HVAC Load Calculations 4-23-2014
Etter Residence HVAC Load Calculations for Etter Lot 560 Nettles Blvd Ft. Pierce, Florida KrIVACHVAC LoADs Prepared By: Residential Energy Calc's Wednesday, April 23, 2014 Rhvac is an ACCA approved Manual J and Manual D computer program. Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D. I�Rhvac Residential 4 Light Commercial, HVAC Loads , Elite Software Development, Inc: Residential; Energy Calc's Etter Residence_,. =Port Saint Lucie, FL 34983" ; Pa e,Z ,Project Report Project Title: Etter Residence Designed By: QEA Associates Project Date: Wednesday, April 23, 2014 Client Name: Etter Client Address: Lot 560 Nettles Blvd Client City: Ft. Pierce, Florida Company Name: Residential Energy Calc's Otis s Reference City: Fort Pierce, Florida Building Orientation: Front door faces South Daily Temperature Range: Medium Latitude: 27 Degrees Elevation: 25 ft. Altitude Factor: 0.999 Outdoor Outdoor Outdoor Indoor Indoor Grains Dry Bulb Wet Bulb Rel.Hum Rel.Hum Dry Bulb Difference Winter: 42 39.4 n/a n/a 70 n/a Summer: 90 78 59% 50% 75 61 CheckFi ures .. max.- Total Building Supply CFM: 1,225 CFM Per Square ft.: 0.719 Square ft. of Room Area: 1,704 Square ft. Per Ton: 584 Volume (W) of Cond. Space: 13,884 Total Heating Required Including Ventilation Air: 33,853 Btuh 33.853 MBH Total Sensible Gain: 27,675 Btuh 79 % Total Latent Gain: 7,340 Btuh 21 % Total Cooling Required Including Ventilation Air: 35,015 Btuh 2.92 Tons (Based On Sensible + Latent) `Notes Rhvac is an ACCA approved Manual J and Manual D computer program. Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D. All computed results are estimates as building use and weather may vary. Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at your design conditions. C:\ ...\Etter Residence.rh9 Wednesday, April 23, 2014, 10:44 AM Rhvac Resident►al & L►ght Commercial HVA_C Loads Elite Software Development, lnc. Res►dent►at Energy Calc's Etter Residencem 2 M Port Saint Lucie, FL 34983 Pa e 3 Miscellaneous ,Re ort Summer: alb Wet Bulb - R7. el Hum Rel.Hum Dry' Bulb . Difference 1 42 90 39.4 78 80% 59% n/a 50% 70 75 n/a .61.09 Main Trunk Runouts Calculate: Yes Yes Use Schedule: Yes Yes Roughness Factor: 0.00300 0.01000 Pressure Drop: 0.1000 in.wg./100 ft. 0.1000 in.wg./100 ft. Minimum Velocity: 650 ft./min 450 ft./min Maximum Velocity: 900 ft./min 750 ft./min Minimum Height: 0 in. 0 in. Maximum Height: 0 in. 0 in. Infiltration Specified: 0.450 AC/hr 0.230 AC/hr 104 CFM 53 CFM Infiltration Actual: 0.406 AC/hr 0.123 AC/hr Above Grade Volume: X 13,884 Cu.ft. X 13,884 Cu.ft. 5,634 Cu.ft./hr 1,705 Cu.ft./hr X 0.0167 X 0.0167 Total Building Infiltration: 94 CFM 28 CFM Total Building Ventilation: 45 CFM 45 CFM ---System 1--- Infiltration & Ventilation Sensible Gain Multiplier: 16.49 = (1.10 X 0.999 X 15.00 Summer Temp. Difference) Infiltration & Ventilation Latent Gain Multiplier: 41.50 = (0.68 X 0.999 X 61.09 Grains Difference) Infiltration & Ventilation Sensible Loss Multiplier: 30.77 = (1.10 X 0.999 X 28.00 Winter Temp. Difference) Winter Infiltration Specified: 0.450 AC/hr (104 CFM), Construction: Average Summer Infiltration Specified: 0.230 AC/hr (53 CFM), Construction: Average Duct_ Load Factor Scenarios for System I, 1 Supply Attic 16B 1 Return Attic 16B 0.12 6 164 No C:1... \Etter Residence.rh9 Wednesday, April 23, 2014, 10:44 AM I,Rhvgd,- Residential & Light Commercial-11,11VAC L6ad' Development, kesicleptial.,Ener6y Cold's Etter Reqidence Port Uht, Lucie'FL " 34983 p6g e 4, Load Preview Report 2 (Scope I TNoent I /TftoI Areal Gain) GLaant I GNa�ntl Loss) ossI CS�Msl CSCFyMs CSAFycMst l DS el Building 2.92, 584 1,704 27,675 1 7,340) 35,015 33,8531 422' 11225 1225 2.92 584 1,704' 27,675 � 7,340z 35,015 33,853 1 422'�j 251 11208 742' 1,868 2,610 1,385. 1,594: 1,5945 1,072 20,317 2,982 23,299 1 20,453 266 924 12x14 40'-- 11.356' 62; 1,418, 2148 281 62 II—E 69 857, 369, 1226, 1,653 21 391 1-4 352 6,923 1781 7,101 5294 69i 315 3 -6 196 5,166 762 5,928' 2,408 31 235: 3—E 10 -- 751 3,711— 4,302 561 135 2—E ----- !2 72 660 oi 700, 11191 15 30, 1-4 143: 2205' 802; 3,007' 2,987 391 100, 1-13 60 191 18 209 470 6 9 1-4 632: 9,067 896. 9,963 12,015 1561 413, 9X9 28-; 22-6'41--- 113, 2-,377-' 103, ----1 1110: 668 95 763 ---2,082-'-_.' 2,200 _27�= 291= ------ 30( --1--6 1-4 ...... ..... .... . 210 1 4,865, 523: 5.388 3,862 5011 ............. 221 3-5 130, 822 94; 916 , 2,262 291mi 37 174 54 448 71 519 1 20-.-- --1-4 -- ----- — - ---- -- Sum of room airflows may be greater than system airflow because system has multiple zones. C:\ ... \Efter Residence.rh9 Wednesday, April 23, 2014, 10:44 AM ;Rhvac - Residential & Light°commercial HVAC Loads Elite Software_Development, Inc.' Residential,Energy Calc's Etter Residence, Port Saint Lucie, FL 34983 Page 5 Duct Size Preview Room or Source Minimum Maximum Rough. Design SP Duct Duct I Htg Clg Act. Duct Duct Name Velocity Velocity Factor L/100 Loss Velocity Length Flow Flow Flow Size System 1 - - - - -- -- - - - SupplyRunouts _... ...... ...... Zone 1 _._.. 1-Foyer .. Built -In _..- - , _ 450 750 _ ... 0.01 _ _- 0.1 - - - -- 452.3 28 62 1-5 - - -- 2-Laundry Built -In 450 750, 0.01' 0.1 446.9 ; 21, 39 1-4 3-Living Built-in 450 . 750, 0.01 01 534.7 69 ® 315 3-6 4-Breakfast Built-in 450 750 0.01 01 574 6 : 31 235 3-5 --- -- - -- - - — n — , .. - - - - - - --------- - --- - - 135 � - - - - _ _ 6 Bath 1- Built -In 450 750 0.01 01 344.1 -� 15 ®_ 30 1- -4 - _ - 7-Den/Bedroom 2- Built -In 450 750 0.01 - ' 0.1 T- - 510.91 , _Y - 39 ® 100 • 1 6 - ;- Built -In... - -- 450 f 750 --- - - ...._. 0.01 r-- - — - 1 _ . ,_ - .._.. 99:4, - _..- .. .6 ®_ 9 1-4 Zone 2 9-Hall Built-in 450 750 0.011 01 524.6 27 ® 103 1-6 _.-. - - 10-Walk In Closet 1 Built In . 450 450. 750' 0.01 - - • 0.1 ' 3 48 2 , 29' b3 - 30 1-4 _ 11-Master Bedroom Built -In 450 750 - 0.01 - . 0.1 ---- * 541.1 - - - • 50;® 221 3-5 12-Master Bath Built -In 450 750 0.01 0.1 428.4 29 ® 37 1-4 13-Walk In Closet Built-in 450 750 001 01 233.8 21 20_ 1-4 Other Ducts in System 1 Supply Main Trunk Built -In 650 900 0.003 0.1 , 816.9 • 422' 1 225 1208 Summary System 1 Heating Flow: 422 Cooling Flow. 1225 C:\ ...\Etter Residence.rh9 Wednesday, April 23, 2014, 10:44 AM Rhvac - Re`isidential 'Light Commercial HVAC Load§ _ Elite`Software Development, lnc. Residential Energy Calds Etter Residence _ Port Saint Lucie, FL 34983 Page 6 Total Building Summary Loads Components ,�; F x R z Area ` Sen' «.-��; kaLaf � Sen Total x; s w r Descnption:�G , N y Q an$. xLoss��Gain-�Ga�n <Gain 1A-cm-o: Glazing -Single pane, operable window, clear, 31.5 1,120 0 2,056 2,056 metal frame no break, u-value 1.27, SHGC 0.76 1A-cb-o: Glazing -Single pane, operable window, clear, 107.5 3,249 0 8,174 8,174 metal frame with break, u-value'1.08, SHGC 0.75 7A-1: Glazing -Glass or plastic block, smooth or wide ribs 7 118 0 366 366 or flutes, no screen, no coating, u-value 0.6, SHGC 0.65 1 OA-m: Glazing -French door, single pane clear glass, 12 561 0 435 435 metal frame no break, u-value 1.67, SHGC 0.53 11 D: Door -Wood - Solid Core 21 229 0 213 213 13A-5ocs: Wall -Block, board insulation only, R-5 board 1807.2 6,329 0 3,456 3,456 insulation, open core, siding finish 12C-Osw: Wall -Frame, R-13 insulation in 2 x 4 stud 136 347 0 266 266 cavity, no board insulation, siding finish, wood studs 16C-30: Roof/Ceiling-Under Attic with Insulation on Attic 1704 1,527 0 2,181 2,181 Floor (also use for Knee Walls and Partition Ceilings), Vented Attic, No Radiant Barrier, White or Light Color Shingles, Any Wood Shake, Light Metal, Tar and Gravel or Membrane, R-30 insulation 22A-ph: Floor -Slab on grade, No edge insulation, no 227 8,630 0 0 0 insulation below floor, any floor cover, passive, heavy moist soil _ Subtotals for structure: 22,110 0 17,147 17,147 People: 6 1,200 1,380 2,580 Equipment: 1,500 900 2,400 Lighting: 0 0 0 Ductwork: 7,466 1,594 5,913 7,507 Infiltration: Winter CFM: 94, Summer CFM: 28 2,892 1,178 470 1,648 Ventilation: Winter CFM: 45, Summer CFM: 45 1,385 1,868 742 2,610 AED Excursion: 0 0 1,123 1,123 Total Building Load Totals: 33,853 7,340 27,675 35,015 ,:Cheek Fi uses E �5 `,• Total Building Supply CFM: 1,225 CFM Per Square ft.: 0.719 Square ft. of Room Area: 1,704 Square ft. Per Ton: 584 Volume (ft3) of Cond. Space: 13,884 'Builiin .Loads F 3 ' Total Heating Required Including Ventilation Air: 33,853 Btuh 33.853 MBH Total Sensible Gain: 27,675 Btuh 79 % Total Latent Gain: 7,340 Btuh 21 % Total Cooling Required Including Ventilation Air: 35,015 Btuh 2.92 Tons (Based On Sensible + Latent) Rhvac is an ACCA approved Manual J and Manual D computer program. Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D. All computed results are estimates as building use and weather may vary. Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at your design conditions. C:\ ...\Etter Residence.rh9 Wednesday, April 23, 2014, 10:44 AM -,,Residential & Light Commercial HVAC Loads " '1'064ESaint Elite Software Development, Inc. 1Rhvac Residential`Energy Calc's Etter Residence. Lucie,'FL 34983 Page 8 Detailed Room Loads - Room,1 - Foyer (Peak Fenestration. Gain Procedure) Room is in zone 1, which peaks at 5 pm Calculation Mode: Htg. & clg. Occurrences: 1 Room Length: 10.0 ft. System Number. 1 Room Width: 4.0 ft. Zone Number: 1 Area: 40.0 sq.ft. Supply Air: 62 CFM Ceiling Height: 8.0 ft. Supply Air Changes: 11.6 AC/hr Volume: 320.0 cu.ft. Req. Vent. Clg: 0 CFM Number of Registers: 1 Actual Winter Vent.: 3 CFM Runout Air: 62 CFM Percent of Supply.: 5 % Runout Duct Size: 5 in. Actual Summer Vent.: 2 CFM Runout Air Velocity: 452 ft./min. Percent of Supply: 3 % Runout Air Velocity: 452 ft./min. Actual Winter Infil.: 5 CFM Actual Loss: 0.169 in.wg./100 ft. Actual Summer Infil.: 1 CFM �M kDescri tion .`Ht Value`s HTM HTNIGa Gains , ; 4K�>;, r ;;Quantity, . , . ; ; , i, :Loss.... , S -Wall-13A-5ocs 10 X 8 47 0,125 3.5 165 1.9 0 90 W -Wall-13A-5ocs 4 X 8 32 0.125 3.5 112 1.9 0 61 S-Door-11 D 3 X 7 21 0.390 10.9 229 10.1 0 213 S-GIsAA-cm-o shgc-0.75 0%S 12 1.270 35.6 427 49.3 0 591 UP-Ceil-16C-30 10 X 4 40 0.032 0.9 36 1.3 0 51 Floor-22A-ph 14 ft..Per. 14 1.358 38.0 532 0.0 0 0 Subtotals for Structure: 1,501 0 1,006 Infil.: Win.: 5.0, Sum.: 1.6 112 1.366 153 0.223 62 25 Ductwork: 494- 273 AED Excursion_: 52 Room Totals: _ _ 2,148 _ 62 1,356 C:\ ...\Etter Residence.rh9 Wednesday, April 23, 2014, 10:44 AM Rhvac - Residential & Light Commercial HVAC Loads; Elite Software, Development, Inc. Energy 106it Etter Re sidence' Samt Luc eFL 34983,Pa e'9 Detailed -Room Loads - Room 2 -_Laundry, (Peak Fenestration Gain Procedure) Room is in zone 1, which peaks at 5 pm Calculation Mode: Htg. & clg. Occurrences: 1 Room Length:' 11.5 ft. System Number: 1 Room Width: 6.0 ft. Zone Number: 1 Area: 69.0 sq.ft. Supply Air: 39 CFM Ceiling Height: 8.0 ft. Supply Air Changes: 4.2 AC/hr Volume: 552.0 cu.ft. Req. Vent. Clg: ' 0 CFM Number of Registers: 1 Actual Winter Vent.: 2 CFM Runout Air: 39 CFM Percent of Supply.: 6 % Runout Duct Size: 4 in. Actual Summer Vent.: 1 CFM Runout Air Velocity: 447 ft./min. Percent of Supply: 3 % Runout Air Velocity: 447 ft./min. Actual Winter Infil.: 5 CFM Actual Loss: 0.227 in.wg./100 ft. Actual Summer Infil.: 2 CFM At f f f4NAMf UensWLaf ff Y qy .4 �y 5 � ,� „ Quantity x 1/alue. HTM„ Loss,IIII a �, . Gain: x rGain S -Wall-13A-5ocs 11.5 X 8 92 0.125 3.5 322 1.9 0 176 W -Wall-13A-5ocs 4 X 8 32 0.125 3.5, 112 1.9 0 61 UP-Ceil-16C-30 11.5 X 6 69 0.032 0.9 62 1.3 0 88 Floor-22A-ph 16 ft._ Per. 16 1.358 38.0 _ 608 _ 0.0 0 0 Subtotals for Structure: 1,104 0 325 Infil.: Win.: 5.5, Sum.: 1.7 124 1.363 169 0.218 69 27 Ductwork: 380 173 AED Excursion: 33 Equipment: 300 300 Room Totals: 1,653 369 857 C:\ ...\Etter Residence.rh9 Wednesday, April 23, 2014, 10:44 AM Residential & Light Commercial_HVAC Loads ; ` = Elite Software Development, Inc. [Rhvac Residential Energy,Calc's Etter Residence , Po'rt Saint Lucie, FL 34M ` : Pa a 10- Detailed Room :Loads - Room 3 -. Living (Peak Fenestration Gain Procedure) General ., X"' � . Room is in zone 1, which peaks at 5 pm Calculation Mode: Htg. & clg. Occurrences: 1 Room Length: 22.0 ft. System Number: 1 Room Width: 16.0 ft. Zone Number: 1 Area: 352.0 sq.ft. Supply Air: 315 CFM Ceiling Height: 8.0 ft. Supply Air Changes: 6.7 AC/hr Volume: 2,816.0 cu.ft. Req. Vent. Clg: 0 CFM Number of Registers: 3 Actual Winter Vent.: 7 CFM Runout Air: 105 CFM Percent of Supply.: 2 % Runout Duct Size: 6 in. Actual Summer Vent.: 11 CFM Runout Air Velocity: 535 ft./min. Percent of Supply: 3 % Runout Air Velocity: 535 ft./min. Actual Winter Infil.: 14 CFM Actual Loss: 0.183 in.wg./100 ft. Actual Summer Infil.: 4 CFM `Ht9 E ,fin'#j �Clg F Lath Sena B. �,Descri +�HT.M. Gam .1,1Gain;<, W -Wall-13A-5ocs 16 X 10 133 0.125 3.5 466 1.9 0 254 E -Wall-13A-5ocs 16 X 10 150 0.125 3.5 525 1.9 0 287 W -GIs-1A-cb-o shgc-0.75 1%S 27 1.080 30.2 816 134.7 0 3,636 E -GIs-1A-cb-o shgc-0.75 0%S 10 1.080 30.2 302 56.6 0 566 UP-Ceil-16C-30 22 X 16 352 0.032 0.9 315 1.3 0 451 Floor-22A-ph 32 ft..Per. 32 1.358 38.0 1,217 0.0 0 0 Subtotals for Structure: 3,641 0 5,194 Infil.: Win.: 14.2, Sum.: 4.3 320 1.363 436 0.222 178 71 Ductwork: 1,217 1,393 AED_Excursion: 265 Room Totals: 5,294 178 6,923 C:\ ...\Etter Residence.rh9 Wednesday, April 23, 2014, 10:44 AM Rhvac -Residential& Light Commercial HVAC Loads Elite Software Development,' Inc. Residential Energy Ues Etter Residence poit,Saint Lucie, FL 34983 . � x ' ; - . - pa a 11 'Detailed Room Loads - Room 4 - Breakfast. (Peak Fenestration Gain Procedure) Room is in zone 1, which peaks at 5 pm Calculation Mode: Htg. & clg. Occurrences: 1 Room Length: 14.0 ft. System Number: 1 Room Width: 14.0 ft. Zone Number: 1 Area: 196.0 sq.ft. Supply Air: 235 CFM Ceiling Height: 8.0 ft. Supply Air Changes: 9.0 AC/hr Volume: 1,568.0 cu.ft. Req. Vent. Clg: 0 CFM Number of Registers: 3 Actual Winter Vent.: 3 CFM Runout Air: 78 CFM Percent of Supply.: 1 % Runout Duct Size: 5 in. Actual Summer Vent.: 8 CFM Runout Air Velocity: 575 ft./min. Percent of Supply: 3 % Runout Air Velocity: 575 ft./min. Actual Winter Infil.: 5 CFM Actual Loss: 0.272 in.wg./100 ft. Actual Summer Infil.: 1 CFM Item : . A it Q rea y, rSen , CIg 4z � Lat3 � r Sen tl1 F.�2y,0.'�'M�ib'ti$i�si-7 4 Y.!'�lk;' .. - cif^ ,`.�a Yy ,.....:Quanti -.. , f, slue 3 T .:: .Loss .. _ ♦V_ :. r ,HTM am. t Gamc; W -Wall-13A-5ocs 14 X 8 89.5 0.125 3.5 313 1.9 0 171 W -GIs-1A-cb-o shgc-0.75 2%S 22.5 1.080 30.2 680 134.3 0 3,022 UP-Ceil-1 6C-30 14 X 14 196 0.032 0.9 176 1.3 0 251 Floor-22A-014 ft..Per. 14 1.358 38.0 532 0.0 0 0 Subtotals for Structure: 1,701 0 3,444 Infil.: Win.: 5.0, Sum.: 1.5 112 1.366 153 0.223 62 25 Ductwork: 554 1,040 AED Excursion: 197 People: 200 lat/per, 230 sen/per: 2 400 460 Equipment: 300 0 _ _ _ _ _ Room Totals: 2,408 762 6,166 C:\ ...\Etter Residence.rh9 Wednesday, April 23, 2014, 10:44 AM RHva c - Residential & Light Commercial HVAC Loads Elite Software Development, Inc. Residential Energy CaIds Etter Residence: Port Saint Lucie,' FL 34983 Rae 12 -Detailed Room Loads'- Room 5 - Kitchen (Peak Fenestration Gain Procedure) ,'10e000...:z Room is in zone 1, which peaks at 5 pm Calculation Mode: Htg. & clg. Occurrences: 1 Room Length: 14.0 ft. System Number: 1 Room Width: 10.0 ft. Zone Number: 1 Area: 140.0 sq.ft. Supply Air: 135 CFM Ceiling Height: 8.0 ft. Supply Air Changes: 7.2 AC/hr Volume: 1,120.0 cu.ft. Req. Vent. Clg: 0 CFM Number of Registers: 2 Actual Winter Vent.: 6 CFM Runout Air: 67 CFM Percent of Supply.: 4 % Runout Duct Size: 5 in. Actual Summer Vent.: 5 CFM Runout Air Velocity: 494 ft./min. Percent of Supply: 3 % Runout Air Velocity: 494 ft./min. Actual Winter Infil.: 12 CFM Actual Loss: 0.201 in.wg./100 ft. Actual Summer Infil.: 4 CFM � a ..,�'� 4 .' t x` t &z`' +xx : 1.W,'w� .� s i qr"�:°; �4U �iFltg Sens �' xCl9� F, HTMH Loss TM Gain ,Sen Gam a_.;' :Value. ,� b .l_'_.; . W -Wall-13A-5ocs 14 X 8 108 0.125 3.5 378 1.9 0 207 N -Wall-13A-5ocs 10 X 8 68 0.125 3.5 238 1.9 0 130 NE-Wall-13A-5ocs 10 X 8 80 0.125 3.5 280 1.9 0 153 W -GIs-7A-1 shgc-0.65 5%S (2) 4 0.600 16.8 68 109.5 0 438 N -GIs-10A-m shgc-0.53 5%S 12 1.670 46.8 561 40.3 0 484. UP-Ceil-16C-30 14 X 10 140 0.032 0.9 125 1.3 0 179 Floor-22A-ph 34 ft..Per. 34 1.358 38.0 1,293 0.0 0 0 Subtotals for Structure: 2,943 0 1,591 Infil.: Win.: 12.0, Sum.: 3.6 272 1.360 370 0.221 151 60 Ductwork: 989 596 AED Excursion: 113 Equipment: _ 600 600 Room Totals: 4,302 751 2,960 C:\ ...\Etter Residence.rh9 Wednesday, April 23, 2014, 10:44 AM 1 Rhvac Residential '& Light Commercial HVAC Loads Elite Software Development, Inc. .Residential. Energy Calc s Etter Residence Port.Saint Lucie' FL 34983 _.. Pa a 13 Detailed Room Loads - Room 6 - Bath 1 (Peak Fenestration Gain Procedure) ..... M ..i�.,. .� i£: .1L. 5: .., h .� $ .r�:Yu�,�( g lk. ....��h p1 .� ✓^"..�.'tM` `Sti :: !''Cr 4j. W T 5 +$a Room is in zone 1, which peaks at 5 pm Calculation Mode: Htg. & clg. Occurrences: 1 Room Length: 9.0 ft. System Number: 1 Room Width: 8.0 ft. Zone Number: 1 Area: 72.0 sq.ft. Supply Air: 30 CFM Ceiling Height: 8.0 ft. Supply Air Changes: 3.1 AC/hr Volume: 576.0 cu.ft. Req. Vent. Clg: 0 CFM Number of Registers: 1 Actual Winter Vent.: 2 CFM Runout Air: 30 CFM Percent of Supply.: 5 % Runout Duct Size: 4 in. Actual Summer Vent.: 1 CFM Runout Air Velocity: 344 ft./min. Percent of Supply: 3 % Runout Air Velocity: 344 ft./min. Actual Winter Infil.: 3 CFM Actual Loss: 0.136 in.wg./100 ft. Actual Summer Infil.: 1 CFM y _U Areasz_ Item . v� s�E#�,� Wa ' Desen tion�4, �;, TfUI Ia�S��x .,.,��' �, x :,Qaariti„ ,;�,�ValueI; I NE-Wall-13A-5ocs 9 X 8 66 0.125 3.5 231 1.9 0 126 NE-GIs-1A-cb-o shgc-0.75 0%S 6 1.060 30.2 181 44.7 0 268 UP-Ceil-16C-30 9 X 8 72 0.032 0.9 65 1.3 0 92 Floor-22A-ph 9 ft.. Per. 9 1.358 38.0 342 0.0 0 0 _ _ _ _ _ Subtotals for Structure: 819 '0 486 Infil.: Win.: 3.2, Sum.: 1.0 72 1.361 98 0.222 40 16 Ductwork: 274 133 AED Excursion: 25 Room Totals: 1,191 40 660 C:\ ...\Etter Residence.rh9 Wednesday, April 23, 2014, 10:44 AM Rhdac - Residential & Light Commercial HVAC Loads: Ciids Elite Software Development, Inc.' Etter R ence P6 ttSainlal t Luc er FL 34983 a e14 Page Detailed Room "Loads - Room 7 - Den/Bedroom 2 (Peak Fenestration Gain Procedure) General... Room is in zone 1; which peaks at 5 pm Calculation Mode: Htg. & clg. Occurrences: 1 Room Length: 13.0 ft. System Number: 1 Room Width: 11.0 ft. Zone Number: 1 Area: 143.0 sq.ft. Supply Air: 100 CFM Ceiling Height: 8.0 ft. Supply Air Changes: 5.3 AC/hr Volume: 1,144.0 cu.ft. Req. Vent. Clg: 0 CFM Number of Registers: 1 Actual Winter Vent.: 4 CFM Runout Air: 100 CFM Percent of Supply.: 4 % Runout Duct Size: 6 in. Actual Summer Vent.: 3 CFM Runout Air Velocity: 511 ft./min. Percent of Supply: 3 % Runout Air Velocity: 511 ft./min. Actual Winter Infil.: 8 CFM Actual Loss: 0.167 in.wg./100 ft. Actual Summer Infil.: 2 CFM Item Area -U- , Htg . Sen Cig Lat : Sen Description' Quanti Val HTM Loss .. ` HTM Gain _ Gain` NE-Wall-13A-5ocs 10 X 8 65 0.125 3.5 228 1.9 0 124 E -Wall-13A-5ocs 13 X 8 104 0.125 3.5 364 1.9 0 199 NE-GIs-1A-cb-o shgc-0.75 0%S 15 1.080 30.2 454 44.7 0 670 U P-Ceil-1 6C-30 13 X 11 143 0.032 0.9 128 1.3 0 183 Floor-22A-ph 23 ft.. Per. 23 1.358 38.0 875 0.0 0 0 Subtotals for Structure: 2,049 0 1,176 Infil.: Win.: 8.1, Sum.: 2.5 184 1.364 251 0.223 102 41 Ductwork: 687 444 AED Excursion: 84 People: 200 lat/per, 230 sen/per: 2 400 460 Equipment: 300 0 Room Totals: 2,987 802 2,205 C:\ ...\Etter Residence.rh9 Wednesday, April 23, 2014, 10:44 AM '-Rhvac - Residential & Light Commercial HVAC Loads • Residential Energy Calds „ , Elite,Software Development,, Inc. Etter Residence .Poo,'SaintLucie, FL 34983 Page 16 Detailed Room Loads - Room 8 - Stairway (Peak Fenestration Gain Procedure) General~� � t Room is in zone 1, which peaks at 5 pm Calculation Mode: Htg. & clg. Occurrences: 1 Room Length: 15.0 ft. System Number: 1 Room Width: 4.0 ft. Zone Number: 1 Area: 60.0 sq.ft. Supply Air: 9 CFM Ceiling Height: 8.0 ft. Supply Air Changes: 1.1 AC/hr Volume: 480.0 cu.ft. Req. Vent. Clg: 0 CFM Number of Registers: 1 Actual Winter Vent.: 1 CFM Runout Air: 9 CFM Percent of Supply.: 8 % Runout Duct Size: 4 in. Actual Summer Vent.: 0 CFM Runout Air Velocity: 99 ft./min. Percent of Supply: 3 % Runout Air Velocity: 99 ft./min. Actual Winter Infil.: 1 CFM Actual Loss: 0.012 in.wg./100 ft. Actual Summer Infil.: 0 CFM item,*"g ;, . tg x� ,Sen E ics iY�d a�&/.kS L} s.' & .' .: jxn P 6;, „�a ..,,. s ...Quantit' _ .Value HTMtF h Loss, ;.HTMu ,AGain:Gain E -Wall- 1 3A-5ocs 4 X 8 32 0.125 3.5 112 1.9 0 61 UP-Ceil-16C-30 15 X 4 60 0.032 0.9 54 1.3 0 77 Floor-22Aph 4 ft.. Per. 4 1.358 38.0 152 0.0 0 0 Subtotals for Structure: 318 0 138 Infil.: Win.: 1.4, Sum.: 0.4 32 1.375 44 0.219 18 7 Ductwork: 108 38 AED Excursion: 7 Room Totals: 470 18 191 C:\ ...\Etter Residence.rh9 Wednesday, April 23, 2014, 10:44 AM Rhvac - Residential.& Light Commercial HVAC Loads ;: Elite Software Development, Inc.` Residential Energy CaVs 11`1"POft Etter Residence_. Saint Lucie, FL 34983 e, Pa a 16. Detailed Room Loads - Room 9 - Hall (Peak Fenestration Gain Procedure General ' jj�J, sY ..§K .3 y i , .. n:, x .. , _ ,. ,. rti s.t..:,r} `k ,4 ,. . o...isn♦»!T )k, .wL _ .3 Room is in zone 2, which peaks at 5 pm Calculation Mode: Htg. & clg. Occurrences: 1 Room Length: 16.0 ft. System Number: 1 Room Width: 8.0 ft. Zone Number: 2 Area: 128.0 sq.ft. Supply Air: 103 CFM Ceiling Height: 8.0 ft. Supply Air Changes: 6.0 AC/hr Volume: 1,024.0 cu.ft. Req. Vent. Clg: 0 CFM Number of Registers: 1 .Actual Winter Vent.: 3 CFM Runout Air: 103 CFM Percent of Supply.: 3 % Runout Duct Size: 6 in. Actual Summer Vent.: 3 CFM Runout Air Velocity: 525 ft./min. Percent of Supply: 3 % Runout Air Velocity: 525 ft./min. Actual Winter Infil.: 9 CFM Actual Loss: 0.176 in.wg./l00 ft. Actual Summer Infil.: 3 CFM San�Clg Item : :,:Area ,�U� Fltg�WOO t sLat n, wrSen Dese�i tion'a;>,,.h" .` Ay. .°>�Quantt t.:_Value FIT,Nf L ..,. i._._ss HTM Ga E-Wa11-13A-5ocs 8 X 8.5 48.5 0.125 3.5 170 1.9 0 93 E -Wall-12C-Osw 16 X 8.5 136 0.091 2.5 347 2.0 0 266 E -GIs-1 A-cm-o shgc-0.75 0%S 19.5 1.270 35.6 693 59.2 0 1,154 UP-Ceil-16C-30 16 X 8 128 0.032 0.9 115 1.3 0 164 Subtotals for Structure: 1,325 0 1,677 Infil.: Win.: 9.0, Sum.: 2.7 204 1.363 278 0.221 113 45 Ductwork: 479 456 AED Excursion: 87 Room Totals: 2,082 113 2,264 C:\ ...\Etter Residence.rh9 Wednesday, April 23, 2014, 10:44 AM Rhvac - Residential &,Light Commercial HVAC Loads- " ` L Elite Software Development„ Inc. Residential: Energy Calc s Etter Residence Port Saint Lucie, FL 34983� . _ . : ` Pa a 17 .Detailed Room Loads ' Room,1 O - Walk In -Closet 1 (Peak Fenestration Gain Procedure) General ' � }..�� ,�.. K,�a � .t,.,�>A M�. ,:,� _ ' �,. ks �...,hf�"` `r�.�t��� .�::af ��� _�. � 4Y r`=4K �,��,�.•; � ,r; Room is in zone 2, which peaks at 5 pm Calculation Mode: Htg. & clg. Occurrences: 1 Room Length: 11.0 ft. System Number: 1 Room Width: 10.0 ft. Zone Number: 2 Area: 110.0 sq.ft. Supply Air: 30 CFM Ceiling Height: 8.5 ft. Supply Air Changes: 2.0 AC/hr Volume: 935.0 cu.ft. Req. Vent. Clg: 0 CFM Number of Registers: 1 Actual Winter Vent.: 3 CFM Runout Air: 30 CFM Percent of Supply.: 10 % Runout Duct Size: 4 in. Actual Summer Vent.: 1 CFM Runout Air Velocity: 348 ft./min. Percent of Supply: 3 % Runout Air Velocity: 348 ft./min. Actual Winter Infil.: 8 CFM Actual Loss: 0.139 in.wg./100 ft. Actual Summer Infil.: 2 CFM ', ,+ i.S t ',.' }t ... �-� 1. 12 item �Ar�ea tHtg+ S:enF r�C9r a mat ,'$e �Garn; i S -Wall-13A-5ocs 10.2 X 8.5 86.7 0.125 3.5 303 1.9 0 166 W -Wall-13A-5ocs 10 X 8.5 85 0.125 3.5 298 1.9 0 163 UP-Ceil-16C-30 11 X 10 110 0.032 0.9 99 1.3 0 141 Floor-22A-ph 20 ft..Per. 20 1.358 38.0 760 0.0 0 0 Subtotals for Structure: 1,460 0 470 Infil.: Win.: 7.6, Sum.: 2.3 172 1.363 234 0.221 95 38 Ductwork: 506 134 AED Excursion: 26 Room Totals: 2,200 95 668 C:\ ...\Etter Residence.rh9 Wednesday, April 23, 2014, 10:44 AM Rhvac . Residential & Light Commercial HVAC Loads, Elite Software Development, Inc.' Residential Energy.Galc's ... ; Efter_Residence„ Portsaint Lucie, FL 34983 Page, 18 Detailed Room Loads - Room ' 11 - Master Bedroom (Peak Fenestration Gain Procedure),. �i ;..• � Mv`tf .. Y ..:1. l 'Y +f{i. �...: � �'.. �'p� .. ^`C.-. 4t it ,_. _. .. .. . ' Room is in zone 2, which peaks at 5 pm Calculation Mode: Htg. & clg. Occurrences: 1 Room Length: 17.5 ft. System Number: 1 Room Width: 12.0 ft. Zone Number: 2 Area: 210:0 sq.ft. Supply Air: 221 CFM Ceiling Height: 8.5 ft. Supply Air Changes: 7.4 AC/hr Volume: 1,785.0 cu.ft. Req. Vent. Clg: 0 CFM Number of Registers: 3 Actual Winter Vent.: 5 CFM Runout Air: 74 CFM Percent of Supply.: 2 % Runout Duct Size: 5 in. Actual Summer Vent.: 7 CFM Runout Air Velocity: 541 ft./min. Percent of Supply: 3 % Runout Air Velocity: 541 ft./min. Actual Winter Infil.: 10 CFM Actual Loss: 0.241 in.wg./100 ft. Actual Summer Infil.: 3 CFM Item r{, ,�Areas$ fU x. }Htg , :: z SeClg Will LatY'° Sen + nili �. Descry tion �,, r 'HTMb f{� Hr..� GalfiMr s� .....:Q_uantitf#Value 500 a F .Gain, W -Wall-13A-5ocs 12 X 8.5 87 0.125 3.5 305 1.9 0 166 NE-Wall-I3A-5ocs 14 X 8.5 107 0.125 3.5 375 1.9 0 205 W -GIs-1A-cb-o shgc-0.75 2%S 15 1.080 30.2 454 134.3 0 2,015 NE-GIs-1A-cb-o shgc-0.75 0%oS (2) 12 1.080 30.2 362 44.7 0 536 UP-Ceil-16C-30 17.5 X 12 210 0.032 0.9 188 1.3 0 269 Floor-22A-ph 26 ft..Per. 26 1.358 38.0 989 0.0 0 0 Subtotals for Structure: 2,673 0 3,191 Infil.: Win.: 9.8, Sum.: 3.0 221 1.362 301 0.222 123 49 Ductwork: 888 979 AED Excursion: 186 People: 200 fat/per, 230 sen/per: 2 400 460 Room Totals: 3,862 523 4,865 C:\ ...\Etter Residence.rh9 Wednesday, April 23, 2014, 10:44 AM 46 - Residential & Light Commercial'HVAC Loads - Elite Software Development, Inc. Residential Energy Calc's Etter Residence° :Port Saint Lucie, FL 34983 Page 19 Detailed Room Loads - Room 12 - Master Bath (Peak Fenestration Gain Procedure) Room is in zone 2, which peaks at 5 pm Calculation Mode: Htg. & cig. Occurrences: 1 Room Length: 13.0 ft. System Number: 1 Room Width: 10.0 ft. Zone Number: 2 Area: 130.0 sq.ft. Supply Air: 37 CFM Ceiling Height: 8.5 ft. Supply Air Changes: 2.0 AC/hr Volume: 1,105.0 cu.ft. Req. Vent. Clg: 0 CFM Number of Registers: 1 Actual Winter Vent.: 3 CFM Runout Air: 37 CFM Percent of Supply.: 8 % Runout Duct Size: 4 in. Actual Summer Vent.: 1 CFM Runout Air Velocity: 428 ft./min. Percent of Supply: 3 % Runout Air Velocity: 428 ft./min. Actual Winter Infil.: 8 CFM Actual Loss: 0.208 in.wg./l00 ft. Actual Summer Infil.: 2 CFM Item;, ur�`ri �yyArea jH�U x, en SLaCItT�alue DescK: .,..Quanti,MV; MM.oss�f Gxhai> n NE-Wall-13A-5ocs 12 X 8.5 99 0.125 3.5 347 1.9 0 189 E -Wall-13A-5ocs 8 X 8.5 68 0.125 3.5 238 1.9 0 130 NE-GIs-7A-1 shgc-0.65 0%S 3 0.600 16.8 50 34.0 0 102 U P-Ceil-1 6C-30 13 X 10 130 0.032 0.9 116 1.3 0 166 Floor-22A-ph 20 ft.. Per. 20 1.358 38.0 760 0.0 0 0 Subtotals for Structure: _ 1,511 _ 0 587 Infil.: Win.: 7.5, Sum.: 2.3 170 1.359 231 0.224 94 38 Ductwork: 520 165 AED Excursion: 31 _ Room Totals: _ 2,262 94 822 C:\ ...\Etter Residence.rh9 Wednesday, April 23, 2014, 10:44 AM ,Rhvac - Re_sidential& Light Commercial HVAC Loads Elite Software Development, Inc. _ Residential Energy Cald _ Etter Residence. : Port Saint Lucie, FL 34983 s Raga 20 Detailed Room Loads - Room 13 - Walk In Closet 2. (Peak Fenestration Gain 'Procedure) h pg General i t � aa. A. F .Arig: rSh 'fib � t.S! l <f� 3}Y13"f5 'tij`SA,�✓��N,4�AjY �?,t"K,:��i`��. �FJ 4:4�3L�Y l...'%Y.%Mr � ,E:3 N Room is in zone 2, which peaks at 5 pm Calculation Mode: Htg. & clg. Occurrences: 1 Room Length: 6.0 ft. System Number: 1 Room Width: 9.0 ft. Zone Number: 2 Area: 54.0 sq.ft. Supply Air: 20 CFM Ceiling.Height: 8.5 ft. Supply Air Changes: 2.7 AC/hr Volume: 459.0 cu.ft. Req. Vent. Clg: 0 CFM Number of Registers: 1 Actual Winter Vent.: 2 CFM Runout Air: 20 CFM Percent of Supply.: 11 % Runout Duct Size: 4 in. Actual Summer Vent.: 1 CFM Runout Air Velocity: 234 ft./min. Percent of Supply: 3 % Runout Air Velocity: 234 ft./min. Actual Winter Infil.: 6 CFM Actual Loss: 0.064 in.wg./100 ft. Actual Summer Infil.: 2 CFM €.;4.0 Area CI" Lata MtSen; QuantitValue,„ ; Loss HTM�,� ;HTMt: _,Gaina W -Wall-13A-5ocs 9 X 8.5 76.5 0.125 3.5 268 1.9 0 146 NE-Wall-13A-5ocs 6 X 8.5 51 0.125 3.5 179 1.9 0 98 UP-Ceil-16C-30 6 X 9 54 0.032 0.9 48 1.3 0 69 Floor-22A-ph 15 ft..Per. 1.358 38.0 570 0.0 0 _ _15 Subtotals for Structure: 1,065 _0 0 313 Infil.: Win.: 5.6, Sum.: 1.7 128 1.365 174 0.220 71 28 Ductwork: 370 90 AED Excursion: 17 Room Totals: 1,609 71 448 Q\ ...\Etter Residence.rh9 Wednesday, April 23, 2014, 10:44 AM Rhy c, -;,Residential & Light Commercial HVAC Loads Elite Software Development,'Inc.'. Residential Energy,Calds .. ; ._ Etter Residence.. Port Saint Lucie, FL _34983 ., - ` . Pa a 21 System 1 Room. Load Summaty h , Htg ��, Mm Runfr�,�r Run , t �Clg ,°Clg, Min 'Act' --Zone 1-- 1 Foyer 40 2,148 28 1-5 452 - 1,356 62 62 62 2 Laundry 69 1,653 21 1-4 447 857 369 39 39 3 Living 352 5,294 69 3-6 535 6,923 178 315 315 4 Breakfast 196 2,408 31 3-5 575 5,166 762 235 235 5 Kitchen 140 4,302 56 2-5 494 2,960 751 135 135 6 Bath 1 72 1,191 15 1-4 344 660 40 30 30 7 Den/Bedroom 2 143 2,987 39 1-6 511 2,205 802 100 100 _ 8_ Stairway 60 470 6 1-4 99 191 18 9 _ _ 9 Zone 1 subtotal 1,072 20,453 266 20,317 21'982 924 924 ---Zone 2-- 9 Hall 128 2,082 27 1-6 525 2,264 113 103 103 10 Walk In Closet 1 110 2,200 29 1-4 348 668 95 30 30 11 Master Bedroom 210 3,862 50 3-5 541 4,865 523 221 221 12 Master Bath 130 2,262 29 1-4 428 822 94 37 37 13 Walk In Closet 2 54 1,609 21 1-4 234 448 71 20 20 Zone 2 subtotal 632 12,015 15_6 9,067 896_ 4_1.3413__ Ventilation _ .1,385 _ _ 742 1,868 Duct Latent 1,594 System 1 total 1,704 33,853 422 27,675 7,340 1,225 1,225 System 1 Main Trunk Size: 12x18 in. Velocity: 817 ft./min Loss per 100 ft.: 0.094 in.wg Note: Since the system is multizone, the Peak Fenestration Gain Procedure was used to determine glass sensible gains at the room and zone levels, so the sums of the zone sensible gains and airflows for cooling shown above are not intended to equal the totals at the system level. Room and zone sensible gains and cooling CFM values are for the hour in which the glass sensible gain for the zone is at its peak. Sensible gains at the system level are based on the "Average Load Procedure + Excursion" method. Coolin S stem=Sumrna- ..; ;: { `' 4 Cooling Sensible/Latent Sensible , p Latenty Y Total; Net Required: 2.92 79% / 21 % 27,675 7,340 35,015 Actual: 3.02 78% / 22% 28,200 8,000 36,200 [Equipment Data.: : Heating System Cooling System Type: Electric Resistance Standard Air Conditioner Model: 14AJM36 14AJM36 Indoor Model: RHLL-HM3617+RCSL-H3617 Brand: SPLIT SYSTEM Description: SPLIT SYSTEM 8KW 15.5 SEER Efficiency: 0% 15.5 SEER Sound: 0 0 Capacity: 36,200 Btuh 36,200 Btuh Sensible Capacity: n/a 28,200 Btuh Latent Capacity: n/a 8,000 Btuh AHRI Reference No.: n/a 341209 Q\ ...\Etter Residence.rh9 Wednesday, April 23, 2014, 10:44 AM