HomeMy WebLinkAboutduct/blowerDuct Leakage Test Report
Prescriptive or Performance Method
Permit #
Job Information
Builder: DR HORTON
Community: CREEKSIDE Lot: 14
Address: 9503 POTOMAC DRIVE Unit:
City: FORT PIERCE
State: FL Zip: 34945
Duct Leakage Test Results
�Presciptive Method 0 Performance Method
System 1
cfm25
Q,Vrescriptive Method cfm25 (total)
To qualify as "substantially leak free" On must be less than or equal to 0.04
System 2
cfm25
if air handler unit is installed. if air handler unit is not installed, Qn Total
must be less than or equal to 0.03. This testing method meets the
System 3
cfm25
requirements in accordance with Section R403.2.2
Sum of any additional
systems
cfm25
Total of all systems
O performance Method cfm25 (Out or Total)
cfm25
To qualify as "substantially leak free" Qn must not be greater than the
proposed duct leakage Qn specified on Form R405-2014
58 -
1828 0.03 On
Total of all systems
Total Conditioned
leakage Type selected Qn specified on Form
Square Footage
on Form R405-2014 R405-2014 (Energy Cale)
✓ PASS
FAIL
(Energy Ca(c)
Testing Company
Company Name: SUN SEAL LLC Phone: 321-412-0035
1 hereby verify that the above duct leakage testing results are in accordance with the Florida Building Code requirements with the selected
compliance path as stated above, either the Prescriptive Method or Performance Method.
Date of Test: 01 /21 /2022
Signature of Tester--�P,:Z( IN ievz
Printed Name of Tester: DANIEL MURPHY
License/Certification # 5066440 Issuing Authority
UN Envelope Leakage Test Report
" (Blower Boor Test)
R405.4.2.1 Compliance
Permit #
Job information
Builder: DR HORTON Community:
CREEKSIDE tot: 14
Address: 9503 POTOMAC DRIVE
Unit:
City: FORT PIERCE
State: FL Zip: 34945
Air Leakage Test Results Passing results must be 7 ACH(50) or less
1551 x 60 _ 15720.9 = 5.9
Method for calculating building volume:
CFM(50) Building Volume ACH(50)
p Retrieved from architectural plans
ode software calculated
7PASS FAIL
O Field measured and calculated
! I When ACi(50) is less than 3, Mechanical
l l
Ventilation installation must be verified by building department.
Certification of Test Results
R402A.1.2 Testing. The building or dwelling unit shall be tested and verified as having an air leakage rate or not exceeding 7 air changes
per hour in Climate Zones 1 and 2, 3 air changes per hour in Climate Zones 3 through 8. Testing shall be conducted with a blower door at a
pressure of 0.2 inches w.g. (50 Pascals). Testing shall be conducted by wither individuals as defined in Section 553.993(5) or (7), F.S. or
individuals licensed as set forth in Section 489.105(3)(f), (g), or (i) or an approved third party. A written report of the results of the test
shall be signed by the party conducting the test and provided to the code official. Testing shall be performed at any time after creation of
all
Testing Company
Company Name: SUN SEAL LLC Phone: 321-412-0035
1 hereby verify that the above duct leakage testing results are in accordance with the Florida Building Code requirements with the selected
compliance path as stated above, either the Prescriptive Method or Performance Method.
Date of Test: 01 /21 /2022
Signature of Tester:
Printed Name of Tester: DANIEL MURPHY
License/Certification # 5066440 Issuing Authority BPI