Loading...
HomeMy WebLinkAbout402.4 33CHAPTER 4 GAS PIPING INSTALLATIONS TABLE 402.4(33) CORRUGATED STAINLESS STEEL TUBING (CSST) Gas Undiluted Propane Inlet Pressure 2.0 psi Pressure Drop 1.0 psi Specific Gravity 1.50 2020 Florida Building Code, Fuel Gas, 7th Edition First Printing: Jul 2020 Copyright © ICC All Rights Reserved. Accessed by Energized Electric on 03/15/2021 pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Any Unauthorized reproduction or distribution is a violation of the federal copyright, and subject to civil and criminal penalties thereunder. INTENDED USE: SIZING BETWEEN 2 PSI SERVICE AND THE LINE PRESSURE REGULATOR TUBE SIZE (EHD) Flow Designation 13 15 18 19 23 25 30 31 37 39 46 48 60 62 Length (ft)Capacity in Thousands of Btu per Hour 10 426 558 927 1,110 1,740 2,170 4,100 4,720 7,130 7,958 15,200 16,800 29,400 34,200 25 262 347 591 701 1,120 1,380 2,560 2,950 4,560 5,147 9,550 10,700 18,800 21,700 30 238 316 540 640 1,030 1,270 2,330 2,690 4,180 4,719 8,710 9,790 17,200 19,800 40 203 271 469 554 896 1,100 2,010 2,320 3,630 4,116 7,530 8,500 14,900 17,200 50 181 243 420 496 806 986 1,790 2,070 3,260 3,702 6,730 7,610 13,400 15,400 75 147 196 344 406 663 809 1,460 1,690 2,680 3,053 5,480 6,230 11,000 12,600 80 140 189 333 393 643 768 1,410 1,630 2,590 2,961 5,300 6,040 10,600 12,200 100 124 169 298 350 578 703 1,260 1,450 2,330 2,662 4,740 5,410 9,530 10,900 150 101 137 245 287 477 575 1,020 1,180 1,910 2,195 3,860 4,430 7,810 8,890 200 86 118 213 248 415 501 880 1,020 1,660 1,915 3,340 3,840 6,780 7,710 250 77 105 191 222 373 448 785 910 1,490 1,722 2,980 3,440 6,080 6,900 300 69 96 173 203 343 411 716 829 1,360 1,578 2,720 3,150 5,560 6,300 400 60 82 151 175 298 355 616 716 1,160 1,376 2,350 2,730 4,830 5,460 500 53 72 135 158 268 319 550 638 1,030 1,237 2,100 2,450 4,330 4,880 2020 Florida Building Code, Fuel Gas, 7th Edition First Printing: Jul 2020 Copyright © ICC All Rights Reserved. Accessed by Energized Electric on 03/15/2021 pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Any Unauthorized reproduction or distribution is a violation of the federal copyright, and subject to civil and criminal penalties thereunder. For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895kPa, 1-inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.293 1 W, 1 cubic foot per hour = 0.0283 m /h, 1 degree = 0.01745 rad. Notes: 1.Table does not include effect of pressure drop across the line regulator. Where regulator loss exceeds / psi (based on 13 in. w.c. outlet pressure), DO NOT USE THIS TABLE. Consult with the regulator manufacturer for pressure drops and capacity factors. Pressure drops across a regulator may vary with flow rate. 2.CAUTION: Capacities shown in the table might exceed maximum capacity for a selected regulator. Consult with the regulator or tubing manufacturer for guidance. 3.Table includes losses for four 90-degree bends and two end fittings. Tubing runs with larger numbers of bends or fittings shall be increased by an equivalent length of tubing to the following equation: L = 1.3n where L is additional length (feet) of tubing and n is the number of additional fittings or bends. 4.EHD—Equivalent Hydraulic Diameter, which is a measure of the relative hydraulic efficiency between different tubing sizes. The greater the value of EHD, the greater the gas capacity of the tubing. 5.All table entries have been rounded to three significant digits. 3 1 2 2020 Florida Building Code, Fuel Gas, 7th Edition First Printing: Jul 2020 Copyright © ICC All Rights Reserved. Accessed by Energized Electric on 03/15/2021 pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Any Unauthorized reproduction or distribution is a violation of the federal copyright, and subject to civil and criminal penalties thereunder.