HomeMy WebLinkAboutPHOTOVOLTAIC SYSTEMPV-1 FREEDOM FOREVER INDY 8.00 TEMPLATECONTRACTOR LICENSE: CERTIFIED ELECTRICAL CONTRACTOR EC13008056 FREEDOM FOREVER LLC 2619 CONSULATE DR SUITE 800, ORLANDO, FL 32819 Tel: (800) 385-1075 REVISED BY DATENO. SHEET: REVISIONS JOB NO: F112409 DESIGNED BY: ANTON CLIENT: DENIS SULLIVAN 7903 KENWOOD ROAD, FORT PIERCE, FL 34951 AHJ: ST. LUCIE COUNTY UTILITY: FPL - FLORIDA POWER & LIGHT PHONE: (772) 464-9154 SYSTEM: SYSTEM SIZE (DC): 19 X 350 = 6.650 kW SYSTEM SIZE (AC): 6.000 kW @ 240V MODULES: 19 X LONGI SOLAR: LR4-60HPB-350M OPTIMIZERS: 19 X SOLAREDGE P401 INVERTER: SOLAREDGE SE6000H-USRGM [SI1] DATE: 12/13/2021 MOD SWAP; LAYOUT CHANGE 12/13/20211 THIS PROJECT COMPLIES WITH THE FOLLOWING: 2020 7TH EDITION FLORIDA BUILDING CODE: BUILDING 2020 7TH EDITION FLORIDA BUILDING CODE: RESIDENTIAL 2020 7TH EDITION FLORIDA BUILDING CODE: MECHANICAL 2020 7TH EDITION FLORIDA BUILDING CODE: PLUMBING 2020 7TH EDITION FLORIDA BUILDING CODE: FUEL GAS 2020 7TH EDITION FLORIDA BUILDING CODE: ENERGY CONSERVATION 2020 7TH EDITION FLORIDA BUILDING CODE: EXISTING BUILDING 2020 7TH EDITION FLORIDA BUILDING CODE: ACCESSIBILITY 2020 7TH EDITION FLORIDA FIRE PREVENTION CODE (NFPA) 2017 NATIONAL ELECTRIC CODE (NEC) AS ADOPTED BY ST. LUCIE COUNTY SITE LOCATION CODES: VICINITY MAP: TABLE OF CONTENTS: CONSTRUCTION NOTES: PHOTOVOLTAIC SYSTEM PV-1 SITE LOCATION PV-2 SITE PLAN PV-2A ROOF PLAN WITH MODULES LAYOUT PV-2B STRUCTURAL CALCULATIONS PV-3 MOUNTING DETAILS PV-4 THREE LINE DIAGRAM PV-5 CONDUCTOR CALCULATIONS PV-6 EQUIPMENT & SERVICE LIST PV-7 LABELS PV-7A SITE PLACARD PV-8 OPTIMIZER CHART PV-9 SAFETY PLAN PV-10 SAFETY PLAN APPENDIX MANUFACTURER SPECIFICATION SHEETS CONDUIT AND CONDUCTOR SPECIFICATIONS ARE BASED ON MINIMUM CODE REQUIREMENTS AND ARE NOT MEANT TO LIMIT UP-SIZING AS REQUIRED BY FIELD CONDITIONS. ALL SOLAR ENERGY SYSTEM EQUIPMENT SHALL BE SCREENED TO THE MAXIMUM EXTENT POSSIBLE AND SHALL BE PAINTED A COLOR SIMILAR TO THE SURFACE UPON WHICH THEY ARE MOUNTED. MODULES SHALL BE TESTED , LISTED AND INDENTIFIED WITH FIRE CLASSIFICATION IN ACCORDANCE WITH UL 2703. SMOKE AND CARBON MONOXIDE ALARMS ARE REQUIRED PER SECTION R314 AND 315 TO BE VERIFIED AND INSPECTED BY INSPECTOR IN THE FIELD. DIG ALERT (811) TO BE CONTACTED AND COMPLIANCE WITH EXCAVATION SAFETY PRIOR TO ANY EXCAVATION TAKING PLACE PHOTOVOLTAIC SYSTEM GROUND WILL BE TIED INTO EXISTING GROUND AT MAIN SERVICE FROM DC DISCONNECT/INVERTER AS PER 2017 NEC SEC 250.166(A). SOLAR PHOTOVOLTAIC SYSTEM EQUIPMENT WILL BE INSTALLED IN ACCORDANCE WITH REQUIREMENTS OF ART. 690 OF THE 2017 NEC THE MAIN SERVICE PANEL WILL BE EQUIPPED WITH A GROUND ROD OR UFER UTILITY COMPANY WILL BE NOTIFIED PRIOR TO ACTIVATION OF THE SOLAR PV SYSTEM SOLAREDGE OPTIMIZERS ARE LISTED TO IEC 62109-1 (CLASS II SAFETY) AND UL 1741 STANDARDS INSTALL CREW TO VERIFY ROOF STRUCTURE PRIOR TO COMMENCING WORK. EMT CONDUIT ATTACHED TO THE ROOF USING CONDUIT MOUNT. SITE LOCATION THIS SYSTEM IS DESIGNED FOR WIND SPEED: 152 MPH CATEGORY C EXPOSURE GREG ALBRIGHT MSPUM AC INV JB SITE PLAN SCALE: 1/16" = 1'-0"1 ROOF LINE PROPERTY LINEDRIVEWAYKENWOOD ROAD (E) MAIN SERVICE PANEL (N) 19 LONGI SOLAR: LR4-60HPB-350M (E) UTILITY METER PV SYSTEM 6.650 kW-DC 6.000 kW-AC (N) SOLAREDGE SE6000H-USRGM [SI1] INVERTER WITH RAPID SHUTDOWN (N) AC DISCONNECT EATON DG222NRB BOS WILL BE AS CLOSE AS POSSIBLE TO MSP WITHIN 10' PV-2 FREEDOM FOREVER INDY 8.00 TEMPLATECONTRACTOR LICENSE: CERTIFIED ELECTRICAL CONTRACTOR EC13008056 FREEDOM FOREVER LLC 2619 CONSULATE DR SUITE 800, ORLANDO, FL 32819 Tel: (800) 385-1075 REVISED BY DATENO. SHEET: REVISIONS JOB NO: F112409 DESIGNED BY: ANTON CLIENT: DENIS SULLIVAN 7903 KENWOOD ROAD, FORT PIERCE, FL 34951 AHJ: ST. LUCIE COUNTY UTILITY: FPL - FLORIDA POWER & LIGHT PHONE: (772) 464-9154 SYSTEM: SYSTEM SIZE (DC): 19 X 350 = 6.650 kW SYSTEM SIZE (AC): 6.000 kW @ 240V MODULES: 19 X LONGI SOLAR: LR4-60HPB-350M OPTIMIZERS: 19 X SOLAREDGE P401 INVERTER: SOLAREDGE SE6000H-USRGM [SI1] DATE: 12/13/2021 MOD SWAP; LAYOUT CHANGE 12/13/20211 THIS SYSTEM DESIGNED WITH: WIND SPEED: 152 WIND EXPOSURE: C ROOF AREA: 2826 SQ FT SITE PLAN LEGEND: OBSTRUCTION PIPE VENT MODULES CONDUIT SETBACK MSP AC JB AC DISCONNECT MSP JUNCTION BOX INV INVERTER PM PRODUCTION METER GREG ALBRIGHT 80'-11"128'-4"80'-11"128'-4"31'-2"8'-6"56'-3"9'-11" (N) JUNCTION BOX MSPUM AC INV JB PV-2A FREEDOM FOREVER INDY 8.00 TEMPLATECONTRACTOR LICENSE: CERTIFIED ELECTRICAL CONTRACTOR EC13008056 FREEDOM FOREVER LLC 2619 CONSULATE DR SUITE 800, ORLANDO, FL 32819 Tel: (800) 385-1075 REVISED BY DATENO. SHEET: REVISIONS JOB NO: F112409 DESIGNED BY: ANTON CLIENT: DENIS SULLIVAN 7903 KENWOOD ROAD, FORT PIERCE, FL 34951 AHJ: ST. LUCIE COUNTY UTILITY: FPL - FLORIDA POWER & LIGHT PHONE: (772) 464-9154 SYSTEM: SYSTEM SIZE (DC): 19 X 350 = 6.650 kW SYSTEM SIZE (AC): 6.000 kW @ 240V MODULES: 19 X LONGI SOLAR: LR4-60HPB-350M OPTIMIZERS: 19 X SOLAREDGE P401 INVERTER: SOLAREDGE SE6000H-USRGM [SI1] DATE: 12/13/2021 MOD SWAP; LAYOUT CHANGE 12/13/20211 ROOF PLAN SCALE: 3/32" = 1'-0"1 FIRE ACCESS PATHWAYS MODIFIED SETBACKS PROPOSED AT RIDGE: TOTAL ARRAY AREA = 342.95 SF TOTAL ROOF AREA = 2826 SF TOTAL ARRAY AREA AS A % TO ROOF AREA = 12.14% 12.14% < 33% (N) 19 LONGI SOLAR: LR4-60HPB-350M BOS WILL BE AS CLOSE AS POSSIBLE TO MSP WITHIN 10' (E) UTILITY METER PV SYSTEM 6.650 kW-DC 6.000 kW-AC NOTES: 1. EMT CONDUIT ATTACHED TO THE ROOF USING CONDUIT MOUNTS 2. ATTACHED CLAMPS AT 25% FROM THE EDGE AND 50% FROM THE CENTER OF THE MODULES 3. JUNCTION BOX IS MOUNTED TO THE RAIL. ROOF AREA: 2826 SQ FT THIS SYSTEM DESIGNED WITH: WIND SPEED: 152 WIND EXPOSURE: C ROOF PLAN WITH MODULES LAYOUT LEGEND: OBSTRUCTION PIPE VENT MODULES CONDUIT SETBACK MSP AC JB AC DISCONNECT MSP JUNCTION BOX INV INVERTER PM PRODUCTION METER GREG ALBRIGHT FIRE ACCESS PATHWAYS 2'-0"2'-0"2'-0"2'-0"2'-0"2'-0" ROOF AREA STATEMENT ROOF MODULE QUANTITY ROOF PITCH ARRAY PITCH AZIMUTH ROOF AREA ARRAY AREA 1 19 26°26°180°862 SQ FT 342.95 SQ FT PV-2B FREEDOM FOREVER INDY 8.00 TEMPLATECONTRACTOR LICENSE: CERTIFIED ELECTRICAL CONTRACTOR EC13008056 FREEDOM FOREVER LLC 2619 CONSULATE DR SUITE 800, ORLANDO, FL 32819 Tel: (800) 385-1075 REVISED BY DATENO. SHEET: REVISIONS JOB NO: F112409 DESIGNED BY: ANTON CLIENT: DENIS SULLIVAN 7903 KENWOOD ROAD, FORT PIERCE, FL 34951 AHJ: ST. LUCIE COUNTY UTILITY: FPL - FLORIDA POWER & LIGHT PHONE: (772) 464-9154 SYSTEM: SYSTEM SIZE (DC): 19 X 350 = 6.650 kW SYSTEM SIZE (AC): 6.000 kW @ 240V MODULES: 19 X LONGI SOLAR: LR4-60HPB-350M OPTIMIZERS: 19 X SOLAREDGE P401 INVERTER: SOLAREDGE SE6000H-USRGM [SI1] DATE: 12/13/2021 MOD SWAP; LAYOUT CHANGE 12/13/20211 ROOF DETAILS: TOTAL ROOF AREA: 2826 SQ FT ARRAY COVERAGE: 12.14% SYSTEM DISTRIBUTED WEIGHT: 2.31 LBS SFM INFINITY \ ROCKIT MICRORAIL POINT-LOAD: 22.62 LBS ROOF DETAILS GREG ALBRIGHT By Yuri at 7:04:27 PM, 12/16/2021 ROOF DECK / MEMBRANE SLIDER AND TRIMRAIL ROOF ATTACHMENT BUILDING STRUCTURE 5/16" STAINLESS STEEL LAG BOLT OR STRUCTURAL SCREW WITH 2-1/2" MIN. EMBEDMENT AND FLAT WASHER 2.5" TRIMRAIL 2.5" MIN. EMBED.FLASHING ROOF / DECK MEMBRANE SLIDERS BUILDING STRUCTURE 5/16" STAINLESS STEEL LAG BOLT OR STRUCTURAL SCREW WITH 2-1/2" MIN. EMBEDMENT AND FLAT WASHER 2.5" MICRORAIL FLASHING 2.5" MIN. EMBED. LONGI SOLAR: LR4-60HPB-350M LONGI SOLAR: LR4-60HPB-350M SLIDERS MICRORAIL 2.5" MI N. E M B E D. 5/16" STAINLESS STEEL LAG BOLT OR STRUCTURAL SCREW WITH 2-1/2" MIN. EMBEDMENT AND FLAT WASHER TRIMRAIL 2.5" MI N. E M B E D. FLASHING FLASHING SLIDER AND TRIMRAIL ROOF ATTACHMENT 2X4 TRUSS @ 24" O.C. ROOF / DECK MEMBRANE 3" M IN .MAX" . LONGI SOLAR: LR4-60HPB-350M ATTACHMENT DETAIL Scale: NTS SOLAR PV ARRAY SECTION VIEW Scale: NTS ARRAY FLOOR PLAN WITH MODULES LAYOUT Scale: NTS PV-3 FREEDOM FOREVER INDY 8.00 TEMPLATECONTRACTOR LICENSE: CERTIFIED ELECTRICAL CONTRACTOR EC13008056 FREEDOM FOREVER LLC 2619 CONSULATE DR SUITE 800, ORLANDO, FL 32819 Tel: (800) 385-1075 REVISED BY DATENO. SHEET: REVISIONS JOB NO: F112409 DESIGNED BY: ANTON CLIENT: DENIS SULLIVAN 7903 KENWOOD ROAD, FORT PIERCE, FL 34951 AHJ: ST. LUCIE COUNTY UTILITY: FPL - FLORIDA POWER & LIGHT PHONE: (772) 464-9154 SYSTEM: SYSTEM SIZE (DC): 19 X 350 = 6.650 kW SYSTEM SIZE (AC): 6.000 kW @ 240V MODULES: 19 X LONGI SOLAR: LR4-60HPB-350M OPTIMIZERS: 19 X SOLAREDGE P401 INVERTER: SOLAREDGE SE6000H-USRGM [SI1] DATE: 12/13/2021 MOD SWAP; LAYOUT CHANGE 12/13/20211 MOUNTING DETAILS MAX ATTACHMENT SPAN - 4' STAGGERED GREG ALBRIGHT By Yuri at 7:04:27 PM, 12/16/2021 SOLAREDGE P401 POWER OPTIMIZERS JUNCTION BOX STRING-1 2 - #10 AWG, PV WIRE 1 - #6 AWG IN FREE AIR OR #8 AWG MUST BE IN EMT CONDUIT STRING-2 SOLAREDGE P401 POWER OPTIMIZERS 2 - #10 AWG, PV WIRE 9 LONGI SOLAR: LR4-60HPB-350M 10 LONGI SOLAR: LR4-60HPB-350M 4 - #10 AWG, THWN-2 1 - #8 EGC, THWN-2 IN 3/4" OR LARGER EMT CONDUIT UM (E) 200A / 2P MAIN BREAKER (TOP FED) (E) 200A RATED MAIN SERVICE PANEL 1PH, 120/240V 60HZ (E) UTILITY METER (N) LINESIDE TAP VIA UL LISTED CONNECTORS 1 - #6 GEC, BARE COPPER FREE AIR BONDED EXISTING UFER TIE IN TO UTILITY OVERHEAD FEED (N) 60A FUSED AC DISCONNECT EATON DG222NRB 2 - 35 AMP FUSES 3 - #8 AWG, THWN-2 1 - #8 EGC, THWN-2 IN 3/4" OR LARGER EMT CONDUIT A TAPBOX MAY BE USED IN LIEU OF PERFORMING THE LINESIDE TAP IN THE MAIN SERVICE PANEL. THIS IS DEPENDENT UPON SITE CONDITIONS. 3 - #6 AWG, THWN-2 IN 3/4" OR LARGER EMT CONDUIT (N) SOLAREDGE SE6000H-USRGM [SI1] INVERTER AC DC RAPID SHUTDOWN SWITCH CONNECT TO EXISTING UFER NOTE: CONDUIT AND CONDUCTORS SPECIFICATIONS ARE BASED ON MINIMUM CODE REQUIREMENTS AND ARE NOT MEANT TO LIMIT UP-SIZING AS REQUIRED BY FIELD CONDITIONS BACKFEED FUSE SIZING MAX. CONTINUOUS OUTPUT 25.00A @ 240V 25.00 X 1.25 = 31AMPS 35A FUSES - OK PV SYSTEM 6.650 kW-DC 6.000 kW-AC PV-4 FREEDOM FOREVER INDY 8.00 TEMPLATECONTRACTOR LICENSE: CERTIFIED ELECTRICAL CONTRACTOR EC13008056 FREEDOM FOREVER LLC 2619 CONSULATE DR SUITE 800, ORLANDO, FL 32819 Tel: (800) 385-1075 REVISED BY DATENO. SHEET: REVISIONS JOB NO: F112409 DESIGNED BY: ANTON CLIENT: DENIS SULLIVAN 7903 KENWOOD ROAD, FORT PIERCE, FL 34951 AHJ: ST. LUCIE COUNTY UTILITY: FPL - FLORIDA POWER & LIGHT PHONE: (772) 464-9154 SYSTEM: SYSTEM SIZE (DC): 19 X 350 = 6.650 kW SYSTEM SIZE (AC): 6.000 kW @ 240V MODULES: 19 X LONGI SOLAR: LR4-60HPB-350M OPTIMIZERS: 19 X SOLAREDGE P401 INVERTER: SOLAREDGE SE6000H-USRGM [SI1] DATE: 12/13/2021 MOD SWAP; LAYOUT CHANGE 12/13/20211 THREE LINE DIAGRAM GREG ALBRIGHT PV-5 FREEDOM FOREVER INDY 8.00 TEMPLATECONTRACTOR LICENSE: CERTIFIED ELECTRICAL CONTRACTOR EC13008056 FREEDOM FOREVER LLC 2619 CONSULATE DR SUITE 800, ORLANDO, FL 32819 Tel: (800) 385-1075 REVISED BY DATENO. SHEET: REVISIONS JOB NO: F112409 DESIGNED BY: ANTON CLIENT: DENIS SULLIVAN 7903 KENWOOD ROAD, FORT PIERCE, FL 34951 AHJ: ST. LUCIE COUNTY UTILITY: FPL - FLORIDA POWER & LIGHT PHONE: (772) 464-9154 SYSTEM: SYSTEM SIZE (DC): 19 X 350 = 6.650 kW SYSTEM SIZE (AC): 6.000 kW @ 240V MODULES: 19 X LONGI SOLAR: LR4-60HPB-350M OPTIMIZERS: 19 X SOLAREDGE P401 INVERTER: SOLAREDGE SE6000H-USRGM [SI1] DATE: 12/13/2021 MOD SWAP; LAYOUT CHANGE 12/13/20211 CONDUCTOR CALCULATIONS GREG ALBRIGHT WIRE SCHEDULE RACEWAY #EQUIPMENT WIRE LOCATION CONDUCTOR QTY. AWG WIRE SIZE STARTING ALLOWABLE AMPACITY @ 90°C 310.15(B)(16) STARTING CURRENT APPLIED TO CONDUCTORS IN RACEWAY TEMPERATURE CORRECTION FACTOR 310.15(B)(2)(a) ADJUSTMENT FACTOR FOR MORE THAN 3 CONDUCTORS 310.15(B)(3)(a) ADJUSTED CONDUCTOR AMPACITY @ 90°C MAXIMUM CURRENT APPLIED TO CONDUCTORS IN RACEWAY 1 DC MODULE TO OPTIMIZER ROOF / FREE-AIR 210 40 13.95 1 1 40.00 17.44 2 DC OPTIMIZER TO JUNCTION BOX ROOF / FREE-AIR 2 10 40 15.00 1 1 40.00 18.75 3 DC JUNCTION BOX TO INVERTER EXTERIOR WALL 4 10 40 15.00 1 0.8 32.00 18.75 4 AC INVERTER TO AC DISCONNECT EXTERIOR WALL 3 8 55 25.00 1 1 55.00 31.25 5 AC AC DISCONNECT TO POI EXTERIOR WALL 36 75 25.00 1 1 75.00 31.25 CONDUCTOR AMPACITY CALCULATIONS IN ACCORDANCE WITH NEC 690.8. MATERIAL LIST: PV-6 FREEDOM FOREVER INDY 8.00 TEMPLATECONTRACTOR LICENSE: CERTIFIED ELECTRICAL CONTRACTOR EC13008056 FREEDOM FOREVER LLC 2619 CONSULATE DR SUITE 800, ORLANDO, FL 32819 Tel: (800) 385-1075 REVISED BY DATENO. SHEET: REVISIONS JOB NO: F112409 DESIGNED BY: ANTON CLIENT: DENIS SULLIVAN 7903 KENWOOD ROAD, FORT PIERCE, FL 34951 AHJ: ST. LUCIE COUNTY UTILITY: FPL - FLORIDA POWER & LIGHT PHONE: (772) 464-9154 SYSTEM: SYSTEM SIZE (DC): 19 X 350 = 6.650 kW SYSTEM SIZE (AC): 6.000 kW @ 240V MODULES: 19 X LONGI SOLAR: LR4-60HPB-350M OPTIMIZERS: 19 X SOLAREDGE P401 INVERTER: SOLAREDGE SE6000H-USRGM [SI1] DATE: 12/13/2021 MOD SWAP; LAYOUT CHANGE 12/13/20211 QTY.PART PART # DESCRIPTION 19 MODULES 114-350 LONGI SOLAR: LR4-60HPB-350M 19 OPTIMIZERS 130-401 SOLAREDGE P401 POWER OPTIMIZER - FRAME MOUNTED MODULE ADD-ON 1 JUNCTION BOX 480-276 600VDC NEMA 3R UL LISTED JUNCTION BOX 2 CONNECTORS 240-300 STAUBLI / MULTI-CONTACT MC4 CONNECTORS (FEMALE) 2 CONNECTORS 240-301 STAUBLI / MULTI-CONTACT MC4 CONNECTORS (MALE) 1 INVERTER 120-603 SOLAREDGE SE6000H-USRGM [SI1] 240V INVERTER UL1741 SA CERTIFIED INTEGRATED ARC FAULT PROTECTION AND RAPID SHUTDOWN 1 AC DISCONNECT 323-061 60A RATED 240VAC NEMA 3R UL LISTED 2 FUSES 330-035 35A FUSE 1 PH 240VAC 1 FUSE REDUCER 330-530 30A-60A FUSE REDUCER 35 ROOF ATTACHMENT 1 261 -602 SFM INFINITY \ ROCKIT MICRORAIL 14 SFM TRIM 1 241-253 FLASHKIT SFM / ROCK-IT TRIM COMP DARK 36 SFM SLIDER 1 261-603 FLASHKIT SFM / ROCK-IT SLIDER COMP DARK 11 BONDING CLAMP 1 221-100 N/S BONDING CLAMP 4 BONDING CLAMP 1 241-404 TRIM BONDING CLAMP 20 MOUNT ASSEMBLY 1 241-405 MLPE MOUNT ASSY 12 SFM SPLICE 1 261-604 SFM / ROCK-IT SPLICE 3 SFM ATTACHED SPLICE 1 211-101 ATTACHED SPLICE 8 INCH 16 TRIMRAIL 1 261-606 TRIMRAIL UNIV CLIP W/ HDW 5 TRIM SPLICE 1 261-605 TRIM SPLICE DRK 9 TRIMRAIL 1 211-115 TRIMRAIL UNIV DRK 19 GROUND LUG 1 260-585 ILSCO GROUND LUG 19 TRIM END CAPS 1 221-200 UNIRAC SFM / ROCK-IT TRIM END CAPS BREAKER SIZES:SERVICE LIST: NONE EQUIPMENT & SERVICE LIST GREG ALBRIGHT 1. NEC ARTICLES 690 AND 705 AND FBC SECTION R324 MARKINGS SHOWN HEREON. 2. ALL MARKING SHALL CONSIST OF THE FOLLOWING: A. UV RESISTANT SIGN MATERIAL WITH ENGRAVED OR MACHINE PRINTED LETTERS OR ELECTRO-PLATING. B. RED BACKGROUND COLOR WHITE TEXT AND LINE WORK. C. ARIAL FONT. 3. ALL SIGNS SHALL BE SIZED APPROPRIATELY AND PLACED IN THE LOCATIONS SPECIFIED. SIGNAGE CANNOT BE HAND-WRITTEN. 4. SIGNS SHALL BE ATTACHED TO THE SERVICE EQUIPMENT WITH POP-RIVETS OR SCREWS NOTES:M 690.54 705.12(B)(2)(3)(b) "WARNING" DUAL POWER SOURCES SECOND SOURCE IS PHOTOVOLTAIC SYSTEM RATED AC OUTPUT CURRENT - 25.00 AMPS AC NORMAL OPERATING VOLTAGE - 240 VOLTS WARNING: POWER SOURCE OUTPUT CONNECTION DO NOT RELOCATE THIS OVERCURRENT DEVICE. TURN RAPID SHUTDOWN SWITCH TO THE "OFF" POSITION TO SHUT DOWN PV SYSTEM AND REDUCE SHOCK HAZARD IN THE ARRAY 690.56(C)(1)(A) SOLAR PV SYSTEM EQUIPPED WITH RAPID SHUTDOWN AC 690.15, 690.54 PV SYSTEM AC DISCONNECT RATED AC OUTPUT CURRENT - 25.00 AMPS AC NORMAL OPERATING VOLTAGE - 240 VOLTS RAPID SHUTDOWN SWITCH FOR SOLAR PV SYSTEM 690.56(C)(3) INVERTER ARRAY J/BDC "WARNING" ELECTRICAL SHOCK HAZARD. TERMINALS ON BOTH LINE AND LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION 690.13 (B) 690.53 NEC 690.31(G)(3) & (4)PMPV METER SOLAR ELECTRIC PV PANELS PV SYSTEM DC DISCONNECT MAXIMUM VOLTAGE: 480V MAXIMUM CIRCUIT CURRENT: 16.5A MAX RATED OUTPUT CURRENT OF THE CONTROLLER OR DC-TO-DC CONVERTER: 15A TURN RAPID SHUTDOWN SWITCH TO THE "OFF" POSITION TO SHUT DOWN ENTIRE PV SYSTEM NFPA 11.12.2.1.1.1.1 SOLAR ELECTRIC PV PANELS EMERGENCY RESPONDER THIS SOLAR PV SYSTEM EQUIPPED WITH RAPID SHUTDOWN TURN RAPID SHUTDOWN SWITCH TO THE "OFF" POSITION. ONLY CONDUCTORS INSIDE BUILDING OR OFF THE ROOF WILL SHUT DOWN NFPA 11.12.2.1.1.1.2 SOLAR ELECTRIC PV PANELS EMERGENCY RESPONDER THIS SOLAR PV SYSTEM EQUIPPED WITH RAPID SHUTDOWN "WARNING" PHOTOVOLTAIC POWER SOURCE EVERY 10' ON CONDUIT AND ENCLOSURES PV-7 FREEDOM FOREVER INDY 8.00 TEMPLATECONTRACTOR LICENSE: CERTIFIED ELECTRICAL CONTRACTOR EC13008056 FREEDOM FOREVER LLC 2619 CONSULATE DR SUITE 800, ORLANDO, FL 32819 Tel: (800) 385-1075 REVISED BY DATENO. SHEET: REVISIONS JOB NO: F112409 DESIGNED BY: ANTON CLIENT: DENIS SULLIVAN 7903 KENWOOD ROAD, FORT PIERCE, FL 34951 AHJ: ST. LUCIE COUNTY UTILITY: FPL - FLORIDA POWER & LIGHT PHONE: (772) 464-9154 SYSTEM: SYSTEM SIZE (DC): 19 X 350 = 6.650 kW SYSTEM SIZE (AC): 6.000 kW @ 240V MODULES: 19 X LONGI SOLAR: LR4-60HPB-350M OPTIMIZERS: 19 X SOLAREDGE P401 INVERTER: SOLAREDGE SE6000H-USRGM [SI1] DATE: 12/13/2021 MOD SWAP; LAYOUT CHANGE 12/13/20211 LABELS GREG ALBRIGHT MSPUM AC INV JB MAIN SERVICE PANEL INVERTER EQUIPPED WITH RAPID SHUTDOWN JUNCTION BOX 19 PV MODULES KENWOOD ROAD AC DISCONNECT UTILITY METER CAUTION: MULTIPLE SOURCES OF POWER LOCATED AS SHOWN. DANGEROUS VOLTAGE MAY BE PRESENT AT ALL TIMES 6X8" TYP - NEC 705.10 PV-7A FREEDOM FOREVER INDY 8.00 TEMPLATECONTRACTOR LICENSE: CERTIFIED ELECTRICAL CONTRACTOR EC13008056 FREEDOM FOREVER LLC 2619 CONSULATE DR SUITE 800, ORLANDO, FL 32819 Tel: (800) 385-1075 REVISED BY DATENO. SHEET: REVISIONS JOB NO: F112409 DESIGNED BY: ANTON CLIENT: DENIS SULLIVAN 7903 KENWOOD ROAD, FORT PIERCE, FL 34951 AHJ: ST. LUCIE COUNTY UTILITY: FPL - FLORIDA POWER & LIGHT PHONE: (772) 464-9154 SYSTEM: SYSTEM SIZE (DC): 19 X 350 = 6.650 kW SYSTEM SIZE (AC): 6.000 kW @ 240V MODULES: 19 X LONGI SOLAR: LR4-60HPB-350M OPTIMIZERS: 19 X SOLAREDGE P401 INVERTER: SOLAREDGE SE6000H-USRGM [SI1] DATE: 12/13/2021 MOD SWAP; LAYOUT CHANGE 12/13/20211 1. NEC ARTICLES 690 AND 705 AND FBC SECTION R324 MARKINGS SHOWN HEREON. 2. ALL MARKING SHALL CONSIST OF THE FOLLOWING: A. UV RESISTANT SIGN MATERIAL WITH ENGRAVED OR MACHINE PRINTED LETTERS OR ELECTRO-PLATING. B. RED BACKGROUND COLOR WHITE TEXT AND LINE WORK. C. AERIAL FONT. 3. ALL SIGNS SHALL BE SIZED APPROPRIATELY AND PLACED IN THE LOCATIONS SPECIFIED. SIGNAGE CANNOT BE HAND-WRITTEN. 4. SIGNS SHALL BE ATTACHED TO THE SERVICE EQUIPMENT WITH POP-RIVETS OR SCREWS. NOTES: SITE PLACARD GREG ALBRIGHT 1 2 3 4 5 6 7 8 9 10 1-10 11-20 21-30 31-40 41-50 51-60 1 2 3 4 5 6 7 8 9 10 1-10 11-20 21-30 31-40 41-50 51-60 PV-8 FREEDOM FOREVER INDY 8.00 TEMPLATECONTRACTOR LICENSE: CERTIFIED ELECTRICAL CONTRACTOR EC13008056 FREEDOM FOREVER LLC 2619 CONSULATE DR SUITE 800, ORLANDO, FL 32819 Tel: (800) 385-1075 REVISED BY DATENO. SHEET: REVISIONS JOB NO: F112409 DESIGNED BY: ANTON CLIENT: DENIS SULLIVAN 7903 KENWOOD ROAD, FORT PIERCE, FL 34951 AHJ: ST. LUCIE COUNTY UTILITY: FPL - FLORIDA POWER & LIGHT PHONE: (772) 464-9154 SYSTEM: SYSTEM SIZE (DC): 19 X 350 = 6.650 kW SYSTEM SIZE (AC): 6.000 kW @ 240V MODULES: 19 X LONGI SOLAR: LR4-60HPB-350M OPTIMIZERS: 19 X SOLAREDGE P401 INVERTER: SOLAREDGE SE6000H-USRGM [SI1] DATE: 12/13/2021 MOD SWAP; LAYOUT CHANGE 12/13/20211 SOLAREDGE OPTIMIZER CHART OPTIMIZER CHART GREG ALBRIGHT KENWOOD ROAD SAFETY PLAN MARK UP KEY INSTRUCTIONS: 1. USE SYMBOLS IN KEY TO MARK UP THIS SHEET. 2. SAFETY PLAN MUST BE MARKED BEFORE JOB STARTS AS PART OF THE PRE-PLAN 3. DOCUMENT ALL ADDITIONAL HAZARDS ON THIS PAGE & MAKE NOTES ON THE JHA SHEET IN CASE OF EMERGENCY NEAREST HOSPITAL OR OCCUPATIONAL/INDUSTRIAL CLINIC NAME: _______________________________________________ ADDRESS: ___________________________________________ SAFETY COACH CONTACT INFORMATION NAME: _______________________________________________ PHONE NUMBER: _____________________________________ ALL EMPLOYEES ON SITE SHALL BE MADE AWARE OF THE SAFETY PLAN AND SIGN INDICATING THAT THEY ARE AWARE OF THE HAZARDS ON-SITE AND THE PLAN FOR WORKING SAFELY. NAME SIGNATURE __________ ________________ __________ ________________ __________ ________________ __________ ________________ __________ ________________ __________ ________________ __________ ________________ __________ ________________ __________ ________________ __________ ________________ DATE: ______________ TIME:___________________________ PERMANENT ANCHOR TEMPORARY ANCHOR INSTALLER LADDER JUNCTION / COMBINER BOX STUB-OUT SKYLIGHT NO LADDER ACCESS (STEEP GRADE OR GROUND LEVEL OBSTRUCTIONS) RESTRICTED ACCESS CONDUIT GAS SHUT OFF WATER SHUT OFF SERVICE DROP POWER LINES P T IL B S 7 Z GAS H2O PV-9 FREEDOM FOREVER INDY 8.00 TEMPLATECONTRACTOR LICENSE: CERTIFIED ELECTRICAL CONTRACTOR EC13008056 FREEDOM FOREVER LLC 2619 CONSULATE DR SUITE 800, ORLANDO, FL 32819 Tel: (800) 385-1075 REVISED BY DATENO. SHEET: REVISIONS JOB NO: F112409 DESIGNED BY: ANTON CLIENT: DENIS SULLIVAN 7903 KENWOOD ROAD, FORT PIERCE, FL 34951 AHJ: ST. LUCIE COUNTY UTILITY: FPL - FLORIDA POWER & LIGHT PHONE: (772) 464-9154 SYSTEM: SYSTEM SIZE (DC): 19 X 350 = 6.650 kW SYSTEM SIZE (AC): 6.000 kW @ 240V MODULES: 19 X LONGI SOLAR: LR4-60HPB-350M OPTIMIZERS: 19 X SOLAREDGE P401 INVERTER: SOLAREDGE SE6000H-USRGM [SI1] DATE: 12/13/2021 MOD SWAP; LAYOUT CHANGE 12/13/20211 SAFETY PLAN GREG ALBRIGHT JOB HAZARD ANALYSIS Crew leader to fill out all sections below, hold a pre-job safety meeting with all personnel, and upload this completed document and the Safety Plan to Site Capture Ladder Access x Ladders must be inspected before each use. x Extension ladders must be set up on a firm and level surface at a 4-to-1 rise to run angle (or 75 degrees) and the top must be secured to the structure. Extension style ladders placed on uneven, loose or slippery surfaces must additionally have the base firmly anchored or lashed so the base will not slip out. x Extension ladders must be used with walk-through devices or the ladder must extend 36" above the stepping off point. x A-frame ladders must only be climbed with the ladder spreader bars locked in the open position; A-frame ladders shall not be climbed while in the closed position (ex, closed and used while leaned against a structure). x Additional notes: Mobile Equipment x Only Qualified operators will operate equipment; operators must maintain a certification on their person for the equipment being operated. x Type(s) of mobile equipment (Type/Make/Model): x Qualified operator(s): Material Handling and Storage x Materials will be staged/stored in a way that does not present a hazard to client, personnel or public. Materials stored on the roof will be physically protect from failing or sliding off. Fall Protection x A site-specific plan for fall prevention and protection is required prior to starting work and must remain onsite at all times until work is complete; a fall rescue plan must be outlined and discussed among the crew prior to work start. x First-person-Up (FPU) must install their anchor and connect before any other task, including installing other anchors. The Last-Person-Down (LPD) must be the only person on a roof uninstalling fall protection. x FPCP (name and title): x FPU and LPD (name and title): Electrical Safety x The Electrical Qualified Person (EQP) is required onsite to perform electrical work. x All electrical work will be performed with equipment in an electrically safe condition (de-energized) unless approval has been granted prior to work. x Service drops and overhead electrical hazards will be indentified and protected from contact, as neccessary. x EQP (name and tile): Public Protection x The safety of the Client and Public must be maintained at all times. x The Client and the Public shall be prevented from entering the work zone through the use of barriers and/or signage, as required. x Company, Client and Public property shall be protected from falling objects. x Pets (including dogs) shall be secured by their owners prior to work start. x The Client should not leave pets, family members, or others in charge or care of Employees, Contractors, or Temporary Workers. x Crew leader responsible for communication with the client: x Client and public is excluded from work area by barricades (N/A, Yes, No): Training and Pre-Job Safety Briefing x All employees onsite shall be made aware of the specific hazards of this project and review this HJA during a pre-job briefing, and their signature indicates awareness of site conditions and the plan to eliminate any hazards identified prior to and during the project. x Crew leader (name/title): x Crew member (name/title): x Crew member (name/title): x Crew member (name/title): x Crew member (name/title): x Crew member (name/title): Airborne Contaminants: x Asbestos-containing (Transite) piping (ACP) - Do not disturb (move, drill, cut fracture, etc.) x Asbestos-containing thermal insulation (ACI) and Asbestos-containing duct wrapping (ACW) - do not disturb, no attic or crawlspace access is allowed if work to be performed could cause exposure to personnel, client or public. x If yes, list specific tasks and protection in place: Weather and Environment x The site supervisor shall forecast the weather conditions at the job site, prior to crew arrival, in order to mitigate any hazards associated with inclement weather (heat, cold, wind, rain, etc.) x The site supervisor will utilized a portable wind meter (anemometer) to verify actual onsite wind conditions, by checking at the ground and on any elevated work surface (ex, rooftop) prior to work start, at midday and prior to solar panel staging on a roof. x Elevated work involving the moving or maneuvering of solar panels shall cease at 25mph (sustained wind) until wind subsides. x Forecasted weather maximum temp (degrees f): Heat Related Illness Prevention x Employees shall have access to potable drinking water that is fresh, pure, and suitably cool. The water shall be located as close as practicable to the areas where employees are working. Water shall be supplied in sufficient quantity at the beginning of the work shift to provide at least one quart per employee per hour for drinking for the entire shift. Employees may begin the shift with smaller quantities of water if they identify the location and have effective means for replenishment during the shift to allow employees to drink on quart or more per hour. The frequent drinking of water shall be encouraged. x Shade shall be present when temperature exceeds 80 degrees Fahrenheit. When the outdoor temperature in the work exceeds 80 degrees Fahrenheit, employees shall have and maintain one or more areas with shade at all times. x New employees must be acclimatized. New employees will be monitored by their Crew Leader (site supervisor) for the first two (2) weeks of employment or longer when necessary. x Employees will be allowed and encouraged to implement scheduled breaks during each shift. Employees must take cool-down breaks in the shade any time they feel the need to do so to protect them from overheating. Supervisors are REQUIRED to allow employees any break period they need during high heat conditions. x Cool Vests are encouraged for all employees at all times during periods of high heat. x Identify the location of the closet Occupational/Industrial Clinic or Hospital in case a crew member becomes ill. What is the specific plan to provide and replenish sufficient water for all employees on site? x If offsite replenish is necessary, where will you go to replenish water (location/address): x Who will replenish the drinking water (name): Restroom facilities x Employees shall have access to restroom facilities with hand-washing stations. Use of onsite restroom is at the client's discretion (location is annotated below). If client does not give permission, location of suitable restroom facilities with hand-washing stations offsite will be provided. The onsite supervisor will identify location and make arrangements to ensure all employees have access at any point. x Restroom facilities will be (circle one): Onsite - Offsite x If Offsite, add location name and address: Incident Reporting Procedure x Contact your Site Supervisor Name: Phone: x Contact your Manager Name: Phone: x Contact your Site Supervisor Name: Phone: With: Your full name, phone number, office location, brief description of what happen and when. NOTE ADDITIONAL HAZARDS NOT ADDRESSED ABOVE (add as many as necessary by using additional sheets) Define the Hazard:Method/steps to prevent incident: Define the Hazard:Method/steps to prevent incident: Define the Hazard:Method/steps to prevent incident: Define the Hazard:Method/steps to prevent incident: PV-10 FREEDOM FOREVER INDY 8.00 TEMPLATECONTRACTOR LICENSE: CERTIFIED ELECTRICAL CONTRACTOR EC13008056 FREEDOM FOREVER LLC 2619 CONSULATE DR SUITE 800, ORLANDO, FL 32819 Tel: (800) 385-1075 REVISED BY DATENO. SHEET: REVISIONS JOB NO: F112409 DESIGNED BY: ANTON CLIENT: DENIS SULLIVAN 7903 KENWOOD ROAD, FORT PIERCE, FL 34951 AHJ: ST. LUCIE COUNTY UTILITY: FPL - FLORIDA POWER & LIGHT PHONE: (772) 464-9154 SYSTEM: SYSTEM SIZE (DC): 19 X 350 = 6.650 kW SYSTEM SIZE (AC): 6.000 kW @ 240V MODULES: 19 X LONGI SOLAR: LR4-60HPB-350M OPTIMIZERS: 19 X SOLAREDGE P401 INVERTER: SOLAREDGE SE6000H-USRGM [SI1] DATE: 12/13/2021 MOD SWAP; LAYOUT CHANGE 12/13/20211 SAFETY PLAN GREG ALBRIGHT Power Optimizer P370 / P401 / P404 / P485 / P500 / P505 / P601 25 YEAR WARRANTY PV power optimization at the module level Specifically designed to work with SolarEdge inverters Up to 25% more energy Next generation maintenance with module-level monitoring Mitigates all types of modules mismatch-loss, from manufacturing tolerance to partial shading Superior efficiency (99.5%) Flexible system design for maximum space utilization Module-level voltage shutdown for installer and firefighter safety Fast installation with a single bolt solaredge.com POWER OPTIMIZERPower Optimizer P370 / P401 / P404 / P485 / P500 / P505 / P601 OPTIMIZER MODEL (typical module compatibilty) P370 (60&70 Cell modules) P401 (60&70 Cell modules) P404 (for 60-cell and 72 cell, short strings) P485 (for high voltage modules) P500 (for 96-cell modules) P505 (for higher current modules) P601 (for 1 x high power PV module) UNIT INPUT Rated Input DC Power(1) 370 400 405 485 500 505 600 W Absolute Maximum Input Voltage (Voc at lowest temperature) 60 80 125 80 83 65 Vdc MPPT Operating Range 8 - 60 12.5 - 80 12.5 - 105 8 - 80 12.5-83 12.5 - 65 Vdc Maximum Short Circuit Current (Isc) 11 1.5 11 10.1 14 Adc Maximum Efficiency 99.5 % Weighted Efficiency 98.8 98.6 % Overvoltage Category II OUTPUT DURING OPERATION (POWER OPTIMIZER CONNECTED TO OPERATING SOLAREDGE INVERTER) Maximum Output Current 15 Adc Maximum Output Voltage 60 80 60 80 Vdc OUTPUT DURING STANDBY (POWER OPTIMIZER DISCONNECTED FROM SOLAREDGE INVERTER OR SOLAREDGE INVERTER OFF) Safety Output Voltage per Power Optimizer 1 ± 0.1 Vdc STANDARD COMPLIANCE EMC FCC Part 15 Class B, IEC61000-6-2, IEC61000-6-3 Safety IEC62109-1 (class II safety), UL1741 RoHS Yes Fire Safety VDE-AR-E 2100-712:2013-05 INSTALLATION SPECIFICATIONS Maximum Allowed System Voltage 1000 Vdc Dimensions (W x L x H) 129 x 153 x 27.5 / 5.1 x 6 x 1.1 129 x 153 x 29.5 / 5.1 x 6 x 1.16 129 x 153 x 42.5 / 5.1 x 6 x 1.7 129 x 159 x 49.5 / 5.1 x 6.2 x 1.9 129 x 153 x 33.5 / 5.1 x 6 x 1.3 129 x 162 x 59 / 5.1 x 6.4 x 2.3 129 x 153 x 52 / 5.1 x 6 x 2 mm / in Weight (including cables) 655 / 1.5 775 / 1.7 845 / 1.9 750 / 1.7 1064 / 2.3 gr / lb Input Connector MC4(2) Single or Dual MC4(2)(3) MC4(2) Input Wire Length 0.16 / 0.52, 0.9 / 2.95 0.16 / 0.52 m / ft Output Connector MC4 Output Wire Length 1.2 / 3.9 1.4 / 4.5 m / ft Operating Temperature Range(4) -40 to +85 / -40 to +185 Ü& / Ü) Protection Rating IP68 Relative Humidity 0 - 100 % (1) Rated power of the module at STC will not exceed the optimizer “Rated Input DC Power”. Modules with up to +5% power tolerance are allowed (2) For other connector types please contact SolarEdge (3) For dual version for parallel connection of two modules use the P485. In the case of an odd number of PV modules in one string, installing one P485 dual version power optimizer connected to one PV module is supported. When connecting a single module, seal the unused input connectors using the supplied pair of seals (4) For ambient temperature above +70°C / +158°F power de-rating is applied. Refer to Power Optimizers Temperature De-Rating Technical Note for more details PV System Design Using a Solaredge Inverter(5) Single Phase HD-WAVE Single Phase Three Phase Three Phase for 277/480V Grid Minimum String Length (Power Optimizers) P370, P401, P500(6) 8 16 18 P404, P485, P505, P601 6 14 (13 with SE3K(7)) 14 Maximum String Length (Power Optimizers) 25 50 50 Maximum Nominal Power per String(8) 5700 5250 11250(9) 12750(10) W Parallel Strings of Different Lengths or Orientations Yes (5) It is not allowed to mix P404/P485/P505/P601 with P370/P401/P500 in one string (6) The P370/P401/P500 cannot be used with the SE3K three phase inverter (available in some countries; refer to the three phase inverter SE3K-SE10K datasheet) (7) Exactly 10 when using SE3K-RW010BNN4 (8) ,IWKHLQYHUWHUVUDWHG$&SRZHU•PD[LPXPQRPLQDOSRZHUSHUVWULQJWKHQWKHPD[LPXPSRZHUSHUVWULQJZLOOEHDEOHWRUHDFKXp to the inverters maximum input DC power Refer to: https://www.solaredge.com/sites/default/files/se-power-optimizer-single-string-design-application-note.pdf (9) For the 230/400V grid: it is allowed to install up to 13,500W per string when the maximum power difference between each string is 2,000W (10) For the 277/480V grid: it is allowed to install up to 15,000W per string when the maximum power difference between each string is 2,000W © SolarEdge Technologies, Ltd. All rights reserved. SOLAREDGE, the SolarEdge logo, OPTIMIZED BY SOLAREDGE are trademarks or registered trademarks of SolarEdge Technologies, Inc. All other trademarks mentioned herein are trademarks of their respective owners. Date: 0/2021 DS-000047-2.-ENG. Subject to change without notice. INVERTERSsolaredge.com Optimized installation with HD-Wave technology 6SHFLÀFDOO\GHVLJQHGWRZRUNZLWK SRZHURSWLPL]HUV %XLOWLQPRGXOHOHYHOPRQLWRULQJ 2XWGRRUDQGLQGRRULQVWDOODWLRQ 2SWLRQDO5HYHQXHJUDGHGDWD$16,& &ODVV DFFXUDF\ 5HFRUGEUHDNLQJH඼FLHQF\ )L[HGYROWDJHLQYHUWHUIRUORQJHUVWULQJV ,QWHJUDWHGDUFIDXOWSURWHFWLRQDQGUDSLGVKXWGRZQIRU 1(&DQGSHUDUWLFOHDQG ([WUHPHO\VPDOO 8/6$FHUWLÀHGIRU&38&5XOHJULG FRPSOLDQFH Single Phase Inverter with HD-Wave Technology for North America 6(+866(+866(+866(+86 6(+866(+866(+86 12-25 YEARWARRANTY SE3000H-US SE3800H-US SE5000H-US SE6000H-US SE7600H-US SE10000H-US SE11400H-US OUTPUT Rated AC Power Output 3000 3800 @ 240V 3300 @ 208V 5000 6000 @ 240V 5000 @ 208V 7600 10000 11400 @ 240V 10000 @ 208V VA Maximum AC Power Output 3000 3800 @ 240V 3300 @ 208V 5000 6000 @ 240V 5000 @ 208V 7600 10000 11400 @ 240V 10000 @ 208V VA AC Output Voltage Min.-Nom.-Max. (211 - 240 - 264)9999999Vac AC Output Voltage Min.-Nom.-Max. (183 - 208 - 229)-9 -9 --9 Vac AC Frequency (Nominal)59.3 - 60 - 60.5(1)Hz Maximum Continuous Output Current @240V 12.5 16 21 25 32 42 47.5 A Maximum Continuous Output Current @208V -16-24- -48.5A GFDI Threshold 1 A Utility Monitoring, Islanding Protection, &RXQWU\&RQÀJXUDEOH7KUHVKROGV Yes INPUT Maximum DC Power @240V 4650 5900 7750 9300 11800 15500 17650 W Maximum DC Power @208V -5100 -7750 --15500 W Transformer-less, Ungrounded Yes Maximum Input Voltage 480 Vdc Nominal DC Input Voltage 380 400 Vdc Maximum Input Current @240V(2)8.5 10.5 13.5 16.5 20 27 30.5 Adc Maximum Input Current @208V(2)-9-13.5--27Adc Max. Input Short Circuit Current 45 Adc Reverse-Polarity Protection Yes Ground-Fault Isolation Detection 600k Sensitivity 0D[LPXP,QYHUWHU(੕FLHQF\99 99.2 % &(&:HLJKWHG(੕FLHQF\99 99 @ 240V 98.5 @ 208V % Nighttime Power Consumption < 2.5 W ADDITIONAL FEATURES Supported Communication Interfaces RS485, Ethernet, ZigBee (optional), Cellular (optional) Revenue Grade Data, ANSI C12.20 Optional(3) Rapid Shutdown - NEC 2014 and 2017 690.12 Automatic Rapid Shutdown upon AC Grid Disconnect STANDARD COMPLIANCE Safety UL1741, UL1741 SA, UL1699B, CSA C22.2, Canadian AFCI according to T.I.L. M-07 Grid Connection Standards IEEE1547, Rule 21, Rule 14 (HI) Emissions FCC Part 15 Class B INSTALLATION SPECIFICATIONS AC Output Conduit Size / AWG Range 1" Maximum / 14-6 AWG 1" Maximum /14-4 AWG DC Input Conduit Size / # of Strings / AWG Range 0D[LPXPᐎULQJV$:*0D[LPXPᐎULQJV$:* Dimensions with Safety Switch (HxWxD)17.7 x 14.6 x 6.8 / 450 x 370 x 174 21.3 x 14.6 x 7.3 / 540 x 370 x 185 in / mm Weight with Safety Switch 22 / 10 25.1 / 11.4 26.2 / 11.9 38.8 / 17.6 OENJ Noise < 25 <50 dBA Cooling Natural Convection Operating Temperature Range -13 to +140 / -25 to +60(4) Ü)Ü&RSWLRQ (5)Ü)Ü& Protection Rating NEMA 4X (Inverter with Safety Switch) (1) For other regional settings please contact SolarEdge support (2)$KLJKHUFXUUHQWVRXUFHPD\EHXVHGWKHLQYHUWHUZLOOOLPLWLWVLQSXWFXUUHQWWRWKHYDOXHVᐎDWHG (3) Revenue grade inverter P/N: SExxxxH-US000NNC2 (4) For power de-rating information refer to: KWWSVZZZVRODUHGJHFRPVLWHVGHIDXOWÀOHVVHWHPSHUDWXUHGHUDWLQJQRWHQDSGI (5) -40 version P/N: SExxxxH-US000NNU4 SE3000H-US SE3800H-US SE5000H-US SE6000H-US SE7600H-US SE10000H-US SE11400H-US OUTPUT Rated AC Power Output 3000 3800 @ 240V 3300 @ 208V 5000 6000 @ 240V 5000 @ 208V 7600 10000 11400 @ 240V 10000 @ 208V VA Maximum AC Power Output 3000 3800 @ 240V 3300 @ 208V 5000 6000 @ 240V 5000 @ 208V 7600 10000 11400 @ 240V 10000 @ 208V VA AC Output Voltage Min.-Nom.-Max. (211 - 240 - 264)9 9 9 9 9 9 9 Vac AC Output Voltage Min.-Nom.-Max. (183 - 208 - 229)-9 -9 --9 Vac AC Frequency (Nominal)59.3 - 60 - 60.5(1)Hz Maximum Continuous Output Current @240V 12.5 16 21 25 32 42 47.5 A Maximum Continuous Output Current @208V -16 -24 --48.5 A GFDI Threshold 1 A Utility Monitoring, Islanding Protection, &RXQWU\&RQÀJXUDEOH7KUHVKROGV Yes INPUT Maximum DC Power @240V 4650 5900 7750 9300 11800 15500 17650 W Maximum DC Power @208V -5100 -7750 --15500 W Transformer-less, Ungrounded Yes Maximum Input Voltage 480 Vdc Nominal DC Input Voltage 380 400 Vdc Maximum Input Current @240V(2)8.5 10.5 13.5 16.5 20 27 30.5 Adc Maximum Input Current @208V(2)-9 -13.5 --27 Adc Max. Input Short Circuit Current 45 Adc Reverse-Polarity Protection Yes Ground-Fault Isolation Detection 600k Sensitivity 0D[LPXP,QYHUWHU(੕FLHQF\99 99.2 % &(&:HLJKWHG(੕FLHQF\99 99 @ 240V 98.5 @ 208V % Nighttime Power Consumption < 2.5 W ADDITIONAL FEATURES Supported Communication Interfaces RS485, Ethernet, ZigBee (optional), Cellular (optional) Revenue Grade Data, ANSI C12.20 Optional(3) Rapid Shutdown - NEC 2014 and 2017 690.12 Automatic Rapid Shutdown upon AC Grid Disconnect STANDARD COMPLIANCE Safety UL1741, UL1741 SA, UL1699B, CSA C22.2, Canadian AFCI according to T.I.L. M-07 Grid Connection Standards IEEE1547, Rule 21, Rule 14 (HI) Emissions FCC Part 15 Class B INSTALLATI ON SPECIFICATI ONS AC Output Conduit Size / AWG Range 1" Maximum / 14-6 AWG 1" Maximum /14-4 AWG DC Input Conduit Size / # of Strings / AWG Range 0D[LPXPᐎULQJV$:*0D[LPXPᐎULQJV$:* Dimensions with Safety Switch (HxWxD)17.7 x 14.6 x 6.8 / 450 x 370 x 174 21.3 x 14.6 x 7.3 / 540 x 370 x 185 in / mm Weight with Safety Switch 22 / 10 25.1 / 11.4 26.2 / 11.9 38.8 / 17.6 OENJ Noise < 25 <50 dBA Cooling Natural Convection Operating Temperature Range -13 to +140 / -25 to +60(4) Ü)Ü&RSWLRQ (5)Ü)Ü& Protection Rating NEMA 4X (Inverter with Safety Switch) (1) For other regional settings please contact SolarEdge support (2)$KLJKHUFXUUHQWVRXUFHPD\EHXVHGWKHLQYHUWHUZLOOOLPLWLWVLQSXWFXUUHQWWRWKHYDOXHVᐎDWHG (3) Revenue grade inverter P/N: SExxxxH-US000NNC2 (4) For power de-rating information refer to:KWWSVZZZVRODUHGJHFRPVLWHVGHIDXOWÀOHVVHWHPSHUDWXUHGHUDWLQJQRWHQDSGI (5) -40 version P/N: SExxxxH-US000NNU4 Single Phase Inverter with HD-Wave Technology for North America 6(+866(+866(+866(+86 6(+866(+866(+86 Œ6RODU(GJH7HFKQRORJLHV,QF$OOULJKWVUHVHUYHG62/$5('*(WKH6RODU(GJHORJR237,0,=('%<62/$5('*(DUHWUDGHPDUNVRUUHJLVWHUHGWUDGHPDUNVRI6RODU(GJH7HFKQRORJLHV,QF$OO RWKHUWUDGHPDUNVPHQWLRQHGKHUHLQDUHWUDGHPDUNVRIWKHLUUHVSHFWLYHRZQHUV'DWH9(1*1$06XEMHFWWRFKDQJHZLWKRXWQRWLFH pe.eaton.com Eaton general duty cartridge fuse safety switch DG222NRB UPC:782113144221 Dimensions: Height:14.37 IN● Length:7.35 IN● Width:8.4 IN● Weight:10 LB Notes:Maximum hp ratings apply only when dual element fuses are used. 3-Phase hp rating shown is a grounded B phase rating, UL listed. Warranties: Eaton Selling Policy 25-000, one (1) year from the date of installation of the Product or eighteen (18) months from the date of shipment of the Product, whichever occurs first. ● Specifications: Type:General duty, cartridge fused● Amperage Rating:60A● Enclosure:NEMA 3R● Enclosure Material:Painted galvanized steel● Fuse Class Provision:Class H fuses● Fuse Configuration:Fusible with neutral● Number Of Poles:Two-pole● Number Of Wires:Three-wire● Product Category:General duty safety switch● Voltage Rating:240V● Supporting documents: Eatons Volume 2-Commercial Distribution● Eaton Specification Sheet - DG222NRB● Certifications: UL Listed● Product compliance:No Data ______________________________________________________________________ © 2016 Eaton. All rights reserved. Take your business to the next level with SFM INFINITY, UNIRAC’s rail-less PV mounting system for flush mount installations on comp shingle and tile roofs. An advanced 3rd generation product platform in use by top solar contractors nationwide, SFM INFINITY optimizes your operations on and off the roof, with approximately 40% less labor, 30% logistics savings, and 20% fewer roof attachments than traditional solar racking. Plus, 87% of homeowners prefer SFM INFINITY’s aesthetics. SUPERIOR PERFORMANCE Enhance your business with two installs per day and 30% less cost. EASY INSTALLATION Pre-assembled components, 20% fewer roof attachments, and level array in seconds with post height adjustment. HOMEOWNER PREFERRED More than 4 out of 5 homeowners prefer SFM INFINITY’S aesthetics over a leading rail brand. SFM INFINITY FRONT TRIM AND END CAPS UNIVERSAL COMPONENTS FIT 32 – 40MM MODULES EOWNER PREFERRED 25 YEAR FULL-SYSTEM WARRANTY ONE SKU FITS 32 TO 40mm REVOLUTIONIZING ROOFTOP SOLAR FOR QUESTIONS OR CUSTOMER SERVICE VISIT UNIRAC.COM OR CALL (505) 248-2702 REVOLUTIONIZING ROOFTOP SOLAR FOR QUESTIONS OR CUSTOMER SERVICE VISIT UNIRAC.COM OR CALL (505) 248-2702 SFM INFINITY DESIGN GUIDELINES APPLICATION GUIDE While you will see advantages simply from switching to SFM INFINITY, the following guidelines will help you to maximize its benefits. When possible, design in landscape orientation in order to fit more modules on the roof and minimize roof attachments. DEFAULT TO LANDSCAPE SFM INFINITY is easily configured in mixed array shapes and module orientations to maximize array density and to avoid vent pipes and other obstacles. Because mounting locations are not constrained by rails, SFM INFINITY has unmatched flexibility to enhance your projects. MIX MODULE ORIENTATIONS Visit UNIRAC’s mobile-friendly library of short, topic-specific videos which answer common questions and demonstrate how simple it is to install SFM INFINITY. CONSULT THE QUICK TIPS VIDEOS Quick Tips Videos: https://unirac.com/SFM-Infinity/ Layout your arrays in U-Builder, UNIRAC’s free solar design software, to optimize SFM INFINITY’S capabilities, including mixing module orientations and minimizing roof attachments. Quickly create layouts on Google or Bing Maps and generate project documents. DESIGN IN U-BUILDER U-Builder: https://design.unirac.com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ϸ 8/'HVLJQ/RDG5DWLQJ36)'RZQZDUG36)8SZDUG36)'RZQ6ORSH 7HVWHG/RDGVSVI3D'RZQZDUGSVI3D8SOLIWSVI3D'RZQ6ORSH 7ULQD7603'DQG6XQSRZHU635(XVHGIRU0HFKDQLFDO/RDGLQJ ,QFUHDVHGVL]H0/WHVW 0D[LPXP0RGXOH6L]HIWð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´JDSEHWZHHQWKHERWWRPRIWKHPRGXOHDQGWKHURRI¶V VXUIDFH See section 7.0 illustraction # 1 and 1a for a complete list of PV modules evaluated with these racking systems 5DWLQJV 1$ (' $SU 0DQGDWRU\ AUTHORIZATION TO MARK Applicant:Manufacturer: Address:Address: Country:Country: Contact: Contact: Phone: Phone: FAX: FAX: Email: Email: Standard(s): Product: Brand Name: Models: This Authorization to Mark is for the exclusive use of Intertek's Client and is provided pursuant to the Certification agreement between Intertek and its Client. Intertek's responsibility and liability are limited to the terms and conditions of the agreement. Intertek assumes no liability to any party, other than to the Client in accordance with the agreement, for any loss, expense or damage occasioned by the use of this Authorization to Mark. Only the Client is authorized to permit copying or distribution of this Authorization to Mark and then only in its entirety. Use of Intertek’s Certification mark is restricted to the conditions laid out in the agreement and in this Authorization to Mark. Any further use of the Intertek name for the sale or advertisement of the tested material, product or service must first be approved in writing by Intertek. Initial Factory Assessments and Follow up Services are for the purpose of assuring appropriate usage of the Certification mark in accordance with the agreement, they are not for the purposes of production quality control and do not relieve the Client of their obligations in this respect. Intertek Testing Services NA Inc. 545 East Algonquin Road, Arlington Heights, IL 60005 Telephone 800-345-3851 or 847-439-5667 Fax 312-283-1672 Mounting Systems, Mounting Devices, Clamping/Retention Devices, and Ground Lugs for Use with Flat- Plate Photovoltaic Modules and Panels [UL 2703: 2015 Ed.1] Photovoltaic Mounting System, Sun Frame Microrail - Installed Using Unirac Installation Guide, Rev PUB2019MAR01 with Annex North Row Extension Installation Guide Rev PUB2019FEB20 Unirac SFM Unirac Control Number:5003705 Authorized by: for Dean Davidson, Certification Manager This document supersedes all previous Authorizations to Mark for the noted Report Number. klaus.nicolaedis@unirac.com toddg@unirac.com jia.liu@cxymj.com buwan.luo@cxymj.com Party Authorized To Apply Mark:Same as Manufacturer Report Issuing Office:Lake Forest, CA U.S.A. Klaus Nicolaedis Tom Young Jia Liu Robin Luo 505-462-2190 505-843-1418 +86-15267030962 +86-13621785753 NA NA Unirac, Inc Cixi Emeka Aluminum Co. Ltd 1411 Broadway Blvd NE Albuquerque, NM 87102 No. 688 ChaoSheng Road Cixi City Zhejiang Province 315311 USA China This authorizes the application of the Certification Mark(s) shown below to the models described in the Product(s) Covered section when made in accordance with the conditions set forth in the Certification Agreement and Listing Report. This authorization also applies to multiple listee model(s) identified on the correlation page of the Listing Report. This document is the property of Intertek Testing Services and is not transferable. The certification mark(s) may be applied only at the location of the Party Authorized To Apply Mark. Page 1 of 1 ATM for Report 102393982LAX-002 ATM Issued: 9-Apr-2019 ED 16.3.15 (20-Apr-17) Mandatory ĐŽ&ĂƐƚĞŶ^ŽůĂƌ>> ϰϭϰϭtsĂŶƵƌĞŶ^ƚ͕^ƚĞϮ WŚŽĞŶŝdž͕ϴϱϬϬϵ d>͗;ϴϳϳͿϴϱϵͲϯϵϰϳ ƚƚŶ͗͘ĐŽ&ĂƐƚĞŶ^ŽůĂƌ>>ͲŶŐŝŶĞĞƌŝŶŐĞƉĂƌƚŵĞŶƚ ^ƵďũĞĐƚ͗ŶŐŝŶĞĞƌŝŶŐĞƌƚŝĨŝĐĂƚŝŽŶĨŽƌƚŚĞ^ƚĂƚĞŽĨ&ůŽƌŝĚĂ ƵŝůĚŝŶŐŽĚĞƐ͗ ϭ͘ ^ͬ^/ϳͲϭϲ͕DŝŶŝŵƵŵĞƐŝŐŶ>ŽĂĚƐĨŽƌƵŝůĚŝŶŐƐĂŶĚKƚŚĞƌ^ƚƌƵĐƚƵƌĞƐ͕ďLJŵĞƌŝĐĂŶ ^ŽĐŝĞƚLJŽĨŝǀŝůŶŐŝŶĞĞƌƐ Ϯ͘ ϮϬϮϬ&ͲƵŝůĚŝŶŐ͕ϳƚŚĚŝƚŝŽŶ͕ĂƐĞĚŽŶϮϬϭϴ/ŶƚĞƌŶĂƚŝŽŶĂůƵŝůĚŝŶŐŽĚĞ ϯ͘ ϮϬϮϬ&RͲZĞƐŝĚĞŶƚŝĂů͕ϳƚŚĚŝƚŝŽŶ͕ĂƐĞĚŽŶϮϬϭϴ/ŶƚĞƌŶĂƚŝŽŶĂůZĞƐŝĚĞŶƚŝĂůŽĚĞ ϰ͘ ϰϮϴ͕ĐĐĞƉƚĂŶĐĞƌŝƚĞƌŝĂĨŽƌDŽĚƵůĂƌ&ƌĂŵŝŶŐ^LJƐƚĞŵƐhƐĞĚƚŽ^ƵƉƉŽƌƚWŚŽƚŽǀŽůƚĂŝĐ ;WsͿWĂŶĞůƐ͕EŽǀĞŵďĞƌϭ͕ϮϬϭϮďLJ/Ͳ^ ϱ͘ ůƵŵŝŶƵŵĞƐŝŐŶDĂŶƵĂůϮϬϭϱ͕ďLJdŚĞůƵŵŝŶƵŵƐƐŽĐŝĂƚŝŽŶ͕/ŶĐ͘ ϲ͘ E^/ͬtE^ͲϮϬϭϴ͕EĂƚŝŽŶĂůĞƐŝŐŶ^ƉĞĐŝĨŝĐĂƚŝŽŶĨŽƌtŽŽĚŽŶƐƚƌƵĐƚŝŽŶ͕ďLJƚŚĞ ŵĞƌŝĐĂŶtŽŽĚŽƵŶĐŝů ĞƐŝŐŶƌŝƚĞƌŝĂ͗ZŝƐŬĂƚĞŐŽƌLJ// ^ĞŝƐŵŝĐĞƐŝŐŶĂƚĞŐŽƌLJсͲ džƉŽƐƵƌĞĂƚĞŐŽƌLJс͕Θ ĂƐŝĐtŝŶĚ^ƉĞĞĚ;ƵůƚŝŵĂƚĞͿƉĞƌ^ϳͲϭϲсϵϬŵƉŚƚŽϭϴϬŵƉŚ 'ƌŽƵŶĚ^ŶŽǁ>ŽĂĚсϬƚŽϲϬ;ƉƐĨͿ dŚŝƐůĞƚƚĞƌĐĞƌƚŝĨŝĞƐƚŚĂƚƚŚĞůŽĂĚŝŶŐĐƌŝƚĞƌŝĂĂŶĚĚĞƐŝŐŶďĂƐŝƐĨŽƌƚŚĞ ĐŽ&ĂƐƚĞŶͲZŽĐŬ/ƚ^LJƐƚĞŵ^ƉĂŶdĂďůĞƐĂƌĞ ŝŶĐŽŵƉůŝĂŶĐĞǁŝƚŚƚŚĞĂďŽǀĞĐŽĚĞƐ͘ /ĨLJŽƵŚĂǀĞĂŶLJƋƵĞƐƚŝŽŶƐŽŶƚŚĞĂďŽǀĞ͕ĚŽŶŽƚŚĞƐŝƚĂƚĞƚŽĐĂůů͘ WƌĞƉĂƌĞĚďLJ͗ W^͕/ŶĐ͘ʹ^ƚƌƵĐƚƵƌĂůŶŐŝŶĞĞƌƐ ZŽƐĞǀŝůůĞ͕ DĂLJϮϭ͕ϮϬϮϭ W^͕/ŶĐ͘ʹ^ƚƌƵĐƚƵƌĂůŶŐŝŶĞĞƌƐŚĂƐƉƌŽǀŝĚĞĚĞŶŐŝŶĞĞƌŝŶŐĂŶĚƐƉĂŶƚĂďůĞƐĨŽƌƚŚĞĐŽ&ĂƐƚĞŶͲZŽĐŬ/ƚ^LJƐƚĞŵ͕ĂƐƉƌĞƐĞŶƚĞĚ ŝŶW^ZĞƉŽƌƚηϮϬϭϱͲϬϱϴϴϰ,'͘Ϭϳ͘Ϭϭ͕ΗŶŐŝŶĞĞƌŝŶŐĞƌƚŝĨŝĐĂƚŝŽŶĨŽƌƚŚĞĐŽ&ĂƐƚĞŶͲZŽĐŬ/ƚ^LJƐƚĞŵĨŽƌ'ĂďůĞĂŶĚ,ŝƉ ZŽŽĨƐΗ͘ůůŝŶĨŽƌŵĂƚŝŽŶ͕ĚĂƚĂ͕ĂŶĚĂŶĂůLJƐŝƐƚŚĞƌĞŝŶĂƌĞďĂƐĞĚŽŶ͕ĂŶĚĐŽŵƉůLJǁŝƚŚ͕ƚŚĞĨŽůůŽǁŝŶŐďƵŝůĚŝŶŐĐŽĚĞƐĂŶĚƚLJƉŝĐĂů ƐƉĞĐŝĨŝĐĂƚŝŽŶƐ͗ ZĞ͗ZĞƉŽƌƚηϮϬϭϱͲϬϱϴϴϰ,'͘Ϭϳ͘ϬϭʹĐŽ&ĂƐƚĞŶͲZŽĐŬ/ƚ^LJƐƚĞŵĨŽƌ'ĂďůĞĂŶĚ,ŝƉZŽŽĨƐ EXP. 02/28/2023 ZACHE RPAULK. E NSECIL A R I D AOLF NOISSE FORP L E N GINEERSTATE OF No. 73522 05/21/2021 THIS ITEM HAS BEEN ELECTRONICALLY SIGNED AND SEALED BY PAUL K. ZACHER, PE ON 05/21/2021 USING A SHA-1 AUTHENTICATION CODE. PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED SIGNED AND SEALED AND THE SHA-1 AUTHENTICATION CODE MUST BE VERIFIED ON ANY ELECTRONIC COPIES.