HomeMy WebLinkAbout23445_Compaction Report_SIGNEDTRIANGLE TESTING LAB, INC.
FL REG.#3101
4750 ROYAL PALM BEACH BOULEVARD
WEST PALM BEACH, FLORIDA 33411
(561)790-3049
e-mail: triangle2992@gmail.com
Date: December 7, 2021
To: The City of Port St. Lucie Building Department
Re: Soil Compaction Report-Density of In-Place Compacted Soil
SYNERGY HOMES - RESIDENCE
8401 S INDIAN RIVER DRIVE
FORT PIERCE, FL
Test Date Test # Test Location Elevation In-Place Readings MMPD Values %
Density Moisture Density Moisture
12/07/21 1 Southeast Area 1’-2’ 107.7 6.8 109.5 5.6 98.4
12/07/21 2 Center Area 0-1’ 108.2 6.1 109.5 5.6 98.8
12/07/21 3 Northwest Area 1’-2’ 108.5 6.5 109.5 5.6 99.1
Remarks: All elevations are measured from top of pad grade. (Mod Proctor Test #1)
Verification Statement
This statement shall serve as verification that the soil beneath the proposed structure has been tested in accordance
with Section R401.4 of the 2020 Florida Building Code, Residential edition. The tests were conducted from the
existing grade.
Density tests were taken at a minimum of three (3) locations throughout the total depth of fill. The depth of fill was
approximately 2.0 feet. The foundation setbacks were based on information furnished by the client, at the time of
testing.
Based on the location and depths tested, we verify that the fill has been compacted to a minimum of 95% of the
maximum dry density as determined by ASTM D-1557 and that the minimum soil bearing value beneath the proposed
foundation area is 2,500 pounds per square foot.
Respectfully submitted,
Richard Boyette, FL PE #42485
Vice President
December 7, 2021
File # 23445
Richard Boyette, State of Florida, Professional
Engineer, License No. 42485
This document has been digitally signed and
sealed by Richard Boyette on the date indicated
here. Printed copies of this document are not
considered signed and sealed and the signature
must be verified on any electronic copies.