HomeMy WebLinkAboutENGINEERED TANK SPECS 11850 APPALOOSA F DocuSign Envelope ID: 19B88110-B558-449D-A611-56BF164BOE27
7/32" GALV. CABLE W/
(2)HDG CLAMPS TO
ANCHOR (PULLED
TIGHT)
500 MAX
GALLON LP
GAS TANK
"X8"X 12" SOLID
CMU BLOCK EA. LEG
5/8"X40" SINGLE 6"
HELICAL ANCHOR
2 PAIRS
( ) LAYERS OF 302
#
FELT BETWEEN STRAP AND TANK
7/32" GALV. CABLE W/
(2)HDG CLAMPS TO
ANCHOR (PULLED
TIGHT)
500 MAX
GALLON LP
GAS TANK
"X8"X12" SOLID
CMU BLOCK EA. LEG
500 GALLON MAX ABOVEGROUND HORIZONTAL TANK
GENERAL NOTES:
1. HELICAL ANCHORS SHALL HAVE AN ALLOWABLE PULL—OUT CAPACITY AS SHOWN BELOW. ANCHORS
SHALL BE INSTALLED PER ANCHOR MANUFACTURER TO ACHIEVE STATED LOAD CAPACITY. CAPACITY
VARIES WITH SOIL TYPE. VERIFY ANCHOR CAPACITY WITH SOIL TYPE ENCOUNTERED.
500 GAL TANK 2 PAIR AT 1350# EACH HELICAL OR 4 PAIR AT 650# EACH
250 GAL TANK 650#
120 GAL TANK 350#
2. CHECK FOR UNDERGROUND UTILITIES PRIOR TO ANCHOR INSTALLATION
3. LOCATION OF TANK RELATIVE TO ADJACENT STRUCTURES AND FEATURES ARE DEPENDENT UPON
LOCAL CODES AND IS THE RESPONSIBILITY OF OTHERS.
4. THE TANK AS SHOWN HAS BEEN DESIGNED TO PREVENT FLOTATION, COLLAPSE, OR LATERAL
MOVEMENT DURING THE BASE FLOOD EVENT
5. WIND LOAD DESIGN CRITERIA
160 MPH; EXPOSURE "D"; GCpi N/A; Cf = 0.6
yt;• No 40111 .•;*
:of =
• •W .
o STATE OF -44, Z
'0 s'�•0 R
4 �•� COMO OIL AND PROPANE
* S ...... ��
O;III%0*0` FARLEY ENGINEERING LLC
11850 APPALOOSA CTL: Consulting Engineer #40111 — CA28108
2022-01-31 PORT ST LUCIE, FL 8800 N. U.S. #1, Suite #2 , Sebastian, Florida 32958
(772) 589.6229 (772) 589.2296 fax