HomeMy WebLinkAboutProduct Approval ( Siding )SCIS Home I Log In I User Registration I Hot Topics I Submit Surcharge I Stats & Fads I Pul
Contact Us I SCIS Site Map I
Product Approval
1 USER: Public User
Product Approval Menu > Product or Application Search > Application Us[ > Application Detail
FL 3
Appllcatlon Type
Code Version
Applicatlon Status
Comments
Archived
Product Manufacturer
Addtess/Phone/Emall
Authorlud Signature
Technical Representative
Address/Phone/Emall
Quality Assurance Representative
Address/Phone/Emall
Category
Subcategory
Compliance Method
Florida Englneer or Architect Name who developed the Evaluation Report
Florida Ucense
Quality Assurance Entity
Quality Assurance Contract Expiration Date
Validated By
Certificate of Independence
Referenced Standard and Year (of Standard)
Equlvalence of Product Standards
Certified By
Sections from the Code
Product Approval Method
Date Submitted
Date Validated
Date Pending FBC Approval
Date Approved
FL27502-R1
Revision
2020
Approved
Elite Structures Inc.
Elite Structures Inc
po box 207
Adel, GA 31620
(229)896-7569
Janasht@elite-structures.com
Jason Nash
Janash@elite-structures.com
Panel Wails
Siding
Evaluation Report from a Florida Registered Architect or a Ucensed Florida Professional Engineer
r, Evaluation Report - Hardcopy Recelved
Lucas A. TUmer
PE-58201
Intertek Testing Services NA, Inc. - QA Entity
12/31/2023
Scott Walters, PE
Validation Cheddist - Hardcopy Received
EL27502Ji1 MI FvalRepgrt-IltcEBRYValLpdt
Standard
ASTM E1592
Yeat
2012
Method 1 Option D
02/09/2021
02/12/2021
02/22/2021
04/13/2021
FL* Model, Number or Name Description
27502.1 26 Ga. PBR Wall Panel 26 Ga. Non -Structural PER Wall Panel
Llmitp of Use Installation InstruWons
Approved for use In XVNL• No FL27502 R3 II Etlte-PBR.os
Approved for use outside NVHZ. Yes Verified By: Lucas A. Turner PE R58201
Impact Resistant- No Created by Independent Third Party: Yes
Design Pressure[ N/A Evaluation Reports
other: Please see evaluation report and Installation Instructions for additional details FL27502 RI AE Evaliteport-Elite-PBR-Wall.pdf
Back NSxL
v`
cantact-us:: 26DLBIaItSf<re nnad.Tallahassee-EI.32349P1ume: 8Sn487-1a29
The State of Florida Is an AA/EEO employer. Ca :: Edxacv�:_r•renumt :: Accesslbillt S tement :: Re(und.5tatement
Under Florida law, emall addresses are public records. If you do not want your e-mall address released In response to a public -records request, do not send electronic mail to this entity. Instead, contact the office by phone or by traditional mall. If you have any questions, please contact
850.487.1395. *Pursuant to Section 455.275(1), Florida Statutes, effective October 1, 2012, licensees licensed under Chapter 455, F.S. must provide the Department with an email address If they have one. The emalls provided may be used for official communication with the licensee. However
email addresses are public record. If you do not wish to supply a personal address, please provide the Department with an mall address which can be made available to the public. To determine 8 you are a licensee under Chapter 455, F.S., please dick hem.
Product Approval Accepts:
®®®E4E
Credit Card
Safe
URNER
ENGINEERING &
CONSULTING. INC.
2428 Old Natchez Trace Trail
Camden, TN 38320
Ph. 941-380-1574
FBPE C.O.A. #29779
Evaluation Report — Elite PBR Wall
February 9, 2021
Product Description: PBR 26-Ga. 80ksi Steel Through -Fastened Non -Structural Wall Panel with
AZ55 Galvalume Coating, Applied Over Purlins/Girts
Manufacturer: Elite Structures Inc., 401 Old Quitman Rd., Adel, GA 31620
Statement of Compliance: This report evaluates the above -listed product per the requirements of
FAC Product Approval Rule Chapter 61G20-3.005 (4). This product complies with the requirements
of the 71h Edition (2020) Florida Building Code generally and section 1403.3 specifically, for use
outside the High Velocity Hurricane Zone. The product testing standards performed are outlined
below.
Technical Documentation:
1) This report, prepared by Lucas A. Turner, P.E., at 2428 Old Natchez Trace Trl, Camden, TN
2) Approval drawing Elite-PBR, signed and sealed by Lucas A. Turner, RE
3) Test Report I1936.04-55044, from Intertek / Architectural Testing; Lithia Springs, GA
a. Testing Performed: ASTM E1592-05(12)
4) Supplemental Calcs. to support Elite-PBR, signed and sealed by Lucas A. Turner, P.E.
Installation: Units must be installed according to approval document Elite-PBR, with 7"-5"-7"
pattern at panel ends and 12" o.c. across panel width into 16 Ga. 50ksi steel min. purlin/girt supports,
by others. Structural supports and sheathing shall be designed by others to resist the applied loads.
Through -panel fasteners into 16 Ga. steel supports shall be #12x1-1/4" Steelbinder drill point tip with
integral EPDM gasket or approved equivalent. Overlap ribs shall be joined with #140/8"
Steelbinder drill point tip with integral EPDM gasket or approved equivalent at 20" o.c. lengthwise.
Limitations of Use: This product:
• May be used up to 36" panel widths as indicated in Elite-PBR
• Was structurally tested to -120 psf load; with factor of safety and panel/anchor analysis this
results in an allowable Design Pressure of -60 psf at 48" support spacing
• Is non -impact and may only be used over Approved walls in windbome debris regions
• Was not tested for water infiltration resistance; weatherproofing of wall assembly is by others
• May not be used in the High Velocity Hurricane Zone
Certification of Independence: I do not have, nor do I intend to acquire, nor will I acquire, a
financial interest in Elite Structures Inc. or in any company manufacturing or distributing products
for which this report is being issued. I do not have, nor do I intend to acquire, nor will I acquire, a
financial interest in any other entity involved in the testing or approval process of this product.
ZZ
.o No. 58209
A * 2/9/2021
t
%�4° STATE OF •�►�� Lucas A. Turner P.E.
i71�pOAT4,0 p!N,.,� `��� FL PE #58201
In A l ltI�
PBR 26 GA, 80KSI STEEL NON-STRUCTURAL OVER 16 GA. 50 KSI MIN, PURLINS/GIRTS
SCREW -DOWN PANEL FASTENER SPACING @ INTERMEDIATE SUPPORTS
3'-0'
12-14 x 1 1/4 STEELBINDER
DRILLER W/WASHER OR
APPROVED EQUIVALENT
:n
M
SCREW -DOWN PANEL FASTENER SPACING @ PANEL ENDS
3'-0'
12-14 x l 1/4 STEELBINDER
DRILLER W/WASHER OR
APPROVED EQUIVALENT
#14-14 x 7/8' STEELBINDER
DRILLER W/WASHER OR
APPROVED EQUIVALENT
AT 20' MAX. O.C.
1/2' X 3/32' TAPE SEALER
PIGTAIL TO ENDLAP
SIDELAP
1/2' X 3/32' TAPE SEALER
CONTINUOUS AT ENDLAP