HomeMy WebLinkAboutSLC-2010-0677 Compaction Test 104Tested For:
14150 NW 3rd Avenue
Miami, Florida - 33168
Jose Barreto
Cc:
Attention:
Title:Project Manager
Jose Barreto (joseb@ceielectric.net)
Project #:7112-21-182-002
Project:A2P0048A
Address:14101 South Angle Road
West St. Lucie, Florida - 34945, United States
Joel Hernandez
Permit #:
Inspector:
CEI, LLC 04/26/2021Report Date:
General Location:Generator Pad
Test Method:ASTM D-6938 (Nuclear)Field Activity Date:04/23/2021
Gauge Make:Troxler Project Specifications:98 %
Gauge Model:3430 Modified Proctor(AASHTO T-180)Gauge S/N:28286
Retest Required:Yes X NoVertical Reference:
Test Date Proctor Number Soil Description Max. Dry
Density (pcf)
Optimum
Moisture (%)
04/23/2021 L1 Light brown sand with rock 119.0 9.5
Test
No
Elevation or
Re-Test No
Depth
(Inch)Test Location
Proctor
Max
Density
(lbs/ft^3)
Proctor
Optimum
Moisture
(%)
Field
Percent
Moisture
(%)
Field
Density
(lbs/ft^3)
Percent
Compaction
(%)
Spec: 98
Meet
Spec ?
1 Pad 12 Center Northside of Pad 119.0 9.5 7.8 117.9 99.1 Yes
2 Pad 12 Center Southside of Pad 119.0 9.5 6.9 118.5 99.6 Yes
0 -
0 -
0 -
Remarks:
Report Copied to:
Notes: As requested, a representative from our company arrived on site as scheduled and performed the above test. These test results apply only to
the specific locations noted and do not represent any other location. Reports may not be reproduced except in full, without permission.