HomeMy WebLinkAboutBARCLAY BEACH CLUBBARCLAY BEACH CLUB
2800 NORTH HIGHWAY A1A
FORT PIERCE, FL 34949
1.NO FIRE ALARM WORK IS PERFORMED UNDER THIS PERMIT.
2.NO STRUCTURAL WORK, DESIGN CHANGES, OR ADDITIONS ARE PERFORMED UNDER THIS PERMIT THEREFORE
ARCHITECTURAL DRAWINGS ARE NOT PROVIDED OR REQUIRED.
a.ALL NEW WORK AND EXISTING CONSTRUCTION ARE CLEARLY IDENTIFY. DRAWINGS ARE OF SUFFICIENT
CLARITY AND QUALITY TO EFFECTIVELY CONVEY THE NATURE AND SCOPE OF THE PROPOSED WORK.
b.THE CLASS OF REHAB IS “RENOVATION” PER CHAPTER 43, SECTION 43.4… “THE REPLACEMENT IN KIND,
STRENGTHENING OR UPGRADING OF BUILDING ELEMENTS, MATERIALS, EQUIPMENT OR FIXTURES THAT DOES
NOT RESULT IN THE RECONFIGURATION OF THE BUILDING SPACES WITHIN”.
c.WORK UNDER THIS PERMIT MEETS THE DEFINITION FROM FBC, EXISTING AS “ALTERATION - LEVEL 1” AND IS
COVERED BY THE PROVISIONS OF CHAPTER 7. IAW CHAPTER 7, THE “ALTERATIONS” MADE BY THIS PERMIT
MEET THE STANDARDS OF CONFORMANCE FOR ALL AREA WORK.
3.NO NEW DESIGN FEATURES OR ENGINEERING CHANGES ARE MADE UNDER THIS PERMIT. MECHANICAL AND
ELECTRICAL DRAWINGS ARE BASED SOLELY ON THE SCOPE OF THE WORK TO BE PERFORMED; ALL WORK IS DIRECT
REPLACEMENT OF EXISTING COMPONENTS.
4.ELECTRICAL CIRCUITS FOR THE ELEVATOR CAB LIGHTING, PIT LIGHTING, MACHINE ROOM (MR) LIGHTING AND MR
GFCI CIRCUITS ARE ALL PRE-EXISTING CIRCUITS VERIFIED TO BE POWERED FROM SEPARATE SOURCES.
REPLACEMENT OF THESE COMPONENTS AND FIXTURE ARE ALL DIRECT REPLACEMENT OF EXISTING EQUIPMENT;
THE ONLY NEW CIRCUITS ADDED ARE AC MINI SPLIT IN THE MACHINE ROOM.
2800 North Highway A1A
Fort Pierce, FL 34949
CS.1 - COVER SHEET
E.0 - MR PANEL SCHEDULE
E.1 - ELEVATOR MACHINE ROOM
M.1 - ELEVATOR MACHINE ROOM
1.INSTALL NEW ELEVATOR MACHINE ROOM AIR CONDITIONER.
2.INSTALL NEW CIRCUITS FOR ELEVATOR MACHINE ROOM AC.
3.DIRECT REPLACEMENT OF ELEVATOR MAIN LINE DISCONNECTS.
4.DIRECT REPLACEMENT OF ELEVATOR CAB LIGHT DISCONNECTS.
5.DIRECT REPLACEMENT OF ALL NECESSARY LOAD SIDE CONDUIT AND WIRE FROM THE MAIN LINE
POWER AND CAB LIGHT DISCONNECTS TO THE NEW ELEVATOR CONTROLLERS.
6.DIRECT REPLACEMENT OF LIGHT FIXTURES IN THE ELEVATOR MACHINE ROOM.
7.DIRECT REPLACEMENT OF EXISTING NON-GFCI OUTLET WITH GFCI RECEPTACLE IN THE ELEVATOR
MACHINE ROOM.
8.DIRECT REPLACEMENT OF LIGHT FIXTURES IN THE ELEVATOR PITS.
9.DIRECT REPLACEMENT OF EXISTING NON-GFCI OUTLET WITH GFCI RECEPTACLE IN THE ELEVATOR PITS.
10.DIRECT REPLACEMENT OF EXISTING MOTOR OPERATED DAMPER IN HOISTWAY.
11.INSTALL NEW AUTOMATIC TRANSFER SWITCH.
SCOPE OF WORK
GENERAL NOTES
DRAWING SCALE
PROJECT NO.
DRAWING NO.
SHEET OF
DATEDRAWN BY
T H I S D O C U M E N T C O N T A I N S
I N F O R M A T I O N T H A T C A N N O T B E
R E P R O D U C E D O R D I V U L G E D , I N
W H O L E O R I N P A R T , W I T H O U T
W R I T T E N A U T H O R I Z A T I O N F R O M
N I C H O L S C O N T R A C T I N G , I N C .
3 0 1 -9 2 4 -5 2 5 8
FREDERICK NICHOLS -CGC1522915
GREGORY JOHN GRESETH - EC13009689
GREGORY JOHN GRESETH - CAC1820514
5 0 8 O L N E Y S A N D Y S P R I N G R O A D
S U I T E #2 0 0
S A N D Y S P R I N G , M D 2 0 8 6 0
PHONE:3 0 1 -9 2 4 -5 2 5 8
FAX:3 0 1 -9 2 4 -5 2 4 5
W W W .N I C H O L S C O N T R A C T I N G .C O M
J.PaglinawanCONTRACT L I CENSE INFO R M A TIONLIST O F D R A W I N G S
NO.BY REVISION DATE
1
2
3
SCOPE OF WORK
GENERAL NOTES
ARCH Full Bleed D (36.00 X 24.00 Inches)
12345678
F
E
D
C
B
A
12345678
F
E
D
C
B
A
OCCUPANCY CLASSIFICATION
TYPE OF CONSTRUCTION
NO. OF STORIES
APPLICABLE BUILDING CODES
01-20-21122 6242021
Barclay Beach Club
1 OF 5
CS.1
HOISTWAY
RESIDENTIAL, GROUP R-2
TYPE IB
11 STORIES
FBC 2020 - 7TH EDITION, NFPA 101, NFPA 90A,
NFPA 70 - 2017 EDITION, NFPA 72
MACHINE ROOM
(ROOF LEVEL)
GENERATOR ROOM
ENTRANCE
(GROUND LEVEL)
ELECTRICAL SYMBOL LEGENDS
SHEET SYMBOL LEGENDS
FIXTURE SCHEDULE
AC UNIT 1-LINE DIAGRAM
PANEL SCHEDULE
VOLTAGE DROP
DRAWING SCALE
PROJECT NO.
DRAWING NO.
SHEET OF
DATEDRAWN BY
T H I S D O C U M E N T C O N T A I N S
I N F O R M A T I O N T H A T C A N N O T B E
R E P R O D U C E D O R D I V U L G E D , I N
W H O L E O R I N P A R T , W I T H O U T
W R I T T E N A U T H O R I Z A T I O N F R O M
N I C H O L S C O N T R A C T I N G , I N C .
3 0 1 -9 2 4 -5 2 5 8
FREDERICK NICHOLS - CGC1522915
GREGORY JOHN GRESETH - EC13009689
GREGORY JOHN GRESETH - CAC1820514
5 0 8 O L N E Y S A N D Y S P R I N G R O A D
S U I T E #2 0 0
S A N D Y S P R I N G , M D 2 0 8 6 0
PHONE:3 0 1 -9 2 4 -5 2 5 8
FAX:3 0 1 -9 2 4 -5 2 4 5
W W W .N I C H O L S C O N T R A C T I N G .C O M
J.PaglinawanCONTRACT L I CENSE INFO R M A TIONSHEET C O N T E N T S
NO.BY REVISION DATE
1
2
3
ARCH Full Bleed D (36.00 X 24.00 Inches)
12345678
F
E
D
C
B
A
12345678
F
E
D
C
B
A
AS
SHOWN
VP
ELEVATOR
PIT
64
64
120
120
2X4 LED
VAPORTIGHT
LIGHT
LITHONIA
C232120RE
FOUR BROTHERS
C48232VP
WHITE
WHITE
SURFACE
MOUNT
SURFACE
MOUNT
LOCATION WATTS VOLTS FIXTURE
TYPE MODEL #FINISH COMMENTS
G E N E R A L E L E C T R I C A L N O T E
PLANS SUBMITTED FOR REVIEW
AFTER DECEMBER 31, 2017 ARE
DESIGNED IN ACCORDANCE WITH
THE 2014 NATIONAL ELECTRICAL
CODE.
FIXTURE SCHEDULE
ELECTRICAL SYMBOL LEGEND
MAGNETIC MOTOR STARTER
COMBINATION MOTOR STARTER
(480,0,20) = VOLTAGE, STARTER SIZE, FUSE AMPS
MANUAL STARTER W/ OVERLOAD
PROTECTION
SURFACE JUNCTION BOX
SURFACE JUNCTION BOX - WALL
FLUSH JUNCTION BOX - CEILING
FLUSH JUNCTION BOX - WALL
FLUSH JUNCTION BOX - FLOOR
MOTOR (# = HORSEPOWER)
FIXED EQUIPMENT LOCATION
NON FUSED DISCONNECT SWITCH
(30 = AMP)
FUSED DISCONNECT SWITCH
(30/30 = AMP/FUSE)
REVENUE METER, KWH/D
CONDUIT UP, CONDUIT DOWN
WIRING
(480,0,20)
$m
J
J
J
J
J
#
F
(30)
(30/30)
M
DOOR SWITCH
MOUNTING LOCATION:WALL
2-WAY SWITCH
MOUNTING LOCATION:WALL
3-WAY SWITCH
MOUNTING LOCATION:WALL
$D
$2
$3
TELEPHONE OUTLET
SMOKE DETECTOR - CEILING
HEAT DETECTOR - CEILING
DUPLEX RECEPTACLE - GFCI
QUAD RECEPTACLE - GFCI
LED VAPORTIGHT LIGHT,
4' - T8 BULB, WHITE
F
F
S
H
VP
SHEET SYMBOL LEGEND
LINE CONTINUE BREAK
NEW WORK CONNECTION TO EXISTING WORK
DETAIL REFERENCE
TOP - DETAIL #
BOTTOM - SHEET OF APPEARANCE
#
X0.0
SECTION REFERENCE
TOP - DETAIL #
BOTTOM - SHEET OF APPEARANCE
#
X0.0
#LOW VOLTAGE FEEDER DESIGNATOR
ELEVATION DESIGNATION
EQUIPMENT DESIGNATION#
PLAN CONTINUATION DESIGNATION
BOTTOM - SHEET OF CONTINUATIONX0.0
REFER
REVISION ##
2 TON AC 1- LINE DIAGRAM
PANEL SCHEDULE
VOLTAGE DROP
2X4 LED
VAPORTIGHT
LIGHT
LED VAPORTIGHT LIGHT,
4' - T8 BULB, WHITE
01-20-21122 6/24/2021
Barclay Beach CluE
2 OF 5
E0.1
Elevator Panel
AC IDU
(30)
F (30/20)
3 #12 THWN + 12G in 1/2" Conduit
3 #12 THWN + 12G in 1/2" Conduit
2 # 12 THWN + 12G in 1/2" Conduit
2 # 12 THWN + 12G in 1/2" Conduit
AC ODU
Circuit 18 \ 19
F
2800 North Highway A1A
Fort Pierce, FL 34949
GFCI
$GFCI GFCIVP
VP
$GFCIVP
VP
$MACHINE ROOM ELECTRICAL
ELEVATOR PIT ELECTRICAL
1.INSTALL NEW ELEVATOR
MACHINE ROOM AIR
CONDITIONER.
2.INSTALL NEW CIRCUITS FOR
ELEVATOR MACHINE ROOM AC.
3.DIRECT REPLACEMENT OF
ELEVATOR MAIN LINE
DISCONNECTS.
4.DIRECT REPLACEMENT OF
ELEVATOR CAB LIGHT
DISCONNECTS.
5.DIRECT REPLACEMENT OF ALL
NECESSARY LOAD SIDE
CONDUIT AND WIRE FROM THE
MAIN LINE POWER AND CAB
LIGHT DISCONNECTS TO THE
NEW ELEVATOR CONTROLLERS.
6.DIRECT REPLACEMENT OF
LIGHT FIXTURES IN THE
ELEVATOR MACHINE ROOM.
7.DIRECT REPLACEMENT OF
EXISTING NON-GFCI OUTLET
WITH GFCI RECEPTACLE IN THE
ELEVATOR MACHINE ROOM.
8.DIRECT REPLACEMENT OF
LIGHT FIXTURES IN THE
ELEVATOR PITS.
9.DIRECT REPLACEMENT OF
EXISTING NON-GFCI OUTLET
WITH GFCI RECEPTACLE IN THE
ELEVATOR PITS.
10.DIRECT REPLACEMENT OF
EXISTING MOTOR OPERATED
DAMPER IN HOISTWAY.
11.INSTALL NEW AUTOMATIC
TRANSFER SWITCH.
DRAWING SCALE
PROJECT NO.
DRAWING NO.
SHEET OF
DATEDRAWN BY
T H I S D O C U M E N T C O N T A I N S
I N F O R M A T I O N T H A T C A N N O T B E
R E P R O D U C E D O R D I V U L G E D , I N
W H O L E O R I N P A R T , W I T H O U T
W R I T T E N A U T H O R I Z A T I O N F R O M
N I C H O L S C O N T R A C T I N G , I N C .
3 0 1 -9 2 4 -5 2 5 8
FREDERICK NICHOLS - CGC1522915
GREGORY JOHN GRESETH - EC13009689
GREGORY JOHN GRESETH - CAC1820514
5 0 8 O L N E Y S A N D Y S P R I N G R O A D
S U I T E #2 0 0
S A N D Y S P R I N G , M D 2 0 8 6 0
PHONE:3 0 1 -9 2 4 -5 2 5 8
FAX:3 0 1 -9 2 4 -5 2 4 5
W W W .N I C H O L S C O N T R A C T I N G .C O M
J.PaglinawanCONTRACT L I CENSE INFO R M A TIONSHEET C O N T E N T S
NO.BY REVISION DATE
1
2
3
ARCH Full Bleed D (36.00 X 24.00 Inches)
12345678
F
E
D
C
B
A
12345678
F
E
D
C
B
A
G E N E R A L E L E C T R I C A L N O T E
PLANS SUBMITTED FOR REVIEW
AFTER DECEMBER 31, 2017 ARE
DESIGNED IN ACCORDANCE WITH
THE 2014 NATIONAL ELECTRICAL
CODE.
DRAWINGS ARE PROVIDED TO
REFERENCE LOCATIONS OF WORK
SITES AND SURROUNDING AREAS. ALL
MEASUREMENTS AND DISTANCES
MUST BE VERIFIED AT THE WORK SITE.
#
NOTE
CONSTRUCTION NOTES
KEY PLAN
01-20-21122 6/24/2021
Barclay BeacN CluE
3 OF 5
E1.1
APPLICABLE BUILDING CODESAC IDUFeet
0 1.5 3
1/2" = 1'
MACHINE ROOM- ELECTRICAL- GROUND LEVELA1
SCALE
Feet
0 1.5 3
1/2" = 1'
ELEVATOR PIT- ELECTRICAL- GROUND FLOORA2
SCALE
AC
CL
FBC 2020 - 7TH EDITION, NFPA 101, NFPA 90A,
NFPA 70 - 2017 EDITION, NFPA 72
2800 North Highway A1A
Fort Pierce, FL 34949Feet
0 1.5 31/2" = 1'
ELECTRICAL ROOM- GROUND FLOORA2
SCALE
AC
AC ODUCL
ML
ML
ELEVATOR
1
MACHINE
ELEVATOR
2
MACHINE
CNTLR 1 CNTLR 2
ATS
GENERATOR
ATS 1 - LINE DIAGRAM
4 X 500 MCM + 3G THHN IN 3" C
4 X 500 MCM + 3G THHN IN 3" C
NORMAL
SOURCE
GENERATOR
4
2
1
3
5
6 6 6
6 6 6
7
8
8
8
8 99
10
11
CL - 2 # 12 THHN + 12G 1
2" C
ML - 3 # 3 THHN + 6G 1 1
4" C
GFCI
MACHINE ROOM MECHANICAL
DRAWING SCALE
PROJECT NO.
DRAWING NO.
SHEET OF
DATEDRAWN BY
T H I S D O C U M E N T C O N T A I N S
I N F O R M A T I O N T H A T C A N N O T B E
R E P R O D U C E D O R D I V U L G E D , I N
W H O L E O R I N P A R T , W I T H O U T
W R I T T E N A U T H O R I Z A T I O N F R O M
N I C H O L S C O N T R A C T I N G , I N C .
3 0 1 -9 2 4 -5 2 5 8
5 0 8 O L N E Y S A N D Y S P R I N G R O A D
S U I T E #2 0 0
S A N D Y S P R I N G , M D 2 0 8 6 0
PHONE:3 0 1 -9 2 4 -5 2 5 8
FAX:3 0 1 -9 2 4 -5 2 4 5
W W W .N I C H O L S C O N T R A C T I N G .C O M
J.PaglinawanCONTRACT L I CENSE INFO R M A TIONSHEET C O N T E N T S
NO.BY REVISION DATE
1
2
3
ANSI Expand B (11.00 X 17.00 Inches)
12345678
F
E
D
C
B
A
12345678
F
E
D
C
B
A
DRAWINGS ARE PROVIDED TO
REFERENCE LOCATIONS OF WORK
SITES AND SURROUNDING AREAS. ALL
MEASUREMENTS AND DISTANCES
MUST BE VERIFIED AT THE WORK SITE.
NOTE
MECHANICAL NOTES
DRAWING NOTES
1/2" = 1'-0"
APPLICABLE BUILDING CODES
NFPA 101 LIFE SAFE CODE
01-20-21122 6/24/2021
Barclay Beach Condo
4 OF 5
M1.1
·THE CONDENSATE REMOVAL SYSTEM
FOR THE INDOOR AC UNIT SHALL BE
EQUIPPED WITH A WATER LEVEL
MONITORING DEVICE THAT WILL SHUT OF
THE EQUIPMENT SERVED IN THE EVENT
THAT THE PRIMARY DRAIN BECOMES
RESTRICTED (FBC M-307.2.3).
·THE CONDENSATE DRAIN LINE SHALL BE
MADE OF POLYETHYLENE, ABS, CPVC OR
PVC PIPE OR TUBING AND SHALL BE A
MINIMUM ¾” INTERNAL DIAMETER AND
NOT DECREASE IN SIZE FROM THE DRAIN
PAN TO THE PLACE OF CONDENSATE
DISPOSAL. IF A CONDENSATE PUMP IS
NOT INSTALLED, THE LINE SHALL
MAINTAIN A MINIMUM 1/8TH UNIT
DOWNWARD SLOPE OVER ITS LENGTH
(FBC 307.2.1).
·FASTEN THE CONDENSING UNIT TO WALL
MOUNT BRACKET (FL PRE-APPROVED
#18362.1) USING FOUR (4) M10, GRADE 80
BOLTS WITH LOCK WASHERS AND NUTS
(FBC, MECHANICAL 301.13 AND FBC 1620).
·ALL THROUGH PENETRATIONS, RELATED
TO THIS WORK, SHALL BE SEALED WITH
FIRE RATED FOAM AND/OR MASONRY
AND PROTECTED BY AN APPROVED
PENETRATION FIRESTOP SYSTEM, USING
INTUMESCENT MATERIALS, INSTALLED AS
TESTED IAW WITH ASTM 814 OR UL 1479.
·THE CONDENSATE DRAIN SHALL
TERMINATE IN THE CLOSEST PLACE THAT
MEETS THE REQUIREMENTS AS AN
APPROVED PLACE OF DISPOSAL (A
GRASSY/DIRT/MULCHED AREA OR
APPROVED DRAIN/DRAIN PIPE).
CONDENSATE SHALL NOT DISCHARGE
INTO A STREET, ALLEY OR OTHER AREAS
SO AS TO CAUSE A NUISANCE. (FBC
M-307.2).
·MINIMUM EFFICIENCY REQUIRED FOR
PACKAGE UNIT AC AS PER FBC, ENERGY
CONSERVATION C403.2.3 IS 14.0 SEER.
·MACHINE ROOM CONSTRUCTION IS
POURED SLAB FLOOR, CMU WALLS AND
POURED SLAB CEILING. DOOR IS HOLLOW
METAL WITH THRESHOLD AND
WEATHER-STRIPPING. EXISTING
CONSTRUCTION IS IN ACCORDANCE WITH
FBC, ENERGY EFFICIENCY C503.2
FREDERICK NICHOLS -CGC1522915
GREGORY JOHN GRESETH - EC13009689
GREGORY JOHN GRESETH - CAC1820514
CONFIGURATION A - 2 HR F RATINGS
SECTION A-A
SYSTEM NO. C-AJ-1014
F RATING – 2 HR
T RATING – 0 HR
L RATING AT AMBIENT – LESS THAN 1 CFM/SQ FT
L RATING AT 400 F – LESS THAN 1 CFM/SQ FT
A
2
A
4
4
2
1
3
1. FLOOR OR WALL ASSEMBLY – MIN 3-1/4 IN. (83 MM) THICK REINFORCED LIGHTWEIGHT OR NORMAL WEIGHT (100-150 PCF
OR 1600-2400 KG/M3) CONCRETE. WALL MAY ALSO BE CONSTRUCTED OF ANY UL CLASSIFIED CONCRETE BLOCKS*. MAX
DIAM OF CIRCULAR OPENING IS 6 IN. (152 MM). SEE CONCRETE BLOCK (CAZT) CATEGORY IN THE FIRE RESISTANCE
DIRECTORY FOR NAMES OF MANUFACTURERS.
2. THROUGH PENETRANTS – ONE METALLIC PIPE OR CONDUIT TO BE CENTERED WITHIN THE FIRESTOP SYSTEM. A NOM
ANNULAR SPACE OF 3/4 IN. (19 MM) IS REQUIRED WITHIN THE FIRESTOP SYSTEM. PIPE OR CONDUIT TO BE RIGIDLY
SUPPORTED ON BOTH SIDES OF FLOOR OR WALL ASSEMBLY. THE FOLLOWING TYPES AND SIZES OF METALLIC PIPES OR
CONDUITS MAY BE USED:
A. STEEL PIPE – NOM 4 IN. DIAM (102 MM) (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL PIPE.
B. CONDUIT – NOM 4 IN. (102 MM) DIAM (OR SMALLER) STEEL ELECTRICAL METALLIC TUBING OR STEEL CONDUIT.
3. PACKING MATERIAL – MIN 4 PCF (64 KG/M3) MINERAL WOOL BATT INSULATION FIRMLY PACKED INTO OPENING AS A
PERMANENT FORM. PACKING MATERIAL TO BE RECESSED FROM TOP SURFACE OF FLOOR OR FROM BOTH SURFACES OF
WALL AS REQUIRE TO ACCOMMODATE THE REQUIRED THICKNESS OF FILL MATERIAL. MIN THICKNESS OF PACKING
MATERIAL IN FLOORS AND WALLS TO BE 2-3/4 IN. (70 MM) AND 2-1/4 IN. (57 MM), RESPECTIVELY.
4. FILL, VOID OR CAVITY MATERIAL* – SEALANT – MIN 1/2 IN. (13 MM) THICKNESS OF FILL MATERIAL APPLIED WITHIN
ANNULUS, FLUSH WITH TOP SURFACE OF FLOOR OR WITH BOTH SURFACES OF WALL. AS AN ALTERNATE, THE
PERMANENT FORMING MATERIAL (ITEM 3) MAY BE OMITTED IF THE FILL MATERIAL THICKNESS IS INCREASED TO A MIN
1-1/2 IN. (38 MM).
3M COMPANY – TYPES FB-1000 NS, FB-1003SL (FLOORS ONLY), FB-2000 OR FB-2000+.
*BEARING THE UL CLASSIFICATION MARK
"MACHINE
ROOM"
"OUTSIDE OF
ROOF DECK"
Feet
0 2.5 5
VOLTAGE DROP
WALL PENETRATION
NTSSCALE
MACHINE ROOM- MECHANICAL-GROUND LEVELA1
NTSSCALE
PENETRATION THRU WALLA1
1
ELEVATOR
1
NORTH
AC IDUAC AC
AC ODU2
WALL MOUNT BRACKET
2800 North Highway A1A
Fort Pierce, FL 34949
ELEVATOR
2
NORTH
MUZ-HM24NA
MSZ-HM24NA
MACHINE ROOM MECHANICAL
DRAWING SCALE
PROJECT NO.
DRAWING NO.
SHEET OF
DATEDRAWN BY
T H I S D O C U M E N T C O N T A I N S
I N F O R M A T I O N T H A T C A N N O T B E
R E P R O D U C E D O R D I V U L G E D , I N
W H O L E O R I N P A R T , W I T H O U T
W R I T T E N A U T H O R I Z A T I O N F R O M
N I C H O L S C O N T R A C T I N G , I N C .
3 0 1 -9 2 4 -5 2 5 8
5 0 8 O L N E Y S A N D Y S P R I N G R O A D
S U I T E #2 0 0
S A N D Y S P R I N G , M D 2 0 8 6 0
PHONE:3 0 1 -9 2 4 -5 2 5 8
FAX:3 0 1 -9 2 4 -5 2 4 5
W W W .N I C H O L S C O N T R A C T I N G .C O M
J.PaglinawanCONTRACT L I CENSE INFO R M A TIONSHEET C O N T E N T S
NO.BY REVISION DATE
1
2
3
ANSI Expand B (11.00 X 17.00 Inches)
12345678
F
E
D
C
B
A
12345678
F
E
D
C
B
A
DRAWINGS ARE PROVIDED TO
REFERENCE LOCATIONS OF WORK
SITES AND SURROUNDING AREAS. ALL
MEASUREMENTS AND DISTANCES
MUST BE VERIFIED AT THE WORK SITE.
NOTE
MECHANICAL NOTES
DRAWING NOTES
############
APPLICABLE BUILDING CODES
NFPA 101 LIFE SAFE CODE
01-20-21122 6242021
Barclay Beach Condo
5 OF 5
M2.1
FREDERICK NICHOLS -CGC1522915
GREGORY JOHN GRESETH - EC13009689
GREGORY JOHN GRESETH - CAC1820514
Feet
0 2.5 5
VOLTAGE DROP
WALL PENETRATION
NTSSCALE
TOP OF HOISTWAY- MECHANICAL-ROOF LEVELA1
2800 North Highway A1A
Fort Pierce, FL 34949
ID #QTY.W (IN)H (IN)LOCATION
2-2 1 24.0 17.0 HOISTWAY
TAG FREE AREA
(ft2)
FREE AREA
(%)
MAX WIND-
LOAD (psf)
SECT
WIDE
SECT
HIGH
SHIP
SECT
MULLION
(IN)
1.10 39.0 200 1 1 3 STANDARD
NOTE:
DAMPER OPERATIONS
*LOSS OF POWER - DAMPER SPRING
OPERATED OPEN
"PLAN VIEW"
MOD (17"X24")
LOCATION
A
ROOF LEVEL
TOP OF
HOISTWAY
HOISTWAY
MOD (17"X24")
LOCATION
9'
1
1
"ROOF DECK"
HOISTWAY
HOISTWAY
"SECTION VIEW"
1.DIRECT REPLACEMENT OF
EXISTING MOTOR OPERATED
DAMPER IN HOISTWAY.