HomeMy WebLinkAboutAPPROVED NEW Manual J UpdatedCalculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Nov-12 13:15:43
Right-Suite® Universal 2021 21.0.10 RSU29066 Page 1
...ments\Wrightsoft HVAC\1916 Lynx Dr PSL Prop.rup Calc = MJ8 Front Door faces: N
1554Job:Load Short Form 7/12/2021Date:House Chris BatemanBy:
Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
Project Information
Zaros Residence, NisAir Air ConditioningFor:
1916 Lynx Dr, Fort Pierce, FL 34949
Design Information
InfiltrationClgHtg
SimplifiedMethod9041Outside db (°F)
AverageConstruction quality7570Inside db (°F)
0Fireplaces1529Design TD (°F)
L-Daily range
5030Inside humidity (%)
572Moisture difference (gr/lb)
HEATING EQUIPMENT COOLING EQUIPMENT
Make Make Lennox
Trade Trade LENNOX
Model Cond ML14XC1S042-230A**
AHRI ref Coil CBA27UHE-042-230*++TDR
AHRI ref 10259441
Efficiency 100 EFF Efficiency 13.0 EER, 16 SEER
Heating input kW9.6 Sensible cooling Btuh29400
Heating output Btuh32602 Latent cooling Btuh12600
Temperature rise °F21 Total cooling Btuh42000
Actual air flow cfm1400 Actual air flow cfm1400
Air flow factor cfm/Btuh0.040 Air flow factor cfm/Btuh0.049
Static pressure in H2O0.70 Static pressure in H2O0.70
Space thermostat Load sensible heat ratio 0.78
ROOM NAME Area Htg load Clg load Htg AVF Clg AVF
(ft²)(Btuh)(Btuh)(cfm)(cfm)
Master Bed 288 5537 5153 220 253
WIC 78 1524 596 61 29
Bed 2 193 2436 1537 97 75
Bath 52 872 426 35 21
Bed 3 209 5118 3060 203 150
Foyer 126 2557 1438 101 70
Hall 2 34 0 0 0 0
Lin 5 0 0 0 0
Laundry 81 1589 1218 63 60
Dining 288 2588 1500 103 74
Pantry 48 1201 456 48 22
Bath 2 36 88 73 3 4
Living 545 4697 5292 186 259
Kit Nook 291 5578 7097 221 348
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Nov-12 13:15:43
Right-Suite® Universal 2021 21.0.10 RSU29066 Page 2
...ments\Wrightsoft HVAC\1916 Lynx Dr PSL Prop.rup Calc = MJ8 Front Door faces: N
Master Bath 148 1436 669 57 33
Wtr Clst 24 49 41 2 2
Hall 24 0 0 0 0
House 2469 35269 28555 1400 1400
Other equip loads 1743 926
Equip. @ 0.95 RSM 28124
Latent cooling 8220
TOTALS 2469 37012 36344 1400 1400
2021-Nov-12 13:15:43
Right-Suite® Universal 2021 21.0.10 RSU29066 Page 1
...ments\Wrightsoft HVAC\1916 Lynx Dr PSL Prop.rup Calc = MJ8 Front Door faces: N
1554Job:Building Analysis 7/12/2021Date:House Chris BatemanBy:
Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
Project Information
Zaros Residence, NisAir Air ConditioningFor:
1916 Lynx Dr, Fort Pierce, FL 34949
Design Conditions
Location: CoolingHeatingIndoor:7570Indoor temperature (°F)St Lucie Co Intl, FL, US
1529Design TD (°F)ft26Elevation:
5030Relative humidity (%)°N28Latitude:
Outdoor:56.92.4Moisture difference (gr/lb)CoolingHeating
Infiltration:9041Dry bulb (°F)
SimplifiedMethod)L(15-Daily range (°F)
AverageConstruction quality77-Wet bulb (°F)
0Fireplaces7.515.0Wind speed (mph)
Heating
Walls
Glazing
Ceilings
Floors
Infiltration
Ducts
Ventilation
% of loadBtuhBtuh/ft²Component
16.260063.1Walls
17.5648615.2Glazing
000Doors
10.538921.6Ceilings
17.966422.72.7Floors
11.643042.2Infiltration
21.47938Ducts
00Piping
00Humidification
4.71743Ventilation0Adjustments
100.037012Total
Cooling
Walls
Glazing
Ceilings Infiltration
Ducts
Internal Gains
Ventilation
% of loadBtuhBtuh/ft²Component
12.536821.9Walls
26.3776118.2Glazing
000Doors
10.229981.2Ceilings
000Floors
3.911430.6Infiltration
30.08850Ducts
3.1926Ventilation
14.04120Internal gains
00Blower
0Adjustments
100.029480Total
Latent Cooling Load = 8220 Btuh
Overall U-value = 0.221 Btuh/ft²-°F
Data entries checked.
2021-Nov-12 13:15:43
Right-Suite® Universal 2021 21.0.10 RSU29066 Page 1
...ments\Wrightsoft HVAC\1916 Lynx Dr PSL Prop.rup Calc = MJ8 Front Door faces: N
1554Job:Component Constructions 7/12/2021Date:House Chris BatemanBy:
Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
Project Information
Zaros Residence, NisAir Air ConditioningFor:
1916 Lynx Dr, Fort Pierce, FL 34949
Design Conditions
Location: CoolingHeatingIndoor:
7570Indoor temperature (°F)St Lucie Co Intl, FL, US
1529Design TD (°F)ft26Elevation:
5030Relative humidity (%)°N28Latitude:
Outdoor:56.92.4Moisture difference (gr/lb)CoolingHeating
Infiltration:9041Dry bulb (°F)
SimplifiedMethod)L(15-Daily range (°F)
AverageConstruction quality77-Wet bulb (°F)
0Fireplaces7.515.0Wind speed (mph)
Construction descriptions GainLoss Clg HTMHtg HTMInsul RU-valueAreaOr
BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft²
Walls
Blk Wall, Stuc Ext, R-4.2 Ext Bd Ins, 8" Thk, 1/2" Gyp Bd Int Fnsh 21603.125.20.107693n 13821.99
3271.995113.125.20.107164e
9371.9914653.125.20.107470s
691.991083.125.20.10735sw
4141.996473.125.20.107208w
31291.9948923.125.20.1071569all
Partitions
Frm Wall, 1/2" Gyp Bd Ext, R-11 Cav Ins, 1/2" Gyp Bd Int Fnsh, 2"x4", 16"
OC Stud
5531.4611152.9411.00.101379
Windows
Impact: Impact; NFRC rated (SHGC=0.18); 50% blinds 45°, medium;
50% outdoor insect screen; foreground = green grass (0.23); 1 ft overhang
(1.67 ft window ht, 1 ft sep.); 8 ft head ht
598.828713.000.4507n
Impact: Impact; NFRC rated (SHGC=0.18); 50% blinds 45°, medium;
50% outdoor insect screen; foreground = green grass (0.23); 1 ft overhang
(2 ft window ht, 1 ft sep.); 8 ft head ht
1418.8220913.000.45016n
Impact: Impact; NFRC rated (SHGC=0.24); 50% blinds 45°, medium;
50% outdoor insect screen; foreground = green grass (0.23); 1 ft overhang
(3.17 ft window ht, 1 ft sep.); 8 ft head ht
10911.516016.800.58010n
Impact: Impact; NFRC rated (SHGC=0.24); 50% blinds 45°, medium;
50% outdoor insect screen; foreground = green grass (0.23); 1 ft overhang
(5.17 ft window ht, 1 ft sep.); 8 ft head ht
25711.537716.800.58022n
25711.537716.800.58022n
30513.637716.800.58022s
47921.836916.800.58022sw
63028.137716.800.58022w
192817.3187616.800.580112all
Impact: Impact; NFRC rated (SHGC=0.19); 50% blinds 45°, medium;
50% outdoor insect screen; foreground = green grass (0.23); 10.5 ft
overhang (5.2 ft window ht, 1 ft sep.); 8 ft head ht
949.02938.9900.31010e
2349.022348.9900.31026e
3289.023278.9900.31036all
Impact: Impact; NFRC rated (SHGC=0.22); 50% blinds 45°, medium;
50% outdoor insect screen; foreground = green grass (0.23); 1 ft overhang
(5.17 ft window ht, 1 ft sep.); 8 ft head ht
60927.240318.000.62022e
2021-Nov-12 13:15:43
Right-Suite® Universal 2021 21.0.10 RSU29066 Page 2
...ments\Wrightsoft HVAC\1916 Lynx Dr PSL Prop.rup Calc = MJ8 Front Door faces: N
Impact: Impact; NFRC rated (SHGC=0.19); 50% blinds 45°, medium;
50% outdoor insect screen; foreground = green grass (0.23); 10.5 ft
overhang (8 ft window ht, 1 ft sep.); 8 ft head ht
2269.432168.9900.31024e
Impact: Impact; NFRC rated (SHGC=0.18); 50% blinds 45°, medium;
50% outdoor insect screen; foreground = green grass (0.23); 1 ft overhang
(3.7 ft window ht, 1 ft sep.); 8 ft head ht
18710.822513.000.45017s
Impact: Impact; NFRC rated (SHGC=0.19); 50% blinds 45°, medium;
50% outdoor insect screen; foreground = green grass (0.23); 1 ft overhang
(5.2 ft window ht, 1 ft sep.); 8 ft head ht
4289.154218.9900.31047s
Impact: Impact; NFRC rated (SHGC=0.21); 50% blinds 45°, medium;
50% outdoor insect screen; foreground = green grass (0.23); 10 ft
overhang (8 ft window ht, 1 ft sep.); 8 ft head ht
96915.1120618.800.65064w
109015.1135718.800.65072w
205915.1256418.800.650136all
Doors
(none)
Ceilings
Attic, Shngls, R-20 Ceil Ins, 5/8" Gyp Bd Int Fnsh 0.3862469 29981.2138921.5821.0
Floors
On Grade Depth, Tile Flr Fnsh 00664228.700.989232
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Nov-12 13:15:43
Right-Suite® Universal 2021 21.0.10 RSU29066 Page 1
...ments\Wrightsoft HVAC\1916 Lynx Dr PSL Prop.rup Calc = MJ8 Front Door faces: N
1554Job:Project Summary 7/12/2021Date:House Chris BatemanBy:
Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
Project Information
Zaros Residence, NisAir Air ConditioningFor:1916 Lynx Dr, Fort Pierce, FL 34949
Notes:
Design Information
St Lucie Co Intl, FL, USWeather:
Winter Design Conditions Summer Design Conditions
Outside db °F41 Outside db °F90Inside db °F70 Inside db °F75
Design TD °F29 Design TD °F15Daily range L
Relative humidity %50Moisture difference gr/lb57
Heating Summary Sensible Cooling Equipment Load Sizing
Structure Btuh27331 Structure Btuh19705
Ducts Btuh7938 Ducts Btuh8850Central vent (55 cfm) 1743 Btuh Central vent (55 cfm) Btuh926
Outside air Outside airHumidification Btuh0 Blower Btuh0
Piping Btuh0Equipment load Btuh37012 Use manufacturer's data n
Rate/swing multiplier 0.95InfiltrationEquipment sensible load Btuh28124
Method Latent Cooling Equipment Load SizingSimplified
Construction quality Average0Fireplaces Structure Btuh3409
Ducts Btuh2697Central vent (55 cfm) Btuh2113
CoolingHeating Outside air24692469Area (ft²) Equipment latent load Btuh8220
2532325323Volume (ft³)Air changes/hour 0.160.32 Equipment Total Load (Sen+Lat)Btuh36344
Equiv. AVF (cfm) 68135 Req. total capacity at 0.70 SHR ton3.3
Heating Equipment Summary Cooling Equipment Summary
Make Make LennoxTrade Trade LENNOX
Model Cond ML14XC1S042-230A**AHRI ref Coil CBA27UHE-042-230*++TDR
AHRI ref 10259441Efficiency 100 EFF Efficiency 13.0 EER, 16 SEER
Heating input kW9.6 Sensible cooling Btuh29400Heating output Btuh32602 Latent cooling Btuh12600
Temperature rise °F21 Total cooling Btuh42000Actual air flow cfm1400 Actual air flow cfm1400
Air flow factor cfm/Btuh0.040 Air flow factor cfm/Btuh0.049Static pressure in H2O0.70 Static pressure in H2O0.70
Space thermostat Load sensible heat ratio 0.78
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Nov-12 13:15:43Right-Suite® Universal 2021 21.0.10 RSU29066 Page 1...ments\Wrightsoft HVAC\1916 Lynx Dr PSL Prop.rup Calc = MJ8 Front Door faces: N
1554Job:Right-J® Worksheet 7/12/2021Date:House Chris BatemanBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name House Master Bed
2 Exposed wall 231.6 ft 31.0 ft
3 Room height 10.3 ft 10.0 heat/coolft
4 Room dimensions ft287.5x1.0
5 Room area 2468.8 ft²287.5 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW Blk Wall, Stuc Ext, 0.107Blk Wall, Stuc Ext, 0.107 nn 3.123.12 1.991.99 770 693 2160 1382 175 153 476 304
.GG ImpactImpact 0.4500.450 nn 13.0513.05 8.828.82 7 0 87 59 0 0 0 0
.GG ImpactImpact 0.4500.450 nn 13.0513.05 8.828.82 16 0 209 141 0 0 0 0
.GG ImpactImpact 0.5800.580 nn 16.8216.82 11.4811.48 10 0 160 109 0 0 0 0
11 GG ImpactImpact 0.5800.580 nn 16.8216.82 11.4811.48 22 0 377 257 22 0 377 257
GG ImpactImpact 0.5800.580 nn 16.8216.82 11.4811.48 22 0 377 257 0 0 0 0
WW Blk Wall, Stuc Ext, 0.107Blk Wall, Stuc Ext, 0.107 ee 3.123.12 1.991.99 247 164 511 327 0 0 0 0
GG ImpactImpact 0.3100.310 ee 8.998.99 9.029.02 10 10 93 94 0 0 0 0
GG ImpactImpact 0.3100.310 ee 8.998.99 9.029.02 26 26 234 234 0 0 0 0
GG ImpactImpact 0.6200.620 ee 17.9817.98 27.1827.18 22 0 403 609 0 0 0 0
GG ImpactImpact 0.3100.310 ee 8.998.99 9.439.43 24 23 216 226 0 0 0 0
WW Blk Wall, Stuc Ext, 0.107Blk Wall, Stuc Ext, 0.107 ss 3.123.12 1.991.99 557 470 1465 937 0 0 0 0
GG ImpactImpact 0.4500.450 ss 13.0513.05 10.8210.82 17 17 225 187 0 0 0 0
GG ImpactImpact 0.3100.310 ss 8.998.99 9.159.15 47 40 421 428 0 0 0 0
GG ImpactImpact 0.5800.580 ss 16.8216.82 13.6313.63 22 19 377 305 0 0 0 0
WW Blk Wall, Stuc Ext, 0.107Blk Wall, Stuc Ext, 0.107 swsw 3.123.12 1.991.99 57 35 108 69 0 0 0 0
GG ImpactImpact 0.5800.580 swsw 16.8216.82 21.8121.81 22 3 369 479 0 0 0 0
WW Blk Wall, Stuc Ext, 0.107Blk Wall, Stuc Ext, 0.107 ww 3.123.12 1.991.99 366 208 647 414 135 71 221 142
GG ImpactImpact 0.5800.580 ww 16.8216.82 28.1328.13 22 0 377 630 0 0 0 0
GG ImpactImpact 0.6500.650 ww 18.8518.85 15.1415.14 64 58 1206 969 64 58 1206 969
GG ImpactImpact 0.6500.650 ww 18.8518.85 15.1415.14 72 66 1357 1090 0 0 0 0
PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 379 379 1115 553 0 0 0 0
CC Attic, Shngls, R-20 0.386Attic, Shngls, R-20 0.386 --1.581.58 1.211.21 2469 2469 3892 2998 288 288 453 349
FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 2469 232 6642 0 288 31 889 0
6 c) AED excursion 1687 858
Envelope loss/gain 23027 14442 3622 2879
12 a) Infiltration 4304 1143 669 178
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 4 920 0 0
Appliances/other 3200 500
Subtotal (lines 6 to 13)27331 19705 4291 3556
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 0 0 0 0
14 Subtotal 27331 19705 4291 3556
15 Duct loads 29%45%7938 8850 29%45%1246 1597
Total room load 35269 28555 5537 5153
Air required (cfm)Air required (cfm)1400 1400 220 253
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Nov-12 13:15:43Right-Suite® Universal 2021 21.0.10 RSU29066 Page 2...ments\Wrightsoft HVAC\1916 Lynx Dr PSL Prop.rup Calc = MJ8 Front Door faces: N
1554Job:Right-J® Worksheet 7/12/2021Date:House Chris BatemanBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name WIC Bed 2
2 Exposed wall 13.0 ft 15.5 ft
3 Room height 10.0 heat/coolft 10.0 heat/coolft
4 Room dimensions ft6.0x13.0 ft192.8x1.0
5 Room area 78.0 ft²192.8 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW Blk Wall, Stuc Ext, 0.107Blk Wall, Stuc Ext, 0.107 nn 3.123.12 1.991.99 130 130 405 259 155 133 413 264
.GG ImpactImpact 0.4500.450 nn 13.0513.05 8.828.82 0 0 0 0 0 0 0 0
.GG ImpactImpact 0.4500.450 nn 13.0513.05 8.828.82 0 0 0 0 0 0 0 0
.GG ImpactImpact 0.5800.580 nn 16.8216.82 11.4811.48 0 0 0 0 0 0 0 0
11 GG ImpactImpact 0.5800.580 nn 16.8216.82 11.4811.48 0 0 0 0 0 0 0 0
GG ImpactImpact 0.5800.580 nn 16.8216.82 11.4811.48 0 0 0 0 22 0 377 257
WW Blk Wall, Stuc Ext, 0.107Blk Wall, Stuc Ext, 0.107 ee 3.123.12 1.991.99 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3100.310 ee 8.998.99 9.029.02 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3100.310 ee 8.998.99 9.029.02 0 0 0 0 0 0 0 0
GG ImpactImpact 0.6200.620 ee 17.9817.98 27.1827.18 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3100.310 ee 8.998.99 9.439.43 0 0 0 0 0 0 0 0
WW Blk Wall, Stuc Ext, 0.107Blk Wall, Stuc Ext, 0.107 ss 3.123.12 1.991.99 0 0 0 0 0 0 0 0
GG ImpactImpact 0.4500.450 ss 13.0513.05 10.8210.82 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3100.310 ss 8.998.99 9.159.15 0 0 0 0 0 0 0 0
GG ImpactImpact 0.5800.580 ss 16.8216.82 13.6313.63 0 0 0 0 0 0 0 0
WW Blk Wall, Stuc Ext, 0.107Blk Wall, Stuc Ext, 0.107 swsw 3.123.12 1.991.99 0 0 0 0 0 0 0 0
GG ImpactImpact 0.5800.580 swsw 16.8216.82 21.8121.81 0 0 0 0 0 0 0 0
WW Blk Wall, Stuc Ext, 0.107Blk Wall, Stuc Ext, 0.107 ww 3.123.12 1.991.99 0 0 0 0 0 0 0 0
GG ImpactImpact 0.5800.580 ww 16.8216.82 28.1328.13 0 0 0 0 0 0 0 0
GG ImpactImpact 0.6500.650 ww 18.8518.85 15.1415.14 0 0 0 0 0 0 0 0
GG ImpactImpact 0.6500.650 ww 18.8518.85 15.1415.14 0 0 0 0 0 0 0 0
PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0
CC Attic, Shngls, R-20 0.386Attic, Shngls, R-20 0.386 --1.581.58 1.211.21 78 78 123 95 193 193 304 234
FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 78 13 373 0 193 16 445 0
6 c) AED excursion -17 -44
Envelope loss/gain 901 337 1538 711
12 a) Infiltration 280 74 334 89
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 0 0 0 0
Appliances/other 0 250
Subtotal (lines 6 to 13)1181 411 1873 1050
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 0 0 15 11
14 Subtotal 1181 411 1888 1061
15 Duct loads 29%45%343 185 29%45%548 476
Total room load 1524 596 2436 1537
Air required (cfm)Air required (cfm)61 29 97 75
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Nov-12 13:15:43Right-Suite® Universal 2021 21.0.10 RSU29066 Page 3...ments\Wrightsoft HVAC\1916 Lynx Dr PSL Prop.rup Calc = MJ8 Front Door faces: N
1554Job:Right-J® Worksheet 7/12/2021Date:House Chris BatemanBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name Bath Bed 3
2 Exposed wall 5.5 ft 38.5 ft
3 Room height 10.0 heat/coolft 10.0 heat/coolft
4 Room dimensions ft9.5x5.5 ft13.5x15.5
5 Room area 52.3 ft²209.3 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW Blk Wall, Stuc Ext, 0.107Blk Wall, Stuc Ext, 0.107 nn 3.123.12 1.991.99 55 46 142 91 155 139 433 277
.GG ImpactImpact 0.4500.450 nn 13.0513.05 8.828.82 0 0 0 0 0 0 0 0
.GG ImpactImpact 0.4500.450 nn 13.0513.05 8.828.82 0 0 0 0 16 0 209 141
.GG ImpactImpact 0.5800.580 nn 16.8216.82 11.4811.48 10 0 160 109 0 0 0 0
11 GG ImpactImpact 0.5800.580 nn 16.8216.82 11.4811.48 0 0 0 0 0 0 0 0
GG ImpactImpact 0.5800.580 nn 16.8216.82 11.4811.48 0 0 0 0 0 0 0 0
WW Blk Wall, Stuc Ext, 0.107Blk Wall, Stuc Ext, 0.107 ee 3.123.12 1.991.99 0 0 0 0 135 113 351 225
GG ImpactImpact 0.3100.310 ee 8.998.99 9.029.02 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3100.310 ee 8.998.99 9.029.02 0 0 0 0 0 0 0 0
GG ImpactImpact 0.6200.620 ee 17.9817.98 27.1827.18 0 0 0 0 22 0 403 609
GG ImpactImpact 0.3100.310 ee 8.998.99 9.439.43 0 0 0 0 0 0 0 0
WW Blk Wall, Stuc Ext, 0.107Blk Wall, Stuc Ext, 0.107 ss 3.123.12 1.991.99 0 0 0 0 95 95 296 189
GG ImpactImpact 0.4500.450 ss 13.0513.05 10.8210.82 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3100.310 ss 8.998.99 9.159.15 0 0 0 0 0 0 0 0
GG ImpactImpact 0.5800.580 ss 16.8216.82 13.6313.63 0 0 0 0 0 0 0 0
WW Blk Wall, Stuc Ext, 0.107Blk Wall, Stuc Ext, 0.107 swsw 3.123.12 1.991.99 0 0 0 0 0 0 0 0
GG ImpactImpact 0.5800.580 swsw 16.8216.82 21.8121.81 0 0 0 0 0 0 0 0
WW Blk Wall, Stuc Ext, 0.107Blk Wall, Stuc Ext, 0.107 ww 3.123.12 1.991.99 0 0 0 0 0 0 0 0
GG ImpactImpact 0.5800.580 ww 16.8216.82 28.1328.13 0 0 0 0 0 0 0 0
GG ImpactImpact 0.6500.650 ww 18.8518.85 15.1415.14 0 0 0 0 0 0 0 0
GG ImpactImpact 0.6500.650 ww 18.8518.85 15.1415.14 0 0 0 0 0 0 0 0
PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0
CC Attic, Shngls, R-20 0.386Attic, Shngls, R-20 0.386 --1.581.58 1.211.21 52 52 82 63 209 209 330 254
FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 52 6 158 0 209 39 1104 0
6 c) AED excursion -12 -61
Envelope loss/gain 542 251 3126 1634
12 a) Infiltration 119 31 830 220
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 0 0 0 0
Appliances/other 0 250
Subtotal (lines 6 to 13)660 283 3956 2104
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 15 11 10 7
14 Subtotal 676 294 3966 2112
15 Duct loads 29%45%196 132 29%45%1152 948
Total room load 872 426 5118 3060
Air required (cfm)Air required (cfm)35 21 203 150
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Nov-12 13:15:43Right-Suite® Universal 2021 21.0.10 RSU29066 Page 4...ments\Wrightsoft HVAC\1916 Lynx Dr PSL Prop.rup Calc = MJ8 Front Door faces: N
1554Job:Right-J® Worksheet 7/12/2021Date:House Chris BatemanBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name Foyer Hall 2
2 Exposed wall 18.5 ft 0 ft
3 Room height 12.4 heat/coolft 10.0 heat/coolft
4 Room dimensions ft7.0x18.0 ft4.0x8.5
5 Room area 126.0 ft²34.0 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW Blk Wall, Stuc Ext, 0.107Blk Wall, Stuc Ext, 0.107 nn 3.123.12 1.991.99 0 0 0 0 0 0 0 0
.GG ImpactImpact 0.4500.450 nn 13.0513.05 8.828.82 0 0 0 0 0 0 0 0
.GG ImpactImpact 0.4500.450 nn 13.0513.05 8.828.82 0 0 0 0 0 0 0 0
.GG ImpactImpact 0.5800.580 nn 16.8216.82 11.4811.48 0 0 0 0 0 0 0 0
11 GG ImpactImpact 0.5800.580 nn 16.8216.82 11.4811.48 0 0 0 0 0 0 0 0
GG ImpactImpact 0.5800.580 nn 16.8216.82 11.4811.48 0 0 0 0 0 0 0 0
WW Blk Wall, Stuc Ext, 0.107Blk Wall, Stuc Ext, 0.107 ee 3.123.12 1.991.99 87 26 82 53 0 0 0 0
GG ImpactImpact 0.3100.310 ee 8.998.99 9.029.02 10 10 93 94 0 0 0 0
GG ImpactImpact 0.3100.310 ee 8.998.99 9.029.02 26 26 234 234 0 0 0 0
GG ImpactImpact 0.6200.620 ee 17.9817.98 27.1827.18 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3100.310 ee 8.998.99 9.439.43 24 23 216 226 0 0 0 0
WW Blk Wall, Stuc Ext, 0.107Blk Wall, Stuc Ext, 0.107 ss 3.123.12 1.991.99 0 0 0 0 0 0 0 0
GG ImpactImpact 0.4500.450 ss 13.0513.05 10.8210.82 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3100.310 ss 8.998.99 9.159.15 0 0 0 0 0 0 0 0
GG ImpactImpact 0.5800.580 ss 16.8216.82 13.6313.63 0 0 0 0 0 0 0 0
WW Blk Wall, Stuc Ext, 0.107Blk Wall, Stuc Ext, 0.107 swsw 3.123.12 1.991.99 0 0 0 0 0 0 0 0
GG ImpactImpact 0.5800.580 swsw 16.8216.82 21.8121.81 0 0 0 0 0 0 0 0
WW Blk Wall, Stuc Ext, 0.107Blk Wall, Stuc Ext, 0.107 ww 3.123.12 1.991.99 0 0 0 0 0 0 0 0
GG ImpactImpact 0.5800.580 ww 16.8216.82 28.1328.13 0 0 0 0 0 0 0 0
GG ImpactImpact 0.6500.650 ww 18.8518.85 15.1415.14 0 0 0 0 0 0 0 0
GG ImpactImpact 0.6500.650 ww 18.8518.85 15.1415.14 0 0 0 0 0 0 0 0
PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 143 143 419 208 0 0 0 0
CC Attic, Shngls, R-20 0.386Attic, Shngls, R-20 0.386 --1.581.58 1.211.21 126 126 199 153 34 34 54 41
FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 126 19 531 0 34 0 0 0
6 c) AED excursion -41 -2
Envelope loss/gain 1773 927 54 40
12 a) Infiltration 187 50 0 0
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 0 0 0 0
Appliances/other 0 0
Subtotal (lines 6 to 13)1961 977 54 40
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 21 15 -54 -40
14 Subtotal 1981 992 0 0
15 Duct loads 29%45%575 446 29%45%0 0
Total room load 2557 1438 0 0
Air required (cfm)Air required (cfm)101 70 0 0
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Nov-12 13:15:43Right-Suite® Universal 2021 21.0.10 RSU29066 Page 5...ments\Wrightsoft HVAC\1916 Lynx Dr PSL Prop.rup Calc = MJ8 Front Door faces: N
1554Job:Right-J® Worksheet 7/12/2021Date:House Chris BatemanBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name Lin Laundry
2 Exposed wall 0 ft 19.0 ft
3 Room height 10.0 heat/coolft 10.0 heat/coolft
4 Room dimensions ft1.5x3.0 ft12.5x6.5
5 Room area 4.5 ft²81.3 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW Blk Wall, Stuc Ext, 0.107Blk Wall, Stuc Ext, 0.107 nn 3.123.12 1.991.99 0 0 0 0 0 0 0 0
.GG ImpactImpact 0.4500.450 nn 13.0513.05 8.828.82 0 0 0 0 0 0 0 0
.GG ImpactImpact 0.4500.450 nn 13.0513.05 8.828.82 0 0 0 0 0 0 0 0
.GG ImpactImpact 0.5800.580 nn 16.8216.82 11.4811.48 0 0 0 0 0 0 0 0
11 GG ImpactImpact 0.5800.580 nn 16.8216.82 11.4811.48 0 0 0 0 0 0 0 0
GG ImpactImpact 0.5800.580 nn 16.8216.82 11.4811.48 0 0 0 0 0 0 0 0
WW Blk Wall, Stuc Ext, 0.107Blk Wall, Stuc Ext, 0.107 ee 3.123.12 1.991.99 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3100.310 ee 8.998.99 9.029.02 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3100.310 ee 8.998.99 9.029.02 0 0 0 0 0 0 0 0
GG ImpactImpact 0.6200.620 ee 17.9817.98 27.1827.18 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3100.310 ee 8.998.99 9.439.43 0 0 0 0 0 0 0 0
WW Blk Wall, Stuc Ext, 0.107Blk Wall, Stuc Ext, 0.107 ss 3.123.12 1.991.99 0 0 0 0 0 0 0 0
GG ImpactImpact 0.4500.450 ss 13.0513.05 10.8210.82 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3100.310 ss 8.998.99 9.159.15 0 0 0 0 0 0 0 0
GG ImpactImpact 0.5800.580 ss 16.8216.82 13.6313.63 0 0 0 0 0 0 0 0
WW Blk Wall, Stuc Ext, 0.107Blk Wall, Stuc Ext, 0.107 swsw 3.123.12 1.991.99 0 0 0 0 0 0 0 0
GG ImpactImpact 0.5800.580 swsw 16.8216.82 21.8121.81 0 0 0 0 0 0 0 0
WW Blk Wall, Stuc Ext, 0.107Blk Wall, Stuc Ext, 0.107 ww 3.123.12 1.991.99 0 0 0 0 0 0 0 0
GG ImpactImpact 0.5800.580 ww 16.8216.82 28.1328.13 0 0 0 0 0 0 0 0
GG ImpactImpact 0.6500.650 ww 18.8518.85 15.1415.14 0 0 0 0 0 0 0 0
GG ImpactImpact 0.6500.650 ww 18.8518.85 15.1415.14 0 0 0 0 0 0 0 0
PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 190 190 558 277
CC Attic, Shngls, R-20 0.386Attic, Shngls, R-20 0.386 --1.581.58 1.211.21 5 5 7 5 81 81 128 99
FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 5 0 0 0 81 19 545 0
6 c) AED excursion 0 -36
Envelope loss/gain 7 5 1231 340
12 a) Infiltration 0 0 0 0
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 0 0 0 0
Appliances/other 0 500
Subtotal (lines 6 to 13)7 5 1231 840
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution -7 -5 0 0
14 Subtotal 0 0 1231 840
15 Duct loads 29%45%0 0 29%45%358 377
Total room load 0 0 1589 1218
Air required (cfm)Air required (cfm)0 0 63 60
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Nov-12 13:15:43Right-Suite® Universal 2021 21.0.10 RSU29066 Page 6...ments\Wrightsoft HVAC\1916 Lynx Dr PSL Prop.rup Calc = MJ8 Front Door faces: N
1554Job:Right-J® Worksheet 7/12/2021Date:House Chris BatemanBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name Dining Pantry
2 Exposed wall 16.5 ft 10.5 ft
3 Room height 10.4 heat/coolft 10.0 heat/coolft
4 Room dimensions ft24.0x12.0 ft6.0x8.0
5 Room area 288.0 ft²48.0 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW Blk Wall, Stuc Ext, 0.107Blk Wall, Stuc Ext, 0.107 nn 3.123.12 1.991.99 0 0 0 0 0 0 0 0
.GG ImpactImpact 0.4500.450 nn 13.0513.05 8.828.82 0 0 0 0 0 0 0 0
.GG ImpactImpact 0.4500.450 nn 13.0513.05 8.828.82 0 0 0 0 0 0 0 0
.GG ImpactImpact 0.5800.580 nn 16.8216.82 11.4811.48 0 0 0 0 0 0 0 0
11 GG ImpactImpact 0.5800.580 nn 16.8216.82 11.4811.48 0 0 0 0 0 0 0 0
GG ImpactImpact 0.5800.580 nn 16.8216.82 11.4811.48 0 0 0 0 0 0 0 0
WW Blk Wall, Stuc Ext, 0.107Blk Wall, Stuc Ext, 0.107 ee 3.123.12 1.991.99 0 0 0 0 25 25 78 50
GG ImpactImpact 0.3100.310 ee 8.998.99 9.029.02 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3100.310 ee 8.998.99 9.029.02 0 0 0 0 0 0 0 0
GG ImpactImpact 0.6200.620 ee 17.9817.98 27.1827.18 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3100.310 ee 8.998.99 9.439.43 0 0 0 0 0 0 0 0
WW Blk Wall, Stuc Ext, 0.107Blk Wall, Stuc Ext, 0.107 ss 3.123.12 1.991.99 125 78 243 156 80 80 249 159
GG ImpactImpact 0.4500.450 ss 13.0513.05 10.8210.82 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3100.310 ss 8.998.99 9.159.15 47 40 421 428 0 0 0 0
GG ImpactImpact 0.5800.580 ss 16.8216.82 13.6313.63 0 0 0 0 0 0 0 0
WW Blk Wall, Stuc Ext, 0.107Blk Wall, Stuc Ext, 0.107 swsw 3.123.12 1.991.99 0 0 0 0 0 0 0 0
GG ImpactImpact 0.5800.580 swsw 16.8216.82 21.8121.81 0 0 0 0 0 0 0 0
WW Blk Wall, Stuc Ext, 0.107Blk Wall, Stuc Ext, 0.107 ww 3.123.12 1.991.99 0 0 0 0 0 0 0 0
GG ImpactImpact 0.5800.580 ww 16.8216.82 28.1328.13 0 0 0 0 0 0 0 0
GG ImpactImpact 0.6500.650 ww 18.8518.85 15.1415.14 0 0 0 0 0 0 0 0
GG ImpactImpact 0.6500.650 ww 18.8518.85 15.1415.14 0 0 0 0 0 0 0 0
PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 47 47 137 68 0 0 0 0
CC Attic, Shngls, R-20 0.386Attic, Shngls, R-20 0.386 --1.581.58 1.211.21 288 288 454 350 48 48 76 58
FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 288 17 473 0 48 11 301 0
6 c) AED excursion -44 -13
Envelope loss/gain 1729 958 704 254
12 a) Infiltration 269 71 226 60
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 0 0 0 0
Appliances/other 0 0
Subtotal (lines 6 to 13)1998 1030 931 314
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 8 6 0 0
14 Subtotal 2005 1035 931 314
15 Duct loads 29%45%582 465 29%45%270 141
Total room load 2588 1500 1201 456
Air required (cfm)Air required (cfm)103 74 48 22
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Nov-12 13:15:43Right-Suite® Universal 2021 21.0.10 RSU29066 Page 7...ments\Wrightsoft HVAC\1916 Lynx Dr PSL Prop.rup Calc = MJ8 Front Door faces: N
1554Job:Right-J® Worksheet 7/12/2021Date:House Chris BatemanBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name Bath 2 Living
2 Exposed wall 0 ft 19.5 ft
3 Room height 10.0 heat/coolft 10.4 heat/coolft
4 Room dimensions ft6.0x6.0 ft545.3x1.0
5 Room area 36.0 ft²545.3 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW Blk Wall, Stuc Ext, 0.107Blk Wall, Stuc Ext, 0.107 nn 3.123.12 1.991.99 0 0 0 0 0 0 0 0
.GG ImpactImpact 0.4500.450 nn 13.0513.05 8.828.82 0 0 0 0 0 0 0 0
.GG ImpactImpact 0.4500.450 nn 13.0513.05 8.828.82 0 0 0 0 0 0 0 0
.GG ImpactImpact 0.5800.580 nn 16.8216.82 11.4811.48 0 0 0 0 0 0 0 0
11 GG ImpactImpact 0.5800.580 nn 16.8216.82 11.4811.48 0 0 0 0 0 0 0 0
GG ImpactImpact 0.5800.580 nn 16.8216.82 11.4811.48 0 0 0 0 0 0 0 0
WW Blk Wall, Stuc Ext, 0.107Blk Wall, Stuc Ext, 0.107 ee 3.123.12 1.991.99 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3100.310 ee 8.998.99 9.029.02 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3100.310 ee 8.998.99 9.029.02 0 0 0 0 0 0 0 0
GG ImpactImpact 0.6200.620 ee 17.9817.98 27.1827.18 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3100.310 ee 8.998.99 9.439.43 0 0 0 0 0 0 0 0
WW Blk Wall, Stuc Ext, 0.107Blk Wall, Stuc Ext, 0.107 ss 3.123.12 1.991.99 0 0 0 0 47 47 146 93
GG ImpactImpact 0.4500.450 ss 13.0513.05 10.8210.82 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3100.310 ss 8.998.99 9.159.15 0 0 0 0 0 0 0 0
GG ImpactImpact 0.5800.580 ss 16.8216.82 13.6313.63 0 0 0 0 0 0 0 0
WW Blk Wall, Stuc Ext, 0.107Blk Wall, Stuc Ext, 0.107 swsw 3.123.12 1.991.99 0 0 0 0 0 0 0 0
GG ImpactImpact 0.5800.580 swsw 16.8216.82 21.8121.81 0 0 0 0 0 0 0 0
WW Blk Wall, Stuc Ext, 0.107Blk Wall, Stuc Ext, 0.107 ww 3.123.12 1.991.99 0 0 0 0 156 84 262 167
GG ImpactImpact 0.5800.580 ww 16.8216.82 28.1328.13 0 0 0 0 0 0 0 0
GG ImpactImpact 0.6500.650 ww 18.8518.85 15.1415.14 0 0 0 0 0 0 0 0
GG ImpactImpact 0.6500.650 ww 18.8518.85 15.1415.14 0 0 0 0 72 66 1357 1090
PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0
CC Attic, Shngls, R-20 0.386Attic, Shngls, R-20 0.386 --1.581.58 1.211.21 36 36 57 44 545 545 860 662
FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 36 0 0 0 545 20 559 0
6 c) AED excursion -2 1049
Envelope loss/gain 57 42 3184 3062
12 a) Infiltration 0 0 437 116
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 0 0 2 460
Appliances/other 0 0
Subtotal (lines 6 to 13)57 42 3621 3638
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 11 8 19 14
14 Subtotal 68 50 3640 3652
15 Duct loads 29%45%20 23 29%45%1057 1640
Total room load 88 73 4697 5292
Air required (cfm)Air required (cfm)3 4 186 259
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Nov-12 13:15:43Right-Suite® Universal 2021 21.0.10 RSU29066 Page 8...ments\Wrightsoft HVAC\1916 Lynx Dr PSL Prop.rup Calc = MJ8 Front Door faces: N
1554Job:Right-J® Worksheet 7/12/2021Date:House Chris BatemanBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name Kit Nook Master Bath
2 Exposed wall 34.1 ft 10.0 ft
3 Room height 10.0 heat/coolft 10.0 heat/coolft
4 Room dimensions ft290.5x1.0 ft147.5x1.0
5 Room area 290.5 ft²147.5 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW Blk Wall, Stuc Ext, 0.107Blk Wall, Stuc Ext, 0.107 nn 3.123.12 1.991.99 0 0 0 0 100 93 291 186
.GG ImpactImpact 0.4500.450 nn 13.0513.05 8.828.82 0 0 0 0 7 0 87 59
.GG ImpactImpact 0.4500.450 nn 13.0513.05 8.828.82 0 0 0 0 0 0 0 0
.GG ImpactImpact 0.5800.580 nn 16.8216.82 11.4811.48 0 0 0 0 0 0 0 0
11 GG ImpactImpact 0.5800.580 nn 16.8216.82 11.4811.48 0 0 0 0 0 0 0 0
GG ImpactImpact 0.5800.580 nn 16.8216.82 11.4811.48 0 0 0 0 0 0 0 0
WW Blk Wall, Stuc Ext, 0.107Blk Wall, Stuc Ext, 0.107 ee 3.123.12 1.991.99 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3100.310 ee 8.998.99 9.029.02 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3100.310 ee 8.998.99 9.029.02 0 0 0 0 0 0 0 0
GG ImpactImpact 0.6200.620 ee 17.9817.98 27.1827.18 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3100.310 ee 8.998.99 9.439.43 0 0 0 0 0 0 0 0
WW Blk Wall, Stuc Ext, 0.107Blk Wall, Stuc Ext, 0.107 ss 3.123.12 1.991.99 210 170 531 340 0 0 0 0
GG ImpactImpact 0.4500.450 ss 13.0513.05 10.8210.82 17 17 225 187 0 0 0 0
GG ImpactImpact 0.3100.310 ss 8.998.99 9.159.15 0 0 0 0 0 0 0 0
GG ImpactImpact 0.5800.580 ss 16.8216.82 13.6313.63 22 19 377 305 0 0 0 0
WW Blk Wall, Stuc Ext, 0.107Blk Wall, Stuc Ext, 0.107 swsw 3.123.12 1.991.99 57 35 108 69 0 0 0 0
GG ImpactImpact 0.5800.580 swsw 16.8216.82 21.8121.81 22 3 369 479 0 0 0 0
WW Blk Wall, Stuc Ext, 0.107Blk Wall, Stuc Ext, 0.107 ww 3.123.12 1.991.99 75 53 164 105 0 0 0 0
GG ImpactImpact 0.5800.580 ww 16.8216.82 28.1328.13 22 0 377 630 0 0 0 0
GG ImpactImpact 0.6500.650 ww 18.8518.85 15.1415.14 0 0 0 0 0 0 0 0
GG ImpactImpact 0.6500.650 ww 18.8518.85 15.1415.14 0 0 0 0 0 0 0 0
PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0
CC Attic, Shngls, R-20 0.386Attic, Shngls, R-20 0.386 --1.581.58 1.211.21 291 291 458 353 148 148 233 179
FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 291 34 978 0 148 10 287 0
6 c) AED excursion 75 -20
Envelope loss/gain 3586 2542 897 404
12 a) Infiltration 737 196 216 57
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 2 460 0 0
Appliances/other 1700 0
Subtotal (lines 6 to 13)4323 4897 1113 462
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 0 0 0 0
14 Subtotal 4323 4897 1113 462
15 Duct loads 29%45%1255 2200 29%45%323 207
Total room load 5578 7097 1436 669
Air required (cfm)Air required (cfm)221 348 57 33
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Nov-12 13:15:43Right-Suite® Universal 2021 21.0.10 RSU29066 Page 9...ments\Wrightsoft HVAC\1916 Lynx Dr PSL Prop.rup Calc = MJ8 Front Door faces: N
1554Job:Right-J® Worksheet 7/12/2021Date:House Chris BatemanBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name Wtr Clst Hall
2 Exposed wall 0 ft 0 ft
3 Room height 10.0 heat/coolft 10.0 heat/coolft
4 Room dimensions ft4.0x6.0 ft4.0x6.0
5 Room area 24.0 ft²24.0 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW Blk Wall, Stuc Ext, 0.107Blk Wall, Stuc Ext, 0.107 nn 3.123.12 1.991.99 0 0 0 0 0 0 0 0
.GG ImpactImpact 0.4500.450 nn 13.0513.05 8.828.82 0 0 0 0 0 0 0 0
.GG ImpactImpact 0.4500.450 nn 13.0513.05 8.828.82 0 0 0 0 0 0 0 0
.GG ImpactImpact 0.5800.580 nn 16.8216.82 11.4811.48 0 0 0 0 0 0 0 0
11 GG ImpactImpact 0.5800.580 nn 16.8216.82 11.4811.48 0 0 0 0 0 0 0 0
GG ImpactImpact 0.5800.580 nn 16.8216.82 11.4811.48 0 0 0 0 0 0 0 0
WW Blk Wall, Stuc Ext, 0.107Blk Wall, Stuc Ext, 0.107 ee 3.123.12 1.991.99 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3100.310 ee 8.998.99 9.029.02 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3100.310 ee 8.998.99 9.029.02 0 0 0 0 0 0 0 0
GG ImpactImpact 0.6200.620 ee 17.9817.98 27.1827.18 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3100.310 ee 8.998.99 9.439.43 0 0 0 0 0 0 0 0
WW Blk Wall, Stuc Ext, 0.107Blk Wall, Stuc Ext, 0.107 ss 3.123.12 1.991.99 0 0 0 0 0 0 0 0
GG ImpactImpact 0.4500.450 ss 13.0513.05 10.8210.82 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3100.310 ss 8.998.99 9.159.15 0 0 0 0 0 0 0 0
GG ImpactImpact 0.5800.580 ss 16.8216.82 13.6313.63 0 0 0 0 0 0 0 0
WW Blk Wall, Stuc Ext, 0.107Blk Wall, Stuc Ext, 0.107 swsw 3.123.12 1.991.99 0 0 0 0 0 0 0 0
GG ImpactImpact 0.5800.580 swsw 16.8216.82 21.8121.81 0 0 0 0 0 0 0 0
WW Blk Wall, Stuc Ext, 0.107Blk Wall, Stuc Ext, 0.107 ww 3.123.12 1.991.99 0 0 0 0 0 0 0 0
GG ImpactImpact 0.5800.580 ww 16.8216.82 28.1328.13 0 0 0 0 0 0 0 0
GG ImpactImpact 0.6500.650 ww 18.8518.85 15.1415.14 0 0 0 0 0 0 0 0
GG ImpactImpact 0.6500.650 ww 18.8518.85 15.1415.14 0 0 0 0 0 0 0 0
PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0
CC Attic, Shngls, R-20 0.386Attic, Shngls, R-20 0.386 --1.581.58 1.211.21 24 24 38 29 24 24 38 29
FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 24 0 0 0 24 0 0 0
6 c) AED excursion -1 -1
Envelope loss/gain 38 28 38 28
12 a) Infiltration 0 0 0 0
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 0 0 0 0
Appliances/other 0 0
Subtotal (lines 6 to 13)38 28 38 28
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 0 0 -38 -28
14 Subtotal 38 28 0 0
15 Duct loads 29%45%11 13 29%45%0 0
Total room load 49 41 0 0
Air required (cfm)Air required (cfm)2 2 0 0
2021-Nov-12 13:15:45
Right-Suite® Universal 2021 21.0.10 RSU29066 Page 1
...ments\Wrightsoft HVAC\1916 Lynx Dr PSL Prop.rup Calc = MJ8 Front Door faces: N
1554Job:Duct System Summary 7/12/2021Date:House Chris BatemanBy:
Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
Project Information
Zaros Residence, NisAir Air ConditioningFor:
1916 Lynx Dr, Fort Pierce, FL 34949
CoolingHeating
External static pressure in H2O0.70in H2O0.70
Pressure losses in H2O0in H2O0
Available static pressure in H2O0.70in H2O0.70
Supply / return available pressure 0.511 / 0.189 in H2O in H2O0.511 / 0.189
Lowest friction rate in/100ft0.253in/100ft0.253
Actual air flow cfm1400cfm1400
Total effective length (TEL) ft277
Supply Branch Detail Table
Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv
Name (Btuh)(cfm) (cfm)FR (in)(in)Matl Ln (ft)Ln (ft) Trunk
st2100.020.8VlFx0x04.00.4232542872hBath
st195.031.5VlFx0x04.00.4044473cBath 2
st295.027.0VlFx0x06.00.419901162436hBed 2
st2100.027.4VlFx0x08.00.4011802445118hBed 3
st195.028.6VlFx0x06.00.414881232588hDining
st295.021.6VlFx0x06.00.438851222557hFoyer
st5135.058.6VlFx0x08.00.2642091333549cKit Nook
st5135.061.2VlFx0x08.00.2612091333549cKit Nook-A
st195.029.9VlFx0x05.00.40972761589hLaundry
st5135.062.2VlFx0x07.00.2591561122646cLiving
st5135.058.7VlFx0x07.00.2641561122646cLiving-A
st4135.067.3VlFx0x05.00.25339681436hMaster Bath
st4135.065.7VlFx0x07.00.2551521322577cMaster Bed
st4135.057.9VlFx0x07.00.2651521322577cMaster Bed-A
st5135.067.2VlFx0x05.00.25327571201hPantry
st4135.058.5VlFx0x05.00.26435731524hWIC
st4135.061.8VlFx0x04.00.2602241cWtr Clst
Bold/italic values have been manually overridden
2021-Nov-12 13:15:45
Right-Suite® Universal 2021 21.0.10 RSU29066 Page 2
...ments\Wrightsoft HVAC\1916 Lynx Dr PSL Prop.rup Calc = MJ8 Front Door faces: N
Supply Trunk Detail Table
Trunk Htg Clg Design Veloc Diam H x W Duct
Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk
st4 Peak AVF 407 380 0.253 746 10.0 0x0 VinlFlx st3
st5 Peak AVF 547 756 0.253 707 14.0 0x0 VinlFlx st3
st3 Peak AVF 954 1136 0.253 813 16.0 0x0 VinlFlx st1
st1 Peak AVF 1157 1300 0.253 736 18.0 0x0 VinlFlx
st2 Peak AVF 523 380 0.401 666 12.0 0x0 VinlFlx
Return Branch Detail Table
Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct
Name Size (in) (cfm)(cfm)(ft)FR (fpm)(in)(in)Opening (in) Matl Trunk
rb2 0x 2440 180 74.7 0.253 552 9.0 x0 0 VlFx rt1
rb3 0x 2390 179 74.3 0.254 542 9.0 x0 0 VlFx rt1
rb1 0x 8610 983 54.0 0.350 556 18.0 x0 0 VlFx rt1
rb4 0x 3360 338 0 0 0 0 x0 0 VlFx
Return Trunk Detail Table
Trunk Htg Clg Design Veloc Diam H x W Duct
Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk
rt1 Peak AVF 1344 1342 0.253 760 18.0 0x0 VinlFlx
2021-Nov-12 13:15:45
Right-Suite® Universal 2021 21.0.10 RSU29066 Page 1
...ments\Wrightsoft HVAC\1916 Lynx Dr PSL Prop.rup Calc = MJ8 Front Door faces: N
1554Job:Manual S Compliance Report 7/12/2021Date:House Chris BatemanBy:
Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
Project Information
Zaros Residence, NisAir Air ConditioningFor:
1916 Lynx Dr, Fort Pierce, FL 34949
Cooling Equipment
Design Conditions
°F76.8Entering coil DB:Btuh29480Sensible gain:°F90.4Outdoor design DB:
°F63.9Entering coil WB:Btuh8220Latent gain:°F77.4Outdoor design WB:
Btuh37700Total gain:°F75.0Indoor design DB:
cfm1400Estimated airflow:%50Indoor RH:
Manufacturer's Performance Data at Actual Design Conditions
Split ACEquipment type:
ML14XC1S042-230A**+CBA27UHE-042-230*++TDRModel:LennoxManufacturer:
cfm1400Actual airflow:
% of load100Btuh29400Sensible capacity:
% of load153Btuh12600Latent capacity:
%70SHR:% of load111Btuh42000Total capacity:
Heating Equipment
Design Conditions
°F68.3Entering coil DB:Btuh37012Heat loss:°F41.0Outdoor design DB:
°F70.0Indoor design DB:
Manufacturer's Performance Data at Actual Design Conditions
Elec stripEquipment type:
Model:Manufacturer:
cfm1400Actual airflow:
°F50Temp. rise:% of load88kW9.6Output capacity:
Meets all requirements of ACCA Manual S.