HomeMy WebLinkAboutAPPROVED Mount AnalysisJuly 12, 2021 FL COA# 31011
Gustavo Dezzuto Tower Engineering Professionals
SBA Network Services 326 Tryon Road
8051 Congress Ave. Raleigh, NC 27603
Boca Raton, FL 33487 (919) 661-6351
(561) 226-9444 Structures@tepgroup.net
Subject: Appurtenance Mount Analysis
Carrier Designation: Dish Wireless Co-Locate
Site Number: MIMIA00768A
Site Name: MIMIA00768A
SBA Network Services: Site Number: FL10049-A
Site Name: Midway Road
Engineering Firm Designation: TEP Project Number: 62749.566934
Site Data: 375 E. Midway Road, Fort Pierce, St. Lucie County, FL 34982
Latitude 27° 22' 25.32, Longitude -80° 19' 20.79''
303.0± Foot - Guyed Tower
210.0 Foot Mount Height - Sector
Dear Gustavo Dezzuto,
Tower Engineering Professionals is pleased to submit this “Appurtenance Mount Analysis” to determine the
structural integrity of the antenna mount on the above mentioned tower.
The purpose of the analysis is to determine acceptability of the mount's stress level. Based on our analysis we
have determined the stress level for the mount structure, under the following load case, to be:
LC1: Existing + Proposed + Reserved Loading Sufficient Capacity
Note: See Table 2 for the existing, proposed, and reserved loading
The analysis has been performed in accordance with the ANSI/TIA-222-H Structural Standard for Antenna
Supporting Structures, Antennas, and Small Wind Turbine Support Structures and the 2020 Florida Building Code,
7th Edition.
All equipment proposed in this report shall be installed in accordance with the appurtenances listed in Table 2 for
the determined available structural capacity to be effective.
We at Tower Engineering Professionals appreciate the opportunity of providing our continuing professional
services to you and SBA Network Services. If you have any questions or need further assistance on this or any
other projects please give us a call.
Structural analysis prepared by: Anand Bhatt / DC
Respectfully submitted by:
Ronald E. Glover, P.E., S.E.
07/12/2021
July 12, 2021
Sector Mount Analysis Midway Road (FL10049-A)
TEP Project Number 62749.566934 Page 2
ANALYSIS CRITERIA
Table 1 - Mount Analysis Parameters
Ultimate
Wind Speed
(MPH)
Ice
Thickness
(in)
Ice Wind
Speed (MPH)
Exposure
Category
Risk
Category
Topo
Procedure Kzt
Seismic
Design
Category
160 0.0 30 C II Method 2 1.0 A
Table 2 - Existing, Proposed, and Reserved Antenna Loading Configuration
Existing/
Proposed/
Reserved
Mount
Level
(ft)
Ant
CL
(ft)
Qty Antenna Model Mount
Type
Owner/
Tenant
Final
Loading
Config.
210.0 210.0
3 JMA Wireless MX08FRO665-21 (3) Sabre
C10837002C-
32788 V-Boom
Sector Mounts
Dish
Wireless
3 Fujitsu TA08025-B605
3 Fujitsu TA08025-B604
1 Raycap RDIDC-9181-PF-48
ANALYSIS RESULTS
Table 3 - Mount Component Stresses vs. Capacity
Notes Component % Capacity Pass / Fail
- Face Horizontal 29.7 Pass
- Support Arm 26.7 Pass
- Support Bracing 20.3 Pass
- Mount Pipe 21.7 Pass
- Stabilizer Arm 13.1 Pass
- Connection Bolts 11.7 Pass
Table 4 - Documents Provided
Document Remarks Source
Mount Assembly
Drawings
Sabre, dated July 13, 2020
DWG No. C10837002C-32788 SBA
Correspondence Correspondence from SBA Network Communications in reference to the
existing, proposed and reserved loading. SBA
July 12, 2021
Sector Mount Analysis Midway Road (FL10049-A)
TEP Project Number 62749.566934 Page 3
RECOMMENDATIONS
1) If the load differs from that described in Table 2 of this report or the provisions of this analysis are
found to be invalid, another structural analysis should be performed.
2) The mount has sufficient capacity to carry the existing, proposed, and reserved loading. No
modifications are required at this time.
ANALYSIS ASSUMPTIONS
1) The mount was built in accordance with the manufacturer’s specifications.
2) The mount has been maintained in accordance with the manufacturer’s specification.
3) The configuration of antennas, transmission cables, mounts and other appurtenances are as
specified in Table 2. All mount components have been assumed to be in sufficient condition to
carry their full design capacity for this analysis. Refer to the issued mapping for any structural
and/or maintenance issues found during our site visit.
4) Serviceability with respect to antenna twist, tilt, roll, or lateral translation, is not checked and is
left to the carrier or tower owner to ensure conformance.
5) All material grades used for this analysis, unless verified by mount manufacturer design, were
assumed per AISC Table 2-4, 15th Edition. See RISA 3-D output for confirmation on grades used
in this analysis.
This analysis may be affected if any assumptions are not valid or have been made in error. Tower
Engineering Professionals should be notified to determine the effect on the structural integrity of the
mount.
July 12, 2021
Sector Mount Analysis Midway Road (FL10049-A)
TEP Project Number 62749.566934 Page 4
APPENDIX A
RISA-3D OUTPUT
Tower Engineering Profes...
APB
TEP No. 62749.566934
Midway Road (FL10049-A)
SK - 1
July 12, 2021 at 10:21 AM
Sabre C10837002 THD V-Boom.r3d
Y
XZ
Envelope Only Solution
Tower Engineering Profes...
APB
TEP No. 62749.566934
Midway Road (FL10049-A)
SK - 2
July 12, 2021 at 10:21 AM
Sabre C10837002 THD V-Boom.r3d
-.032k-.139k
-.032k
-.022k
Y
XZ
Loads: BLC 1, Dead
Envelope Only Solution
Tower Engineering Profes...
APB
TEP No. 62749.566934
Midway Road (FL10049-A)
SK - 3
July 12, 2021 at 10:21 AM
Sabre C10837002 THD V-Boom.r3d.22.1 5.1 5
.1 7 N
C.1 7N
C .1 5
NCN
C .1 5
.1 9.1 9.1 9 .22.1 9
NCN C
.1 9
.09.12 .08NC.2 2
NC.1 8.17.24.12 .2 2
.1 9 N
C
.24.09
.1 7 .1 9N
C .2 2
NC.14.1 7
N
C .2 2
.1 7
.22.1 7.1 7
NC.20N C
NC.19 NC.3 0
.27.24.27.14.12.1 8
.
1
3
.12.24.08.24.27NC.1 6 N
C.1 6N
C
.1 4
.19 .14N
C
.1 4.1 4 .08.3 0
.1 4 .27.27.08NC.2 2 N
C.2 2N
C
.2 4 NCN
C
.2 4.2 4.2 4
.08Y
XZ
Code Check
( Env )
No Calc
> 1.0
.90-1.0
.75-.90
.50-.75
0.-.50
Member Code Checks Displayed (Enveloped)
Envelope Only Solution
Tower Engineering Profes...
APB
TEP No. 62749.566934
Midway Road (FL10049-A)
SK - 4
July 12, 2021 at 10:22 AM
Sabre C10837002 THD V-Boom.r3dMP-1F F 1 -B H 1
F F 1 -B H 1
F P -3FP3-R1FP-3FP3-R2
F F 1 -B H 1
SF1-R4FP3-R3
F F 1 -B H 1
S F 1 -BHSF1-BHSF1-BH MP-1S F 1 -BH
SF1-R2R 2
S F 1 -BH
SF1-D1SF1-D 2SF1-V2R4F F 1 -T H 1
SF2-R2F F 1 -B H 2SF1-V1SF2-BHS F 1-D 2F F 1 -T H 1
F P -1FP1-R1
SF2-BHSF1-D1
S F 1 -T H
F P -1FP1-R2
F F 1 -T H 1
SF1-R3MP-2S F 1 -T H
FP1-R3
F F 1 -T H 1
S F 1 -T H
MP-1S F 1 -T HSF1-T H
SF1-R1SF2-V1R 1
R3SF2-D2SF2-R1F F 1 -T H 2
SF2-THSF2-BHSF2-THMP-2SF2-D1F F 1 -B H 2
S
A
-
1
SF2-D1SF2-BHMP-3SF2-BHSF2-THSF2-R4F P -4FP4-R3FP-4FP4-R2
F F 1 -B H 3
SF2-D2 MP-2FP4-R1
F F 1 -B H 3
F F 1 -B H 3 SF2-V2F F 1 -T H 2
F F 1 -B H 3 SF2-THSF2-THMP-3SF2-R3F P -2FP2-R1FP-2FP2-R2
F F 1 -T H 3M50FP2-R3
F F 1 -T H 3
F F 1 -T H 3
F F 1 -T H 3
MP-3Y
XZ
Envelope Only Solution
Tower Engineering Profes...
APB
TEP No. 62749.566934
Midway Road (FL10049-A)
SK - 5
July 12, 2021 at 10:22 AM
Sabre C10837002 THD V-Boom.r3dPIPE_2.5P IP E _2 .0
P IP E _2 .0
C W S 0 0 9 5 2
C W S 0 0 9 5 2P IP E _2 .0
P IP E _2 .0
1 .9 O .D . x 0 .2 0 01.9 O .D . x 0 .2 0 01.9 O .D . x 0 .2 0 0 PIPE_2.51 .9 O .D . x 0 .2 0 01.9 O .D . x 0 .2 0 0
SR 3/4SR 3 /4
SR 3/4P IP E _2 .0
P IP E _2 .0SR 3/41.9 O.D. x 0.200S R 3 /4
P IP E _2 .0
C W S 0 0 9 5 2
1.9 O.D. x 0.200SR 3/4
1 .9 O .D . x 0 .2 0 0 C W S 0 0 9 5 2P IP E _2 .0
PIPE_2.51 .9 O .D . x 0 .2 0 0
P IP E _2 .0
1 .9 O .D . x 0 .2 0 0
PIPE_2.51 .9 O .D . x 0 .2 0 01.9 O .D . x 0 .2 0 0
SR 3/4S
R 3/4
P IP E _2 .0
1.9 O.D. x 0.2001.9 O.D. x 0.2001.9 O.D. x 0.200PIPE_2.5SR 3/4P IP E _2 .0
P
I
P
E
_
2
.
0
SR 3/41.9 O.D. x 0.200PIPE_2.51.9 O.D. x 0.2001.9 O.D. x 0.200C W S 0 0 9 5 2
C W S 0 0 9 5 2
P IP E _2 .0
S
R 3/4 PIPE_2.5P IP E _2 .0
P IP E _2 .0 SR 3/4P IP E _2 .0
P IP E _2 .0 1.9 O.D. x 0.2001.9 O.D. x 0.200PIPE_2.5C W S 0 0 9 5 2
C W S 0 0 9 5 2
P IP E _2 .0
P IP E _2 .0
P IP E _2 .0
P IP E _2 .0
PIPE_2.5Y
XZ
Envelope Only Solution
Company : Tower Engineering Professionals, Inc.July 12, 202110:22 AMDesigner : APBJob Number : TEP No. 62749.566934Checked By: DCModel Name : Midway Road (FL10049-A)(Global) Model SettingsDisplay Sections for Member CalcsMax Internal Sections for Member CalcsInclude Shear Deformation?Increase Nailing Capacity for Wind?Include Warping?Trans Load Btwn Intersecting Wood Wall?Area Load Mesh (in^2)Merge Tolerance (in)P-Delta Analysis ToleranceInclude P-Delta for Walls?Automatically Iterate Stiffness for Walls?Max Iterations for Wall StiffnessGravity Acceleration (ft/sec^2)Wall Mesh Size (in)Eigensolution Convergence Tol. (1.E-)Vertical AxisGlobal Member Orientation PlaneStatic SolverDynamic Solver5 97 YesYesYesYes144.120.50%YesYes332.2244YXZSparse AcceleratedAccelerated SolverHot Rolled Steel CodeAdjust Stiffness?RISAConnection CodeCold Formed Steel CodeWood CodeWood TemperatureConcrete CodeMasonry CodeAluminum CodeStainless Steel CodeAISC 15th(360-16): LRFDNoNoneNoneNone< 100FNoneNoneNone - BuildingNoneNumber of Shear RegionsRegion Spacing Increment (in)Biaxial Column MethodParme Beta Factor (PCA)Concrete Stress BlockUse Cracked Sections?Use Cracked Sections Slab?Bad Framing Warnings?Unused Force Warnings?Min 1 Bar Diam. Spacing?Concrete Rebar SetMin % Steel for ColumnMax % Steel for Column44Exact Integration.65RectangularYesNoNoYesNoREBAR_SET_ASTMA61518RISA-3D Version 17.0.4 Page 1 [C:\...\...\...\...\RISA-3D\Sabre C10837002 THD V-Boom.r3d] Company : Tower Engineering Professionals, Inc.July 12, 202110:22 AMDesigner : APBJob Number : TEP No. 62749.566934Checked By: DCModel Name : Midway Road (FL10049-A)(Global) Model Settings, ContinuedSeismic CodeSeismic Base Elevation (ft)Add Base Weight?Ct XCt ZT X (sec)T Z (sec)R XR ZCt Exp. XCt Exp. ZSD1SDSS1TL (sec)Risk CatDrift CatASCE 7-16Not EnteredYes.02.02Not EnteredNot Entered33.75.751115I or IIOtherOm ZOm XCd ZCd XRho ZRho X111111Hot Rolled Steel PropertiesLabel E [ksi] G [ksi] Nu Therm (/1E...Density[k/ft... Yield[ksi] Ry Fu[ksi] Rt1A36 Gr.362900011154.3.65.49361.5581.22A572 Gr.502900011154.3.65.49501.1651.13A500 Gr.B RND2900011154.3.65.49421.4581.34A500 Gr.B Rect2900011154.3.65.49461.4581.35A53 Gr.B2900011154.3.65.49351.6601.26A500 Gr. C - 462900011154.3.65.49461.5621.27A500 Gr. C - 502900011154.3.65.49501.5621.2Hot Rolled Steel Section SetsLabel Shape Type Design List Material Design R... A [in2]Iyy [in4] Izz [in4] J [in4]1Face HorizontalPIPE_2.0NoneNoneA500 Gr. C - 50Typical1.02.627.6271.252Support Horiz...1.9 O.D. x 0.200NoneNoneA500 Gr. C - 50Typical1.068.391.391.7823Mount PipesPIPE_2.5NoneNoneA53 Gr.BTypical1.611.451.452.894Support BracingSR 3/4NoneNoneA572 Gr.50Typical.442.016.016.0315Stabilizer ArmPIPE_2.0NoneNoneA572 Gr.50Typical1.02.627.6271.256Face PlateCWS00952NoneNoneA36 Gr.36Typical1.063.022.4.075Cold Formed Steel Section SetsLabel Shape Type Design List Material Design Rules A [in2] Iyy [in4] Izz [in4] J [in4]1CF1A8CU1.25X057BeamNoneA653 SS Gr...Typical.581.0574.41.00063Material TakeoffMaterial Size Pieces Length[ft] Weight[K]1General2RIGID255.803Total General255.80RISA-3D Version 17.0.4 Page 2 [C:\...\...\...\...\RISA-3D\Sabre C10837002 THD V-Boom.r3d]
Company : Tower Engineering Professionals, Inc.July 12, 202110:22 AMDesigner : APBJob Number : TEP No. 62749.566934Checked By: DCModel Name : Midway Road (FL10049-A)Material Takeoff (Continued)Material Size Pieces Length[ft] Weight[K]45Hot Rolled Steel6A36 Gr.36CWS0095241.3.0057A500 Gr. C - 501.9 O.D. x 0.200417.0628A500 Gr. C - 50PIPE_2.0622.0769A53 Gr.BPIPE_2.5324.13110A572 Gr.50PIPE_2.016.5.02311A572 Gr.50SR 3/4828.04212Total HR Steel2698.8.339Joint Boundary ConditionsJoint Label X [k/in] Y [k/in] Z [k/in] X Rot.[k-ft/rad]Y Rot.[k-ft/rad] Z Rot.[k-ft/rad]1TC1-1ReactionReactionReaction2TC1-2ReactionReactionReaction3SA-2AReactionReactionReactionMember Primary DataLabel I Joint J Joint K Joint Rotate(de... Section/ShapeType Design List Material Design Rules1FF1-BH1FF5FF6Face HorizontalNoneNoneA500 Gr. ...Typical2FF1-BH2FF6FF7Face HorizontalNoneNoneA500 Gr. ...Typical3FF1-BH3FF7FF8Face HorizontalNoneNoneA500 Gr. ...Typical4FF1-TH1FF1FF2Face HorizontalNoneNoneA500 Gr. ...Typical5FF1-TH2FF2FF3Face HorizontalNoneNoneA500 Gr. ...Typical6FF1-TH3FF3FF4Face HorizontalNoneNoneA500 Gr. ...Typical7FP-1SA-1ASF1-490Face PlateNoneNoneA36 Gr.36Typical8FP-2SF2-4X72B90Face PlateNoneNoneA36 Gr.36Typical9FP-3SA-1CSF1-890Face PlateNoneNoneA36 Gr.36Typical10FP-4SF2-8SA-1D90Face PlateNoneNoneA36 Gr.36Typical11FP1-R1SA-1ACP-1RIGIDNoneNoneRIGIDTypical12FP1-R2R1CP-5RIGIDNoneNoneRIGIDTypical13FP1-R3SF1-4FF2RIGIDNoneNoneRIGIDTypical14FP2-R1SF2-4FF3RIGIDNoneNoneRIGIDTypical15FP2-R2R2CP-6RIGIDNoneNoneRIGIDTypical16FP2-R3X72BCP-2RIGIDNoneNoneRIGIDTypical17FP3-R1SA-1CCP-3RIGIDNoneNoneRIGIDTypical18FP3-R2R3CP-7RIGIDNoneNoneRIGIDTypical19FP3-R3SF1-8FF6RIGIDNoneNoneRIGIDTypical20FP4-R1SA-1DCP-4RIGIDNoneNoneRIGIDTypical21FP4-R2R4CP-8RIGIDNoneNoneRIGIDTypical22FP4-R3SF2-8FF7RIGIDNoneNoneRIGIDTypical23M50X72BSA-1BRIGIDNoneNoneRIGIDTypical24MP-1MP-1AMP-1BMount PipesNoneNoneA53 Gr.BTypical25MP-2MP-2AMP-2BMount PipesNoneNoneA53 Gr.BTypical26MP-3MP-3AMP-3BMount PipesNoneNoneA53 Gr.BTypical27R1TC1-1SF1-1RIGIDNoneNoneRIGIDTypical28R2TC1-2SF1-5RIGIDNoneNoneRIGIDTypical29R3TC1-1SF2-1RIGIDNoneNoneRIGIDTypical30R4TC1-2SF2-5RIGIDNoneNoneRIGIDTypical31SA-1SA-1BSA-2AStabilizer ArmNoneNoneA572 Gr....Typical32SF1-BHX72X73Support HorizontalNoneNoneA500 Gr. ...Typical33SF1-D1SF1-D1ASF1-D1BSupport BracingNoneNoneA572 Gr....Typical34SF1-D2N71N69Support BracingNoneNoneA572 Gr....Typical35SF1-R1X72ASF1-1RIGIDNoneNoneRIGIDTypical36SF1-R2X72SF1-5RIGIDNoneNoneRIGIDTypicalRISA-3D Version 17.0.4 Page 3 [C:\...\...\...\...\RISA-3D\Sabre C10837002 THD V-Boom.r3d] Company : Tower Engineering Professionals, Inc.July 12, 202110:22 AMDesigner : APBJob Number : TEP No. 62749.566934Checked By: DCModel Name : Midway Road (FL10049-A)Member Primary Data (Continued)Label I Joint J Joint K Joint Rotate(de... Section/ShapeType Design List Material Design Rules37SF1-R3X73ASF1-4RIGIDNoneNoneRIGIDTypical38SF1-R4X73SF1-8RIGIDNoneNoneRIGIDTypical39SF1-THX72AX73ASupport HorizontalNoneNoneA500 Gr. ...Typical40SF1-V1SF1-V1ASF1-V1BSupport BracingNoneNoneA572 Gr....Typical41SF1-V2SF1-V2ASF1-V2BSupport BracingNoneNoneA572 Gr....Typical42SF2-BHX76X77Support HorizontalNoneNoneA500 Gr. ...Typical43SF2-D1SF2-D1ASF2-D1BSupport BracingNoneNoneA572 Gr....Typical44SF2-D2N72N70Support BracingNoneNoneA572 Gr....Typical45SF2-R1X74SF2-1RIGIDNoneNoneRIGIDTypical46SF2-R2X76SF2-5RIGIDNoneNoneRIGIDTypical47SF2-R3X75SF2-4RIGIDNoneNoneRIGIDTypical48SF2-R4X77SF2-8RIGIDNoneNoneRIGIDTypical49SF2-THX74X75Support HorizontalNoneNoneA500 Gr. ...Typical50SF2-V1SF2-V1ASF2-V1BSupport BracingNoneNoneA572 Gr....Typical51SF2-V2SF2-V2ASF2-V2BSupport BracingNoneNoneA572 Gr....TypicalMember Advanced DataLabel I Release J Release I Offset[in] J Offset[in] T/C Only Physical Defl Rat...Analysis ... Inactive Seismic...1FF1-BH1Yes** NA **None2FF1-BH2Yes** NA **None3FF1-BH3Yes** NA **None4FF1-TH1Yes** NA **None5FF1-TH2Yes** NA **None6FF1-TH3Yes** NA **None7FP-1Yes** NA **None8FP-2Yes** NA **None9FP-3Yes** NA **None10FP-4Yes** NA **None11FP1-R1Yes** NA **None12FP1-R2Yes** NA **None13FP1-R3Yes** NA **None14FP2-R1Yes** NA **None15FP2-R2Yes** NA **None16FP2-R3Yes** NA **None17FP3-R1Yes** NA **None18FP3-R2Yes** NA **None19FP3-R3Yes** NA **None20FP4-R1Yes** NA **None21FP4-R2Yes** NA **None22FP4-R3Yes** NA **None23M50Yes** NA **None24MP-1Yes** NA **None25MP-2Yes** NA **None26MP-3Yes** NA **None27R1Yes** NA **None28R2Yes** NA **None29R3Yes** NA **None30R4Yes** NA **None31SA-1BenPINYes** NA **None32SF1-BHBenPINYes** NA **None33SF1-D1Yes** NA **None34SF1-D2Yes** NA **None35SF1-R1Yes** NA **None36SF1-R2Yes** NA **None37SF1-R3Yes** NA **NoneRISA-3D Version 17.0.4 Page 4 [C:\...\...\...\...\RISA-3D\Sabre C10837002 THD V-Boom.r3d]
Company : Tower Engineering Professionals, Inc.July 12, 202110:22 AMDesigner : APBJob Number : TEP No. 62749.566934Checked By: DCModel Name : Midway Road (FL10049-A)Member Advanced Data (Continued)Label I Release J Release I Offset[in] J Offset[in] T/C Only Physical Defl Rat...Analysis ... Inactive Seismic...38SF1-R4Yes** NA **None39SF1-THBenPINYes** NA **None40SF1-V1Yes** NA **None41SF1-V2Yes** NA **None42SF2-BHBenPINYes** NA **None43SF2-D1Yes** NA **None44SF2-D2Yes** NA **None45SF2-R1Yes** NA **None46SF2-R2Yes** NA **None47SF2-R3Yes** NA **None48SF2-R4Yes** NA **None49SF2-THBenPINYes** NA **None50SF2-V1Yes** NA **None51SF2-V2Yes** NA **NoneHot Rolled Steel Design ParametersLabel Shape Length[... Lbyy[ft] Lbzz[ft] Lcomp top...Lcomp bot...L-torq... Kyy Kzz Cb Funct...1FF1-BH1Face Horizontal1.52.12.1Lateral2FF1-BH2Face Horizontal811Lateral3FF1-BH3Face Horizontal1.52.12.1Lateral4FF1-TH1Face Horizontal1.52.12.1Lateral5FF1-TH2Face Horizontal811Lateral6FF1-TH3Face Horizontal1.52.12.1Lateral7FP-1Face Plate.323.001.001.65.65Lateral8FP-2Face Plate.323.001.001.65.65Lateral9FP-3Face Plate.323.001.001.65.65Lateral10FP-4Face Plate.323.001.001.65.65Lateral11MP-1Mount Pipes8SegmentSegment2.12.1Lateral12MP-2Mount Pipes8SegmentSegment2.12.1Lateral13MP-3Mount Pipes8SegmentSegment2.12.1Lateral14SA-1Stabilizer Arm6.52511Lateral15SF1-BHSupport Horizontal4.2553.30611Lateral16SF1-D1Support Bracing4.2812.142.14.65.65Lateral17SF1-D2Support Bracing4.2812.142.14.65.65Lateral18SF1-THSupport Horizontal4.2553.30611Lateral19SF1-V1Support Bracing2.719.65.65Lateral20SF1-V2Support Bracing2.719.65.65Lateral21SF2-BHSupport Horizontal4.2553.30611Lateral22SF2-D1Support Bracing4.2812.142.14.65.65Lateral23SF2-D2Support Bracing4.2812.142.14.65.65Lateral24SF2-THSupport Horizontal4.2553.30611Lateral25SF2-V1Support Bracing2.719.65.65Lateral26SF2-V2Support Bracing2.719.65.65LateralCold Formed Steel Design ParametersLabel Shape Lengt... Lbyy[ft] Lbzz[ft] Lcomp to...Lcomp b... Kyy Kzz Cm-yyCm-zz Cb R y swayz swayNo Data to Print ...Basic Load CasesBLC Description Category X Gravity Y Gravity Z Gravity Joint Point Distributed Area(Me... Surface(P...1DeadNone-1520 Wind - No IceNone526RISA-3D Version 17.0.4 Page 5 [C:\...\...\...\...\RISA-3D\Sabre C10837002 THD V-Boom.r3d] Company : Tower Engineering Professionals, Inc.July 12, 202110:22 AMDesigner : APBJob Number : TEP No. 62749.566934Checked By: DCModel Name : Midway Road (FL10049-A)Basic Load Cases (Continued)BLC Description Category X Gravity Y Gravity Z Gravity Joint Point Distributed Area(Me... Surface(P...330 Wind - No IceNone1052445 Wind - No IceNone1052560 Wind - No IceNone1052690 Wind - No IceNone5267120 Wind - No IceNone10528135 Wind - No IceNone10529150 Wind - No IceNone105210180 Wind - No IceNone52611210 Wind - No IceNone105212225 Wind - No IceNone105213240 Wind - No IceNone105214270 Wind - No IceNone52615300 Wind - No IceNone105216315 Wind - No IceNone105217330 Wind - No IceNone105218Ice WeightNone526190 Wind - IceNone5262030 Wind - IceNone10522145 Wind - IceNone10522260 Wind - IceNone10522390 Wind - IceNone52624120 Wind - IceNone105225135 Wind - IceNone105226150 Wind - IceNone105227180 Wind - IceNone52628210 Wind - IceNone105229225 Wind - IceNone105230240 Wind - IceNone105231270 Wind - IceNone52632300 Wind - IceNone105233315 Wind - IceNone105234330 Wind - IceNone105235LmNone136LvNone137Seismic Load XELX-1538Seismic Load ZELZ-15Load CombinationsDescription So...P... S... BLCFac...BLCFac...BLCFac...BLCFac...BLCFac...BLCFac...BLCFac...BLCFac...BLCFac...BLCFac...11.4DYesY11.420.9D+1.0 0-WindYesY1.92130.9D+1.0 30-WindYesY1.93140.9D+1.0 45-WindYesY1.94150.9D+1.0 60-WindYesY1.95160.9D+1.0 90-WindYesY1.96170.9D+1.0 120-WindYesY1.97180.9D+1.0 135-WindYesY1.98190.9D+1.0 150-WindYesY1.991100.9D+1.0 180-WindYesY1.9101110.9D+1.0 210-WindYesY1.9111120.9D+1.0 225-WindYesY1.9121130.9D+1.0 240-WindYesY1.9131140.9D+1.0 270-WindYesY1.9141150.9D+1.0 300-WindYesY1.9151160.9D+1.0 315-WindYesY1.9161RISA-3D Version 17.0.4 Page 6 [C:\...\...\...\...\RISA-3D\Sabre C10837002 THD V-Boom.r3d]
Company : Tower Engineering Professionals, Inc.July 12, 202110:22 AMDesigner : APBJob Number : TEP No. 62749.566934Checked By: DCModel Name : Midway Road (FL10049-A)Load Combinations (Continued)Description So...P... S... BLCFac...BLCFac...BLCFac...BLCFac...BLCFac...BLCFac...BLCFac...BLCFac...BLCFac...BLCFac...170.9D+1.0 330-WindYesY1.9171181.2D+1.0 0-WindYesY11.221191.2D+1.0 30-WindYesY11.231201.2D+1.0 45-WindYesY11.241211.2D+1.0 60-WindYesY11.251221.2D+1.0 90-WindYesY11.261231.2D+1.0 120-WindYesY11.271241.2D+1.0 135-WindYesY11.281251.2D+1.0 150-WindYesY11.291261.2D+1.0 180-WindYesY11.2101271.2D+1.0 210-WindYesY11.2111281.2D+1.0 225-WindYesY11.2121291.2D+1.0 240-WindYesY11.2131301.2D+1.0 270-WindYesY11.2141311.2D+1.0 300-WindYesY11.2151321.2D+1.0 315-WindYesY11.2161331.2D+1.0 330-WindYesY11.2171341.2D+1.0Di+1.0 0-Win...Y11.2181191351.2D+1.0Di+1.0 30-Wi...Y11.2181201361.2D+1.0Di+1.0 45-Wi...Y11.2181211371.2D+1.0Di+1.0 60-Wi...Y11.2181221381.2D+1.0Di+1.0 90-Wi...Y11.2181231391.2D+1.0Di+1.0 120-...Y11.2181241401.2D+1.0Di+1.0 135-...Y11.2181251411.2D+1.0Di+1.0 150-...Y11.2181261421.2D+1.0Di+1.0 180-...Y11.2181271431.2D+1.0Di+1.0 210-...Y11.2181281441.2D+1.0Di+1.0 225-...Y11.2181291451.2D+1.0Di+1.0 240-...Y11.2181301461.2D+1.0Di+1.0 270-...Y11.2181311471.2D+1.0Di+1.0 300-...Y11.2181321481.2D+1.0Di+1.0 315-...Y11.2181331491.2D+1.0Di+1.0 330-...Y11.2181341501.2D+1.5LvYesY361.511.2511.2D+1.5Lm+1.0 0-Wi...YesY11.22.035351.5521.2D+1.5Lm+1.0 30-...YesY11.23.035351.5531.2D+1.5Lm+1.0 45-...YesY11.24.035351.5541.2D+1.5Lm+1.0 60-...YesY11.25.035351.5551.2D+1.5Lm+1.0 90-...YesY11.26.035351.5561.2D+1.5Lm+1.0 120-...YesY11.27.035351.5571.2D+1.5Lm+1.0 135-...YesY11.28.035351.5581.2D+1.5Lm+1.0 150-...YesY11.29.035351.5591.2D+1.5Lm+1.0 180-...YesY11.210.035351.5601.2D+1.5Lm+1.0 210-...YesY11.211.035351.5611.2D+1.5Lm+1.0 225-...YesY11.212.035351.5621.2D+1.5Lm+1.0 240-...YesY11.213.035351.5631.2D+1.5Lm+1.0 270-...YesY11.214.035351.5641.2D+1.5Lm+1.0 300-...YesY11.215.035351.5651.2D+1.5Lm+1.0 315-...YesY11.216.035351.5661.2D+1.5Lm+1.0 330-...YesY11.217.035351.567(1.2+0.2Sds)D+1.0 0 ...YesY11.2...ELX.034068(1.2+0.2Sds)D+1.0 30...YesY11.2...ELX.029ELZ.01769(1.2+0.2Sds)D+1.0 45...YesY11.2...ELX.024ELZ.02470(1.2+0.2Sds)D+1.0 60...YesY11.2...ELX.017ELZ.02971(1.2+0.2Sds)D+1.0 90...YesY11.2...0ELZ.03472(1.2+0.2Sds)D+1.0 12...YesY11.2...ELX-.017ELZ.02973(1.2+0.2Sds)D+1.0 13...YesY11.2...ELX-.024ELZ.024RISA-3D Version 17.0.4 Page 7 [C:\...\...\...\...\RISA-3D\Sabre C10837002 THD V-Boom.r3d] Company : Tower Engineering Professionals, Inc.July 12, 202110:22 AMDesigner : APBJob Number : TEP No. 62749.566934Checked By: DCModel Name : Midway Road (FL10049-A)Load Combinations (Continued)Description So...P... S... BLCFac...BLCFac...BLCFac...BLCFac...BLCFac...BLCFac...BLCFac...BLCFac...BLCFac...BLCFac...74(1.2+0.2Sds)D+1.0 15...YesY11.2...ELX-.029ELZ.01775(1.2+0.2Sds)D+1.0 18...YesY11.2...ELX-.034076(1.2+0.2Sds)D+1.0 21...YesY11.2...ELX-.029ELZ-.01777(1.2+0.2Sds)D+1.0 22...YesY11.2...ELX-.024ELZ-.02478(1.2+0.2Sds)D+1.0 24...YesY11.2...ELX-.017ELZ-.02979(1.2+0.2Sds)D+1.0 27...YesY11.2...0ELZ-.03480(1.2+0.2Sds)D+1.0 30...YesY11.2...ELX.017ELZ-.02981(1.2+0.2Sds)D+1.0 31...YesY11.2...ELX.024ELZ-.02482(1.2+0.2Sds)D+1.0 33...YesY11.2...ELX.029ELZ-.01783(0.9-0.2Sds)*DL+1.0 ...YesY1.887ELX.034084(0.9-0.2Sds)*DL+1.0 ...YesY1.887ELX.029ELZ.01785(0.9-0.2Sds)*DL+1.0 ...YesY1.887ELX.024ELZ.02486(0.9-0.2Sds)*DL+1.0 ...YesY1.887ELX.017ELZ.02987(0.9-0.2Sds)*DL+1.0 ...YesY1.8870ELZ.03488(0.9-0.2Sds)*DL+1.0 ...YesY1.887ELX-.017ELZ.02989(0.9-0.2Sds)*DL+1.0 ...YesY1.887ELX-.024ELZ.02490(0.9-0.2Sds)*DL+1.0 ...YesY1.887ELX-.029ELZ.01791(0.9-0.2Sds)*DL+1.0 ...YesY1.887ELX-.034092(0.9-0.2Sds)*DL+1.0 ...YesY1.887ELX-.029ELZ-.01793(0.9-0.2Sds)*DL+1.0 ...YesY1.887ELX-.024ELZ-.02494(0.9-0.2Sds)*DL+1.0 ...YesY1.887ELX-.017ELZ-.02995(0.9-0.2Sds)*DL+1.0 ...YesY1.8870ELZ-.03496(0.9-0.2Sds)*DL+1.0 ...YesY1.887ELX.017ELZ-.02997(0.9-0.2Sds)*DL+1.0 ...YesY1.887ELX.024ELZ-.02498(0.9-0.2Sds)*DL+1.0 ...YesY1.887ELX.029ELZ-.017Joint Loads and Enforced Displacements (BLC 35 : Lm)Joint Label L,D,M Direction Magnitude[(k,k-ft), (in,rad), (k*s^2/ft...1X56LY-.5Joint Loads and Enforced Displacements (BLC 36 : Lv)Joint Label L,D,M Direction Magnitude[(k,k-ft), (in,rad), (k*s^2/ft...1FF5LY-.25Member Point Loads (BLC 1 : Dead)Member Label Direction Magnitude[k,k-ft] Location[ft,%]1MP-1Y-.0321.52MP-1Y-.07523MP-1Y-.06424SF2-THY-.02215MP-1Y-.0326.5Member Point Loads (BLC 2 : 0 Wind - No Ice)Member Label Direction Magnitude[k,k-ft] Location[ft,%]1MP-1X-.5171.52MP-1X-.09823MP-1X-.08624SF2-THX-.16715MP-1X-.5176.5Member Point Loads (BLC 3 : 30 Wind - No Ice)Member Label Direction Magnitude[k,k-ft] Location[ft,%]RISA-3D Version 17.0.4 Page 8 [C:\...\...\...\...\RISA-3D\Sabre C10837002 THD V-Boom.r3d]
Company : Tower Engineering Professionals, Inc.July 12, 202110:22 AMDesigner : APBJob Number : TEP No. 62749.566934Checked By: DCModel Name : Midway Road (FL10049-A)Member Point Loads (BLC 3 : 30 Wind - No Ice) (Continued)Member Label Direction Magnitude[k,k-ft] Location[ft,%]1MP-1X-.3891.52MP-1X-.09923MP-1X-.09124SF2-THX-.12915MP-1X-.3896.56MP-1Z-.2241.57MP-1Z-.05728MP-1Z-.05229SF2-THZ-.075110MP-1Z-.2246.5Member Point Loads (BLC 4 : 45 Wind - No Ice)Member Label Direction Magnitude[k,k-ft] Location[ft,%]1MP-1X-.2691.52MP-1X-.09223MP-1X-.08824SF2-THX-.09315MP-1X-.2696.56MP-1Z-.2691.57MP-1Z-.09228MP-1Z-.08829SF2-THZ-.093110MP-1Z-.2696.5Member Point Loads (BLC 5 : 60 Wind - No Ice)Member Label Direction Magnitude[k,k-ft] Location[ft,%]1MP-1X-.1561.52MP-1X-.07323MP-1X-.07224SF2-THX-.05715MP-1X-.1566.56MP-1Z-.271.57MP-1Z-.12728MP-1Z-.12429SF2-THZ-.099110MP-1Z-.276.5Member Point Loads (BLC 6 : 90 Wind - No Ice)Member Label Direction Magnitude[k,k-ft] Location[ft,%]1MP-1Z-.2431.52MP-1Z-.16323MP-1Z-.16324SF2-THZ-.09715MP-1Z-.2436.5Member Point Loads (BLC 7 : 120 Wind - No Ice)Member Label Direction Magnitude[k,k-ft] Location[ft,%]1MP-1X.1561.52MP-1X.07323MP-1X.07224SF2-THX.05715MP-1X.1566.56MP-1Z-.271.57MP-1Z-.12728MP-1Z-.1242RISA-3D Version 17.0.4 Page 9 [C:\...\...\...\...\RISA-3D\Sabre C10837002 THD V-Boom.r3d] Company : Tower Engineering Professionals, Inc.July 12, 202110:22 AMDesigner : APBJob Number : TEP No. 62749.566934Checked By: DCModel Name : Midway Road (FL10049-A)Member Point Loads (BLC 7 : 120 Wind - No Ice) (Continued)Member Label Direction Magnitude[k,k-ft] Location[ft,%]9SF2-THZ-.099110MP-1Z-.276.5Member Point Loads (BLC 8 : 135 Wind - No Ice)Member Label Direction Magnitude[k,k-ft] Location[ft,%]1MP-1X.2691.52MP-1X.09223MP-1X.08824SF2-THX.09315MP-1X.2696.56MP-1Z-.2691.57MP-1Z-.09228MP-1Z-.08829SF2-THZ-.093110MP-1Z-.2696.5Member Point Loads (BLC 9 : 150 Wind - No Ice)Member Label Direction Magnitude[k,k-ft] Location[ft,%]1MP-1X.3891.52MP-1X.09923MP-1X.09124SF2-THX.12915MP-1X.3896.56MP-1Z-.2241.57MP-1Z-.05728MP-1Z-.05229SF2-THZ-.075110MP-1Z-.2246.5Member Point Loads (BLC 10 : 180 Wind - No Ice)Member Label Direction Magnitude[k,k-ft] Location[ft,%]1MP-1X.5171.52MP-1X.09823MP-1X.08624SF2-THX.16715MP-1X.5176.5Member Point Loads (BLC 11 : 210 Wind - No Ice)Member Label Direction Magnitude[k,k-ft] Location[ft,%]1MP-1X.3891.52MP-1X.09923MP-1X.09124SF2-THX.12915MP-1X.3896.56MP-1Z.2241.57MP-1Z.05728MP-1Z.05229SF2-THZ.075110MP-1Z.2246.5Member Point Loads (BLC 12 : 225 Wind - No Ice)Member Label Direction Magnitude[k,k-ft] Location[ft,%]1MP-1X.2691.52MP-1X.0922RISA-3D Version 17.0.4 Page 10 [C:\...\...\...\...\RISA-3D\Sabre C10837002 THD V-Boom.r3d]
Company : Tower Engineering Professionals, Inc.July 12, 202110:22 AMDesigner : APBJob Number : TEP No. 62749.566934Checked By: DCModel Name : Midway Road (FL10049-A)Member Point Loads (BLC 12 : 225 Wind - No Ice) (Continued)Member Label Direction Magnitude[k,k-ft] Location[ft,%]3MP-1X.08824SF2-THX.09315MP-1X.2696.56MP-1Z.2691.57MP-1Z.09228MP-1Z.08829SF2-THZ.093110MP-1Z.2696.5Member Point Loads (BLC 13 : 240 Wind - No Ice)Member Label Direction Magnitude[k,k-ft] Location[ft,%]1MP-1X.1561.52MP-1X.07323MP-1X.07224SF2-THX.05715MP-1X.1566.56MP-1Z.271.57MP-1Z.12728MP-1Z.12429SF2-THZ.099110MP-1Z.276.5Member Point Loads (BLC 14 : 270 Wind - No Ice)Member Label Direction Magnitude[k,k-ft] Location[ft,%]1MP-1Z.2431.52MP-1Z.16323MP-1Z.16324SF2-THZ.09715MP-1Z.2436.5Member Point Loads (BLC 15 : 300 Wind - No Ice)Member Label Direction Magnitude[k,k-ft] Location[ft,%]1MP-1X-.1561.52MP-1X-.07323MP-1X-.07224SF2-THX-.05715MP-1X-.1566.56MP-1Z.271.57MP-1Z.12728MP-1Z.12429SF2-THZ.099110MP-1Z.276.5Member Point Loads (BLC 16 : 315 Wind - No Ice)Member Label Direction Magnitude[k,k-ft] Location[ft,%]1MP-1X-.2691.52MP-1X-.09223MP-1X-.08824SF2-THX-.09315MP-1X-.2696.56MP-1Z.2691.57MP-1Z.09228MP-1Z.08829SF2-THZ.093110MP-1Z.2696.5RISA-3D Version 17.0.4 Page 11 [C:\...\...\...\...\RISA-3D\Sabre C10837002 THD V-Boom.r3d] Company : Tower Engineering Professionals, Inc.July 12, 202110:22 AMDesigner : APBJob Number : TEP No. 62749.566934Checked By: DCModel Name : Midway Road (FL10049-A)Member Point Loads (BLC 17 : 330 Wind - No Ice)Member Label Direction Magnitude[k,k-ft] Location[ft,%]1MP-1X-.3891.52MP-1X-.09923MP-1X-.09124SF2-THX-.12915MP-1X-.3896.56MP-1Z.2241.57MP-1Z.05728MP-1Z.05229SF2-THZ.075110MP-1Z.2246.5Member Point Loads (BLC 18 : Ice Weight)Member Label Direction Magnitude[k,k-ft] Location[ft,%]1MP-1Y01.52MP-1Y023MP-1Y024SF2-THY015MP-1Y06.5Member Point Loads (BLC 19 : 0 Wind - Ice)Member Label Direction Magnitude[k,k-ft] Location[ft,%]1MP-1X-.0181.52MP-1X-.00623MP-1X-.00624SF2-THX-.00615MP-1X-.0186.5Member Point Loads (BLC 20 : 30 Wind - Ice)Member Label Direction Magnitude[k,k-ft] Location[ft,%]1MP-1X-.0141.52MP-1X-.00323MP-1X-.00324SF2-THX-.00515MP-1X-.0146.56MP-1Z-.0081.57MP-1Z-.00228MP-1Z-.00229SF2-THZ-.003110MP-1Z-.0086.5Member Point Loads (BLC 21 : 45 Wind - Ice)Member Label Direction Magnitude[k,k-ft] Location[ft,%]1MP-1X-.0091.52MP-1X-.00323MP-1X-.00324SF2-THX-.00315MP-1X-.0096.56MP-1Z-.0091.57MP-1Z-.00328MP-1Z-.00329SF2-THZ-.003110MP-1Z-.0096.5Member Point Loads (BLC 22 : 60 Wind - Ice)Member Label Direction Magnitude[k,k-ft] Location[ft,%]RISA-3D Version 17.0.4 Page 12 [C:\...\...\...\...\RISA-3D\Sabre C10837002 THD V-Boom.r3d]
Company : Tower Engineering Professionals, Inc.July 12, 202110:22 AMDesigner : APBJob Number : TEP No. 62749.566934Checked By: DCModel Name : Midway Road (FL10049-A)Member Point Loads (BLC 22 : 60 Wind - Ice) (Continued)Member Label Direction Magnitude[k,k-ft] Location[ft,%]1MP-1X-.0051.52MP-1X-.00323MP-1X-.00324SF2-THX-.00215MP-1X-.0056.56MP-1Z-.0091.57MP-1Z-.00428MP-1Z-.00429SF2-THZ-.003110MP-1Z-.0096.5Member Point Loads (BLC 23 : 90 Wind - Ice)Member Label Direction Magnitude[k,k-ft] Location[ft,%]1MP-1Z-.0091.52MP-1Z-.00323MP-1Z-.00324SF2-THZ-.00315MP-1Z-.0096.5Member Point Loads (BLC 24 : 120 Wind - Ice)Member Label Direction Magnitude[k,k-ft] Location[ft,%]1MP-1X.0051.52MP-1X.00323MP-1X.00324SF2-THX.00215MP-1X.0056.56MP-1Z-.0091.57MP-1Z-.00428MP-1Z-.00429SF2-THZ-.003110MP-1Z-.0096.5Member Point Loads (BLC 25 : 135 Wind - Ice)Member Label Direction Magnitude[k,k-ft] Location[ft,%]1MP-1X.0091.52MP-1X.00323MP-1X.00324SF2-THX.00315MP-1X.0096.56MP-1Z-.0091.57MP-1Z-.00328MP-1Z-.00329SF2-THZ-.003110MP-1Z-.0096.5Member Point Loads (BLC 26 : 150 Wind - Ice)Member Label Direction Magnitude[k,k-ft] Location[ft,%]1MP-1X.0141.52MP-1X.00323MP-1X.00324SF2-THX.00515MP-1X.0146.56MP-1Z-.0081.57MP-1Z-.00228MP-1Z-.0022RISA-3D Version 17.0.4 Page 13 [C:\...\...\...\...\RISA-3D\Sabre C10837002 THD V-Boom.r3d] Company : Tower Engineering Professionals, Inc.July 12, 202110:22 AMDesigner : APBJob Number : TEP No. 62749.566934Checked By: DCModel Name : Midway Road (FL10049-A)Member Point Loads (BLC 26 : 150 Wind - Ice) (Continued)Member Label Direction Magnitude[k,k-ft] Location[ft,%]9SF2-THZ-.003110MP-1Z-.0086.5Member Point Loads (BLC 27 : 180 Wind - Ice)Member Label Direction Magnitude[k,k-ft] Location[ft,%]1MP-1X.0181.52MP-1X.00623MP-1X.00624SF2-THX.00615MP-1X.0186.5Member Point Loads (BLC 28 : 210 Wind - Ice)Member Label Direction Magnitude[k,k-ft] Location[ft,%]1MP-1X.0141.52MP-1X.00323MP-1X.00324SF2-THX.00515MP-1X.0146.56MP-1Z.0081.57MP-1Z.00228MP-1Z.00229SF2-THZ.003110MP-1Z.0086.5Member Point Loads (BLC 29 : 225 Wind - Ice)Member Label Direction Magnitude[k,k-ft] Location[ft,%]1MP-1X.0091.52MP-1X.00323MP-1X.00324SF2-THX.00315MP-1X.0096.56MP-1Z.0091.57MP-1Z.00328MP-1Z.00329SF2-THZ.003110MP-1Z.0096.5Member Point Loads (BLC 30 : 240 Wind - Ice)Member Label Direction Magnitude[k,k-ft] Location[ft,%]1MP-1X.0051.52MP-1X.00323MP-1X.00324SF2-THX.00215MP-1X.0056.56MP-1Z.0091.57MP-1Z.00428MP-1Z.00429SF2-THZ.003110MP-1Z.0096.5Member Point Loads (BLC 31 : 270 Wind - Ice)Member Label Direction Magnitude[k,k-ft] Location[ft,%]1MP-1Z.0091.52MP-1Z.0032RISA-3D Version 17.0.4 Page 14 [C:\...\...\...\...\RISA-3D\Sabre C10837002 THD V-Boom.r3d]
Company : Tower Engineering Professionals, Inc.July 12, 202110:22 AMDesigner : APBJob Number : TEP No. 62749.566934Checked By: DCModel Name : Midway Road (FL10049-A)Member Point Loads (BLC 31 : 270 Wind - Ice) (Continued)Member Label Direction Magnitude[k,k-ft] Location[ft,%]3MP-1Z.00324SF2-THZ.00315MP-1Z.0096.5Member Point Loads (BLC 32 : 300 Wind - Ice)Member Label Direction Magnitude[k,k-ft] Location[ft,%]1MP-1X-.0051.52MP-1X-.00323MP-1X-.00324SF2-THX-.00215MP-1X-.0056.56MP-1Z.0091.57MP-1Z.00428MP-1Z.00429SF2-THZ.003110MP-1Z.0096.5Member Point Loads (BLC 33 : 315 Wind - Ice)Member Label Direction Magnitude[k,k-ft] Location[ft,%]1MP-1X-.0091.52MP-1X-.00323MP-1X-.00324SF2-THX-.00315MP-1X-.0096.56MP-1Z.0091.57MP-1Z.00328MP-1Z.00329SF2-THZ.003110MP-1Z.0096.5Member Point Loads (BLC 34 : 330 Wind - Ice)Member Label Direction Magnitude[k,k-ft] Location[ft,%]1MP-1X-.0141.52MP-1X-.00323MP-1X-.00324SF2-THX-.00515MP-1X-.0146.56MP-1Z.0081.57MP-1Z.00228MP-1Z.00229SF2-THZ.003110MP-1Z.0086.5Member Point Loads (BLC 37 : Seismic Load X)Member Label Direction Magnitude[k,k-ft] Location[ft,%]1MP-1X-.0321.52MP-1X-.07523MP-1X-.06424SF2-THX-.02215MP-1X-.0326.5Member Point Loads (BLC 38 : Seismic Load Z)Member Label Direction Magnitude[k,k-ft] Location[ft,%]1MP-1Z-.0321.5RISA-3D Version 17.0.4 Page 15 [C:\...\...\...\...\RISA-3D\Sabre C10837002 THD V-Boom.r3d] Company : Tower Engineering Professionals, Inc.July 12, 202110:22 AMDesigner : APBJob Number : TEP No. 62749.566934Checked By: DCModel Name : Midway Road (FL10049-A)Member Point Loads (BLC 38 : Seismic Load Z) (Continued)Member Label Direction Magnitude[k,k-ft] Location[ft,%]2MP-1Z-.07523MP-1Z-.06424SF2-THZ-.02215MP-1Z-.0326.5Member Distributed Loads (BLC 2 : 0 Wind - No Ice)Member Label Direction Start Magnitude[k/ft,... End Magnitude[k/ft,F,... Start Location[ft,%] End Location[ft,%]1FF1-BH1X-.016-.0160%1002FF1-BH2X-.016-.0160%1003FF1-BH3X-.016-.0160%1004FF1-TH1X-.016-.0160%1005FF1-TH2X-.016-.0160%1006FF1-TH3X-.016-.0160%1007FP-1X-.005-.0050%1008FP-2X-.005-.0050%1009FP-3X-.005-.0050%10010FP-4X-.005-.0050%10011MP-1X-.016-.0160%10012MP-2X-.016-.0160%10013MP-3X-.016-.0160%10014SA-1X-.016-.0160%10015SF1-BHX-.012-.0120%10016SF1-D1X-.006-.0060%10017SF1-D2X-.006-.0060%10018SF1-THX-.012-.0120%10019SF1-V1X-.006-.0060%10020SF1-V2X-.006-.0060%10021SF2-BHX-.012-.0120%10022SF2-D1X-.006-.0060%10023SF2-D2X-.006-.0060%10024SF2-THX-.012-.0120%10025SF2-V1X-.006-.0060%10026SF2-V2X-.006-.0060%100Member Distributed Loads (BLC 3 : 30 Wind - No Ice)Member Label Direction Start Magnitude[k/ft,... End Magnitude[k/ft,F,... Start Location[ft,%] End Location[ft,%]1FF1-BH1X-.012-.0120%1002FF1-BH2X-.012-.0120%1003FF1-BH3X-.012-.0120%1004FF1-TH1X-.012-.0120%1005FF1-TH2X-.012-.0120%1006FF1-TH3X-.012-.0120%1007FP-1X-.004-.0040%1008FP-2X-.004-.0040%1009FP-3X-.004-.0040%10010FP-4X-.004-.0040%10011MP-1X-.014-.0140%10012MP-2X-.014-.0140%10013MP-3X-.014-.0140%10014SA-1X-.014-.0140%10015SF1-BHX-.013-.0130%10016SF1-D1X-.005-.0050%10017SF1-D2X-.005-.0050%10018SF1-THX-.013-.0130%10019SF1-V1X-.005-.0050%100RISA-3D Version 17.0.4 Page 16 [C:\...\...\...\...\RISA-3D\Sabre C10837002 THD V-Boom.r3d]
Company : Tower Engineering Professionals, Inc.July 12, 202110:22 AMDesigner : APBJob Number : TEP No. 62749.566934Checked By: DCModel Name : Midway Road (FL10049-A)Member Distributed Loads (BLC 3 : 30 Wind - No Ice) (Continued)Member Label Direction Start Magnitude[k/ft,... End Magnitude[k/ft,F,... Start Location[ft,%] End Location[ft,%]20SF1-V2X-.005-.0050%10021SF2-BHX-.005-.0050%10022SF2-D1X-.005-.0050%10023SF2-D2X-.005-.0050%10024SF2-THX-.005-.0050%10025SF2-V1X-.005-.0050%10026SF2-V2X-.005-.0050%10027FF1-BH1Z-.007-.0070%10028FF1-BH2Z-.007-.0070%10029FF1-BH3Z-.007-.0070%10030FF1-TH1Z-.007-.0070%10031FF1-TH2Z-.007-.0070%10032FF1-TH3Z-.007-.0070%10033FP-1Z-.002-.0020%10034FP-2Z-.002-.0020%10035FP-3Z-.002-.0020%10036FP-4Z-.002-.0020%10037MP-1Z-.008-.0080%10038MP-2Z-.008-.0080%10039MP-3Z-.008-.0080%10040SA-1Z-.008-.0080%10041SF1-BHZ-.006-.0060%10042SF1-D1Z-.003-.0030%10043SF1-D2Z-.003-.0030%10044SF1-THZ-.006-.0060%10045SF1-V1Z-.003-.0030%10046SF1-V2Z-.003-.0030%10047SF2-BHZ-.003-.0030%10048SF2-D1Z-.003-.0030%10049SF2-D2Z-.003-.0030%10050SF2-THZ-.003-.0030%10051SF2-V1Z-.003-.0030%10052SF2-V2Z-.003-.0030%100Member Distributed Loads (BLC 4 : 45 Wind - No Ice)Member Label Direction Start Magnitude[k/ft,... End Magnitude[k/ft,F,... Start Location[ft,%] End Location[ft,%]1FF1-BH1X-.008-.0080%1002FF1-BH2X-.008-.0080%1003FF1-BH3X-.008-.0080%1004FF1-TH1X-.008-.0080%1005FF1-TH2X-.008-.0080%1006FF1-TH3X-.008-.0080%1007FP-1X-.002-.0020%1008FP-2X-.002-.0020%1009FP-3X-.002-.0020%10010FP-4X-.002-.0020%10011MP-1X-.012-.0120%10012MP-2X-.012-.0120%10013MP-3X-.012-.0120%10014SA-1X-.012-.0120%10015SF1-BHX-.01-.010%10016SF1-D1X-.004-.0040%10017SF1-D2X-.004-.0040%10018SF1-THX-.01-.010%10019SF1-V1X-.004-.0040%10020SF1-V2X-.004-.0040%100RISA-3D Version 17.0.4 Page 17 [C:\...\...\...\...\RISA-3D\Sabre C10837002 THD V-Boom.r3d] Company : Tower Engineering Professionals, Inc.July 12, 202110:22 AMDesigner : APBJob Number : TEP No. 62749.566934Checked By: DCModel Name : Midway Road (FL10049-A)Member Distributed Loads (BLC 4 : 45 Wind - No Ice) (Continued)Member Label Direction Start Magnitude[k/ft,... End Magnitude[k/ft,F,... Start Location[ft,%] End Location[ft,%]21SF2-BHX-.002-.0020%10022SF2-D1X-.004-.0040%10023SF2-D2X-.004-.0040%10024SF2-THX-.002-.0020%10025SF2-V1X-.004-.0040%10026SF2-V2X-.004-.0040%10027FF1-BH1Z-.008-.0080%10028FF1-BH2Z-.008-.0080%10029FF1-BH3Z-.008-.0080%10030FF1-TH1Z-.008-.0080%10031FF1-TH2Z-.008-.0080%10032FF1-TH3Z-.008-.0080%10033FP-1Z-.002-.0020%10034FP-2Z-.002-.0020%10035FP-3Z-.002-.0020%10036FP-4Z-.002-.0020%10037MP-1Z-.012-.0120%10038MP-2Z-.012-.0120%10039MP-3Z-.012-.0120%10040SA-1Z-.012-.0120%10041SF1-BHZ-.009-.0090%10042SF1-D1Z-.004-.0040%10043SF1-D2Z-.004-.0040%10044SF1-THZ-.009-.0090%10045SF1-V1Z-.004-.0040%10046SF1-V2Z-.004-.0040%10047SF2-BHZ-.002-.0020%10048SF2-D1Z-.004-.0040%10049SF2-D2Z-.004-.0040%10050SF2-THZ-.002-.0020%10051SF2-V1Z-.004-.0040%10052SF2-V2Z-.004-.0040%100Member Distributed Loads (BLC 5 : 60 Wind - No Ice)Member Label Direction Start Magnitude[k/ft,... End Magnitude[k/ft,F,... Start Location[ft,%] End Location[ft,%]1FF1-BH1X-.004-.0040%1002FF1-BH2X-.004-.0040%1003FF1-BH3X-.004-.0040%1004FF1-TH1X-.004-.0040%1005FF1-TH2X-.004-.0040%1006FF1-TH3X-.004-.0040%1007FP-1X-.001-.0010%1008FP-2X-.001-.0010%1009FP-3X-.001-.0010%10010FP-4X-.001-.0010%10011MP-1X-.008-.0080%10012MP-2X-.008-.0080%10013MP-3X-.008-.0080%10014SA-1X-.008-.0080%10015SF1-BHX-.007-.0070%10016SF1-D1X-.003-.0030%10017SF1-D2X-.003-.0030%10018SF1-THX-.007-.0070%10019SF1-V1X-.003-.0030%10020SF1-V2X-.003-.0030%10021SF2-BHX-.000675-.0006750%100RISA-3D Version 17.0.4 Page 18 [C:\...\...\...\...\RISA-3D\Sabre C10837002 THD V-Boom.r3d]
Company : Tower Engineering Professionals, Inc.July 12, 202110:22 AMDesigner : APBJob Number : TEP No. 62749.566934Checked By: DCModel Name : Midway Road (FL10049-A)Member Distributed Loads (BLC 5 : 60 Wind - No Ice) (Continued)Member Label Direction Start Magnitude[k/ft,... End Magnitude[k/ft,F,... Start Location[ft,%] End Location[ft,%]22SF2-D1X-.003-.0030%10023SF2-D2X-.003-.0030%10024SF2-THX-.000675-.0006750%10025SF2-V1X-.003-.0030%10026SF2-V2X-.003-.0030%10027FF1-BH1Z-.007-.0070%10028FF1-BH2Z-.007-.0070%10029FF1-BH3Z-.007-.0070%10030FF1-TH1Z-.007-.0070%10031FF1-TH2Z-.007-.0070%10032FF1-TH3Z-.007-.0070%10033FP-1Z-.002-.0020%10034FP-2Z-.002-.0020%10035FP-3Z-.002-.0020%10036FP-4Z-.002-.0020%10037MP-1Z-.014-.0140%10038MP-2Z-.014-.0140%10039MP-3Z-.014-.0140%10040SA-1Z-.014-.0140%10041SF1-BHZ-.01-.010%10042SF1-D1Z-.005-.0050%10043SF1-D2Z-.005-.0050%10044SF1-THZ-.01-.010%10045SF1-V1Z-.005-.0050%10046SF1-V2Z-.005-.0050%10047SF2-BHZ-.001-.0010%10048SF2-D1Z-.005-.0050%10049SF2-D2Z-.005-.0050%10050SF2-THZ-.001-.0010%10051SF2-V1Z-.005-.0050%10052SF2-V2Z-.005-.0050%100Member Distributed Loads (BLC 6 : 90 Wind - No Ice)Member Label Direction Start Magnitude[k/ft,... End Magnitude[k/ft,F,... Start Location[ft,%] End Location[ft,%]1FF1-BH1Z000%1002FF1-BH2Z000%1003FF1-BH3Z000%1004FF1-TH1Z000%1005FF1-TH2Z000%1006FF1-TH3Z000%1007FP-1Z000%1008FP-2Z000%1009FP-3Z000%10010FP-4Z000%10011MP-1Z-.016-.0160%10012MP-2Z-.016-.0160%10013MP-3Z-.016-.0160%10014SA-1Z-.016-.0160%10015SF1-BHZ-.007-.0070%10016SF1-D1Z-.006-.0060%10017SF1-D2Z-.006-.0060%10018SF1-THZ-.007-.0070%10019SF1-V1Z-.006-.0060%10020SF1-V2Z-.006-.0060%10021SF2-BHZ-.007-.0070%10022SF2-D1Z-.006-.0060%100RISA-3D Version 17.0.4 Page 19 [C:\...\...\...\...\RISA-3D\Sabre C10837002 THD V-Boom.r3d] Company : Tower Engineering Professionals, Inc.July 12, 202110:22 AMDesigner : APBJob Number : TEP No. 62749.566934Checked By: DCModel Name : Midway Road (FL10049-A)Member Distributed Loads (BLC 6 : 90 Wind - No Ice) (Continued)Member Label Direction Start Magnitude[k/ft,... End Magnitude[k/ft,F,... Start Location[ft,%] End Location[ft,%]23SF2-D2Z-.006-.0060%10024SF2-THZ-.007-.0070%10025SF2-V1Z-.006-.0060%10026SF2-V2Z-.006-.0060%100Member Distributed Loads (BLC 7 : 120 Wind - No Ice)Member Label Direction Start Magnitude[k/ft,... End Magnitude[k/ft,F,... Start Location[ft,%] End Location[ft,%]1FF1-BH1X.004.0040%1002FF1-BH2X.004.0040%1003FF1-BH3X.004.0040%1004FF1-TH1X.004.0040%1005FF1-TH2X.004.0040%1006FF1-TH3X.004.0040%1007FP-1X.001.0010%1008FP-2X.001.0010%1009FP-3X.001.0010%10010FP-4X.001.0010%10011MP-1X.008.0080%10012MP-2X.008.0080%10013MP-3X.008.0080%10014SA-1X.008.0080%10015SF1-BHX.000675.0006750%10016SF1-D1X.003.0030%10017SF1-D2X.003.0030%10018SF1-THX.000675.0006750%10019SF1-V1X.003.0030%10020SF1-V2X.003.0030%10021SF2-BHX.007.0070%10022SF2-D1X.003.0030%10023SF2-D2X.003.0030%10024SF2-THX.007.0070%10025SF2-V1X.003.0030%10026SF2-V2X.003.0030%10027FF1-BH1Z-.007-.0070%10028FF1-BH2Z-.007-.0070%10029FF1-BH3Z-.007-.0070%10030FF1-TH1Z-.007-.0070%10031FF1-TH2Z-.007-.0070%10032FF1-TH3Z-.007-.0070%10033FP-1Z-.002-.0020%10034FP-2Z-.002-.0020%10035FP-3Z-.002-.0020%10036FP-4Z-.002-.0020%10037MP-1Z-.014-.0140%10038MP-2Z-.014-.0140%10039MP-3Z-.014-.0140%10040SA-1Z-.014-.0140%10041SF1-BHZ-.001-.0010%10042SF1-D1Z-.005-.0050%10043SF1-D2Z-.005-.0050%10044SF1-THZ-.001-.0010%10045SF1-V1Z-.005-.0050%10046SF1-V2Z-.005-.0050%10047SF2-BHZ-.01-.010%10048SF2-D1Z-.005-.0050%10049SF2-D2Z-.005-.0050%100RISA-3D Version 17.0.4 Page 20 [C:\...\...\...\...\RISA-3D\Sabre C10837002 THD V-Boom.r3d]
Company : Tower Engineering Professionals, Inc.July 12, 202110:22 AMDesigner : APBJob Number : TEP No. 62749.566934Checked By: DCModel Name : Midway Road (FL10049-A)Member Distributed Loads (BLC 7 : 120 Wind - No Ice) (Continued)Member Label Direction Start Magnitude[k/ft,... End Magnitude[k/ft,F,... Start Location[ft,%] End Location[ft,%]50SF2-THZ-.01-.010%10051SF2-V1Z-.005-.0050%10052SF2-V2Z-.005-.0050%100Member Distributed Loads (BLC 8 : 135 Wind - No Ice)Member Label Direction Start Magnitude[k/ft,... End Magnitude[k/ft,F,... Start Location[ft,%] End Location[ft,%]1FF1-BH1X.008.0080%1002FF1-BH2X.008.0080%1003FF1-BH3X.008.0080%1004FF1-TH1X.008.0080%1005FF1-TH2X.008.0080%1006FF1-TH3X.008.0080%1007FP-1X.002.0020%1008FP-2X.002.0020%1009FP-3X.002.0020%10010FP-4X.002.0020%10011MP-1X.012.0120%10012MP-2X.012.0120%10013MP-3X.012.0120%10014SA-1X.012.0120%10015SF1-BHX.002.0020%10016SF1-D1X.004.0040%10017SF1-D2X.004.0040%10018SF1-THX.002.0020%10019SF1-V1X.004.0040%10020SF1-V2X.004.0040%10021SF2-BHX.01.010%10022SF2-D1X.004.0040%10023SF2-D2X.004.0040%10024SF2-THX.01.010%10025SF2-V1X.004.0040%10026SF2-V2X.004.0040%10027FF1-BH1Z-.008-.0080%10028FF1-BH2Z-.008-.0080%10029FF1-BH3Z-.008-.0080%10030FF1-TH1Z-.008-.0080%10031FF1-TH2Z-.008-.0080%10032FF1-TH3Z-.008-.0080%10033FP-1Z-.002-.0020%10034FP-2Z-.002-.0020%10035FP-3Z-.002-.0020%10036FP-4Z-.002-.0020%10037MP-1Z-.012-.0120%10038MP-2Z-.012-.0120%10039MP-3Z-.012-.0120%10040SA-1Z-.012-.0120%10041SF1-BHZ-.002-.0020%10042SF1-D1Z-.004-.0040%10043SF1-D2Z-.004-.0040%10044SF1-THZ-.002-.0020%10045SF1-V1Z-.004-.0040%10046SF1-V2Z-.004-.0040%10047SF2-BHZ-.009-.0090%10048SF2-D1Z-.004-.0040%10049SF2-D2Z-.004-.0040%10050SF2-THZ-.009-.0090%100RISA-3D Version 17.0.4 Page 21 [C:\...\...\...\...\RISA-3D\Sabre C10837002 THD V-Boom.r3d] Company : Tower Engineering Professionals, Inc.July 12, 202110:22 AMDesigner : APBJob Number : TEP No. 62749.566934Checked By: DCModel Name : Midway Road (FL10049-A)Member Distributed Loads (BLC 8 : 135 Wind - No Ice) (Continued)Member Label Direction Start Magnitude[k/ft,... End Magnitude[k/ft,F,... Start Location[ft,%] End Location[ft,%]51SF2-V1Z-.004-.0040%10052SF2-V2Z-.004-.0040%100Member Distributed Loads (BLC 9 : 150 Wind - No Ice)Member Label Direction Start Magnitude[k/ft,... End Magnitude[k/ft,F,... Start Location[ft,%] End Location[ft,%]1FF1-BH1X.012.0120%1002FF1-BH2X.012.0120%1003FF1-BH3X.012.0120%1004FF1-TH1X.012.0120%1005FF1-TH2X.012.0120%1006FF1-TH3X.012.0120%1007FP-1X.004.0040%1008FP-2X.004.0040%1009FP-3X.004.0040%10010FP-4X.004.0040%10011MP-1X.014.0140%10012MP-2X.014.0140%10013MP-3X.014.0140%10014SA-1X.014.0140%10015SF1-BHX.005.0050%10016SF1-D1X.005.0050%10017SF1-D2X.005.0050%10018SF1-THX.005.0050%10019SF1-V1X.005.0050%10020SF1-V2X.005.0050%10021SF2-BHX.013.0130%10022SF2-D1X.005.0050%10023SF2-D2X.005.0050%10024SF2-THX.013.0130%10025SF2-V1X.005.0050%10026SF2-V2X.005.0050%10027FF1-BH1Z-.007-.0070%10028FF1-BH2Z-.007-.0070%10029FF1-BH3Z-.007-.0070%10030FF1-TH1Z-.007-.0070%10031FF1-TH2Z-.007-.0070%10032FF1-TH3Z-.007-.0070%10033FP-1Z-.002-.0020%10034FP-2Z-.002-.0020%10035FP-3Z-.002-.0020%10036FP-4Z-.002-.0020%10037MP-1Z-.008-.0080%10038MP-2Z-.008-.0080%10039MP-3Z-.008-.0080%10040SA-1Z-.008-.0080%10041SF1-BHZ-.003-.0030%10042SF1-D1Z-.003-.0030%10043SF1-D2Z-.003-.0030%10044SF1-THZ-.003-.0030%10045SF1-V1Z-.003-.0030%10046SF1-V2Z-.003-.0030%10047SF2-BHZ-.006-.0060%10048SF2-D1Z-.003-.0030%10049SF2-D2Z-.003-.0030%10050SF2-THZ-.006-.0060%10051SF2-V1Z-.003-.0030%100RISA-3D Version 17.0.4 Page 22 [C:\...\...\...\...\RISA-3D\Sabre C10837002 THD V-Boom.r3d]
Company : Tower Engineering Professionals, Inc.July 12, 202110:22 AMDesigner : APBJob Number : TEP No. 62749.566934Checked By: DCModel Name : Midway Road (FL10049-A)Member Distributed Loads (BLC 9 : 150 Wind - No Ice) (Continued)Member Label Direction Start Magnitude[k/ft,... End Magnitude[k/ft,F,... Start Location[ft,%] End Location[ft,%]52SF2-V2Z-.003-.0030%100Member Distributed Loads (BLC 10 : 180 Wind - No Ice)Member Label Direction Start Magnitude[k/ft,... End Magnitude[k/ft,F,... Start Location[ft,%] End Location[ft,%]1FF1-BH1X.016.0160%1002FF1-BH2X.016.0160%1003FF1-BH3X.016.0160%1004FF1-TH1X.016.0160%1005FF1-TH2X.016.0160%1006FF1-TH3X.016.0160%1007FP-1X.005.0050%1008FP-2X.005.0050%1009FP-3X.005.0050%10010FP-4X.005.0050%10011MP-1X.016.0160%10012MP-2X.016.0160%10013MP-3X.016.0160%10014SA-1X.016.0160%10015SF1-BHX.012.0120%10016SF1-D1X.006.0060%10017SF1-D2X.006.0060%10018SF1-THX.012.0120%10019SF1-V1X.006.0060%10020SF1-V2X.006.0060%10021SF2-BHX.012.0120%10022SF2-D1X.006.0060%10023SF2-D2X.006.0060%10024SF2-THX.012.0120%10025SF2-V1X.006.0060%10026SF2-V2X.006.0060%100Member Distributed Loads (BLC 11 : 210 Wind - No Ice)Member Label Direction Start Magnitude[k/ft,... End Magnitude[k/ft,F,... Start Location[ft,%] End Location[ft,%]1FF1-BH1X.012.0120%1002FF1-BH2X.012.0120%1003FF1-BH3X.012.0120%1004FF1-TH1X.012.0120%1005FF1-TH2X.012.0120%1006FF1-TH3X.012.0120%1007FP-1X.004.0040%1008FP-2X.004.0040%1009FP-3X.004.0040%10010FP-4X.004.0040%10011MP-1X.014.0140%10012MP-2X.014.0140%10013MP-3X.014.0140%10014SA-1X.014.0140%10015SF1-BHX.013.0130%10016SF1-D1X.005.0050%10017SF1-D2X.005.0050%10018SF1-THX.013.0130%10019SF1-V1X.005.0050%10020SF1-V2X.005.0050%10021SF2-BHX.005.0050%10022SF2-D1X.005.0050%10023SF2-D2X.005.0050%100RISA-3D Version 17.0.4 Page 23 [C:\...\...\...\...\RISA-3D\Sabre C10837002 THD V-Boom.r3d] Company : Tower Engineering Professionals, Inc.July 12, 202110:22 AMDesigner : APBJob Number : TEP No. 62749.566934Checked By: DCModel Name : Midway Road (FL10049-A)Member Distributed Loads (BLC 11 : 210 Wind - No Ice) (Continued)Member Label Direction Start Magnitude[k/ft,... End Magnitude[k/ft,F,... Start Location[ft,%] End Location[ft,%]24SF2-THX.005.0050%10025SF2-V1X.005.0050%10026SF2-V2X.005.0050%10027FF1-BH1Z.007.0070%10028FF1-BH2Z.007.0070%10029FF1-BH3Z.007.0070%10030FF1-TH1Z.007.0070%10031FF1-TH2Z.007.0070%10032FF1-TH3Z.007.0070%10033FP-1Z.002.0020%10034FP-2Z.002.0020%10035FP-3Z.002.0020%10036FP-4Z.002.0020%10037MP-1Z.008.0080%10038MP-2Z.008.0080%10039MP-3Z.008.0080%10040SA-1Z.008.0080%10041SF1-BHZ.006.0060%10042SF1-D1Z.003.0030%10043SF1-D2Z.003.0030%10044SF1-THZ.006.0060%10045SF1-V1Z.003.0030%10046SF1-V2Z.003.0030%10047SF2-BHZ.003.0030%10048SF2-D1Z.003.0030%10049SF2-D2Z.003.0030%10050SF2-THZ.003.0030%10051SF2-V1Z.003.0030%10052SF2-V2Z.003.0030%100Member Distributed Loads (BLC 12 : 225 Wind - No Ice)Member Label Direction Start Magnitude[k/ft,... End Magnitude[k/ft,F,... Start Location[ft,%] End Location[ft,%]1FF1-BH1X.008.0080%1002FF1-BH2X.008.0080%1003FF1-BH3X.008.0080%1004FF1-TH1X.008.0080%1005FF1-TH2X.008.0080%1006FF1-TH3X.008.0080%1007FP-1X.002.0020%1008FP-2X.002.0020%1009FP-3X.002.0020%10010FP-4X.002.0020%10011MP-1X.012.0120%10012MP-2X.012.0120%10013MP-3X.012.0120%10014SA-1X.012.0120%10015SF1-BHX.01.010%10016SF1-D1X.004.0040%10017SF1-D2X.004.0040%10018SF1-THX.01.010%10019SF1-V1X.004.0040%10020SF1-V2X.004.0040%10021SF2-BHX.002.0020%10022SF2-D1X.004.0040%10023SF2-D2X.004.0040%10024SF2-THX.002.0020%100RISA-3D Version 17.0.4 Page 24 [C:\...\...\...\...\RISA-3D\Sabre C10837002 THD V-Boom.r3d]
Company : Tower Engineering Professionals, Inc.July 12, 202110:22 AMDesigner : APBJob Number : TEP No. 62749.566934Checked By: DCModel Name : Midway Road (FL10049-A)Member Distributed Loads (BLC 12 : 225 Wind - No Ice) (Continued)Member Label Direction Start Magnitude[k/ft,... End Magnitude[k/ft,F,... Start Location[ft,%] End Location[ft,%]25SF2-V1X.004.0040%10026SF2-V2X.004.0040%10027FF1-BH1Z.008.0080%10028FF1-BH2Z.008.0080%10029FF1-BH3Z.008.0080%10030FF1-TH1Z.008.0080%10031FF1-TH2Z.008.0080%10032FF1-TH3Z.008.0080%10033FP-1Z.002.0020%10034FP-2Z.002.0020%10035FP-3Z.002.0020%10036FP-4Z.002.0020%10037MP-1Z.012.0120%10038MP-2Z.012.0120%10039MP-3Z.012.0120%10040SA-1Z.012.0120%10041SF1-BHZ.009.0090%10042SF1-D1Z.004.0040%10043SF1-D2Z.004.0040%10044SF1-THZ.009.0090%10045SF1-V1Z.004.0040%10046SF1-V2Z.004.0040%10047SF2-BHZ.002.0020%10048SF2-D1Z.004.0040%10049SF2-D2Z.004.0040%10050SF2-THZ.002.0020%10051SF2-V1Z.004.0040%10052SF2-V2Z.004.0040%100Member Distributed Loads (BLC 13 : 240 Wind - No Ice)Member Label Direction Start Magnitude[k/ft,... End Magnitude[k/ft,F,... Start Location[ft,%] End Location[ft,%]1FF1-BH1X.004.0040%1002FF1-BH2X.004.0040%1003FF1-BH3X.004.0040%1004FF1-TH1X.004.0040%1005FF1-TH2X.004.0040%1006FF1-TH3X.004.0040%1007FP-1X.001.0010%1008FP-2X.001.0010%1009FP-3X.001.0010%10010FP-4X.001.0010%10011MP-1X.008.0080%10012MP-2X.008.0080%10013MP-3X.008.0080%10014SA-1X.008.0080%10015SF1-BHX.007.0070%10016SF1-D1X.003.0030%10017SF1-D2X.003.0030%10018SF1-THX.007.0070%10019SF1-V1X.003.0030%10020SF1-V2X.003.0030%10021SF2-BHX.000675.0006750%10022SF2-D1X.003.0030%10023SF2-D2X.003.0030%10024SF2-THX.000675.0006750%10025SF2-V1X.003.0030%100RISA-3D Version 17.0.4 Page 25 [C:\...\...\...\...\RISA-3D\Sabre C10837002 THD V-Boom.r3d] Company : Tower Engineering Professionals, Inc.July 12, 202110:22 AMDesigner : APBJob Number : TEP No. 62749.566934Checked By: DCModel Name : Midway Road (FL10049-A)Member Distributed Loads (BLC 13 : 240 Wind - No Ice) (Continued)Member Label Direction Start Magnitude[k/ft,... End Magnitude[k/ft,F,... Start Location[ft,%] End Location[ft,%]26SF2-V2X.003.0030%10027FF1-BH1Z.007.0070%10028FF1-BH2Z.007.0070%10029FF1-BH3Z.007.0070%10030FF1-TH1Z.007.0070%10031FF1-TH2Z.007.0070%10032FF1-TH3Z.007.0070%10033FP-1Z.002.0020%10034FP-2Z.002.0020%10035FP-3Z.002.0020%10036FP-4Z.002.0020%10037MP-1Z.014.0140%10038MP-2Z.014.0140%10039MP-3Z.014.0140%10040SA-1Z.014.0140%10041SF1-BHZ.01.010%10042SF1-D1Z.005.0050%10043SF1-D2Z.005.0050%10044SF1-THZ.01.010%10045SF1-V1Z.005.0050%10046SF1-V2Z.005.0050%10047SF2-BHZ.001.0010%10048SF2-D1Z.005.0050%10049SF2-D2Z.005.0050%10050SF2-THZ.001.0010%10051SF2-V1Z.005.0050%10052SF2-V2Z.005.0050%100Member Distributed Loads (BLC 14 : 270 Wind - No Ice)Member Label Direction Start Magnitude[k/ft,... End Magnitude[k/ft,F,... Start Location[ft,%] End Location[ft,%]1FF1-BH1Z000%1002FF1-BH2Z000%1003FF1-BH3Z000%1004FF1-TH1Z000%1005FF1-TH2Z000%1006FF1-TH3Z000%1007FP-1Z000%1008FP-2Z000%1009FP-3Z000%10010FP-4Z000%10011MP-1Z.016.0160%10012MP-2Z.016.0160%10013MP-3Z.016.0160%10014SA-1Z.016.0160%10015SF1-BHZ.007.0070%10016SF1-D1Z.006.0060%10017SF1-D2Z.006.0060%10018SF1-THZ.007.0070%10019SF1-V1Z.006.0060%10020SF1-V2Z.006.0060%10021SF2-BHZ.007.0070%10022SF2-D1Z.006.0060%10023SF2-D2Z.006.0060%10024SF2-THZ.007.0070%10025SF2-V1Z.006.0060%10026SF2-V2Z.006.0060%100RISA-3D Version 17.0.4 Page 26 [C:\...\...\...\...\RISA-3D\Sabre C10837002 THD V-Boom.r3d]
Company : Tower Engineering Professionals, Inc.July 12, 202110:22 AMDesigner : APBJob Number : TEP No. 62749.566934Checked By: DCModel Name : Midway Road (FL10049-A)Member Distributed Loads (BLC 15 : 300 Wind - No Ice)Member Label Direction Start Magnitude[k/ft,... End Magnitude[k/ft,F,... Start Location[ft,%] End Location[ft,%]1FF1-BH1X-.004-.0040%1002FF1-BH2X-.004-.0040%1003FF1-BH3X-.004-.0040%1004FF1-TH1X-.004-.0040%1005FF1-TH2X-.004-.0040%1006FF1-TH3X-.004-.0040%1007FP-1X-.001-.0010%1008FP-2X-.001-.0010%1009FP-3X-.001-.0010%10010FP-4X-.001-.0010%10011MP-1X-.008-.0080%10012MP-2X-.008-.0080%10013MP-3X-.008-.0080%10014SA-1X-.008-.0080%10015SF1-BHX-.000675-.0006750%10016SF1-D1X-.003-.0030%10017SF1-D2X-.003-.0030%10018SF1-THX-.000675-.0006750%10019SF1-V1X-.003-.0030%10020SF1-V2X-.003-.0030%10021SF2-BHX-.007-.0070%10022SF2-D1X-.003-.0030%10023SF2-D2X-.003-.0030%10024SF2-THX-.007-.0070%10025SF2-V1X-.003-.0030%10026SF2-V2X-.003-.0030%10027FF1-BH1Z.007.0070%10028FF1-BH2Z.007.0070%10029FF1-BH3Z.007.0070%10030FF1-TH1Z.007.0070%10031FF1-TH2Z.007.0070%10032FF1-TH3Z.007.0070%10033FP-1Z.002.0020%10034FP-2Z.002.0020%10035FP-3Z.002.0020%10036FP-4Z.002.0020%10037MP-1Z.014.0140%10038MP-2Z.014.0140%10039MP-3Z.014.0140%10040SA-1Z.014.0140%10041SF1-BHZ.001.0010%10042SF1-D1Z.005.0050%10043SF1-D2Z.005.0050%10044SF1-THZ.001.0010%10045SF1-V1Z.005.0050%10046SF1-V2Z.005.0050%10047SF2-BHZ.01.010%10048SF2-D1Z.005.0050%10049SF2-D2Z.005.0050%10050SF2-THZ.01.010%10051SF2-V1Z.005.0050%10052SF2-V2Z.005.0050%100Member Distributed Loads (BLC 16 : 315 Wind - No Ice)Member Label Direction Start Magnitude[k/ft,... End Magnitude[k/ft,F,... Start Location[ft,%] End Location[ft,%]1FF1-BH1X-.008-.0080%100RISA-3D Version 17.0.4 Page 27 [C:\...\...\...\...\RISA-3D\Sabre C10837002 THD V-Boom.r3d] Company : Tower Engineering Professionals, Inc.July 12, 202110:22 AMDesigner : APBJob Number : TEP No. 62749.566934Checked By: DCModel Name : Midway Road (FL10049-A)Member Distributed Loads (BLC 16 : 315 Wind - No Ice) (Continued)Member Label Direction Start Magnitude[k/ft,... End Magnitude[k/ft,F,... Start Location[ft,%] End Location[ft,%]2FF1-BH2X-.008-.0080%1003FF1-BH3X-.008-.0080%1004FF1-TH1X-.008-.0080%1005FF1-TH2X-.008-.0080%1006FF1-TH3X-.008-.0080%1007FP-1X-.002-.0020%1008FP-2X-.002-.0020%1009FP-3X-.002-.0020%10010FP-4X-.002-.0020%10011MP-1X-.012-.0120%10012MP-2X-.012-.0120%10013MP-3X-.012-.0120%10014SA-1X-.012-.0120%10015SF1-BHX-.002-.0020%10016SF1-D1X-.004-.0040%10017SF1-D2X-.004-.0040%10018SF1-THX-.002-.0020%10019SF1-V1X-.004-.0040%10020SF1-V2X-.004-.0040%10021SF2-BHX-.01-.010%10022SF2-D1X-.004-.0040%10023SF2-D2X-.004-.0040%10024SF2-THX-.01-.010%10025SF2-V1X-.004-.0040%10026SF2-V2X-.004-.0040%10027FF1-BH1Z.008.0080%10028FF1-BH2Z.008.0080%10029FF1-BH3Z.008.0080%10030FF1-TH1Z.008.0080%10031FF1-TH2Z.008.0080%10032FF1-TH3Z.008.0080%10033FP-1Z.002.0020%10034FP-2Z.002.0020%10035FP-3Z.002.0020%10036FP-4Z.002.0020%10037MP-1Z.012.0120%10038MP-2Z.012.0120%10039MP-3Z.012.0120%10040SA-1Z.012.0120%10041SF1-BHZ.002.0020%10042SF1-D1Z.004.0040%10043SF1-D2Z.004.0040%10044SF1-THZ.002.0020%10045SF1-V1Z.004.0040%10046SF1-V2Z.004.0040%10047SF2-BHZ.009.0090%10048SF2-D1Z.004.0040%10049SF2-D2Z.004.0040%10050SF2-THZ.009.0090%10051SF2-V1Z.004.0040%10052SF2-V2Z.004.0040%100Member Distributed Loads (BLC 17 : 330 Wind - No Ice)Member Label Direction Start Magnitude[k/ft,... End Magnitude[k/ft,F,... Start Location[ft,%] End Location[ft,%]1FF1-BH1X-.012-.0120%1002FF1-BH2X-.012-.0120%100RISA-3D Version 17.0.4 Page 28 [C:\...\...\...\...\RISA-3D\Sabre C10837002 THD V-Boom.r3d]
Company : Tower Engineering Professionals, Inc.July 12, 202110:22 AMDesigner : APBJob Number : TEP No. 62749.566934Checked By: DCModel Name : Midway Road (FL10049-A)Member Distributed Loads (BLC 17 : 330 Wind - No Ice) (Continued)Member Label Direction Start Magnitude[k/ft,... End Magnitude[k/ft,F,... Start Location[ft,%] End Location[ft,%]3FF1-BH3X-.012-.0120%1004FF1-TH1X-.012-.0120%1005FF1-TH2X-.012-.0120%1006FF1-TH3X-.012-.0120%1007FP-1X-.004-.0040%1008FP-2X-.004-.0040%1009FP-3X-.004-.0040%10010FP-4X-.004-.0040%10011MP-1X-.014-.0140%10012MP-2X-.014-.0140%10013MP-3X-.014-.0140%10014SA-1X-.014-.0140%10015SF1-BHX-.005-.0050%10016SF1-D1X-.005-.0050%10017SF1-D2X-.005-.0050%10018SF1-THX-.005-.0050%10019SF1-V1X-.005-.0050%10020SF1-V2X-.005-.0050%10021SF2-BHX-.013-.0130%10022SF2-D1X-.005-.0050%10023SF2-D2X-.005-.0050%10024SF2-THX-.013-.0130%10025SF2-V1X-.005-.0050%10026SF2-V2X-.005-.0050%10027FF1-BH1Z.007.0070%10028FF1-BH2Z.007.0070%10029FF1-BH3Z.007.0070%10030FF1-TH1Z.007.0070%10031FF1-TH2Z.007.0070%10032FF1-TH3Z.007.0070%10033FP-1Z.002.0020%10034FP-2Z.002.0020%10035FP-3Z.002.0020%10036FP-4Z.002.0020%10037MP-1Z.008.0080%10038MP-2Z.008.0080%10039MP-3Z.008.0080%10040SA-1Z.008.0080%10041SF1-BHZ.003.0030%10042SF1-D1Z.003.0030%10043SF1-D2Z.003.0030%10044SF1-THZ.003.0030%10045SF1-V1Z.003.0030%10046SF1-V2Z.003.0030%10047SF2-BHZ.006.0060%10048SF2-D1Z.003.0030%10049SF2-D2Z.003.0030%10050SF2-THZ.006.0060%10051SF2-V1Z.003.0030%10052SF2-V2Z.003.0030%100Member Distributed Loads (BLC 18 : Ice Weight)Member Label Direction Start Magnitude[k/ft,... End Magnitude[k/ft,F,... Start Location[ft,%] End Location[ft,%]1FF1-BH1Y000%1002FF1-BH2Y000%1003FF1-BH3Y000%100RISA-3D Version 17.0.4 Page 29 [C:\...\...\...\...\RISA-3D\Sabre C10837002 THD V-Boom.r3d] Company : Tower Engineering Professionals, Inc.July 12, 202110:22 AMDesigner : APBJob Number : TEP No. 62749.566934Checked By: DCModel Name : Midway Road (FL10049-A)Member Distributed Loads (BLC 18 : Ice Weight) (Continued)Member Label Direction Start Magnitude[k/ft,... End Magnitude[k/ft,F,... Start Location[ft,%] End Location[ft,%]4FF1-TH1Y000%1005FF1-TH2Y000%1006FF1-TH3Y000%1007FP-1Y000%1008FP-2Y000%1009FP-3Y000%10010FP-4Y000%10011MP-1Y000%10012MP-2Y000%10013MP-3Y000%10014SA-1Y000%10015SF1-BHY000%10016SF1-D1Y000%10017SF1-D2Y000%10018SF1-THY000%10019SF1-V1Y000%10020SF1-V2Y000%10021SF2-BHY000%10022SF2-D1Y000%10023SF2-D2Y000%10024SF2-THY000%10025SF2-V1Y000%10026SF2-V2Y000%100Member Distributed Loads (BLC 19 : 0 Wind - Ice)Member Label Direction Start Magnitude[k/ft,... End Magnitude[k/ft,F,... Start Location[ft,%] End Location[ft,%]1FF1-BH1X-.000692-.0006920%1002FF1-BH2X-.000692-.0006920%1003FF1-BH3X-.000692-.0006920%1004FF1-TH1X-.000692-.0006920%1005FF1-TH2X-.000692-.0006920%1006FF1-TH3X-.000692-.0006920%1007FP-1X-.000173-.0001730%1008FP-2X-.000173-.0001730%1009FP-3X-.000173-.0001730%10010FP-4X-.000173-.0001730%10011MP-1X-.000754-.0007540%10012MP-2X-.000754-.0007540%10013MP-3X-.000754-.0007540%10014SA-1X-.000623-.0006230%10015SF1-BHX-.000522-.0005220%10016SF1-D1X-.000197-.0001970%10017SF1-D2X-.000197-.0001970%10018SF1-THX-.000522-.0005220%10019SF1-V1X-.000197-.0001970%10020SF1-V2X-.000197-.0001970%10021SF2-BHX-.000522-.0005220%10022SF2-D1X-.000197-.0001970%10023SF2-D2X-.000197-.0001970%10024SF2-THX-.000522-.0005220%10025SF2-V1X-.000197-.0001970%10026SF2-V2X-.000197-.0001970%100Member Distributed Loads (BLC 20 : 30 Wind - Ice)Member Label Direction Start Magnitude[k/ft,... End Magnitude[k/ft,F,... Start Location[ft,%] End Location[ft,%]1FF1-BH1X-.000519-.0005190%100RISA-3D Version 17.0.4 Page 30 [C:\...\...\...\...\RISA-3D\Sabre C10837002 THD V-Boom.r3d]
Company : Tower Engineering Professionals, Inc.July 12, 202110:22 AMDesigner : APBJob Number : TEP No. 62749.566934Checked By: DCModel Name : Midway Road (FL10049-A)Member Distributed Loads (BLC 20 : 30 Wind - Ice) (Continued)Member Label Direction Start Magnitude[k/ft,... End Magnitude[k/ft,F,... Start Location[ft,%] End Location[ft,%]2FF1-BH2X-.000519-.0005190%1003FF1-BH3X-.000519-.0005190%1004FF1-TH1X-.000519-.0005190%1005FF1-TH2X-.000519-.0005190%1006FF1-TH3X-.000519-.0005190%1007FP-1X-.00013-.000130%1008FP-2X-.00013-.000130%1009FP-3X-.00013-.000130%10010FP-4X-.00013-.000130%10011MP-1X-.000653-.0006530%10012MP-2X-.000653-.0006530%10013MP-3X-.000653-.0006530%10014SA-1X-.000539-.0005390%10015SF1-BHX-.00045-.000450%10016SF1-D1X-.00017-.000170%10017SF1-D2X-.00017-.000170%10018SF1-THX-.00045-.000450%10019SF1-V1X-.00017-.000170%10020SF1-V2X-.00017-.000170%10021SF2-BHX-.00019-.000190%10022SF2-D1X-.00017-.000170%10023SF2-D2X-.00017-.000170%10024SF2-THX-.00019-.000190%10025SF2-V1X-.00017-.000170%10026SF2-V2X-.00017-.000170%10027FF1-BH1Z-.00027-.000270%10028FF1-BH2Z-.00027-.000270%10029FF1-BH3Z-.00027-.000270%10030FF1-TH1Z-.00027-.000270%10031FF1-TH2Z-.00027-.000270%10032FF1-TH3Z-.00027-.000270%10033FP-1Z-6.7e-5-6.7e-50%10034FP-2Z-6.7e-5-6.7e-50%10035FP-3Z-6.7e-5-6.7e-50%10036FP-4Z-6.7e-5-6.7e-50%10037MP-1Z-.000419-.0004190%10038MP-2Z-.000419-.0004190%10039MP-3Z-.000419-.0004190%10040SA-1Z-.000346-.0003460%10041SF1-BHZ-.000227-.0002270%10042SF1-D1Z-.000109-.0001090%10043SF1-D2Z-.000109-.0001090%10044SF1-THZ-.000227-.0002270%10045SF1-V1Z-.000109-.0001090%10046SF1-V2Z-.000109-.0001090%10047SF2-BHZ-9.6e-5-9.6e-50%10048SF2-D1Z-.000109-.0001090%10049SF2-D2Z-.000109-.0001090%10050SF2-THZ-9.6e-5-9.6e-50%10051SF2-V1Z-.000109-.0001090%10052SF2-V2Z-.000109-.0001090%100Member Distributed Loads (BLC 21 : 45 Wind - Ice)Member Label Direction Start Magnitude[k/ft,... End Magnitude[k/ft,F,... Start Location[ft,%] End Location[ft,%]1FF1-BH1X-.000346-.0003460%1002FF1-BH2X-.000346-.0003460%100RISA-3D Version 17.0.4 Page 31 [C:\...\...\...\...\RISA-3D\Sabre C10837002 THD V-Boom.r3d] Company : Tower Engineering Professionals, Inc.July 12, 202110:22 AMDesigner : APBJob Number : TEP No. 62749.566934Checked By: DCModel Name : Midway Road (FL10049-A)Member Distributed Loads (BLC 21 : 45 Wind - Ice) (Continued)Member Label Direction Start Magnitude[k/ft,... End Magnitude[k/ft,F,... Start Location[ft,%] End Location[ft,%]3FF1-BH3X-.000346-.0003460%1004FF1-TH1X-.000346-.0003460%1005FF1-TH2X-.000346-.0003460%1006FF1-TH3X-.000346-.0003460%1007FP-1X-8.6e-5-8.6e-50%1008FP-2X-8.6e-5-8.6e-50%1009FP-3X-8.6e-5-8.6e-50%10010FP-4X-8.6e-5-8.6e-50%10011MP-1X-.000533-.0005330%10012MP-2X-.000533-.0005330%10013MP-3X-.000533-.0005330%10014SA-1X-.00044-.000440%10015SF1-BHX-.000364-.0003640%10016SF1-D1X-.000139-.0001390%10017SF1-D2X-.000139-.0001390%10018SF1-THX-.000364-.0003640%10019SF1-V1X-.000139-.0001390%10020SF1-V2X-.000139-.0001390%10021SF2-BHX-6.3e-5-6.3e-50%10022SF2-D1X-.000139-.0001390%10023SF2-D2X-.000139-.0001390%10024SF2-THX-6.3e-5-6.3e-50%10025SF2-V1X-.000139-.0001390%10026SF2-V2X-.000139-.0001390%10027FF1-BH1Z-.000311-.0003110%10028FF1-BH2Z-.000311-.0003110%10029FF1-BH3Z-.000311-.0003110%10030FF1-TH1Z-.000311-.0003110%10031FF1-TH2Z-.000311-.0003110%10032FF1-TH3Z-.000311-.0003110%10033FP-1Z-7.8e-5-7.8e-50%10034FP-2Z-7.8e-5-7.8e-50%10035FP-3Z-7.8e-5-7.8e-50%10036FP-4Z-7.8e-5-7.8e-50%10037MP-1Z-.000592-.0005920%10038MP-2Z-.000592-.0005920%10039MP-3Z-.000592-.0005920%10040SA-1Z-.000489-.0004890%10041SF1-BHZ-.000318-.0003180%10042SF1-D1Z-.000154-.0001540%10043SF1-D2Z-.000154-.0001540%10044SF1-THZ-.000318-.0003180%10045SF1-V1Z-.000154-.0001540%10046SF1-V2Z-.000154-.0001540%10047SF2-BHZ-5.5e-5-5.5e-50%10048SF2-D1Z-.000154-.0001540%10049SF2-D2Z-.000154-.0001540%10050SF2-THZ-5.5e-5-5.5e-50%10051SF2-V1Z-.000154-.0001540%10052SF2-V2Z-.000154-.0001540%100Member Distributed Loads (BLC 22 : 60 Wind - Ice)Member Label Direction Start Magnitude[k/ft,... End Magnitude[k/ft,F,... Start Location[ft,%] End Location[ft,%]1FF1-BH1X-.000173-.0001730%1002FF1-BH2X-.000173-.0001730%1003FF1-BH3X-.000173-.0001730%100RISA-3D Version 17.0.4 Page 32 [C:\...\...\...\...\RISA-3D\Sabre C10837002 THD V-Boom.r3d]
Company : Tower Engineering Professionals, Inc.July 12, 202110:22 AMDesigner : APBJob Number : TEP No. 62749.566934Checked By: DCModel Name : Midway Road (FL10049-A)Member Distributed Loads (BLC 22 : 60 Wind - Ice) (Continued)Member Label Direction Start Magnitude[k/ft,... End Magnitude[k/ft,F,... Start Location[ft,%] End Location[ft,%]4FF1-TH1X-.000173-.0001730%1005FF1-TH2X-.000173-.0001730%1006FF1-TH3X-.000173-.0001730%1007FP-1X-4.3e-5-4.3e-50%1008FP-2X-4.3e-5-4.3e-50%1009FP-3X-4.3e-5-4.3e-50%10010FP-4X-4.3e-5-4.3e-50%10011MP-1X-.000377-.0003770%10012MP-2X-.000377-.0003770%10013MP-3X-.000377-.0003770%10014SA-1X-.000311-.0003110%10015SF1-BHX-.000237-.0002370%10016SF1-D1X-9.8e-5-9.8e-50%10017SF1-D2X-9.8e-5-9.8e-50%10018SF1-THX-.000237-.0002370%10019SF1-V1X-9.8e-5-9.8e-50%10020SF1-V2X-9.8e-5-9.8e-50%10021SF2-BHX-2.4e-5-2.4e-50%10022SF2-D1X-9.8e-5-9.8e-50%10023SF2-D2X-9.8e-5-9.8e-50%10024SF2-THX-2.4e-5-2.4e-50%10025SF2-V1X-9.8e-5-9.8e-50%10026SF2-V2X-9.8e-5-9.8e-50%10027FF1-BH1Z-.00027-.000270%10028FF1-BH2Z-.00027-.000270%10029FF1-BH3Z-.00027-.000270%10030FF1-TH1Z-.00027-.000270%10031FF1-TH2Z-.00027-.000270%10032FF1-TH3Z-.00027-.000270%10033FP-1Z-6.7e-5-6.7e-50%10034FP-2Z-6.7e-5-6.7e-50%10035FP-3Z-6.7e-5-6.7e-50%10036FP-4Z-6.7e-5-6.7e-50%10037MP-1Z-.000725-.0007250%10038MP-2Z-.000725-.0007250%10039MP-3Z-.000725-.0007250%10040SA-1Z-.000599-.0005990%10041SF1-BHZ-.000359-.0003590%10042SF1-D1Z-.000189-.0001890%10043SF1-D2Z-.000189-.0001890%10044SF1-THZ-.000359-.0003590%10045SF1-V1Z-.000189-.0001890%10046SF1-V2Z-.000189-.0001890%10047SF2-BHZ-3.6e-5-3.6e-50%10048SF2-D1Z-.000189-.0001890%10049SF2-D2Z-.000189-.0001890%10050SF2-THZ-3.6e-5-3.6e-50%10051SF2-V1Z-.000189-.0001890%10052SF2-V2Z-.000189-.0001890%100Member Distributed Loads (BLC 23 : 90 Wind - Ice)Member Label Direction Start Magnitude[k/ft,... End Magnitude[k/ft,F,... Start Location[ft,%] End Location[ft,%]1FF1-BH1Z000%1002FF1-BH2Z000%1003FF1-BH3Z000%1004FF1-TH1Z000%100RISA-3D Version 17.0.4 Page 33 [C:\...\...\...\...\RISA-3D\Sabre C10837002 THD V-Boom.r3d] Company : Tower Engineering Professionals, Inc.July 12, 202110:22 AMDesigner : APBJob Number : TEP No. 62749.566934Checked By: DCModel Name : Midway Road (FL10049-A)Member Distributed Loads (BLC 23 : 90 Wind - Ice) (Continued)Member Label Direction Start Magnitude[k/ft,... End Magnitude[k/ft,F,... Start Location[ft,%] End Location[ft,%]5FF1-TH2Z000%1006FF1-TH3Z000%1007FP-1Z000%1008FP-2Z000%1009FP-3Z000%10010FP-4Z000%10011MP-1Z-.000838-.0008380%10012MP-2Z-.000838-.0008380%10013MP-3Z-.000838-.0008380%10014SA-1Z-.000692-.0006920%10015SF1-BHZ-.000263-.0002630%10016SF1-D1Z-.000218-.0002180%10017SF1-D2Z-.000218-.0002180%10018SF1-THZ-.000263-.0002630%10019SF1-V1Z-.000218-.0002180%10020SF1-V2Z-.000218-.0002180%10021SF2-BHZ-.000263-.0002630%10022SF2-D1Z-.000218-.0002180%10023SF2-D2Z-.000218-.0002180%10024SF2-THZ-.000263-.0002630%10025SF2-V1Z-.000218-.0002180%10026SF2-V2Z-.000218-.0002180%100Member Distributed Loads (BLC 24 : 120 Wind - Ice)Member Label Direction Start Magnitude[k/ft,... End Magnitude[k/ft,F,... Start Location[ft,%] End Location[ft,%]1FF1-BH1X.000173.0001730%1002FF1-BH2X.000173.0001730%1003FF1-BH3X.000173.0001730%1004FF1-TH1X.000173.0001730%1005FF1-TH2X.000173.0001730%1006FF1-TH3X.000173.0001730%1007FP-1X4.3e-54.3e-50%1008FP-2X4.3e-54.3e-50%1009FP-3X4.3e-54.3e-50%10010FP-4X4.3e-54.3e-50%10011MP-1X.000377.0003770%10012MP-2X.000377.0003770%10013MP-3X.000377.0003770%10014SA-1X.000311.0003110%10015SF1-BHX2.4e-52.4e-50%10016SF1-D1X9.8e-59.8e-50%10017SF1-D2X9.8e-59.8e-50%10018SF1-THX2.4e-52.4e-50%10019SF1-V1X9.8e-59.8e-50%10020SF1-V2X9.8e-59.8e-50%10021SF2-BHX.000237.0002370%10022SF2-D1X9.8e-59.8e-50%10023SF2-D2X9.8e-59.8e-50%10024SF2-THX.000237.0002370%10025SF2-V1X9.8e-59.8e-50%10026SF2-V2X9.8e-59.8e-50%10027FF1-BH1Z-.00027-.000270%10028FF1-BH2Z-.00027-.000270%10029FF1-BH3Z-.00027-.000270%10030FF1-TH1Z-.00027-.000270%10031FF1-TH2Z-.00027-.000270%100RISA-3D Version 17.0.4 Page 34 [C:\...\...\...\...\RISA-3D\Sabre C10837002 THD V-Boom.r3d]
Company : Tower Engineering Professionals, Inc.July 12, 202110:22 AMDesigner : APBJob Number : TEP No. 62749.566934Checked By: DCModel Name : Midway Road (FL10049-A)Member Distributed Loads (BLC 24 : 120 Wind - Ice) (Continued)Member Label Direction Start Magnitude[k/ft,... End Magnitude[k/ft,F,... Start Location[ft,%] End Location[ft,%]32FF1-TH3Z-.00027-.000270%10033FP-1Z-6.7e-5-6.7e-50%10034FP-2Z-6.7e-5-6.7e-50%10035FP-3Z-6.7e-5-6.7e-50%10036FP-4Z-6.7e-5-6.7e-50%10037MP-1Z-.000725-.0007250%10038MP-2Z-.000725-.0007250%10039MP-3Z-.000725-.0007250%10040SA-1Z-.000599-.0005990%10041SF1-BHZ-3.6e-5-3.6e-50%10042SF1-D1Z-.000189-.0001890%10043SF1-D2Z-.000189-.0001890%10044SF1-THZ-3.6e-5-3.6e-50%10045SF1-V1Z-.000189-.0001890%10046SF1-V2Z-.000189-.0001890%10047SF2-BHZ-.000359-.0003590%10048SF2-D1Z-.000189-.0001890%10049SF2-D2Z-.000189-.0001890%10050SF2-THZ-.000359-.0003590%10051SF2-V1Z-.000189-.0001890%10052SF2-V2Z-.000189-.0001890%100Member Distributed Loads (BLC 25 : 135 Wind - Ice)Member Label Direction Start Magnitude[k/ft,... End Magnitude[k/ft,F,... Start Location[ft,%] End Location[ft,%]1FF1-BH1X.000346.0003460%1002FF1-BH2X.000346.0003460%1003FF1-BH3X.000346.0003460%1004FF1-TH1X.000346.0003460%1005FF1-TH2X.000346.0003460%1006FF1-TH3X.000346.0003460%1007FP-1X8.6e-58.6e-50%1008FP-2X8.6e-58.6e-50%1009FP-3X8.6e-58.6e-50%10010FP-4X8.6e-58.6e-50%10011MP-1X.000533.0005330%10012MP-2X.000533.0005330%10013MP-3X.000533.0005330%10014SA-1X.00044.000440%10015SF1-BHX6.3e-56.3e-50%10016SF1-D1X.000139.0001390%10017SF1-D2X.000139.0001390%10018SF1-THX6.3e-56.3e-50%10019SF1-V1X.000139.0001390%10020SF1-V2X.000139.0001390%10021SF2-BHX.000364.0003640%10022SF2-D1X.000139.0001390%10023SF2-D2X.000139.0001390%10024SF2-THX.000364.0003640%10025SF2-V1X.000139.0001390%10026SF2-V2X.000139.0001390%10027FF1-BH1Z-.000311-.0003110%10028FF1-BH2Z-.000311-.0003110%10029FF1-BH3Z-.000311-.0003110%10030FF1-TH1Z-.000311-.0003110%10031FF1-TH2Z-.000311-.0003110%10032FF1-TH3Z-.000311-.0003110%100RISA-3D Version 17.0.4 Page 35 [C:\...\...\...\...\RISA-3D\Sabre C10837002 THD V-Boom.r3d] Company : Tower Engineering Professionals, Inc.July 12, 202110:22 AMDesigner : APBJob Number : TEP No. 62749.566934Checked By: DCModel Name : Midway Road (FL10049-A)Member Distributed Loads (BLC 25 : 135 Wind - Ice) (Continued)Member Label Direction Start Magnitude[k/ft,... End Magnitude[k/ft,F,... Start Location[ft,%] End Location[ft,%]33FP-1Z-7.8e-5-7.8e-50%10034FP-2Z-7.8e-5-7.8e-50%10035FP-3Z-7.8e-5-7.8e-50%10036FP-4Z-7.8e-5-7.8e-50%10037MP-1Z-.000592-.0005920%10038MP-2Z-.000592-.0005920%10039MP-3Z-.000592-.0005920%10040SA-1Z-.000489-.0004890%10041SF1-BHZ-5.5e-5-5.5e-50%10042SF1-D1Z-.000154-.0001540%10043SF1-D2Z-.000154-.0001540%10044SF1-THZ-5.5e-5-5.5e-50%10045SF1-V1Z-.000154-.0001540%10046SF1-V2Z-.000154-.0001540%10047SF2-BHZ-.000318-.0003180%10048SF2-D1Z-.000154-.0001540%10049SF2-D2Z-.000154-.0001540%10050SF2-THZ-.000318-.0003180%10051SF2-V1Z-.000154-.0001540%10052SF2-V2Z-.000154-.0001540%100Member Distributed Loads (BLC 26 : 150 Wind - Ice)Member Label Direction Start Magnitude[k/ft,... End Magnitude[k/ft,F,... Start Location[ft,%] End Location[ft,%]1FF1-BH1X.000519.0005190%1002FF1-BH2X.000519.0005190%1003FF1-BH3X.000519.0005190%1004FF1-TH1X.000519.0005190%1005FF1-TH2X.000519.0005190%1006FF1-TH3X.000519.0005190%1007FP-1X.00013.000130%1008FP-2X.00013.000130%1009FP-3X.00013.000130%10010FP-4X.00013.000130%10011MP-1X.000653.0006530%10012MP-2X.000653.0006530%10013MP-3X.000653.0006530%10014SA-1X.000539.0005390%10015SF1-BHX.00019.000190%10016SF1-D1X.00017.000170%10017SF1-D2X.00017.000170%10018SF1-THX.00019.000190%10019SF1-V1X.00017.000170%10020SF1-V2X.00017.000170%10021SF2-BHX.00045.000450%10022SF2-D1X.00017.000170%10023SF2-D2X.00017.000170%10024SF2-THX.00045.000450%10025SF2-V1X.00017.000170%10026SF2-V2X.00017.000170%10027FF1-BH1Z-.00027-.000270%10028FF1-BH2Z-.00027-.000270%10029FF1-BH3Z-.00027-.000270%10030FF1-TH1Z-.00027-.000270%10031FF1-TH2Z-.00027-.000270%10032FF1-TH3Z-.00027-.000270%10033FP-1Z-6.7e-5-6.7e-50%100RISA-3D Version 17.0.4 Page 36 [C:\...\...\...\...\RISA-3D\Sabre C10837002 THD V-Boom.r3d]
Company : Tower Engineering Professionals, Inc.July 12, 202110:22 AMDesigner : APBJob Number : TEP No. 62749.566934Checked By: DCModel Name : Midway Road (FL10049-A)Member Distributed Loads (BLC 26 : 150 Wind - Ice) (Continued)Member Label Direction Start Magnitude[k/ft,... End Magnitude[k/ft,F,... Start Location[ft,%] End Location[ft,%]34FP-2Z-6.7e-5-6.7e-50%10035FP-3Z-6.7e-5-6.7e-50%10036FP-4Z-6.7e-5-6.7e-50%10037MP-1Z-.000419-.0004190%10038MP-2Z-.000419-.0004190%10039MP-3Z-.000419-.0004190%10040SA-1Z-.000346-.0003460%10041SF1-BHZ-9.6e-5-9.6e-50%10042SF1-D1Z-.000109-.0001090%10043SF1-D2Z-.000109-.0001090%10044SF1-THZ-9.6e-5-9.6e-50%10045SF1-V1Z-.000109-.0001090%10046SF1-V2Z-.000109-.0001090%10047SF2-BHZ-.000227-.0002270%10048SF2-D1Z-.000109-.0001090%10049SF2-D2Z-.000109-.0001090%10050SF2-THZ-.000227-.0002270%10051SF2-V1Z-.000109-.0001090%10052SF2-V2Z-.000109-.0001090%100Member Distributed Loads (BLC 27 : 180 Wind - Ice)Member Label Direction Start Magnitude[k/ft,... End Magnitude[k/ft,F,... Start Location[ft,%] End Location[ft,%]1FF1-BH1X.000692.0006920%1002FF1-BH2X.000692.0006920%1003FF1-BH3X.000692.0006920%1004FF1-TH1X.000692.0006920%1005FF1-TH2X.000692.0006920%1006FF1-TH3X.000692.0006920%1007FP-1X.000173.0001730%1008FP-2X.000173.0001730%1009FP-3X.000173.0001730%10010FP-4X.000173.0001730%10011MP-1X.000754.0007540%10012MP-2X.000754.0007540%10013MP-3X.000754.0007540%10014SA-1X.000623.0006230%10015SF1-BHX.000522.0005220%10016SF1-D1X.000197.0001970%10017SF1-D2X.000197.0001970%10018SF1-THX.000522.0005220%10019SF1-V1X.000197.0001970%10020SF1-V2X.000197.0001970%10021SF2-BHX.000522.0005220%10022SF2-D1X.000197.0001970%10023SF2-D2X.000197.0001970%10024SF2-THX.000522.0005220%10025SF2-V1X.000197.0001970%10026SF2-V2X.000197.0001970%100Member Distributed Loads (BLC 28 : 210 Wind - Ice)Member Label Direction Start Magnitude[k/ft,... End Magnitude[k/ft,F,... Start Location[ft,%] End Location[ft,%]1FF1-BH1X.000519.0005190%1002FF1-BH2X.000519.0005190%1003FF1-BH3X.000519.0005190%1004FF1-TH1X.000519.0005190%1005FF1-TH2X.000519.0005190%100RISA-3D Version 17.0.4 Page 37 [C:\...\...\...\...\RISA-3D\Sabre C10837002 THD V-Boom.r3d] Company : Tower Engineering Professionals, Inc.July 12, 202110:22 AMDesigner : APBJob Number : TEP No. 62749.566934Checked By: DCModel Name : Midway Road (FL10049-A)Member Distributed Loads (BLC 28 : 210 Wind - Ice) (Continued)Member Label Direction Start Magnitude[k/ft,... End Magnitude[k/ft,F,... Start Location[ft,%] End Location[ft,%]6FF1-TH3X.000519.0005190%1007FP-1X.00013.000130%1008FP-2X.00013.000130%1009FP-3X.00013.000130%10010FP-4X.00013.000130%10011MP-1X.000653.0006530%10012MP-2X.000653.0006530%10013MP-3X.000653.0006530%10014SA-1X.000539.0005390%10015SF1-BHX.00045.000450%10016SF1-D1X.00017.000170%10017SF1-D2X.00017.000170%10018SF1-THX.00045.000450%10019SF1-V1X.00017.000170%10020SF1-V2X.00017.000170%10021SF2-BHX.00019.000190%10022SF2-D1X.00017.000170%10023SF2-D2X.00017.000170%10024SF2-THX.00019.000190%10025SF2-V1X.00017.000170%10026SF2-V2X.00017.000170%10027FF1-BH1Z.00027.000270%10028FF1-BH2Z.00027.000270%10029FF1-BH3Z.00027.000270%10030FF1-TH1Z.00027.000270%10031FF1-TH2Z.00027.000270%10032FF1-TH3Z.00027.000270%10033FP-1Z6.7e-56.7e-50%10034FP-2Z6.7e-56.7e-50%10035FP-3Z6.7e-56.7e-50%10036FP-4Z6.7e-56.7e-50%10037MP-1Z.000419.0004190%10038MP-2Z.000419.0004190%10039MP-3Z.000419.0004190%10040SA-1Z.000346.0003460%10041SF1-BHZ.000227.0002270%10042SF1-D1Z.000109.0001090%10043SF1-D2Z.000109.0001090%10044SF1-THZ.000227.0002270%10045SF1-V1Z.000109.0001090%10046SF1-V2Z.000109.0001090%10047SF2-BHZ9.6e-59.6e-50%10048SF2-D1Z.000109.0001090%10049SF2-D2Z.000109.0001090%10050SF2-THZ9.6e-59.6e-50%10051SF2-V1Z.000109.0001090%10052SF2-V2Z.000109.0001090%100Member Distributed Loads (BLC 29 : 225 Wind - Ice)Member Label Direction Start Magnitude[k/ft,... End Magnitude[k/ft,F,... Start Location[ft,%] End Location[ft,%]1FF1-BH1X.000346.0003460%1002FF1-BH2X.000346.0003460%1003FF1-BH3X.000346.0003460%1004FF1-TH1X.000346.0003460%1005FF1-TH2X.000346.0003460%1006FF1-TH3X.000346.0003460%100RISA-3D Version 17.0.4 Page 38 [C:\...\...\...\...\RISA-3D\Sabre C10837002 THD V-Boom.r3d]
Company : Tower Engineering Professionals, Inc.July 12, 202110:22 AMDesigner : APBJob Number : TEP No. 62749.566934Checked By: DCModel Name : Midway Road (FL10049-A)Member Distributed Loads (BLC 29 : 225 Wind - Ice) (Continued)Member Label Direction Start Magnitude[k/ft,... End Magnitude[k/ft,F,... Start Location[ft,%] End Location[ft,%]7FP-1X8.6e-58.6e-50%1008FP-2X8.6e-58.6e-50%1009FP-3X8.6e-58.6e-50%10010FP-4X8.6e-58.6e-50%10011MP-1X.000533.0005330%10012MP-2X.000533.0005330%10013MP-3X.000533.0005330%10014SA-1X.00044.000440%10015SF1-BHX.000364.0003640%10016SF1-D1X.000139.0001390%10017SF1-D2X.000139.0001390%10018SF1-THX.000364.0003640%10019SF1-V1X.000139.0001390%10020SF1-V2X.000139.0001390%10021SF2-BHX6.3e-56.3e-50%10022SF2-D1X.000139.0001390%10023SF2-D2X.000139.0001390%10024SF2-THX6.3e-56.3e-50%10025SF2-V1X.000139.0001390%10026SF2-V2X.000139.0001390%10027FF1-BH1Z.000311.0003110%10028FF1-BH2Z.000311.0003110%10029FF1-BH3Z.000311.0003110%10030FF1-TH1Z.000311.0003110%10031FF1-TH2Z.000311.0003110%10032FF1-TH3Z.000311.0003110%10033FP-1Z7.8e-57.8e-50%10034FP-2Z7.8e-57.8e-50%10035FP-3Z7.8e-57.8e-50%10036FP-4Z7.8e-57.8e-50%10037MP-1Z.000592.0005920%10038MP-2Z.000592.0005920%10039MP-3Z.000592.0005920%10040SA-1Z.000489.0004890%10041SF1-BHZ.000318.0003180%10042SF1-D1Z.000154.0001540%10043SF1-D2Z.000154.0001540%10044SF1-THZ.000318.0003180%10045SF1-V1Z.000154.0001540%10046SF1-V2Z.000154.0001540%10047SF2-BHZ5.5e-55.5e-50%10048SF2-D1Z.000154.0001540%10049SF2-D2Z.000154.0001540%10050SF2-THZ5.5e-55.5e-50%10051SF2-V1Z.000154.0001540%10052SF2-V2Z.000154.0001540%100Member Distributed Loads (BLC 30 : 240 Wind - Ice)Member Label Direction Start Magnitude[k/ft,... End Magnitude[k/ft,F,... Start Location[ft,%] End Location[ft,%]1FF1-BH1X.000173.0001730%1002FF1-BH2X.000173.0001730%1003FF1-BH3X.000173.0001730%1004FF1-TH1X.000173.0001730%1005FF1-TH2X.000173.0001730%1006FF1-TH3X.000173.0001730%1007FP-1X4.3e-54.3e-50%100RISA-3D Version 17.0.4 Page 39 [C:\...\...\...\...\RISA-3D\Sabre C10837002 THD V-Boom.r3d] Company : Tower Engineering Professionals, Inc.July 12, 202110:22 AMDesigner : APBJob Number : TEP No. 62749.566934Checked By: DCModel Name : Midway Road (FL10049-A)Member Distributed Loads (BLC 30 : 240 Wind - Ice) (Continued)Member Label Direction Start Magnitude[k/ft,... End Magnitude[k/ft,F,... Start Location[ft,%] End Location[ft,%]8FP-2X4.3e-54.3e-50%1009FP-3X4.3e-54.3e-50%10010FP-4X4.3e-54.3e-50%10011MP-1X.000377.0003770%10012MP-2X.000377.0003770%10013MP-3X.000377.0003770%10014SA-1X.000311.0003110%10015SF1-BHX.000237.0002370%10016SF1-D1X9.8e-59.8e-50%10017SF1-D2X9.8e-59.8e-50%10018SF1-THX.000237.0002370%10019SF1-V1X9.8e-59.8e-50%10020SF1-V2X9.8e-59.8e-50%10021SF2-BHX2.4e-52.4e-50%10022SF2-D1X9.8e-59.8e-50%10023SF2-D2X9.8e-59.8e-50%10024SF2-THX2.4e-52.4e-50%10025SF2-V1X9.8e-59.8e-50%10026SF2-V2X9.8e-59.8e-50%10027FF1-BH1Z.00027.000270%10028FF1-BH2Z.00027.000270%10029FF1-BH3Z.00027.000270%10030FF1-TH1Z.00027.000270%10031FF1-TH2Z.00027.000270%10032FF1-TH3Z.00027.000270%10033FP-1Z6.7e-56.7e-50%10034FP-2Z6.7e-56.7e-50%10035FP-3Z6.7e-56.7e-50%10036FP-4Z6.7e-56.7e-50%10037MP-1Z.000725.0007250%10038MP-2Z.000725.0007250%10039MP-3Z.000725.0007250%10040SA-1Z.000599.0005990%10041SF1-BHZ.000359.0003590%10042SF1-D1Z.000189.0001890%10043SF1-D2Z.000189.0001890%10044SF1-THZ.000359.0003590%10045SF1-V1Z.000189.0001890%10046SF1-V2Z.000189.0001890%10047SF2-BHZ3.6e-53.6e-50%10048SF2-D1Z.000189.0001890%10049SF2-D2Z.000189.0001890%10050SF2-THZ3.6e-53.6e-50%10051SF2-V1Z.000189.0001890%10052SF2-V2Z.000189.0001890%100Member Distributed Loads (BLC 31 : 270 Wind - Ice)Member Label Direction Start Magnitude[k/ft,... End Magnitude[k/ft,F,... Start Location[ft,%] End Location[ft,%]1FF1-BH1Z000%1002FF1-BH2Z000%1003FF1-BH3Z000%1004FF1-TH1Z000%1005FF1-TH2Z000%1006FF1-TH3Z000%1007FP-1Z000%1008FP-2Z000%100RISA-3D Version 17.0.4 Page 40 [C:\...\...\...\...\RISA-3D\Sabre C10837002 THD V-Boom.r3d]
Company : Tower Engineering Professionals, Inc.July 12, 202110:22 AMDesigner : APBJob Number : TEP No. 62749.566934Checked By: DCModel Name : Midway Road (FL10049-A)Member Distributed Loads (BLC 31 : 270 Wind - Ice) (Continued)Member Label Direction Start Magnitude[k/ft,... End Magnitude[k/ft,F,... Start Location[ft,%] End Location[ft,%]9FP-3Z000%10010FP-4Z000%10011MP-1Z.000838.0008380%10012MP-2Z.000838.0008380%10013MP-3Z.000838.0008380%10014SA-1Z.000692.0006920%10015SF1-BHZ.000263.0002630%10016SF1-D1Z.000218.0002180%10017SF1-D2Z.000218.0002180%10018SF1-THZ.000263.0002630%10019SF1-V1Z.000218.0002180%10020SF1-V2Z.000218.0002180%10021SF2-BHZ.000263.0002630%10022SF2-D1Z.000218.0002180%10023SF2-D2Z.000218.0002180%10024SF2-THZ.000263.0002630%10025SF2-V1Z.000218.0002180%10026SF2-V2Z.000218.0002180%100Member Distributed Loads (BLC 32 : 300 Wind - Ice)Member Label Direction Start Magnitude[k/ft,... End Magnitude[k/ft,F,... Start Location[ft,%] End Location[ft,%]1FF1-BH1X-.000173-.0001730%1002FF1-BH2X-.000173-.0001730%1003FF1-BH3X-.000173-.0001730%1004FF1-TH1X-.000173-.0001730%1005FF1-TH2X-.000173-.0001730%1006FF1-TH3X-.000173-.0001730%1007FP-1X-4.3e-5-4.3e-50%1008FP-2X-4.3e-5-4.3e-50%1009FP-3X-4.3e-5-4.3e-50%10010FP-4X-4.3e-5-4.3e-50%10011MP-1X-.000377-.0003770%10012MP-2X-.000377-.0003770%10013MP-3X-.000377-.0003770%10014SA-1X-.000311-.0003110%10015SF1-BHX-2.4e-5-2.4e-50%10016SF1-D1X-9.8e-5-9.8e-50%10017SF1-D2X-9.8e-5-9.8e-50%10018SF1-THX-2.4e-5-2.4e-50%10019SF1-V1X-9.8e-5-9.8e-50%10020SF1-V2X-9.8e-5-9.8e-50%10021SF2-BHX-.000237-.0002370%10022SF2-D1X-9.8e-5-9.8e-50%10023SF2-D2X-9.8e-5-9.8e-50%10024SF2-THX-.000237-.0002370%10025SF2-V1X-9.8e-5-9.8e-50%10026SF2-V2X-9.8e-5-9.8e-50%10027FF1-BH1Z.00027.000270%10028FF1-BH2Z.00027.000270%10029FF1-BH3Z.00027.000270%10030FF1-TH1Z.00027.000270%10031FF1-TH2Z.00027.000270%10032FF1-TH3Z.00027.000270%10033FP-1Z6.7e-56.7e-50%10034FP-2Z6.7e-56.7e-50%10035FP-3Z6.7e-56.7e-50%100RISA-3D Version 17.0.4 Page 41 [C:\...\...\...\...\RISA-3D\Sabre C10837002 THD V-Boom.r3d] Company : Tower Engineering Professionals, Inc.July 12, 202110:22 AMDesigner : APBJob Number : TEP No. 62749.566934Checked By: DCModel Name : Midway Road (FL10049-A)Member Distributed Loads (BLC 32 : 300 Wind - Ice) (Continued)Member Label Direction Start Magnitude[k/ft,... End Magnitude[k/ft,F,... Start Location[ft,%] End Location[ft,%]36FP-4Z6.7e-56.7e-50%10037MP-1Z.000725.0007250%10038MP-2Z.000725.0007250%10039MP-3Z.000725.0007250%10040SA-1Z.000599.0005990%10041SF1-BHZ3.6e-53.6e-50%10042SF1-D1Z.000189.0001890%10043SF1-D2Z.000189.0001890%10044SF1-THZ3.6e-53.6e-50%10045SF1-V1Z.000189.0001890%10046SF1-V2Z.000189.0001890%10047SF2-BHZ.000359.0003590%10048SF2-D1Z.000189.0001890%10049SF2-D2Z.000189.0001890%10050SF2-THZ.000359.0003590%10051SF2-V1Z.000189.0001890%10052SF2-V2Z.000189.0001890%100Member Distributed Loads (BLC 33 : 315 Wind - Ice)Member Label Direction Start Magnitude[k/ft,... End Magnitude[k/ft,F,... Start Location[ft,%] End Location[ft,%]1FF1-BH1X-.000346-.0003460%1002FF1-BH2X-.000346-.0003460%1003FF1-BH3X-.000346-.0003460%1004FF1-TH1X-.000346-.0003460%1005FF1-TH2X-.000346-.0003460%1006FF1-TH3X-.000346-.0003460%1007FP-1X-8.6e-5-8.6e-50%1008FP-2X-8.6e-5-8.6e-50%1009FP-3X-8.6e-5-8.6e-50%10010FP-4X-8.6e-5-8.6e-50%10011MP-1X-.000533-.0005330%10012MP-2X-.000533-.0005330%10013MP-3X-.000533-.0005330%10014SA-1X-.00044-.000440%10015SF1-BHX-6.3e-5-6.3e-50%10016SF1-D1X-.000139-.0001390%10017SF1-D2X-.000139-.0001390%10018SF1-THX-6.3e-5-6.3e-50%10019SF1-V1X-.000139-.0001390%10020SF1-V2X-.000139-.0001390%10021SF2-BHX-.000364-.0003640%10022SF2-D1X-.000139-.0001390%10023SF2-D2X-.000139-.0001390%10024SF2-THX-.000364-.0003640%10025SF2-V1X-.000139-.0001390%10026SF2-V2X-.000139-.0001390%10027FF1-BH1Z.000311.0003110%10028FF1-BH2Z.000311.0003110%10029FF1-BH3Z.000311.0003110%10030FF1-TH1Z.000311.0003110%10031FF1-TH2Z.000311.0003110%10032FF1-TH3Z.000311.0003110%10033FP-1Z7.8e-57.8e-50%10034FP-2Z7.8e-57.8e-50%10035FP-3Z7.8e-57.8e-50%10036FP-4Z7.8e-57.8e-50%100RISA-3D Version 17.0.4 Page 42 [C:\...\...\...\...\RISA-3D\Sabre C10837002 THD V-Boom.r3d]
Company : Tower Engineering Professionals, Inc.July 12, 202110:22 AMDesigner : APBJob Number : TEP No. 62749.566934Checked By: DCModel Name : Midway Road (FL10049-A)Member Distributed Loads (BLC 33 : 315 Wind - Ice) (Continued)Member Label Direction Start Magnitude[k/ft,... End Magnitude[k/ft,F,... Start Location[ft,%] End Location[ft,%]37MP-1Z.000592.0005920%10038MP-2Z.000592.0005920%10039MP-3Z.000592.0005920%10040SA-1Z.000489.0004890%10041SF1-BHZ5.5e-55.5e-50%10042SF1-D1Z.000154.0001540%10043SF1-D2Z.000154.0001540%10044SF1-THZ5.5e-55.5e-50%10045SF1-V1Z.000154.0001540%10046SF1-V2Z.000154.0001540%10047SF2-BHZ.000318.0003180%10048SF2-D1Z.000154.0001540%10049SF2-D2Z.000154.0001540%10050SF2-THZ.000318.0003180%10051SF2-V1Z.000154.0001540%10052SF2-V2Z.000154.0001540%100Member Distributed Loads (BLC 34 : 330 Wind - Ice)Member Label Direction Start Magnitude[k/ft,... End Magnitude[k/ft,F,... Start Location[ft,%] End Location[ft,%]1FF1-BH1X-.000519-.0005190%1002FF1-BH2X-.000519-.0005190%1003FF1-BH3X-.000519-.0005190%1004FF1-TH1X-.000519-.0005190%1005FF1-TH2X-.000519-.0005190%1006FF1-TH3X-.000519-.0005190%1007FP-1X-.00013-.000130%1008FP-2X-.00013-.000130%1009FP-3X-.00013-.000130%10010FP-4X-.00013-.000130%10011MP-1X-.000653-.0006530%10012MP-2X-.000653-.0006530%10013MP-3X-.000653-.0006530%10014SA-1X-.000539-.0005390%10015SF1-BHX-.00019-.000190%10016SF1-D1X-.00017-.000170%10017SF1-D2X-.00017-.000170%10018SF1-THX-.00019-.000190%10019SF1-V1X-.00017-.000170%10020SF1-V2X-.00017-.000170%10021SF2-BHX-.00045-.000450%10022SF2-D1X-.00017-.000170%10023SF2-D2X-.00017-.000170%10024SF2-THX-.00045-.000450%10025SF2-V1X-.00017-.000170%10026SF2-V2X-.00017-.000170%10027FF1-BH1Z.00027.000270%10028FF1-BH2Z.00027.000270%10029FF1-BH3Z.00027.000270%10030FF1-TH1Z.00027.000270%10031FF1-TH2Z.00027.000270%10032FF1-TH3Z.00027.000270%10033FP-1Z6.7e-56.7e-50%10034FP-2Z6.7e-56.7e-50%10035FP-3Z6.7e-56.7e-50%10036FP-4Z6.7e-56.7e-50%10037MP-1Z.000419.0004190%100RISA-3D Version 17.0.4 Page 43 [C:\...\...\...\...\RISA-3D\Sabre C10837002 THD V-Boom.r3d] Company : Tower Engineering Professionals, Inc.July 12, 202110:22 AMDesigner : APBJob Number : TEP No. 62749.566934Checked By: DCModel Name : Midway Road (FL10049-A)Member Distributed Loads (BLC 34 : 330 Wind - Ice) (Continued)Member Label Direction Start Magnitude[k/ft,... End Magnitude[k/ft,F,... Start Location[ft,%] End Location[ft,%]38MP-2Z.000419.0004190%10039MP-3Z.000419.0004190%10040SA-1Z.000346.0003460%10041SF1-BHZ9.6e-59.6e-50%10042SF1-D1Z.000109.0001090%10043SF1-D2Z.000109.0001090%10044SF1-THZ9.6e-59.6e-50%10045SF1-V1Z.000109.0001090%10046SF1-V2Z.000109.0001090%10047SF2-BHZ.000227.0002270%10048SF2-D1Z.000109.0001090%10049SF2-D2Z.000109.0001090%10050SF2-THZ.000227.0002270%10051SF2-V1Z.000109.0001090%10052SF2-V2Z.000109.0001090%100Member Area Loads Joint A Joint B Joint C Joint D Direction Distribution Magnitude[ksf]No Data to Print ...Envelope Joint ReactionsJoint X [k] LC Y [k] LC Z [k] LC MX [k-ft] LC MY [k-ft] LC MZ [k-ft] LC1TC1-1max2.6613.719591.69540980980982min-3.70327.0752-.989130101013TC1-2max2.151181.043191.17840980980984min-1.10210-.45811-1.846280101015SA-2Amax2.48827.607271.114270980980986min-2.49819-.5793-1.111190101017Totals:max2.631181.427521.727218min-2.63126.583-1.72729Envelope AISC 15th(360-16): LRFD Steel Code ChecksMember Shape Code Check Loc[ft] LC Shear ...Loc[ft] Dir LCphi*Pn...phi*Pn...phi*M...phi*M... Cb Eqn1FF1-TH2PIPE_2.0.297026.06642715.3745.92.6742.6741.7...H1-1b2SF2-TH1.9 O.D. x 0....267.53219.0873.9891928.56548.0662.1782.1781.9...H1-1b3SF2-BH1.9 O.D. x 0....238.48819.11601928.56548.0662.1782.1781.9...H1-1b4FF1-TH3PIPE_2.0.235019.10402738.72645.92.6742.6742.2...H1-1b5FP-2CWS00952.224019.1200y2734.44134.441.3591.5231.8...H1-1b6FF1-TH1PIPE_2.0.2231.17226.1181.1722738.72645.92.6742.6741.7...H1-1b7MP-1PIPE_2.5.2172.58326.0492.51836.93950.7153.5963.5961.5...H1-1b8SF2-V1SR 3/4.2032.71919.0232.719277.80319.88.249.2492.3...H1-1b9SF2-D2SR 3/4.1904.28119.0224.2811811.13719.88.249.2492.5...H1-1b10SF1-BH1.9 O.D. x 0....186.48860.06905328.56548.0662.1782.1781.9...H1-1b11FP-1CWS00952.186.32327.056.323y2734.44134.441.3591.5231.2...H1-1b12FF1-BH2PIPE_2.0.177026.06641915.3745.92.6742.6741.8...H1-1b13FP-3CWS00952.173.32326.044.323y2634.44134.441.3591.5231.2...H1-1b14SF1-TH1.9 O.D. x 0....172.48860.06905328.56548.0662.1782.1781.9...H1-1b15SF1-V1SR 3/4.1712.71919.0222.71937.80319.88.249.2492.3...H1-1b16FP-4CWS00952.159019.0460y1934.44134.441.3591.5231.1...H1-1b17FF1-BH1PIPE_2.0.1521.17218.1081.1722638.72645.92.6742.6741.4...H1-1b18FF1-BH3PIPE_2.0.139.32819.110.3281938.72645.92.6742.6741.4...H1-1b19MP-2PIPE_2.5.1375.41727.0872.5832736.93950.7153.5963.5962.0...H1-1bRISA-3D Version 17.0.4 Page 44 [C:\...\...\...\...\RISA-3D\Sabre C10837002 THD V-Boom.r3d]
Company : Tower Engineering Professionals, Inc.July 12, 202110:22 AMDesigner : APBJob Number : TEP No. 62749.566934Checked By: DCModel Name : Midway Road (FL10049-A)Envelope AISC 15th(360-16): LRFD Steel Code Checks (Continued)Member Shape Code Check Loc[ft] LC Shear ...Loc[ft] Dir LCphi*Pn...phi*Pn...phi*M...phi*M... Cb Eqn20SA-1PIPE_2.0.131011.00402322.13745.92.6742.6741.1...H1-1b*21SF1-D2SR 3/4.1174.28165.0304.2812011.13719.88.249.2492.3...H1-1b22SF2-D1SR 3/4.117019.0202.142011.13719.88.249.2491.9...H1-1b23SF1-D1SR 3/4.094059.0222.141911.13719.88.249.2492.3...H1-1b24MP-3PIPE_2.5.0855.41719.0635.4172736.93950.7153.5963.5963.2...H1-1b25SF1-V2SR 3/4.081027.0160277.80319.88.249.2492.6...H1-1b26SF2-V2SR 3/4.0802.71919.0172.719277.80319.88.249.2492.1...H1-1bEnvelope None Cold Formed Steel Code ChecksMember Shape Code Che... Loc[ft] LC Shear...Loc[ft] Dir LCPn[k] Tn[k] Mnyy[k-ft]Mnzz[k-ft] Cb Cmyy Cmzz EqnNo Data to Print ...RISA-3D Version 17.0.4 Page 45 [C:\...\...\...\...\RISA-3D\Sabre C10837002 THD V-Boom.r3d]
July 12, 2021
Sector Mount Analysis Midway Road (FL10049-A)
TEP Project Number 62749.566934 Page 5
APPENDIX B
ADDITIONAL CALCULATIONS
Midway Road (FL10049-A)
TEP No.
Analysis By:APB 7/12/2021
Checked By:DC 7/12/2021
Code Revisions:IBC 2018
Tower Type:68.0
Ult. Wind Velocity:160.0 mph Kzt:1.000 Section 2.6.6
Live Load Velocity:30.0 mph Kd:0.950
Ice Wind Velocity:30.0 mph Kz-Mount:1.480 Section 2.6.5.2
Base Ice Thickness:0.00 inches Kz-Antenna:1.480 Section 2.6.5.2
Mount Centerline:210.0 ft Kiz:1.203 Section 2.6.10
Antenna Centerline:210.0 ft Ice Thickness:0.000 inches - Section 2.6.10
Exposure Category:C Kes-wind:1.00 Annex S (Table S-1)
Topo Category:1 Kes-ice:1.00 Annex S (Table S-1)
Risk Category:II Ks:1.00 Section 2.6.7
Ground Elevation:14 ft
(qzGh)Mount:92.07 (qzGh)Mount:3.24
(qzGh)Antenna:92.07 (qzGh)Antenna:3.24
62749.566934
Wind Calculations:
TIA-222-H
3 Sided Guyed Tower
Wind Inputs:
Without Ice - (psf) With Ice - (psf)
Universal Force Generator - V1.8
Midway Road (FL10049-A)TEP No.Analysis By:APB7/12/2021Checked By:DC 7/12/2021Antenna Loads are Calculated in Accordance with TIA-222-HAzimuth is the absolute angle measured clockwise from RISA-3D global X-axis.MFR Model Height (in) Width (in) Depth (in)Wt. (lbs) Azimuth°Qty Shape Member Label Location #1 (ft,%) Location #2 (ft,%) Location #3 (ft,%)JMA Wireless MX08FRO665-21 72.00 20.00 8.00 64.50 0.00 1 Flat MP-1 1.50 6.50Fujitsu TA08025-B605 15.75 14.96 9.05 74.96 90.00 1 Flat MP-1 2.00Fujitsu TA08025-B604 15.75 14.96 7.87 63.93 90.00 1 Flat MP-1 2.00Raycap RDIDC-9181-PF-48 16.57 14.57 8.46 21.85 0.00 1 Flat SF2-TH 1.0062749.566934Distance from start node of the memberUniversal Force Generator - V1.8
Midway Road (FL10049-A)
TEP No.
Analysis By:APB 7/12/2021
Checked By:DC 7/12/2021
Member Forces are Calculated in Accordance with TIA-222-H
Member Name Wind Proj. (in) Length (in) Shape θ (°)Perimeter (in)
FF1-BH1 2.375 132.00 Round 90.00 7.46
FF1-BH2 2.375 132.00 Round 90.00 7.46
FF1-BH3 2.375 132.00 Round 90.00 7.46
FF1-TH1 2.375 132.00 Round 90.00 7.46
FF1-TH2 2.375 132.00 Round 90.00 7.46
FF1-TH3 2.375 132.00 Round 90.00 7.46
FP-1 0.500 3.88 Flat 90.00 5.25
FP-2 0.500 3.88 Flat 90.00 5.25
FP-3 0.500 3.88 Flat 90.00 5.25
FP-4 0.500 3.88 Flat 90.00 5.25
MP-1 2.875 96.00 Round 9.03
MP-2 2.875 96.00 Round 9.03
MP-3 2.875 96.00 Round 9.03
SA-1 2.375 78.30 Round 7.46
SF1-BH 1.900 51.06 Round 54.79 5.97
SF1-D1 0.750 51.37 Round 2.36
SF1-D2 0.750 51.37 Round 2.36
SF1-TH 1.900 51.06 Round 54.79 5.97
SF1-V1 0.750 32.63 Round 2.36
SF1-V2 0.750 32.63 Round 2.36
SF2-BH 1.900 51.06 Round -54.79 5.97
SF2-D1 0.750 51.37 Round 2.36
SF2-D2 0.750 51.37 Round 2.36
SF2-TH 1.900 51.06 Round -54.79 5.97
SF2-V1 0.750 32.63 Round 2.36
SF2-V2 0.750 32.63 Round 2.36
62749.566934
Universal Force Generator V1.8
Midway Road (FL10049-A)
TEP No.
Analysis By:APB 7/12/2021
Checked By:DC 7/12/2021
Moment Bolt Group - Leg Connection
Code Revisions:
Bolt Type:
Bolt Size:0.625 in Single Bolt Capacity =11.7%PASS
# Bolts:4
Plate Width:N/A in Bolt Capacity=9.2%PASS
Plate Height:N/A in
Bolt H Gap:6.5 in
Bolt V Gap:2.0 in
Plate T:N/A in
Slip Member Ø:N/A in
Bolt Grade:A307
Fybolt:36.0 ksi Flat
Fubolt:60.0 ksi 50
r:3.4 in 0.500
J:46.3 in4/in2 65
Abolt:0.3 in2 Agross:4.28 in2
Abolt, Net Tensile:0.2 in2 11 ANet Tensile:3.72 in2
Pretension:9.5 kips
Tn =181.29
No
Bolt Size:1.000 Max Fx:3.703 kip
Bolt Fu:120 ksi Max Fy:1.043 kip
BoltA, Net Tensile:0.606 in2 Max Fz: 1.846 kip
Vmax=4.138 kips
ØRNV =35.343 kips
Tmax =1.043 kips
ØRNT =54.54 kips
62749.566934
Headed Bolts
Connection Inputs:Capacities:
ANSI/TIA-222-H
Bolt Properties:
Single Bolt Check
Mount Single Bolt Connection Check - V1.3