HomeMy WebLinkAboutEvaluation Report ICC-ESICC-ES Evaluation Report ESR-2074
Reissued December 1, 2012
This report is subject to renewal February 1, 2015.
wwwAcc-es.org 1 (800) 423-6687 1 (662) 699-0643 A Subsidiary of the Intemational Code Council®
DIVISION: 08 00 00—OPENINGS
Section: 08 95 00—Vents
REPORT HOLDER:
SMARTVENT PRODUCTS, INC.
450 ANDBRO DRIVE, SUITE 2B
PITMAN, NEW JERSEY 08071
(856) 307-1468 -
www.smartvent.com
eval(&smartvent.com
EVALUATION SUBJECT:
SMART VENT® AUTOMATIC FOUNDATION FLOOD VENTS:
FLOODVENTTM MODEL #1540-520; FLOODVENTTM
STACKING MODEL #1540-521; SMARTVENTTM MODEL
#1540-510; SMARTVENTTM STACKING MODEL #1540-511,
WOOD WALL FLOOD MODEL #1540-570; WOOD WALL
FLOOD OVERHEAD DOOR MODEL #1540-574;
FLOODVENTTM OVERHEAD DOOR MODEL #1540-524;
SMARTVENTTM OVERHEAD DOOR MODEL #1540-514
1.0 EVALUATION SCOPE
Compliance with the following codes:
■ 2009 and 2006 Intemational Building Code® (IBC)
■ 2009 and 2006 International Residential Code® (IRC)
Properties evaluated:
■ Physical operation
■ Water flow
2.0 USES
The Smart Vent® units are automatic foundation flood
vents (AFFVs) employed to equalize hydrostatic pressure
on nonfire-resistance-rated foundation walls, rolling -type
overhead doors and building walls subject to rising or
falling flood waters. The Smart Vent® units are intended for
use where flood hazard areas have been established in
accordance with IBC Section 1612.3 or IRC Section
R3222.1. Certain models also allow natural ventilation in
accordance with Section 1203 of the IBC or Section 408.1
of the IRC.
3.0 DESCRIPTION
3.1 'General:
When subjected to pressure from rising water, the Smart
Vent® AFFVs disengage, then pivot open to allow flow in
either direction to equalize water level and hydrostatic
pressure from one side of the foundation to the other. The
AFFV pivoting door is normally held in the closed position
by a buoyant release device. When subjected to rising
water, the buoyant release device causes the unit to
unlatch, allowing the plate to rotate out of the way and
allow flow. The water level stabilizes, equalizing the lateral
forces. Each unit is fabricated from stainless steel, and
each opening provides 76 square inches (49 032 mm2)
of net free area for flood mitigation in the open position.
The SmartVENTTM Stacking Model #1540-511 and
FloodVENTTM Stacking Model #1540-521 units each
contain two vertically arranged openings per unit, providing
152 square inches (98 064 mm ) of net free area for flood
mitigation in the open position.
3.2 Engineered Opening:
The AFFVs comply with the design principle noted in
Section 2.6.2.2 of ASCE/SEI 24 for a maximum rate of rise
and fall of 5.0 feet per hour (0.423 mm/s). In order to
comply with the engineered opening requirement of
ASCE/SEI 24, Smart Vent AFFVs must be installed in
accordance with Section 4.0.
3.3 Model Sizes:
The FloodVENTTM Model #1540-520, SmartVENTTM Model
#1540-510, FloodVENTTM Overhead Door Model #1540-
524, and SmartVENTTM Overhead Door Model #1540-514
units measure 153/4 inches wide by 73/4 inches high
(400 by 196.9 mm). The Wood Wall Flood Model #1540-
570 and Wood Wall Flood Overhead Door Model #1540-
574 units measure 14 inches wide by 83/4 inches high
(355.6 by 222.25 mm). The SmartVENTTM Stacking Model
#1540-511 and FloodVENTTM Stacking Model #1540-521
units measure 16 inches wide by 16 inches high (406.4 by
406.4 mm).
3.4 Ventilation:
The SmartVENT® Model #1540-510 and SmartVENT®
Overhead Door Model #1540-514 both have screen covers
with 1/4-inch-by-1/4-inch (6.35 by 6.35 mm) openings,
yielding 51 square inches (32 903 mm2) of net free area to
supply natural ventilation. The SmartVENTTM Stacking
Model #1540-511 consists of two Model #1540-510 units in
one assembly, and provides 102 square inches (65 806
mm2) of net free area to supply natural ventilation. Other
AFFVs recognized in this report do not offer natural
ventilation.
4.0 INSTALLATION
SmartVENT® and FloodVENTTm are designed to be
installed into walls or overhead doors of existing or new
construction from the exterior side. Installation of the vents
must be in accordance with the manufacturer's
ICC-ES Evaluation Reports are not to be construed as representing aesthetics or any other attributes not specifically addressed, nor are they to be construed
as an endorsement ofthe subject of the report or a recommendation for its use. There is no warranty by ICC Evaluation Service, LLC, express or implied, as
to any finding or other matter in this report, or as to any product covered by the report.
Copyright © 2012
I�IA�WI
mmwm¢
ioao
Page 1 of 2
ESR-2074 I Most Widely Accepted anF �sted Page 2 of 2
instructions, the applicable code and/ this report. The 5.1 The Smart Vent® AFFVs must be installed in
mounting straps allow mounting in wood, masonry and accordance with this report, the applicable code and
concrete walls up to 12 inches (305 mm) thick. In order to the manufacturer's installation instructions. In the
comply with the engineered opening design principle noted event of a conflict, the instructions in this report
in Section 2.6.2.2 of ASCE/SEI 24, the Smart Vent® AFFVs govern.
must be installed as follows:
■ With a minimum of two openings on different sides of
each enclosed area.
■ With a minimum of one AFFV for every 200 square
feet (18.6 mz) of enclosed area, except that the
SmartVENTTM Stacking Model #1540-511 and
FloodVENTTM Stacking Model #1540-521 must be
installed with a minimum of one AFFV for every 400
square feet (37.2 mz) of enclosed area.
■ Below the base flood elevation.
■ With the bottom of the AFFV located a maximum of
12 inches (305.4 mm) above grade.
5.0 CONDITIONS OF USE
The Smart Vent® AFFVs described in this report comply
with, or are suitable alternatives to what is specified in,
those codes listed in Section 1.0 of this report, subject to
the following conditions:
5.2 The Smart Vent AFFVs must not be used in the
place of "breakaway walls" in coastal high hazard
areas, but are permitted for use in conjunction with
breakaway walls in other areas.
6.0 EVIDENCE SUBMITTED
Data in accordance with the [CC -ES Acceptance Criteria
for Automatic Foundation Flood Vents (AC364), dated
October 2007.
7.0 IDENTIFICATION
The Smart VENT® models recognized in this report must
be identified by a label bearing the manufacturer's name
(Smartvent Products, Inc.), the model number, and the
evaluation report number (ESR-2074).