HomeMy WebLinkAboutREVISION Multiple DocsOFFICE USE ONLY:
DATE FILED: ' '
REVISIONFEE:
PERMIT # 2- D ✓ T
RECEIPT #
PLANNING & DEVELOPMENT SERVICES
BUILDING & CODE REGULATION DIVISION
2300 VIRGINIA AVENUE
FORT PIERCE, FL 34982-5652 RECEIVED
(772) 462-1553
JAN'2 0 2022
APPLICATION FOR BUILDING PERMIT REVISIONS
PROJECT INFORMATION Permitting Department
St. Lucie County
LOCATION/SITE _
• rrrrann_
DETAILED DESCRIPTION OF PROJECT
CONTRACTOR INFORMATION:
STATE of FL REG./CERT. #: CBC051145
BUSINESS NAME: GRBK GHO Homes LLC
QUALIFIERS NAME: William Handler
ADDRESS: 590 NW Mercantile Place
CITY: Pt St Lucie STATE: FL
PHONE (DAYTIME). 772-773-0075
OWNER/BUILDER INFORMATION:
NAME: GRBK GHO St Lucie LLC
ADDRESS:590 NW Mercantile Place
CITY: Port St Lucie
PHONE (DAYTIME: 772-773-0075
ST. LUCIE CO CERT. #:
ZIP: 34986
FAX: 561-688-0909
STATE: FL ZIP: 34986
FAX: 561-688-0909
ARCHITECT/ENGINEER INFORMATION:
NAME: Donald J Nuelle
ADDRESS: 11634 SW Rowena St
CITY: Port St Lucie
PHONE (DAYTIME): 561-629-6975
SLCCC: 9123109
Revised 06130117
STATE: FL ZIP: 34987
FAX: N/A
REk/11SION
iu
RECEIVED
JAN TO 1011
FORM R405-2020 Permitting Department
FLORIDA ENERGY EFFICIERGYGME FOR BUILDING CONSTRUCTION
Florida Department of Business and Professional Regulation - Residential Performance Method
Project Name: MW-62
Builder Name: GHO BUILDERS
Street: 2650 CONIFER DR
Permit Office: ST. LUCIE COUNTY
City, State, Zip: FORT PIERCE, FL, 34951
Permit Number:
Owner:
Jurisdiction:
Design Location: FL, Fort Pierce
County: St. Lucie (Florida Climate Zone 2 )
1. New construction or existing New (From Plans)
10. Wall Type$1832.4 sqft.)
Insulation Area
2. Single family or multiple family Detached
a. Concrete Block - Ext Insul, Exterior
R=4.1 1632.60 ft2
b. Frame - Wood, Adjacent
R=11.0 199.89 ft
3. Number of units, if multiple family 1
c. N/A
R= ft2
4. Number of Bedrooms 2
d. N/A
R= ft2
11. Ceiling Types (1924.2 sqft.)
Insulation Area
5. Is this a worst case? No
a. Under Attic (Vented)
R=40.0 1832.00 ft2
6. Conditioned floor area above grade (ft2) 1832
b. Knee Wall (Vented)
R=38.0 92.23 ft2
Conditioned floor area below grade (ft2) 0
c. N/A
R= ft2
7. Windows(260.3 sqft.) Description Area
12. Ducts
a. Sup: Attic, Ret: Attic, AH: Main
R ft2
6 494
a. U-Factor: Dbl, U=0.69 260.34 ft2
SHGC: SHGC=0.26
b. U-Factor: N/A ft2
13. Cooling systems
kBtu/hr Efficiency
SHGC:
a. Central Unit
34.6 SEER:16.00
c. U-Factor: N/A ft2
SHGC:
Area Weighted Average Overhang Depth: 6.163 ft.
14. Heating systems
kBtu/hr Efficiency
Area Weighted Average SHGC: 0.260
a. Electric Strip Heat
24.8 COP:1.00
8. Skylights Area
c. U-Factor:(AVG) N/A ft2
15. Hot water systems
SHGC(AVG): N/A
a. Electric
Cap: 50 gallons
9. Floor Types (1832.0 sqft.) Insulation Area
EF: 0.940 -
a. Slab -On -Grade Edge Insulation R=0.0 1832.00 ft2
b. Conservation features
b. N/A R= ft2
None
c. N/A R= ft2
16. Credits
None
Glass/Floor Area: 0.142 Total Proposed Modified Loads: 54.75
PASS
Total Baseline Loads: 57.59
I hereby certify that the plans and specifications covered by
Review of the plans and
Og t%E S7,q?�,
this calculation are in compliance with the Florida Energy
specifications covered by this
Code.
>�.
calculation indicates compliance
y4} �,,'' = = `��.��
with the Florida Energy Code.
rrrrrr'�; :;�: ;;:•'�;� O
PREPARED BY: - ____-
Before construction is completed
C
DATE: 01/05/2022
this building will be inspected for
compliance with Section 553.908
I hereby certify that this building, as designed, is in compliance
Energy Co
Florida Statutes.;
COD 1�
with the Florida e.
we
OWNER/AGENT:
BUILDING OFFICIAL:
DATE:
DATE:
- Compliance requires certification by the air handier unit manufacturer that the air handler enclosure qualifies as
certified factory -sealed in accordance with R403.3.2.1.
- Compliance requires an Air Barrier and Insulation Inspection Checklist in accordance with R402.4.1.1 and this project requires an
envelope leakage test report with envelope leakage no;greater than 7.00 ACH50 (R402.4.1.2).
IC6- C��7 RECEIVED
PXN ,�16 / f" /zv JAN 2 0 2022
1/5/2022 1:47 PM EnergyGauge® USA 7.0.00 - J.2 f 1 Rn �2020) Co T' a Unty, i nnitting age 1 of 4
GnRnn PAn9;_'?n9n IMPI IT CI IMMARY [.HFCKI IRT REPORT
PROJECT
Title:
Building Type:
Owner Name:
# of Units:
Builder Name:
Permit Office:
Jurisdiction:
Family Type:
New/Existing:
Comment:
MW-62
User
1
GHO BUILDERS
ST. LUCIE COUNTY
Detached
New (From Plans)
Bedrooms: 2
Conditioned Area: 1832
Total Stories: 1
Worst Case: No
Rotate Angle: 0
Cross Ventilation: No
Whole House Fan: No
Address Type: Street Address
Lot #
Block/Subdivision:
PlatBook:
Street: 2650 CONIFER DR
County: St. Lucie
City, State, Zip: FORT PIERCE,
FL, 34951
CLIMATE
Design Location
Design Temp
TMY Site 97.5 % 2.5 %
Int Design Temp Heating Design Daily Temp
Winter Summer Degree Days Moisture Range
FL,
Fort Pierce FL_VERO_BEACH_MUNI 39 90
70 75 299 62 Low
BLOCKS
Number
Name
Area Volume
1
Blockl
1832 17953.6
SPACES
Number
Name
Area Volume Kitchen Occupants
Bedrooms InfilID Finished Cooled Heated
1
Main
1832 17953.6 Yes 3
2 1 Yes Yes Yes
FLOORS
#
Floor Type
Space Perimeter R-Value
Area Tile Wood Carpet-
1 Slab -On -Grade Edge Insulatio Main 188.1 ft
1832 ft2 ____ 0 0 1
ROOF
/
V #
Type
Roof Gable Roof
Materials Area Area Color
Rad Solar SA Emitt Emitt Deck Pitch
Barr Absor. Tested Tested Insul. (deg)
1
Hip
Flat tile/slate 2048 ft2 0 ft2 Medium
N 0.4 N 0.9 No 0 26.57
ATTIC
V #
Type
Ventilation Vent Ratio (1 in)
Area RBS IRCC
1
Full attic
Vented 150 1832 ft2 N N
CEILING
#
Ceiling Type
Space R-Value Ins Type Area Framing Frac Truss Type
1
2
Under Attic (Vented)
Knee Wall (Vented)
Main 40 Blown
Main 38 Blown
1832 ft2 0.1 Wood
92.23 ft2 0.11 Wood
1/5/2022 1:47 PM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 2 of 4
GnRhn PAnr,-,?ngn INPI IT Al IMMARY CHFCKI IRT RFP0RT
WALLS
Adjacent
Cavity Width Height
Sheathing Framing Solar
Belo w
V
Ornt
TO Wall T�ipe Space
_ 1
N
Exterior Concrete Block - Ext Insul Main
4.1 19 2 9
4
178.9 ft2
0
0 0.3
0
_ 2
E
Exterior Concrete Block - Ext Insul Main
4.1 58 4 9
4
544.4 ft2
0
0 0.3
0
_ 3
S
Exterior Concrete Block - Ext Insul Main
4.1 43 7 9
4
406.8 ft2
0
0 0.3
0
_ 4
W
Exterior Concrete Block - Ext Insul Main
4.1 53 10 9
4
502.4 ft2
0
0 0.3
0
5
-
Garage Frame - Wood Main
11 21 5 9
4
199.9 ft2
0
0.25 0.3
0
DOORS
#
Ornt Door Type Space
Storms
U-Value
Width
Height
Area
Ft
In
Ft In
1
N Wood Main
None
.39
3
8
24 ft2
WINDOWS
Orientation shown is the entered, Proposed orientation.
Wall
Overhang
#
Ornt ID Frame Panes NFRC
U-Factor SHGC Imp
Area
Depth
Separation
Int Shade
Screening
1
N 1 Metal Double (Clear) Yes
0.69 0.26 N
26.0 ft'
7 ft 0 in
1 ft 0 in
None
None
2
e 2 Metal Double (Clear) Yes
0.69 0.26 N
16.7 ft2
1 ft 0 in
1 ft 0 in
None
None
3
e 2 Metal Double (Clear) Yes
0.69 0.26 N
15.0 ft2
1 ft 0 in
1 ft 0 in
None
None
4
s 3 Metal Double (Clear) Yes
0.69 0.26 N
30.0 ft2
1 ft 0 in
1 ft 0 in
None
None
5
s 3 Metal Double (Clear) Yes
0.69 0.26 N
36.0 ft2
10 ft 0 in
1 ft 0 in
None
None
6
s 3 Metal Double (Clear) Yes
0.69 0.26 N
96.0 ft2
10 ft 0 in
1 ft 0 in
None
None
7
w 4 Metal Double (Clear) Yes
0.69 0.26 N
12.0 ft2
1 ft 0 in
1 ft 0 in
None
None
8
w 4 Metal Double (Clear) Yes
0.69 0.26 N
7.0 ft2
1 ft 0 in
1 ft 0 in
None
None
9
W 4 Metal Double (Clear) Yes
0.69 0.26 N
21.7 ft2
1 ft 0 in
1 ft 0 in
None
None
GARAGE
#
Floor Area Ceiling Area
Exposed Wall Perimeter
Avg. Wall Height
Exposed Wall Insulation
1
583 ft2 583 ft2
64 ft
9.3 ft
1
INFILTRATION
#
Scope
Method SLA
CFM 50 ELA EgLA
ACH
ACH 50
1 Wholehouse Proposed ACH(50) .000436
2094.6 114.92 215.74
.137
7
HEATING SYSTEM
#
System Type Subtype
Speed Efficiency
Capacity
Block
Ducts
1
Electric Strip Heat/ None
COP:1
24.82 kBtu/hr
1
sys#1
1/5/2022 1:47 PM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 3 of 4
FnRM R4n5-2020 INPUT SUMMARY CHECKLIST REPORT
COOLING SYSTEM
# System Type
Subtype
Subtype Efficiency
Capacity
Air Flow
SHR
Block
Ducts
1 Central Unit/
Split
Singl SEER: 16 34.6 kBtu/hr cfm
0.7
1
sys#1
HOT WATER SYSTEM
# System Type
SubType
Location
EF Cap
Use
SetPnt
Conservation
1 Electric
None
Garage
0.94 50 gal
62.3 gal
120 deg
None
SOLAR HOT WATER SYSTEM
FSEC
Collector
Storage
Cert # Company Name
System Model # Collector
Model
# Area
Volume
FEF
None None
ftz
DUCTS
-- Supply ---
-- Return ----
Air
CFM 25 CFM25
HVAC #
V # Location R-Value Area
Location
Area Leakage Type
Handler
TOT OUT
QN
RLF
Heat Cool
1 Attic
6 494 ftZ
Attic
232 ftZ Default Leakage
Main
(Default) (Default)
1 1
TEMPERATURES
Programable Thermostat: N
Ceiling Fans:
CoolingJan Feb
HeatinJan f X Feb
Mar
Mar
Apr
E APr I
Ma X Jun X Jul
May r j Jun Jul
X Aug
f AuSep
Se
Oct
Oct
Nov
Nov
Hx
Dec
Dec
H
Ventin Jan [ Feb
X Mar
[X] A r
May Jun [ Jul
[ Aug
Se [X]
Oct
Nov
Dec
Thermostat Schedule: HERS 2006 Reference
Hours
Schedule Type
1
2 3
4 5 6
7
8 9
10
11
12
Cooling (WD) AM
78
78 78
78 78 78
78
78 78
78
78
78
PM
78
78 78
78 78 78
78
78 78
78
78
78
Cooling (WEH) AM
78
78 78
78 78 78
78
78 78
78
78
78
PM
78
78 78
78 78 78
78
78 78
78
78
78
Heating (WD) AM
68
68 68
68 68 68
68
68 68
68
68
68
PM
68
68 68
68 68 68
68
68 68
68
68
68
Heating (WEH) AM
68
68 68
68 68 68
68
68 68
68
68
68
PM
68
68 68
68 68 68
68
68 68
68
68
68
MASS
Mass Type
Area
Thickness
Furniture Fraction Space
Default 8 Ibs/sq.ft.
0 ft'
0 ft
0.3
Main
1/5/2022 1:47 PM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 4 of 4
2020 - AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA
TABLE 402.4.1.1
AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA a
Project Name: MW-62 Builder Name: GHO BUILDERS
Street: 2650 CONIFER DR Permit Office: ST. LUCIE COUNTY
City, State, Zip: FORT PIERCE, FL, 34951 - Permit Number:
U
Owner: Jurisdiction:
W
Design Location: FL, Fort Pierce
U
COMPONENT
AIR BARRIER CRITERIA
INSULATION INSTALLATION CRITERIA
General
A continuous air barrier shall be installed in the building envelope.
Air -permeable insulation shall
The exterior thermal envelope contains a continuous air barrier.
not be used as a sealing material.
requirements
Breaks or joints in the air barrier shall be sealed.
The air barrier in any dropped ceiling/soffit shall be aligned with
The insulation in any dropped ceiling/soffit
Ceiling/attic
the insulation and any gaps in the air barrier shall be sealed.
shall be aligned with the air barrier.
Access openings, drop down stairs or knee wall doors to
unconditioned attic spaces shall be sealed.
The junction of the foundation and sill plate shall be sealed.
Cavities within corners and headers of frame walls
Walls
The junction of the top plate and the top of exterior walls shall be
shall be insulated by completely filling the cavity
sealed.
with a material having a thermal resistance of R-3
Knee walls shall be sealed.
per inch minimum.
Exterior thermal envelope insulation for framed
walls shall be installed in substantial contact and
continuous alignment with the air barrier.
Windows, skylights
The space between window/doorjambs and framing, and
and doors
skylights and framing shall be sealed.
Rim joists
Rim joists shall include the air barrier.
Rim joists shall be insulated.
Floors
The air barrier shall be installed at any exposed edge of
Floor framing cavity insulation shall be installed to
(including
insulation.
maintain permanent contact with the underside of
above -garage
subfloor decking, or floor framing cavity insulation
and cantilevered
shall be permitted to be in contact with the top side
floors)
of sheathing, or continuous insulation installed on
the underside of floor framing and extends from the
bottom to the top of all perimeter floor framing
members.
Crawl space walls
Exposed earth in unvented crawl spaces shall be covered with
Where provided instead of floor insulation, insulation
a Class I vapor retarder with overlapping joints taped.
shall be permanently attached to the crawlspace walls.
Shafts, penetrations
Duct shafts, utility penetrations, and flue shafts opening to
exterior or unconditioned space shall be sealed.
Batts in narrow cavities shall be cut to fit, or narrow
cavities shall be filled by insulation that on
Narrow cavities
installation readily conforms to the available cavity
spaces.
Garage separation
Air sealing shall be provided between the garage and conditioned spac
as.
Recessed lighting
Recessed light fixtures installed in the building thermal envelope
Recessed light fixtures installed in the building
shall be sealed to the finished surface.
thermal envelope shall be air tight and IC rated.
Plumbing and wiring
Batt insulation shall be cut neatly to fit around wiring
and plumbing in exterior walls, or insulation that on
installation readily conforms to available space shall
extend behind o4o'no and wiring.
Shower/tub
The air barrier installed at exterior walls adjacent to showers and
Exterior walls adjacent to showers and tubs shall
on exterior wall
tubs shall separate them from the showers and tubs.
be insulated.
Electrical/phone box or
The air barrier shall be installed behind electrical or communication
exterior walls
boxes or air -sealed boxes shall be installed.
HVAC register boots
HVAC supply and return register boots that penetrate building
thermal envelope shall be sealed to the sub -floor, wall covering or
Concealed
When required to be sealed, concealed fire sprinklers shall only be
sprinklers
sealed in a manner that is recommended by the manufacturer.
Caulking or other adhesive sealants shall not be used to fill voids
between e s and walls or cemlmnas.
a. In addition, inspection of log walls shall be in accordance with the provisions of IGG-4U0.
1/5/2022 1:47 PM EnergyGauge@ USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 1
FORM R405-2020
ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD
ESTIMATED ENERGY PERFORMANCE INDEX* = 95
The lower the EnergyPerformance Index, the more efficient the home.
2650 CONIFER DR, FORT PIERCE, FL, 34951
1. New construction or existing
New (From Plans)
10. Wall Type and Insulation
Insulation
Area
2. Single family or multiple family
Detached
a. Concrete Block - Ext Insul, Exterior
R=4.1
1632.60 ft2
b. Frame - Wood, Adjacent
R=11.0
199.89 ft2
3. Number of units, if multiple family
1
c. N/A
R=
ft2
4. Number of Bedrooms
2
d. N/A
R=
ft2
11. Ceiling Type and insulation level
Insulation
Area
5. Is this a worst case?
No
a. Under Attic (Vented)
R=40.0
1832.00 ft2
6. Conditioned floor area (ft2)
1832
b. Knee Wall (Vented)
R=38.0
92.23 ft2
c. N/A
R=
ft2
7. Windows- Description
Area
12. Ducts, location &insulation level
R ft2
a. U-Factor: Dbl, U=0.69
260.34 ft2
a. Sup: Attic, Ret: Attic, AH: Main
6 494
SHGC: SHGC=0.26
b. U-Factor: N/A
ft2
SHGC:
13. Cooling systems
kBtu/hr
Efficiency
c. U-Factor: N/A
ft2
a. Central Unit
34.6 SEER:16.00
SHGC:
d. U-Factor: N/A
ft2
14. Heating systems
kBtu/hr
Efficiency
SHGC:
a. Electric Strip Heat
24.8
COP:1.00
Area Weighted Average Overhang Depth:
6.163 ft.
Area Weighted Average SHGC:
0.260
8. Skylights Description
Area
15. Hot water systems
Cap:
50 gallons
a. U-Factor(AVG): N/A
ft2
a. Electric
EF: 0.94
SHGC(AVG): N/A
b. Conservation features
9. Floor Types
Insulation
Area
None
a. Slab -On -Grade Edge Insulation
R=0.0
1832.00 ft2
Credits (Performance method)
None
b. N/A
R=
ft2
c. N/A
R=
ft2
certify that this home has complied with the Florida Energy Efficiency Code for Building
Construction through the above ener y saving features which will be installed (or exceeded)
in this home before final inspection. therwise, a new EPL Display Card will be completed
based on installed Code compliant fe tures.
Builder Signature: Date: t %1%Qz
Address of New Home:FS,'Or, City/FL Zip:er�-�
�-tas
*Note: This is not a Building Energy Rating. If your Index is below 70, your home may qualify for energy efficient
mortgage (EEM) incentives if you obtain a Florida Energy Rating. For information about the Florida Building Code,
Energy Conservation, contact the Florida Building Commission's support staff.
**Label required by Section R303.1.3 of the Florida Building Code, Energy Conservation, if not DEFAULT.
1 /5/2022 1:47 PM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 1 of 1
Envelope Leakage Test Report (Blower Door Test)
Residential Prescriptive, Performance or ERI Method Compliance
2020 Florida Building Code, Energy Conservation, 7th Edition
Jurisdiction:
Permit #:
Job Information
Builder: GHO BUILDERS Community: Lot: NA
Address: 2650 CONIFER DR
City: FORT PIERCE State: FL Zip: 34951
Air Leakage Test Results -Passing results must meet either the Performance, Prescriptive, or ERl Method
,0 PRESCRIPTIVE METHOD -The building or dwelling unit shall be tested and; verified as having an air leakage rate of not exceeding 7 air
changes per hour at a pressure of 0.2 inch w.g. (50 Pascals) in Climate Zones 1 and 2.
0 PERFORMANCE or ERI METHOD -The building or dwelling unit shall be tested and verified as having an air leakage rate of not exceeding
.'the selected ACH(50) value, as shown on Form R405-2020 (Performance) or R406-2020 (ERI), section labeled as infiltration, sub -section ACH50.
ACH(50) specified on Form R405-2020-Energy Calc (Performance) or R406-2020 (ERl): 7.000
x 60 = 17954 = Method for calculating building volume:
CFM(50) Building Volume ACH(50) 0 Retrieved from architectural plans
F-1 PASS • Code software calculated
When ACH(50) is less than 3, Mechanical Ventilation installation 0 Field measured and calculated
must be verified by building department.
R402.4.1.2 Testing. Testing shall be conducted in accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g. (50 Pascals)
Testing shall be conducted by either individuals as defined in Section 553.993(5) or (7), Florida Statues.or individuals licensed as set forth in Section
489.105(3)(f), (g), or (i) or an approved third party. A written report of the results of the test shall be signed by the party conducting the test and
provided to thecode official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope.
During testing:
1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or other infiltration
control measures.
2. Dampers including exhaust, intake, makeup air, back draft and flue dampers shall be closed, but not sealed beyond intended infiltration control
measures.
3. Interior doors, if installed at the time of the test, shall be open.
4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed.
5. Heating and cooling systems, if installed at the time of the test, shall be turned off.
6. Supply and return registers, if installed at the time of the test, shall be fully open.
Testing Company
Company Name: Phone:
I hereby verify that the above Air Leakage results are in accordance with the 2020 7th Edition Florida Building Code
Energy Conservation requirements according to the compliance method selected above.
Signature of Tester: Date of Test:
Printed Name of Tester:
License/Certification #: Issuing Authority:
1/5/2022 1:48:15 PM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 1
Load Job:
-�,- wrightsoft Ld Short FDate: Aug 3, 2021
Entire Mouse By.
Projectu s
Far: MV1r-62
2650 CONIFER DR, FORT PIERCE, FL34951
Design
Informati•
Htg
Glg
Infiltration
Outside db (°F)
43
91
Method
Simplified
Inside db ff)
70
72
Construction quality
Average
Design TD (°F)
27
19
Firep[aces
0
Daily range
-
L
Inside humidity (%)
30
50
Moisture difference (grtlb)
0
65
HEATING EQUIPMENT
COOLING EQUIPMENT
Make
Make Lennox
Trade
Trade LENNOX
Model
Cond ML14XC1S036 230C'*
AHRI ref
Coil CBA27UHE a36-230*++TDR
AHRI ref 204289057
Efficiency
100 EFF
Efficiency 13.0 EER,16 SEER
Healing input
7.3
kW
Sensible cooting 24220
Btuh
Healing output
24817
Btuh
Latent coolirtg 10380
Btuh
Temperature rise
20
°F
Total coating 34600
Btuh
Actual airflow
1153
corn
Actual airflow 1153
cfm
Air flow factor
0.046
dm.Btuh
Airflow factor 0.046
cfmBtuh
Static pressure
0
in H2O
Static pressure 0
'in H2O
Space thermostat
Load sensible heat ratio 0.72
ROOM NAME
Area
OF)
Htg toad
(Btuh)
Cog load
(Bath)
HtgAVF
(drn)
CIgAVF
(dm)
MASTER SUITE
312
5009
3794
230
176
HERWIC
60
927
520
43
24
MASTER BATH
169
T-780
2198
82
102
BED 2
205
2905
3264.
133
152
UTILITY
73
866
894
40
42
BATH 2
51
41
333
2
15
FOYER
69
734
530
34
25
DINING
133
3650
3152
168
146.
KITCHEN
156
1,724
2387
79
111
DEN
181
3823,
3218
175
149
GREAT RM
376
3629
4156
167
193
IJAI I thfi C(`LA
.AO
104
QQG
7
40
Calculations approved byACCAtG meetall requirements of Manual J.8th Ed.
-� wrI hts4jft= 2021-AL0313:18:38
^- 9. Rigit Stiz9 h vema1202121DASASU249b4 Page 1
�+�.ers%ryuserooamereslwdgfzoftHVACV.,,f62tu� C2Pc=li4G9 FraczOD�6aoe9:'P8
Entire House
1833
2512E
.24831
1153
1153
Other equip loads
0
0
Equip. @ 0.95 RSM
23714
Latent cooling
9689
T/1TAI C
qAn!
1,1 _FR
11 A:3
Calculations approved byACCAta meet all requirements of Manual J 8th Ed.
ti wri htsoft® 2021•At9-0313:18:38'
.. 9 .�-.,. RigttSute^tkiv--i- 120212"DSRStMgE4 Paget
ACCA _ers0.rtyUser0oamarts\Wri9luaftWACV:W-62stp Catc=NUS Frort Dbzrb=E N
- - wrightsoft- Project Summary
Entire House
Project Information
For MW-62
2650 CONIFER DR, FORT PIERCE; FL34951
Motes:
Design Information
Weather: Mere Beach Municipal AP FL, US
Job:
Date: Aug.3, 2021
By.
Winterbesign Conditions
Summer'Design Conditions
Outside db
43
'F
Outside db
91
OF
Inside db
70
°F
Insidedb
72
OF
Design TD
27
OF
Design TD.
19
OF
Daily,range
L
Relative humidity
50
%
Moisture ditfererice
65
grAb
Heating Summary
Sensible Cooling, Equipment Load Sizing
Structure
21926
Btuh
Structure
214,05
Stuh
Ducts
3199
Btuh
Ducts
3427
Btuh
Central vent (0 cfm)
0
Btuh
Centralvent (0 cfm)
0
Btuh
(none)
(none)
Humidification
0
Btuh
Blower
0
Btuh
Piping
0
Btuh
Equipment load
25126
Btuh
Use manufactureft data
n
Ratelsm—ngi multipplier
Equipment load,
0.95
237.14
Btuh
Infiltration
sensibIle
Method
Simpliined
Latent Cooling-Equiprnent
Load Sizing
Construction quality
Average
Fireplaces
a
Structure
'8161
Btuh
Ducts
1527
Btuh
Genoa] vent (0efm)
0
Btuh
f; Qeatirtc�
coolfcn� g;;
(none)
Btuh
Area (ft2)
1833
1833
Equipment latent load
9689
Volume (ft)
18050
18Q60
Air changeslhour
0.38
0.201
Equipment Total Load (Sen+Lat)
33403
Btuh
Equiv AVF (cfm)
114
60
Req. total capacity at 0.70 SHR
2.8
ton
Heating Equipment Summary
Cooling Equipment' Summary
Make
Make Lennox
Trade
Trade LENNOX
Model
Cond ML14XC1S036-230C"
AHRI ref
Gait CBA27UHE-036-230'++TDR
AHR[ ref 204289057
Efficiency
100 EFF
Efficiency 13:0 EER,.16 SEER
Heating input
7.3
kW
Sensible coating
24220.
Btuh
Heating output
24817
Btuh
Latentcoollrtg
10380
Btuh
Temperature rise
20
OP
Tout cooling
34600
Btuh
Actual airflow
1153
cfm
Actual airflow
1153
cfm
Airflowfactor
0.046
cfm]Btuh
Airflowfadbir
0.046
cfrhBtuh
Static pressure
0
.in H2O
Stadcpressure
0
in-1-120
Space thermostat
Load sensible heat ratio
0.72
Calculations approved byACCA to meet all requirements of` -Manua( J Sth-Ed.
-��- wr➢ghtsoft® 2021-Aug•0313:18:38
.-- •�^ Rigtl•Stitct&LWversal2a212t.ODSRSt/2SM
Pagel
ACCI', _.ers%ArtWserl Xamri!lWrigtrofthVAClVW-62np Catc=WS Erozbbbnrt ms: N
GH O HOMES
MW-62
2650 CONIFER DR
FORT PIERCE, FL 34951