HomeMy WebLinkAboutEngineeringCBUCK Engineering
Speclalty Structural &nglnL=L=r1nq CBUCK, Inc. Certificate of Authorization #8064
Evaluation Report
`7M 5V Crimp"
Metal Roof Assembly
Manufacturer:
Innovative Distribution, LLC d/b/a JM Metals
1505 Cox Road
Cocoa, Florida 32926
321.639.1537
I
for
Florida Product Approval
# FL 12966.6 R3
Florida Building Code 2010
i
Per Rule 9N-3
Method: 1- D
Category: Roofing
Sub - Category: Metal Roofing
Product: JM 5V Crimp Roof Panel j
Material: Steel
Panel Thickness: 26 gauge
Panel Width: 24"
Support: Wood Deck
I
Prepared by: {I
James L. Buckner P.E..S.E.C.B. 1
i
Florida Professional Engineer # 31242
Florida Evaluation ANE ID: 1916
Project Manager: Diana Galloway
Report No. 12-132-5V-S9W-ER
Date: 4/6/ 12 t
Contents:
Evaluation Report Pages 1— 9 dames L. Buckner, P.E., SECB
CBUCK, Inc.
1399 N. Killian Drive, Suite 4, West Palm Beach, Florida 33403
Phone: (561)491-9927 Fax: (561)491-9928 Website: www.cb.uckinc.net
Florida P.E. :31242
�� 12
I
FL #: FL 12966.6-113 -
Date: 4/6/12
g Page Report No.: 22of 5V-s6w-ER
CBUCK . Engineerin
Specialfiy Structural Engineering CBUCK, Inc. Certificate of Authorization #8064
Manufacturer: JM Metals
Product Name: JM 5V Crimp
Product Category: Roofing
Product Sub -Category Metal Roofing
Compliance Method: State Product Approval Rule 9N-3.005 (1) (d)
Product/System
"JM 5V Crimp" `
Description:
26 gauge Steel roof panel mechanically attached to Plywood Deck with screws.
Product Assembly as
Refer to Page 4 of this report for product assembly components/materials &
Evaluated:
standards:
1. Roof Panel
2. Fasteners
3. Underlayment
4. Insulation (Optional)
Support:
Type:
Wood Deck
(Design of support and its attachment to support framing is outside the scope of
this evaluation.)
Description:
• 15/32 (min.) or greater plywood,
• or Wood plank (min. specific gravity of 0.42)
Slope:
Minimum slope shall be in accordance with manufacturer's recommendations, FBC
Section 1507.4.2 and applicable code sections.
Performance:
Wind Uplift Resistance:
• Design Uplift Pressure: METHOD 1: - 85 PSF
(Refer to "Table A" attachment details herein) METHOD 2:-114.25 PSF
METHOD 3:-114.25 PSF
FL #: FL 12966.6-113
Date: 4/6/12
CBUCK Engineering Page 3 of 9 Report No.: 5v-56w-ER
Specialty Structural Engineering CBUCK, Inc. Certificate of Authorization #8064
Performance Standards: The product described herein has demonstrated compliance with:
• U L580-06 — Test for Uplift Resistance of Roof Assemblies
• UL 1897-04 —Uplift test for roof covering systems
• TAS 125-03 —Standard Requirements for Metal Roofing Systems
Standards Equivalency: The UL 580-94 & UL 1897-98 standard version used to test the evaluated product
assembly is equivalent with the prescribed standards in UL 580-06 & UL 1897-04
adopted by the Florida Building Code 2010:
Code Compliance: The product described herein has demonstrated compliance with Florida Building
Code 2010, Section 1504.3:2.
Evaluation Report This product evaluation is limited to compliance with the structural requirements
Scope: of the Florida Building Code, as related to the scope section to Florida Product
Approval Rule 9N-3.001.
Limitations and • Scope of "Limitations and Conditions of Use" for this evaluation:
Conditions of Use: This evaluation report for "Optional Statewide Approval' contains technical
documentation, specifications and installation method(s) which include
"Limitations and Conditions of Use" throughout the report in accordance
with Rule 9N-3.005. Per Rule 9N-3.004, the Florida Building Commission is
the authority to approve products under "Optional Statewide Approval'.
• _Option for application outside "Limitations and Conditions of Use"
Rule 9N-3.005(1)(e) allows engineering analysis for "project specific approval
by the local authorities having jurisdiction in accordance with the alternate
methods and materials authorized in the Code". Any modification of the
product as evaluated in this report and approved by the Florida Building
Commission is outside the scope of this evaluation and will be the
responsibility of others.
• Design of support system is outside the scope of this report.
• Fire Classification is outside the scope of Rule 9N-3, and 'is therefore not
included in this evaluation.
• This evaluation report does not evaluate the use of this product for use in the
High Velocity Hurricane Zone code section. (Dade & Broward Counties)
• This metal roof system was tested to transmit the roof loads directly to the
building structural support deck.
Quality Assurance: The manufacturer has demonstrated compliance of roof panel products in
accordance with the Florida Building Code and Rule 9N-3.0005 (3) for
manufacturing under a quality assurance program audited by an approved quality
assurance entity through Keystone Certifications, Inc. (FBC Organization #: QUA
1824).
CBUCK Engineering
FL #: FL 12966.6-113
Date: 4/6/12
Report No.: 12-132-5V-S6W-ER
Page 4 of 9
Specialty Structural Engineering CBUCK, Inc. Certificate of Authorization #8064
Components/Materials Roof Panel:
"JM 5V Crimp"
(by Manufacturer): Material:
Steel
Thickness:
26 gauge (min.)
Panel Width:
24" (max.) Coverage
Rib Height:
3/8"
Yield Strength:
40 ksi min.
Corrosion Resistance:
In compliance with FBC Section 1507.4.3:
• ASTM A792 coated, or
• ASTM A653 G90 galvanized steel
Fastener:
Type:
Hex -Head Wood Screw with WSW
Size :
#9 -15 x 1"
Corrosion Resistance:
Per FBC Section 1506.6 and 1507.4.4
Standard:
Per ANSI/ASME B18.6.4
Adhesive/Seam Sealant:
Product Name: Bostik Chem -Calk 915
Type: One component, polyurethane adhesive
Application Size: 3/16" bead
Application Location: along male flange the full length of panel underlaps
(Refer to Table "A" and drawings Page 8)
Components/Materials Underlayment:
(by Others): Per roofing manufacturer's guidelines in compliance with FBC Section 1507.4.5
Insulation (Optional):
Type:
Thickness:
Properties:
Density:
Or Compressive Strength:
Rigid Insulation Board
3" (max.)
2.25 pcf (Ibs/ft3) min.
20 psi min.
Insulation shall comply with FBC Section 1508. When insulation is incorporated,
fastener length shall conform to penetrate thru bottom of support a minimum of
3/16".
I \ CBUCK Engtneertnq
FL #: FL 12966.6-113
Date: 4/6/12
Report No.: 12-132-5V-S6W-ER
Page 5 of 9
Speclalfiy Structural Engineering CBUCK, Inc. Certificate of Authorization #8064
Installation: Installation Method:
(Refer to drawings on Pages 6-7 of this report.)
■ Fastener spacing: Refer to Table "A" Below
(along the length of the panel)
■ Row Spacing: Refer to table "A" Below
(along the row, across the panel profile)
■ Rib Interlock: Lapped
■ Minimum fastener penetration thru bottom of support, 3/16".
■ For panel construction at the end of panels, refer to manufacturer's
instructions and any site specific design.
TABLE "A"
METHOD 1:
METHOD 2:
METHOD 3:
Design Pressure:
- 85 PSF
-114.25 PSF
-114.25 PSF
Fastener Spacing:
12"
12"
12"
Row Spacing:
12"
12"
12"
Fastener
Location:
Corrugation
Peaks
Corrugation
Peaks
Corrugation
Valleys
Adhesive:
Not required
Refer to Drawing
Details 2A & 26
Not required
Install the "JM 5V Crimp" roof panel assembly in compliance with the installation
method listed in this report and applicable code sections, of FBC 2010. The
installation method described herein is in accordance with the scope of this
evaluation report. Refer to manufacturer's installation instructions as a
supplemental guide for attachment.
Referenced Data: 1. TAS 125-03 Uplift Test
By Hurricane Test Laboratory, LLC (FBC Organization #TST ID: 1527)
Method 1: Report 0223-0307-01; Test Date: 03 / 05 / 01- 03 / 08 / 01
Method 2: Report 0223-0913-07; , Report Date: 09 / 08 / 08
Method 3: Report 0223-0517-06; Test Date: 05 / 19 / 06 - 05 / 22 / 06
2. Quality Assurance
By Keystone Certifications, Inc. (QUA ID: 1824)
JM Metals, Licensee #: 344
3. Equivalency of Test Standard Certification
By James L. Buckner, P.E. @ CBUCK Engineering
(FBC Organization # ANE 1916)
4. Certification of Independence
By James L. Buckner, P.E. @ CBUCK Engineering
(FBC Organization # ANE 1916)
FL #: FL 12966.6-R3
Date: 4/6/12
• COU'_K Engineering Report No.: 162of 32 5v-s6w-ER
IN
Specialty Structural Engineering CBUCK, Inc. Certificate of Authorization #8064
Installation Method
JM Metals
"JM 5V Crimp" (26 Gauge) Roof Panel Attached to Wood Deck
Profile Drawings
24' Maximum Net Coverage
c
00
M
IM 5V Crimp" Panel .
Typical Panel Profile View
TABLE "A"
METHOD 1:
METHOD 2:
METHOD 3:
Design Pressure:
- 85 PSF
-114.25 PSF
-114.25 PSF
Fastener Spacing:
12"
12"
12"
Row Spacing:
12"
12"
12"
Fastener
Location:
Corrugation
Peaks
Corrugation
Peaks
Corrugation
Valleys
Adhesive:
Not'required
Refer to Drawing
Details 2A & 2B
Not required
FL #: FL 12966.6-R3
Date: 4/6/12
• g Page Report No.: 7 of 92 5V-S6W-ER
ICBUCK Engineerin
Specialty Structural Engineering CBUCK, Inc. Certificate of Authorization #8064
Installation Method
JM Metals
"JM 5V Crimp" (26 Gauge) Roof Panel Attached to Wood peck
12" o.c. Typical
Fastener Spacing
Across Panel Width
#9-15 Hex -Head Screw
with Weather Seal washer
3/16" min. penetration thru deck
// \\ Spaced 12" o.c. across the Panel
Detail 1A - Typical Assembly Profile View (METHOD 1)
ruylu-15/32" or greater Plywood, or a i ' �
Thickness
- Wood plank icknessss 3 & Maximum
Detail 1B - Typical Assembly Isometric View (METHOD 1)
CSUCK Engineering
FL #: FL 12966.6-113
Date: 4/6/12
Report No.: 12-132-5V-S6W-ER
Page S of 9
Speclafty ' Structural Engineering CBUCK, Inc. Certificate of Authorization #8064
Installation Method
JM Metals
"JM 5V Crimp" (26 Gauge) Roof Panel Attached to Wood Deck
12" o.c: Typical
3/16" Bead Bostick Adhesive
along full length of male flange
at panel underlaps
Fastener Spacinq
Across Panel Width
#9-15 Hex -Head Screw
with Weather Seal washer
3/16" min. penetration thru deck
Spaced IT' o.c. across the Panel
Detail 2A - Typical Assembly Profile View (METHOD 2)
Fasteners -
#9 -15 Hex -Head Screws With "JM 5V-Crimp" Roof Panel
EPDM Bonded Steel Washers I-
Deck:
-15/32" or greater
Plywood, or
- Wood plank
Optional:
3/16" bead Bostick adhesive Rigid Insulation
along panel underlaps Thickness 3" Maximum
Detail 213 - Typical Assembly Isometric View (METHOD 2)
FL #: FL 12966.6-113
Date: 4/6/12
CBUCK . Enginserinq Page Report No.:192 f 92 5V-S6W-ER
SpeelaltLj Structural Engineering CBUCK, Inc. Certificate of Authorization #8064
Installation Method
JM Metals
"JM 5V Crimp" (26 Gauge) Roof Panel Attached to Wood Deck
IT o.c. Typical
Fastener Spacing
Across Panel Width
#9-15 Hex -Head Screw
with Weather Seal washer
3/16' min. penetration thru deck
Spaced Ir' o.c. across the Panel
Detail 3A - Typical Assembly Profile View (METHOD 3)
Fasteners -
15/37 or greater Plywood, or Rigid Insulation
- Wood plank Thickness 3" Maximum
•, e
Detail 3B - Typical Assembly Isometric View (METHOD 3)