Press Alt + R to read the document text or Alt + P to download or print.
This document contains no pages.
HomeMy WebLinkAboutHVAC Test & BalanceT�
,1 __ 4
The Ai rtex Corporation
HVAC Systems — Specialty Metals
Commercial / Industrial '
CA01815780 CSCIII0262
Submittal Data
Project: PGA lClubhouse at The Reserve
Architect: Basham & Lucas Design Group, Inc
Inc.
General Contractor: Kast Construction
Mechanical Contractor: The Airtex Corporation
Item Submitted: Test and Balance
Specification Section: 1
Manufacturer: Air L
Inc.
Supplier: Air Logic Services, Inc.
The attached items are being submitted for:
■ Approval
❑ Re -submittal
❑ Record Purposes
❑ For Review Only
❑ Com Hance Submittal
P
JUL 1 3 BAD D
=�13
To the best of my knowledge, and belief, the attached
material/equipment is in compliance with the approved plans and
specifications.
Submitted By: Daniela Naranjo
Date: July 7th, 2015
1 4SO - B Skeen Road West Palm Beach, Florida aa41 1
Phone 501-6ea-a446 Fax 561 -SOS-a41 4
Alrtexcorp.com
I ;:i
4
Air Logic Services, Inc.
8973 SW 212 LANE
CUTLER BAY, FLORIDA 33189
PGA CLUBHOUSE @ THE RESERVE
1916 PERFECT DRIVE PORT ST. LUCIE, FLORIDA 34986
HVAC TEST & BALANCE - JUNE 2015
N AAA
F ", w @-
PHONE: (305) 971- 9672 office@airiogicservices.com FAX: (305) 971- 6649
Air Logic Services, Inc.
Pri
CERTIFIED TEST, ADJUST, AND
BALANCE REPORT
JUNE 22, 2015
PROJECT:
PGA CLUBHOUSE @ THE RESERVE
1916 PERFECT DRIVE
PORT ST. LUCIE, FLORIDA 34986
DESIGN ENGINEER:
GREGORY ENGINEERING, INC.
'4567 DEEP RIVER PLACE
JACKSONVILLE, FLORIDA 32224
i
HVAC CONTRACTOR:
THE AIRTEX CORPORATION
1450-B SKEES ROAD
WEST PALM BEACH, FLORIDA 33411
NEBB TAB FIRM:
AIR LOGIC SERVICES, INC.
8973 SW 212 LANE
CUTLER BAY, FLORIDA 33189
CERTIFICATION #3443
I Page 1 of 31
y " i
Air Logic Services, Inc.
PROJECT:
PGA CLUBHOUSE @ THE RESERVE
1916 PERFECT DRIVE
PORT ST. LUCIE, FLORIDA 34986
THE DATA REPRESENTED IN THIS REPORT IS A RECORD OF SYSTEM MEASUREMENTS AND FINAL
ADJUSTMENTS THAT HAVE BEEN OBTAINED IN ACCORDANCE WITH THE CURRENT EDITION OF THE
NEBB PROCEDURAL STANDARDS FOR TESTING, ADJUSTING AND BALANCING OF ENVIRONMENTAL
SYSTEMS. ANY VARIANCES FROM DESIGN QUANTITIES, WHICH EXCEED NEBB TOLERANCES, ARE
NOTED IN THE TEST -ADJUST -BALANCE REPORT PROJECT SUMMARY.
SUBMITTED AND CERTIFIED BY:
CERTIFICATION #:
CERTIFICATION EXPIRATION DATE:
JUNE 30, 2015
DATE
AIR LOGIC SERVICES, INC.
3443
MARCH,31, 2017
wIli
czam
ROBIN A: BLANK
CERTIFICATION
3443
Exp. W31/17
2� �4 ���
ROBIN BLANK
Page 2 of 31
Air Logic Services, Inc.
TABLE OF CONTENTS
Project: 1 PGA CLUBHOUSE @ THE RESERVE
Address: 1916 PERFECT DRIVE, PORT ST. LUCIE, FLORIDA 34986
SECTION
DESCRIPTION
PAGES
I
COVER PAGE
-
PROJECT INFORMATION
1
NEBB CERTIFICATION
2
1
TABLE OF CONTENTS
3
1
COVER LETTER
4
II
ROOFTOP UNITS
5 -15
III
EVAPORATORS
16 -17
IV
FANS
18 -19
V
AIR DISTRIBUTION SCHEDULE
20 - 23
VI
EQUIPMENT PICTURES
24 - 25
VII
EQUIPMENT SUBMITTAL DATA
26 - 29
VIII
INSTRUMENT CALIBRATION INFORMATION
30 - 31
Page 3 of 31
1M
Air Logic Services, Inc.
8973 SW 212 LANE
CUTLER BAY, FLORIDA 33189
i
I'
PHONE: (305) 971 - 9672 OFFICE@AIRLOGICSERVICES.COM
i
The Airtex Corporation
1450-B Skees Road
West Palm Beach, Florida 33411
Attention: Ms. Daniela Naranjo
Subject: HVAC Test and Balance
Reference: PGA Clubhouse @ The Reserve
1916 Perfect Drive
Port St. Lucie, Florida 34986
FAX. (305) 971 - 6649
�f-. -,�R
ROBIN A. BLANK
CERTIFICATION
3443
Exp. WV17
Ms. Naranjo,
On Wednesday, June 24, 2015, we completed our test and balance procedures for the
HVAC system installed and operating at the above referenced project. The following field data and
general comments are for your information and affirmative action:
GENERAL COMMENTS:
1 Total air quantities were determined by pitot tube traverse of the main supply, exhaust,
and outside air ducts where available.
2 Individual airflow quantities measured by digital flowhood manufactured by Alnor.
OBSERVATIONS:
1 There is no access above the ceiling. All balancing was performed using the opposed
blade dampers at each diffuser.
2 There is no balancing damper installed serving the exhaust diffuser in Women's Toilet
144. There is no means to reduce air quantity.
3 The opposed blade dampers on the supply diffusers serving the Men's Locker Room were
closed 100% during balancing procedures. These grills are excessively noisy.
For any questions please contact our office at your convenience, thank you.
JUNE 30, 2015
DATE:
1
-G-2L�cz�
ROBIN BLANK
Page 4 of 31
i I
Air -Logic Services, Inc.
Project: ,PGA CLUBHOUSE @ THE RESERVE
Address: 1916 PERFECT DRIVE, PORT ST. LUCIE, FLORIDA 34986
ROOFTOP UNITS
Page 5 of 31
9 4
Air Logic Services, Inc.
Project: PGA CLUBHOUSE @ THE RESERVE
Address: 1 1916 PERFECT DRIVE, PORT ST. LUCIE, FLORIDA 34986
Rooftop Unit # 1 .
Location:"
Roof
Serves:"c' .
Meeting /Ante Rooms
.; Make':
Trane
-Type:.
Horizontal Draw Thru
Model
WSC036,E3RBAlGB
Nc Fansc '-'
1
Serial
150312498E
FanType-.`
Forward Curve
MotorRPM
1725
Motor Sheave'x'Shaft ;;
1VL34 x 5/8
Center„Diameter ? .;,
8"
Fan.Sheave`x>Shaft''';;;'°
AK51 x 3/4
Belt Adjustment,:`,
Min out
-,,Belt'(s): :::'
AX26
Description: •.
Design
'Actual:= :,. -
Calculation / Factors
Notesa ,
Fan°RPM
-
887.
�Motor'Size / SF . , `
1 / 1.15 ,
1 / 1.15
;:Volts/Phase%Cycle
230 / 3 / t0
210 / 210 / 212
Amps
5
2.4 / 2.2 / 2.5
Frame
56
56
CFM'.
1,075
1,080
100%
OA.CFM
150
135
90%
Pre'-Filter 'StMic:. e
- !
.4"
Pre-CHW,Coil'Static:;,.
=
.44"
Fan Suction Static:.:
-
.53"
Discharge Static:
-
.38"
External Static Dress
.6"
.78"
TotaFStatc Press. <'
-
91"
APD- .:,,;
-
.09"
~OA Temperature `";
95 / 74
88 / 78
Mixed Air Temp: `;;,'-.,
80 / 67
74 / 66
Leaving Air`Temp::"'
58 / 55.6
55 / 54
Total BTUH
37,220
39,457
106%
Readings By: Billy Lambert
Date:06/23/2015
Page 6 of 31
Air Logic Services, Inc.
Project: I PGA CLUBHOUSE @ THE RESERVE
Address: 1916 PERFECT DRIVE, PORT ST. LUCIE, FLORIDA 34986
i
Rooftop Unit # 1 Compressor Data
:Compressor #411
pesign. `:"
Actual:
Notes:.
Volts
209/3/60
210/210/212
Amps
113.5
11.4/9.9/11.4
Suction:
-
140
a.. _ Discharge:
-
340
Condenser -Fans
11115
Direct Drive
HP .
.25
.25
Volts"
208 / 1 / 60
210
Ampsr .. ..
1.3
1
Electric Duct Heater
Description:
Design:
Actual:
Notes:
KW''
14.5
4.5
VOLTS
208/3/60
210/210/212
AMPS
.12.5
13.8/13.4/13.5
Readings By: Billy Lambert Date: 06/23/2015 Page 7 of 31
Air Logic Services,, Inc.
Project: I PGA CLUBHOUSE @ THE RESERVE
Address: 1 1916 PERFECT DRIVE, PORT ST. LUCIE, FLORIDA 34986
Rooftop Unit # 2
Location::;,'
j Roof'
Serves:: .,:
Toilets / Lockers /Gallery
'Make
Trane
:' Type. _.
Horizontal Draw Thru
Model
WSC03613R13A1GB
N'o. Fans:`
1
`,. Serial . t`
150312484E
fan Type::':`
Forward Curve
Motor;RPM ` °`
1725
Motor"Sheave,x Shaft;
1VL34 x 5/8
Center Diameter; ',
71/2
"Fan -Sheave xShaft. ;,;
AK51 x 3/4
Belt; Ad"ustmentc r`
Max / Out
Belt; :'
AX26
Desch tion ,
Deli n "
Actualc"
Calculation .Factors
- Notes:
FanRPM_1
1092
Motor.Size [SF . ',
1 / 1.5 1
1 / 1.15
Volts/Phase/Cycle :
208 / 3 / 60
211 / 209 / 209
A' rnp&i
2.5 j
2.9/2.8/2.7
Frame
56
56
CFM
1,200 1
1,170
98%
Oq CFM ;`
300 i
275
92%
Pre -Filter Static::`=:
j
.95"
Pre- CHW,CoilfSta tic:,
-
.98"
FanucnStac
1.08"io
Mischarge�Static:,
-
.3"
_'Otern'al Static Press:.
.6" 1
1.25"
:.Totai:Static Press l
-
1.38"
"Coil`'-APD .: ,:,
-
.1"
,�'OA Temperature'!,',
95 / 79
88 / 78
Mixed'!Air-Temp;,'":
80 / 67
84 / 68
Leaving AWTemp. ` .
59 / 56.7
60 / 57.3
Total"BTUH
38,030
40,350
106%
Readings By: Billy Lambert Date: 06/23/2015 Page 8 of 31
Air Logic Services, Inc.
Proiect: I PGA CLUBHOUSE Ca) THE RESERVE
lAddress: I 1916 PERFECT. DRIVE, PORT ST. LUCIE, FLORIDA 34986
p Unit # 2 Compressor Data
Compressor # 1
74 `Design ::
Ac'tual•.
Notes:
Volts "
208 / 3 / 60
209 / 209 / 211
Amps
13.5
12 / 12.2 / 10.8
.: Suction'.
-
145
Discharge
-
350
Condenser.Fans
RPM " '
�1115
Direct Drive
Hf? :
.25
.25
,.:.;Volts`
208 / 1 / 60
209
mps
1.3
1.1
Electric Duct Heater
',,'be scription. ,-
:. Design
Actual
Notes:
KW f
14.5
4.5 .
VOLTS
20$
/ 3 / 60
209
, :,AMP5
112.5
12/10.3/12.7
Readings By: Billy Lambert Date: 06/23/2015 Page 9 of 31
Air Logic Services, Inc.
Project: PGA CLUBHOUSE @ THE RESERVE
Address: 1916 PERFECT DRIVE, PORT ST. LUCIE, FLORIDA 34986
Rooftop Unit # 3
Location: Roof
Toilets / Lockers / Gallery
Makes
Trane
Type:
Horizontal Draw Thru
Model -
WSC
No Fans: °.
1
Serial: -
15031263LL
Fan Type:
Forward Curve
Nlotor'RPM..-" `
1725
,,'Motor Sheave x Shaft:,
1VL40 x 5/8
Cen#er Diameter,:
11
Fan Sheave x Shaft:
AK64 x 1
Belt, Adjustment:
Mid / Out
Belt:
AX35
Description:..
Design";
,Actual:'
Calculation / Factors.
Notes:
Fan•RPM, ,
-
847
,Motor Size/SF
1/1.5
1/1.5
Volts/Phase/Cycle
208 / 3 / 60
209 / 209 / 211
Amps,'.
3.6
3.7/3.8/3.3
-" Frame
56
56
CFM
2,7001
2,715
101%
'. QA CFM :....
425
390
92%
Pre- Filter Static:
-
.35"
Ore-CHW Coll Static:
-
.36"
;Fan Suction Static:.
-
.59"
Discharge Static:
-
.71"
External Static Press.
.6"
1.06"
.TotalStatic Press. ..
-
1.3"
Coil APD
-
.23"
OA Temperature
95 / 79
88 / 78
Mixed Air Temp.,
80 / 67
82 / 68
Leaving Air Temp.
56.9 / 55.8
60 / 57
Total BTUH
92,330
95,929
104%
Readings By: Billy Lambert Date: 06/23/2015 Page 10 of 31
Air Logic Services, Inc.
jProject: I , PGA CLUBHOUSE @ THE RESERVE
jAddress: 1 1916 PERFECT DRIVE, PORT ST. LUCIE, FLORIDA 34986
Unit # 3 Compressor Data
Compressor # 1: ' .
,Design , y
Actual:: -
Notes:
Volts
208 / 3 / 60
209 / 211 / 211
Amps
25
20.6 / 23.5 / 22.6
=-'Suction:
-
140
Discharge:
-
390
Condenser:Fans
RPM'• ".'
-
Direct Drive
HP'
.75
.75
Volts
208 % 1 / 60
209
Amps
3.5
3.1
Electric Duct Heater
Description:
Design:
Actual:.
Notes:
KIlV>
13.5
13.5
VOLTS ...
2081/ 3 / 60
211 / 209 / 209
" AMPS
37.5
38 / 37.8 / 40
Readings By: Billy Lambert Date: 06/23/2015 Page 11 of 31
Air Logic Services, Inc.
Project: PGA CLUBHOUSE @ THE RESERVE
Address: 1916 PERFECT DRIVE, PORT ST. LUCIE, FLORIDA 34986
Rooftop Unit # 4
Location Roof
Serves: Member Dining
I
,. ,Make:.
Trane
Type:,,,
Horizontal Draw Thru
. ; Model
WSC12DE3RGAOKB
No6�Fans:,
1
. —. Serial,
1502128191-
Farr Type:
Forward Curve
Description. ;° =°
:d ., :..,Design
._Actual:
Calcufa, tion [Factors
.:Notes.* .
Fan; RPM
-
Direct drive
;Volts/Phase/Cycle,'
208 / 3 /j60
207 / 207 / 209
., Ainps..,
NA
1
1.8 / 1.6 / 1.9
1
CFM'
3,6001
3,310
92
OA CFM
750 j
790
105%
Pre -Filter Static:
-
.36"
Pre' -CAW. Coil Static::
-
.39"
Fan Suction -Static:
-
.51"
Discharge Static:
-
26"
External Static Press.
.6"
.62"
;Total Static Press'.
77"
Coil APD , ,..
-
.12"
OATemperature
95 / 79'
88 / 78
°, Mixed Airjemp, -
80 / 67
82 / 67
Leaving Air Temp. -:
56.3 / 55.8
54.5 / 54
Total''BTUH "'
123,440
132,565
107%
NOTE:
Fan motor nameplate not available.
Readings By: Billy Lambert Date: 06/23/2015 Page 12 of 31
Air Logic Services, Inc.
Project: PGA CLUBHOUSE @ THE RESERVE
Address: 1916 PERFECT DRIVE, PORT ST. LUCIE, FLORIDA 34986
Rooftop Unit # 4 Compressor Data
i
Compressor # 1:'
_'' :Design
Actual:
:' Notes:.,'
208 / 3 / 60
207 / 207 / 209
Amps
1,8.1
15.3 / 14.6 / 14.8
Suction:: '
! -
140
Discharge:
-
370
tompre'ssor # 2:..
j
Volts ' .;
208 % 3 / 60
207 / 207 / 209
'k"
18.1
15.3/16.8/16
:Suction:
j -
125
Discharge:
-
380
-Coridenser Fans
1
1
HIP
:75
.75
Volts
208 / 1 / 60
209
Amps
2.7
2.3/1.9/2
Electric Duct Heater
Descriptibm.
Design: °
Actual:
'Notes:
KW"''
13.5
13.5
VOLTS
208 / 3 / 60
209 / 207 / 207
-TAMPS
37.5
38 / 39.5 / 38.2
Readings By: Billy Lambert Date: 06/23/2015 Page 13 of 31
Air Logic Services, Inc.
lProject: l PGA CLUBHOUSE @ THE RESERVE
lAddress: 1 1916 PERFECT DRIVE, PORT ST. LUCIE, FLORIDA 34986 1
Rooftop Unit # 5
Location
Roof
Serves
Member Bar
Make
Trane
Type; . ,
Horizontal Draw Thru
{ ;: Model n'
WSC090E3RGAOJB
No Fansi'
1
Serial'
15031Z624L
Fan Type:',
Forward. Curve
Motor RPM -
1725
IVlotor Sheave; -Shaft:
1VL40 x 5/8
CeMeri'Diametera'
11"
;Fan Sheave x Shaft: `
A64 x 1
Belt Adjustment `
Max / Out
Belt `
AX35
-Description
Design : `
., Actualc-, , :.
,Calculation"/ Factors
Notes:
Fen RPM
-
986
„Motor Sie / SF ,°
1 / 1.5 1
1 / 1.5
,Volts/Phase/Cycie'_
208 / 3 / 60
209 / 209 / 211
Amps
3.6
4.6/4.4/4.4
Frame:"
56
56
`` C•FM,
2,800
2,595
93%
OA CFM
500
460
92%
Pre"4ilter Static:
-
.42"
Pre-CHW Coil Static:
-
.44"
Fan`8ucton Static;;.,
-
.61"
-'Discharge Static:
- !
1.29"
External Static Press:.
.6"
1.71" -
Total'Static P,ress.; ;:
-
1.9" '
Coil APD
-
.17"
OA"Te"mperatu`re;.'`'
95 / 79
8i3 / 78
Mixed; Air Temp;,
80 / 67
87 / 69
'Leaving Air Temp. '
57.5 / 56.2
60 / 58
Total-BTUH `, .:
92,890
93,883
101%
NOTE:
Motor pulley is at max pitch diameter.
Readings By: Billy Lambert Date: 06/23/2015 Page 14 of 31
In
Air Logic Services, Inc.
Project: I PGA CLUBHOUSE @ THE RESERVE
Address: 1916 PERFECT DRIVE, PORT ST. LUCIE, FLORIDA 34986
p Unit # 5 Compressor Data
Compressor
Design.
:Actual
Notes
`'``Volts
208
% 3 / 60
209 / 209 / 211
;`Amps
125
22.1 / 23.3 / 22.8
Suction
-
150
Discharge
-
380
Condenser Fans:"::
c
RPM
1100
Direct Drive
HP;
75
.75
Volts i
208 % 1 / 60
209
Amps
3.5
2.5
Electric Duct Heater
Description
Design
Actual.
Notes:
KW ,
13.5
13.5
' VOLTS
208/ 3 / 60
209 / 209 / 211.
AMPS j
37.5
40 / 40.8 / 38.3
Readings By: Billy Lambert Date: 06/23/2015 Page 15 of 31
w
Air Logic Services, Inc.
(Project: I I PGA CLUBHOUSE @ THE RESERVE
(Address: 1 1916 PERFECT DRIVE, PORT ST. LUCIE, FLORIDA 34986
EVAPORATORS
Page 16 of 31
of
Air Logic Services, Inc.
Project: I 'PGA CLUBHOUSE @ THE RESERVE
Address: 1 1916 PERFECT DRIVE, PORT ST. LUCIE, FLORIDA 34986
Evaporators
Location . :.I
Kitchen
Server's: ;
Kitchen
Make
Trane
Type:
Ceiling Cassette
°Modol."
4TVC003613100
' No. Fans: ,
1
a, serial
'NA
Fan Type:;
Turbo Fan
Description:
pesign a.; .
Actual'.
Calculation /Factors
Notes:
.CFM;
1059 j
970
92%
Ent: Temp
75 / 63 1
75 / 68
` Leaving Terrip: . °,
NA, I
59 / 57.5
35,0001
32,892
94%
CFMi
1059
975
92%
;v .,EntTemp
75 / 631
75 / 68
Leaving Temp.r� � �
NA
59 / 57
-BTUH
35,000
34,450
98%
a : '.FCU-:3
CFM : " "
1059
990
93%
Ent. TefMp f
75 / 63
71 / 67
LeiMng1eirip. •
NA
58 / 56
BTUH. ,'
35,000
34,275
98%
CFM..
1059
985
93%
Ent:.Temp
75 / 63
71 / 66.5
Leaving;TeMp.' .%
NA
58.5 / 56
? BTUH
35,000
32,392
93%'
Variable Flow Condensing Unit
"Make'., ;
Trane
Model :.:`
' 4TVH0144B300N6
;- " ": Ser�ai:. ` `
NA
Location ,, , .
Roof
Refrigerant Type: ,' ,,
R410A
Xompressor # 1:..,..
;°Design = • : ;;
Actual:
,Notes:
" "Dolts ;,
208 / 3 / 60
209 / 208 / 211
T*Ia Amps
40.8
29.5 / 32.3 / 31
Readings By: Billy Lambert Date: 06/23/2015 Page 17 of 31
Air Logic Services, Inc.
lProject: I I PGA CLUBHOUSE @ THE RESERVE
(Address: 1 1916 PERFECT DRIVE, PORT ST. LUCIE. FLORIDA 34986 1
FANS
Page 18 of 31
Air Logic Services, Inc.
Project: PGA CLUBHOUSE @ THE RESERVE
Address: 1916 PERFECT DRIVE, PORT ST. LUCIE, FLORIDA 34986
Exhaust Fan # 2
Make:
Loren Cook
Location:
Roof
Model
120ACE12OC10D
:Type:
Centrifugal
. Serial: `"
305SF62502
Area Served:
Locker Room
Description:
Design ` =;. ,.
- ` 'Actual,
Calculation/ Factors:
Notes:
Fan iRPM
847
Direct Drive
Motor Size / SF; , .
1/6 / NA
1/6 / NA
Volts / Phase -/-Cycle
120 / 1 / 60
122
Amps
1.8 !
1.5
Motor Frame,
48Y
48Y
tFM
650
740
114%
. Static .
.25" !
NA
NOTE:
1 Speed control at minimum. r
j Exhaust Fan # 3
Make:
Loren' Cook
Location:'
Roof
Model:
120ACE120C100
Type:
NA
Serial ,
NA
Area Served: - :
NA
Description:
''Design "
Actual:
Calculation [Factors:
Notes:
-Fan-'RPM `
847
Direct Drive
Motor Size / SF :;
.167 / NA
.167 / NA
Volts./ Phase /. Cycle
120 / 1 / 60
122
Amps . „
1.8
1.7
Motorframe•" .'
48Y
48Y
CFM
650
655
101%
Static
.25"
NA
Re( dings By: Billy Lambert Date: 06/24/2015 Page 19 of 31
Air Logic Services, Inc.
Project: PGA CLUBHOUSE @ THE RESERVE
Address: 1916 PERFECT DRIVE, PORT ST. LUCIE, FLORIDA 349867
AIR DISTRIBUTION SCHEDULE
Page 20 of 31
IM
Air Logic Services, Inc.
IProiect: I PGA CLUBHOUSE (@ THE RESERVE 1
jAddress: I 1916,PERFECT DRIVE, PORT ST. LUCIE, FLORIDA 34986
Supply Air Distribution Schedule
Area Served
Size .,.
;.,Design CFM
.Actual CFMc'
..
%. '
Notes':
RTU#1
Hall 142
8110
175,
185
106%
Hall 142
8110
150
160
107%
Storage 152
8110
225
205
91%
Meeting Room 155
8110
275
275
100%
Meeting Room 155
8" 0
275
255
93%
TOTAL:
1100
1080
98%
RTU#2
Women's
8110
100
105
105%
Men's Toilet 143
811
0
200
200
100%
Men's Locker 151
8" 0
150
145
97%
Women's Locker 145
8'10
150
160
107%
Gallery 141
8110
200
190
95%
Gallery 141
8110
200
180
90%
Gallery 141
8"
200
190
95%
TOTAL:
1200
1170
98%
RTU#3
Hall140
10"o
425
350
82%
Hall140
8110
150
120
80%
Hall 140
7110
175
180
103%
Men's Locker 130
8110
225
250
111%
1
Men's Locker 130
8"0
225
305
136%
1
Men's Toilet 129
8110
275
240
87%
1
Restroom
8110
275
330
120%
1
Restroom
8110
"0
200
245
123%
1
Gallery 141
8110
200
220
110%
Gallery 141
8110
200
240
120%
Gallery 141
8110
"0
200
235
118%
TOTAL:
2550
2715
106%
Readings By: Billy Lambert Date: 06/24/2015 Page 21 of 31
.-I
Air Logic Services, Inc.
Project: PGA CLUBHOUSE @ THE RESERVE
Address: 1916 PERFECT DRIVE, PORT ST. LUCIE, FLORIDA 34986
Supply Air Distribution Schedule
Area Served..
Size
Design CFM , .
,,: ,Actual CFM;;
. ;%
Notes:-, `'
RTU # 4
1
Member Dining 124
20 x 6
450
415
92%
Member Dining 124
20 x 6
450
425
94%
Member Dining 124
20 x 6
450
410
91%
Member Dining 124
20 ii 6
450
415
92%
Member Dining 124
20 x 6
450
410
91%
Member Dining 124
20 x 6
450
410
91%
Member Dining 124
20 x 6
450
410
91%
Member Dining 124
20 x 6
450
415
92%
TOTAL:
3600
3310
92%
RTU#5
Condition Member Bar 125
10110
400
365
91%
Condition Member Bar 125
10310
400
395
99%
Condition Member Bar 125
10310
400
300
75%
2
Condition Member Bar 125
10110
400
405
101%
Condition Member Bar 125
10310
400
410
103%
Condition Member Bar 125
10110
400
410
103%
Condition Member Bar 125
10110
400
no
78%
2
TOTAL:
1
2800
1 2595
93%
NOTE:
1 Opposed blade dampers closed; noisy.
2 Opposed blade damper wide open.
Readings By: Billy Lambert Date: 06/24/2015 Page 22 of 31
W
Air Logic Services, Inc.
lProject: I PGA CLUBHOUSE @ THE RESERVE
lAddress: 1 1916 PERFECT DRIVE, PORT ST. LUCIE, FLORIDA 34986 1
Exhaust Air Distribution Schedule
Area:Served
Size
Design,CFM� ..
,. " Actual°CFM "
-r%
Notes::
EF#2
Restroom
8" 0
100
220
220%
1
Restroom
8110
"0
50
100
200%
2
Shower
8" 0
50
70
140%
2
Restroom
12 x112
300
270
90%
Shower
8" 0
50
30
60%
Shower
8110
50
50
100%
TOTAL:
600
740
123%
EF#3
Restroom
12 x 12
300
285
95%
Shower
12 x 12
50 .
55
110%
Shower
12 x 12
50
45
90%
Restroom
12 x 12
150
160
107%
Shower
6110
50'
55
110%
Shower
6110
50
1 55
110%
TOTAL:
1 650
1 655
1 01%
NOTES:
1 No balancing damper installed.
2 Opposed blade damper is closed.
Readings By: Billy Lambert Date: 06/24/2015 Page 23 of 31
Air Logic Services,, Inc.
Project: PGA CLUBHOUSE @ THE RESERVE
Address: 1916 PERFECT DRIVE, PORT ST. LUCIE, FLORIDA 34986
EQUIPMENT PICTURES
Page 24 of 31
Air Logic Services, Inc.
Project: PGA CLUBHOUSE @ THE RESERVE
Address: 1916 PERFECT DRIVE, PORT ST. LUCIE, FLORIDA 34986
:NT PICTURES:
Page 25 of 31
Air Logic Services, Inc.
Project: I I PGA CLUBHOUSE @ THE RESERVE
Address: 1 1916 PERFECT DRIVE; PORT ST. LUCIE, FLORIDA 34986
I
I
EQUIPMENT SUBMITTAL DATA
I
Page 26 of 31
w
PGA Clubhouse at the Reserve October 21, 2014
Tan Data-.3-10Ton R-410 Packaged Heat. Pump (Qtv: 5)
Item
Ta s
Q '.
Description
Model Number
Al
RTUA
1
3 Ton R-410 Packaged Heat Pum .
W$C036E.3RBA--1210000000000A000000
A2
RTU-2
1
3 Ton R-410 Packaged Heat Pump
WSC036URBA-13000000000.0A000000
A3
RTU-3
1
7.5 Ton R-410 Packaged Heat Pump
WSC090E3RGA-=BOOOOOOOOOOA000000
A4
RTU-4
1
10 Ton R-410 Packaged Heat Pump
WSC120E3RGA--B000060000OA000000'
A5
RTU-5
1
7:5 Ton R-410 Packaged Heat Pump
WSC090E3RGA--B0000000000A0000:00
Product Data - 3-10Ton R-410 Packaged Heat
All Units
DX cooling
Standard efficiency - Convertible
209-230/60/3
Microprocessor controls 3ph
Motorized OA damper 0-50%, 3 ph
Condensate Drain Pan Overflow Switch
3H/2C Touchscreen, programmable (Fld
1 year parts, 5 year compressor warrant,
Item: Al, A2 Qty: 2 Tag(s): RTU-1, RTU-2
3 Ton
6kW@240,480,600 Berate to.unit vo
Item: A3, A5 Qty: 2 Tag(s): RTU-3, RTU-5
7.5 Ton
18 kW@240,480,600 derate to unit v
Item: A4 Qty: 1 Tag(s): RTU-4
10 Ton
18 kW@240,480,600 derate to unit
Pump
Performance Data - 3-10Ton R-410 Packaged I Heat Pump
Tags
RTU4
RTU-2
RTU-3
RTU-4
RTU-5
Gross Total. Capacity MBh
37.22
38.03
92.33
12144
92.89
Gross Sensible Capacity MBh
25.44
27.25
67.31
92.12
67.97
Ambient Temperature F
95.00
95.00
95:00
95.00
95.00
SEER RI"., btuh/watt
13.00
13.00
-
-
-
EER @ AHRI Conditions (EER)
11.1
111
11.1
IEER
-
-
12.00
13.10
12.00
Design Airflow cfni
1075
1200
2700
3600
2800
Design ESP in H2O
0:600
0.600
0.600
0.600
0.600
Cooling EDB
80.00
80.00
80.00
80.00
80.00
Cooling EWB;(F)
67.00
67.00
67.00
67.00
67.00
Evap Coil Leavin Air Temp DB F
58.09
56.97
56.92,
56.31
57.52
Evap Coil Leaving Air Temp B f
55.68
66.74
55.83
55.79
66.20
Outputhtq ca acit ' MBh
39.61
39.94
85.52
109.66
85.65
Electric heat output MBh
20.49
20.49
61.47
61.47
61.47
Electric heat air tem _rise F
17.55 .
16.72
20.97
15.72
20.22
Com ressor 1 RLA (A)-
13.50
13.50
25.00
18.10
25.00
Cornressor 2-RLA A
0.00
0.00
.0.00
18.10
0.00
Evaporator fan FLA.(A)
5.00
5.00
3.60
8.50'
3.60
Condenser fan. FLA A
2.00
2.00
3.50
2.70
3.50
Electric Heat FLA A
12.50
12:50
37.50
37.50
37.50
MCA A
39.50
39.50
85:20
-98.80
85.20
MOP A
45' 00
45.00
100.00
100.00
100.00
Min. unit -operating weight lb
514.0
514.0
804.0
1199.0
804.0
Max unit operating wei ht Ib
691.0
691.0
993.0
11407.0
1993.0
FLD = Fumished by Trane U. S. Inc. / Installed by Equipment Submittal Page 3 of 24
Others
Page 27 of 31
,i ►
1��� MARK: EF-1
COOKNR ui ornwon PROJECT:
I 40
us DATE:121312014
GEMINI
El
Ceiling Fans F D
100 Series ® g
E
STANDARD CONSTRUCTION FEATURES: J
Forward curved injection molded polypropyle. one fan N K
wheel - Injection molded flame resistant fan housing
with round outlet duct - 22 ga, galvanized steel inlet box -i- H G L
- Isolation mounted motor, mounted to one piece @ M
galvanized stamped steel integral motor mountlinlet -
Permanently lubricated 2-speed motor with built-in B Grille Grille.
thermal overload protection and disconnect plug - Field
wiring compartment with receptacle - Adjustable
prepunched mounting bracket - White, high 'impact IA
styrene injection molded grille - Shipped'in ISTA
certified transit tested packaging. ZA1111 1 o_
Pwrfnrmance
Qty
Catalog
Number
Flow
(CFM)
SP
(inwc)
Nominal
RPM
Input
Watts
1
GC-146
50
1 .25.0
661
25
Altitutle (n): 6 ( emperature (r): ru
Motor Information
VoltslPh/Hz Nameplate Amps
115/1/00 313
Sound Data Inlet Sound Power by Octave Band
1
2
3
4
5
6
7
8
LwA
dBA
Sones
43
45
46
44
36
30
1241161
44
1 29
1 .7
Accessories:
WHITE PLASTIC GRILLE
FAN SPEED. CONTROLLER 5 AMP 120 VOLT
TIME DELAY SWITCH
100 SERIES DAMPER
GEMINI ISOLATOR KIT - ISOLATORS
Ceiling Motioh Sensor
Dimensions inches)
A Plastic 13-1141 M 3-1/4
B Plastic 15-1/2 1N 14
D
4
E
4
F
12
G
5/8
H
8-3/8
J O.D.
5-15/16
K
12-3/4
L
6-11N6
NOTE Acce`ssodesmay aHeddimensionsshown.
Shipping Weight(ibs)*** 20�
1-Includes ran, motor & a=ssones.
0.5c
OAC
0.3(
06
0.2(
0.1(
MEN
®®■■�01111111■■■
, r r
MME—
M©-MM■
r
Fan Curve Legend
CFM vs SP 0.0 -
CFM vs Watts 0
Point of Operation 0
System Curve
20.0 40.0 60.0 80.0 100
Flow (CFM)
W
a9.4.93.Wi l
Page 28 of 31
ly
M®U!!rY MARK: EF-2 AND 3
COOKMIANIPROJECT: PGA CLUBHOUSE AT THE RESERVE
c@us DATE:1/2912015
ACE-D
Downblast Centrifugal
Exhaust Ventilator
Roof Mounted/Direct Drive
STANDARD CONSTRUCTION FEATURES:
All aluminum housing - Backward inclined all aluminum wheel - Two piece
top cap with stainless steel quick release latches (sizes 120 -180) - Welded
curb cap corners - Birdscreen - Permanently lubricated ball bearing motors
- Corrosion resistant fasteners - Transit testeid packaging.
Performance
Oty
Catalog
Number
Flow
(CFM)
SP
(inwc)
Fan
RPM
Power
(HP)
FEG
2
120C10D
650
.250
1 847
.043
n/a(<1 HP)
Altitude (ft): 0 Temperature (F): 70
Motor Information
HP RPM Volts/Ph/Hz Enclosure TOL
1/6 1075 115/1/60 1 ODP -SE Yes
Sound Data Inlet Sound Power b Octave Band
1 2 3 4 5 6 7 8 LwA dBA Sones
57 60 56 51 51 45 41 36 55 44 3.5
Accessories:
STD DISCONNECT PRE -WIRED NEMA1
ROOF CURB RCG 18-18H -LESS NLR W/TRAY
ALUMINUM BIRDSCREEN
FAN SPEED CONTROLLER 5A 120V PREWIRED
HURRICANE RATED CONSTRUCTION
MIAMI-DADE COUNTY, FL NOA 13-0708.12 / 10-2-2018
TAS-201: Large Missile Impact Test
TAS-202: Uniform Static Air Pressure Test
TAS-203: Cyclic Wind Pressure Test
FLORIDA PRODUCT APPROVAL, FL11693
Fan Curve Legend
CFM vs SP
CFM vs HP
Point of Operation Q
System Curve
1. -- T Sq m t
Dimensions (inches)
A
1-7/16
B
28-7/16
C
26-9/16
G
2
T Sq.
20
Roof Open. Sq.*
15-1 /2
NOTE: Accessories may affect dimensions shown.
Shipping Weight(lbs)l 109
Roof opening size for curbs supplied by Cook only.
—Includes fan, motor & accessories.
Fan Curve
0.40 -
0.32
v 0.24
c
CL
W 0.16
0.08
Now
�EW__41hwqh'
No
ME
■■■M.■M■■.
■■.E■EE.■■
■.,.■®■„■■
MENEEMENNE
MEMENNE
no
EMEMENNEEN
MENOMONEE%
0.00'
0
200 400 600 800
Flow (CFM)
Page 29 of 31
.050
.040
030 G
9
.020 9
.010
0.00
1000
vs.5.12.12792 Page 7 of 9
Air Logic Services, Inc.
(Project: I PGA CLUBHOUSE @ THE RESERVE
lAddress: 1 1916 PERFECT DRIVE, PORT ST. LUCIE, FLORIDA 34986 1
INSTRUMENT CALIBRATION INFORMATION
Page 30 of 31
� I or
it
Air Logic Services, Inc.
IProject: , I I PGA CLUBHOUSE @ THE RESERVE
lAddress- I 19161PERFECT DRIVE, PORT ST. LUCIE, FLORIDA 34986
Instrument Calibration Form
4v Descnp— tjiom.,
" del-Nurnb6r:
M'0
Serial Number:
tal Date:.
Dij6'Dbte:,,
Dwyer.25" Differential Gauge
DW33501
NA
NR
NR
Dwyer.50" Differential Gauge
DW33502
NA
NR
NR
Dwyer 3.0" Differential Gauge
DW33505
NA
NR
NR
Dwyer Pitot Tube - 18 Inch
DW33103
NA
NR
'NR
Dwyer Pitot Tube - 48 Inch..
DW33106,
NA
NR
NR
Dwyer Pitot Tube - 36 Inch
DW33105
NA
NR
NR
Dwyer Pitot Tube - 12 Inch
'DW33109
NA
NR
NR
Alnor Hydronic Manometer
HM680
70804205
1/19/2015
1/19/2016
Alnor, Inc. Capture Hood
EBT721
91208058
1/13/2015
1/13/2016
Alnor Rotating Vane Anemometer,
RVA801
A03061
6/2/2015
6/2/2016
Fluke Humidity Thermohygrometer
971
25241945
9/18/2014
9/18/2015
Fluke Electronic AC/DC Clamp Meter
324
26310196WS
9/18/2014
9/18/2015
Alnor Hydronic Temperature Probe
801291
71449009
12/11/2014
12/11/2015
Alnor Micromanometer
5825
T58250851003
1/19/2015
1/19/2016
Hoto Digital Stroboscope
ESL-100
111082
7/25/2014
1 7/25/2015
Cole - Parmer Contact Probe
Type K
I NA
1/19/2015
1/19/2016
United McGill Duct Pressure Blower
NA 1
5892-5
NR
I NR
NOTES:
1 NA - Not Applicable.
2 NR - Not Required.
Page 31 of 31