HomeMy WebLinkAboutDuct Leakage Test ReportFORM R405-2017
Duct Leakage Test Report -
Residential Perscriptive, Performance or ERI Method Compliance
2017 Florida Building Code, Energy Conservation, 6th Edition
Jurisdiction: Permit Number:
Job Information
E
Builder: Community: Lot:
Address: 6609 Deland Ave Unit:
City: Fort Pierce State: FL Zip: 33951
Duct Leakage Test Results _ - I
System 1
cfm25
System 2
cfm25
System 3
cfm25
Sum of any
additional systems
cfm25
Total of all
systems
cfm25
_ 1318 _ Qn
Total of all Total Conditioned
systems Square Footage
❑ PASS ❑ FAIL
Prescriptive Method cfm25 (Total)
To qualify as "substantially leak free", Qn Total must be less
than or equal to 0.04 if air handler unit is installed. If air handler
unit is not installed,- Qn Total must be less than or equal to
0.03. This testing method meets the requirements in
accordance with Section R403.3.3.
Is the air handler unit installed ❑ YES(- 0.04 on)
during testing? 0 NO (<=0.03On)
❑: Performance / ERI Method cfm25 (Out or Total)
To qualify using this method, Qn must be not greater than the
proposed duct leakage Qn specified -on Form R405-2017 or
R40e-2017.
Leakage Type selected on Form Qn specified on Form R405-2017
R405-2017 (Energy Cato) or R406-2017 (Energy Calc) or R406-2017
Default Leakage
Duct tightness shall be verified by testing in accordance with ANSI/RESNET/ICC380 by either
individuals as defined in Section 553.993(5) or (7), Florida Statutes, or individuals licensed as set
forth in Section 489.105(3)(f), (g) or (i), Florida Statues.
Testing Company, ; ' 1. F
Company Name: Phone:
I hereby verify that the above duct leakage test results are in accordance with the 2017 6th Edition Florida Building Code
Energy Conservation requirements according to the compliance method selected above.
Signature of Tester: Date of Test:
Printed Name of Tester:
License/Certification #: Issuing Authority:
Ri htSuite® Universal 2019 19.0.15 RSU15408 Ri ht-Ener ® Florida 2017 Section 405.4.1 Compliant Software Mar-13 Page 14
wriightsofY° 9 9 sr P Page 14
rwre�r a ,yy d LoadlRight Suitet2020\Ana\Jomilton Jovani.rup Calc = MJ8 Front Door faces: N
Reference Home Characteristics
Jomilton Jovani Loza
6609 Deland Ave
Fort Pierce, FL 33951
Above -grade Walls (Uo)
Above -grade Wall Solar Absorptance
Above -grade Wall Infared Emittance
Basement Walls (Uo)
Above -grade Floors (Uo)
Slab Insulation R-Value
Ceilings (Uo)
Roof Solar Absorptance
Roof Infared Emittance
Attic Vent Area (fF)
Crawlspace VentArea (ft2)
Exposed MasonryFloorArea (ft2)
Carpet & Pad R-Value
Door Area (ftz)
Door U-Factor
North Window Area (ft2)
South Window Area (ftz)
East Window Area (ftz)
West Window Area (ft2)
Window U-Factor
Window SHGC (Heating)
Window SHGC (Cooling)
ACH50
Internal Gains * (Btu/day)
Water'heater gallons per day
Water Heater set point temperature
Water heater efficiency rating
Labeled Heating System Rating and Efficiency
Labeled Cooling System Rating and Efficiency
Air Distribution System Efficiency
Thermostat Type
Heating Thermostat Settings
Title: Jomilton Jovani
FLBase2017
0.084
0.75
0.90
n/a
n/a
0.0
0.030
0.75
0.90
4.38
n/a
262.94
2.0
0.00
n/a
0.00
44.71
44.71
44.71
0.400
0.2169
0.2169
7.00
61578
60.00
120.00
0.94
HSPF = 8.2
SEER = 14.0
0.88
Manual
72.0 (All hours)
TMY City: FL —Fort —Myers -Page