HomeMy WebLinkAboutWINDSPEED & EXPOSURECONTRACTOR: WYNNE BUILDING CORP DESIGN CRITERIA: Applicable Codes, Regulations, and Standards 1. The 7th Edition (2020) Florida Building Code, specifically Chapter 16 Structural Design, Chapter 20 Aluminum, and Chapter 23 Wood. 2. AA ASM 35 and AA ADMl Specifications for Aluminum Structures, Part 1-A of the Aluminum Design Manual prepared by The Aluminum Association. and the AAF Guide to Aluminum Construction in High Wind Areas. 3. ASCE 7-16. Loading Criteria 1. Live Load: 10 PSF per 7th Edition (2020) Florida Building Code, Appendix I Section 105.1 2. Dead Load: 1 PSF 3. Wind Load: 3.1. Building Occupancy Category, Section 1604.5 and Table 1604.5: Risk Category 1. 3.2. Ultimate Design Wind Speed: V- = 150 MPH, Nominal Design Wind Speed: VASD = 116 MPH 3.3. Exposure Category, Section 1609.4.3: Exposure B 3.4. Screen Enclosure Section2002.4 4. Building Category for Aluminum Structures, Section 2002.6: Category Type 1 - Patio Cover / Screen Room: Non -Habitable, Unconditioned Roof Type 1. Roof Type: MONOSLOPE 2. Roof Material:3" x 12" 0.030" Town & Country Industries Riser Panel, Florida Product Approval Number FL 17638-R2 Foundation Design Existing concrete slab. No additional concrete footine or slab is required to resist the loads imposed upon the existing slab by the proposed construction if the existing slab is a minimum of 4" thick and in sound condition, flee from structural cracking, spalling, or other deterioration. Specifications The following specifications are applicable to this project: 1. All work shall be in accordance with the 7th Edition (2020) Florida Building Code, and any other applicable local codes and regulations. 2. Aluminum extrusions shall be 6005 T5 Alloy. Due to quality control issues, no manufacturer substitution is acceptable without the specific written, signed and sealed authorization of Florida Aluminum Engineering, Inc. 3. Screen material shall be 18/14 screen unless approved by Florida Aluminum Engineering, Inc. 4. Fasteners are required to be corrosion resistant, minimum SAE Grade 2 or better zinc plated to ASTM B633, or coated stainless steel series "300", or uncoated stainless steel series "400". 5. Approved concrete screw anchors to be Simpson Titen-HID or equivalent. 6. All Self Mating Beam Sections are to be stitched with either #14 screws 6" from ends and 24" center to center or # 12 screws 6" from ends and 12" center to center. 7. Where concrete specifications are required, whether in the screen enclosure scope or not, by one or more regulatory agency, the following specifications are applicable: a. Concrete shall conform to ASTM C94 for the following components: i. Portland Cement Type 1,- ASTM C 150 ii. Aggregates - Large Aggregate 3/4" max - ASTM C 33 iii. Air entraining +/- I% - ASTM C 260 iv.Water reducing agent - ASTM C 494 v. Clean Potable water vi. Other admixtures not permitted b. Metal accessories shall conform to: i. Reinforcing Bars - ASTM A615, grade 60 ii. Welded wire fabric - ASTM At85 c. Concrete slump at discharge chute not less than 3" or more than 5". Water added after batching is not permuted. d. Prepare and place concrete per American Concrete Institute Manual of Standard Practice, Parts 1, 2, and 3 including hot weather recommendations. e. Moist cure or polyethylene curing permitted. f. Prior to placing concrete, treat the entire subsurface area for termites in compliance with the FBC. g. Concrete shall be placed over a polyethylene vapor barrier. h. All aluminum components embedded within concrete shall be coated with a bituminous paint or epoxy. 8. All flashing and weatherproofing shall be provided by the contractor. 9. Door location shall be determined by contractor in the field. 10. Use of these plans acknowledges and accepts a limit of liability not to exceed design and engineering fee. WIND SPEED AND EXPOSURE HAVE BEEN DETERMINED USING THE ADVANCED TECHNOLOGY COUNCIL'S WEBSITE AND GOOGLE EARTH. 1X3 10'-0' 3X3XO.090 /POST 2X3GIRT 7'-4- 7'-4' 7'-4- 6'-0' 6'-0' -�I'- 6-0' 4'- 6'-0' 9 -0' 2f-O' 24'-0' 9'-0' �.Zco o o� 0_ W (0 :o * W re Q o 6. ) 0 c~n Q� ;: �• Z 3X3X0.090- POST n a I I O O 3X3XO.090 POST 8'-6' +1'' t o.-0' 3X3X0.090 POSTN 2X3GIRT of T 8.-6. 1X3 IY W W W ti _z m � � o Z W t0 W Z J Z Q Z O d n N t/1 C¢ V W C J LL o O = CL d U Z Z � U N��q"y Z � ''nn s} c} Q W Waw� Q W =2 m I� Z 0 Z $ LL W tr_ W OZ O Z Z Z Q Q C2 U LU m H W W W p a Lo 0 Z m d C)O LL TP DATE DRAWN 11 /16/21 REVISION SHEET NO: A-1 ALUMINUM MEMBERS DEgENSIONS HOLLOW SECTIONS ®0®®®®011111N *Illllp flf/',, 2 x 2: 2" x 2" x 0.046"®� •' •••• �� m�,i 2x3: 2"x3"x0.050" 4"x4"x0.125" ••• 2x4: 2x4"x0.050" POST �'�•co LL 6,• 2 x 5: 2" x 5" x 0.050" I I e co O 0 INTERNAUEXTERNAL �• O OPEN BACK SECTIONS E B SECTIONS I (2) 3/8" DIA CONCRETE I I 4" x 4" x 1/8" EXTRUDED POST BASE W/ (2) 3/8" 2 cc Lij co s. ® (� d LIJ v 0 0 1 x x 2" x 0.040" SCREW ANCHORS _ DIA. THRU BOLTS N Q V : 0. 0 1 x 3: 1" x 3" x 0.045" _ (3" CONC. EMBED) _ _ o •, O •••• SNAP SECTIONS o00 • '• �/ 2 x 2 Snap: 2" x 2" x 0.045" u ®m®®�' m/� •' .. .. • 2 x 3 Snap: 2" x 3" x 0.050" I I ,ffflflll Q��`i``�� 2 x 4 Snap: 2" x 4" x 0.045" I I 3"x 3" x 0.090" 111111111,,, SELF MATING (SNIB) (2) 3/8" DIA. CONCRETE I i POST 2 x 4 SMB: 2" x 4" x 0.044"x 0.100" SCREW ANCHORS fz 2 x 5 SMB: 2" x 5" x 0.050" x 0.100" (3" CONC. EMBED) ( W W 2 x 6 SMB: 2" x 6" x 0.050" x 0.120" I W 0- Z 2 x 7 SMB: 2" x 7" x 0.05T' x 0.120" 2 x 8 SMB: 2" x 8" x 0.072" x 0.124" 1" x 3" OB W/ 1 /4" CONCRETE I I I NTERNAUEXTERNAL I 3" x 3" x 0.090" Z 2 x 9 SMB: 2" x 9" x 0.072" x 0.124" SCREW ANCHOR 6" 3" x 3" x 1/8" EXTRUDED POST W z e} 2 x 10 Slvffi: 2" x 10" x 0.092" x 0.398" FROM UPRIGHT & @ POST BASE W/ (2) 3/8" I I J 24" O.C. (MIN. 3" EMBED.) DIA. THRU BOLTS INTERNAUEXTERNAL Q Q p MINIMUM FASTENER EDGE DISTANCE:1/2" I 3" x 3" x 1/8" EXTRUDED POST BASE 3/8" Z , Z d MINIMUM FASTENER SPACING: 3/4" -- --- — -- - - -- (2) 3/8" DIA CONCRETE I SCREW ANCHORS DIA. THRU BOLTS L S 0 H — N Z CONCRETE SCREW ANCHOR (3" CONC. EMBED) N U SIMPSON TITEN HD OR EQUIVALENT n I LWL 0 J SHEET METAL SCREWS (SW: ;. 0 _ IT W / BUILDEX OR EQUIVALENTCLI— a ° .. Z z B 3" x 3" POST TO CONCRETE CONNECTION DETAIL Z — A-2 SCALE:NTS B-� POST TO CONCRETE CONNECTION DETAIL 4 '. in � � � qq Z w N u � Y A_� SCALE: NTS J J m m Q2� Qwz Z F Z 118" x 2" x 2" EXTRUDED I D Z$ m ANGLE 5052 H-32 ALLOY I J W p W/ (4) #14 x 3/4" SMS U- 0 INTO DJ o a I LL ss i d[ANCHOR CONC SLAB / FOOTING e BEDMENT PLAN° o.SEE CHAIR RAIL MEMBER I I t!! - 0 Z O L�J SIDE VIEW — -- — — — — — — Q Ow ZQ --- — — a�wuu (1) 3/8" DIA. CONCRETE j// 1"x 1"x 1/8" ANGLE W/ 0] I.- W SCREW ANCHORS (21/4" CONC. EMBED) I UPRIGHT I j PRE -HUNG (2) #14 x 5/8" EACH FLANGE EACH SIDE OF UPRIGHT 04 Z p d � DOOR JAMB Z c 3" x 3" x 0.090" POST _ I I N O u_ DRAWN BY I I 4" .. ° e TP a 1"x 3" BASE PLATE °'. DATE DRAWN ANCHORED TO CONC W/ 1/4" e• ;e a °. 11/16/21 CONCRETE SCREW ANCHOR a ; .. (MIN. 1 1/4" EMBED) ° ° n a • • REVISION 6" MAX EACH SIDE OF POST °q• AND 24" O.C. MAX 6" i C CHAIR RAIL TO POST CONNECTION DETAIL 2 _ FRONT VIEW A_2 SCALE: NTS - 4 _ DJ-1 UPRIGHT TO CONCRETE (a) PRE -HUNG SHEET NO: A-2 DOOR LOCATION DETAIL SCALE: NTS A 2 #14 SMS x 1" W/ \ #14 x 3/4" SMS W/ NEOPRENE FACED NEOPRENE FACED WASHER 12" O.C. \'% .� '� • • •• �l1 IIJ • / @ \\ ,. ,• 3" RISER WASHER @ 4" O.C. ALONG LENGTH PANEL •.• �• /� III' •'4_.• OF ALL END BEAMS ,,��/ ` •, �•co LL ' It Q coO c'), i W Lu �- FLASHING • GGG ', O • 0 2 x 6 BY v ••• Z 2" x 3" x 0.045" TOP RAIL - • CROSS BEAM #14 x 3/4" SMS W/ OTHERS I II O II//;,� ••••• '• �� `` •• \ �•�•••,C�10 NO ANGLE RE, JIRED i o NEOPRENEFACED 3" RISER // \\\\ Q UNLESS SPLICED OR _ CORNER - ATTACH w/ (4) I I ° WASHER @ 4" O.C. PANEL \\ #10 x 4" LG III 1 1/2" x 2 1/8" x 1 1/2" x 1/8" x 6" LONG ALUM RECEIVING 3" x 3" PB I UPRIGHT--""" f' I CHANNEL W/ (5) #14 x 3/4" PRIGHT ;' 1 W W INTO THE UPRIGHT AND � W � (5) #14 x 3/4" SMS INTO EACH SIDE OF BEAM #14 3/4" SMS W/ ,� Z nl 3" RISER x (' PANEL NEOPRENE FACED WASHER 4" O.C. EXISTING' I BUILDING,, Z W LD 2" x 3" x 0.045" TOP �(3) @ I / z RT RAIL w/ (4) #10 x 4" SMS INTO POST 3/8" DIA. THRU BOLTS 3 3/8" DIA. O THRU BOLTS / / / / .J Q Q Z Z 2" 2" 3" LG 2" 2" 3" LG ' ' c) N LU x x x x 1/8' ANGLE 1/8' ANGLE 2"x5"SMB ; I Ln x x N Q w 2" x 5" SMB 3" x 3" x 0.090" W c V CO POST LL 3" x 3" x 0.090" 0 (4) #10 x 3!4" (4) #10 x 3/4" POST SMSINTO SMS INTO - - - ' CL SCREW BOSSES SCREW BOSSES (2) INTO TOP RAIL (2) INTO TOP RAIL (2) INTO POST (2) INTO POST N m CONNECTION AT CORNER CONNECTION AT SPLICE S—� S-2 RISER PANEL TO POST cD 4TH WALL DETAIL z Z W RISER PAN ROOF TO POST CONNECTION SCALE: NTS t S A-3 SCALE: NTS A-3 10 (D N z J X 3 TOP RAIL CONNECTION TO 3 X 3 UPRIGHT y� A-? SCALE: NTS J J Z J 5 Q W �6g� Q Z<a� 1..1- Q9 ..� OZ° m .J ED o LL o #14 x 3/4" SMS W/ #14 x 3/4" SMS W/ FLASHING NEOPRENE FACED #14 SMS x 3/4" W/ BY NEOPRENE FACED #14 SMS x 3/4" W/ WASHER @ 4" O.C. 3" RISER NEOPRENE FACED WASHER @ 4" O.C. OTHERS NEOPRENE FACED %PANEL WASHER @ 12" O.C. #14 x 3/4" SMS W/ WASHER @ 12" O.C. ALONG LENGTH 3" RISER NEOPRENE FACED 3" RISER ALONG LENGTH / OF ALL END BEAMS PANEL WASHER @ 4" O.C. PANEL OF ALL END BEAMS 2" x 3" TOP RAIL wl (4) #10 x 4" SMS INTO POST t/1 (L Oz / ® 2"x2"x3"LG W 0 Z 1 /8" ANGLE Q -- Z 2" x 3" x 0.045" ° I EXISTING' I END BEAM ® 2" x 3" x 0.045" o #10 x 3/4" < _j W Q J Of ° BUILDING/ i ° END BEAM o T(2) �(4) SMS INTO _ _-- 3/8" DIA. THRU BOLTS _._. ._- — - SCREW BOSSES Z) W x m W 11/2"x21/8"x11/2"x0.062" / INTO TOP RAIL (2) INTO POST N " z LU 0_ ,; ALUM RECEIVING CHANNEL i'1 W/ (3) #12 x 3/4" SMS EACH 2(x 50SM8 1 1/8" x 2 1/8" x 1 112" x 0.062" x 3" LONG ALUM RECEIVING CHANNEL W/ (3) 2" x 5" SMB J LU 0 Z 2 � cr�j 1 o O SIDE OF BEAM & (2) 3/8" DIA. #14 x 3/4" SMS EACH SIDE OF d. ('4 LL LL THRU BOLTS INTO THE POST /' j" BEAM & (2) 3/8" DIA. THRU BOLTS 1 118" x 2" x 1 1/8" x 5" x 0.125" DRAWN BY 3/8" DIA. THRU BOLT I 3" x 3" x 0.090" INTO POST ALUM RECEIVING CHANNEL W/ (4) #14 x 3/4" SMS INTO TP 2" x 5" SMB POST EACH SIDE OF BEAM & #14 x 1" SMS INTO CORNER POST DATE DRAWN L 11 /16/21 3" x 3" x 0.090" REVISION POST 1 _ S-3 ISER PANEL TO CORNER POST 4TH WALL DETAIL S-4 RISER PANEL TO CORNER POST CONNECTION S-5 RISER PANEL ROOF TO POST CONNECTION 0 A-3 SCALE: NTS •7 SCALE: NTS 4 /� -3 SCALE: NTS SHEETNO: /'1 A-3- L 2" x SMB EDGE BEAM 3" RISER PANEL m m m 2" x 3" x 0.045" KNEE BRACE 1 1/2" x 2 1 /8" x 1 1/2" x 0.062" x 3" LONG ALUM RECEIVING CHANNEL W/ (3) #12 x 3/4" SMS EA. FACE & (3) #12 x 3/4" INTO POST #14 x 3/4" SMS W/ NEOPRENE FACED WASHER @ 4" O.C. V� \_3" x 3" x 0.090" POST S-6 KNEE BRACE CONNECTION DETAIL A_A SCALE: NTS #14 x 3/4" SMS W/ NEOPRENE FACED WASHER @ 12" O.C. ALONG LENGTH OF ALL END / CROSS BEAMS 2" x 3" x 0.045" END BEAM 3" RISER PANEL m m m #14 x 3/4" SMS W/ NEOPRENEFACED WASHER @ 4" O.C. 12" MAX OVERHANG 2" x 3" x 0.045" I 3" x 3" x 0.090" KNEE BRACE POST m,i I 1 1/2" x 2 1 /8" x 1 1/2" x 0.062" x 3" LONG ALUM RECEIVING CHANNEL W/ (3) #12 x 3/4" SMS EA. FACE & (3) #12 x 3/4" INTO POST I S-7 KNEE BRACE CONNECTION DETAIL A -A SCALE: NTS NP LL Zco O O W O :U * LU Q O' , Qom• �• z C #14 SMS x 3/4" W! #14 x 3/4" SMS W/ LASHING #14 SMS x 3/4" W/ NEOPRENE FACED NEOPRENE FACED NEOPRENE FACED #14 x 3/4" SMS W/ 1 1/2" x 2 1/8" x 1 1/2" x 0.125" 1 1/2" x 2 118" x 1 1/2" x 0.125" WASHER @ 12" O.C. WASHER @ 4" O.C. WASHER @ 12" O.C. NEOPRENE FACED BEAM DEPTH CHANNEL W/ BEAM DEPTH CHANNEL W/ ALONG LENGTH ALONG LENGTH WASHER @ 4" O.C. (4) #14 x 3/4" SMS INTO (4) #14 x 3/4" SMS INTO OF ALL END BEAMS 3" RISER OF ALL END BEAMS BEAM EACH SIDE & BEAM EACH SIDE & PANEL (4) #14 x 3/4" SMS INTO (4) #14 x 3/4" SMS INTO 3" RISER PANEL CARRIER BEAM CARRIER BEAM I 2" x 5" SMB ® ® 5SM EXISTING / I BUILDING 2" x 3" TOP RAIL - NO 2" x 5" SMB 2" x 6" SMB m�', i" ANGLE REQUIRED UNLESS m INTERIOR BEAM m e CROSS BEAM j SPLICED OR CORNER - ATTACH w/ (4) #10 x 4" LG 11/2"x21/8"x11/2"x0.125"x BEAM DEPTH CHANNEL W/ 2" x 6" SMB 1 1/2" x 21 /8" xl 1/2" x 6" x 0.125" 3" x 3" x 0.090" I (4) #14 x 3/4" SMS INTO CROSS BEAM ALUM RECEIVING CHANNEL ' i / / UPRIGHT BEAM EACH SIDE & ( i %I 2" x 5" SMB (4) # x /4" SMS INTO W/ (5) #12 x 3/4" SMS EACH /' ; 4 UPRSIDE OF BEAM & (3) 3/8" DIA. ' j THRU BOLTS INTO THE POST ,% / - - - � 3" x 3" POST S-$ INT BEAM TO CROSS BEAM ATTACHMENT A_ A SCALE: NTS S'9 ISER PANEL TO POST 4TH WALL DETAIL A_A SCALE NTS S-1 0 2 X 3 TOP RAIL CONNECTION TO SIDE WALL 3 X 3 UPRIGHT A-4 SCALE: NTS Lu Lu W W p,' Z L M z W t�D W z J OC Q Q Z Z CL W O N z C/1 Q U C/I C O0O J , _ CL ~ G U Z Z O O NNq Z rw'm^n J R ri�� aW- W a oz¢� Oz° h J W LL S H � O 0 U Q Z Q V m W w Lu nZoCL� }y}��m a. >NOJ Li - DRAWN N BY TP DATE DRAWN 11 /16/21 REVISION 1 - 0 - A A-4 f4g111LL 1111111 j///ti „, Q `r 0 O ' .. Z o :W W #14 SMS x 3/4” W/ NEOPRENE FACED � '� r► Q �GV:' WASHER @ 12" O.C. #14 SMS x 3/4" W/ ALONG LENGTH #14 x 3/4" SMS W/ NEOPRENE FACED ♦ Z ♦i •••, I♦ ' OF ALL END BEAMS 3" x 12" RISER NEOPRENE FACED WASHER @ 12" O.C. PAN PANEL ...• '' .' ,i ... • • • �� WASHER @ 4" O.C. ALONG LENGTH OF ALL END BEAMS 2" x 5" x SMB" NIU111111 P�O,```, * END BEAM I 1 1/8" x 2" x 1 1/8" x 5" x 0.125" _ ._.._ 3" x 3" x 0.090" ALUM RECEIVING CHANNEL W W _ 0 I� ® - --- POST NOTCHED W/ 4 #14 x 3/4" SMS INTO O W d Z 2"x5"SMB END BEAM a ��0 FOR CARRIER BEAM EACH SIDE OF BEAM & 3 � O 3/8" DIA. THRU BOLTS _ � m 1 2"x3"x0.045" END BEAM 2"x 5" SMB INTO POST (7 0 Z W w --- _. -- - CARRIER BEAM W Z 1 1/2 21/8' 1 1/2" 0 062" 3" - O Z Q Z o x x x x LONG L. ALUM RECEIVING CHANNEL W/ (3) I I O d N #14 x 3/4" SMS EACH SIDE OF __. _ �_ _ _ — N Z 1 1/2" x 2 1/8" x 1 1/2" x 0.125" x 5" LONG BEAM & (2) 3/8 DIA. THRU BOLTS _ . _ . -._. w N ALUM RECEIVING CHANNEL W/ (4) INTO POST 3/8" DIA. CQC W G #14 x 3/4" SMS EACH SIDE OF BEAM & (3) 3/8" DIA. THRU BOLTS2" x 5" SMB THRU D A BOLTS LL 0INT_ POST ~ 3" x 3" x 0.090" d j POST G ~ �U� S-f RISER PANEL TO POST INTERIOR CONNECTION S-12 MUTLIPLE MEMBER TO POST CONNECTION ZZ w N Z A_5 SCALE: NTS /�_C SCALE: NTS /"1 J VI`� z „� q J w� <^ n n it J �LLmm G Q W <MM w Q W Z�mm owl o LL 0 LL 1 1/2" x 21/8" x 1 1/2" x 0.125" 1 1/2" x 2 1/8" x 1 1/2"x 0.125" BEAM DEPTH CHANNEL W/ BEAM DEPTH CHANNEL W/ (4) #14 x SMS INTO (5) #14 x 3/4" SMS INTO EACH BEAM EACH SIDE & _ BEAM EACH SIDE 8, (4) #14 x 3/4" SMS INTO (4) #14 x 3/4"SMS INTO ~ , 4TH WALL EDGE BEAM 4TH WALL EDGE BEAM � O Z O Q m zz 2" x 6" SMB 2" x 5" SMB m Q Q o Q _ W ° m � U WO W � m I,- W ® CV o Z O 0_ Lo �2" W rn O � x 5" SMB 2" x 5" SMB 4TH WALL CL N LL DRAWN BY 4TH WALL EDGE BEAM EDGE BEAM TP DATE DRAWN 11 /16/21 REVISION 2 - S', S-13 CROSS BEAM TO 4TH WALL BEAM ATTACHMENT NT BEAM TO END BEAM ATTACHMENT A_55 SCALE: NTS q SCALE: NTS A-5 - SHEET NO: 1 11 A-5