Loading...
HomeMy WebLinkAboutResponse letter To CommentsReinaldo A. Gomez Architect AR #0013736 16047 SW 68 ST Miami, Florida 33193 Phone: 786-261-9551 5/28/20 Response to comments: Permit Number: 2002-0505 Building 05a. PROVIDE THE CORRECT OCCUPANCY CLASSIFICATION FOR THE SERVICE AREA. DEPENDING ON THE TYPE OF WORK BEING PERFORMED WILL BE AN'F' OR'S'. Asa. See sheet A,1 for corrections Q5b. SEE SECTION 508 FOR REQUIREMENTS ON MIXED USE OCCUPANCIES. SHOW COMPLIANCE ON THE PLANS. Aft. See sheet A-1 for corrections. We are considering these spaces as nonseparated occupancies and applyng the regulation as per section 608.3 of the FBC 2017 6°h edition. Q7. CONFIRM THE CORRECT NUMBER OF EXITS ARE PROVIDED FOR THE OCCUPANTS IN THE IN THE SERVICE AREA PLUS THE MEZZANINE. (1006) A7. As per table 1006.2.1 one exit is acceptable for "F" occupancy since occupant load is less than 49 and common path of travel of 100' max. Q8. PLEASE SHOW HOW THE RESTROOMS COMPLY WITH THE ADA SECTION (202.1) A8. This section of code doesn't apply to this project. There will be no addition nor alteration to the existing space. Page 2 of 2 Ito Perm l Sa2=_n I 2003-0387 151782 ZONING COMPLI / BUSINESS Pending 7159 S U S 1, PORT ST LUCIE, 34952 a.- - --------------------------------- — ------------- ---- --------------------------- -------_•---------------------- -•--------------- �P�L7AtSS= i 2002-0505 151782 COMMERCIAL RENOVATION Pending 7159 S U S 1, PORT Si LUCIE, 34952 Go 0 Permit Screen ---------------------- 2002-0391 ------------------ 151782 -----------.._..- - COMMERCIAL RENOVATION — — - =--------------------------------------------._..................----------I Vold 7159 S U S 1, PORT ST LUCIE, 34952 Go to Permit en Scre 1912-0140 151782 WINDOW/DOOR INSTALLATION COMMERCIAL --------- Issued ..._..............-------------------------- 7159 S U S 1, PORT ST LUCIE, 34952 Go to Permit Screen ----r--..-- 1603-0168 — 151782 — ELECTRIC - COMMERCIAL Pending 7159 S U S 1 ,PORT ST LUCIE 34952 Go to Permit reen _ --- 1603.0167 - - --- -- - I----- --- 151782 --- — ELECTRIC - COMMERCIAL Vold 7159 S U S i , PORT ST LUCIE, 34952 Go M Permit Screen 1311-0007 -------_ 151782 -- - .__ _ ._.. --- -- - - .... ZONING COMPLI / BUSINESS ------ Finaled - _- — -- - - - 7159 S U S I, PORT Sr LUCIE, 34952 Go to Permit Screen 1309-0325 151782 — COMMERCIAL RENOVATION Finaled 7159 S U S 1, PORT ST LUCIE, 34952 Go to Permit Screen -- - - - - - - - - - 1101-0092 - - - - ----------= 151782 ------------ - - ZONING COMPLI / BUSINESS --------------------- ...---------------------------.._..------------- Finaled - 7159 S U S 1, PORT ST LUCIE, 34952 Go to Permit Screen 0810-0318 151782 SEE ZSE - ZONING COMPL/SPEC EVENTS ---------------------- Finaled ------------------- 7159 S U S 1 , PORT ST LUCIE, 34952 Go to Permit. Screen ----------------------;-------------------- j 0807-0386 151782 ------------------ .....--.------------------------------------------_- SEE ZSE - ZONING COMPL/SPEC EVENTS Vold 7159 S U S 1 , PORT ST LUCIE, 34952 — CzoSo Perm t Screzn —Go. i 0411-0089 151782 — ............. SEE ZSE - ZONING COMPL/SPEC EVENTS ....__...........__;..---..-_..._..-------'----------------------.._...... Finaled i 7159 S U S I, PORT ST LUCIE, 34952 to Permit Screen 24102332 151782 SEE ZSE -ZONING COMPL/SPEC EVENTS Finaled 7159 S U S 1, PORT ST LUCIE, 34952 ..... ...... . ------ - - Go to Permit Screen ...----'------------------ -............................... .............__.....- 15985101 ; ------'-------------------------------- --._.._........... ...... ....._..._... 151782 - -- - - - - ---------------------.-............... ZONING COMPLI / BUSINESS -----._...-------....--------- ......----------------------- ...................,._..._..........._..._...-..---'--... Finaled ---- 7159 S U S 1, PORT ST LUCIE, 34952 zo [o Permit Screen 15985103 151782 -- ZONING COMPLI / BUSINESS Void ....... --------------------._,... 7159 S U S_I , PORT ST LUCIE, 34952 - ,G{1So.cr n Permit S 21120728 ! ..................---� 151782 --------...........................,.........__......-----....---..._.........-----......------------..__.._...................--.....---:...--------------------------------•-•----_. _- SEE ZSE -ZONING COMPL/SPEC EVENTS Finaledi 7159 S U S 1, PORT ST LUCIE, 34952 Go to Permit Screen 21120028 151782 MECH/HVAC - DO NOT USE Flnaled i 7159 S U S 1 , PORT ST LUCIE, 34952 Go to Permit Screen 21110785 151782 GAS/GAS PIPING - 1 & 2 FAMILY RESIDENTIAL — Finaled 7159 S U S 1, PORT ST LUCIE, 34952 - . Goto Permit Screen --'.......----------------i------------- i 21090536 -------`--------------------'-------___.._.._. 351782 SIGN -.DONT USE Finaled i 7159 S U S 1, PORT ST LUCIE, 34952 Go to Permit Screen 21060479 151782 - .......___......----------.._................_..........-.-`.---"-`-----'---'--.......------------------------- DEMOLITION Finaled 7159 S U S 1, PORT ST LUCIE, 34952 Go to Permit Screen ......................'-------------- 21050678 i ._---. _........_,.._......._...-: 151782 --.._._.__............................_---------..._-..-'---------....--'------------------_.__..-._...._.......-......_•--------------.....................-•-•------•-----......-..... ? COMMERCIAL RENOVATION Flnaled 7359 S U S 1 , PORT Si LUCIE, 34952 Go to Permit Screen 15985102 ; 151782 ZONING COMPLI / BUSINESS Finaled 7159 S U S 1 , PORT ST LUCIE, 34952 -------------------- - -- - .. ---- - -- - - - - - - - - - - - - .-.--- _--`-`-_ --` - -`= - -.._._ _-----M._._.-.--- http://code/(S(huOizragodvimhf5ch0fi5wc))NiewPropertyData.aspx 5/29/2020 Page I of 2 BUILDING & CODE SYSTEM You are logged in sTwaEcomplli ... .. as: vemlon 31.: ditlPermit I Search Permit Review I Inspection I Permit Fee/pay I Mlsc Fee Contractor I Reports I Malnt I Fiscal I Flood Log I front Count ERD I Green Cert Energy Caic I Er __ Type in ParcelId Property Owner OR Property Address AND Press ENTER. Submit Query ParcelId: 3422-211-0010-000/6 Print ' rrrr�,�'U-Pry �' 1 f }1�"iyM' Property Appraiser Homr, OeDWeb ---` - ��''VN4i�»nh tI�-OFS'Xwn' V �� Last, first (Doe, John) _> €Enter Property Owner: (Press ELATE--� To Enter NEW Parcel sE� pier Parcel Address: (Press ENTER OR View Parcel [Enter Parcel Id: (Press ENTER) i Add New ParcelYl To Add Permit, Select Permit �" Select Permit Type"�� Type Sea Property Alerts[ PROPERTY INFORIVIATIO_N IhParcel Map Pro er ^Appraiser Card View alerts -Show Property Appraiser Data I I Flood Map Viewer _ _ -- - I Show GM Project Conditions of Approval Project Name ( Dept Condition Category Condition Desc No data to display Date Condition Expires rPROPERTYINFORMATION --- ---------- .. J ;Edit X Parcel #•. Map# 534122— I Subdivision: Plat Book Ia __y .- : Plat Page: ICI Jurisdiction: SP1 iNTt0CIE1C0�INTI OR Book «S$ OR Page: Section: r— Township: r!GS Range r Lot #. � b Block: r DOR: RE .mom Lot Size: Flood Zone: ��— _•] Minimum Flood Elevation: �—_ _i_ Flood Map: [_-_-_--___—_� „Historic: Parent ParcelId: [�__ Ty_pe;[ jl _ Utility Type: UTILITIES—�� Utility Number: __� _Parcel L_ _� Sewer Type: UTILITIES Sewer Number: ;Zoning: CG +COMMERCIAL GENERAL j Location: Imi AINLANDY W --�� Future 'SitePla nName:nd 'Last ----_--_uY Changed By:IclaNik°d Date Last Changed: 3102c� Created By: iial�yF Date Created: ?.f iIU13 { ',I122 36 40 BEG AT SE COR OF NE 1/9OF NW 1/4 RUN S 27 DEG 38 MIN E 210 FT TO N LI OF RIO MAR DR, TH S 62 DEG 22 MIN W 30 FT, TH N 27 DEG 38 MIN W 225.83-FT, TH N 89 DEG 49 MIN W 555.72 FT M/L, TH N 00 DEG 07 MIN E 800 FT, TH S 89 DEG 49 MIN E 400 FT, TH S 00 DEG 'PROPERTY ADDRESS INFORMATION I _.__..._._ _.._...----------- - - - - - - - - - - - - - -----. - I --------- ---- --- `.' Addressl Address2 City State Zip Last Changed By Date Last Changed Created By Date Created r Edit 1 7159 S U S 1 PORT ST LUCIE FL 349S2 -'- nellb 2/23/2013 ' I PA Property Appraiser Street Address: 7115 S US HIGHWAY 1 +'+ PROPERTY OWNER INFORMATION Add Owner € - ----'i---'----- -----•_._.----...------------- --------------------•---- ----------- - ---•-•..................._" -----------------_._..-------------•-- i First Name Last Name I Company Street Address J City State ;Zip Phone -------�-----.... ---------t -----•------------ (Cell Fax I EflailLast Changed -Edit Delete - - - - - PORT ST WCIE PLAZA I LLC POP T S7 L- I - - 112 PHYLISnCr I ELMONT { NY- -11003 (772) 286-6292- - f - nellb -- 02/23/2013 111 1 .. I .--.-.-... ------------ - - ------------------------------------- - - - ---------------- j IPROPERTY COMMENTS - - ------ ---- II Add Comment — ---- --- --- - — - ------ - Parcel Comment Reported By Date Reported No data to display - .-._ --- 1DDIwONAL INFORMATION.- ----_ dl BUILDING PERMITS INFORMATION — _ 1� Building Permit # Parcel Current Id Type Status Job Description http://code/(S(huOizragodyjmhf5ch0fi5wc))NiewPropertyData.aspx 5/29/2020 311.2 Moderate -hazard storage, Group S-1. Storage Group S-1 occupancies are buildings occupied for storage uses that are not classified as Group S-2, including, but not limited to, storage of the following: Aerosols, Levels 2 and 3 Aircraft hangar (storage and repair) Bags: cloth, burlap and paper Bamboos and rattan Baskets Belting: canvas and leather Books and paper in rolls or packs Boots and shoes Buttons, including cloth covered, pearl or bone Cardboard and cardboard boxes Clothing, woolen wearing apparel Cordage Dry boat storage (indoor) Furniture Furs Glues, mucilage, pastes and size Grains Horns and combs, other than celluloid Leather Linoleum Lumber otor vehic a reps garages con' lying wi the aximtfm allowable q antic es of Nazar, (lou eraal's listed 'n,' a le, Q7.;11s)�(�eePSectio�"4:(iCzT�.BJ) Photo engravings Resilient flooring Silks Soaps Sugar Tires, bulk storage of Tobacco, cigars, cigarettes and snuff Upholstery and mattresses Wax candles 311.3 Low -hazard storage, Group S-2. Storage Group S-2 occupancies include, among others, buildings used for the storage of noncombustible materials such as products on wood pallets or in paper cartons with or without single thick- ness divisions; or in paper wrappings. Such products are per- mitted to have a negligible amount of plastic trim, such as knobs, handles or film wrapping. Group S-2 storage uses shall include, but not be limited to, storage of the following: Asbestos Beverages up to and including 16-percent alcohol in metal, glass or ceramic containers Cement in bags Chalk and crayons Dairy products in nonwaxed coated paper containers USE AND OCCUPANCY CLASSIFICATION Dry cell batteries Electrical coils Electrical motors Empty cans Food products Foods in noncombustible containers Fresh fruits and vegetables in nonplastic trays or containers Frozen foods Glass Glass bottles, empty or filled with noncombustible liquids Gypsum board Inert pigments Ivory Meats Metal cabinets Metal desks with plastic tops and trim Metal parts Metals Mirrors Oil -filled and other types of distribution transformers Parking garages, open or enclosed Porcelain and pottery Stoves Talc and soapstones Washers and dryers SECTION 312 UTILITY ,AND MISCELLANEOUS GROUP U 312.1 General. Buildings and structures of an accessory character and miscellaneous structures not classified in any specific occupancy shall be constructed, equipped and main- tained to conform to the requirements of this code commen- surate with the fire and life hazard incidental to their occupancy. Group U shall include, but not be limited to, the following: Agricultural buildings Aircraft hangars, accessory to a one- or two-family residence (see Section 412.5) Barns Carports Fences more than 6 feet (1829 mm) in height Grain silos, accessory to a residential occupancy Greenhouses Livestock shelters Private garages Retaining walls Sheds Stables Tanks Towers FLORIDA BUILDING CODE — BUILDING, 6th EDITION (2017) 63 ! a qCopyright © 2017ICC. ALL RIGHTS RESERVED. Accessed by John Peterson on Sep at, 2017 5:12:51 AM pursuant to License Agreement with ICC. No further reproduction or 7� ® distribution authorized. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER. SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY defined in Section 406.5.2. These openings shall be per- mitted to be provided in courts with a minimum dimen- sion of 20 feet (6096 mm) for the full width of the openings. 406.5.6 Fire separation distance. Exterior walls and openings in exterior walls shall comply with Tables 601 and 602. The distance to an adjacent lot line shall be deter- mined in accordance with Table 602 and Section 705. 406.5.7 Means of egress. Where persons other than park- ing attendants are permitted, open parking garages shall meet the means of egress requirements of Chapter 10. Where no persons other than parking attendants are per- mitted, there shall be no fewer than two exit stairways. Each exit stairway shall be not less than 36 inches (914 mm) in width. Lifts shall be permitted to be installed for use of employees only, provided they are completely enclosed by noncombustible materials. [F] 406.5.8 Standpipe system. An open parking garage shall be equipped with a standpipe system as required by Section 905.3. 406.5.9 Enclosure of vertical openings. Enclosure shall not be required for vertical openings except as specified in Section 406.5.7. 406.5.10 Ventilation. Ventilation, other than the percent- age of openings specified in Section 406.5.2, shall not be required. 406.5.11 Prohibitions. The following uses and alterations are not permitted: ' 1. Vehicle repair work. 2. Parking of buses, trucks and similar vehicles. 3. Partial or complete closing of required openings in exterior walls by tarpaulins or any other means. 4. Dispensing of fuel. 406.6 Enclosed parking garages. Enclosed parking garages shall comply with Sections 406.6.1 through 406.6.3. 406.6.1 Heights and areas. Enclosed vehicle parking garages and portions thereof that do not meet the defini- tion of open parking garages shall be limited to the allow- able heights and areas specified in Sections 504 and 506 as modified by Section 507. Roof parking is permitted. 406.6.2 Ventilation. A mechanical ventilation system shall be provided in accordance with the Florida Building Code, Mechanical. [F] 406.6.3 Automatic sprinkler system. An enclosed parking garage shall be equipped with an automatic sprin- kler system in accordance with Section 903.2.10. 406.7 Motor fuel -dispensing facilities. Motor fuel -dispens- ing facilities shall comply with the Florida Fire Prevention Code and Sections 406.7.1 and 406.7.2. 406.7.1 Vehicle fueling pad. The vehicle shall be fueled on noncoated concrete or other approved paving material having a resistance not exceeding 1 megohm as deter- mined by the methodology in EN 1081. 406.7.2 Canopies. Canopies under which fuels are dis- pensed shall have a clear, unobstructed height of not less than 13 feet 6 inches (4115 mm) to the lowest projecting element in the vehicle drive -through area. Canopies and their supports over pumps shall be of noncombustible materials, fire -retardant -treated wood complying with Chapter 23, wood of Type IV sizes or of construction pro- viding 1-hour fire resistance. Combustible materials used in or on a canopy shall comply with one of the following: 1. Shielded from the pumps by a noncombustible ele- ment of the canopy, or wood of Type IV sizes; 2. Plastics covered by aluminum facing having a thick- ness of not less than 0.010 inch (0.30 mm) or corro- sion -resistant steel having a base metal thickness of not less than 0.016 inch (0.41 mm). The plastic shall have aflame spread index of 25 or less and a smoke - developed index of 450 or less when tested in the form intended for use in accordance with ASTM E84 or UL 723 and a self -ignition temperature of 650°F (343°C) or greater when tested in accordance with ASTM D 1929; or 3. Panels constructed of light -transmitting plastic materials shall be permitted to be installed in cano- pies erected over motor vehicle fuel -dispensing sta- tion fuel dispensers, provided the panels are located not less than 10 feet (3048 mm) from any building on the same lot and face yards or streets not less than 40 feet (12192 mm) in width on the other sides. The aggregate areas of plastics shall be not greater than 1,000 square feet (93 in). The maximum area of any individual panel shall be not greater than 100 square feet (9.3 m). 406.7.2.1 Canopies used to support gaseous hydro- gen systems. Canopies that are used to shelter dispens- ing operations where flammable compressed gases are located on the roof of the canopy shall be in accordance with the following: 1. The canopy shall meet or exceed Type I construc- tion requirements. 2. Operations located under canopies shall be lim- ited to refueling only. 3. The canopy shall be constructed in a manner that prevents the accumulation of hydrogen gas. 06.8 Repailr Sarsy Repair garages shall be constructed to accordance with the Florida Fire Prevention Code and Sections 406.8.1 through 406.8.6. This occupancy shall not include motor fuel -dispensing facilities, as regulated in Sec- tion 406.7. 406.8.1 Mixed uses. Mixed uses shall be allowed in the same building as a repair garage subject to the provisions of Section 508. L 406.8.2 Ventila ;io . Repair garages shall be mechanically ventilated in accordance with the Florida Building Code, Mechanical. The ventilation system shall be controlled at the entrance to the garage. FLORIDA BUILDING CODE — BUILDING, 6th EDITION (2017) 77 �p gg Copyright O 2017 ICC. ALL RIGHTS RESERVED. Accessed by John Peterson on Sep 21, 2017 5:12:51 AM pursuant to License Agreement with ICC. No further reproduction or distribution authorized. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT. AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY 406.8.3 Floor surface. Repair garage floors shall be of shall be separated from other areas in accordance with Sec - concrete or similar noncombustible and nonabsorbent tion 407.3 except spaces conforming to Sections 407.2.1 materials. through 407.2.6. Exception: Slip -resistant, nonabsorbent, interior floor 407.2.1 Waiting and similar areas. Waiting areas and finishes having a critical radiant flux not more than similar spaces constructed as required for corridors shall 0.45 W/cmZ, as determined by NFPA 253, shall be per- be permitted to be open to a corridor, only where all of the miffed. following criteria are met: 406.8.4 Heating equipment. Heating equipment shall be 1. The spaces are not occupied as care recipient's installed in accordance with the Florida Building Code, sleeping rooms, treatment rooms, incidental uses in Mechanical. accordance with Section 509, or hazardous uses. [F] 406.8.5 Gas detection system. Repair garages used for the repair of vehicles fueled by nonodorized gases such as hydrogen and nonodorized LNG, shall be provided with a flammable gas detection system. [F] 406.8.5.1 System design. The flammable gas detection system shall be listed or approved and shall be calibrated to the types of fuels or gases used by vehi- cles to be repaired. The gas detection system shall be designed to activate when the level of flammable gas exceeds 25 percent of the lower flammable limit (LFL). Gas detection shall be provided in lubrication or chassis service pits of repair garages used for repairing nono- dorized LNG -fueled vehicles. [F] 406.8.5.1.1 Gas detection system components. Gas detection system control units shall be listed and labeled in accordance with UL 864 or UL 2017. Gas detectors shall be listed and labeled in accor- dance with UL 2075 for use with the gases and vapors being detected. [F] 406.8.5.2 Operation. Activation of the gas detec- tion system shall result in all of the following: 1. Initiation of distinct audible and visual alarm sig- nals in the repair garage. 2. Deactivation of all heating systems located in the repair garage. 3. Activation of the mechanical ventilation system, where the system is interlocked with gas detec- tion. [F] 406.8.5.3 Failure of the gas detection system. Failure of the gas detection system shall result in the deactivation of the heating system, activation of the mechanical ventilation system where the system is interlocked with the gas detection system and cause a trouble signal to sound in an approved location. [F] 406.8.6 Automatic sprinkler system. A repair garage shall be equipped with an automatic sprinkler system in accordance with Section 903.2.9.1. 2. The open space is protected by an automatic fire detection system installed in accordance with Sec- tion 907. 3. The corridors onto which the spaces open, in the same smoke compartment, are protected by an auto- matic lire detection system installed in accordance with Section 907, or the smoke compartment in which the spaces are located is equipped throughout with quick -response sprinklers in accordance with Section 903.3.2. 4. The space is arranged so as not to obstruct access to the required exits. 407.2.2 Care providers' stations. Spaces for care pro- viders', supervisory staff, doctors' and nurses' charting, communications and related clerical areas shall be permit- ted to be open to the corridor, where such spaces;are.con- structed as required for corridors. 407.2.3 Psychiatric treatment areas. -Areas wherein psy- chiatric care recipients who are not capable of self-preser- vation are housed, or group meeting or multipurpose therapeutic spaces other than incidental uses in accordance with Section 509, under continuous supervision by facility staff, shall be permitted to be open to the corridor, where the following criteria are met: 1. Each area does not exceed 1,500 square feet (140 in 2). 2. The area is located to permit supervision by the facility staff. 3. The area is arranged so as not to obstruct any access to the required exits. 4. The area is equipped with an automatic fire detec- tion system installed in accordance with Section 907.2. 5. Not more than one such space is permitted in any one smoke compartment. 6. The walls and ceilings of the space are constructed as required for corridors. 407.2.4 Gift shops. Gift shops and associated storage that SECTION 407 per - GROUP 1-2 are less than 500 square feet (455 m) in area shall be mitted to be open to the corridor where such spaces are 407.1 General. Occupancies in Group I-2 shall comply with constructed as required for corridors. the provisions of Sections 407.1 through 407.10 and other 407.2.5 Nursing home housing units. In Group I-2, Con - applicable provisions of this code. dition 1, occupancies, in areas where nursing home resi- 407.2 Corridors continuity and separation. Corridors in dents are housed, shared living spaces, group meeting or occupancies in Group I-2 shall be continuous to the exits and multipurpose therapeutic spaces shall be permitted to be 76 FLORIDA BUILDING CODE — BUILDING, 6th EDITION (2017) F G ! 5 Copyright © 2017ICC. ALL RIGHTS RESERVED. Accessed by John Peterson on Sep zt, 2017 s:u:st AM pursuant to License Agreement with ICC. No further reproduction or E distribution authorized. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT. AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER. n � processing operations that are not classified as a Group H hazardous or Group S storage occupancy. 306.2 Moderate -hazard factory industrial, Group F-1. Factory industrial uses that are not classified as Factory Industrial F-2 Low Hazard shall be classified as F-1 Moder- ate Hazard and shall include, but not be limited to, the follow- ing: Aircraft (manufacturing, not to include repair) Appliances Athletic equipment Automobiles and other motor vehicles Bakeries Beverages: over 16-percent alcohol content Bicycles Boats Brooms or brushes Business machines Cameras and photo equipment Canvas or similar fabric Carpets and rugs (includes cleaning) Clothing Construction and agricultural machinery Disinfectants Dry cleaning and dyeing Electric generation plants Electronic -- ngines (i clu 'ng rebui'lding+) ood processi g establishments and commercial kitchens not associated with restaurants, cafeterias and similar dining facilities more than 2,500 square feet (232 m2) in area. Furniture Hemp products Jute products Laundries Leather products Machinery Metals Millwork (sash and door) Motion pictures and television filming (without spectators) Musical instruments Optical goods Paper mills or products Photographic film Plastic products Printing or publishing Recreational vehicles Refuse incineration Shoes Soaps and detergents Textiles Tobacco Trailers Upholstering Wood; distillation Woodworking (cabinet) USE AND OCCUPANCY CLASSIFICATION 306.3 Low -hazard factory industrial, Group F-2. Factory industrial uses that involve the fabrication or manufacturing of noncombustible materials that during finishing, packing or processing do not involve a significant fire hazard shall be classified as F-2 occupancies and shall include, but not be limited to, the following: Beverages: up to and including 16-percent alcohol content Brick and masonry Ceramic products Foundries Glass products Gypsum Ice Metal products (fabrication and assembly) SECTION 307 HIGH -HAZARD GROUP H [F] 307.1 High -hazard Group H. High -hazard Group H occupancy includes, among others, the use of a building or structure, or a portion thereof, that involves the manufactur- ing, processing, generation or storage of materials that consti- tute a physical or health hazard in quantities in excess of those allowed in control areas complying with Section 414, based on the maximum allowable quantity limits for control areas set forth in Tables 307.1(1) and 307.1(2). Hazardous occupancies are classified in Groups H-1, H-2, H-3, H-4 and H-5 and shall be in accordance with this section, the require- ments of Section 415 and the Florida Fire Prevention Code. Hazardous materials stored, or used on top of roofs or cano- pies, shall be classified as outdoor storage or use and shall comply with the Florida Fire Prevention Code. [F] 307.1.1 Uses other than Group H. An occupancy that stores, uses or handles hazardous materials as described in one or more of the following items shall not be classified as Group H, but shall be classified as the occupancy that it most nearly resembles. I. Buildings. and structures occupied for the applica- tion of flammable finishes, provided that such buildings or areas conform to the requirements of Section 416 and the Florida Fire Prevention Code. 2. Wholesale and retail sales and storage of flamma- ble and combustible liquids in mercantile occu- pancies conforming to the Florida Fire Prevention Code. 3. Closed piping system containing flammable or combustible liquids or gases utilized for the opera- tion of machinery or equipment. 4. Cleaning establishments that utilize combustible liquid solvents having a flash point of 140°F (60°C) or higher in closed systems employing equipment listed by an approved testing agency, provided that this occupancy is separated from all other areas of the building by 1-hour fire barriers constructed in accordance with Section 707 or 1- hour horizontal assemblies constructed in accor- dance with Section 711, or both. FLORIDA BUILDING CODE — BUILDING, 6th EDITION (2017) 55 IB ,J & a B 8, Copyright 0 2017 ICC. ALL RIGHTS RESERVED. Accessed by John Peterson on Sep 21,2017 5:12:51 AM pursuant to License Agreement with ICC. No further repro? 9i 9 8 ® 6a distribution authorized. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICI AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER. AZNw-;O47R PFR WFPA t; IkSTALL PANIC WIROWARE OCCUPANT LOAD ERRING I j DEVICE ON EXISTING DOOR IS LESS THAN 1W. 61E j �� -- _ I FE '()STING �w 145(360) � V EXISTING. ; EQUIPMENT R FSFR"� ROOM STORAGE 16(180) EXISTING D:ISTING MEWS n RR EXIS"PING KITCHEN 3 ' C3 EXISTING , Ar —�_ CORRIDOR --.---- i a I 200 S.FJCCC. Fmow ;r - WOMEWS !' RR (rI I I a3 ) ,si 138(360) NEW I t� PLATFORN FESt tir I' EXISTING DINING AREA NEW a PLATFORM <. } 6,103 S.F. , 340 OCr 15 S.F.!CCC. ,1' LACCESSIBLE PUTFRMNF IO_ --- REMODELED f ° BARARFA DOORFIA�EXISTUIO t PANIC HARDVdARE DEVICE. 39(180) 38(180) EXIStDINING PG EXISTING DINING ` ROOM LOBBY ^J 1,154S.F.-77CCC. 1 15 S.FJCCC. Eo FE ! INSTAL). PANIC HARDWARE W Z DEVICE ONEn•1STINGDOOP.=.139(360) �F ! � � E`(ISTNG �'� = VESTIBULE ' ta'-r 1 v _ rlu •• F �,�1 um: f crrcar ca' f rit%.r sM�r i �__ xr.c _ zrxr.:; •• � ; „"c7TT._..� I—a•t. _I r.:ac•�x „.. �� zl rtrztr ►iR�4d' �i�r•3� IP�:Ei.'3'c,T&5T# ) �VVN �aY'"+°"na.a'I n x Ad � C Sl+f3F Sti�F E S F1� �_ I _ _ L _ _ _ _ �' z xsW�� u•era-n. z_�.Y.:y _ _ _ rs a' • C '.,T--l+ — — d...K^Xi ,x ...»__-__ `f`nK.7-..:.,..� ,--Gw....0 +r ..m-3,.....-. �•YS .. • � E I ' PAgrRWN�:AIi IUE LOINyR TI V vxrAxF EI r33 09 Iv- -ow v � 4BS;'i�Akr� • n. G� '� I %�'•xir}�f'- eaxax I �F}_"F'fkEF.1 1 emtsr '2u ra � 'xpr v1`{ of ru;tccsx avmtr .)uEv.r M¢cr Xx�r 1 r O I I SALES N'40 SERVICE FOR t •,bz i'' - :) I rtaam eorrl: FOINCR OUTDOOR raa r[r. f•+ca+rat srr rr< F 1 mzr• aver !.m•rn vrzox .}x r J li � M;.csr ¢hEarr � EOUEtnENT 4a.rnr I (wv T:^r� rYX 't)r '� �tY'rd I I� - uxw era=u I ._ - _µM eoau �-.>tco�i�yyjl(SG a➢bxhzu � c:_�a�;;. �, I 1 laf 'x yq, J t raac}) b 4 � 49' I vorrn edorrr - � d�➢ / I M:P.:fii (LAnuC9T ., yY�:1581rt • :Ak3M�{'; MJb Z" n"EST tt. i Yrp ro111kN I � � A ,� rG k of I --� '-------..� ; ----� � F •k`E J i � a" `� ` ' xAOl}31 RiU1YfJt fA01YFA •ariFY. � {1fIiKHILY'. •' r ` I a:•tar vrxar• LCAar licsr 5cy�ar i�4 E U.!aarer M1wcesr nrvcmyx w. c�yj '^'h. t57 n jjj f l ldonEil P:Anttil S-� Ftl 1 fv.atg' i t. 11 IT-i , I `- 11 _ -- 3� -G �i Jd4,�a 'Q� �JTr icYC.E�� „ iF '" Ai,G"c iC,'R'? r . � �.»• ____ ___ 3 p _��a�rn:•w-'µ'�:'uirao-x via n�ww,v . — -_.----_,^7.., wt'.2 � ruxr ra, 1, i p"..'.M lecd�.��w'i�u��.Y.. x''i."1..pu �.e.� .� °4'd` d "'..E1�ns 1�. -- �°+Fso� •..'�""" 1+,3 ... t 2 • E. t �R �" 1 9,..b '�•w � ` N N ` -- — — � fwwrniu E'fd4t:�.t ems: ! I �' �i�"�FI�'E£�r�'.'� t o d` s-r rAa�n rvq)xr Ttl+"7 a } , ' tl7 II 4 a i I rnunoi' - �r I r � 7x � c rcrvr,, � � y u •,YJi �,�� ��M I k f�N�r6Jtr.Gx. a i! ` ��i iia�`$' ,'� :iFF�+!'E� E'•d@ a'��uc'aE I t � o i,l � �! i d 33 Ip• 1 r cv yttK•m'�x�F�tci uV �.•ti I 2 E� -�"T £S� t�' GRe'l4Fr� LIU PJ�6uFa�fOer'3{Eii i tr I:�ay ; !! a, a �,� @it ef°Fy�{'ril4'!¢' '.,"`,�9•) < � I ,� � ^- �" °r'x•n,r.., ��_� 41u 91 �f 'F`.R:7eaTn z.S•A —" -tt� ,-tu .n rntr p 1 s tl :G'-1'12" , 1f•r W UNIT7159 �[[10L223SF- - , 'M' MERCANTILE +I 1 6RE F 6RE F 6NE F SRE F 6)�lF uxI6xT3' 3<xT6xri' 30xT6xTS NxTe•A3T 31xT6-lOS ,yqyqy,, �B �,j Q EALSTVLG3JW p 165 C�INWf�i1RtRED sl�s� b Sz-s b ENTIiv h E I PARTS ROOM �M I � SNEIF � Ea 6RELF E I EJ09TOlGt TE NN-A�IT FAA�RTIDIION WALL SALES COUNTER ,�Iy1,111r S1MO — — 11sd— WULPATNOF— mm b EAISTPIO SRR I RATFD fURRID EOCNU WALL COLUMN- 10.6' I T•6 11'-P 2 5 g I MOWER MOWER HONER MOWER M R y RETAIL m I ��iT oDG�s)T SIiOWROOM p"RGEsr LA�R6 sr a) o MODEL) MODEL) F1) _ I "GROUP M" N m SALES AND SERVICE FOR POWER MOWER POWER OUTDOOR YOWE0. MOWER M R Boxer Boxer EOUIMENT arxer eo•Aer er (LARGEST GARGE6T (INGEST (INGEST ST NOOEL) LWDEL) NOOEL) MOOEL) EL) i I E%ISTPIG COLUMN POWER 40WE0. POWER MOWER M R 6mmr emar 6mMr aP r (INGEST (LARGEST (LNGE6T G—EST .mo ST E E%ISIWO I YODEII MODEL) YODEL) MODEL) MO ) I MOWER MOWER 40WER MOWER M 6mxer ewer boxer 6mGES ryAbox I GNGE6T GARGEST GARGEST ODU) A6 NOD MODEL) T I MODEL) MODEL) YODEL) I I MOWER MOWE0. Im-7 x RA0.GEST (LARGEST (1N0T 6' MODEL) MODEL) S-s EfO MO M j 1S-T fALul41 I � DOL� — — STORAGE m ExISIM01NF0 i1 � V E� — 2 ' EXIS T= PATNOF �_ OMEN I TRAKL _ TMEIIANINEM —I I O �M G I I O EASTI cauuN I T �` LIFT Txnxz �1 UFT rxnxe� I �' J7 — I Lr_ I � 2 e O i I --- I =_= EXISTING MEN R.R. SERVICE PAIS1e1 AREA --- "GROUP F" I > FXlSie10 COW" EATSTPIOE COLUMN -. CSUMN T APR SOR ` �� OFFICE ROOM I EMSTUIG LDO —0 � E>aSO AAIEO MOM W E® ELEG PANELS FA PNEL 70' -1 1/2" 44 iii ----- W.• --- n y. ..i T; pip g�fl a}° piT — i _ 1 y rcag �Ig i df 2e t I n¢ x. i 4 e ars4 «{Ig3 �# -'t. k�I FS lG 'd'f'i£3 Ft {�� I a y ![ Yfi{ J,j �{�, ; 'j� �,'•,rt �h �Fa ]JP J3 £ C44 3 .-- 5i9 it-" _..,d vie. dt r y � pin I � � �' � ���� � „��� � € � � r 3 � R�2�•� r 'i �y. �p . ` 4 'i^ �-._-iti-c-�,'—���«'2.�c'_ _`_�. - ls^ ']S:CXrKs -� X.�S.v'-x- -�-•r i-zcs.��ss:..4..baZ? �-C.�:«" $_' f1_ _x7Gs :LY 1J7-1E 1(1' D EXISTING FLOOR 0 ..EXISTING CONDITIONS" PLANS 7159 LAS-1 D r PORT ST. L1JCIE, FL 34952 �s>, ..••