A. T. DESIGNS, INC.
CIVIL/STRUCTURAL ENGINEERING AND PROJECT MANAGEMENT SERVICES
Board of Directors January 11, 2022
c/o ATLANTIS ONE CONDOMINIUM
ASSOCIATION, INC.
10102 South Ocean Drive ^��D1 — 3-15
Jensen Beach, Florida 34957
FILE n h
Re: Emergency Corner Balcony Shoring
01 and 10 Cantilevered Balconies REVIEWED FOR
Atlantis One Condominium CODE COMPLIANCE
T. LUCIE COUNTY BOCC
Dear Board Members: ,j.a� Vc'� b-OA
While conducting our investigation and evaluation of the individual walkways and
individual unit balconies, it has become apparent that the 01 and 10 stack cantilevered balcony
slabs has sustained significant long-term deterioration, which has resulted in the excess
sagging (deflection) of the said balcony slabs. The degree and/or severity of the slab deflection
varies from floor to floor, but the observed conditions raise real concerns about the structural
integrity of the horizontal structural elements. In addition, severity of degradation of the
perimeter aluminum picket railings also is of concern.
Based on our evaluation, we therefore are recommending that all of the 01 and 10 unit
corner cantilevered balconies be immediately shored to address the observed deflection
conditions. The placement and anchorage of the 5K (min.) post shores around the perimeter of
the balconies, in accordance with the included drawing, is imperative to provide support for the
existing slabs, preventing any further deflection. The anchored post shores can also provide
additional lateral support for the existing perimeter balcony railings, further securing the
balconies. The post shores will most likely remain in place until the initiation of the pending
concrete restoration and remediation project.
I have been asked to arrange for a contractor to initiate the immediate implementation
and placement of the shoring of the 01 and 10 stack balcony slabs and also to secure the
identified loose railings. I have previously worked with DMF Construction, Inc. who is presently
working down the street from the Condominium, and fortunately is available to start with the
placement of the post shores by midday tomorrow. During the placement of the shoring and
securing of the railings, access to the corner stack balconies will be restricted to only the
workers. Once all the shoring has been installed, secured and inspected, along with the
perimeter railings, the residents will most likely be able to occupy or use the balconies.
111111110/��I
%�`, �,1?I aq t my office should there be any further questions.
O
*ems G'E lY� S; �ii�
,pe ull s 'tt '
A. . D
® � r
; 1Qtl�r a all''
cc ``slr4ilil��eal�Io��
300 PROSPERITY FARMS ROAD,SUITE G•NORTH PALM BEACH,FLORIDA 33408
(561)881-7280•FAX(561)BB1-0201 -Email:atd@atdesigns.net
±84" ±84"
Y -
PROPOSED 5K POST w
SHORES (TYP)
co
T
PROPOSED
5K POST___-®
SHORES
(NP)
tf
00
EXISTING
ACCORDIAN
HURRICAIN
SHUTTER AND
PROPOSED TRACK
5K POST
SHORES
~(TYP) EXISTING
RAI LI N G
CORNER BALCONY SHORING
f 12"-14"
INSTALLATION
CONFIGURATION
NTS
S.
E N••
• o .419 �
LOCATION
ALE����, =
NOTES : �,eeaeaao
1. THE CONTRACTOR SHALL FOLLOW ALL APPLICABLE LOCAL AND STATE CODES AND ORDINANCES.
2. 5K POST SHORES SHALL HAVE 12"x 12" PLYWOOD BOARDS PLACED ABOVE AND BELOW AT
CONTACT AREAS OF EXISTING BALCONY SLABS.
3. THE NORTH CORNER BALCONY SHALL MIRROR THIS CONFIGURATION
Pe A. T. DESIGNS. INC.
TM ATLANTIS ONE CONDOMINIUM .CON�aMM®SK— 1 CORNER BALCONY EMERGENCY SHORING DETAIL 99ZNGR=Mf(;
(561) 881-7280
JAN 2022 aoo er( eVty F.rm.Bo.a.B.lra c
NT.`S. HUTCHINSON ISLAND FLORIDA "°""" tee°"S