Loading...
HomeMy WebLinkAboutHVAC Load CalculationsLynn & Andrew Stefanik Residence HVAC Load Calculations for Lynn & Andrew Stefanik Lot 44 River Point At The Sands Fort Pierce, Florida E Ell Ell 1W FJ ft " EL::& RosiDeNnAL, FxFtVACHVAC LoADs Prepared By: Residential Energy Calds Thur y March 03, 2016 1 OPY Rhvac is an ACCA approved Manual J and Manual D computer program. Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D. C:\ ...\Lynn & Andrew Stefanik Residence.rh9 Thursday, March 03, 2016, 4:00 PM Rhvac Residential & Light Commercial HVAC Loads Elite Software Development, Inc. Residential Energy Calc's Lynn &Andrew Stefarnk Residence •Port Saint `L' ucie, FL '34983 Fa a 3' Miscellaneous', Report System 1 Rleem Outdoor,' :; Qutdoor` Outdoor Indoor Indoor Grains Input Data D Bulb � ' Wet Bulb ` ReLHum' `Rel.Hum D Bulb' Difference Winter: 42 39.4 80% n/a 70 n/a Summer: 90 78 59% 50% 75 61.09 Duct Sizing. I npUts, Main Trunk Runouts Calculate: Yes Yes Use Schedule: Yes Yes Roughness Factor: 0.00300 0.01.000 Pressure Drop: 0.1000 in.wg./100 ft. 0.1000 in.wg./100 ft. Minimum Velocity: 650 ft./min 450 ft./min Maximum Velocity: 900 ft./min 750 ft./min Minimum Height: 0 in. 0 in. Maximum Height: 0 in. 0 in. ,Outside Air Data . Winter Summer Infiltration Specified: 0.320 AC/hr 0.160 AC/hr 114 CFM 57 CFM Infiltration Actual: 0.312 AC/hr 0.144 AC/hr Above Grade Volume: X 21,320 Cu.ft. X 21,320 Cut: 6,655 Cu.ft./hr 3,064 Cu.ft./hr X 0.0167 X 0.0167 Total Building Infiltration: 111 CFM 51 CFM Total Building Ventilation: 25 CFM 25 CFM ---System 1--- Infiltration & Ventilation Sensible Gain Multiplier: 16.49 = (1.10 X 0.999 X 15.00 Summer Temp. Difference) Infiltration & Ventilation Latent Gain Multiplier: 41.50 = (0.68 X 0.999 X 61.09 Grains Difference) Infiltration & Ventilation Sensible Loss Multiplier: 30.77 = (1.10 X 0.999 X 28.00 Winter Temp. Difference) Winter Infiltration Specified: 0.320 AC/hr (114 CFM), Construction: Average_ Summer Infiltration Specified: 0.160 AC/hr (57 CFM), Construction: Average Duct Load FactorScenarios for System -1 Attic Duct': Duct I Surface From No. , Type Description Location Ceiling Leakage, Insulation Area [T]MDD . 1 Supply Attic 16B 0.12 6 576 No 1 Return Attic 16B 0.12 6 426 No C:\ ...\Lynn & Andrew Stefanik Residence.rh9 Thursday, March 03, 2016, 4:00 PM Rhvac - Residential, &Ught Commercial HVAC Loads, Elite.'Softare Development, Inc. ,Residenti6l.'Enbrgy,,,Cal!c's�; Lynn &.Andrew,Stefanik Residen6e Fort Saint Lucie, FL;'34983 Page 4. Load Preview 2 Sys Sys Sys Net Sen Lpt N Sen Htg Clg Act Duct I Scope I Ton j lion j Area Gain I Gain j Gain tj Loss I CFM1 CFMI CFMI Size I Build! ' ng System I Ventilation Supply Duct Latent -Return Duct --Zone 1 1-Master Bedroom 2-Walk In Closet 3-Master Bath 4-Bedroom- 2 5-Bath 2 6-Bedroom 3 7-Foyer 8-Dining 9-Great Room 10-Kitchen 11-Study 12-Powder Room .... ..... -------- - - - 13-Laundry 3.86, 552 1 2,132 36,623 - 9,733' 46,357 38,877' 477; 1,452' 1,452 3.86' 552' 2,132 - -------- - - 36,623� 9,733' 46,357 38,8771 47711MI 1,452 14X17 -- - ------ 412' 1,038: 1,450 769: 586! 586 4,302, 1,69011 5,992 1,385 2,132 -- 31,909 --- ----- 6,419 38,328 36,723! 1,4521 14X17 280 6,630 1,385, 8,015' 7,9851 104 302 3-6 60 380 92: 472. 1,288: 171 17 1-4 .. . ........ 140' 128T 1,0921 2,379 1,552 20i 59 1-4 ........ ----- -------- ------ 168 1,538; 510 f 2,0481 1,936 25� -- ---- --- 70 1-5 140 710' 92: 802, 1,5521 20� 32 1-4 210 6,346' 7951 7,141 6,570, 85 289 3-6 -- --- ----- 84� 1,979 174' 2,153' 2,532. 331= 90 1-6 208! 381 73, 454, 940 12 17, 1-4 450 6,515 365. 6,880 4,540 59, 296- 3-6 162, 3,922; 1,248 � 5,170 3,645 47 M 178, 2­6 - - -------- ...... - - -­ ------ ........... 132, 893' -- -------- ­ 101 ­ - .. , '-­ 994 - . ., - - 1,773: ­­ ' 23jiM __ _'_ _' - 41 - ' _' 1-4 49; 202' 64, 266 7- k 1-4 49 1,127 428 1555 1742 2 3�, 51 1-4 C:\ ... \Lynn & Andrew Stefanik Residence.rh9 Thursday, March 03, 2016, 4:00 PM [Rhvac, - Residential, & Light Comrnercial,HyAC Loadsi, Elite bottware Ueveiqpment,inc.r I Residential En ergy Calds, Lynn & Andr6vStefanilk Re_ siqence Port Saint Lucie FL 34983 Page 5 Duct Size Preview Room or Minimum Maximum Rough. Design SPI Duct Duct Htg CIg Act. Duct Source Loss Velocity Length Flow Flow Flow Size Duct Name Velocity Velocity Factor 100 Vel System 1 ---- - ----- Supply Runouts .. . .......... - - - - - - --- - -------- -- --- Zone I 1 -Maste'rBedroom 450 750: 0.01 0.1 512.1 104 302 3-6 2-Wa'lk In"Clos-et Built-in --------- -- - ---------- - --- 450 ----- -- 750- 0.01. 0.1 -4- 198.1 17,= 17 -- --- ----- 1-4 3-Master Bath Built-in 450 750 0.01, 0.1 291M 59 1-4 4-Bedroom 2 Built-in ... . ....... 4501 750 0.01 _-6.70.8.., 0.11 513 26 70 1-5 5-Bath 2 Built-in 450- 750 0.01 0.1, 370.1 20= � 32 1-4 6-Bedroom 3 Built-in 450; 750 0.01: 0.1 490.1 85 289 3-6 7-Foyer 'Built-in 450 750 0.01 ......... . 0.1 ------ 90, 8-Dining Built -In 450 750 0.011 0.1 198.8 __33,= 12,:m 17: _1-6 1-4 9-Great Room 'Built -In 450 750' 0.01, 0.1, 503.2 W 296 3-6 I 0-Kitchen Built-in 50 4' 750 0.01 0.1 454.3' 47; 178 2-6 1 I -Study Built-in 450 75D 0.01 0.1 465.5- 23, 41 1-4 12-Powder Room Built-in 450- 750. 0.01 0.1 105.3- 69 9 1-4 1 laundry... 'Built-in .. .... . ... 450 750 . ..... 0.01, 0.1 587.8 23: 51 1-4 Other Ducts in System I Sui)Dlv Main Trunk Built-in 650, 900 0.003 0.1. --- ------- --------- 878.4: - ------ 477 ®j 1,462 14x17 Summary System 1 - ----- ---- ----- ---------- . ..... - --- ----- Heating Flow: 477 Cooling Flow: 1452 C:\ ... \Lynn & Andrew Stefanik Residence. rh9 Thursday, March 03, 2016, 4:00 PM RFrVac Residential & Light Commercial HVAC Loads Elite Software Development, Inc: Lynn & Andrew Stefamk Residence" Port;Sain't Cup erg LC34983•' " a e6 Total Building Summary Loads,. Component Area Sen s Lat Sen ;' Total ;.. l QuanLoss n; ,� zGam .Gain 1D-cb-o: Glazing -Double pane, operable window, clear, 230.3 4,191 0 11,739 11,739 metal frame with break, u-value 0.65, SHGC 0.67 1013-m: Glazing -French door, double pane clear glass, 48 1,948 0 2,366 2,366 metal frame no break, u-value 1.45, SHGC 0.47 11 D: Door -Wood - Solid Core 84 810 0 762 762 13A-4ocs: Wall -Block, board insulation only, R-4 board 1628.7 6,520 0 3,565 3,565 insulation, open core, siding finish 12C-Obw: Part -Frame, R-13 insulation in 2 x 4 stud 319 436 0 436 436 cavity, no board insulation, brick finish, wood studs 16E-30: Roof/Ceiling-Under Attic with Insulation on Attic 2132 1,909 0 1,705 1,705 Floor (also use for Knee Walls and Partition Ceilings), Vented Attic, No Radiant Barrier, Light Tile, Slate or Concrete, R-30 insulation 22A-ph: Floor -Slab on grade, No edge insulation, no 231 8,781 0 0 0 insulation below floor, any floor cover; passive, heavy moist soil Subtotals for structure: _ _ 24,595 0 20,573 20,573 People: 11 2,200 2,530 4,730 Equipment: 2,100 1,500 3,600 Lighting: 0 0 0 Ductwork: 10,098 2,277 9,617 11,894 Infiltration: Winter CFM: 111, Summer CFM: 51 3,414 2,119 841 2,960 Ventilation: Winter CFM: 25, Summer CFM: 25 769 1,038 412 1,450 AED Excursion: 0 0 1,150 1,150 _ _ _ _ Total Building Load Totals: _ _ 38,877 9,733 36,623 46,357 Check Fi ures Total Building Supply CFM: 1,452 CFM Per Square ft.: 0.681 Square ft. of Room Area: 2,132 Square ft. Per Ton: 552 Volume (fP) of Cond. Space: 21,320 Building Loads Total Heating Required Including Ventilation Air: 38,877 Btuh 38.877 MBH Total Sensible Gain: 36,623 Btuh 79 % Total Latent Gain: 9,733 Btuh 21 . % Total Cooling Required Including Ventilation Air: 46,357 Btuh 3.86 Tons (Based On Sensible + Latent) Notes Rhvac is an ACCA approved Manual J and Manual D computer program. Calculations are performed per ACCA Manual J 8th Edition„ Version 2., and ACCA Manual D. All computed results are estimates as building use and weather may vary. Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at your design conditions. C:\ ...\Lynn & Andrew Stefanik Residence.rh9 Thursday, March 03, 2016, 4:00 PM ' AC Loads 9 Res dental Ede dy Cal, s' ht Commercial HV ; _ 9Y - Elite Software Development, Inc. Lynn & Andrew Stefanik Residence ;Port Saint,Lucie, FL 34983 Pa e 8 Detailed Room Loads - Room 1 - Master Bedroom (Average Load Procedure) ,General Calculation Mode: Htg. & clg. Occurrences: 1 Room Length: 20.0 ft. System Number: 1 Room Width: 14.0 ft. Zone Number: 1 Area: 280.0 sq.ft. Supply Air: 302 CFM Ceiling Height: 10.0 ft. Supply Air Changes: 6.5 AC/hr Volume: 2,800.0 cu.ft. Req. Vent. Clg: 0 CFM Number of Registers: 3 Actual Winter Vent.: 5 CFM Runout Air: 101 CFM Percent of Supply.: 2 % Runout Duct Size: 6 in. Actual Summer Vent.: 5 CFM Runout Air Velocity: 512 ft./min. Percent of Supply: 2 % Runout Air Velocity: 512 ft./min. Actual Winter Infil.: 20 CFM Actual Loss: 0.168 in.wg./100 ft. Actual Summer Infil.: 9 CFM Item Area, -U- Htg Sen Clg Lat : Sen, Description Quantity Value,, , HTM Loss HTM Gain Gain W -Wall-13A-4ocs 14 X 10 104 0.143 4.0 416 2.2 0 228 S -Wall-13A-4ocs 20 X 10 181.6 0.143 4.0 727 2.2 0 397 N -Wall-13A-4ocs 8 X 10 14 0.143 4.0 56 2.2 0 31 N-Door-11 D 3 X 7 21 0.390 10.9 229 10.1 0 213 N-Door-11 D 3 X 7 21 0.390 10.9 229 10.1 0 213 W -GIs-1 D-cb-o shgc-0.67 27%S (2) 36 0.650 18.2 656 60.3 0 2,170 S -GIs-1 D-cb-o shgc-0.67 100%S 18.4 0.650 18.2 334 23.8 0 438 (2) N -GIs-10B-m shgc-0.47 100%S (2) 24 1.450 40.6 974 31.7 0 760 UP-Ceil-16E-30 20 X 14 280 0.032 0.9 251 0.8 0 224 Floor-22A_ph 42 ft:.Per. 42 1.358 38.0 1,597 0.0 0 0 _ _ Subtotals for Structure: 5,469 0 4,674 Infil.: Win.: 20.2, Sum.: 9.3 420 1.479 621 0.364 385 153 Ductwork: 1,895 1,104 AED Excursion: 239 People: 200 lat/per, 230 sen/per: 2 400 460 Equipment_ 600 0 _ _ Room Totals: 7,985 1,385 6,630 C:\ ...\Lynn & Andrew Stefanik Residence.rh9 Thursday, March 03, 2016, 4:00 PM C. ential arre'Dev6loprnent, In Port Sain[,,,Residential, Luce, FL 34983ht Commercial HVAC Loads Lyntn & Andrew Stefan k Resi 9e 9 ,Detailed Room Loads - Room 2 -Walk Iri Closet (Average Load Procedure) General Calculation Mode: Htg. & clg. Occurrences: 1 Room Length: 10.0 ft. System Number: 1 Room Width: 6.0 ft. Zone Number: 1 Area: 60.0 sq:ft. Supply Air: 17 CFM Ceiling Height: 10.0 ft. Supply Air Changes: 117 AC/hr Volume: 600.0 cu.ft. Req. Vent. Clg: 0 CFM Number of Registers: 1 Actual Winter Vent.: 1 CFM Runout Air: 17 CFM Percent of Supply.: 5 % Runout Duct Size: 4 in. Actual Summer Vent.: 0 CFM Runout Air Velocity: 198 ft./min. Percent of Supply: 2 % Runout Air Velocity: 198 ft./min. Actual Winter Infil.: 5 CFM Actual Loss: 0.046 in.wg./100 ft. Actual Summer Infil.: 2 CFM Item Area U a Htg t Sen { Clg Lat : Sen;. Description Quantit` Ualue; HTM y'_., Loss i 1 .HTM , `Gain. _=. Gain` S -Wall-13A-4ocs 10 X 10 100 0.143 4.0 400 2.2 0 219 UP-Ceil-16E-30 10 X 6 60 0.032 0.9 54 0.8 0 48 Floor-22A-ph 10 ft.. Per. 10 1.358 38.0 380 0.0 0 0 Subtotals for Structure: 834 0 267 Infil.: Win.: 4.8, Sum.: 2.2 100 1.480 148 0.360 92 36 Ductwork: 306 63 AED Excursion: 14 Room Totals: 1,288 92 380 C:\ ...\Lynn & Andrew Stefanik Residence.rh9 Thursday, March 03, 2016, 4:00 PM iRhvac Residential & Lighm t Comercial HVAC Loads Elite Software Development, Inc.l Residential Energy Calc's Lynn & Andrew Stefamk Resdence.1 Port Saint Lucie, FL'34983 Page 10 Detailed Room Loads - Room 3 - Master Bath (Average Load Procedure) ,General Calculation Mode: Htg. & clg. Occurrences: 1 Room Length: 14.0 ft. System Number: 1 Room Width: 10.0 ft. Zone Number: 1 Area: 140.0 sq.ft. Supply Air: 59 CFM Ceiling Height: 10.0 ft. Supply Air Changes: 2.5 AC/hr Volume: 1,400.0 cu.ft. Req. Vent. Clg: 0 ' CFM Number of Registers: 1 Actual Winter Vent.: 1 CFM Runout Air: 59 CFM Percent of Supply.: 2 % Runout Duct Size: 4 in. Actual Summer Vent.: 1 CFM Runout Air Velocity: 671 ft./min. Percent of Supply: 2 % Runout Air Velocity: 671 ft./min. Actual Winter Infil.: 5 CFM Actual Loss: 0.505 in.wg./100 ft. Actual Summer Infil.: 2 CFM S -Wall-13A-4ocs 10 X 10 90.8 0.143 4.0 364 2.2 0 199 S -GIs-1 D-cb-o shgc-0.67 100%S 9.2 0.650 18.2 167 23.8 0 219 U P-Ceil-1 6 E-30 14 X 10 140 0.032 0.9 125 0.8 0 112 Floor-22A-ph 10 ft.. Per. 10 1.358 38.0 380 0.0 0 0 Subtotals for Structure: 1,036 0 530 Infil.: Win.: 4.8, Sum.: 2.2 100 1.480 148 0.360 92 36 Ductwork: 368 214 AED Excursion: 46 People: 200 [at/per, 230 sen/per: 2 400 460 Equipment: 600 0 Room Totals: 1,552 1,092 1,287 C:\ ...\Lynn & Andrew Stefanik Residence.rh9 Thursday, March 03, 2016, 4:00 PM 7Rhvac Residential .&Light commercial HVAC Loads =' 'Elite Software Development, Inc. _ Residential Energy CalcIs, Lynn;& Andrew Stefarnk Residence r Port Saint Lucie, FL 34983 Pao - Detailed Room Loads - Room 4'-- Bedroom 2 (Average Load Procedure) GeneraF7 Calculation Mode: Htg. & clg. Occurrences: 1 Room Length: 14.0 ft. System Number: 1 Room Width: 12.0 ft. Zone Number: 1 Area: 168.0 sq.ft. Supply Air: 70 CFM Ceiling Height: 10.0 ft. Supply Air Changes: 2.5 AC/hr Volume: 1,680.0 cu.ft. Req. Vent. Clg: 0 CFM Number of Registers: 1 Actual Winter Vent.: 1 CFM Runout Air: 70 CFM Percent of Supply.: 2 % Runout Duct Size: 5 in. Actual Summer Vent.: 1 CFM Runout Air Velocity: 513 ft./min. Percent of Supply: 2 % Runout Air Velocity: 513 ft./min. Actual Winter Infil.: 6 CFM Actual Loss: 0.217 in.wg./100 ft. Actual Summer Infil.: 3 CFM S -Wall-13A-4ocs 12 X 10 105 0.143 4.0 420 2.2 0 230 S -GIs-1 D-cb-o shgc-0.67 100%S 15 0.650 18.2 273 23.9 0 358 UP-Ceil-16E-30 14 X 12 168 0.032 0.9 151 0.8 0 134 Floor-22A-ph 12 ft..Per. 12 1.358 38.0 456 0.0 0 0 Subtotals for Structure: 1,300 0 722 Infil.: Win.: 5.8, Sum.: 2.7 120 1.475 177 0.367 110 44 Ductwork: 459 256 AED Excursion: 55 People: 200 lat/per, 230 sen/per: 2 400 460 Room Totals: 1,936 510 1,538 C:\ ...\Lynn & Andrew Stefanik Residence.rh9 Thursday, March 03, 2016, 4:00 PM Rhvac Residential 8 Light Commercial HVAC Loads Residential Energy Calds Elite Software Development, Inc.' Lynn &Andrew Stefanik Residence. PortSaint;,Lucie, FL 34983 'Page,12 "Detailed. Room Loads - Room 5 Bath 2 (Average Load 'Procedure)" "General Calculation Mode: Htg. & clg. Occurrences: 1 Room Length: 14.0 ft. System Number: 1 Room Width: 10.0 ft. Zone Number: 1 Area: 140.0 sq.ft. Supply Air: 32 CFM Ceiling Height: 10.0 ft. Supply Air Changes: 1.4 AC/hr Volume: 1,400.0 cu.ft. Req. Vent. Clg: 0 CFM Number of Registers: 1 Actual Winter Vent.: 1 CFM Runout Air: 32 CFM Percent of Supply.: 3 % Runout Duct Size: 4 in. Actual Summer Vent.: 1 CFM Runout Air Velocity: 370 ft./min. Percent of Supply: 2 % Runout Air Velocity: 370 ft./min. Actual Winter Infil.: 5 CFM Actual Loss: 0.156 in.wg./100 ft. Actual Summer Infil.:. 2 CFM Item :Descn tion:� _ '.,�3 .� Area U Quantity,. .:Value.,,'_ Htg Sen *rzClg HT , ., Loss' HTIVI: Gain-�? Pon Gain S -Wall-13A-4ocs 10 X 10 90.8 0.143 4.0 364 2.2 0 199 S -GIs-1 D-cb-o shgc-0.67 100%S 9.2 0.650 18.2 I 167 23.8 0 219 UP-Ceil-16E-30 14 X 10 140 0.032 0.9 125 0.8 0 112 Floor-22A-ph 10 ft.. Per. 10 1.358 38.0 380 0.0 0 0 Subtotals for Structure: 1,036 0 530 Infil.: Win.: 4.8, Sum.: 2.2 100 1.480 148 0.360 92 36 Ductwork: 368 118 A_ED Excursion: 26 Room Totals: 1,552 92 710 C:\ ...\Lynn & Andrew Stefanik Residence.rh9 Thursday, March 03, 2016, 4:00 PM Rhvac Residential & Light Commercial HVAC Loads Residential Energy Calc s '{ „ ' Elite Software Development, Inc. Lynn &Andrew Stefanik Residence Port Saint Lucie, I- 34983 ; ' . V : Pa a 13 Detailed Room Loads - Room 6 - Bedroom. 3 (Average Load Procedure) General Calculation Mode: Htg. & clg. Occurrences: 1 Room Length: 15.0 ft. System Number: 1 Room Width: 14.0 ft. Zone Number: 1 Area: 210.0 sq.ft. Supply Air: 289 CFM Ceiling Height: 10.0 ft. Supply Air Changes: 8.2 AC/hr Volume: 2,100.0 cu.ft. Req. Vent. Clg: 0 CFM Number of Registers: 3 Actual Winter Vent.: 4 CFM Runout Air: 96 CFM Percent of Supply.: 2 % Runout Duct Size: 6 in. Actual Summer Vent.: 5 CFM Runout Air Velocity: 490 ft./min. Percent of Supply: 2 % Runout Air Velocity: 490 ft./min. Actual Winter Infil.: 21 CFM Actual Loss: 0.154 in.wg./100 ft. Actual Summer Infil.: 10 CFM Item Area -U- . Htg Sen -Clg Lat Sen Description, Quantity,Value,; HTM Loss HTM 11, Gain. Gain S -Wall-13A-4ocs 15 X 10 150 0.143 4.0 601 2.2 0 328 E -Wall-13A-4ocs 14 X 10 81.5 0.143 4.0 326 2.2 0 178 N -Wall-13A-4ocs 14 X 10 140 0.143 4.0 561 2.2 0 306 E -GIs-1 D-cb-o shgc-0.67 27%S (2) 36 0.650 18.2 656 60.3 0 2,170 E -GIs-1 D-cb-o shgc-0.67 33%S 22.5 0.650 18.2 409 57.5 0 1,293 UP-Ceil-16E-30 15 X 14 210 0.032 0.9 188 0.8 0 168 Floor-22A-ph 43 ft..Per. 43 1.358 38.0 1,635 0.0 0 0 Subtotals for Structure: 4,376 0 4,443 Infil.: Win.: 20.6, Sum.: 9.5 430 1.477 635 0.365 395 157 Ductwork: 1,559 1,057 AED Excursion: 229 People: 200 lat/per, 230 sen/per: 2 400 460 Room Totals: 6,570 795 6,346 C:\ ...\Lynn & Andrew Stefanik Residence.rh9 Thursday, March 03, 2016, 4:00 PM Rhvac Residential & Light Cornniercial HVAC Loads Elite Software Development, Inc,. Residential' Energy Calc's r Lynn `& Andrew Stefanik Residence' Port Saint Lucie, FL. 34983. ,• , .. -Pa a 14, Detailed Room Loads - Room► '7 = Foyer -(A verage Load -Procedure) ,General,7777771 Calculation Mode: Htg. & clg. Occurrences: 1 Room Length: 12.0 ft. System Number: 1 Room Width: 7.0 ft. Zone Number: 1 Area: 84.0 sq.ft. Supply Air: 90 CFM Ceiling Height: 10.0 ft. Supply Air Changes: 6.4 AC/hr Volume: 840.0 cu.ft. Req. Vent. Clg: 0 FM Number of Registers: 1 Actual Winter Vent.: 2 CFM Runout Air: 90 CFM Percent of Supply.: 2 % Runout Duct Size: 6 in. Actual Summer Vent.: 2 CFM Runout Air Velocity: 459 ft./min. Percent of Supply: 2 % Runout Air Velocity: 459 ft./min. Actual Winter Infil.: 9 CFM Actual Loss: 0.135 in.wg./100 ft. Actual Summer Infil.: 4 ' CFM Item wt Area U Htgx Sen ; 'Y ,?nClg Lat Sen:: Description _ b Quantit ..HTM Loss.¢ t HTM Gain Gain E -Wall-13A-4ocs 7 X 10 37 0.143 4.0 148 2.2 0 81 N -Part-15'/15°-12C-Obw 12 X 10 99 0.091 1.4 135 1.4 0 135 E-Door-11 D 3 X 7 21 0.390 10.9 229 10.1 0 213 N-Door-11 D 3 X 7 21 0.390 5.9 1 123 5.9 0 123 E -GIs-1 D-cb-o shgc-0.67 0%S (2) 12 0.650 18.2 218 74.2 0 890 UP-Ceil-16E-30 12 X 7 84 0.032 0.9 75 0.8 0 67 Floor-22A-ph 19 ft..Per. 19 1.358 38.0 722 0.0 0 0 Subtotals for Structure: 1,650 0 1,509 Infil.: Win.: 9.1, Sum.: 4.2 190 1.479 281 0.363 174 69 Ductwork: 601 330 A_E_D Excursion: 71 Room Totals: T 2,532 174 1,979 C:\ ...\Lynn & Andrew Stefanik Residence.rh9 Thursday, March 03, 2016, 4:00 PM Rhyac Reside tial & Light Commercial HVAC Loads Elite Software Development, Inc: 3Residenbal EnergyCalc s •. _ L nn & Andrew Stefanik Residence_ Porfa' int Lucie, FL '34983 ` - Page 15 Detailed Room Loads,- Room 8 = Dining (Average Load Procedure) General Calculation Mode: Htg. & clg. Occurrences: 1 Room Length: 16.0 ft. System Number: 1 Room Width: 13.0 ft. Zone Number: 1 Area: 208.0 sq.ft. Supply Air: 17 CFM Ceiling Height: 10.0 ft. Supply Air Changes: 0.5 AC/hr Volume: 2,080.0 cu.ft. Req. Vent. Clg: 0 CFM Number of Registers: 1 Actual Winter Vent.: 1 CFM Runout Air: 17 CFM Percent of Supply.: 4 % Runout Duct Size: 4 in. Actual Summer Vent.: 0 CFM Runout Air Velocity: 199 ft./min. Percent of Supply: 2 % Runout Air Velocity: 199 ft./min. Actual Winter Infil.: 4 CFM Actual Loss: 0.047 in.wg./100 ft. Actual Summer Infil.: 2 CFM Item: Area U Htg Sen �Clg Description. Quantif` Value, HTM ,Loss HTM Lat«, Sen, ; Gam' Gain` E -Part-I5'/15°-1.2C-Obw 8 X 10 80 0.091 1.4 109 1.4 0 109 UP-Ceil-16E-30 16 X 13 208 0.032 0.9 186 0.8 0 166 Floor-22A-ph 8 ft..Per. 8 1.358 38.0 304 0.0 0 0 Subtotals for Structure: 599 0 275 Infil.: Win.: 3.8, Sum.: 1.8 80 1.475 118 0.363 73 29 Ductwork: 223 64 AED Excursion: 14 Room Totals: 940 73 381 C:\ ...\Lynn & Andrew Stefanik Residence.rh9 Thursday, March 03, 2016, 4:00 PM Rhvac -:,Residential & Ligot Commercial HVAC Loads�j Elite Software Development,'Inc. ~ [56tailed Room,Loa'ds -"Room 9*-, Great Ro0M'(Av&rag'e Load Procedure), Room Length: 25.0 ft. System Number: Room Width: 18.0 ft. Zone Number: Area: 4600 oqƒL Supply Air: 296 CFM Ceiling Height: 10.0 ft. Supply Air Changes: , 4.0 AC/hr Volume: 4.600.0 cu]t. Req. Vent. C|Q: O CFK8 Number of Registers: 3 Actual Winter Vent.: 3 CFM Runout Air: 88 CFyN Percent ofGupphy.: 1 96 F{unouiDuct Size: 6 in. Actual Summer Vent.: G CFYN RunoutAir Velocity: 503 ft./min. Percent ofSupply: 2 Y6 FlunmutAir Velocity: 503 ft./min. Actual Winter |nfiL g CFK8 Actual Loss: 0.162 in.wg./l 00 ft. Actual Summer Infil.: 4 CFM W -Wall-1 3A400n18X10 128 0i143 4.0 480 2.2 O 263 W -3ls-1D-cb-o shgc-0.67O%S (2) 36 0.650 18.2 856 74.2 O 260 VV-G|o-1OB-nohgo-O.47O96S (2) 24 1.450 40.8 974 68.8 O 1.608 UP'Coi|-16E-3035X18 450 0.032 0.9 403 0.8 .O 360 Floor22A- h18ftPer. 1.368 3G�D 684 O�O O O Subtotals for Structure: 3.187 O 4.899 � |n@.:VVin.:8.8.Gum.:4.O 180 1.478 286 0.367 165 GG Ouubmodx: 1.077 1.085 � AEDExouroion: 235 20 230 C:\... \Lynn&Andrew 8tefanU«Raeidonne.rhS ' Thuroday, March O3.2O18.4:OOPM ential Commeccial HVAC Loads e Software Development, Inc.' Res dent leEnergy Calc's'ght 1'.P'6�'8aint'L"dci6, ynn & A drew Stefan k Re deence FL 34983 P Detailed R66m .Loads - Room' 10 - Kitchen (Average Load Procedure) General. Calculation Mode: Htg. & clg. Occurrences: 1 Room Length: ,. 18.0 ft. System Number: 1 Room Width: 9.0 ft. Zone Number: 1 Area: 162.0 sq.ft. Supply Air: 178 CFM Ceiling Height: '10.0 ft. Supply Air Changes: 6.6 AC/hr Volume: 1,620.0 cu.ft. Req. Vent. Clg: 0 CFM Number of Registers: 2 Actual Winter Vent.:, 2 CFM Runout Air: 89 CFM Percent of Supply.: 1 % Runout Duct Size: 6 in. ' Actual Summer Vent.: 3 CFM Runout Air Velocity: 454 ft./min. Percent of Supply: 2 % Runout Air Velocity: .454 ft./min. Actual Winter Infil.: 13 CFM Actual Loss: 0.133 in.wg./100 ft. Actual Summer Infil.: 6 CFM ;Item; y Area s U > Htgj X S,en —Cl r Lat: Sen' Description; . -, 2 Quantity :Value,; HTM Loss, HTM Gain:, Gain W -Wall-13A-4ocs 9 X 10 81 0.143 4.0 324 2.2 0 177 N -Wall-13A-4ocs 18 X 10 180 0.143 4.0 721 2.2 0 394 W -GIs-1 D-cb-o shgc-0.67 0%S 9 0.650 18.2 164 74.2 0 668 UP-Ceil-16E-30 18 X 9 162 0.032 0.9 145 0.8 0 130 Floor-22A-ph27ft_Per.-------------- - ------ 27--- -1.358 -----38-0 -- 1,027-- - 0_0-------------0. Subtotals for Structure: 2,381 0 1,369 Infil.: Win.: 13.0, Sum.: 6.0 270 1.478 399 0.363 248 98 Ductwork: 865 653 AED Excursion: 141 People: 200 lat/per, 230 sen/per: 2 400 460 Equipment _ -----------------------------------3,645-- _ -- --- 600 1,200 Room Totals:..----------------- 1,248 3,922 C:\ ...\Lynn & Andrew Stefanik Residence.rh9 Thursday, March 03, 2016, 4:00 PM Rhvac Residential"& Light Commercial HVAC Loads Elite Software Development, Inc. Residential Energy Calc's m _ Lynn &Andrew Stefartik Residence Port'Saint Lucie, FL '34983 Page 18 Detailed Room Loads. —Room 1 I:'- 8tudy(Avers e-Load Procedure) General77777777 Calculation Mode: Htg. & c1g. Occurrences: 1 Room Length: 12.0 ft. System Number: 1 Room Width: 11.0 ft. Zone Number: 1 Area: 132.0 sq.ft. Supply Air: 41 CFM Ceiling Height: 10.0 ft. Supply Air Changes: 1.8 AC/hr Volume: 1,320.0 cu.ft. Req. Vent. Clg: 0 CFM Number of Registers: 1 Actual Winter Vent.: 1 CFM Runout Air: 41 CFM Percent of Supply.: 3 % Runout Duct Size: 4 in. Actual Summer Vent.: 1 CFM Runout Air Velocity: 466 ft./min. Percent of Supply: 2 % Runout Air Velocity: 466 ft./min. Actual Winter Infil.: 5 CFM Actual Loss: 0.245 in.wg./100 ft. Actual Summer Infil.: 2 CFM Item,-:,r t, U R Htg x f Sen;� Clg Lat ;Sen Description ` ti,Quantify _ value„ ., HTM k.` Loss.. , ~ HTM'.° Gain . Gain`' N -Wall-13A-4ocs 11 X 10 95 0.143 4.0 380 2.2 0 208 N -GIs-1 D-cb-o shgc-0.67 100%S 15 0.650 18.2 273 23.9 0 358 UP-Ceil-16E-30 12 X 11 1.32 0.032 0.9 118 0.8 0 106 Floor-22A-ph 11 ft..Per. 11 1.358 38.0 418 0.0 0 0 Subtotals for Structure: 1,189 0 672 Infil.: Win.: 5.3, Sum.: 2.4 110 1.482 163 0.364 101 40 Ductwork: 421 149 AED Excursion: 32 Room Totals: 1,773 101 893 C:\ ...\Lynn & Andrew Stefanik Residence.rh9 Thursday, March 03, 2016, 4:00 PM 0 Rhvac Residential & Light Commercial HVAC Loads r ,' , Elite Software Development, Inc: Residential ,Energy Calc's Lynn & Andrew Stefaink Residence , Port S.amt Lucie,. FL 34983 Pa a 19 ` .Detailed Room Loads - Room .12 -, Powder Rooh7 (Average Load Procedure) General - - Calculation Mode: Htg. & clg. Occurrences: 1 Room Length: 7.0 ft. System Number: 1 Room Width: 7.0 ft. Zone Number: 1 Area: 49.0 sq.ft. Supply Air: 9 CFM Ceiling Height: 10.0 ft. Supply Air Changes: 1.1 AC/hr Volume: 490.0 cu.ft. Req. Vent. Clg: 0 CFM Number of Registers: 1 Actual Winter Vent.: 0 CFM Runout Air: 9 CFM Percent of Supply.: 5 % Runout Duct Size: 4 in. Actual Summer Vent.: 0 CFM Runout Air Velocity: 105 ft./min. Percent of Supply: 2 % Runout Air Velocity: 105 ft./min. Actual Winter Infil.: 3 CFM Actual Loss: 0.014 in.wg./100 ft. Actual Summer Infil.: 2 CFM Item,- Area U F }' Htg ` SenClg } La t Sen Description; Quantity s Value,;' ,iT~HTM. t L Loss HTM. . : Gain` ` Gain E -Part-150/150-12C-Obw 7 X 10 70 0.091 1.4 96 1.4 0 96 UP-Ceil-16E-30 7 X 7 49 0.032 0.9 44 0.8 0 39 Floor-22A-ph 7 ft..Per. 7 1.358 38.0 266 0.0 0 0 Subtotals for Structure: 406 0 135 Infil.: Win.: 3.4, Sum.: 1.5 70 1.471 103 0.371 64 26 Ductwork: 158 34 AED Excursion: 7 Room Totals: _ 667 64 202 C:\ ...\Lynn & Andrew Stefanik Residence.rh9 Thursday, March 03, 2016, 4:00 PM Rhvac Residential & Light Commercial HVAC Loads_ Elite Software Development, Inc.. Residential Energy Ca CS Lynn & Andrew Stefanik Residence Port Saint Lucie FL 34983 „. . ; "' ,'Pa a 20 Detailed Room Loads - Room 13 -Laundry (Average Load. Procedure) General Calculation Mode: Htg. & clg. Occurrences: 1 Room Length: 7.0 ft. System Number: 1 Room Width: 7.0 ft. Zone Number: 1 Area: 49.0 sq.ft. Supply Air: 51 CFM' Ceiling Height: 10.0 ft. Supply Air Changes: 6.3 AC/hr Volume: 490.0 cu.ft. Req. Vent. Clg: 0 CFM Number of Registers: 1 Actual Winter Vent.: 1 CFM Runout Air: 51 CFM Percent of Supply.: 2 % Runout Duct Size: 4 in. Actual Summer Vent.: 1 CFM Runout Air Velocity: 588 ft./min. Percent of Supply: 2 % Runout Air Velocity: 588 ft./min. Actual Winter Infil.: 7 CFM Actual Loss: 0.389 in.wg./100 ft. Actual Summer Infil.: 3 CFM Item 4 $Area UnHtg Sen �bp` n ,gClgLat` Sen Gain tion ' _; :Quantit =Value. ; HTM Loss'{ HTM'. Gain.: - . N -Wall-13A-4ocs 7 X 10 58 0.143 4.0 232 2.2 0 127 E -Part-1 Y/15°-12C-Obw 7 X 10 70 0.091 1.4 96 1.4 0 96 N -GIs-1 D-cb-o shgc-0.67 100%S 12 0.650 18.2 218 23.8 0 286 UP-Ceil-16E-30 7 X 7 49 0.032 0.9 44 0.8 0 39 Floor-22A-ph 14 ft..Per. _ _ _ 14 1.358 38.0 _ 532 _ 0.0 0 0 Subtotals for Structure: 1,122 0 548 Infil.: Win.: 6.7, Sum.: 3.1 140 1.479 207 0.364 128 51 Ductwork: 413 188 AED Excursion: 41 Equipment: 300 300 Room Totals: 1,742 428 1,127 C:\ ...\Lynn & Andrew Stefanik Residence.rh9 Thursday, March 03, 2016, 4:00 PM Rhvac Residential & Light Commercial HVAC Loads Elite Software Development, tnc. Residential Energy Calc's Lynin &Andrew Stefarnk Residence,; :PortSainfLucie,.FL 34983 ;:. , Pa e'21 Systerm:1.Ropm-16ad Summary . Htg Min Run Run Clg„,Clg Min Act Room Area Sens ` . Htg Duct: Duct Seris' Lat , Clg Sys No Name SF Btuh ` , �CFM Size Vel Btuh Btuh CFM " CFM ---Zone 1--- 1 Master Bedroom 280 7,985 104 3-6 512 6,630 1,385 302 302 2 Walk In Closet 60 1,288 17 1-4 198 380 92 17 17 3 Master Bath 140 1,552 20 1-4 671 1,287 1,092 59 59 4 Bedroom 2 168 1,936 25 1-5 513 1,538 510 70 70 5 Bath 2 140 1,552 20 1-4 370 710 92 32 32 6 Bedroom 3 210 6,570 85 3-6 490 6,346 795 289 289 7 Foyer 84 2,532 33 1-6 459 1,979 174 90 90 8 Dining 208 940 12 1-4 199 381 73 17 17 9 Great Room 450 4,540 59 3-6 503 6,515 365 296 296 10 Kitchen 162 3,645 47 2-6 454 3,922 1,248 178 178 11 Study 132 1,773 23 1-4 466 893 101 41 41 12 Powder Room 49 667 9 1-4 105 202 64 9 9 13 Laundry 49 1,742 23 1-4 588 1,127 428 51 51 Ventilation 769 412 1,038 Duct Latent 586 Return Duct _ _ 1,385 4,302 1,690 _stem 1 total 2,132 38,877 477 36,623 9,733 1,452 1,452 System 1 Main Trunk Size: 14x17 in. Velocity: 878 ft./min Loss per 100 ft.: 0.099 in.wg [Cool.ing System Summary Actual: 3.92 79% / 21 % 37,000 10,000 47,000 Equi, meht Data Heating System Cooling System Type: Two Speed Heat Pump Standard Air Conditioner Model: RXBH24A10J RPRL048JEC Indoor Model: RHPLHM4824JC Brand: Prestige Series Prestige Series Description: Heat Pump HSPF 9.5 16 Seer with Heat Pump Efficiency: Hi: 9.5 / Lo: 0 HSPF 16 SEER Sound: 0 0 Capacity: 47,000 Btuh 47,000 Btuh Sensible Capacity: n/a 37,000 Btuh Latent Capacity: n/a 10,000 Btuh C:\ ...\Lynn & Andrew Stefanik Residence.rh9 Thursday, March 03, 2016, 4:00 PM