HomeMy WebLinkAboutType Of Permit ( Addition )41
#I
2400 Rhode Island Ave
Fort Pierce, Florida 34950
ST. LUCIE COUNTY FIRE DISTRICT
BUREAU OF FIRE PREVENTION
PLAN REVIEW
TYPE OF PERMIT
Telephone (561)-462-2312
Fax:: (561)-462-2323
( ) New Construction ( ) Tenant Improvement ( ) Addition (X ) Renovation/alteration ( ) Shell Only
Jurisdiction: St Lucie County
Occupancy: Truck Wash
Address: 300 Kings Hwy
Contractor: Riverside Construction Co
Contractors address: 500 Gardenia
Arch itect/Engineer: John A Shaver
Building owner: Beale Holdings Inc
Occupancy type: Mixed
Gross sq. ft. 5165 sq ft
Occupant load:
Construction type ( NFPA-220) Type:
F.P.B. B-99-205
Building Dept. 99110346
Number of stories: 1
Phone # 561-231-4556
City: Vero Beach, FL Zip: 32963
Phone #:
Review date: 11-30-99
Automatic sprinklers:
Net sq. ft.
Based on:
SBCCI: Type: V
NOTE
1. All revisions must be in compliance before the final inspection, or so noted.
2. The Fire Marshal required 24 hour notice on all inspections.
3. The respective Building Department shall schedule all final inspections through the Fire Marshal's Office.
4. Failed inspections require payment of fee prior to scheduling of any further inspections.
5. Permit fees are required to be paid in full prior to any inspections.
6. A copy of the required revision/s have been transmitted to the Architect( ) Contractor ( ). .
REVISIONS REQUIRED
1. HVAC Provide either a fire stat or a duct type smoke detector for automatic fan shutdown.
2. Provide emergency lighting for the interior occupied space and the mechanical room.
3. Provide a 2A-10BC rated fire extinguisher for the interior occupied space and a 3A40BC rated fire
extinguisher for the mechanical room.
4. Penetrations through the wall separating the office and mechanical room shall be of the proper UL Design.
Reviewed By: A�-�� Date: November 30, 1999
Tony Liento