HomeMy WebLinkAboutfire department approvalSAINT LUCIE COUNTY FIRE DISTRICT
PLAN REVIEW FORM
5160 N.W. Milner Drive
Port Saint Lucie, FL 34983
Telephone: 772-621-3322
Fax: 772-621-3604
Web Address: www.slcfd.com
Building Dept. SLC FMO Permit # B-22-41
Project Name KINGS COMMERCIAL CENTER BLDG. 1 BLDG Permit # 211 1-0063
Address 7506 COMMERCIAL CIRCLE City FORT PIERCE
Contractor EEXCEL CONSTRUCTION LLC
Address [7416-A SW 48 ST City MIAMI
State FL Zip 33155 Telephone 305 778 4444
.Architect/Engineer ARCHITECTONIC INC. � Telephone (772-460-7751
Occupancy Type B/F-1� Construction Type IIB Square Feet 11208
Occupant Load 39 Number of Stories Access Box N/A Access Key Switch N/A T�
AFSPermit IN/A I FAPermit IN/A I FFPPermit IN/A
General Notes
1. An electronic copy of the construction documents submitted on a CD is required. The file format shall be .pdf only.
2. All revisions, including the electronic copy must be received prior to permitting.
3. The Fire Marshal requires 24 hour notice on all inspections.
4. A Radio coverage Pre -Survey Signal Strength inspection is required before any final inspection is scheduled.
5. The respective Building Department shall schedule all final inspections through the Fire Marshal's Office.
6. Failed inspections require payment of fee prior to rescheduling of further inspections.
7. Penetrations through rated assemblies shall be of the proper LIL design. Design criteria shall be submitted with the construction plans.
8. Fire alarm panels shall be located indoors within air conditioned space.
9. Plans and construction are subject to corrections in the field to maintain code compliance.
10. Automatic fan shutdown is required for HVAC system/s that exceed 2,000 cfm design capacity.
11. The Installation or Alteration of Fire Sprinklers, Fire Alarms, and Fixed Fire Protection Systems require a separate review and permit.
THE CURRENTLY ADOPTED VERSION OF THE FLORIDA FIRE PREVENTION CODE IS ENFORCED.
BUILDINGS WITH LIGHT -FRAME TRUSS -TYPE CONSTRUCTION SHALL BE MARKED WITH APPROVED FIREFIGHTER SAFETY
WARNING SIGNS IN ACCORDANCE WITH FLORIDA ADMINISTRATIVE CODES 69A-3.012 AND 69A-60.0081 PRIOR TO RECEIVING
6 A CERTIFICATE OF OCCUPANCY.
See General Notes Above and Required Revisions Below
-BDAS PRE SIGNAL STRENGTH SURVEY REQUIRED ON ALL NEW CONSTRUCTION.
-PORTABLE FIRE EXTINGUISHERS TAGGED FROM A,LICENSED CONTRACTOR REQUIRED.
-EXIT AND EMERGENCY LIGHTING REQUIRED.
Page 1❑ of E Reviewed by BRIAN PUTNAM Date 2/7/2022
_—._