ducted dehumidifier is configured with only its supply duct connected into the supply side of the central heating and cooling system,
a backdraft damper shall be installed in the dehumidifier supply duct between the dehumidifier and central supply duct.
3. A ducted dehumidifier shall not be ducted to or from a central ducted cooling system on the return duct side upstream from the
central cooling evaporator coil.
4, Ductwork associated with a dehumidifier located in unconditioned space shall be insulated to a minimum of R-6.
SECTION R404
ELECTRICAL POWER AND LIGHTING SYSTEMS
❑R404.1 Lighting equipment (Mandatory). Not less than 90 percent of the lamps in permanently installed luminaires shall have an
efficacy of at least 45 lumens -per -watt or shall utilize lamps with an efficacy of not less than 65 lumens -per -watt.
R404.1.1 Lighting equipment (Mandatory). Fuel gas lighting systems shall not have continuously burning pilot lights.
11/12/2021 10:43 AM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 5 of 5
2020 - AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA
TABLE 402.4.1.1
AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA
Project Name: TBD Carlton PSL Prop Builder Name: PSL Prop
Street: TBD Carlton Permit Office:
City, State, Zip: Fort Pierce , FL , 34983 Permit Number:
w
Owner: Chhay Residence Jurisdiction: St. Lucie
X
Design Location: FL, ST_LUCIE_CO_INTL
COMPONENT
AIR BARRIER CRITERIA
INSULATION INSTALLATION CRITERIA
General
A continuous air barrier shall be installed in the building envelope.
Air -permeable insulation shall
The exterior thermal envelope contains a continuous air barrier.
not be used as a sealing material.
requirements
Breaks or joints in the air barrier shall be sealed.
The air barrier in any dropped ceiling/soffit shall be aligned with
The insulation in any dropped ceiling/soffit
Ceiling/attic
the insulation and any gaps in the air barrier shall be sealed.
shall be aligned with the air barrier.
Access openings, drop down stairs or knee wall doors to
unconditioned attic spaces shall be sealed.
The junction of the foundation and sill plate shall be sealed.
Cavities within comers and headers of frame walls
Walls
The junction of the top plate and the top of exterior walls shall be
shall be Insulated by completely filling the cavity
sealed.
with a material having a thermal resistance of R-3
Knee walls shall be sealed.
per inch minimum.
Exterior thermal envelope insulation for framed
walls shall be installed in substantial contact and
continuous alignment with the air barrier.
Windows, skylights
The space between window/doorjambs and framing, and
skylights and framing shall be sealed.
and doors
Rim joists
Rim joists shall include the air barrier.
Rim joists shall be insulated.
Floors
The air barrier shall be installed at any exposed edge of
Floor framing cavity insulation shall be installed to
(including
insulation.
maintain permanent contact with the underside of
subfloor decking, or floor framing cavity insulation
above -garage
shall be permitted to be in contact with the lop side
and cantilevered
of sheathing, or continuous insulation installed on
floors)
the underside of floor framing and extends from the
bottom to the top of all perimeter floor framing
members.
Crawl space walls
Exposed earth in unvenled crawl spaces shall be covered with
Where provided instead of floor insulation, insulation
a Class I vapor retarder with overlapping joints taped.
shall be permanently attached to the crawlspace wall
.
Duct shafts, utility penetrations, and flue shafts opening to
Shafts, penetrations
exterior or unconditioned space shall be sealed.
Batts in narrow cavities shall be cut to fit, or narrow
cavities shall be filled by insulation that on
Narrow cavities
installation readily conforms to the available cavity
spaces.
Garage separation
Air sealing shall be provided between the garage and conditioned spa
s.
Recessed lighting
Recessed light fixtures installed In the building thermal envelope
Recessed light fixtures installed in the building
shall be sealed to the finished surface.
thermal envelope shall be air tight and IC rated.
Batt insulation shall be cut neatly to fit around wiring
Plumbing and wiring
and plumbing in exterior walls, or insulation that on
Installation readily conforms to available space shall
extend behind piping and wirinn
Showerltub
The air barrier installed at exterior walls adjacent to showers and
Exterior walls adjacent to showers and tubs shall
on exterior wall
tubs shall separate them from the showers and tubs,
be insulated.
Electrical/phone box or
The air barrier shall be installed behind electrical or communication
exterior walls
boxes or air -sealed boxes shall be Installed.
HVAC register boots
HVAC supply and return register boots that penetrate building
thermal envelope shall be sealed to the sub -floor, wall covering or
Concealed
When required to be sealed, concealed fire sprinklers shall only be
sealed in a manner that is recommended by the manufacturer.
sprinklers
Caulking or other adhesive sealants shall not be used to fill voids
a. In addition, inspection
of
log
wens snan oe in
acwruance wai i it to Na u.,o,u„o
01
11/12/2021 10:43 AM
EnergyGauge®
USA 7.0.00 -
FlaRes2020 FBC
7ih Edition
(2020)
Compliant Software
Page 1
of 1
Envelope Leakage Test Report (Blower Door Test)
Residential Prescriptive, Performance or ERI Method Compliance
2020 Florida Building Code, Energy Conservation, 7th Edition
Jurisdiction: St. Lucie
Permit #:
Job Information
Builder: PSL Prop Community: Lot: NA
Address: TBD Carlton
City: Fort Pierce State: FL Zip: 34983
Air Leakage Test Results Passing results must meet either the Performance, Prescriptive, or ERI Method
O PRESCRIPTIVE METHOD -The building or dwelling unit shall be tested and verified as having an air leakage rate of not exceeding 7 air
changes per hour at a pressure of 0.2 inch w.g. (50 Pascals) in Climate Zones 1 and 2.
O PERFORMANCE or ERI METHOD -The building or dwelling unit shall be tested and verified as having an air leakage rate of not exceeding
the selected ACH(50) value, as shown on Form R405-2020 (Performance) or R406-2020 (ERI), section labeled as infiltration, sub -section ACH50.
ACH(50) specified on Form R405-2020-Energy Cale (Performance) or R406-2020 (ERI): 6.000
x 60 =-3.9039E12 — Method for calculating building volume:
CFM(50) Building Volume ACH(50) O Retrieved from architectural plans
PASS • Code software calculated
When ACH(50) is less than 3, Mechanical Ventilation installation O Field measured and calculated
must be verified by building department.
R402.4.1.2 Testing. Testing shall be conducted in accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g. (50 Pascals)
Testing shall be conducted by either individuals as defined in Section 553.993(5) or (7), Florida Statues.or individuals licensed as set forth in Section
489.105(3)(01 (9), or (I) or an approved third party. A written report of the results of the test shall be signed by the party conducting the lest and
provided to lhecode official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope.
During testing:
1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or other infiltration
control measures.
2. Dampers including exhaust, intake, makeup air, back draft and flue dampers shall be closed, but not sealed beyond intended infiltration control
measures.
3. Interior doors, if installed at the time of the test, shall be open.
4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed.
5. Heating and cooling systems, if installed at the time of the lest, shall be turned off.
6. Supply and return registers, if installed at the time of the test, shall be fully open.
Testing Company
Company Name: Phone:
I hereby verify that the above Air Leakage results are in accordance with the 2020 7th Edition Florida Building Code
Energy Conservation requirements according to the compliance method selected above.
Signature of Tester: Date of Test:
Printed Name of Tester:
License/Certification #: Issuing Authority:
11/12/2021 10:43:36 AM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 1 of 1