HomeMy WebLinkAboutA1.11 R3 CODE REVIEWproject: CODE REVIEW FOR CONVERTING THE EXISTING CHIQUITA CITRUS PACKING BUILDING, LOCATED AT 5701 ENVIRONMENTAL DRIVE, FT. PIERCE INTO CONTENDER BOATS, BOAT MANUFACTURERS ARCHITECTS PROJECT #2020-33/2 AUGUST 3, 2021 The existing Pre -Engineered Metal Building is approximately 103,480 sq. ft. in area and was constructed in 1986. The Eaves height is 27'-0" with a Ridge height of 34'-0" Originally the Building was used for Citrus Packing and was divided into a Fruit processing area, Fruit coloring area. Warehouse space, Office, Cannery, Maintenance area and Toilet Rooms. The proposed new use will be Boat Building/Assembly which will include Cutting Booths, Spray Booths, Lamination area. Assembly area, Test Pool area, Stockroom, Office, Toilet Rooms and a partial 4,461 sq. ft. second floor constructed over the existing Stock Room area. This area will be used as a Stock Room / Upholstery area to fabricate seats destined for new boats. There is an exiting Automatic Fire Sprinkler System in the Building which will be modified as necessary to suit the purposed new use. The existing Construction appears to be non-combustible, Type 11-B (Sprinklered). By definition, this Project does not involve a Change of Occupancy but does involve a Change of Use. CODE REFERENCES Florida Building Code 2020 - Building Florida Building Code 2020 - Existing Buildings Florida Building Code 2020 - Accessibility Florida Building Code 2020 - Plumbing Florida Fire Prevention Code 7"1 Edition CODE REVIEW 1) CERTIFICATE OF OCCUPANCY: FBC 1001.2 Since this Project involves a Change of Use, an approved Certificate of Occupancy will be required from the Building Department. i) Change of Use FBC 1001.2.1 See Item 1) above ii) Change of Occupancy Classification or Group FBC 1001.2.2 N/A iii) Certificate of Occupancy Required FBC 1001.3 See Item 1) above. 2) SPECIAL USE AND OCCUPANCY FBC 1002 NIA 3) BUILDING ELEMENTS AND MATERIALS FBC 1003 See FBC Section 1012. 4) FIRE PROTECTION FBC 1004; FBC 1012; FBC 2020-BUILDING; CH.9; LSC 40.3.5 (Reserved) The existing Building = 103.480 sq. ft. New Second Floor Addition = 4.461 sq. ft TOTAL AREA = 107,941 sq.ft. 107,941 sq.ft. > 12,000 sq.ft. The Building is equipped with an existing Automatic Fire Sprinkler System. 5) MEANS OF EGRESS FBC 1005; FBC 1012; FBC 2020-BUILDING; FBC CH.10; LSC 40.2.2 See FBC Section 1012. 6) ACCESSIBILITY FBC 1006; FBC 2020-BUILDING; FBC 2020-ACCESSIBLITY All work in connection with this Section will comply with the appropriate Sections of FBC 2017, Accessibility. 7) STRUCTURAL FBC 1007 Any and all new Structural design will be based on the requirements of FBC 2020-Building Table 1607.1. 8) SNOW AND WIND LOADS FBC 1007.2 If as a result of Change of Use, the Wind Load requirement change, the Building will be analyzed to comply with the applicable Wind Load requirement of FBC 2020-Building. 9) SEISMIC LOADS FBC 1007.3 N/A 10) COMPLIANCE WITH INTERNATIONAL BUILDING CODE LEVEL SEISMIC FORCES FBC 1007.3.1 N/A 11) ACCESS RISK TO LEVEL IV FBC 1007.3.2 N/A 12) ELECTRICAL FBC 1008; 1008.1; 1008.2; 1008.3 AND 1008.4 The existing Occupancy Classification and proposed new Occupancy is Group "F" (F-1). No Change of Occupancy. All existing and new Electrical wiring and equipment to comply with NFPA 70. All unsafe conditions to be corrected, if a new Electrical service is required or the number of Electrical outlets has to be increased, all existing/new work to comply with NFPA 70. 13) MECHANICAL FBC 1009 The existing Mechanical system is to be removed and replaced with a new HVAC system meeting the requirements of the Florida Building Code -Mechanical 2020. 14) PLUMBING If the Change of Use warrants additional Plumbing fixtures or Water supply the new Occupancy shall comply with the provisions of FBC 2020-Plumbing. 15) OTHER REQUIREMENTS FBC 1011; 1011.1 The Light and Ventilation requirements for the Change of Use to comply with FBC 2020-Building. 16) CHANGE OF OCCUPANCY CLASSIFICATION FBC 1012 This Project involves a Change of Use Classification. i) Current Occupancy Classification Group "F": F-1: Sprinklered ii) Proposed Occupancy Classification Group -F": F-1: Sprinklered iii) Proposed Change of Use Currently: Fruit Packing Proposed: Boat Building 17) CHANGE OF OCCUPANCY CLASSIFICATION WITHOUT SEPARATION FBC 1012.1.1.1; FBC 2020 - BUILDING; FBC 508.2 Existing Administration Area is less than 10% of the Total Building Floor Area and is considered Accessory Use; Non -separated. l 18) CHANGE OF OCCUPANCY CLASSIFICATION WITH SEPARATION FBC 1012.1.1.2 N/A 19) FIRE PROTECTION AND INTERIOR FINISH FBC 1012.1.2; LSC 40.3.5; 40.3.3 See Items 1012.2 and 1012.3 below. 20) CHANGE OF OCCUPANCY CLASSIFICATION BASED ON HAZARD CATEGORY FBC 1012.1.3 N/A 21) ACCESSIBILITY FBC 1012.1.4 See Item 1012.8 below. 22) FIRE PROTECTION SYSTEMS FBC 1012.2 i) Fire Protection Systems FBC 1012.2.1; FBC 2020; CH.9-Fire Protection Systems; LSC 40.3.5 The Building is equipped with an existing Fire Sprinkler System. ii) Fire Alarm and Detection System FBC 1012.2.2; LSC 40.3.4 The Fire area is 107,942 sq. ft. > 12,000 sq. ft. The existing Building is protected with an Automatic Fire Sprinkler System and the Occupant notifications appliances will be activated throughout the Building upon Sprinkler water flow. iii) Initiation LSC 40.3.4.2 Initiation of the required Fire Alarm System to be either by manual means or by activation of the approved Fire Detection System. 23) INTERIOR FINISH FBC 1012.3; FBC 2020-Building; CH. 8; Table 803.11; LSC 40.3.3 All new wall and ceiling finishes to comply with the following: OCCUPANCY CLASSIFICATION F-1; SPRINKLERED INTERIOR EXIT CORRIDOR & ENCLOSURES FOR STAIRWAYS RAMPS AND EXIT ACCESS STAIRWAYS AND ROOMS AND ENCLOSED SPACES EXIT PASSAGEWAYS RAMP C C C CLASS C - Flame Spread Index: 76-200 Smoke Developed Index: 0-450 1) Interior Floor Finish FBC 1012.3; FBC 2020-Building; FBC 804.4.2; LSC 10.2.7.4; 40.3.3.3 The minimum Critical Flux for all Floor finishes will be Class 11. 24) MEANS OF EGRESS, GENERAL FBC 1012.4; TABLE 1012.4; FBC 2020-BUILDING; CH. 10; LSC 40.2 Hazard Categories Previous (F-1) = 4 Proposed (F-1) = 4 No Change of Occupancy Classification. 25) MEANS OF EGRESS FOR CHANGE TO A HIGHER HAZARD CATEGORY FBC 1012.4.1; FBC 2020-BUILDING; CH.10 N/A. 26) MEANS OF EGRESS FOR A CHANGE OF USE TO EQUAL OR LOWER HAZARD CATEGORY FBC 1012.4.2 N/A 27) EGRESS CAPACITY FBC 1012.4.3; FBC 2020-BUILDING; FBC 1005.3.1; LSC CH.7 i) Occupant Load: First Floor: 103,480 - 100 = 1,035 Occupants Occupant Load: Second Floor: 4,461 - 100 = 45 Occupants Total Occupant Load = 1,080 Occupants ii) Egress capacity Required: First Floor: 1,035 x 0.2" = 207" Egress Capacity Provided: First Floor: 11 x 36" = 396" iii) Egress Capacity Required: Second Floor: 45 x 0.2" = 9" Egress Capacity Provided: Second Floor: 2 x 36" = 72" The Occupant Load from the second floor will be 45 < 49. A single exit is permitted and two (2) are provided. 28) HANDRAILS FBC 1012.4.4; 805.9; FBC 2020-BUILDING; FBC 1011.11; FBC 1014; LSC 7.2.2 Existing & New Handrails: All Handrails to be mounted 34" / 38" above stair treads. 29) GUARDS FBC 1012.4.5; FBC 805.11; FBC 2020-Building; FBC 1015; FBC 1015.3; LSC 7.1.8 Existing and New Guard Rails: All Guard Rails to be mounted not less than 42" above adjacent floor surface. 0 30) HEIGHTS AND AREAS FBC 1012.5 Previous relative Hazard = 3 Proposed relative Hazard = 3 31) HEIGHTS AND AREA FOR CHANGE TO A HIGHER HAZARD CATEGORY FBC 1012.5.1; FBC 2020-BUILDING; FBC TABLE 506.2 N/A 32) HEIGHT AND AREA FOR CHANGE OF USE TO EQUAL OR LESSOR HAZARD CATEGORY FBC 1012.5.2 Floor area deemed acceptable. 33) EXTERIOR WALL FIRE -RESISTANCE RATINGS FBC 1012.6; FBC TABLE 1012.6 The Relative Hazard for the F-1 Occupancy (existing & proposed use) = 2 No change required to the existing Exterior Walls. 34) OPENING PROTECTIVES FBC 1012.6.3 (EX. #3) The Building is protected by an existing Automatic Fire Sprinkler System therefore exterior Opening Protectives are not required. 35) ENCLOSURE OF VERTICAL SHAFTS FBC 1012.7; 1012.7.1; LSC 7.2.2; 40.2.2.3 i) Stairways FBC 1012.7.2; FBC 2020-Building CHA0; FBC 1011 There will be two (2) new staircases up to the second floor Stock Room. One is an exterior stair the other interior. Both will be non-combustible material. i.e. metal. ii) Other Vertical Shafts FBC 1012.7.3 N/A 36) ACCESSIBILITY FBC 1012.8; FBC 2020-ACCESSIBILITY i) Accessible Routes FBC 206 An Accessible Route exists from the Accessible Parking to the Building Entrance. ii) Accessible Means of Egress FBC 207 The Main Entrance into the Office area is accessible. iii) Parking Spaces FBC 208; FBC TABLE 208.2 There are currently three (3) Handicapped parking spaces indicated on the Site Plan and 167 total Parking spaces. For 101 to 150 Vehicles Table 208.2 indicates that six (6) Accessible Parking spaces are required. iv) Drinking Fountains FBC 211; FBC 602.1 /602.6 See Plumbing Fixture Schedule. v) Kitchens, Kitchenettes and Sinks FBC 212; FBC 804 vi) Toilet Facilities and Bathing Facilities FBC 212; FBC 603 See Plumbing Fixture Schedule. 37) ENERGY CONSERVATION FBC 1013 The new HVAC System will be designed based on the requirements of the Florida Building Code 2020-Energy Conservation. 38) MINIMUM PLUMBING FIXTURE CALCULATIONS FBC 2020-Plumbing; FBC TABLE 403.1 Occupancy Group F-1 Florida Plumbing Code, Section 403.1.1, Exception. For justification of not meeting the Minimum Plumbing Fixture Requirement, as shown in the Table above, see attached Letter from Contender Boats, per 403.1.1, justifying the redistribution of the sexes and maximum 200-person occupancy load for this Facility. based on statistical data from their existing Boat Manufacturing Plant in Miami. Total Number of Occupants First Floor; 103,480 sq. ft. _ 100 = 1,035 Occupants " The Boat Manufacturing Plant will have a maximum employee count of 200 people and redistribution of the sexes for 100 men and 100 women. Assuming 50% Male/Female ratio: 200 - 2 = 100 each Sex. ii) Minimum Number of Required Fixtures FBC 403.1 Water Closets: 1 per 100 Male/Female Lavatories; Male/Female 1 per 100 Drinking Fountains: 1 per 400 Service Sink; 1 0 MINIMUM PLUMBING FIXTURE COUNT WATER CLOSETS LAVATORIES DRINKING FOUNTAINS SERVICE SINKS Required Provided' Required Provided' Required Provided Required Provided' Male 1 3 3 Unnals 1 5 1 2 1 1 Female 1 5 1 6 L"MinimumPlumbing Fixture Requirements noted for reference only ZL 0 KE N OVATI 0 N r 0K CONTENDEK I30AT5 5701 ENVIRONMENTAL DRIVE 5T. LUCIE COUNTY, FLORIDA Key Man 55Ue5: No.: Date: Description: A. 12/08/20 CLIENT REVIEW B. 05/25/21 FINAL REVIEW C. 06/23/21 PERMIT SET D. 8/04/21 PERMIT RE5FON5E E. 10/15/21 PERMIT RESPONSE 2 F. 12/17/21 FERMIT K 5FON13E 3 DONADIO & Associates, Architects P.A. 2001 9th Avenue, Suite 308 Vero Beach, FL 32960 Te1.772.794.2929 Fax.772.562.8600 www.donadio-arch.com License No. AAOW2238 CorS%Itart: Drawing Title: CODE KEVIEW Reference North Y�'Z'•_ Ai10a/1Ki Drr: Drawing File: � JLH Chd: XREF File: :s AJD tProject No.: Plot File: 2020-33 Sheet No.: Date Al .11 Copyright © 2020, Donadio & Associates, Architects, P.A., All Rights Reserved