Loading...
HomeMy WebLinkAboutENGINEERED TANK SPECS 11850 APPALOOSA F DocuSign Envelope ID: 19B88110-B558-449D-A611-56BF164BOE27 7/32" GALV. CABLE W/ (2)HDG CLAMPS TO ANCHOR (PULLED TIGHT) 500 MAX GALLON LP GAS TANK "X8"X 12" SOLID CMU BLOCK EA. LEG 5/8"X40" SINGLE 6" HELICAL ANCHOR 2 PAIRS ( ) LAYERS OF 302 # FELT BETWEEN STRAP AND TANK 7/32" GALV. CABLE W/ (2)HDG CLAMPS TO ANCHOR (PULLED TIGHT) 500 MAX GALLON LP GAS TANK "X8"X12" SOLID CMU BLOCK EA. LEG 500 GALLON MAX ABOVEGROUND HORIZONTAL TANK GENERAL NOTES: 1. HELICAL ANCHORS SHALL HAVE AN ALLOWABLE PULL—OUT CAPACITY AS SHOWN BELOW. ANCHORS SHALL BE INSTALLED PER ANCHOR MANUFACTURER TO ACHIEVE STATED LOAD CAPACITY. CAPACITY VARIES WITH SOIL TYPE. VERIFY ANCHOR CAPACITY WITH SOIL TYPE ENCOUNTERED. 500 GAL TANK 2 PAIR AT 1350# EACH HELICAL OR 4 PAIR AT 650# EACH 250 GAL TANK 650# 120 GAL TANK 350# 2. CHECK FOR UNDERGROUND UTILITIES PRIOR TO ANCHOR INSTALLATION 3. LOCATION OF TANK RELATIVE TO ADJACENT STRUCTURES AND FEATURES ARE DEPENDENT UPON LOCAL CODES AND IS THE RESPONSIBILITY OF OTHERS. 4. THE TANK AS SHOWN HAS BEEN DESIGNED TO PREVENT FLOTATION, COLLAPSE, OR LATERAL MOVEMENT DURING THE BASE FLOOD EVENT 5. WIND LOAD DESIGN CRITERIA 160 MPH; EXPOSURE "D"; GCpi N/A; Cf = 0.6 yt;• No 40111 .•;* :of = • •W . o STATE OF -44, Z '0 s'�•0 R 4 �•� COMO OIL AND PROPANE * S ...... �� O;III%0*0` FARLEY ENGINEERING LLC 11850 APPALOOSA CTL: Consulting Engineer #40111 — CA28108 2022-01-31 PORT ST LUCIE, FL 8800 N. U.S. #1, Suite #2 , Sebastian, Florida 32958 (772) 589.6229 (772) 589.2296 fax