HomeMy WebLinkAboutApproved E0.AELECTRICAL NOTES THESE NOTES APPLY TO ENTIRE PROJECT: A. CODES. ALL ELECTRICAL WORK SHALL COMPLY WITH THE DRAWINGS AND SPECIFICATIONS, THE NATIONAL ELECTRICAL CODE AND APPLICABLE LOCAL CODES, WHICHEVER IS MORE STRINGENT. B. ENERGY CODE. LIGHT FIXTURES ARE TO COMPLY WITH THE FLORIDA ENERGY CODE. FULL COMPLIANCE WITH THE ENERGY CODE IS REQUIRED, WITH PROVISIONS FOR AUTOMATIC SHUT OFF OF LIGHTING. C. CONDUCTORS. ALL CONDUCTORS ARE TO BE COPPER THWN UNLESS OTHERWISE SHOWN OR REQUIRED BY CODES. ALL POWER CONDUITS ARE TO CONTAIN A GROUND WIRE. MC CABLE IS ALLOWED WITH COPPER GROUND WIRES. D. RACEWAYS. RIGID GALVANIZED CONDUIT AND ELECTRICAL METAL TUBING AND MC CABLE IS TO BE USED IN INTERIOR SPACES. E. HVAC. THE ELECTRICAL CONTRACTOR IS TO COORDINATE WITH THE HEATING, VENTILATING AND AIR CONDITIONING (HVAC) TRADE TO MAKE CERTAIN ALL POWER CIRCUITS, CONTROL CIRCUITS AND CONDUITS ARE INCLUDED IN THE BIDS. ALL HVAC EQUIPMENT IS TO BE PROTECTED WITH FUSES (DUAL ELEMENT) SIZED EXACTLY IN ACCORDANCE WITH THE EQUIPMENT LABELS. SPLIT SYSTEM AIR HANDLERS AND CONDENSING UNITS ARE TO BE CONNECTED WITH CONTROL CIRCUITS. DISCONNECTS ARE TO BE LOCATED WHERE REQUIRED BY THE HVAC CONTRACTOR. UNDER NO CONDITIONS WILL OWNER PAY ADDITIONAL CHARGES FOR HVAC ELECTRICAL WORK. F. SHOP DRAWINGS. SHOP DRAWINGS SHALL BE SUBMITTED TO ENGINEER FOR APPROVAL FOR ALL ELECTRICAL MATERIALS. G. POWER COMPANY. THE ELECTRICAL CONTRACTOR IS TO COORDINATE ALL SERVICE REQUIREMENTS WITH THE POWER COMPANY BEFORE BIDDING TO BE CERTAIN ALL WORK NECESSARY TO MEET POWER COMPANY SPECIFICATIONS IS IN THE BID. ALL ELECTRICAL GEAR SHALL BE APPROVED BY THE POWER COMPANY. THE ELECTRICAL CONTRACTOR SHALL MEET WITH THE POWER COMPANY PRIOR TO BIDDING TO DETERMINE ALL FEATURES, FUNCTIONS AND LOCATIONS OF SERVICE. FURTHERMORE, THE ELECTRICAL CONTRACTOR IS TO MAINTAIN CONTINUOUS CONTACT WITH THE POWER COMPANY DURING THE PROJECT, AND IS TO NOTIFY THE ENGINEER IMMEDIATELY OF ANY CHANGE PROPOSED. THE ELECTRICAL CONTRACTOR SHALL COORDINATE THE SERVICE THOROUGHLY AND DOCUMENT THE COORDINATION. H. TELEPHONE. THE ELECTRICAL CONTRACTOR IS TO ARRANGE FOR TELEPHONE SERVICE. PRIOR TO BIDDING, THE ELECTRICAL CONTRACTOR IS TO MEET WITH THE TELEPHONE COMPANY AND COORDINATE THE LOCATION OF THE SERVICE POINT ON THE PROPERTY LINE, THE INCOMING SERVICE CABLE, GROUNDING, ETC. IN ADDITION, THE ELECTRICAL CONTRACTOR IS TO INSTALL TELEPHONE CABLES (8#24 CATEGORY 6 CABLE) TO TELEPHONE OUTLET POINTS THROUGHOUT THE PROJECT. ALL CABLES ARE TO BE RADIAL -WITH INDIVIDUAL HOME RUNS TO TELEPHONE BACKBOARD OR TERMINAL. DO NOT LOOP FROM OUTLET TO OUTLET. I. DRAWINGS. THE ELECTRICAL CONTRACTOR IS TO OBTAIN A COMPLETE SET OF DRAWINGS AND SPECIFICATIONS PRIOR TO BIDDING, AND IS TO BECOME THOROUGHLY FAMILIAR WITH THE ARCHITECTURAL, CIVIL, STRUCTURAL, MECHANICAL, AND LANDSCAPING FEATURES OF THE PROJECT. PRIOR TO BIDDING, THE ELECTRICAL CONTRACTOR IS TO HAVE A COMPLETE UNDERSTANDING OF DEMOLITION REQUIREMENTS, CEILING CONFIGURATIONS, WIRING SPACES, FIRE RATED SURFACES, STRUCTURAL FEATURES, AIR CONDITIONING WORK, TEMPORARY POWER REQUIREMENTS, PIPING, PLUMBING AND ALL OTHER FEATURES WHICH BEAR ON THE ELECTRICAL WORK. UNDER NO CONDITION IS THIS PROJECT TO BE BID WITHOUT A COMPLETE SET OF DRAWINGS AND SPECIFICATIONS. J. SCALES. DO NOT SCALE OR TAKE DIMENSIONS FROM ELECTRICAL DRAWINGS. K. MAIN DISCONNECTS. MAIN DISCONNECTS MAY BE HEAVY DUTY FUSED SWITCHES OR CIRCUIT BREAKERS PROPERLY COORDINATED. FUSES ARE TO BE BUSSMAN TYPE LPN-R, LPS-R, OR KRP-C. CIRCUIT BREAKERS ARE TO BE RATED FOR THE AIC SHORT CIRCUITS INDICATED. L. UNDERGROUND WORK. THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR DETERMINING THE EXACT ROUTES OF ALL UNDERGROUND WORK. ROUTES SHOWN ARE APPROXIMATE. POWER, TELEPHONE, CABLE COMPANIES, AND ALL OTHER UTILITY COMPANIES SHALL BE CONSULTED, AND LINES SHALL BE STAKED. DIGGING BY HAND IS REQUIRED AROUND EXISTING UTILITIES. M. TVSS. THE POWER SERVICE IS TO BE PROTECTED FROM LIGHTNING WITH SURGE SUPPRESSORS THROUGH A 30A (2P/3P ) BREAKER (42,000AIC). SINGLE PHASE TO BE EATON TYPE CHSPULTRA. THREE PHASE TO BE EATON CPS-100-A. N. LED LIGHT FIXTURES. LED LIGHTS ARE TO BE CAPABLE OF DIMMING 0-100 WITH DRIVERS AND DIMMERS PROVIDED BY SAME MANUFACTURER. THE CONTRACTOR IS TO INSTALL MULTIPLE CONDUCTORS REQUIRED BY DRIVERS, AND IS TO FIELD MEASURE ALL LOCATIONS AND DIMENSIONS. ALL LENSES, ADJUSTABLE MOUNTING HARDWARE, POWER SUPPLIES, METALLIC HOUSINGS TO BE INCLUDED. 0. LIGHT FIXTURE VOLTAGES. OBTAIN LIGHT FIXTURE VOLTAGES FROM CIRCUITS ON PLANS. DO NOT OBTAIN FROM MODEL NUMBERS ON LIGHT FIXTURE SCHEDULE P. PARKING LOT LIGHTING. PARKING LOT LIGHTING IS TO MEET THE REQUIREMENTS OF THE ST. LUCIE COUNTY SECURITY CODE, AND AS FOLLOWS: LED SOURCES WITH MINIMUM 0.50 FOOT CANDLES, UNIFORMITY RATIO 12 TO 1, ONE (I) FOOT CANDLE ON WALK PATH. THE CONTRACTOR IS TO SUBMIT TO THE ENGINEER A COMPUTER GENERA TED PHOTOMETRIC ANALYSIS SHOWING THE ACTUAL PARKING LOT. IN ADDITION, THE CONTRACTOR IS TO FURNISH A FLORIDA P. E. STRUCTURAL ENGINEER CERTIFICATION FOR WIND SPEED, AND INSTALLATION. THE POLE SET (BELOW GRADE) IS TO BE DETERMINED BY THE STRUCTURAL ENGINEER. THESE REQUIREMENTS APPLY EVEN IF THE CONTRACTOR FURNISHES THE EXACT MAKE AND MODEL SPECIFIED. Q. RECEPTACLE HEIGHTS. COORDINATE WITH BUILDING DEPARTMENT THE MINIMUM HEIGHT FOR RECEPTACLES. AMERICAN DISABILITY ACT REQUIRES 18" ABOVE FINISHED FLOOR. R. EQUIPMENT DISCONNECTS. DISCONNECTS SHOWN CAN BE DELETED IF DISCONNECTING MEANS BUILT IN AND PERMITTED BY THE BUILDING DEPARTMENT. S. COMPLETION REQUIREMENTS. WITHIN 30 DAYS AFTER SYSTEM ACCEPTANCE, RECORD DRAWINGS OF THE ACTUAL INSTALLATION SHALL BE PROVIDED BY THE CONTRACTOR TO BUILDING OWNER WITH A SINGLE LINE DIAGRAM OF THE DISTRIBUTION SYSTEM PLUS FLOOR PLANS SHOWING LOCATIONS AND AREAS SERVED. T. OPERATING AND MAINTENANCE MANUALS. OPERATING AND MAINTENANCE MANUALS FOR EACH PIECE OF EQUIPMENT SHALL BE TURNED OVER BY THE CONTRACTOR TO OWNER WITH SUBMITTAL DATA AND REQUIRED MAINTENANCE PROCEDURES. THE NAME AND ADDRESS OF A QUALIFIED SERVICE AGENCY SHALL BE PROVIDED. U. SHARED NEUTRALS. WHENEVER THE CONTRACTOR USES SHARED NEUTRALS, BREAKERS ARE TO HAVE A COMMON HANDLE (I.E. 2 POLE OR 3 POLE). V. GFCI. OUTLETS INSTALLED OUTDOORS, WITHIN 6' OF A SINK, AND OTHERWISE REQUIRED BY CODE ARE TO BE ON GFCI TYPE CIRCUIT BREAKERS. ELECTRICAL SPECIFICATIONS GENERAL PROVISIONS. PROVIDE ALL LABOR, MATERIALS, TOOLS, SUPPLIES, EQUIPMENT AND TEMPORARY POWER FACILITIES TO COMPLETE THE WORK SHOWN ON THE DRAWINGS AND SPECIFICATIONS. ALL SYSTEMS ARE TO BE COMPLETELY OPERATIONAL. ALL ELECTRICAL WORK SHALL COMPLY WITH THE DRAWINGS AND SPECIFICATIONS, THE NATIONAL ELECTRICAL CODE AND APPLICABLE LOCAL CODES, WHICHEVER IS MOST STRINGENT. OPERATING CLEARANCES. INSTALL ALL WORK NEATLY SO AS TO BE PROPERLY ACCESSIBLE FOR OPERATION, MAINTENANCE AND REPAIR. JOB SITE VISIT. VISIT THE PROJECT SITE PRIOR TO SUBMITTING A BID. VERIFY ALL DIMENSIONS AND DETERMINE THE CHARACTERISTICS OF EXISTING FACILITIES WHICH WILL AFFECT THE PERFORMANCE OF THE WORK, INCLUDING THOSE NOT SHOWN ON DRAWINGS OR SPECIFICATIONS. SUBSTITUTIONS. ALL EQUIPMENT SUBSTITUTIONS MUST BE APPROVED IN WRITING BY THE ENGINEER PRIOR TO BIDDING. TEMPORARY LIGHT AND POWER. THE ELECTRICAL CONTRACTOR SHALL INCLUDE IN HIS BID THE COST OF FURNISHING, INSTALLING, MAINTAINING AND REMOVING ALL MATERIAL AND EQUIPMENT REQUIRED TO PROVIDE LIGHT AND POWER TO PERFORM ALL WORK OF ALL TRADES DURING CONSTRUCTION, AND UNTIL WORK IS COMPLETE. COST OF ALL POWER CONSUMED DURING CONSTRUCTION SHALL BE PAID BY THE PARTY DESIGNATED BY THE PRIME CONTRACTOR. MATERIAL SUBMITTALS. SUBMIT ELECTRONIC PDF SHOP DRAWINGS AND EQUIPMENT DESCRIPTIONS FOR ALL ELECTRICAL WORK PRIOR TO ORDERING. ELECTRICAL MATERIALS FOUND ON THE PROJECT WHICH DO NOT HAVE THE ENGINEER'S APPROVAL MUST BE REMOVED AND REPLACED AT THE ELECTRICAL CONTRACTOR'S EXPENSE. RENOVATIONS. THIS PROJECT INVOLVES RENOVATIONS TO AN EXISTING BUILDING. THE ELECTRICAL CONTRACTOR IS TO ASSIST IN DEMOLITIONS AS REQUIRED BY THE PRIME CONTRACTOR, RELOCATE EXISTING ITEMS OF ELECTRICAL WORK, REWORK CIRCUITS AND PERFORM ALL ELECTRICAL WORK NECESSARY TO FINISH THE JOB WITH THE FINAL CONFIGURATIONS SHOWN. TRENCHING, BORING AND BACKFILLING. EXCAVATION OR BORING, BACKFILLING AND REPAIRING OF PAVING AND GRASSING IS TO BE IN THE BID OF THE ELECTRICAL CONTRACTOR. THE ACTUAL WORK NEED NOT BE PERFORMED BY THE ELECTRICAL TRADES. HOWEVER, THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR ALL EXCAVATION, BORING, DEWATERING, BACKFILLING, TAMPING AND REPAIR OF PAVEMENTS AND GRASSING REQUIRED IN SUPPORT OF ELECTRICAL WORK. LOCATE AND PROTECT EXISTING UTILITIES AND OTHER UNDERGROUND WORK IN A MANNER WHICH WILL ENSURE THAT NO DAMAGE OR SERVICE INTERRUPTION WILL RESULT FROM EXCAVATING OR BACKFILLING. THE ELECTRICAL CONTRACTOR IS COMPLETELY RESPONSIBLE FOR ANY DAMAGE TO UTILITIES OR PROPERTY. PROTECT PROPERTY FROM DAMAGE WHICH MIGHT RESULT FROM EXCAVATING, BORING OR BACKFILLING. PROTECT PERSONS FROM INJURY AT EXCAVATIONS BY BARRICADES WITH WARNINGS AND ILLUMINATION. IN THE EVENT, IT IS SUSPECTED THAT ACTIVE ELECTRICAL LINES ARE BURIED IN THE AREA OF WORK, POWER IS TO BE DISCONNECTED. AN UNDERGROUND LOCATOR SERVICE SHALL BE EMPLOYED. TESTS. CONDUCT OPERATING TESTS FOR APPROVAL. THE SYSTEMS SHALL BE DEMONSTRATED TO OPERATE IN ACCORDANCE WITH THE REQUIREMENTS OF THESE SPECIFICATIONS AND MANUFACTURERS INSTRUCTIONS. TESTS SHALL BE PERFORMED IN THE PRESENCE OF THE ENGINEER OR AN AUTHORIZED REPRESENTATIVE. FURNISH ALL ITEMS REQUIRED TO PERFORM TESTS. DIVISION OF WORK. ALL POWER WIRING IS TO BE BY THE ELECTRICAL CONTRACTOR. THE ELECTRICAL CONTRACTOR SHALL COORDINATE THE INSTALLATION OF DISCONNECTS, STARTERS, THERMOSTATS, FIRESTATS, CONTROL TRANSFORMERS, SWITCHES, ETC. WITH THE OTHER CONTRACTORS TO MAKE CERTAIN NO ITEMS ARE LEFT OUT OF THE BIDS. THE PRIME CONTRACTOR SHALL MAKE ANY SPECIAL DECISIONS REGARDING THE DIVISION OF WORK BETWEEN CONTRACTORS. IN NO EVENT SHALL SUCH WORK REQUIRE ADDITIONAL EXPENSE TO THE OWNER. LOCATIONS. THE ENGINEER MAY MOVE ANY ELECTRICAL DEVICES BY AS MUCH AS TEN (10) FEET PRIOR TO ROUGH -IN AT NO ADDITIONAL COST. CIRCUITS. ALL OUTLETS, LIGHT FIXTURES AND OTHER ITEMS OF EQUIPMENT SHOWN ON DRAWINGS ARE TO BE CIRCUITED. BIDDING FROM A FULL SET OF DRAWINGS. THE ELECTRICAL CONTRACTOR IS TO OBTAIN A COMPLETE SET OF DRAWINGS AND SPECIFICATIONS PRIOR TO BIDDING, AND IS TO BECOME THOROUGHLY FAMILIAR WITH THE ARCHITECTURAL, CIVIL, STRUCTURAL, MECHANICAL AND LANDSCAPING FEATURES OF THE PROJECT. I PRIOR TO BIDDING, THE ELECTRICAL CONTRACTOR IS TO HAVE A COMPLETE UNDERSTANDING OF CEILING CONFIGURATIONS, WIRING SPACES, FIRE RATED SURFACES, FOUNDATIONS, AIR CONDITIONING DUCTWORK, SPRINKLER PIPING, PLUMBING AND ALL OTHER FEATURES WHICH BEAR ON THE ELECTRICAL WORK. UNDER NO CONDITIONS IS THIS PROJECT TO E BID WITHOUT A COMPLETE SET OF DRAWINGS AND SPECIFICATIONS. FIRE RATED SURFACES. FIRE WALL, CEILING AND FLOOR PENETRATIONS ARE TO BE MADE WITH METALLIC RACEWAYS IN A U.L. APPROVED MANNER. DO NOT KNOCK HOLES INTO VOID SPACES OR OTHERWISE DEGRADE FIRE WALLS. ALL PASSAGES INTO OR THROUGH FIRE WALLS ARE TO BE PERFORMED IN A MANNER ACCEPTABLE TO THE BUILDING DEPARTMENT. (NO PENETRATIONS ARE PERMITTED THROUGH FOUR (4) HOUR WALLS.) ONE (1) HOUR FIRE WALLS ARE TO BE PENETRATED IN EACH STUD CAVITY FROM ONLY ONE (1) SIDE IN A U.L. APPROVED MANNER. BASIC MATERIALS AND METHODS U.L. APPROVALS. ALL ELECTRICAL MATERIALS ARE TO BE APPROVED BY THE UNDERWRITER'S LABORATORIES. GALVANIC ACTION (CORROSION). GALVANIC ACTION (CORROSION) IS TO BE AVOIDED BY JOINING METALS WHICH ARE COMPATIBLE. FOR EXAMPLE, ALUMINUM CONDUITS ARE NOT TO MAKE CONTACT WITH BARE STEEL, GALVANIZED STEEL, OR BRASS. STAINLESS STEEL FITTINGS AND HARDWARE ARE REQUIRED OUTSIDE. ELECTRICAL SPECIFICATIONS GALVANIZED RIGID CONDUITS. RIGID STEEL CONDUIT 'GRC'AND FITTINGS ARE TO BE SCHEDULE 40 MILD STEEL PIPE, GALVANIZED. UNDERGROUND GRC CONDUITS ARE TO BE COATED WITH ASPHALT EMULSION TO RESIST CORROSION. ELECTRICAL METAL TUBING. TUBING 'EMT' SHALL BE STEEL TUBING, ZINC -COATED INSIDE AND OUTSIDE. FITTINGS SHALL BE ZINC -COATED. BENDS WHICH TURN UP OUT OF CONCRETE SHALL BE TREATED WITH ASPHALT EMULSION TO RESIST CORROSION. MC CABLES. MC CABLES ARE ALLOWED IN DRY LOCATIONS, INDOORS, WHERE GALVANICALLY COMPATIBLE. FULL SIZE COPPER GROUND WIRES ARE REQUIRED. PVC CONDUITS. NON-METALLIC CONDUITS SHALL BE POLYVINYL CHLORIDE (PVC), U. L. APPROVED FOR 90C, SCHEDULE 40 RIGID, EXCEPT SERVICES TO BE SCHEDULE 80. STRAIGHT RUNS ARE TO HAVE EXPANSION COUPLINGS EVERY 40 FEET. NON-METALLIC TUBING. ENT MAY NOT BE USED. RACEWAY LOCATIONS. LOCATION REQUIREMENTS SET FORTH BY THE BUILDING DEPARTMENT SHALL PREVAIL IF MORE STRINGENT. ALL CONDUITS SHALL BE GRC EXCEPT WHERE OTHERWISE SHOWN ON DRAWINGS, AND AS FOLLOWS: EMT MAY BE USED ONLY INDOORS, IN DRY LOCATIONS, OUT OF SOIL, WHERE NOT PHYSICALLY SUBJECT TO DAMAGE. FLEXIBLE CONDUIT SHALL BE USED ONLY IN SHORT LENGTHS FOR MAKING EQUIPMENT CONNECTIONS. PVC CONDUITS SHALL BE USED ONLY UNDERGROUND OR IN CONCRETE FLOORS. METALLIC RACEWAYS ARE REQUIRED IN CEILING SPACES WHICH SERVE AS RETURN AIR PLENUMS. CONDUITS SHALL NOT BE RUN ABOVE ROOFS. RACEWAY INSTALLATION. WHERE CONDUITS CROSS EXPANSION JOINTS, INSTALL OFFSET EXPANSION JOINTS OR SLIDING EXPANSION JOINTS WITH BONDING STRAPS AND CLAMPS. EXPOSED RUNS OF CONDUIT OR TUBING SHALL BE INSTALLED WITH RUNS PARALLEL OR PERPENDICULAR TO WALLS, STRUCTURAL MEMBERS OR INTERSECTIONS OF VERTICAL PLANES AND CEILINGS, WITH RIGHT ANGLE TURNS. CONDUITS IN STRUCTURAL SLABS SHALL BE PLACED BETWEEN THE UPPER AND LOWER LAYERS OF REINFORCING STEEL. CONDUIT RUNS SHALL ALWAYS BE CONCEALED EXCEPT WHERE INDICATED ON PLANS. ENT MUST ALWAYS BE CONCEALED. A PULL WIRE SHALL BE INSTALLED IN ALL EMPTY CONDUITS. CONDUITS SHALL BE SUPPORTED BY APPROVED PIPE STRAPS, SECURED BY MEANS OF TOGGLE BOLTS ON METAL SURFACES, AND WOOD SCREWS ON WOOD CONSTRUCTION. THE USE OF PERFORATED STRAP OR WIRES WILL NOT BE PERMITTED. UNDERGROUND CONDUITS NOT UNDER CONCRETE SLABS ARE TO BE BURIED AT LEAST TWO (2') FEET BELOW FINISHED GRADE FOR CIRCUITS RATED 600 VOLTS OR LESS. CABINETS. CABINETS FOR OUTDOOR SWITCHES, PANELBOARDS, BREAKERS, WIREWAYS, RECEPTACLES, FIRE ALARM EQUIPMENT, ETC., SHALL BE RATED WEATHERPROOF. STAINLESS STEEL IS PREFERRED. MAIN DISCONNECTS. UNLESS SPECIFICALLY SHOWN OTHERWISE, ALL MAIN DISCONNECTS ARE TO BE HEAVY DUTY FUSED SWITCHES. GENERAL DUTY SWITCHES SHALL BE REMOVED AND REPLACED AT THE ELECTRICAL CONTRACTOR'S EXPENSE. FUSES SHALL BE REJECTION TYPE, U.L. CLASS RK1, UNLESS SHOWN OTHERWISE. SHORT CIRCUIT DESIGN. THE DESIGN CALLS FOR A NUMBER OF SPECIAL CONDITIONS IN ORDER TO HANDLE THE SHORT CIRCUITS AVAILABLE THOROUGHOUT THE ELECTRICAL SYSTEM. UNDER NO CONDITIONS MAY THE ELECTRCIAL CONTRACTOR DEVIATE FROM THE DESIGN IN TYPES OF SWITCHES, FUSES, CONDUCTORS, BREAKERS OR AIC RATINGS OF INTERRUPTING DEVICES. WIRING DEVICES GENERAL. WIRING DEVICES SHALL BE RATED FOR CURRENT, VOLTAGE AND PHASES AS APPLICABLE FOR THE LOADS. WHERE BOXES ARE TO BE MOUNTED ON OPPOSITE SIDES OF A WALL, A MINIMUM SEPARATION OF TWELVE (12") INCHES SHALL BE MAINTAINED. NO THROUGH BOXES ARE PREMITTED. BOXES SHALL BE MOUNTED LEVEL AND PLUMB. SWITCHES ARE TO BE SILENT, 20A, 120V. RECEPTACLES. NEMA 5-20R RECEPTACLES SHALL BE STANDARD TYPES EXCEPT WHERE SPECIAL RECEPTACLES ARE SHOWN. SPECIAL RECEPTACLES ARE TO MATCH EQUIPMENT PLUGS AS COORDINATED BY THE ELECTRICAL CONTRACTOR. THE ELECTRICAL CONTRACTOR IS TO FURNISH AND INSTALL PLUGS AND CORDS ON WATER HEATERS, DISHWASHERS, DISPOSALS, CLOTHES WASHERS, DRYERS, ETC., UNLESS PROVIDED BY OTHER TRADES. COORDINATE PRIOR TO BIDDING. FACE PLATES. FACE PLATES ARE REQUIRED IN INTERIOR SPACES. COLORS ARE TO BE SELECTED BY THE ARCHITECT. OUTSIDE PLATES AND COVERS SHALL BE MOUNTED PLUMB, STRAIGHT, AND FIT FLUSH WITH FINISHED SURFACES WITHOUT THE USE OF SHIMS OR MATS. PLATES SHALL NOT SUPPORT WIRING DEVICES. COMMON GANGED PLATES ARE TO BE EMPLOYED WHEREVER TWO (2) OR MORE DEVICES ARE SHOWN ON THE DRAWINGS IN THE SAME LOCATIONS. PANELBOARDS. PANELBOARDS SHALL BE DEAD -FRONT, CIRCUIT BREAKER TYPE. DIRECTORIES SHALL BE COMPLETE AND TYPEWRITTEN. LOADCENTERS ARE NOT PERMITTED. MOLDED CASE CIRCUIT BREAKERS. BREAKERS SHALL BE THERMAL -MAGNETIC OPERATED, WITH SHORT CIRCUIT RATINGS IN SYMMETRICAL AMPERES EQUAL TO OR GREATER THAN THE AIC RATINGS SHOWN ON THE DRAWINGS. MOTOR PROTECTION. ALL MOTORS ON THIS PROJECT ARE TO BE FULLY PROTECTED IN ACCORDANCE WITH THE NEC. EVERY MOTOR IS TO BE PROTECTED FROM OVERCURRENTS BY THE INSTALLATION OF FUSED SWITCHES LOCATED IN SIGHT OF MOTORS. EACH AIR HANDLING UNIT IS TO BE FED WITH A FUSED SWITCH FOR THE HEATER, AND A SECOND FUSED SWITCH FOR THE MOTOR (MOTOR SWITCH MAY BE ELIMINATED IF THE AHU IS EQUIPPED WITH INTEGRAL PROTECTION COORDINATED PRIOR TO BIDDING). IN APPLICATIONS WITH MOTORS OVER ONE (1) HORSEPOWER, AND WHERE CONTROLS OTHER THAN MANUAL 'ON' AND 'OFF' ARE REQUIRED, MAGNETIC COIL OPERATORS ARE REQUIRED. THE CONTRACTOR IS RESPONSIBLE FOR PROPER VOLTAGES, ENCLOSURE TYPES AND START -STOP OR HAND -OFF -AUTO SWITCHES AS REQUIRED BY THE APPLICATION. OVERLOAD ELEMENTS ARE REQUIRED FOR EVERY LEG ABOVE GROUND. STARTERS SHALL BE ALLEN-BRADLEY OR SQUARE D. CONDUCTORS. CONDUCTORS SHALL BE RATED FOR 600 VOLTS. ALL CONDUCTORS ARE TO BE COPPER. INSULATION SHALL BE TYPE THWN, EXCEPT WHERE SHOWN OTHERWISE. EVERY RACEWAY IS TO HAVE A GROUND WIRE (EXCEPT SERVICE). ELECTRICAL SYMBOL LEGEND SYMBOL DESCRIPTION DUPLEX RECEPTACLE OUTLET NEMA 5-20R Qt DUPLEX RECEPTACLE OUTLET NEMA 5-20R SPLIT WIRED 00C DUPLEX RECEPTACLE OUTLET NEMA 5-20R OVER COUNTER Ouc DUPLEX RECEPTACLE OUTLET NEMA 5-20R UNDER COUNTER SPECIAL PURPOSE OUTLET MUST MATCH EQUIP. PLUG FLOOR OUTLET W/ BRASS PLATE & CARPET RING SPST SWITCH 3-WAY SWITCH 4-WAY SWITCH SPST SWITCH W/ PILOT LIGHT MOTOR RATED SWITCH DIMMER SWITCH WATTAGE AS NOTED 0 O t t t / LIGHT FIXTURE (SURFACE / RECESSED) LIGHT FIXTURE WALL MOUNTED FLUORESCENT LIGHT FIXTURE (SURFACE / RECESSED) FLUORESCENT LIGHT FIXTURE (SURFACE / RECESSED) EMERG. FLUORESCENT STRIP LIGHT FIXTURE EMERGENCY BATTERY PACK LIGHT FIXTURE W/ (2) 25W LTS. EXIT SIGN, UNIVERSAL MOUNTING (DOUBLE / SINGLE FACE) ARROWS AS INDICATED FUSED SWITCH,30A SWITCH, 20A FUSES,2 POLES MOTOR STARTER,NEMA SIZE 1 SWITCH/STARTER, 30A, NEMA 1, 3 POLE PANELBOARDS, SEE SCHEDULES 0/0 ®/® I----i tmf / 3= OP S2 ® N1 EEP f3 -^ ❑ TC TIME CLOCK SWITCH, 4P-ASTRONOMIC W/RESERVE N TELEPHONE RECEP-4x4 BOX WITH SINGLE GANG ADAPTER AND 3/4" EMT TO ACCESSIBLE CEILING SPACE DATA RECEP-4x4 BOX WITH SINGLE GANG ADAPTER AND 3/4" EMT TO ACCESSIBLE CEILING SPACE MOTOR _ STRIP HEATER W/ INTEGRAL CONTACTOR VOLUME CONTROL +44" QUADPLEX RECEP CLOCK +96" SEE RISER MANUAL PULL STATION AREA SMOKE DETECTOR HEAT DETECTOR SPRINKLER VALVE TAMPER SWITCH SPRINKLER WATER FLOW SWITCH b $� C) 0 0 ® i3s. T ® ® FIRE DOOR MAGNETIC HOLD OPEN 7F FIRE FIGHTER'S TELEPHONE OUTLET TS SECURITY GUARD WATCH TOUR STATION ® FIRE STROBE LIGHT WALL MOUNTED AT 80" A.F.F. F� FIRE ALARM SPEAKER/STROBE ®FA VOICE EVACTUATION SYSTEM SPEAKER JUNCTION BOX FIRE ALARM DEVICE ADDRESS TAG DUCT MOUNTED SMOKE DETECTOR REMOTE STATUS INDICATOR FIRE ALARM SYSTEM CONTROL RELAY BEAM TYPE SMOKE DETECTOR Q T1r E S — R <g>< MINIMUM CONDUCTOR SIZING FOR MINIMUM CONDUCTOR SIZING FOR 120V 1 0 BRANCH CIRCUITS 208V/30 BRANCH CIRCUITS (FOR FBC 13-413.BC.1.2 COMPLIANCE) (FOR FBC 13-413.13C.1.2 COMPLIANCE) DESIGN LOAD ON CIRCUIT IN VA DESIGN LOAD ON CIRCUIT IN VA (FROM PANELBOARD SCHEDULE) UP TO: (FROM PANELBOARD SCHEDULE) UP TO: 500 1000 1500 2000 2500 3000 1500 2000 2500 3000 3500 4000 4500 5000 50' 12 12 12 10 10 10 50' 12 12 12 12 1 12 12 1 12 12 o c a 100' 12 12 10 8 8 6 100' 12 12 12 12 12 12 12 12 150' 12 10 8 6 6 4 150' 12 12 12 12 12 10 10 10 a �s 200' 10 8 6 4 4 4 200' 12 12 12 10 10 10 10 8 ir- : iE z 250' 10 6 6 4 4 3 12 12 10 10 10 8 8 8 300' 8 6 4 2 12 10 10 10 8 8 8 8 4 3 MINIMUM CONDUCTOR SIZING FOR MINIMUM CONDUCTOR SIZING FOR 208V/1 0 BRANCH CIRCUITS 480V/30 BRANCH CIRCUITS (FOR FBC 13-413.BC.1.2 COMPLIANCE) (FOR FBC 13-413.BC.1.2 COMPLIANCE) DESIGN LOAD ON CIRCUIT IN VA DESIGN LOAD ON CIRCUIT IN VA (FROM PANELBOARD SCHEDULE) UP TO: (FROM PANELBOARD SCHEDULE) UP TO: 1000 1500 2000 2500 3000 3500 14000 4500 5000 10,000 15,000 20,000 25,000 30,000 50' 12 12 12 12 12 10 10 10 8 L) - o 0 100' 12 10 8 8 8 100' 12 12 12 12 10 10 10 10 8 150' 12 12 12 10 10 8 8 8 8 a� ao 200' 12 12 10 10 8 8 8 6 6 200 12 10 8 8 8 z � 250' 12 10 10 8 8 6 6 6 6 z 300' 12 10 8 8 6 300' 12 10 8 8 6 6 6 4 4 MINIMUM CONDUCTOR SIZING FOR 277V 1 0 BRANCH CIRCUITS (FOR FBC 13-413.BC.1.2 COMPLIANCE) DESIGN LOAD ON CIRCUIT IN VA (FROM PANELBOARD SCHEDULE) UP TO: 2000 3000 4000 5000 10 50' 1 12 12 1 12 o� 100' 12 12 12 10 a 150' 12 12 10 10 200' 12 10 10 8 z 250' 12 10 8 8 �j 300' 10 8 8 8 Know what's below. Call before you dig. CONDUCTOR SIZES SHOWN ON RISER DIAGRAM AND PANELBOARD SCHEDULES ARE MINIMUM REQUIREMENTS. IT IS THE CONTRACTOR'S RESPONSIBILITY TO PERFORM VOLTAGE DROP CALCULATIONS FOR ALL CONDUCTOR RUNS AND SIZE CONDUCTORS FOR A MAXIMUM 2% VOLTAGE DROP. • ALL CONTROL WIRING FOR VENTILATION SOLUTIONS (VS) EQUIPMENT IS TO BE PROVIDED AND INSTALLED BY ELECTRICAL CONTRACTOR. REFER TO VS DRAWINGS FOR CONTROL DEVICE LOCATIONS AND WIRING SPECIFICATIONS. FINAL CONNECTIONS AND PROGRAMMING IS BY VS. • ALL VFD3s ARE PROVIDED BY VS. AND INSTALLED BY ELECTRICAL CONTRACTOR (NOTE: RAU VFD's ARE UNIT MOUNTED, ALL OTHERS ARE IN THE ELECTRICAL ROOMS.) • ALL DISCONNECT SWITCHES FOR VS EQUIPMENT ARE PROVIDED AND INSTALLED BY ELECTRICAL CONTRACTOR. I— A OR AMP AC AF AFF AHJ AHU AT ATC,BMS,EMCS ATS AIC BRKR C or COND CB CD CKT CID CPT CT CU C.U. DC DISC OR DS DIV DN DPV DWG (E) or EXIST EC ELEV ELEC EMER EMIR EMT EP EPO EUH EWC EWH F FA FCA FCR FDR FLA FSS FT FTL FU FVNR FVR G , GND GFI GFP HZ HP IBC IG J OR JB KV KVA KW LCP ELECTRICAL ABBREVIATIONS - AMPERE - ALTERNATING CURRENT - AMP FRAME - ABOVE FINISHED FLOOR - AUTHORITY HAVING JURISDICTION - AIR HANDLING UNIT - AMP TRIP - HVAC CONTROLS - AUTOMATIC TRANSFER SWITCH - AMPS INTERRUPTING CAPACITY - BREAKER - CONDUIT - CIRCUIT BREAKER - CANDELA - CIRCUIT - CONTROL PANEL - CONTROL POWER TRANSFORMER - CURRENT TRANSFORMER - COPPER - CONDENSING UNIT - DIRECT CURRENT - DISCONNECT - DIVISION - DOWN - DRY PIPE VALVE CABINET - DRAWING - EXISTING - ELECTRICAL CONTRACTOR - ELEVATOR - ELECTRICAL - EMERGENCY - ELEVATOR MACHINE ROOM - ELECTRIC METALLIC TUBING - EXPLOSION PROOF - EMERGENCY POWER OFF - ELECTRIC UNIT HEATER - ELECTRIC WATER COOLER - ELECTRICAL WATER HEATER - FUSE - FIRE ALARM - FAULT CURRENT AVAILABLE - FAULT CURRENT RATING - FEEDER - FULL LOADS AMPS - FUSED SAFETY SWITCH - FEET - FEED THRU LUGS - FUSE - FULL VOLTAGE NON REVERSING - FULL VOLTAGE REVERSING - GROUND - GROUND FAULT INTERRUPT - GROUND FAULT PROTECTION - HERTZ - HORSEPOWER - INTERNATIONAL BUILDING CODE - ISOLATED GROUND - JUNCTION BOX - KILOVOLT - KILOVOLT -AMPERE - KILOWATT - LOCAL CONTROL PANEL LP - LIGHTING PANEL LSC - LOCAL CONTROL STATION LTG - LIGHTING M - METER MC - MOTOR CONTROL MCA - MINIMUM CIRCUIT AMPACITY MCB - MAIN CIRCUIT BREAKER MCC - MOTOR CONTROL CENTER MCP - MOTOR CIRCUIT PROTECTION MDS - MAIN DISTRIBUTION SWITCHBOARD MFR - MANUFACTURER +, MH - MOUNTING HEIGHT MI - MINERAL INSULATED MLO - MAIN LUGS ONLY MOM - MOMENT MOP - MAXIMUM OVERCURRENT PROTECTION MS - MOTOR STARTER MSB - MAIN SWITCHBOARD N - NEW NA - NOT APPLICABLE NC - NORMALLY CLOSED NEC - NATIONAL ELECTRICAL CODE NEMA - NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION NF - NON -FUSED NFPA - NATIONAL FIRE PROTECTION ASSOCIATION NFSS - NON -FUSED SAFETY SWITCH NIC - NOT IN CONTRACT NO - NORMALLY OPEN OCPD - OVERCURRENT PROTECTION DEVICE P - POLE PH OR 0 - PHASE NEMA - NATIONAL ELECTRIC MANUFACTURERS ASSOCIATION PB - PULL BOX PC - PHOTOCELL PMT - PAD MOUNTED TRANSFORMER PNL - PANELBOARD PLC - PROGRAMMABLE LOGIC CONTROLLER PT - POTENTIAL TRANSFORMER RCPT OR RECEPT - RECEPTACLE RM - ROOM RVSS - REDUCED VOLTAGE SOLID STATE (MOTOR STARTER) SCHD - SCHEDULE SPD - SURGE PROTECTIVE DEVICES SWBD - SWITCHBOARD TBD - TO BE DETERMINED THD - TOTAL HARMONIC DISTORTION TTB - TELEPHONE TERMINAL BOARD TVSS - TRANSIENT VOLTAGE SURGE SUPPRESSION TYP - TYPICAL UL - UNDERWRITERS LABORATORIES UNO - UNLESS NOTED OTHERWISE UPS - UNINTERRUPTIBLE POWER SUPPLY V - VOLT VFD - VARIABLE FREQUENCY DRIVE W - WIRE W/ - WITH WP - WEATHERPROOF/WATERPROOF XFMR - TRANSFORMER 1-PH - SINGLE PHASE 3-PH - THREE PHASE APPLI CAB L11. BUILDING CODES FLORIDA BUILDING CODE, 6TH EDITION (2017) NFPA 70, NATIONAL ELECTRICAL CODE (2014) FLORIDA FIRE PREVENTION CODE, 6TH EDITION (2017) FLORIDA ENERGY CONSERVATION CODE, 6TH EDITION (2017) FATERIALS AND WORKMANSHIP SHALL COMPLY WITH ALL APPLICABLE CODES AND ORDINANCES IN THEIR LATEST REVISIONS. CONTRACTOR TO COORDINATE SPECIFIC REQUIREMENTS OF EQUIPMENT WITH MANUFACTURERS' SHOP DRAWINGS. ALL EQUIPMENT SHALL BE INSTALLED STRICTLY IN ACCORDANCE WITH THE MANUFACTURERS WRITTEN INSTALLATION INSTRUCTIONS. SHT NO. EO.A E1.1 E2.5 E2.7 SCOPE OF WORK ELECTRICAL SHEET INDEX DESCRIPTION GENERAL NOTES, SPECIFICATIONS, LEGENDS, INDEX PARTIAL SITE PLAN ELECTRICAL - PARTIAL FIRST FLOOR PLAN J0 ELECTRICAL - FIRST FLOOR ELECTRICAL ROOM PLAN La Project: FUR5UIT DOAT5 New Ma- rufacturirg Facility 3901 St Lucie Blvd. Ft Fierce FL 34946 Key Plan: I00Ue5: No.: Date: Description: A. 08/30/21 OWNER 155 U E B. 09/21/21 OWNER REV15ION5 C. 11/01/21 OWNER REVISIONS D. 11/04/21 WALL TYPES UPDATED E. 11/15/21 FOUNDATION PERMIT Architect: DONADIO & Associates, Architects P.A. 2001 9th Avenue, Suite 308 Vero Beach, FL 32960 Te1.772.794.2929 Fax.772.562.8600 License No. AA0002238 www. d o n a d i o -a rch.00 m Consultant: Ca CARDinRL EmmnEERIf1G FISSOCIFITES inn. 575 NVV MERCANTILE PLACE SUITE 206 PORT ST. LUCIE FL 34986 T.561.746.6343 F.561.746.3602 info@CEAengineers.com PE# 78477 CA LIC. 31555 \\ \\QN1111iL iAuuM,/ Digitally signed ��� p h L by Joseph L ���° c, cEN Lammers m e r5 Date: 2021.1 1.1 0 17:04:00-05'00� No, 78477 STATE ❑F c�c '4Z OR _1 P 0u1lllll�In n1t\\\\\\\\\\ Drawing Title: ELECTRICAL - GENEKAL NOTES, 5FECIFICATION5, LEGENDS & INDEX Drn: Dwg. File: NL Chd: XREF File: DJL/JLL Project No.: Plot File: 2021-26 Sheet No.: Cert. No.: 12,456 Date Signed: E O' A Copyright ©2021, Ponadio & Associates, Architects, P.A.