HomeMy WebLinkAboutPlan Review FormSAINT LUCIE COUNTY FIRE DISTRICT
UNTj.PLAN REVIEW FORM
5160 N.W. Milner Drive
Port Saint Lucie, FL 34983
Telephone:772-621-3322
DI SSFax: 772-621-3604
Web Address: www.slcfd.com
w
Bulling Dept. Saint Lucie County FMO Permit # B-14-145
Project Name PGA Clubhouse - Expansion BLDG Permit # 1404 -0 06 3
Address 1916 Perfect Drive City Port Saint Lucie
Architect/Engineer Basham & Lucas Design Group, Inc Telephone 904.731.2323
Occupancy Type Assembly >300 Construction Type 1116 -- Square Feet 13,375
Occupant Load 630per plan Number of Stories I1 — Access Box 1. Required Access Key Switch
AFS Permit Required FA Permit Required FFP Permit Required
General Notes
1. An electronic copy of the construction documents submitted on a CD is required. The file format shall be .pdf only.
2. All revisions, including the electronic copy must be received prior to permitting.
3. The Fire Marshal requires 24 hour notice on all inspections.
4. The respective Building Department shall schedule all final inspections through the Fire Marshal's Office.
S. Failed inspections require payment of fee prior to rescheduling of further inspections.
6. Penetrations through rated assemblies shall be of the proper LIL design. Design criteria shall be submitted with the construction plans.
7. Fire alarm panels shall be located indoors within air conditioned space.
8. Plans and construction are subject to corrections in the field to maintain code compliance.
9. Automatic fan shutdown is required for HVAC system/s that exceed 2,000 cfm design capacity.
10. The Installation or Alteration of Fire Sprinklers, Fire Alarms, and Fixed Fire Protection Systems require a separate review and permit.
THE FLORIDA FIRE PREVENTION CODE, 2010 EDITION 15 CURRENTLY ENFORCED.
BUILDINGS WITH LIGHT -FRAME TRUSS -TYPE CONSTRUCTION SHALL BE MARKED WITH APPROVED FIREFIGHTER SAFETY
WARNING SIGNS IN ACCORDANCE WITH FLORIDA ADMINISTRATIVE CODES 69A-3.012 AND 69A-60.0081 PRIOR TO RECEIVING
A CERTIFICATE OF OCCUPANCY.
See General Notes Above and Required Revisions Below
1. A separate review and permit is required for the installation or alteration of fire sprinkler, fire alarm, and fixed fire systems.
"- ssembly othccupancies with an occupant load greater than 100 persons require panic hardware to be installed on any door
required for e means of egress. The entire building is classified as an assembly occupancy.
3 The Fire Sprinkler Design Criteria listed on sheet FP1.1 indicates the incorrect NFPA 13 and NFPA 24 edition. The 2007 edition is
currently enforced,
4
Page 11 of 1 Reviewed by T.Liento Date 06-11-2014