HomeMy WebLinkAboutAPPROVED NEW Manual J UpdatedCalculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Nov-23 10:04:18
Right-Suite® Universal 2021 21.0.10 RSU29066 Page 1
...ts\Wrightsoft HVAC\5702 Hickory Dr PSL Prop.rup Calc = MJ8 Front Door faces: N
1447Job:Load Short Form 3/29/2021Date:Zone 1 Chris BatemanBy:
Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
Project Information
Maui Spec Home, NisAir Air ConditioningFor:
5702 Hickory Dr, Fort Pierce, FL 34982
Design Information
InfiltrationClgHtg
SimplifiedMethod9041Outside db (°F)
AverageConstruction quality7570Inside db (°F)
0Fireplaces1529Design TD (°F)
L-Daily range
5030Inside humidity (%)
572Moisture difference (gr/lb)
HEATING EQUIPMENT COOLING EQUIPMENT
Make Make Lennox
Trade Trade LENNOX
Model Cond ML14XC1S018-230A**
AHRI ref Coil CBA27UHE-018-230*++TDR
AHRI ref 10259433
Efficiency 100 EFF Efficiency 13.0 EER, 16 SEER
Heating input kW3.3 Sensible cooling Btuh12600
Heating output Btuh11234 Latent cooling Btuh5400
Temperature rise °F17 Total cooling Btuh18000
Actual air flow cfm600 Actual air flow cfm600
Air flow factor cfm/Btuh0.050 Air flow factor cfm/Btuh0.057
Static pressure in H2O0.85 Static pressure in H2O0.85
Space thermostat Load sensible heat ratio 0.73
ROOM NAME Area Htg load Clg load Htg AVF Clg AVF
(ft²)(Btuh)(Btuh)(cfm)(cfm)
Master Bed 2 216 3595 2408 181 137
Leisure Area 192 1057 2635 53 150
M Bath 2 66 799 457 40 26
Bath 2 51 1006 486 50 28
Clst 25 42 81 2 5
Hall 56 0 0 0 0
Bed 4 149 2999 2326 151 132
Bed 3 149 2452 2165 123 123
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Nov-23 10:04:18
Right-Suite® Universal 2021 21.0.10 RSU29066 Page 2
...ts\Wrightsoft HVAC\5702 Hickory Dr PSL Prop.rup Calc = MJ8 Front Door faces: N
Zone 1 902 11951 10557 600 600
Other equip loads 1579 839
Equip. @ 0.95 RSM 10871
Latent cooling 4231
TOTALS 902 13530 15103 600 600
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Nov-23 10:04:18
Right-Suite® Universal 2021 21.0.10 RSU29066 Page 3
...ts\Wrightsoft HVAC\5702 Hickory Dr PSL Prop.rup Calc = MJ8 Front Door faces: N
1447Job:Load Short Form 3/29/2021Date:Zone 2 Chris BatemanBy:
Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
Project Information
Maui Spec Home, NisAir Air ConditioningFor:
5702 Hickory Dr, Fort Pierce, FL 34982
Design Information
InfiltrationClgHtg
SimplifiedMethod9041Outside db (°F)
AverageConstruction quality7570Inside db (°F)
0Fireplaces1529Design TD (°F)
L-Daily range
5030Inside humidity (%)
572Moisture difference (gr/lb)
HEATING EQUIPMENT COOLING EQUIPMENT
Make Make Lennox
Trade Trade LENNOX
Model Cond ML14XC1S024-230A**
AHRI ref Coil CBA27UHE-024-230*++TDR
AHRI ref 10259435
Efficiency 100 EFF Efficiency 13.0 EER, 16 SEER
Heating input kW4.8 Sensible cooling Btuh16800
Heating output Btuh16341 Latent cooling Btuh7200
Temperature rise °F19 Total cooling Btuh24000
Actual air flow cfm800 Actual air flow cfm800
Air flow factor cfm/Btuh0.055 Air flow factor cfm/Btuh0.054
Static pressure in H2O0.85 Static pressure in H2O0.85
Space thermostat Load sensible heat ratio 0.75
ROOM NAME Area Htg load Clg load Htg AVF Clg AVF
(ft²)(Btuh)(Btuh)(cfm)(cfm)
Kitchen 194 3246 4916 178 268
Living Dining 333 3854 4526 211 246
Laundry 39 522 852 29 46
Hers 23 501 167 27 9
His 23 861 279 47 15
Master Bed 250 3926 3025 215 165
M Bath 75 1707 930 93 51
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Nov-23 10:04:18
Right-Suite® Universal 2021 21.0.10 RSU29066 Page 4
...ts\Wrightsoft HVAC\5702 Hickory Dr PSL Prop.rup Calc = MJ8 Front Door faces: N
Zone 2 937 14618 14696 800 800
Other equip loads 1852 983
Equip. @ 0.95 RSM 14958
Latent cooling 5360
TOTALS 937 16470 20318 800 800
2021-Nov-23 10:04:18
Right-Suite® Universal 2021 21.0.10 RSU29066 Page 1
...ts\Wrightsoft HVAC\5702 Hickory Dr PSL Prop.rup Calc = MJ8 Front Door faces: N
1447Job:Building Analysis 3/29/2021Date:Zone 1 Chris BatemanBy:
Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
Project Information
Maui Spec Home, NisAir Air ConditioningFor:
5702 Hickory Dr, Fort Pierce, FL 34982
Design Conditions
Location: CoolingHeatingIndoor:7570Indoor temperature (°F)St Lucie Co Intl, FL, US
1529Design TD (°F)ft26Elevation:
5030Relative humidity (%)°N28Latitude:
Outdoor:56.92.4Moisture difference (gr/lb)CoolingHeating
Infiltration:9041Dry bulb (°F)
SimplifiedMethod)L(15-Daily range (°F)
AverageConstruction quality77-Wet bulb (°F)
0Fireplaces7.515.0Wind speed (mph)
Heating
Walls
Glazing
Other
Ceilings
Floors
Infiltration
Ducts
Ventilation
% of loadBtuhBtuh/ft²Component
19.025733.1Walls
10.1136817.3Glazing
0.5663.7Doors
6.68941.0Ceilings
20.727963.13.1Floors
12.116382.3Infiltration
19.32616Ducts
00Piping
00Humidification
11.71579Ventilation0Adjustments
100.013530Total
Cooling
Walls
Glazing
Other
Ceilings
Infiltration Ducts
Internal Gains
Ventilation
% of loadBtuhBtuh/ft²Component
13.615551.9Walls
13.0148418.8Glazing
0.6673.7Doors
14.316281.8Ceilings
000Floors
4.04580.6Infiltration
26.43007Ducts
7.4839Ventilation
20.72360Internal gains
00Blower
0Adjustments
100.011396Total
Latent Cooling Load = 4231 Btuh
Overall U-value = 0.097 Btuh/ft²-°F
Data entries checked.
2021-Nov-23 10:04:18
Right-Suite® Universal 2021 21.0.10 RSU29066 Page 2
...ts\Wrightsoft HVAC\5702 Hickory Dr PSL Prop.rup Calc = MJ8 Front Door faces: N
1447Job:Building Analysis 3/29/2021Date:Zone 2 Chris BatemanBy:
Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
Project Information
Maui Spec Home, NisAir Air ConditioningFor:
5702 Hickory Dr, Fort Pierce, FL 34982
Design Conditions
Location: CoolingHeatingIndoor:7570Indoor temperature (°F)St Lucie Co Intl, FL, US
1529Design TD (°F)ft26Elevation:
5030Relative humidity (%)°N28Latitude:
Outdoor:56.92.4Moisture difference (gr/lb)CoolingHeating
Infiltration:9041Dry bulb (°F)
SimplifiedMethod)L(15-Daily range (°F)
AverageConstruction quality77-Wet bulb (°F)
0Fireplaces7.515.0Wind speed (mph)
Heating
Walls
Glazing
Other
Ceilings
Floors
Infiltration
Ducts
Ventilation
% of loadBtuhBtuh/ft²Component
18.730763.1Walls
10.8178117.5Glazing
0.91543.7Doors
5.69291.0Ceilings
21.034563.73.7Floors
11.418802.3Infiltration
20.33342Ducts
00Piping
00Humidification
11.21852Ventilation0Adjustments
100.016470Total
Cooling
Walls
Glazing
Other
Ceilings
Infiltration
Ducts
Internal Gains
Ventilation
% of loadBtuhBtuh/ft²Component
11.718311.8Walls
13.9217621.4Glazing
1.01563.7Doors
10.816911.8Ceilings
000Floors
3.45250.6Infiltration
24.23797Ducts
6.3983Ventilation
28.84520Internal gains
00Blower
0Adjustments
100.015679Total
Latent Cooling Load = 5360 Btuh
Overall U-value = 0.107 Btuh/ft²-°F
Data entries checked.
2021-Nov-23 10:04:18
Right-Suite® Universal 2021 21.0.10 RSU29066 Page 1
...ts\Wrightsoft HVAC\5702 Hickory Dr PSL Prop.rup Calc = MJ8 Front Door faces: N
1447Job:Component Constructions 3/29/2021Date:Zone 2 Chris BatemanBy:
Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
Project Information
Maui Spec Home, NisAir Air ConditioningFor:
5702 Hickory Dr, Fort Pierce, FL 34982
Design Conditions
Location: CoolingHeatingIndoor:
7570Indoor temperature (°F)St Lucie Co Intl, FL, US
1529Design TD (°F)ft26Elevation:
5030Relative humidity (%)°N28Latitude:
Outdoor:56.92.4Moisture difference (gr/lb)CoolingHeating
Infiltration:9041Dry bulb (°F)
SimplifiedMethod)L(15-Daily range (°F)
AverageConstruction quality77-Wet bulb (°F)
0Fireplaces7.515.0Wind speed (mph)
Construction descriptions GainLoss Clg HTMHtg HTMInsul RU-valueAreaOr
BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft²
Walls
Blk Wall, Stucco Ext, R-4.1 Ext Bd inI, 8" Thk, 1/2" Gyp Bd Int Fnsh 6543.155.10.109208n 4182.02
5612.028773.155.10.109278e
1142.021783.155.10.10957s
2632.024113.155.10.109130w
13562.0221203.155.10.109673all
Partitions
Frm Wall, 1/2" Gyp Bd Ext, R-11 Cav Ins, 1/2" Gyp Bd Int Fnsh, 2"x4", 16"
OC Stud
4751.469562.9411.00.101326
Windows
Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.24);
50% blinds 45°, medium; 50% outdoor insect screen; foreground = green
grass (0.23); 1 ft overhang (2 ft window ht, 1 ft sep.); 8 ft head ht
16928.110116.800.5806e
Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.24);
50% blinds 45°, medium; 50% outdoor insect screen; foreground = green
grass (0.23); 1 ft overhang (5.92 ft window ht, 1 ft sep.); 8 ft head ht
49928.129916.800.58018e
Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.22);
foreground = green grass (0.23); 8 ft overhang (6.7 ft window ht, 1 ft sep.);
8 ft head ht
113218.8108418.000.62060e
Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.24);
foreground = green grass (0.23); 1 ft overhang (5.2 ft window ht, 1 ft sep.);
8 ft head ht
17734.08716.800.5805w
Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.24);
50% blinds 45°, medium; 50% outdoor insect screen; foreground = green
grass (0.23); 5.4 ft overhang (4.17 ft window ht, 1 ft sep.); 8 ft head ht
19915.921016.800.58013w
Doors
Fbrgls Door 673.73663.697.00.12718s
893.73893.697.00.12724w
1563.731543.697.00.12742all
2021-Nov-23 10:04:18
Right-Suite® Universal 2021 21.0.10 RSU29066 Page 2
...ts\Wrightsoft HVAC\5702 Hickory Dr PSL Prop.rup Calc = MJ8 Front Door faces: N
Ceilings
Attic, Shngl Roof, R-30 Ceil Ins, 1/2" Gyp Bd Int Fnsh 0.034937 16911.809290.9930.0
Floors
On Grade Depth, Tile Flr Fnsh 00345628.700.989121
2021-Nov-23 10:04:18
Right-Suite® Universal 2021 21.0.10 RSU29066 Page 3
...ts\Wrightsoft HVAC\5702 Hickory Dr PSL Prop.rup Calc = MJ8 Front Door faces: N
1447Job:Component Constructions 3/29/2021Date:Zone 1 Chris BatemanBy:
Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
Project Information
Maui Spec Home, NisAir Air ConditioningFor:
5702 Hickory Dr, Fort Pierce, FL 34982
Design Conditions
Location: CoolingHeatingIndoor:
7570Indoor temperature (°F)St Lucie Co Intl, FL, US
1529Design TD (°F)ft26Elevation:
5030Relative humidity (%)°N28Latitude:
Outdoor:56.92.4Moisture difference (gr/lb)CoolingHeating
Infiltration:9041Dry bulb (°F)
SimplifiedMethod)L(15-Daily range (°F)
AverageConstruction quality77-Wet bulb (°F)
0Fireplaces7.515.0Wind speed (mph)
Construction descriptions GainLoss Clg HTMHtg HTMInsul RU-valueAreaOr
BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft²
Walls
Blk Wall, Stucco Ext, R-4.1 Ext Bd inI, 8" Thk, 1/2" Gyp Bd Int Fnsh 3103.155.10.10998n 1982.02
3412.025333.155.10.109169e
6992.0210933.155.10.109347s
12382.0219363.155.10.109614all
Partitions
Frm Wall, 1/2" Gyp Bd Ext, R-11 Cav Ins, 1/2" Gyp Bd Int Fnsh, 2"x4", 16"
OC Stud
3161.466372.9411.00.101217
Windows
Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.24);
50% blinds 45°, medium; 50% outdoor insect screen; foreground = green
grass (0.23); 1 ft overhang (2 ft window ht, 1 ft sep.); 8 ft head ht
5413.56716.800.5804s
8113.510116.800.5806s
13513.516816.800.58010all
Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.24);
50% blinds 45°, medium; 50% outdoor insect screen; foreground = green
grass (0.23); 1 ft overhang (5.92 ft window ht, 1 ft sep.); 8 ft head ht
99928.159716.800.58036e
Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.22);
50% blinds 45°, medium; 50% outdoor insect screen; foreground = green
grass (0.23); 1 ft overhang (6.7 ft window ht, 1 ft sep.); 8 ft head ht
35010.560218.000.62034s
Doors
Fbrgls Door 673.73663.697.00.12718n
Ceilings
Attic, Shngl Roof, R-30 Ceil Ins, 1/2" Gyp Bd Int Fnsh 0.034902 16281.808940.9930.0
Floors
On Grade Depth, Tile Flr Fnsh 00279628.700.98998
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Nov-23 10:04:18
Right-Suite® Universal 2021 21.0.10 RSU29066 Page 1
...ts\Wrightsoft HVAC\5702 Hickory Dr PSL Prop.rup Calc = MJ8 Front Door faces: N
1447Job:Project Summary 3/29/2021Date:Zone 1 Chris BatemanBy:
Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
Project Information
Maui Spec Home, NisAir Air ConditioningFor:5702 Hickory Dr, Fort Pierce, FL 34982
Notes:
Design Information
St Lucie Co Intl, FL, USWeather:
Winter Design Conditions Summer Design Conditions
Outside db °F41 Outside db °F90Inside db °F70 Inside db °F75
Design TD °F29 Design TD °F15Daily range L
Relative humidity %50Moisture difference gr/lb57
Heating Summary Sensible Cooling Equipment Load Sizing
Structure Btuh9334 Structure Btuh7550
Ducts Btuh2616 Ducts Btuh3007Central vent (50 cfm) 1579 Btuh Central vent (50 cfm) Btuh839
Outside air Outside airHumidification Btuh0 Blower Btuh0
Piping Btuh0Equipment load Btuh13530 Use manufacturer's data n
Rate/swing multiplier 0.95InfiltrationEquipment sensible load Btuh10871
Method Latent Cooling Equipment Load SizingSimplified
Construction quality Average0Fireplaces Structure Btuh1445
Ducts Btuh871Central vent (50 cfm) Btuh1915
CoolingHeating Outside air902902Area (ft²) Equipment latent load Btuh4231
85398539Volume (ft³)Air changes/hour 0.190.36 Equipment Total Load (Sen+Lat)Btuh15103
Equiv. AVF (cfm) 2751 Req. total capacity at 0.70 SHR ton1.3
Heating Equipment Summary Cooling Equipment Summary
Make Make LennoxTrade Trade LENNOX
Model Cond ML14XC1S018-230A**AHRI ref Coil CBA27UHE-018-230*++TDR
AHRI ref 10259433Efficiency 100 EFF Efficiency 13.0 EER, 16 SEER
Heating input kW3.3 Sensible cooling Btuh12600Heating output Btuh11234 Latent cooling Btuh5400
Temperature rise °F17 Total cooling Btuh18000Actual air flow cfm600 Actual air flow cfm600
Air flow factor cfm/Btuh0.050 Air flow factor cfm/Btuh0.057Static pressure in H2O0.85 Static pressure in H2O0.85
Space thermostat Load sensible heat ratio 0.73
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Nov-23 10:04:18
Right-Suite® Universal 2021 21.0.10 RSU29066 Page 2
...ts\Wrightsoft HVAC\5702 Hickory Dr PSL Prop.rup Calc = MJ8 Front Door faces: N
1447Job:Project Summary 3/29/2021Date:Zone 2 Chris BatemanBy:
Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
Project Information
Maui Spec Home, NisAir Air ConditioningFor:5702 Hickory Dr, Fort Pierce, FL 34982
Notes:
Design Information
St Lucie Co Intl, FL, USWeather:
Winter Design Conditions Summer Design Conditions
Outside db °F41 Outside db °F90Inside db °F70 Inside db °F75
Design TD °F29 Design TD °F15Daily range L
Relative humidity %50Moisture difference gr/lb57
Heating Summary Sensible Cooling Equipment Load Sizing
Structure Btuh11277 Structure Btuh10899
Ducts Btuh3342 Ducts Btuh3797Central vent (58 cfm) 1852 Btuh Central vent (58 cfm) Btuh983
Outside air Outside airHumidification Btuh0 Blower Btuh0
Piping Btuh0Equipment load Btuh16470 Use manufacturer's data n
Rate/swing multiplier 0.95InfiltrationEquipment sensible load Btuh14958
Method Latent Cooling Equipment Load SizingSimplified
Construction quality Average0Fireplaces Structure Btuh2000
Ducts Btuh1115Central vent (58 cfm) Btuh2245
CoolingHeating Outside air937937Area (ft²) Equipment latent load Btuh5360
88878887Volume (ft³)Air changes/hour 0.210.40 Equipment Total Load (Sen+Lat)Btuh20318
Equiv. AVF (cfm) 3159 Req. total capacity at 0.70 SHR ton1.8
Heating Equipment Summary Cooling Equipment Summary
Make Make LennoxTrade Trade LENNOX
Model Cond ML14XC1S024-230A**AHRI ref Coil CBA27UHE-024-230*++TDR
AHRI ref 10259435Efficiency 100 EFF Efficiency 13.0 EER, 16 SEER
Heating input kW4.8 Sensible cooling Btuh16800Heating output Btuh16341 Latent cooling Btuh7200
Temperature rise °F19 Total cooling Btuh24000Actual air flow cfm800 Actual air flow cfm800
Air flow factor cfm/Btuh0.055 Air flow factor cfm/Btuh0.054Static pressure in H2O0.85 Static pressure in H2O0.85
Space thermostat Load sensible heat ratio 0.75
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Nov-23 10:04:18Right-Suite® Universal 2021 21.0.10 RSU29066 Page 1...ts\Wrightsoft HVAC\5702 Hickory Dr PSL Prop.rup Calc = MJ8 Front Door faces: N
1447Job:Right-J® Worksheet 3/29/2021Date:Zone 1 Chris BatemanBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name Zone 1 Master Bed 2
2 Exposed wall 97.5 ft 30.5 ft
3 Room height 9.5 ft 10.0 heat/coolft
4 Room dimensions ft215.5x1.0
5 Room area 902.0 ft²215.5 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nn 3.153.15 2.022.02 116 98 310 198 0 0 0 0
.DD Fbrgls DoorFbrgls Door 0.1270.127 nn 3.693.69 3.733.73 18 18 66 67 0 0 0 0
.WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ee 3.153.15 2.022.02 205 169 533 341 0 0 0 0
.GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ee 0.000.00 0.000.00 0 0 0 0 0 0 0 0
11 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ee 16.8216.82 28.1328.13 36 0 597 999 0 0 0 0
GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 ee 0.000.00 0.000.00 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ss 3.153.15 2.022.02 390 347 1093 699 130 97 304 194
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ss 16.8216.82 13.4813.48 4 4 67 54 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ss 16.8216.82 13.4813.48 6 6 101 81 0 0 0 0
GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 ss 17.9817.98 10.4510.45 34 22 602 350 34 22 602 350
DD Fbrgls DoorFbrgls Door 0.1270.127 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ww 0.000.00 0.000.00 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ww 0.000.00 0.000.00 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ww 0.000.00 0.000.00 0 0 0 0 0 0 0 0
DD Fbrgls DoorFbrgls Door 0.1270.127 ww 0.000.00 0.000.00 0 0 0 0 0 0 0 0
PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 217 217 637 316 175 175 514 255
CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.990.99 1.801.80 902 902 894 1628 216 216 214 389
FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 902 98 2796 0 216 31 875 0
6 c) AED excursion 0 -51
Envelope loss/gain 7697 4733 2509 1138
12 a) Infiltration 1638 458 299 84
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 2 460 0 0
Appliances/other 1900 500
Subtotal (lines 6 to 13)9334 7550 2808 1722
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 0 0 0 0
14 Subtotal 9334 7550 2808 1722
15 Duct loads 28%40%2616 3007 28%40%787 686
Total room load 11951 10557 3595 2408
Air required (cfm)Air required (cfm)600 600 181 137
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Nov-23 10:04:18Right-Suite® Universal 2021 21.0.10 RSU29066 Page 2...ts\Wrightsoft HVAC\5702 Hickory Dr PSL Prop.rup Calc = MJ8 Front Door faces: N
1447Job:Right-J® Worksheet 3/29/2021Date:Zone 1 Chris BatemanBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name Leisure Area M Bath 2
2 Exposed wall 9.0 ft 6.0 ft
3 Room height 9.3 heat/coolft 9.3 heat/coolft
4 Room dimensions ft191.5x1.0 ft6.0x11.0
5 Room area 191.5 ft²66.0 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nn 3.153.15 2.022.02 42 24 76 48 0 0 0 0
.DD Fbrgls DoorFbrgls Door 0.1270.127 nn 3.693.69 3.733.73 18 18 66 67 0 0 0 0
.WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ee 3.153.15 2.022.02 0 0 0 0 0 0 0 0
.GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ee 0.000.00 0.000.00 0 0 0 0 0 0 0 0
11 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ee 16.8216.82 28.1328.13 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 ee 0.000.00 0.000.00 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ss 3.153.15 2.022.02 0 0 0 0 56 50 157 100
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ss 16.8216.82 13.4813.48 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ss 16.8216.82 13.4813.48 0 0 0 0 6 6 101 81
GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 ss 17.9817.98 10.4510.45 0 0 0 0 0 0 0 0
DD Fbrgls DoorFbrgls Door 0.1270.127 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ww 0.000.00 0.000.00 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ww 0.000.00 0.000.00 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ww 0.000.00 0.000.00 0 0 0 0 0 0 0 0
DD Fbrgls DoorFbrgls Door 0.1270.127 ww 0.000.00 0.000.00 0 0 0 0 0 0 0 0
PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 42 42 123 61 0 0 0 0
CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.990.99 1.801.80 192 192 190 346 66 66 65 119
FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 192 9 258 0 66 6 172 0
6 c) AED excursion -55 -10
Envelope loss/gain 712 467 495 291
12 a) Infiltration 96 27 128 36
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 2 460 0 0
Appliances/other 900 0
Subtotal (lines 6 to 13)809 1854 624 327
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 17 30 0 0
14 Subtotal 826 1884 624 327
15 Duct loads 28%40%231 750 28%40%175 130
Total room load 1057 2635 799 457
Air required (cfm)Air required (cfm)53 150 40 26
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Nov-23 10:04:18Right-Suite® Universal 2021 21.0.10 RSU29066 Page 3...ts\Wrightsoft HVAC\5702 Hickory Dr PSL Prop.rup Calc = MJ8 Front Door faces: N
1447Job:Right-J® Worksheet 3/29/2021Date:Zone 1 Chris BatemanBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name Bath 2 Clst
2 Exposed wall 8.5 ft 0 ft
3 Room height 9.3 heat/coolft 9.3 heat/coolft
4 Room dimensions ft8.5x6.0 ft5.0x5.0
5 Room area 51.0 ft²25.0 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nn 3.153.15 2.022.02 0 0 0 0 0 0 0 0
.DD Fbrgls DoorFbrgls Door 0.1270.127 nn 3.693.69 3.733.73 0 0 0 0 0 0 0 0
.WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ee 3.153.15 2.022.02 0 0 0 0 0 0 0 0
.GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ee 0.000.00 0.000.00 0 0 0 0 0 0 0 0
11 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ee 16.8216.82 28.1328.13 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 ee 0.000.00 0.000.00 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ss 3.153.15 2.022.02 79 75 236 151 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ss 16.8216.82 13.4813.48 4 4 67 54 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ss 16.8216.82 13.4813.48 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 ss 17.9817.98 10.4510.45 0 0 0 0 0 0 0 0
DD Fbrgls DoorFbrgls Door 0.1270.127 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ww 0.000.00 0.000.00 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ww 0.000.00 0.000.00 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ww 0.000.00 0.000.00 0 0 0 0 0 0 0 0
DD Fbrgls DoorFbrgls Door 0.1270.127 ww 0.000.00 0.000.00 0 0 0 0 0 0 0 0
PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0
CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.990.99 1.801.80 51 51 51 92 25 25 25 45
FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 51 9 244 0 25 0 0 0
6 c) AED excursion -10 -1
Envelope loss/gain 598 287 25 44
12 a) Infiltration 182 51 0 0
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 0 0 0 0
Appliances/other 0 0
Subtotal (lines 6 to 13)780 338 25 44
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 5 10 8 14
14 Subtotal 786 348 33 58
15 Duct loads 28%40%220 139 28%40%9 23
Total room load 1006 486 42 81
Air required (cfm)Air required (cfm)50 28 2 5
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Nov-23 10:04:18Right-Suite® Universal 2021 21.0.10 RSU29066 Page 4...ts\Wrightsoft HVAC\5702 Hickory Dr PSL Prop.rup Calc = MJ8 Front Door faces: N
1447Job:Right-J® Worksheet 3/29/2021Date:Zone 1 Chris BatemanBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name Hall Bed 4
2 Exposed wall 0 ft 24.5 ft
3 Room height 9.3 heat/coolft 9.3 heat/coolft
4 Room dimensions ft3.5x16.0 ft13.5x11.0
5 Room area 56.0 ft²148.5 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nn 3.153.15 2.022.02 0 0 0 0 0 0 0 0
.DD Fbrgls DoorFbrgls Door 0.1270.127 nn 3.693.69 3.733.73 0 0 0 0 0 0 0 0
.WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ee 3.153.15 2.022.02 0 0 0 0 102 85 266 170
.GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ee 0.000.00 0.000.00 0 0 0 0 0 0 0 0
11 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ee 16.8216.82 28.1328.13 0 0 0 0 18 0 299 499
GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 ee 0.000.00 0.000.00 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ss 3.153.15 2.022.02 0 0 0 0 126 126 396 253
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ss 16.8216.82 13.4813.48 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ss 16.8216.82 13.4813.48 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 ss 17.9817.98 10.4510.45 0 0 0 0 0 0 0 0
DD Fbrgls DoorFbrgls Door 0.1270.127 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ww 0.000.00 0.000.00 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ww 0.000.00 0.000.00 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ww 0.000.00 0.000.00 0 0 0 0 0 0 0 0
DD Fbrgls DoorFbrgls Door 0.1270.127 ww 0.000.00 0.000.00 0 0 0 0 0 0 0 0
PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0
CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.990.99 1.801.80 56 56 56 101 149 149 147 268
FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 56 0 0 0 149 25 703 0
6 c) AED excursion -3 62
Envelope loss/gain 56 98 1810 1253
12 a) Infiltration 0 0 525 147
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 0 0 0 0
Appliances/other 0 250
Subtotal (lines 6 to 13)56 98 2335 1650
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution -56 -98 8 14
14 Subtotal 0 0 2343 1664
15 Duct loads 28%40%0 0 28%40%657 663
Total room load 0 0 2999 2326
Air required (cfm)Air required (cfm)0 0 151 132
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Nov-23 10:04:18Right-Suite® Universal 2021 21.0.10 RSU29066 Page 5...ts\Wrightsoft HVAC\5702 Hickory Dr PSL Prop.rup Calc = MJ8 Front Door faces: N
1447Job:Right-J® Worksheet 3/29/2021Date:Zone 1 Chris BatemanBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name Bed 3
2 Exposed wall 19.0 ft
3 Room height 9.3 heat/coolft
4 Room dimensions ft13.5x11.0
5 Room area 148.5 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area Load
number (Btuh/ft²-°F)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 W Blk Wall, Stucco Ext 0.109 n 3.15 2.02 74 74 234 150
.D Fbrgls Door 0.127 n 3.69 3.73 0 0 0 0
.W Blk Wall, Stucco Ext 0.109 e 3.15 2.02 102 85 266 170
.G Impact, Clear Low-e 0.580 e 0.00 0.00 0 0 0 0
11 G Impact, Clear Low-e 0.580 e 16.82 28.13 18 0 299 499
G Impact, Clear Low-e 0.620 e 0.00 0.00 0 0 0 0
W Blk Wall, Stucco Ext 0.109 s 3.15 2.02 0 0 0 0
G Impact, Clear Low-e 0.580 s 16.82 13.48 0 0 0 0
G Impact, Clear Low-e 0.580 s 16.82 13.48 0 0 0 0
G Impact, Clear Low-e 0.620 s 17.98 10.45 0 0 0 0
D Fbrgls Door 0.127 s 0.00 0.00 0 0 0 0
W Blk Wall, Stucco Ext 0.109 w 0.00 0.00 0 0 0 0
G Impact, Clear Low-e 0.580 w 0.00 0.00 0 0 0 0
G Impact, Clear Low-e 0.580 w 0.00 0.00 0 0 0 0
D Fbrgls Door 0.127 w 0.00 0.00 0 0 0 0
P Frm Wall, 1/2" Gyp B 0.101 -2.94 1.46 0 0 0 0
C Attic, Shngl Roof, R 0.034 -0.99 1.80 149 149 147 268
F On Grade Depth, Tile 0.989 -28.68 0.00 149 19 545 0
6 c) AED excursion 66
Envelope loss/gain 1492 1154
12 a) Infiltration 407 114
b) Room ventilation 0 0
13 Internal gains: Occupants @ 230 0 0
Appliances/other 250
Subtotal (lines 6 to 13)1898 1518
Less external load 0 0
Less transfer 0 0
Redistribution 17 30
14 Subtotal 1916 1548
15 Duct loads 28%40%537 617
Total room load 2452 2165
Air required (cfm)123 123
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Nov-23 10:04:18Right-Suite® Universal 2021 21.0.10 RSU29066 Page 6...ts\Wrightsoft HVAC\5702 Hickory Dr PSL Prop.rup Calc = MJ8 Front Door faces: N
1447Job:Right-J® Worksheet 3/29/2021Date:Zone 2 Chris BatemanBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name Zone 2 Kitchen
2 Exposed wall 120.5 ft 29.0 ft
3 Room height 9.5 ft 9.3 heat/coolft
4 Room dimensions ft10.5x18.5
5 Room area 936.8 ft²194.3 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nn 3.153.15 2.022.02 208 208 654 418 0 0 0 0
.DD Fbrgls DoorFbrgls Door 0.1270.127 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0
.WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ee 3.153.15 2.022.02 363 278 877 561 0 0 0 0
.GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ee 16.8216.82 28.1328.13 6 0 101 169 0 0 0 0
11 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ee 16.8216.82 28.1328.13 18 0 299 499 0 0 0 0
GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 ee 17.9817.98 18.7818.78 60 51 1084 1132 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ss 3.153.15 2.022.02 74 57 178 114 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0
DD Fbrgls DoorFbrgls Door 0.1270.127 ss 3.693.69 3.733.73 18 18 66 67 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ww 3.153.15 2.022.02 172 130 411 263 172 130 411 263
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ww 16.8216.82 33.9933.99 5 0 87 177 5 0 87 177
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ww 16.8216.82 15.8915.89 13 10 210 199 13 10 210 199
DD Fbrgls DoorFbrgls Door 0.1270.127 ww 3.693.69 3.733.73 24 24 89 89 24 24 89 89
PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 326 326 956 475 98 98 287 142
CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.990.99 1.801.80 937 937 929 1691 194 194 193 351
FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 937 121 3456 0 194 29 832 0
6 c) AED excursion 0 155
Envelope loss/gain 9397 5853 2108 1375
12 a) Infiltration 1880 525 396 111
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 4 920 2 460
Appliances/other 3600 1700
Subtotal (lines 6 to 13)11277 10899 2504 3646
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 0 0 0 0
14 Subtotal 11277 10899 2504 3646
15 Duct loads 30%35%3342 3797 30%35%742 1270
Total room load 14618 14696 3246 4916
Air required (cfm)Air required (cfm)800 800 178 268
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Nov-23 10:04:18Right-Suite® Universal 2021 21.0.10 RSU29066 Page 7...ts\Wrightsoft HVAC\5702 Hickory Dr PSL Prop.rup Calc = MJ8 Front Door faces: N
1447Job:Right-J® Worksheet 3/29/2021Date:Zone 2 Chris BatemanBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name Living Dining Laundry
2 Exposed wall 23.5 ft 6.5 ft
3 Room height 9.3 heat/coolft 9.3 heat/coolft
4 Room dimensions ft18.0x18.5 ft6.0x6.5
5 Room area 333.0 ft²39.0 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nn 3.153.15 2.022.02 0 0 0 0 0 0 0 0
.DD Fbrgls DoorFbrgls Door 0.1270.127 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0
.WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ee 3.153.15 2.022.02 172 112 352 225 0 0 0 0
.GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ee 16.8216.82 28.1328.13 0 0 0 0 0 0 0 0
11 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ee 16.8216.82 28.1328.13 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 ee 17.9817.98 18.7818.78 60 51 1084 1132 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ss 3.153.15 2.022.02 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0
DD Fbrgls DoorFbrgls Door 0.1270.127 ss 3.693.69 3.733.73 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ww 3.153.15 2.022.02 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ww 16.8216.82 33.9933.99 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ww 16.8216.82 15.8915.89 0 0 0 0 0 0 0 0
DD Fbrgls DoorFbrgls Door 0.1270.127 ww 3.693.69 3.733.73 0 0 0 0 0 0 0 0
PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 47 47 137 68 60 60 178 88
CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.990.99 1.801.80 333 333 330 601 39 39 39 70
FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 333 24 674 0 39 7 186 0
6 c) AED excursion -140 -26
Envelope loss/gain 2577 1886 403 132
12 a) Infiltration 396 111 0 0
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 2 460 0 0
Appliances/other 900 500
Subtotal (lines 6 to 13)2973 3357 403 632
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 0 0 0 0
14 Subtotal 2973 3357 403 632
15 Duct loads 30%35%881 1169 30%35%119 220
Total room load 3854 4526 522 852
Air required (cfm)Air required (cfm)211 246 29 46
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Nov-23 10:04:18Right-Suite® Universal 2021 21.0.10 RSU29066 Page 8...ts\Wrightsoft HVAC\5702 Hickory Dr PSL Prop.rup Calc = MJ8 Front Door faces: N
1447Job:Right-J® Worksheet 3/29/2021Date:Zone 2 Chris BatemanBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name Hers His
2 Exposed wall 6.5 ft 10.0 ft
3 Room height 9.3 heat/coolft 9.3 heat/coolft
4 Room dimensions ft3.5x6.5 ft3.5x6.5
5 Room area 22.8 ft²22.8 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nn 3.153.15 2.022.02 0 0 0 0 33 33 103 66
.DD Fbrgls DoorFbrgls Door 0.1270.127 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0
.WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ee 3.153.15 2.022.02 0 0 0 0 0 0 0 0
.GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ee 16.8216.82 28.1328.13 0 0 0 0 0 0 0 0
11 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ee 16.8216.82 28.1328.13 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 ee 17.9817.98 18.7818.78 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ss 3.153.15 2.022.02 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0
DD Fbrgls DoorFbrgls Door 0.1270.127 ss 3.693.69 3.733.73 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ww 3.153.15 2.022.02 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ww 16.8216.82 33.9933.99 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ww 16.8216.82 15.8915.89 0 0 0 0 0 0 0 0
DD Fbrgls DoorFbrgls Door 0.1270.127 ww 3.693.69 3.733.73 0 0 0 0 0 0 0 0
PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 60 60 178 88 60 60 178 88
CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.990.99 1.801.80 23 23 23 41 23 23 23 41
FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 23 7 186 0 23 10 287 0
6 c) AED excursion -5 -9
Envelope loss/gain 387 124 590 186
12 a) Infiltration 0 0 75 21
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 0 0 0 0
Appliances/other 0 0
Subtotal (lines 6 to 13)387 124 664 207
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 0 0 0 0
14 Subtotal 387 124 664 207
15 Duct loads 30%35%115 43 30%35%197 72
Total room load 501 167 861 279
Air required (cfm)Air required (cfm)27 9 47 15
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Nov-23 10:04:18Right-Suite® Universal 2021 21.0.10 RSU29066 Page 9...ts\Wrightsoft HVAC\5702 Hickory Dr PSL Prop.rup Calc = MJ8 Front Door faces: N
1447Job:Right-J® Worksheet 3/29/2021Date:Zone 2 Chris BatemanBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name Master Bed M Bath
2 Exposed wall 30.5 ft 14.5 ft
3 Room height 10.0 heat/coolft 9.3 heat/coolft
4 Room dimensions ft250.3x1.0 ft11.5x6.5
5 Room area 250.3 ft²74.8 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nn 3.153.15 2.022.02 175 175 551 353 0 0 0 0
.DD Fbrgls DoorFbrgls Door 0.1270.127 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0
.WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ee 3.153.15 2.022.02 130 112 354 226 60 54 172 110
.GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ee 16.8216.82 28.1328.13 0 0 0 0 6 0 101 169
11 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ee 16.8216.82 28.1328.13 18 0 299 499 0 0 0 0
GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 ee 17.9817.98 18.7818.78 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ss 3.153.15 2.022.02 0 0 0 0 74 57 178 114
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0
DD Fbrgls DoorFbrgls Door 0.1270.127 ss 3.693.69 3.733.73 0 0 0 0 18 18 66 67
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ww 3.153.15 2.022.02 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ww 16.8216.82 33.9933.99 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ww 16.8216.82 15.8915.89 0 0 0 0 0 0 0 0
DD Fbrgls DoorFbrgls Door 0.1270.127 ww 3.693.69 3.733.73 0 0 0 0 0 0 0 0
PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0
CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.990.99 1.801.80 250 250 248 452 75 75 74 135
FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 250 31 875 0 75 15 416 0
6 c) AED excursion 17 9
Envelope loss/gain 2326 1547 1006 603
12 a) Infiltration 702 196 310 87
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 0 0 0 0
Appliances/other 500 0
Subtotal (lines 6 to 13)3029 2243 1317 689
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 0 0 0 0
14 Subtotal 3029 2243 1317 689
15 Duct loads 30%35%897 782 30%35%390 240
Total room load 3926 3025 1707 930
Air required (cfm)Air required (cfm)215 165 93 51
2021-Nov-23 10:04:19
Right-Suite® Universal 2021 21.0.10 RSU29066 Page 1
...ts\Wrightsoft HVAC\5702 Hickory Dr PSL Prop.rup Calc = MJ8 Front Door faces: N
1447Job:Duct System Summary 3/29/2021Date:Zone 1 Chris BatemanBy:
Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
Project Information
Maui Spec Home, NisAir Air ConditioningFor:
5702 Hickory Dr, Fort Pierce, FL 34982
CoolingHeating
External static pressure in H2O0.85in H2O0.85
Pressure losses in H2O0in H2O0
Available static pressure in H2O0.85in H2O0.85
Supply / return available pressure 0.513 / 0.337 in H2O in H2O0.513 / 0.337
Lowest friction rate in/100ft0.310in/100ft0.310
Actual air flow cfm600cfm600
Total effective length (TEL) ft274
Supply Branch Detail Table
Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv
Name (Btuh)(cfm) (cfm)FR (in)(in)Matl Ln (ft)Ln (ft) Trunk
st4120.036.8VlFx0x05.00.32733611006hBath 2
st4120.045.5VlFx0x07.00.3101481482452hBed 3
st4120.037.5VlFx0x07.00.3261591812999hBed 4
st4120.037.3VlFx0x04.00.3265381cClst
st195.025.2VlFx0x07.00.427180642635cLeisure Area
st195.021.2VlFx0x04.00.4413148799hM Bath 2
st195.024.8VlFx0x06.00.428821081798hMaster Bed 2-A
st195.025.1VlFx0x06.00.427821081798hMaster Bed 2-B
Supply Trunk Detail Table
Trunk Htg Clg Design Veloc Diam H x W Duct
Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk
st4 Peak AVF 392 345 0.310 886 9.0 0x0 VinlFlx st1
st1 Peak AVF 720 720 0.310 674 14.0 0x0 VinlFlx
Bold/italic values have been manually overridden
2021-Nov-23 10:04:19
Right-Suite® Universal 2021 21.0.10 RSU29066 Page 2
...ts\Wrightsoft HVAC\5702 Hickory Dr PSL Prop.rup Calc = MJ8 Front Door faces: N
Return Branch Detail Table
Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct
Name Size (in) (cfm)(cfm)(ft)FR (fpm)(in)(in)Opening (in) Matl Trunk
rb1 0x 1110 70 104.6 0.322 566 6.0 x0 0 VlFx rt1
rb16 0x 2170 164 38.2 0.883 490 9.0 x0 0 VlFx
rb13 0x 1810 159 106.2 0.317 169 14.0 x0 0 VlFx rt1
rb12 0x 1480 148 104.6 0.322 271 10.0 x0 0 VlFx rt1
rb15 0x 640 180 108.8 0.310 515 8.0 x0 0 VlFx rt1
Return Trunk Detail Table
Trunk Htg Clg Design Veloc Diam H x W Duct
Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk
rt1 Peak AVF 503 556 0.310 520 14.0 0x0 VinlFlx
2021-Nov-23 10:04:19
Right-Suite® Universal 2021 21.0.10 RSU29066 Page 3
...ts\Wrightsoft HVAC\5702 Hickory Dr PSL Prop.rup Calc = MJ8 Front Door faces: N
1447Job:Duct System Summary 3/29/2021Date:Zone 2 Chris BatemanBy:
Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
Project Information
Maui Spec Home, NisAir Air ConditioningFor:
5702 Hickory Dr, Fort Pierce, FL 34982
CoolingHeating
External static pressure in H2O0.85in H2O0.85
Pressure losses in H2O0in H2O0
Available static pressure in H2O0.85in H2O0.85
Supply / return available pressure 0.425 / 0.425 in H2O in H2O0.425 / 0.425
Lowest friction rate in/100ft0.704in/100ft0.704
Actual air flow cfm800cfm800
Total effective length (TEL) ft121
Supply Branch Detail Table
Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv
Name (Btuh)(cfm) (cfm)FR (in)(in)Matl Ln (ft)Ln (ft) Trunk
st395.017.9VlFx0x04.00.7531133501hHers
st395.021.6VlFx0x04.00.7291857861hHis
st2100.020.5VlFx0x06.00.7051611072458cKitchen
st2100.020.8VlFx0x06.00.7041611072458cKitchen-A
st395.022.9VlFx0x04.00.7215634852cLaundry
st2100.019.5VlFx0x06.00.7111481272263cLiving Dining
st2100.019.1VlFx0x06.00.7141481272263cLiving Dining-A
st395.018.7VlFx0x05.00.748611121707hM Bath
st395.022.0VlFx0x06.00.726991291963hMaster Bed
st395.017.5VlFx0x06.00.756991291963hMaster Bed-A
Supply Trunk Detail Table
Trunk Htg Clg Design Veloc Diam H x W Duct
Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk
st3 Peak AVF 494 343 0.721 629 12.0 0x0 VinlFlx
st2 Peak AVF 466 617 0.704 785 12.0 0x0 VinlFlx
2021-Nov-23 10:04:19
Right-Suite® Universal 2021 21.0.10 RSU29066 Page 4
...ts\Wrightsoft HVAC\5702 Hickory Dr PSL Prop.rup Calc = MJ8 Front Door faces: N
Return Branch Detail Table
Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct
Name Size (in) (cfm)(cfm)(ft)FR (fpm)(in)(in)Opening (in) Matl Trunk
rsb5 0x 6130 733 0 0 0 0 x0 0 VlFx
rb2 0x 3470 227 0 0 0 0 x0 0 VlFx
2021-Nov-23 10:04:20
Right-Suite® Universal 2021 21.0.10 RSU29066 Page 1
...ts\Wrightsoft HVAC\5702 Hickory Dr PSL Prop.rup Calc = MJ8 Front Door faces: N
1447Job:Manual S Compliance Report 3/29/2021Date:Zone 1 Chris BatemanBy:
Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
Project Information
Maui Spec Home, NisAir Air ConditioningFor:
5702 Hickory Dr, Fort Pierce, FL 34982
Cooling Equipment
Design Conditions
°F77.4Entering coil DB:Btuh11396Sensible gain:°F90.4Outdoor design DB:
°F64.6Entering coil WB:Btuh4231Latent gain:°F77.4Outdoor design WB:
Btuh15627Total gain:°F75.0Indoor design DB:
cfm600Estimated airflow:%50Indoor RH:
Manufacturer's Performance Data at Actual Design Conditions
Split ACEquipment type:
ML14XC1S018-230A**+CBA27UHE-018-230*++TDRModel:LennoxManufacturer:
cfm600Actual airflow:
% of load111Btuh12600Sensible capacity:
% of load128Btuh5400Latent capacity:
%70SHR:% of load115Btuh18000Total capacity:
Heating Equipment
Design Conditions
°F67.1Entering coil DB:Btuh13530Heat loss:°F41.0Outdoor design DB:
°F70.0Indoor design DB:
Manufacturer's Performance Data at Actual Design Conditions
Elec stripEquipment type:
Model:Manufacturer:
cfm600Actual airflow:
°F50Temp. rise:% of load83kW3.3Output capacity:
Meets all requirements of ACCA Manual S.
2021-Nov-23 10:04:20
Right-Suite® Universal 2021 21.0.10 RSU29066 Page 2
...ts\Wrightsoft HVAC\5702 Hickory Dr PSL Prop.rup Calc = MJ8 Front Door faces: N
1447Job:Manual S Compliance Report 3/29/2021Date:Zone 2 Chris BatemanBy:
Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
Project Information
Maui Spec Home, NisAir Air ConditioningFor:
5702 Hickory Dr, Fort Pierce, FL 34982
Cooling Equipment
Design Conditions
°F77.1Entering coil DB:Btuh15679Sensible gain:°F90.4Outdoor design DB:
°F64.3Entering coil WB:Btuh5360Latent gain:°F77.4Outdoor design WB:
Btuh21039Total gain:°F75.0Indoor design DB:
cfm800Estimated airflow:%50Indoor RH:
Manufacturer's Performance Data at Actual Design Conditions
Split ACEquipment type:
ML14XC1S024-230A**+CBA27UHE-024-230*++TDRModel:LennoxManufacturer:
cfm800Actual airflow:
% of load107Btuh16800Sensible capacity:
% of load134Btuh7200Latent capacity:
%70SHR:% of load114Btuh24000Total capacity:
Heating Equipment
Design Conditions
°F67.4Entering coil DB:Btuh16470Heat loss:°F41.0Outdoor design DB:
°F70.0Indoor design DB:
Manufacturer's Performance Data at Actual Design Conditions
Elec stripEquipment type:
Model:Manufacturer:
cfm800Actual airflow:
°F50Temp. rise:% of load99kW4.8Output capacity:
Meets all requirements of ACCA Manual S.