HomeMy WebLinkAboutProject Informationa �
Component Constructions Date:
Entire House By: Eduardo Hernandez
1x7 Fexnt3�rAxerx�4�xaFn esex
CSI Cooling Specialists, Inc.
627 Snowden Dr., Lake Worth, FL 33461 Phone: 561-533-7164 Email: csi000ling@gmail.com Web: www.esicoolingspecialists.com License: CAC1816588
•�ect intormation
For: Jomilton Jovani Loza
6609 Deland Ave, Fort Pierce, FL 33951
Location:
Vero Beach Municipal AP, FL, US
Elevation: 30 ft
Latitude: 28°N
Outdoor: Heating
Dry bulb (T) 43
Dailyrange (T) -
Wet bulb (T) -
Wind speed (mph) 15.0
Indoor:
Indoor temperature (T)
Design TD (T)
Relative humidity (%)
Cooling
Moisture difference (gr/lb)
91
Infiltration:
16 ( L )
Method
78
Shielding / stories
7.5
Pressure / AVF
Heating Cooling
70
75
27
16
50
50
21.9
58.7
Blower door
3 (partial) / 1
50 Pa / 619 cfm
Construction descriptions
Or
Area
U-value
Insul R
Htg HTM
Loss Clg HTM
Gain
fP
Btuh/ft'-°F
ft'-' F/Btuh
BWh/ft'
Btuh
BWh/ft'
Btuh
Walls
13A-5ocs: Blk wall, stucco ext, r-5 ext bd ins, 8" thk, 1/2" gypsum
n
117
0.125
5.0
3.36
393
1.70
199
board int fnsh
ne
19
0.125
5.0
3.36
63
1.70
32
e
205
0.125
5.0
3.36
690
1.70
349
s
332
0.125
5.0
3.36
1116
1.70
564
w
310
0.125
5.0
3.36
1042
1.70
527
nw
19
0.125
5.0
3.36
63
1.70
32
all
1001
0.125
5.0
3.36
3367
1.70
1702
Partitions
12C-Osm: Frm wall, stucco ext, r-13 cav ins, 2"x4" metal frm, 16" o.c.
275
0.115
13.0
3.09
851
1.64
452
stud
Windows
PGT Fixed PW7720 Series: PGT-A-28-00257-00040, L7 3/16 / 0.438 n
19
0.390
0
10.5
201 8.88
170
ARG / GR/CL 7/16 LAM[ PVB, AUN, ARG/AIR (90/10; NFRC rated
(SHG(=0.24); 50% blinds 45°, medium; 50% outdoor insect screen; 12
ft overhang (5.75 ft window ht, 2.6 ft sep.); 6.8 ft head ht
PGT Winguard- SH700 Aluminum Single Hung: 5/16 LAMI 1/8 ANN - .90 n
24
1.070
0
28.8
686 23.3
556
PVB- 1/8ANN; NFRC rated (SHGC=0.65); 50% blinds 45°, medium, 50%
outdoor insect screen; 1.6 ft overhang (5.3 ft window ht, 2.6 ft sep.); a
25
1.070
0
28.8
712 59.1
1461
6.8 ft head ht all
49
1.070
0
28.8
1398 41.5
2017
PGT Fixed PW7720 Series: PGT-A-28-00257-00040, L7 3/16 / 0.438 ne
8
0.390
0
10.5
83 18.0
142
ARG / GR/CL 7/16 LAMI PVB, AUN, ARG/AIR (90/10; NFRC rated
(SHG(=0.24); 50% blinds 45°, medium; 50% outdoor insect screen; 1.6nw
8
0.390
0
10.5
83 18.0
142
ft overhang (5.25 ft window ht, 2.6 ft sep.); 6.8 ft head ht all
16
0.390
0
10.5
165 18.0
284
PGT Winguard- SH700 Aluminum Single Hung: 5/16 LAMI 1/8 ANN - .90 e
7
1.070
0
28.8
213 59.1
436
PVB- 1/8ANN; NFRC rated (SHG(=0.65); 50% blinds45°, medium, 50%
outdoor insect screen; 1.6 ft overhang (3.17 ft window ht, 2.6 ft sep.); w
7
1.070
0
28.8
213 59.1
436
6.8 ft head ht all
15
1.070
0
28.8
425 59.1
873
PGT SGD770 Sliding Glass Door: L7 3/16 / .375 ARG / CUCL 7/16 LAMIs
41
0.650
0
17.5
713 12.2
499
SGP No High Flat Sill, AUAL, ARG/AIR(90/10); NFRC rated
(SHG(=0.22); 50% blinds 45°, medium; 50% outdoor insect screen; 1.6
ft overhang (6.8 ft window ht, 2.6 ft sep.); 6.8 ft head ht
Wrightsoft- 2020-Mar-13 11:49:37
Ae1&..1bn"�.awa.dmt'-. Right -Suite® Universal 2019 19.0.15 RSU15408 Page 1
AGM ...d LoadlRight Suilet2020WnaUomilton Jovani.rup Calc = MJ8 Front Door faces: N
PGT Winguard= SH700 Aluminum Single Hung: 5/16 LAMI 1/8 ANN - .90 s
16
1.070
0
28.8
470
23.3
381
PVB- 1/8ANN; NFRC rated (SHGC=0.65); 50% blinds 45%medium, 50%
outdoor insect screen; 10 ft overhang (5.3 ft window ht, 2.6 ft sep.); s
23
1.070
0
28.8
674
23.3
546
6.8 ft head ht all
40
1.070
0
28.8
1144
23.3
927
Doors
11 P0: Door, mtl pur core type n
21
0.290
10.5
7.80
164
5.36
113
Ceilings
1613-30ad: Attic ceiling, asphalt shingles roof mat, r-30 cell ins, 5/8"
1315
0.032
30.0
0.86
1132
1.69
2217
gypsum board int fnsh
Floors
22A-tph: Bg floor, heavy damp soil, on grade depth, tile fir fnsh
128
1.358
0
36.5
4667
0
0
414- wrlghtsc ft- 2020-Mar-1311:49:37
—M .I-"N-LAa /f�j+q RightSuiteC�Universa1201919.0.15 RSU15408 Paget
...d Load\Right SuiteX2020XAnaUomilton Jovani.rup Calc = MJ8 Front Door faces: N
Project Summary
. Entire House
CSI Cooling Specialists, Inc.
Job:
Date:
By: Eduardo Hernandez
627 Snowden Dr., Lake Worth, FL 33461 Phone: 561-533-7164 Email: csicooling@gmaii.com Web: www.csicoolingspecialists.com License: CAC1816588
Project• •
For: Jomilton Jovani Loza
6609 Deland Ave, Fort Pierce, FL 33951
Notes:
Design Information
Weather: Vero Beach Municipal AP, FL, US
Winter Design Conditions
Summer Design Conditions
Outside db 43 OF
Outside db 91 OF
Inside db 70 OF
Inside db 75 OF
Design TD 27 OF
Design TD 16 OF
Daily range L
Relative humidity 50 %
Moisture difference 59 gr/lb
Heating Summary Sensible Cooling Equipment Load Sizing
Structure
15603 Btuh
Structure
12722
Btuh
Ducts
4585 Btuh
Ducts
6100
Btuh
Central vent (54 cfm)
1586 Btuh
Central vent (54 cfm)
914
Btuh
Outside air
Outside air
Humidification
0 Btuh
Blower
1707
Btuh
Piping
0 Btuh
Equipment load
21774 Btuh
Use manufacturer's data
y
Rate/swing multiplier
Equipment load
1.00
21442
Btuh
Infiltration
sensible
Method
Blower door
Latent Cooling Equipment Load Sizing
Shielding / stories
3 (partial) / 1
Pressure / AVF
50 Pa / 619 cfm
Structure
1851
Btuh
Ducts
1865
Btuh
Central vent (54 cfm)
2139
Btuh
Heating cooling
Outside air
load
5855
Btuh
Area (ft2)
1318 1318
Equipment latent
Volume (fP)
12388 12388
Air changes/hour
0.23 0.13
Equipment Total Load (Sen+Lat)
27297
Btuh
Equiv. AVF (cfm)
47 26
Req. total capacity at 0.70 SHR
2.6
ton
Heating Equipment
Summary
Cooling Equipment
Summary
Make Carrier
Make Carrier
Trade
Trade CARRIER
Model
Cond 24ABC63OA00300
AHRI ref
Coil FX4DNB037L
AHRI ref 9169562
Efficiency
100 EFF
Efficiency 13.0 EER,
16 SEER
Heating input
8.0 kW
Sensible cooling
20160
Btuh
Heating output
27297 Btuh
Latent cooling
8640
Btuh
Temperature rise
26 OF
Total cooling
28800
Btuh
Actual air flow
970 cfm
Actual air flow
970
cfm
Air flow factor
0.048 cfm/Btuh
Air flow factor
0.052
cfm/Btuh
Static pressure
0.40 in H2O
Static pressure
0.40
in H2O
Space thermostat
Load sensible heat ratio
0.79
Bold/italic values have been manually overridden
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
-�- wrigF�tsoft^ RightS2020-Mar-1311:49:37uite®Universal201919.0.15RSU15408 Page
+�+� ...d LoadlRight Sulle120201Ana\Jomilton Jovani.rup Calc = MJ8 Front Door faces: N
Duct System Summary
Entire House
is in�WrtaNMru,Elwosn
CSI Cooling Specialists, Inc.
Job:
Date:
By: Eduardo Hernandez
627 Snowden Dr., Lake Worth, FL 33461 Phone: 561-533-7164 Email: csicooling@gmall.com Web: www.csicoolingspecialists.com License: CAC1816588
Project• •
For: Jomilton Jovani Loza
6609 Deland Ave, Fort Pierce, FL 33951
External static pressure
Pressure losses
Available static pressure
Supply / return available pressure
Lowest friction rate
Actual air flow
Total effective length (TEL)
Heating
0.40 in H2O
0.26 in H2O
0.14 in H2O
0.111 / 0.024 in H2O
0.074 in/100ft
970 cfm
183 ft
Cooling
0.40 in H2O
0.26 in H2O
0.14 in H2O
0.111 / 0.024 in H2O
0.074 in/100ft
970 cfm
Supply Branch Detail Table
Name
Design
(Btuh)
Htg
(cfm)
Clg
(cfm)
Design
FIR
Diam
(in)
H x W
(in)
Duct
Matl
Actual
Ln (ft)
Ftg.Egv
Ln (ft)
Trunk
Bath
c 1248
43
64
0.077
4.0
Ox0
VIFx
24.8
120.0
st2
Bedroom 1
h 4047
194
120
0.074
8.0
Ox 0
VIFx
29.6
120.0
st2
Bedroom 2
h 3588
172
90
0.074
8.0
Ox 0
VIFx
30.5
120.0
st2
Kitchen
c 3118
113
161
0.093
7.0
Ox0
VIFx
19.0
100.0
st1
Living Dining
c 4062
99
209
0.094
8.0
Ox 0
VIFx
18.4
100.0
st1
Master Bathroom
h 1699
82
80
0.128
5.0
Ox 0
VIFx
11.9
75.0
Master Bedroom -A
h 5219
251
231
0.124
9.0
Ox 0
VIFx
14.4
75.0
WIC
h 321
15
15
0.093
4.0
Ox 0
VIFx
19.0
100.0
st1
Supply Trunk Detail Table
Trunk
Htg
Clg
Design
Veloc
Diam
H x W
Duct
Name
Type
(cfm)
(cfm)
FIR
(fpm)
(in)
(in)
Material
Trunk
st2
Peak AVF
410
274
0.074
522
12.0
0 x 0
Vinift
st1
st1
Peak AVF
638
659
0.074
617
14.0
0 x 0
VinlFlx
Return Branch Detail Table
Name
Grille
Size (in)
Htg
(cfm)
Clg
(cfm)
TEL
(ft)
Design
FIR
Veloc
(fpm)
Diam
(in)
H x W
(in)
Stud/Joist
Opening (in)
Duct
Matl
Trunk
rb2
Ox 0
970
970
32.3
0.074
587
11.2
14x 17
RtFg
Bold/italic values have been manually overridden
-+- wrightsoft" 2020-Mar-1311:49:37
�ti ....., ..., �.. �. F.„, Right -Suite® Universal 2019 19.0.15 RSU15408 Page 1
/ +� ...d LoadlRight Suite\20201Ana\Jomilton Jovani.rup Calc = MJ8 Front Door faces: N
M
Manual S Compliance Report Job:
Date:
Entire House By: Eduardo Hernandez
R�.s2��Nli®/R69�r.A 9'�.f
CSI Cooling Specialists, Inc.
627 Snowden Dr., Lake Worth, FL 33461 Phone: 561-533-7164 Email: csicooling@gmail.com Web: www.csicoolingspecialists.com License: CAC1816588
Project• •
For: Jomilton Jovani Loza
6609 Deland Ave, Fort Pierce, FL 33951
Cooling Equipment
Design Conditions
Outdoor design DB:
90.5°F
Sensible gain: 21442 Btuh
Outdoor design WB:
77.7°F
Latent gain: 5855 Btuh
Indoor design DB:
75.0°F
Total gain: 27297 Btuh
Indoor RH:
50%
Estimated airflow: 970 cfm
Manufacturer's Performance Data at Actual Design Conditions
Equipment type: Split AC
Manufacturer: Carrier
Model: 24ABC630A00300+FX4DNB037L
Actual airflow:
970
cfm
Sensible capacity:
22672
Btuh
106% of load
Latent capacity:
5928
Btuh
101% of load
Total capacity:
28600
Btuh
105% of load SHR: 79%
Heating Equipment
Design Conditions
design DB: 43.1°F Heat loss: 21774 Btuh
Indoor design DB: 70.0°F
Manufacturer's Performance Data at Actual Design Conditions
Equipment type: Elec strip
Manufacturer: Carrier Model:
Actual airflow: 970 cfm
Output capacity: 8.0 kW 125% of load
10
Meets all requirements of ACCA Manual S.
Entering coil DB: 79.6°F
Entering coil WB: 65.2°F
Entering coil DB: 67.7°F
Temp. rise: 50 °F
' wrightsoft' 2020-Mar-1311:49:37
�y .e,o•o-n..�-^�rt�P^i RightSuite®Universal 2019 19.0.15 RSU15408 Pa e 1
CrP1 9
...d LoadlRight Suite�20201AnaUomilton Jovani.rup Calc = MJ8 Front Door faces: N
FORM R405-2017
Florida Building Code, Energy Conservation, 6th Edition (2017)
Mandatory Requirements for Residential Performance, Prescriptive and ERI Methods
ADDRESS: 6609 Deland Ave PERMIT #:
Fort Pierce FL 33951
MANDATORY REQUIREMENTS - See individual code sections for full details.
SECTION R401 GENERAL
R401.3 Energy Performance Level (EPL) display card (Mandatory). The building official shall require that an energy performance level (EPL)
display card be completed and certified by the builder to be accurate and correct before final approval of the building for occupancy. Florida law
(Section 553.9085, Florida Statues) requires the EPL display card to be included as an addendum to each sales contract for both presold and
nonpresold residential buildings. The EPL display card contains information indicating the energy performance level and efficiencies of components
installed in a dwelling unit. completed and signed by the builder The building official shall verify that the EPL display card accurately reflects the plans
and specifications submitted to demonstrate compliance for the building. A copy of the EPL display card can be found in Appendix RD.
R402.4 Air leakage (Mandatory). The building thermal envelope shall be constructed to limit air leakage in accordance with the requirements of
Sections R402.4.1 through R402.4.5.
Exception: Dwelling units of R-2 Occupancies and multiple attached single family dwellings shall be permitted to
comply with Section C402.5.
R402A.1 Building thermal envelope. The building thermal envelope shall comply with Sections R402.4.1.1 and R402.4.1.2. The sealing
methods between dissimilar materials shall allow for differential expansion and contraction.
El R402.4.1.1 Installation. The components of the building thermal envelope as listed in Table R402.4.1.1 shall be installed in accordance
w ith the manufacturer's instructions and the criteria listed in Table 402.4.1.1, as applicable to the method of construction. Where required
by the code official, an approved third party shall inspect all components and verify compliance.
. R402.4.1.2 Testing. The building or dwelling unit shall be tested and verified as having an air leakage rate not exceeding seven air
changes per hour in Climate Zones 1 and 2, and three air changes per hour in Climate Zones 3 through 8. Testing shall be conducted in
accordance with ANSI/RESET/ICC 380 and reported at a pressure of 0.2 inch w.g. (50 Pascals). Testing shall be conducted by either
individuals as defined in Section 553.993(5) or (7), Florida Statutes or individuals licensed as set forth in Section 489.105(3)(0(g), or (i) or
an approved third party. A written report of the results of the test shall be signed by the party conducting the test and provided to the code
official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope.
Exception: Testing is not required for additions, alterations, renovations, or repairs, of the building thermal envelope of existing
buildings in which the new construction is less than 85 percent of the building thermal envelope.
During testing:
1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended
weatherstripping or other infiltration control measures.
2. Dampers including exhaust, intake, makeup air, backdraft and flue dampers shall be closed, but not sealed beyond
intended infiltration control measures.
3. Interior doors, if installed at the time of the test, shall be open.
4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed.
5. Heating and cooling systems, if installed at the time of the test, shall be turned off.
6. Supply and return registers, if installed at the time of the test, shall be fully open.
❑ R402.4.2 Fireplaces. New wood -burning fireplaces shall have tight -fitting flue dampers or doors, and outdoor combustion air. Where
using tight -fitting doors on factory -built fireplaces listed and labeledin accordance with UL 127, the doors shall be tested and listed for the
fireplace. Where using tight-figging doors on masonry fireplaces,the doors shall be listed and labeled in accordance with UL 907.
❑ R402.4.3 Fenestration air leakage. Windows, skylights and sliding glass doors shall have an air infiltration rate of no more than 0.3 cfm per
square foot (1.5 Us/m2), and swinging doors no more than 0.5 cfm per square foot (2.6 Us/m2), when tested according to NFRC 400 or
AAMA/WDMA/CSA 101/I.S.2/A440 by an accredited, independent laboratory and listed and labeled by the manufacturer.
Exception: Site -built windows, skylights and doors.
2020-Mar-1311:42:18
wrightsoft& Right -Suite® Universal 2019 19.0.15 RSU15408 Right -Energy® Florida 2017 Section 405.4.1 Compliant Software Page 7
urlcvmrh�.rrf. t. q d Load\Right Suitek2020WnMJomilton Jovani.rup Calc = MJ8 Front Doorfaces: N
FORM R405-2017
MANDATORY REQUIREMENTS -(Continued)
R402.4.4 Rooms containing fuel -burning appliances In Climate Zones 3 through 8, where open combustion air ducts provide combustion air to
open combustion fuel burning appliances, the appliances and combustion air opening shall be located outside the building thermal envelope or
enclosed in a room, isolated from inside the thermal envelope. Such rooms shall be sealed and insulated in accordance with the envelope requirements
of Table R402.1.2, where the walls, floors and ceilings shall meet not less than the basement wall R-value requirement. The door into the room shall be
fully gasketed and any water lines and ducts in the room insulated in accordance with Section R403. The combustion air duct shall be insulated where it
passes through conditioned space to a minimum of R-8.
Exceptions:
1. Direct vent apliances with both intake and exhaust pipes installed continuous to the outside.
2. Fireplaces and stoves complying with Section R402.4.2 and Section R1006 of the Florida Building Code, Residential.
❑ R402.4.5 Recessed lighting. Recessed luminaires installed in the building thermal envelope shall be sealed to limit air leakage
between conditioned and unconditioned spaces. All recessed luminaires shall be IC -rated and labeled as having an air leakage rate not
more than 2.0 cfm (0.944 Us) when tested in accordance with ASTM E283 at a 1.57 psf (75 Pa) pressure differential. All recessed
luminaires shall be sealed with a gasket or caulk between the housing and the interior wall or ceiling covering.
SECTION R403 SYSTEMS
❑ R403.1 Controls
R403.1.1 Thermostat provision (Mandatory). At least one thermostat shall be provided for each separate heating and cooling system.
R403.1.3 Heat pump supplementary heat (Mandatory). Heat pumps having supplementary electric -resistance heat shall have controls
that, except during defrost, prevent supplemental heat operation when the heat pump compressor can meet the heating load.
R403.3.2 Sealing (Mandatory). All ducts, air handlers, filter boxes and building cavities that form the primary air containment passageways
for air distribution systems shall be considered ducts and plenum chambers, shall be constructed and sealed in accordance with Section
C403.2.9.2 of the Commercial Provisions of this code and shall be shown to meet duct tightness criteria below.
Duct tightness shall be verified by testing in accordance with ANSI/RESNET/ICC 380 by either individuals as defined in Section 553.993(5) or (7),
Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(f), (g), or (i), Florida Statutes, to be "substantially leak free" in
accordance with Section R403.3.3.
❑ R403.3.2.1 Sealed air handler. Air handlers shall have a manufacturer's designation for an air leakage of no more than 2 percent
of the design air flow rate when tested in accordance with ASHRAE 193.
R403.3.3 Duct testing. Ducts shall be pressure tested to determine air leakage by one of the following methods:
1. Rough -in test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the system, including the
manufacturer's air handler enclosure if installed at the time of the test. All registers shall be taped or otherwise sealed during the test.
2. Post construction test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the
entire system, including the manufacturer's air handler enclosure. All registers shall be taped or otherwise sealed during the test.
Exceptions:
1. A duct leakage test shall not be required where the ducts and air handlers are located entirely within the building thermal envelope.
2. Duct testing is not mandatory for buildings complying by Section 405 of this code.
A written report of the results of the test shall be signed by the party conducting the test and provided to the code official.
R403.3.5 Building Cavities (Mandatory). Building framing cavities shall not be used as ducts or plenums.
R403.4 Mechanical system piping insulation (Mandatory). Mechanical system piping capable of carrying fluids above 105°F (41°C)
or below 55°F (13°C) shall be insulated to a minimum of R 3.
❑ R403.4.1 Protection of piping Insulation. Piping insulation exposed to weather shall be protected from damage, including that
caused by sunlight, moisture, equipment maintenance, and wind, and shall provide shielding from solar radiation that can cause
degradation of the material. Adhesive tape shall not be permitted.
❑ R403.5.1 Heated water circulation and temperature maintenance systems (Mandatory). Heated water circulation systems shall be in
accordance with Section R403.5.1.1. Heat trace termperature maintenance systems shall be in accordance with Section R403.5.1.2.
Automatic controls, temperature sensors and pumps shall be accessible. Manual controls shall be readily accessible.
❑ R403.5.1.1 Circulation systems. Heated water circulation systems shall be provided with a circulation pump. The system return pipe
shall be dedicated return pipe or a cold water supply pipe. Gravity and thermosiphon circulation systems shall be prohibited!
Controls for circulating hot water system pumps shall start the pump based on the identification of a demand for how water within the
occupancy. The controls shall automatically turn off the pump when the water in the circulation loop is at the desired temperature and
when there is no demand for hot water.
R403.5.1.2 Heat trace systems. Electric heat trace systems shall comply with IEEE 515.1 or UL 515. Controls for such systems
shall automatically adjust the energy input to the heat tracing to maintain the desired water temperature in the piping in accordance
with the times when heated water is used in the occupancy.
Ri ht-Suite® Universal Ri ht-Ener ®Florida2017 Section405.4.1Com Compliant
31Page8
wrightSoft$ 9 9 9Y P � Page 8
arz s•as�orb,acr.�wr ...d Load\Right SuiteX2020WnaUomilton Jovani.rup Calc = MJ8 Front Door faces: N
FORM R405-2017
MANDATORY REQUIREMENTS -(Continued)
R403.5.5 Heat traps (Mandatory). Storage water heaters not equipped with integral heat traps and having vertical pipe risers shall have heat
traps installed on both the inlets and outlets. External heat traps shall consist of either a commercially available heat trap or a
downward and upward bend of at least 3 1/2 inches (89 mm) in the hot water distribution line and cold water line located as close as
possible to the storage tank.
R403.5.6 Water heater efficiencies (Mandatory).
R403.5.6.1 Storage water heater temperature controls.
R403.5.6.1.1 Automatic controls. Service water heating systems shall be equipped with automatic temperature controls capable
of adjustment from the lowest to the highest acceptable temperature settings for the intended use. The minimum temperature
setting range shall be f rom 100°F to 140oF (38°C to 60oC).
11403.5.6.1.2 shut down. A separate switch or a clearly marked circuit breaker shall be provided to permit the power supplied
to electric service systems to be turned off. A separate valve shall be provided to permit the energy supplied to the main burner(s)
of combustion types of service water heating systems to be turned off.
❑ R403.5.6.2 Water heating equipment. Water heating equipment installed in residential units shall meet the minimum efficiencies of
Table C404.2 in Chapter 4 of the Florida Building Code, Energy Conservation, Commercial Provisions, for the type of equipment
installed. Equipment used to provide heating functions as part of a combination system shall satisfy all stated requirements for the
appropriate water heating category. Solar water heaters shall met the criteria of Section R403.5.6.2.1.
R403.5.6.2.1 Solar water heating system. Solar systems for domestic hot water production are rated by the annual solar energy
factor of the system. The solar energy factor of a system shall be determined from the Florida Solar Energy Center Directory of
Certified Solar Systems. Solar collectors shall be tested in accordance with ISO Standard 9806, Test Methods for Solar Collectors,
and SRCC Standard TM-1, Solar Domestic Hot Water System and Component Test Protocol. Collectors in installed solar
water -heating systems should meet the following criteria:
1. Be installed with a tilt angle between 10 degrees and 40 degrees of the horizontal; and
2. Be installed at an orientation within 45 degrees of true south.
❑ R403.6 Mechanical ventilation (Mandatory). The building shall be provided with ventilation that meets the requirements of the Florida
Building Code, Residential or Florida Building Code, Mechanical, as applicable, or with other approved means of ventilation, including:
Natural, Infiltration or Mechanical means. Outdoor air intakes and exhausts shall have automatic or gravity dampers that close when the
ventilation system is not operating.
R403.6.1 Whole -house mechanical ventilation system fan efficacy. When installed to function as a whole -house mechanical
ventilation system, fans shall meet the efficacy requirements of Table R403.6.1.
Exception: Where mechanical ventilation fans are integral to tested and listed HVAC equipment, they shall be powered by
an electronically commutated motor.
❑ R403.6.2 Ventilation air. Residential buildings designed to be operated at a positive indoor pressure of for mechanical
ventilation shall meet the following criteria:
The design air change per hour minimums for residential buildings in ASHRAE 62.2, Ventilation for Acceptable
Indoor Air Quality, shall be the maximum rates allowed for residential applications.
No ventilation or air-conditioning system make-up air shall be provided to conditioned space from attics,
crawlspaces, attached enclosed garages or outdoor spaces adjacent to swimming pools or spas.
If ventilation air is drawn from enclosed spaces(s), then the walls of the space(s) from which air is drawn shall be
insulated to a minimum of R-11 and the ceiling shall be insulated to a minimum or R-19, space permitting, or R-10 otherwise.
R403.7 Heating and cooling equipment (Mandatory).
R403.7.1 Equipment sizing. Heating and cooling equipment shall be sized in accordance with ACCA Manual S based on the
equipment loads calculated in accordance with ACCA Manual J or other approved methodologies, heating and cooling calculation
based on building loads for the directional orientation of the building. The manufacturer and model number of the outdoor and
indoor units (if split system) shall be submitted along with the sensible and total cooling capacities at the design conditions
described in Section R302.1. This code does not allow designer safety factors, provisions for future expansion or other factors that
affect equipment sizing. System sizing calculations shall not include loads created by local intermittent mechanical ventilation such
as standard kitchen and bathroom exhaust systems. New or replacement heating and cooling equipment shall have an efficiency
rating equal to or greater than the minimum required by federal law for the geographic location where the equipment is installed.
TABLE R403.6.1
WHOLE -HOUSE MECHANICAL VENTILATION SYSTEM FAN EFFICACY
FAN LOCATION
AIRFLOW RATE MINIMUM
CFM
MINIMUM EFFICACY (a)
CFMMATT
AIRFLOW RATE MAXIMUM
CFM
Range hoods
Any
2.8 cfm/watt
Any
In -line fan
Any
2.8 cfm/watt
Any
Bathroom, utility room
10
1.4 cfm/watt
< 90
Bathroom, utility room
90
2.8 cfm/watt
Any
For SI: 1 cfm - 28.3 L/min.
(a) When tested in accordance HVI Standard 916
Ri h 2020-Mar-1311:42:18
wrightSofV 9 t-Suite@ Universal Right-Energy®Florida2017 Section Page
A10A"Jd ro" k5ticrag6rt_7 ...d LoadlRight Suite12020WnaUomilton Jovani.rup Calc = MJ8 Front Doorfaces: N
MANDATORY REQUIREMENTS -(Continued)
R403.7.1.1 Cooling equipment capacity. Cooling only equipment shall be selected so that its total capacity is not less
than the calculated total load but not more than 1.15 times greater than the total load calculated according to the procedure selected in
Section 403.7, or the closest available size provided by the manufacturer's product lines. The corresponding latent capacity of the
equipment shall not be less than the calculated latent load.
The published value for AHRltotal capacity is a nominal, rating -test value and shall not be used for equipment sizing. Manufacturer's
expanded performance data shall be used to select cooling -only equipment. This selection shall be based on the outdoor design dry-bulb
temperature for the load calculation (or entering water temperature for water -source equipment), the blower CFM provided by the expanded
performance data, the design value for entering wet -bulb temperature and the design value for entering dry-bulb temperature
Design values for entering wet -bulb and dry-bulb temperatures shall be for the indoor dry bulb and relative humidity used for the load
calculation and shall be adjusted for return side gains if the return duct(s) is installed in an unconditioned space.
Exceptions:
1. Attached single- and multiple -family residential equipment sizing may be selected so that its cooling capacity is
less than the calculated total sensible load but not less than 80 percent of that load.
2. When signed and sealed by a Florida -registered engineer, in attached single- and multiple -family units, the
capacity of equipment may be sized in accordance with good design practice.
R403.7.1.2 Heating equipment capacity.
R403.7.1.2.1 Heat pumps Heat pump sizing shall be based on the cooling requirements as calculated according to Section
R403.7.1.1, and the heat pump total cooling capacity shall not be more than 1.15 times greater than the design cooling load even if
the design heating load is 1.15 times greater than the design cooling load.
R403.7.1.2.2 Electric resistance furnaces. Electric resistance furnaces shall be sized within 4 kW of the design
requirements calculated according to the procedure selected in Section R403.7.1
R403.7.1.2.3 Fossil fuel heating equipment. The capacity of fossil fuel heating equipment with natural draft atmospheric burners
shall not be less than the design load calculated in accordance with Section R403.7.1.
R403.7.1.3 Extra capacity required for special occasions. Residences requiring excess cooling or heating equipment capacity on an
intermittent basis, such as anticipated additional loads caused by major entertainment events, shall have equipment sized or controlled to
prevent continuous space cooling or heating within that space by one or more of the following options:
1. A separate cooling or heating system is utilized to provide cooling or heating to the major entertainment areas.
2. A variable capacity system sized for optimum performance during base load periods is utilized.
R403.8 Systems serving multiple dwelling units (Mandatory). Systems serving multiple dwelling units shall comply with Sections
0403 and C404 of the IECC—Commercial Provisions in lieu of Section R403.
El R403.9 Snow melt and Ice system controls (Mandatory). Snow- and ice -melting systems, supplied through energy service to the building,
shall include automatic controls capable of shutting off the systemw hen the pavement temperature is above 50°F (10°C), and no
precipitation is falling and an automatic or manual control that w ill allow shutoff when the outdoor temperature is above 40°F (4.8°C).
R403.10 Pools and permanent spa energy consumption (Mandatory). The energy consumption of pools and permanent spas
shall be in accordance with Sections R403.10.1 through R403.10.5.
R403.10.1 Heaters. The electric power to heaters shall be controlled by a readily accessible on -off switch that is an
integral part of the heater mounted on the exterior of the heater, or external to and within 3 feet (914 mm) of the heater. Operation
of such switch shall not change the setting of the heater thermostat. Such switches shall be in addition to a circuit breaker for the
power to the heater. Gas -fired heaters shall not be equipped with continuously burning ignition pilots.
R403.10.2 Time switches. Time switches or other control methods that can automatically turn off and on according to a preset schedule
shall be installed for heaters and pump motors. Heaters and pump motors that have built-in time switches shall be in compliance with this
section.
Exceptions:
1. Where public health standards require 24-hour pump operations.
2. Pumps that operate solar- and waste -heat -recovery pool heating systems.
3. Where pumps are powered exclusively from on -site renewable generation.
R403.10.3 Covers. Outdoor heated swimming pools and outdoor permanent spas shall be equipped with a vapor- retardant cover on or at
the water surface or a liquid cover or other means proven to reduce heat loss.
Exception: Where more than 70 percent of the energy for heating, computed over an operation season, is from site -recovered
energy, such as from a heat pump or solar energy source, covers or other vapor -retardant means shall not be required.
R403.10.4 Gas- and oil -fired pool and spa heaters. All gas- and oil -fired pool and spa heaters shall have a minimum thermal
efficiency of 82 percent for heaters manufactured on or after April 16, 2013, when tested in accordance with ANSI Z 21.56. Pool
heaters fired by natural or LP gas shall not have continuously burning pilot lights.
2020-Mar-13 11:42:18
wrightsaW Right -Suite® Universal2019 19.0.15 RSU15408 Right -Energy® Florida 2017 Section 405.4.1 Compliant Software Page 10
ewrrris r.�.�pw r d LoadlRight Suitet2020Wna\JomiltonJovani.rup Calc = MJ8 Front Door faces: N
MANDATORY REQUIREMENTS - (Continued)
R403.10.5 Heat pump pool heaters. Heat pump pool heaters shall have a minimum COP of 4.0 when tested in accordance
with AHRI 1160, Table 2, Standard Rating Conditions -Low Air Temperature. A test report from an independent laboratory is
required to verify procedure compliance. Geothermal swimming pool heat pumps are not required to meet this standard.
R403.11 Portable spas (Mandatory). The energy consumption of electric -powered portable spas shall be controlled by the
requirements of APSP-14.
SECTION R404
ELECTRICAL POWER AND LIGHTING SYSTEMS
R404.1 Lighting equipment (Mandatory). Not less than 75 percent of the lamps in permanently installed lighting fixtures shall be
high -efficacy lamps or not less than 75 percent of the permanently installed lighting fixtures shall contain only high -efficacy lamps.
Exception: Low -voltage lighting.
R404.1.1 Lighting equipment (Mandatory). Fuel gas lighting systems shall not have continuously burning pilot lights.
2020-Mar-13 11:42:18
wright offV RightSuite®Universal201919.0.15RSU16408 Right-Energy®Florida 2017 Section 405.4.1Compliant Saftware Page11
a�xrt{r rat r q d LoadlRight Suite\2020V1na\Jomilton Jovani.rup Calc = MJ8 Front Door faces: N
FORM R405-2017
TABLE 402.4.1.1
AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA
Project Name: Builder Name
Street: 6609 Deland Ave Permit Office:
City, State, Zip: FortPierce, FL 33951 Permit Number:
Owner: Jomilton Jovani Loza Jurisdiction:
Design Location: FL, Vero Beach Municipal AP
COMPONENT
AIR BARRIER CRITERIA
INSULATION INSTALLATION CRITERIA
✓
General
A continuous air barrier shall be Installed In the
requirements
4
building envelope. The exterior thermal envelope
Air -permeable Insulation shall not be used as a
pp
9
❑
contains a continuous barrier. Breaks or joints in the
air barrier shall be sealed.
Ceiling/attic
The air barrier in any dropped ceiling/soffit
The Insulation in any dropped ceiling/soffit
shall be aligned with the insulation and any
shall be aligned with the air barrier.
gaps In the air barrier shall be sealed.
El
Access openings, drop down stairs or knee wall doors
to unconditioned attics paces shall be sealed.
Walls
The junction of the foundation and sill plate
Cavities with corners and headers of frame walls
shall be sealed.The junction of the top plate
shall be insulated by completely filling the cavity
and the top of exterior walls shall be sealed.
with a material having a thermal resistance of R-3
Knee walls shall be sealed.
per inch minimum.
Exterior thermal envelope Insulation for framed
walls shall be Installed in substantial contact and
continuous alignment with the air barrier
Windows, skylights
doors
The space between window/door jambs and framing,
and skylights and framing shall be sealed.
❑
and
Rim joists are insulated and include an air
Rim joists shall be insulated.
❑
Rim joists
barrier.
Floors (including
The air barrier shall be Installed at any exposed
Floor framing cavity Insulation shall be installed
above -garage and
edge of Insulation.
to maintain permanent contact with the underside
cantilevered floors)
of subfloor decking, or floor framing cavity
Insulation shall be permitted to be in contact
El
the top sldeof sheathing, or continuous
Insulation installed on the underside of floor
framing and extends from the bottom to the top of
all perimeter floor framing members.
Crawl space
Exposed earth in unvented crawl spaces shall be
Where provided In lieu of floor Insulation,
walls
covered with a Class I vapor retarder with
Insulation shall be permanently attached
❑
overlapping joints taped.
to the crawlspace walls.
Shafts, penetrations
Duct shafts, utility penetrations, and flue shaft
openings to exterior or unconditioned space shall
❑
be sealed.
Narrow cavities
Batts in narrow cavities shall be cut to fit, or
narrow cavities shall be filled by insulation that
❑
on installation readily conforms to the available
cavity spaces.
Garage
Air sealing shall be provided between the garage
❑
separation
and conditioned spaces.
Recessed
Recessed light fixtures Installed in the building
Recessed light fixtures installed In the
lighting
thermal envelope shall be sealed to the drywall.
building thermal envelope shall be air tight
❑
and IC rated.
Plumbing and
Batt insulation shall be cut neatly to fit around
wiring
wiring and plumbing in exterior walls, or
Insulation that on Installation readily conforms
❑
to available space shall extend behind piping
and wiring.
Shower/tub on
The air barrier shall be installed behind
Exterior walls adjacent to showers and tubs
exterior wall
electrical or communication boxes or air -sealed
shall be insulated.
❑
boxes shall be Installed.
Electrical/phone
The air barrier shall be Installed behind
box on exterior
electrical or communication boxes or air -sealed
❑
walls
boxes shall be installed.
HVAC register
HVAC register boots that penetrate building
boots
thermal envelope shall be sealed to the subfloor
❑
or drywall.
Concealed
When required to be sealed, concealed fire
sprinklers
sprinklers shall only be sealed in a manner that
Is recommended by the manufacturer.
❑
Caulking or other adhesive sealants shall not be
used to fill voids between fire sprinkler cover
plates and walls or ceilings.
a. In addition, inspection of log walls shall be in accordance with the provisions of ICC-400.
wa0-Mar-131 1
wrightsot6Right-Suite® Universal2019 19.0.15 RSU15408 Right-Energy®Flodda2017 Section Compliant 12
ar�sry .r �,q d Load\Right Suite\2020\Ana\Jomlllon Jovani.rup Calc = MJ8 Front Door faces: N