SIDING Inspection/Certification - Permit# SLC-2112-0030
TO:
Jhonnatan Osario
Office manager
FROM:
J. Larry Lammers
President
DATE:
February 1, 2022
RE:
337 E Midway Rd
Fort Pierce, FL
To the best of my knowledge and belief, the building components and site
improvements outlined herein and inspected under my authority have been
completed in conformance with the approved product approvals and/or plans and
the applicable codes.
Requirements for the SIDING improvements made at the property were inspected by
me on 1/31/2022 and include, but are not limited to:
• R703.10.2 Siding Min. Attachment and Min. Thickness
o 11-gage 1-1/2” galv. Roofing nail through top edge at each stud in
accordance with manufacturer's instructions
o 7/16” nominal thickness
o Overlap of min. of 1-1/4”
• Manufacturer’s requirements for blind nailing fastener spacing for 7-1/4” lap
siding:
o Fastener spacing for 7-1/4” wide planks for a 0-15 ft. high building in
high wind speed zone: 16” O.C.
My inspection/review found all the requirements for the installation of the siding meet
or exceed the above requirements.
If you have any questions pertaining to this project, please contact me using the
information below.
Regards,
+772 979 0172
jllammers@purposebuiltengineering.com www.purposebuiltengineering.com
1903 San Diego Ave
Fort Pierce, FL
J. Larry Lammers, P.E.
President