HomeMy WebLinkAboutLeeth Residence - Wind Load Letter eSEALrepared for Clear Choice Windows and Glass Calculations by Seaside Engineers
Project: Leeth Residence Certificate of Authorization No. 32048
Location: 3200 N HWY A1A #410 4265 60th Court
Fort Pierce, Florida Vero Beach, Florida 32967
Project ID:(722) 202‐8008 info@seasideengineers.com
Date: 1/7/2022 www.seasideengineers.com
Design Information
Risk Category II
Windspeed 161 mph
Exposure D
Int. Press. Coef., GCpi(+/‐)0.18 Enclosed
a 5.00 feet
ID
Area
(sqft) Zone
Florida
Product
Approval # or
NOA Manufacturer Model
1 9.2 4 20‐0401.05 PGT 5460 46.4 ‐52.8 50.0 ‐100.0
2 17.9 4 20‐0401.05 PGT 5460 46.4 ‐52.8 50.0 ‐100.0
3 12.2 4 20‐0401.05 PGT 5460 46.4 ‐52.8 50.0 ‐100.0
4 12.2 4 20‐0401.05 PGT 5460 46.4 ‐52.8 50.0 ‐100.0
5 17.9 4 20‐0401.04 PGT 5400 46.4 ‐52.8 50.0 ‐65.0
Select the appropriate fastener size and spacing using the pre‐engineered attachment schedule for the Florida Approved Product(s) or NOA used on this job. The contractor is
responsible to ensure the use of the proper material, reinforcement, components, etc. to meet the indicated pressure per the product approval engineering document. The contractor
is responsible to verify the component is in the appropriate zone using the "a" dimension shown above and diagrams shown below. The building pressures are calculated using the
Allowable Stress Design. Contact Seaside Engineers immediately if the substrate at the attachment locations appears to have deterioration, abnormalities, damage, or other conditions
resulting in questionable integrity.
Component & Cladding Wind Loads
Building Design
Pressure (PSF)
Product Design
Pressure (PSF)Opening Description
DH Window
DH Window
DH Window
DH Window
SH Window