HomeMy WebLinkAboutGeneral Truss Engineering Criteria & Design Loads-Project Information:
Name:
BENNETT RES
Address:
City, State, Zip:
GENERAL TRUSS ENGINEERING CRITERIA & DESIGN LOADS:
Building Code & Chapter Computer Program Used:
Custom VIEW by Alpine
Gravity: 55 psf Roof Total Load Gravity' 55 psf Floor Total Load
Wind: 165 mph from ASCE 7-10 code
This package includes a Truss Index Sheet and 214 individual truss design drawings, together with the attached index of the Truss System
design drawings. I hereby certify that this serves as a cover sheet in accordance with Chapter 61G15-31.003 of the Florida Board of
Professional Regulations.
.,1ilrli..
{� grGOf "'. e
"1111 ! l 101 ",
Note: Furthermore, the responsibility of the undersigned is solely limited to the
design of the truss components shown. The suitability and use of these
trusses for any building is the responsibility of the building designer.
Delegated Engineer: T. Stiles Peet, P.E.
Stiles Engineering Group, Inc.
FL Reg Nos: PE# 49200 CA# 27788
404 SW Camden Ave. Stuart, FL 34994
TEL: 772-223-9883 FAX:772-223-9502
HomeBASE by Alpine .. Page 1 of 6
MM�
41 M.
",1 -. zlltlllz��
—Project information:
Name:
BENNETT RES
Address:
City, State, Zip:
GENERAL TRUSS ENGINEERING CRITERIA & DESIGN LOADS:
Building Code & Chapter Computer Program Used:
Custom VIEW by Alpine
Gravity: 55 psf Roof Total Load Gravity- 55 psf Floor Total Load
Wind: 165 mph from ASCE 7-10 code
This package includes a Truss Index Sheet and 214 individual truss design drawings, together with the attached index of the Truss System
design drawings. I hereby certify that this serves as a cover sheet in accordance with Chapter 61 G15-31.003 of the Florida Board of
Professional Regulations.
_%%11111t,,-
P 49200 ;
o • � e
O 'cL OR%01P �.. .e\
Note: Furthermore, the responsibility of the undersigned is solely limited to the
design of the truss components shown. The suitability and use of these
trusses for any building is the responsibility of the building designer.
Delegated Engineer: T. Stiles Peet, P.E.
Stiles Engineering Group, Inc.
FL Reg Nos: PE# 49200 CA# 27788
404 SW Camden Ave. Stuart, FL 34994
TEL: 772-223-9883 FAX:772-223-9502
HomeBASE by Alpine Page 2 of 6
r �
—Project Information:
Name:
BENNETT RES
Address:
City, State, Zip:
GENERAL TRUSS ENGINEERING CRITERIA & DESIGN LOADS:
Building Code & Chapter. Computer Program Used:
Custom VIEW by Alpine
Gravity: Gravity:
55 psf Roof Total Load 55 psf Floor Total Load
Wind., 165 mph from ASCE 7-10 code
This package includes a Truss Index Sheet and 214 individual truss design drawings, together with the attached index of the Truss System
design drawings ` orfoyig7rtify that this serves as a cover sheet in accordance with Chapter 61 G15-31.003 of the Florida Board of
Professio \a�`�°t�o�.s���
OF
a
FL ORS®P���O o
N
Note: Furthermore, the responsibility of the undersigned is solely limited to the
design of the truss components shown. The suitability and use of these
trusses for any building is the responsibility of the building designer.
Delegated Engineer: T. Stiles Peet, P.E.
Stiles Engineering Group, Inc.
FL Reg Nos: PE# 49200 CA# 27788
404 SW Camden Ave. Stuart, FL 34994
TEL: 772-223-9883 FAX:772-223-9502
HomeBASE by Alpine IPage 3 of 6
-Project Information:
Name:
BENNETT RES
Address:
City, State, Zip:
GENERAL TRUSS ENGINEERING CRITERIA 8t DESIGN LOADS:
Building Code & Chapter., Computer Program Used:
Custom I VIEW by Alpine
Gravity: 55 psf Roof Total Load p Gravity: 55 sf Floor Total Load
Wind. 165 mph from ASCE 7-10 code
This package includes a Truss Index Sheet and 214 individual truss design drawings, together with the attached index of the Truss System
design drawings. I hereby certify that this serves as a cover sheet in accordance with Chapter 61G15-31.003 of the Florida Board of
Professional R bons.
\\`'CS PkET 'f/,
Note: Furthermore, the responsibility of the undersigned is solely limited to the
design of the truss components shown. The suitability and use of these
trusses for any building is the responsibility of the building designer.
Delegated Engineer: T. Stiles Peet, P.E.
Stiles Engineering Group, Inc.
FL Reg Nos: PE# 49200 CA# 27788
404 SW Camden Ave. Stuart, FL 34994
TEL: 772-223-9883 FAX:772-223-9502
HomeBASE by Alpine i Page 4 of 6
\
Q_ K
ROOF & FLOOR TRUSS SYSTEMS
—Project Information:
Name:
BENNETT RES
Address:
City, State, Zip:
GENERAL TRUSS ENGINEERING CRITERIA & DESIGN LOADS:
Building Code & Chapter. Computer Program Used:
VIEW by Alpine
Custom
Gravity: 55 Gravity. 55 sf Floor Total Load
psf Roof Total Load p
Wind: 165
mph from ASCE 7-10 code
This package includes a Truss Index Sheet and 214 individual truss design drawings, together with the attached index of the Truss System
design drawings. I hereby certify that this serves as a cover sheet in accordance with Chapter 61 G15-31.003 of the Florida Board of
Professional R I tions.
1Igj�i ions. .
\\`;. AlEt T � �
SE
_/—
� v
\ UJ
/Itrit11
Note: Furthermore, the responsibility of the undersigned is solely limited to the
design of the truss components shown. The suitability and use of these
trusses for any building is the responsibility of the building designer.
Delegated Engineer: T. Stiles Peet, P.E.
Stiles Engineering Group, Inc.
FL Reg Nos: PE# 49200 CA# 27788
404 SW Camden Ave. Stuart, FL 34994
TEL: 772-223-9883 FAX:772-223-9502
HomeBASE by Alpine
\
Page 5 of 6
—Project Intormatlon:
Name:
BENNETT RES
Address:
ROOF & FLODR TRUSS SYSTEMS
City, State, Zip:
GENERAL TRUSS ENGINEERING CRITERIA & DESIGN LOADS:
Building Code & Chapter- Computer Program Used:
Custom I VIEW by Alpine
Gravity: Gravity:
55 psf Roof Total Load 55 psf Floor Total Load
Wind: 165 mph from ASCE 7-10 code
This package includes a Truss Index Sheet and 214 individual truss design drawings, together with the attached index of the Truss System
design drawin + gay certify that this serves as a cover sheet in accordance with Chapter 61 G15-31.003 of the Florida Board of
Profess\�n��
L11 a `;M"" �'
ESS O\��•��
Note: Furthermore, the responsibility of the undersigned is solely limited to the
design of the truss components shown. The suitability and use of these
trusses for any building is the responsibility of the building designer.
Delegated Engineer: T. Stiles Peet, P.E.
Stiles Engineering Group, Inc.
FL Reg Nos: PE# 49200 CA# 27788
404 SW Camden Ave. Stuart, FL 34994
TEL: 772-223-9883 FAX:772-223-9502
. •
IDate
211
F40C
05/31/16
212
F40C
05/31/16
213
F41
05/31/16
214
F41
05/31/16
HomeBASE by Alpine I Page 6 of 6
)D:(KY3U-5J0) /DdfU-dfd DURIJUIL 11DUJJ0 / !1 I
Value Set: 13B (Effective 6/1/2013)
THIS DWG. PREPARED BY THE ALPINE JOB DESIGNER PROGRAM FROM TRUSS MFR'S
3 Complete Trusses Required
Top chord 2x4 SP M-30 :T2, T4 2x4 SP #2:
Bot chord 2x6 SP M-26
Webs 2x4 SP #3
:Lt Wedge 2x4 SP #3::Rt Wedge 2x4 SP #3:
Lumber value set "13B" uses design values approved 1/30/2013 by ALSC
Special loads
-(Lumber Dur.Fac.=1.25 / Plate Dur.Fac.=1.25)
TC- From 92 plf at 0.00 to 92 plf at 18.56
TC-From 92 plf at 18.56 to 92 pif at 37.86
BC -From 20 plf at 0.00 to 20 plf at 37.86
BC- 24.45 lb Conc. Load at 2.32
BC- 219.88 lb Conc. Load at 5.15
BC- 391.80 lb Conc. Load at 7.98
BC- 561.12 lb Conc. Load at 10.81
BC- 727.34 lb Conc. Load at 13.64
BC- 882.37 lb Conc. Load at 16.46
BC- 997.82 lb Conc. Load at 19.29
BC- 1108.99 lb Conc. Load at 22.12
BC- 1223.15 lb Conc. Load at 24.95
BC- 1334.53 lb Conc. Load at 27.78
BC- 1445.93 lb Conc. Load at 30.61
BC- 1557.27 lb Conc. Load at 33.43
BC- 1688.47 lb Conc. Load at 36.26
Nail Schedule:0.120"x3", min. nails
Top Chord: 1 Row @12.00" o.c.
Bot Chord: 1 Row @ 4.00" o.c.
Webs : 1 Row @ 4" o.c.
Repeat nailing as each layer is applied. Use equal spacing
between rows and stagger nails in each row to avoid splitting.
4" o.c, spacing of nails perpendicular and parallel to
grain required in area over bearings greater than 4"
Wind loads and reactions based on MWFRS
Left and right cantilevers are exposed to wind
Deflection meets U360 live and U240 total load. Creep increase factor for dead load is 1.50.
165 mph wind, 17.00 ft mean hgt, ASCE 7-10, CLOSED bldg, not located within 9.00 ft from roof edge, RISK CAT II, EXP D,
wind TC DL=5.0 psf, wind BC DL=5.0 psf.
In lieu of rigid ceiling use pudins to brace BC @ 24" OC. 18'6"12
io
=3X1
19'3"9
i 6'711 -F 5'11"8-+I--5'11"86,27- -I- 677 -{- 6,10"10-i
rl a"I
-I- 36'2"2
B2
9,77 + 9,11„5 + 9'3"11 9'11"14-�i
37'10"5
12'3"1412
'9"15 2,915 L2'9"151y-29„15 1 2'915 29„152'9„15 2,9„15_I 2'915 29„15-� 2'9„15 17-2
i Zi
249 --'"^39201- 5617 727-N±� 998p+ 1 12ZlAi- 1416p1 155 1 tl
R=6196# U=2585# W=87
(Rigid Surface)
R=10216# U=3742# W=6"9
(Rigid Surface)
DESC. = Al SEQ = 97801
PLT. TYP.-WAVE DESIGN GRIT=CUST0MrrPI-2007 FT/RT=20%(0%)/10(0) QTY= 1 PLIES= 3 TOTAL= 3 REV. 15.01.01 C.0610.23 SCALE=0.1250
••WARNING* • TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING.
REFER TO HIB-91 (HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
T. STILES
TC ILL 30.Opsf
REF
O
D'ONOFRIO DR., SUITE 200, MADISON, WI.53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. -IMPORTANT** FURNISH A
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NDS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GA ASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
BUILDING DESIGNER PER ANSI/TPI 1-1995'SECTION 2. '
P E ET
CERTIFICATION
# 49200
404 SW CAMDEN AVE
STUART, FL 34994
TC DL 15.Opsf
BC DL 10.Opsf
BC LL O.Opsf
TOT.LD. 55.Opsf'
DATE 05-31-2016
DRWG
ROOF & FLOOR TRUSS SYSTEMS
O/A LEN. 371005
4175 MARTIN HIGHWAY
PALM CITY, FL 34990
OFF: (772) 286-3700
FAX: (772) 288-4234
DUR.FAC. 1.25
JOB #: KB0336
SPACING 24.0"
TYPE SPEC
Job:(Kt uj ib) /barDara t3ennen KbU;1st7 / AL
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP M-31 :T2, T3 2x4 SP M-30:
Bot chord 2x4 SP M-31 :B2 2x4 SP M-30:
Webs 2x4 SP #3
:Lt Wedge 2X6 SP #2::Rt Wedge 2X6 SP #2:
Lumber value set "13B" uses design values approved 1/30/2013 by ALSC
In lieu of rigid ceiling use purlins to brace BC @ 24" OC.
Bottom chord checked for 10.00 psf non -concurrent live load.
MWFRS loads based on trusses located at least 17.00 ft. from roof edge.
THIS DWG. PREPARED BY THE ALPINE JOB DESIGNER PROGRAM FROM TRUSS MFR'S LAYOUT
165 mph wind, 17.00 ft mean hgt, ASCE 7-10, CLOSED bldg, not located within 9.00 ft from roof edge, RISK CAT II, EXP D,
wind TC DL=5.0 psf, wind BC DL=5.0 psf.
Wind loads and reactions based on both MWFRS and C&C.
Left and right cantilevers are exposed to wind
Calculated horizontal deflection is 0.15" due to live load and 0.20" due to dead load.
(a) Continuous lateral restraint equally spaced on member. Or 1x4 #3SRB SPF-S or better "T' reinforcement. 80% length of
web member. Attached with 8d Box or Gun (0.113"x2.5",min.)nails @ 6" OC.
Deflection meets U360 live and U240 total load. Creep increase factor for dead load is 1.50.
18'6"15 + 19'1"14
�67'12 5'11"9 + s'11"9 6'2"2 672 + 6'9"10 �
97"9 i8'11"6
35'11"12
3T8"13
9'3"3
91101,11 +{
R=2118# U=1213# RL=312/-323# W=87
(Rigid Surface)
R=2107# U=1209# W=6"9
(Rigid Surface)
DESC. = A2
PLT. TYP.-WAVE
DESIGN CRIT=CUSTOM/TPI-2D07 FT/RT=20%(0%)/10(0) QTY=1 T0TAL=1
REV. 15.01.01C.0610.23
SEQ = 97754
SCALE =0.1875
0
••WARNING•• TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING.
REFER TO HIB-91 (HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
D'ONOFRIO DR., SUITE 200, MADISON, WI.53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. **IMPORTANT** FURNISH A
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NDS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GA ASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
BUILDING DESIGNER PER ANSI/TPI 1-1995 SECTION 2.
T. STILES
P E ET
CERTIFICATION
# 49200
404 SW CAMDEN AVE
STUART, FL 34994
TC LL
TC DL
BC DL
BC LL
TOT.LD.
30.Opsf
15.Opsf
10.Opsf
O.Opsf
55.Opsf
REF
DATE 05-31-2016
DRWG
ROOF & FLOOR TRUSS SYSTEMS
O/A LEN. 370813
4175 MARTIN HIGHWAY
PALM CITY, FL 34990
OFF: (772) 286-3700
FAX: (772) 288-4234
DUR.FAC. 1.25
JOB #: KB0336
SPACING 94.0"
TYPE SPEC
Iob:(KL-3uj6b) /barDara tenet Kt5u33b / H3
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP M-31 :T2 2x4 SP #2::T3 2x4 SP M-30:
Bot chord 2x4 SP M-31 :B2 2x4 SP M-30:
Webs 2x4 SP #3
:Lt Wedge 2X6 SP #2::Rt Wedge 2X6 SP #2:
Lumber value set "13B" uses design values approved 1/30/2013 by ALSC
In lieu of rigid ceiling use purlins to brace BC @ 24" OC.
Bottom chord checked for 10.00 psf non -concurrent live load.
MWFRS loads based on trusses located at least 16.98 ft. from roof edge.
— THIS DWG. PREPARED BY THE ALPINE JOB DESIGNER PROGRAM FROM TRUSS MFR'S LAYOUT
165 mph wind, 16.98 ft mean hgt, ASCE 7-10, CLOSED bldg, not located within 9.00 ft from roof edge, RISK CAT II, EXP D,
wind TC DL=5.0 psf, wind BC DL=5.0 psf.
Wind loads and reactions based on both MWFRS and C&C.
Left and right cantilevers are exposed to wind
Calculated horizontal deflection is 0.14" due to live load and 0.19" due to dead load.
(a) Continuous lateral restraint equally spaced on member. Or 1x4 #3SRB SPF-S or better "T" reinforcement. 80% length of
web member. Attached with 8d Box or Gun (0.113"x2.5",min.)nails @ 6" OC.
Deflection meets L1360 live and U240 total load. Creep increase factor for dead load is 1.50.
�— 18'5"12 -{- 19,01,11
�---676 5'11"35'11"3 i6'1"12 6'1"12 673 ^{
p -i 35'9"8 . _
1 9'6"15
R=2108# U=1206# RL=310/-320# W=87
(Rigid Surface)
8'10"13
9'2"10
9'10"1 —�
37'6'7
R=2096# U=1202# W=6"9
(Rigid Surface)
DESC. = A3 SEQ = 97762
PLT. TYP.-WAVE DESIGNCRIT=CUSTOMIrPI-2007FT1RT=20%(0%)110(0) QTY= 1 TOTAL= 1 REV. 15.01.01C.0610.23 SCALE=0.1875
O
**WARNING** TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING.
REFER TO HIB-91 (HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
D'ONOFRIO DR., SUITE 200, MADISON, WI. 53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. ••IMPORTANT'• FURNISH A
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
T . STILES
P E ET
TC LL 30.Opsf
TC DL 15.Opsf
BC DL 10.Opsf
REF
DATE 05-31-2016
DRWG
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NDS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GA ASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
BUILDING DESIGNER PER ANSI/TPI 1-1995'SECTION 2. 1
CERTIFICATION
# 49200
404 SW CAMDEN AVE
STUART, FL 34994
BC LL O.Opsf
TOT.LD. 55.Opsf
ROOF & FLOOR TRUSS SYSTEMS
O/A LEN. 370607
4175 MARTIN HIGHWAY
PALM CITY, FL 34990
OFF: (772) 286-3700
FAX: (772) 288-4234
DUR.FAC. 1.25
JOB #: KB0336
SPACING 24.0"
'TYPE SPEC
)b:(Kt3ujm) /tsarDara bennen r buj3b / A4
Value Set: 13B (Effective 61112013)
Top chord 2x4 SP #2 :T1 2x4 SP M-30::T5 2x4 SP M-31:
Bot chord 2x4 SP M-31 :B2 2x4 SP M-30:
Webs 2x4 SP #3
:Lt Wedge 2X6 SP #2::Rt Wedge 2X6 SP #2:
Lumber value set "13B" uses design values approved 1/30/2013 by ALSC
Bottom chord checked for 10.00 psf non -concurrent live load.
MWFRS loads based on trusses located at least 8.32 ft. from roof edge.
16'8"9
THIS DWG. PREPARED BY THE ALPINE JOB DESIGNER PROGRAM FROM TRUSS MFR'S LAYOUT'
165 mph wind, 16.63 ft mean hgt, ASCE 7-10, CLOSED bldg, not located within 9.00 ft from roof edge, RISK CAT II, EXP D,
wind TC DL=5.0 psf, wind BC DL=5.0 psf.
Wind loads and reactions based on both MWFRS and C&C.
Left and right cantilevers are exposed to wind
Calculated horizontal deflection is 0.13" due to live load and 0.18" due to dead load.
In lieu of rigid ceiling use puriins to brace BC @ 24" OC.
Deflection meets U360 live and U240 total load. Creep increase factor for dead load is 1.50.
3'10"3 -1 4'11"13
11'11"5 --1]
i 6'0"5 -1 54"2 {5'4"2 1 3'10"3 1 4'11"13 i 5'7"1 -}- 6'5"1 �1
12
`1 5
j- 8'8"6 8'0"3 3'10"3 + 411"13 5'71
r 37'6 11
R=2102# U=1259# RL=291/-292# W=87 R=2108# U=1303# W=6"9
(Rigid Surface) (Rigid Surface)
DESC. = A4
PLT. TYP.-WAVE
4175 MARTIN HIGHWAY
PALM CITY, FL 34990
OFF: (772) 286-3700
FAX: (772) 288-4234
DESIGN CRIT=CUSTOW17PI-2007 FT/RT=20%(0%yt0(0)
QTY= 1 TOTAL= 1
=R TO HIB-91 (HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
OFRIO DR., SUITE 200, MADISON, WI. 53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
;TIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
=LS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. **IMPORTANT** FURNISH A
Y OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
IONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
I TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
I APPLICABLE PROVISIONS OF NDS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GA ASTM A653 GR40 GALV. STEEL
-PT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
GN, POSITION CONNECTORS PER DRAWINGS 160 A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
ROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
ABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
T. STILES
PEET
CERTIFICATION
# 49200
404 SW CAMDEN AVE
STUART. FL 34994
1
1
1
REV. 15.01.01C.0610.23
SEQ = 97748
SCALE=0.1875
TC LL
TC DL
BC DL
BC LL
TOT.LD.
30.Opsf
15.Opsf
10.Opsf
O.Opsf
55.Opsf
REF
DATE 05-31-2016
DRWG
O/A LEN. 370611
DUR.FAC.
1.25
JOB #: KB0336
SPACING
24.0"
TYPE SPEC
JOb:(KBU33b) lbarDara tfennen Kt woto / Ati . THIS DWG. PREPARED BY THE ALPINE JOB DESIGNER PROGRAM FROM TRUSS MFR'S LAYOUT
Value Set: 13B (Effective 611/2013) 165 mph wind, 16.18 ft mean hgt, ASCE 7-10, CLOSED bldg, not located within 9.00 ft from roof edge, RISK CAT II, EXP D,
Top chord 2x4 SP M-30 wind TC DL=5.0 psf, wind BC DL=5.0 psf.
Bot chord 2x4 SP M-31 :B2 2x4 SP M-30::B3 2x4 SP #2: Wind loads and reactions based on both MWFRS and C&C.
Webs 2x4 SP #3
:Lt Wedge 2X6 SP #2: Left and right cantilevers are exposed to wind
Lumber value set "13B" uses design values approved 1/30/2013 by ALSC In lieu of rigid ceiling use pudins to brace BC @ 24" OC.
Deflection meets U360 live and U240 total load. Creep increase factor for dead load is 1.50. Bottom chord checked for 10.00 psf non -concurrent live load.
MWFRS loads based on trusses located at least 8.09 ft. from roof edge.
147'3 i 8710 1 13'1 V 2
YI
77"!1 6'11"8 - + 47'13 - + 47'13 6'3"10 6'5"9 �}�►TA
T3
r 77"!1 6'11"8 187'10 6'3"10- + 6'5"9 0. A
37'1"15
R=2092# U=1230# RL=271/-258# W=87
(Rigid Surface)
R=2086# U=1227# W=6"9
(Rigid Surface)
DESC. = A5 SEQ = 97776
PLT. TYP.-WAVE DESIGN CRIT=CUSTOMlTPI-2007FT/RT=20%(0%)/70(0) QTY= 1 TOTAL= 1 REV. 15.01.01C.0610.23 SCALE=0.1875
0
••WARNING— TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING.
REFER TO HIB-91 (HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
D'ONOFRIO DR., SUITE 200, MADISON, WI. 53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. —IMPORTANT— FURNISH A
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NDS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GA ASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
BUILDING DESIGNER PER ANSI(rPI 1-1995 SECTION 2.
T _ STILES
P E ET
CERTIFICATION
# 49200
404 SW CAMDEN AVE
STUART, FL 34994
TC LL 30.Opsf
TC DL 15.Opsf
BC DL 10.Opsf
BC LL O.Opsf
TOT.LD. 55.Opsf
REF
DATE 05-31-2016
DRWG
ROOF & FLOOR TRUSS SYSTEMS
O/A LEN. 370406
4175 MARTIN HIGHWAY
PALM CITY, FL 34990
OFF: (772) 286-3700
FAX: (772) 288-4234
I DUR.FAC. 1.25
JOB #: KB0336
SPACING 24.0"
TYpE SPEC
JOb:(KBU:fJfi) /Baroara tiennen r bujot) / AD
Value Set: 13B (Effective 611/2013)
Top chord 2x4 SP #2 :T1 2x4 SP M-30:
Bot chord 2x4 SP #2 :B1 2x4 SP M-31:
Webs 2x4 SP #3 :W8 2x4 SP #2:
:Lt Wedge 2X6 SP #2::Rt Wedge 2X6 SP #2:
Lumber value set "13B" uses design values approved 113012013 by ALSC
(b) Continuous lateral restraint equally spaced on member. Or 2x4 #3 Or better "T" reinforcement. 80% length of web
member. Attached with 16d Box or Gun (0.135"x3.5",min.)nails @ 6" OC.
Deflection meets U360 live and U240 total load. Creep increase factor for dead load is 1.50.
i 5'11'7
1 5'117 67B 6'81.9
12
THIS DWG. PREPARED BY THE ALPINE JOB DESIGNER PROGRAM FROM TRUSS MFR'S LAYOUT
165 mph wind, 15.81 ft mean hgt, ASCE 7-10, CLOSED bldg, not located within 9.00 ft from roof edge, RISK CAT II, EXP D,
wind TIC DL=5.0 psf, wind BC DL=5.0 psf.
Wind loads and reactions based on both MWFRS and C&C.
Left and right cantilevers are exposed to wind
(a) Continuous lateral restraint equally spaced on member. Or 1x4 #3SRB SPF-S or better "T' reinforcement. 80% length of
web member. Attached with 8d Box or Gun (0.113"x2.5",min.)nails @ 6" OC.
In lieu of rigid ceiling use pudins to brace BC @ 24" OC.
Bottom chord checked for 10.00 psf non -concurrent live load.
MWFRS loads based on trusses located at least 7.91 ft. from roof edge.
13'6"1 i 11'10"8 --+I
r3n
61819 576
P -y 28'8"8 97' —�Fu
1 5'11"7 6'2"8 + 6,8"g + 6'8"9 4' 7'10"8 �{
37'5"8
R=1682# U=1080# RL=231/-227# W=8"
(Rigid Surface)
DESC. = A6
PLT. TYP.-WAVE DESIGN CRIT=CUSTOMrrPI-2007 FT/RT=20%(0%U70(0) QTY= 1 TOTAL= 1
4175 MARTIN HIGHWAY
PALM CITY, FL 34990
OFF: (772) 286-3700
FAX: (772) 288-4234
R=2244# U=1296# W=8"
(Rigid Surface)
R=418# U=267# W=8"
(Rigid Surface)
--YVAKIVINU - I muoJ K uuIKC C I KCMt t'mK= IN rACKIUAI INU, IN.7IHLLIIVU AIVU ORAVIIVV.
REFER TO HIB-91 (HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
T STILES
D'ONOFRIO DR., SUITE 200, MADISON, W. 53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
•
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. "IMPORTANT" FURNISH A
P E ET
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
CERTIFICATION
WITH APPLICABLE PROVISIONS OF NDS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GA ASTM A653 GR40 GALV. STEEL
# 49200
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
404 SW CAMDEN AVE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
STUART, FL 34994
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
BUILDING DESIGNER PER ANSUTPI 1-1995 SECTION 2. ''
REV. 15.01.01 C.0610.23
SEQ = 97576
SCALE=0.1875
TC LL
TIC DL
BC DL
BC ILL
TOT.LD,
30.Opsf
15.Opsf
10.0psf
O.Opsf
55.Opsf
REF
DATE 05-31-2016
DRWG
O/A LEN. 370508
DUR.FAC.
1.25
JOB #: K60336.
SPACING
24.0"
TYPE SPEC
lob:(KBO336) /1:3arbara ttennett KbUJ;Jb / At
Value Set: 13B (Effective 61112013)
Top chord 2x4 SP #2 :T1 2x4 SP M-30:
Bot chord 2x4 SP #2 :B1 2x4 SP M-30:
Webs 2x4 SP #3
:Lt Wedge 2X6 SP #2::Rt Wedge 2X6 SP #2:
Lumber value set "13B" uses design values approved 1/30/2013 by ALSC
In lieu of rigid ceiling use purlins to brace BC @ 24" OC.
Bottom chard checked for 10.00 psf non -concurrent live load.
MWFRS loads based on trusses located at least 7.70 ft. from roof edge.
THIS DWG. PREPARED BY THE ALPINE JOB DESIGNER PROGRAM FROM TRUSS MFR'S LAYOUT
Negative reaction(s) of -221# MAX. (See below) from a non -wind load case requires uplift connection.
165 mph wind, 15.39 ft mean hgt, ASCE 7-10, CLOSED bldg, not located within 9.00 ft from roof edge, RISK CAT 11, EXP D,
wind TIC DL=5.0 psf, wind BC DL=5.0 psf.
Wind loads and reactions based on both MWFRS and C&C.
Left and right cantilevers are exposed to wind
(a) Continuous lateral restraint equally spaced on member. Or 1 x4 #3SRB SPF-S or better "T" reinforcement. 80% length of
web member. Attached with 8d Box or Gun (0.113"x2.5",min.)nails @ 6" OC.
Deflection meets U360 live and U240 total load. Creep increase factor for dead load is 1.50.
9110"8 17'8"8 9110"8
I— 5'3"2 - 1. 476 6117 5'9"11 — + 5'11 "7 1 47"6 i SY2 -+I
9 _ — 28'8"8 83 7' — ' A
I 9110"8 -1 5'117 i 5911 i 5'117 1 2' }- 7'10"8
37'5"8
R=1626# U=967# RL=194/-194#
W=8" R=2602# U=1490# W=8"
(Rigid Surface)
(Rigid Surface)
R=246/-221# U=115# W=8"
(Rigid Surface)
DESC. = A7
SEQ = 97528
PLT. TYP: WAVE
DESIGN CRIT=CUSTOMrrPI-2007 FTIRT=20%(0%V70(0) QTY= 1 TOTAL= 1
REV. 15.01.01 C.0610.23
SCALE=0.1875
••WARNING- TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING.
REFER TO HIB-91 (HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
T STILES
TICLL
30.Opsf
REF
0
D'ONOFRIO DR., SUITE 200, MADISON, WI. 53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. **IMPORTANT** FURNISH A
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NDS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GA ASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
.
P E ET
CERTIFICATION
# 49200
TC DL
BC DL
BC LL
TOT.LD.
15.Opsf
10.Opsf
0.0psf
55.Opsf
DATE 05-31-2016
DRWG
ROOF & FLOOR TRUSS SYSTEMS
O/A LEN. 370508
4175 MARTIN HIGHWAY
DUR.FAC.
1.25
JOB #: KB0336
PALM CITY, FL 34990
OFF: (772) 286-3700
FAX. (772) 2884234
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
SEFOR ANY CTION 2. PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
SUILDWG DES GNER,LITY AND E OF TAHIS S RPI COMPONENT
404 SW CAMDEN AVE
STUART, FL 34994
SPACING
24.D"
TYPE HIPS
/ Ad
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP M-30 :T2 2x6 SP #2:
Bot chord 2x6 SP M-26
Webs 2x4 SP #3 :W2 2x4 SP M-30:
:W4, W2 2x4 SP #2:
:Lt Wedge 2x4 SP 93::Rt Wedge 2x4 SP #3:
Lumber value set "1313" uses design values approved 1/30/2013 by ALSC
Trusses or components connecting to this girder have been modified by the truss designer. The loading for this girder
requires verification for accuracy.
Special loads
-(Lumber Dur.Fac =1.25 / Plate Dur.Fac.=1.25)
TC- From 92 plf at 0.00 to 92 pit at 7.88
TC- From 46 plf at 7.88 to 46 plf at 29.58
TC- From 93 plf at 29.58 to 93 plf at 37.46
BC- From 20 plf at 0.00 to 20 pit at 7.92
BC- From 10 plf at 7.92 to 10 plf at 29.54
BC- From 20 pit at 29.54 to 20 plf at 37.46
TC- 275.47 lb Conc. Load at 7.92, 9.96,11.96,13.96
15.96,17.96,19.49,21.49,23.49,25.49,27.49
TC- 577.61 lb Conc. Load at 29.54
BC- 124.26lb Conc. Load at 7.92, 9.96,11.96,13.96
15.96,17.96,19.49,21.49, 23.49,25.49, 27.49
BC--1939.44 lb Conc. Load at 29.54
Left and right cantilevers are exposed to wind
THIS DWG. PREPARED FROM COMPUTER INPUT (LOADS & DIMENSIONS)SUBMITTED BY TRUSS MFR.
Negative reaction(s) of -962# MAX. (See below) from a non -wind load case requires uplift connection.
(") 2 plate(s) require special positioning. Refer to scaled plate plot details for special positioning requirements.
165 mph wind, 15.00 ft mean hgt, ASCE 7-10, CLOSED bldg, Located anywhere in roof, RISK CAT 11, EXP D, wind TC
DL=5.0 psf, wind BC DL=5.0 psf.
Wind loads and reactions based on MWFRS.
(a) Continuous lateral restraint equally spaced on member. Or 1x4 #3SRB SPF-S or better "T" reinforcement. 80% length of
web member. Attached with 8d Box or Gun (0.113"x2.5",min.)nails @ 6" OC.
In lieu of rigid ceiling use pudins to brace BC @ 24" OC.
Deflection meets U360 live and U240 total load. Creep increase factor for dead load is 1.50.
(b) Continuous lateral restraint equally spaced on member. Or 2x6 #3 or better "T' reinforcement. 80% length of web
member. Attached with 16d Box or Gun (0.135"x3.5",min.)nails @ 6" OC.
275# 275# z7s# 275# 27. 275#
Bottom chord checked for 10.00 psf non -concurrent live load. �- 7,11" 2'0"� 2' _+ 2T 2' _ + 2��1'6"6y 2z7 2' 277 ' 2' + 2'0W",_ 7111 ---{
11
♦~T10116 21'6"8 7'10"8 -{
F~ 7'10"a 5'4"4 --I-- 5-6^ --I5'6" 5,4"4 7'10"e
12
5 r/
T
n
1 7'10"8 --1 5'4"4 -- I- 5.6" --} 5'6. ,1 5'4"4 -i 7'10"a --{
37'5"8
�- T11" -�? 0"8 2' 2' 2' 2' 1'6"6 2' 2' 2' 2' 2'0"87'11"1 �{
1241 124 124 124�-193J
1240 124# 124# 124# 1240 12400
TT
R=2855# U=1411# W=8" R=3795# U=2455# W=8"
(Rigid Surface) (Rigid Surface)
R=12/-962# Rw=360# W=8"
(Rigid Surface)
DESC. = A8 SEQ = 97617
PLT. TYP.-WAVE DESIGN CRIT=CUSTOM?PI-2007FT/RT=20%(0%)/10(0) QTY= 1 TOTAL= 1 REV. 15.01.01 C.0610.23 SCALE=0.1250
**WARNING** TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING.
REFER TO HIB-91 (HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
T STILES
TC LL 30.Opsf
REF
DATE 05-31-2016
ZA
D'ONOFRIO DR., SUITE 200, MADISON, WI. 53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
TC DL 15.Opsf
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. -IMPORTANT- FURNISH A
COPY OF DESIGN
P E ET
O
Ng
THIS TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
BC DL 10.Opsf
DRWG
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NDS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GA ASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
CERTIFICATION
# 49200
BC LL O.Opsf
TOT,LD. 55.Opsf
ROOF & FLOOR TRUSS SYSTEMS
4175 MARTIN HIGHWAY
O/A LEN. 370508
DUR.FAC. 1.25
JOB #: KB0336
PALM CITY, FL 34990
OFF: (772) 288-3700
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
404 SW CAMDEN AVE
FAX: (772) 288-42,34
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
STUART, FL 34994
SPACING 24.0',
HIPS
BUILDING DESIGNER PER ANS1rrPI 1-1995 SECTION 2.
TYPE
)b:(Kt3U33b) lbarbara benneu r bU33b / b-I
Value Set: 13B (Effective 611/2013)
Top chord 2x6 SP #2 :T6 2x4 SP #2:
Bot chord 2x6 SP #2 :B3 2x6 SP M-26:
Webs 2x4 SP #3 :W4 2x4 SP #2:
At Wedge 2x4 SP #3:
Lumber value set "l3B" uses design values approved 1/30/2013 by ALSC
Special loads
-(Lumber Dur.Fac.=1.25 / Plate Dur.Fac.=1.25)
TC- From 92 plf at 0.00 to 92 plf at 1.28
TC- From 46 plf at 1.28 to 46 plf at 6.14
TC- From 46 plf at 6.14 to 46 pit at 7.01
TC- From 46 plf at 7.01 to 46 plf at 12.53
TC- From 46 plf at 12.53 to 46 plf at 22.99
TC- From 46 plf at 22.99 to 46 plf at 27.95
TC- From 93 plf at 27.95 to 93 plf at 30.86
BC- From 10 plf at 0.00 to 10 plf at 10.00
BC- From 10 plf at 10.00 to 10 pif at 20.86
BC- From 10 pit at 20.86 to 10 plf at 27.95
BC- From 20 pit at 27.95 to 20 plf at 30.86
TC- -39.69 lb Conc. Load at 2.06, 4.06, 6.06
TC- 275.47lb Conc. Load at 8.06,10.06,12.06,14.06
15.95,17.95,19.95,21.95
TC--30.07 lb Conc. Load at 23.95
TC- 123.93 lb Conc. Load at 25.95
TC- 106.53 lb Conc. Load at 27.95
BC- 517.38 lb Conc. Load at 2.06, 4.06, 6.06
BC- 124.26lb Conc. Load at 8.06,10.06,12.06,14.06
15.95,17.95,19.95,21.95
BC- 475.76 lb Conc. Load at 23.95
BC- 247.00 lb Conc. Load at 25.95
BC- 262.72 lb Conc. Load at 27,95
Left end vertical not exposed to wind pressure.
Bottom chord checked for 10.00 psf non -concurrent live load.
MWFRS loads based on trusses located at least 7.50 ft. from roof edge.
THIS DWG. PREPARED BY THE ALPINE JOB DESIGNER PROGRAM FROM TRUSS MFR'S
2 Complete Trusses Required
Nail Schedule:0.1201lx3", min. nails
Top Chord: 1 Row @11.00" o.c.
Bot Chord: 1 Row @10.76" o.c.
Webs : 1 Row @ 4" o.c.
Use equal spacing between rows and stagger nails
in each row to avoid splitting.
165 mph wind, 15.00 ft mean hgt, ASCE 7-10, CLOSED bldg, not located within 4.50 ft from roof edge, RISK CAT II, EXP D,
wind TC DL=5.0 psf, wind BC DL=5.0 psf.
Wind loads and reactions based on both MWFRS and C&C.
Right cantilever is exposed to wind
(J) Hanger Support Required, by others
In lieu of rigid ceiling use puriins to brace BC @ 24" OC.
Deflection meets U360 live and U240 total load. Creep increase factor for dead load is 1.60.
400 -00# 275# 275# 27s# 275# 124#
11t 2' 2' 1 2775` 2, 227s� 2' A•1d71 2' + 2, + 2ao#r 2, + z1...2-1°"15'I
p:4-4'10"449"T- 1611"13 17'10"8
4-10"4--i-'i- 5'4"6 - 5 7^125'4„8 ---IF 7'1 a'a
5fl n
29'11"14 -_° 1
P"+- 4'10"4 �-°♦ 5'4"8 1 5'212 1 5'4"8 -i-- T10"8
30'10"6
9"11 2' 2' 1 2' 1 2' 1 2' 1 2' 1'10"1 2' 2' 2' 2' 1 2' 2' F'10' 15
5170 517 5170 12 124# 72 t24# 12 1240 124 t24i 476 2470 263
R=3875# U=2521# RL=86/-187#
H=H1
R=3903# U=2016# W=6"
(Rigid Surface)
n n
f� f�
CJ th
11
DESC. = B1 SEQ = 97758
PLT. TYP.-WAVE DESIGN CRIT=CUSTOM/rPI-2007FTIRT=20%(0%y10(0) QTY= 1 PLIES= 2 TOTAL= 2 REV. 15.01.01C.0610.23 SCALE=0.1250
O
madWITH
**WARNING** TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING.
REFER TO HIB-91 (HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
D'ONOFRIO DR., SUITE 200, MADISON, WI. 53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. **IMPORTANT** FURNISH A
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NDS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GA ASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
BUILDING DESIGNER PER ANSI/TPI 1-1995 SECTION 2.
T. STILES
P E ET
CERTIFICATION
# 49200
404 SW CAMDEN AVE
STUART, FL 34994
TC ILL 30.Opsf
TC DL 15.Opsf
BC DL 10.Opsf
BC LL O.Opsf
TOT.LD. 55.Opsf
REF
DATE 05-31-2016
DRWG
ROOF & FLOOR TRUSS SYSTEMS
O/A LEN. 301006
4175 MARTIN HIGHWAY
PALM CITY, FL 34990
OFF: (772) 286-3700
FAX: (772) 288-4234
DUR.FAC. 1.25
JOB #: KB0336
SPACING 24.0"
TYPE SPEC
JOD:(r\bU.5150) /Daroala Denney IND0000 r D4
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2 :T4 2x4 SP M-30:
Bot chord 2x4 SP #2 ;B3 2x4 SP M-30:
Webs 2x4 SP #3 :W2 2x4 SP #2:
:Rt Wedge 2X6 SP #2:
Lumber value set "13B" uses design values approved 1 /30/2013 by ALSC
Left end vertical not exposed to wind pressure.
In lieu of rigid ceiling use purlins to brace BC @ 24" OC.
Deflection meets U360 live and L/240 total load. Creep increase factor for dead load is 1.50.
1 4'3"5 4'813
43"5 4'813
THIS DWG. PREPARED BY THE ALPINE JOB DESIGNER PROGRAM FROM TRUSS MFR'S LAYOUT
165 mph wind, 15.39 ft mean hgt, ASCE 7-10, CLOSED bldg, not located within 9.00 ft from roof edge, RISK CAT II, EXP D,
wind TC DL=5.0 psf, wind BC DL=5.0 psf.
Wind loads and reactions based on both MWFRS and C&C.
Right cantilever is exposed to wind
Max JT VERT DEFL: LL: 0.25" DL: 0.33". See detail DEFLCAMB1014 for camber recommendations. Roofs incorporating
this truss require consideration for ponding design by Building Designer.
(J) Hanger Support Required, by others
Bottom chord checked for 10.00 psf non -concurrent live load.
MWFRS loads based on trusses located at least 7.70 ft. from roof edge.
11'11"12 -I 9110"8
5'11"14 + 5'11"14 147"6 5'3"2
—4'3"5 -1- 4'8"13 15'11"14 5'11"14 9'10"8 -I
30'10"6
R=1672# U=1013# RL=129/-195#
H=H1
R=1802# U=1063# W=6"
(Rigid Surface)
DESC. = B2 SEQ = 97540
PLT. TYP.-WAVE DESIGN CRIT=CUST0M/rP1-2007 FT/RT=20%(0%)I10(0) QTY= 1 TOTAL= 1 REV. 15.01.01 C.0610.23 SCALE=0.2500
**WARNING** TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING.
REFER TO HIB-91 (HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
T STILES
TIC LL 30.Opsf
REF
O
D'ONOFRIO DR., SUITE 200, MADISON, WI. 53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. **IMPORTANT** FURNISH A
COPY OF THIS DESIGN -TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NDS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GA ASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
BSUITABILITY AND UILDING DESIGNER, OF THIS COMPONENT PER FOR ANYPARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
ON 2
.
- -h-E ET
CERTIFICATION
# 49200
404 SW CAMDEN AVE
STUART, FL 34994
TIC DL 15.Opsf
-
BIC DL, 1-0.Opsf -
BC LL O.Opsf
'
TOT.LD. 55.Opsf
DATE 05-31-2016
-DRwG
ROOF & FLOOR TRUSS SYSTEMS
O/A LEN. 301006
4175 MARTIN HIGHWAY
LM CITY, FL 34990
PAOFF: (772) 286-3700
FAX. (772) 288-4234
DUR.FAC. 1.25
JOB #: KB0336
SPACING 94
TYPE SPEC
I0D:(Kt1UJ6I3) /t3arDara tsenneu r%nuoiD / bi
Value Set: 13B (Effective 611/2013)
Top chord 2x4 SP #2
Bot chord 2x4 SP #2 :B3 2x4 SP M-30:
Webs 2x4 SP #3 :W2 2x4 SP #2:
:Rt Wedge 2X6 SP #2:
Lumber value set "13B" uses design values approved 1/30/2013 by ALSC
(J) Hanger Support Required, by others
Bottom chord checked for 10.00 psf non -concurrent live load.
MWFRS loads based on trusses located at least 7.91 ft. from roof edge.
THIS DWG. PREPARED BY THE ALPINE JOB DESIGNER PROGRAM FROM TRUSS MFR'S LAYOUT
165 mph wind, 15.82 ft mean hgt, ASCE 7-10, CLOSED bldg, not located within 9.00 ft from roof edge, RISK CAT 11, EXP D,
wind TIC DL=5.0 psf, wind BC DL=5.0 psf.
Wind loads and reactions based on both MWFRS and C&C.
Right cantilever is exposed to wind
Max JT VERT DEFL: LL: 0.20" DL: 0.27". See detail DEFLCAMB1014 for camber recommendations. Roofs incorporating
this truss require consideration for ponding design by Building Designer.
In lieu of rigid ceiling use pudins to brace BC @ 24" OC.
Deflection meets U360 live and LJ240 total load. Creep increase factor for dead load is 1.50.
--2'3"3 + 8'8"15 + 7'11`12 + 877 + 310"11
2,3"3 4,47 4'47 3'11"14 3'11"14 ,{„ 4'1"3 4'1"3 3'10"11
n
30'2 7
ez
�— 2'3"3 8'8"15 1 3'11"14 3'11"14 + 877 3'10"11 --�{
31'0"15
R=1681# U=996# RL=179/-224#
H=H1
DESC. = B3
PLT. TYP.-WAVE DESIGN CRIT=CUST0M/TPI-2007 FT/RT=2096(0%y10(0) QTY= 1 TOTAL= 1
REFER TO HIB-91 (HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE. 583uMy�V
T STILES
D'ONOFRIO DR., SUITE 200, MADISON, WI. 53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. —IMPORTANT" FURNISH A
.
EET
-
O
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. -ALPINE ENGINEERED PRODUCTS;-INC. SHALL NOT BE
_ _P-
RESPONSIBLE FOR ANY -DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NDS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GA ASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
CERTIFICATION
# 49200
ROOF & FLOOR TRUSS SYSTEMS
4175 MARTIN HIGHWAY
PALM CITY, FL 34990
OFF: (772) 286-3700
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
404 SW CAMDEN AVE
STUART, FL 34994
FAX: (772) 288-4234
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
BUILDING DESIGNER PER ANSUTPI 1-1995-SECTION 2. +
R=1812# U=1138# W=67
(Rigid Surface)
REV. 15.01.01 C.0610.23
TIC LL
30.Opsf
TC DL
15.Opsf
BC DL-
10.Opsf
BC LL
O.Opsf
TOT.LD.
55.Opsf
DUR.FAC.
1.25
SPACING
24.0"
SEQ = 97586
SCALE=0.2500
REF
DATE 05-31-2016
O/A LEN. 310015
JOB #: KB0336
TYPE SPEC
1oo:(Kt3us3t)) /rsarDara bennell Kt5u33t:) / ts4
Value Set: 13B (Effective 61112013)
Top chord 2x4 SP M-30 :T2, T3 2x4 SP #2:
Bot chord 2x4 SP #2 :B1 2x4 SP M-30:
Webs 2x4 SP #3 :W8 2x4 SP #2:
:Lt Stub Wedge 2x8 SP #2:
Lumber value set "138" uses design values approved 113012013 by ALSC
In lieu of rigid ceiling use purlins to brace BC @ 24" OC.
Deflection meets U360 live and U240 total load. Creep increase factor for dead load is 1.50.
THIS DWG. PREPARED BY THE ALPINE JOB DESIGNER PROGRAM FROM TRUSS MFR'S LAYOUT
(1) - plates so marked were sized using 0% Fabrication Tolerance, 0 degrees Rotational Tolerance, and/or zero Positioning
Tolerance.
(") 2 plate(s) require special positioning. Refer to scaled plate plot details for special positioning requirements.
165 mph wind, 16.39 ft mean hgt, ASCE 7-10, CLOSED bldg, not located within 9.00 ft from roof edge, RISK CAT 11, EXP D,
wind TIC DL=5.0 psf, wind BC DL=5.0 psf.
Wind loads and reactions based on both MWFRS and C&C..
Bottom chord checked for 10.00 psf non -concurrent live load.
MWFRS loads based on trusses located at least 8.20 ft. from roof edge.
I 12'10"14 }- 4'2"5 4 IT 12'6"15
s 5 7 6 5 7 i 474 s 3"8 i6'3"8 +I
i 6'57 — i6'57 }- 47A 6'3"8 i6'3"8 ��
30'1"1
R=1691# U=930# RL=219/-221# W=8"
(Rigid Surface)
R=1688# U=933#
DESC. = B4 SEQ = 97649
PLT. TYP.-WAVE DESIGN CRIT=CUSTOM/TPI-2007FT/RT=20%(0%)11%0) QTY= 1 TOTAL= 1 REV. 15.01.01C.0610.23 SCALE=0.2500
_
O
**WARNING** TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING.
REFER TO HIB-91 (HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
D'ONOFRIO DR., SUITE 200, MADISON, WI. 53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. "IMPORTANT" FURNISH A
COPY OF THIS DESIGN TO THEINSTALLATIONCONTRACTOR. ALPINE ENGINEERED PRODUCTS- INC. SHALL NOT BE
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NDS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GA ASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
BUILDING DESIGNER PER ANSI/TPI 1-1995-SECTION 2.
T. STILES
- P E ET
CERTIFICATION
# 49200
404 SW CAMDEN AVE
STUART, FL 34994
TC LL 30.Opsf
TIC DL 15.Opsf
BC DL 10.0psf
BC LL O.Opsf
TOT.LD. 55.Opsf
REF
DATE 05-31-2016
DRWG
ROOF & FLOOR TRUSS SYSTEMS
4175 MARTIN HIGHWAY
PALM CITY, FL 34990
OFF: (772) 286-3700
FAX: (772) 288.4234
O/A LEN. 300101
DUR.FAC. 1.25
JOB #: KB0336
SPACING 24.0"
TypE COMN
&(KB0336) /Barbara t3ennett Kt3U33(i / bb
THIS DWG. PREPARED BY THE ALPINE JOB DESIGNER PROGRAM FROM TRUSS MFR'S LAYOUT
Value Set: 13B (Effective 6/112013)
165 mph wind, 16.62 ft mean hgt, ASCE 7-10, CLOSED bldg, not located within 9.00 ft from roof edge, RISK CAT II, EXP D,
wind TICDL=5.0 psf, wind BC DL=5.0 psf.
Tap chord 2x4 SP M-30 :T2 2x4 SP #2:
Bot chord 2x4 SP #2 :B1 2x4 SP M-30:
Wind loads and reactions based on both MWFRS and C&C.
Webs 2x4 SP #3
:Lt Wedge 2X6 SP #2:
Right end vertical not exposed to wind pressure.
Lumber value set "13B" uses design values approved 1/30/2013 by ALSC Left cantilever is exposed to wind
Bottom chord checked for 10.00 psf non -concurrent live load. In lieu of rigid ceiling use purlins to brace BC @ 24" OC.
MWFRS loads based on trusses located at least 8.31 ft. from roof edge. Deflection meets U360 live and U240 total load. Creep increase factor for dead load is 1.50.
15'9"3 9 13 12'4"11 -I
�— 5'9"14 + 5'21 'i" 57"1 i 6'4"14 i 6'4"14
8'4"14 i 14'1"15 + 6'4"14 �I
28'11 "11
R=1700# U=944# RL=282/-241# W=8"
(Rigid Surface)
R=1557# U=834#
DESC. = B5 SEQ = 97545
PLT. TYP.-WAVE DESIGN CRIT=CUSTOMrrPI-2007FT/RT=20%(0%)/10(0) QTY= 1 TOTAL= 1 REV. 15.01.01C.0610.23 SCALE=0.2500
_
O
..WARNING" TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING.
REFER TO HIB-91 (HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
D'ONOFRIO DR., SUITE 200, MADISON, WI. 53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. **IMPORTANT** FURNISH A_ _
COPY -OF THIS DESIGN TO THE INSTALLATION CONTRACTOR.- ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
T " STILES
--
P E ET
TIC LL 30.0 sf
p
TC DL 15.Opsf
- - - - - -
BC DL 10.Opsf
REF
DATE 05-31-2016
DRWG
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NOS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GA ASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
BUILDING DESIGNER PER ANSI/TPI 1-1995•SECTION 2. •.
CERTIFICATION
# 49200
404 SW CAMDEN AVE
STUART, FL 34994
I.
BC LL O.Opsf
TOT.LD. 55.Opsf
ROOF & FLOOR TRUSS SYSTEMS
O/A LEN. 281111
4175 MARTIN HIGHWAY
PALM CITY, FL 34990
OFF: (772) 286-3700
FAX; (772) 288-4234
DUR.FAC. 1.25
JOB #: KB0336
SPACING 24.0"
TYPE COMN
3D:(NISU330) /naroara t3enneu minu.ssb / bb
Value Set: 13B (Effective 611/2013)
Tap chard 2x4 SP #2 :T1 2x4 SP M-30:
Bot chord 2x4 SP M-30
Webs 2x4 SP #3
:Lt Wedge 2X6 SP #2:
Lumber value set "1361" uses design values approved 1/3012013 by ALSC
In lieu of rigid ceiling use pudins to brace BC @ 24" OC.
Bottom chord checked for 10.00 psf non -concurrent live load.
MWFRS loads based on trusses located at least 16.78 ft. from roof edge.
THIS DWG. PREPARED BY THE ALPINE JOB DESIGNER PROGRAM FROM TRUSS MFR'S LAYOUT
165 mph wind, 16.78 ft mean hgt, ASCE 7-10, CLOSED bldg, not located within 9.00 ft from roof edge, RISK CAT II, EXP D,
wind TC DL=5.0 psf, wind BC DL=5.0 psf.
Wind loads and reactions based on both MWFRS and C&C.
Right end vertical not exposed to wind pressure.
Left cantilever is exposed to wind
(a) Continuous lateral restraint equally spaced on member. Or 2x4 #3 or better "T' reinforcement. 80% length of web
member. Attached with 16d Box or Gun (0.135"x3.5",min.)nails @ 6" OC.
Deflection meets U360 live and U240 total load. Creep increase factor for dead load is 1.50.
1616"8 1 10'5"5
5'11"6 "{' 5'3"9 —I 5'3"9 5711 5'2"11
12
U tl i 26'1"6
- 87"3 T11"6
10'5"5
26'11"14
R=1589# U=902# RL=306/-227# W=8"
(Rigid Surface)
R=1446# U=819#
DESC. = B6 SEQ = 97515
PLT.TYP: WAVE DESIGN CRIT=CUSTOM/rP1-2007FTlRT=20%(0%)/10(0) QTY= 1 TOTAL= 1 REV. 15.01.01C.0610.23 SCALE=0.2500
—WARNING" TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING.
REFER TO HIB-91 (HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
T STILES
TC LL 30.Opsf
REF
D'ONOFRIO DR., SUITE 200, MADISON, WI. 53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
.
DATE 05-31-2016
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
TC DL 15.Opsf
O
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. **IMPORTANT** FURNISH A
COPY OF THIS DESIGN TO THE INSTALLATION -ALPINE
_PEE T
_
CONTRACTOR. ENGINEERED PRODUCTS, INC: SHALLNOT BE
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH
CERTIFICATION
BC DL 10.Opsf
BC LL O.Opsf
DRWG
ROOF & FLOOR TRUSS SYSTEMS
APPLICABLE PROVISIONS OF NDS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GA ASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
# 49200
TOT.LD. 55.Opsf
4175 MARTIN HIGHWAY
O/A LEN. 261114
PALM CITY, FL 34990
OFF: (772) 286-3700
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
404 SW CAMDEN AVE
DUR.FAG. 1.25
JOB #: KB0336
FAX: (772) 288-4234
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
STUARTFL 34994
,
SPACING 24.0"
COMN
BUILDING DESIGNER PER ANSI/TPI 1-1995 SECTION 2.
TYPE
Job:(Kt3U3:Ai) /tjaroara tsennelt Ktw Ise / rs/
Value Set: 13B (Effective 611/2013)
Top chord 2x4 SP #2 :T1 2x4 SP M-30:
Bot chord 2x4 SP M-30 :B2 2x4 SP #2:
Webs 2x4 SP #3
:Lt Wedge 2X6 SP #2:
Lumber value set "13B" uses design values approved 1/30/2013 by ALSC
In lieu of rigid ceiling use purlins to brace BC @ 24" OC.
Bottom chord checked for 10.00 psf non -concurrent live load.
MWFRS loads based on trusses located at least 16.86 ft. from roof edge.
16"1"2
r 6'0"15 5'5"2
R=1477# U=834# RL=3261-207# W=8"
(Rigid Surface)
THIS DWG. PREPARED BY THE ALPINE JOB DESIGNER PROGRAM FROM TRUSS MFR'S LAYOUT
165 mph wind, 16.86 ft mean hgt, ASCE 7-10, CLOSED bldg, not located within 9.00 ft from roof edge, RISK CAT ll, EXP D,
wind TC DL=5.0 psf, wind BC DL=5.0 psf.
Wind loads and reactions based on both MWFRS and C&C.
Right end vertical not exposed to wind pressure.
Left cantilever is exposed to wind
(a) Continuous lateral restraint equally spaced on member. Or 1 x4 #3SR8 SPF-S or better "T" reinforcement. 80% length of
web member. Attached with 8d Box or Gun (0. 1 13"x2.5",min.)nails @ 6" OC.
Deflection meets U360 live and U240 total load. Creep increase factor for dead load is 1.50.
8'0"14
5'5"2 4'0"7 i 4'07
12
8'9"8 i8111,11 + 8'0"14
25'
(4
R=1335# U=783#
DESC. = B7 SEQ = 97566
PLT.TYP.-WAVE DESIGN CRIT=CUSTOMfrPI-2007FT/RT-X%(0%)/10(0) QTY= 1 TOTAL= 1 REV. 15.01.01C.0610.23 SCALE=0.2500
O —
V�
**WARNING** TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING.
REFER TO HIB-91 (HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
D'ONOFRIO DR., SUITE 200, MADISON, WI. 53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. **IMPORTANT— FURNISH A
COPY OF THIS DESIGN TO THE -INSTALLATION -CONTRACTOR. ALPINE ENGINEERED PRODUCTS; INC. SHALLNOTBE
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NDS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GA ASTM A553 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
SUITA NG DESND USEER, OF TAHIS S RPI PO990 NENTFOR N p , ARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
T = STILES
P E ET
CERTIFICATION
# 49200
404 SW CAMDEN AVE
STUART, FL 34994
TC LL 30.Opsf
TC DL 15.Opsf
_ _ _ _
BC DL 1-0.Opsf
BC LL 0.0psf
TOT.LD. 55.Opsf
REF
DATE 05-31-2016
_
- DRWG
ROOF & FLOOR TRUSS SYSTEMS
O/A LEN. 25
4175 MARTIN HIGHWAY
PALM CITY, FL 34990
OFF: (772) 286-3700
FAX: (772) 288-4234
DUR.FAC. 1.25
JOB #: KB0336
SPACING 24.0"
TYPE CONIN
)Ob:(K13U=)) /t3arDara tSennen mou Sib / tsts
Value Set: 13B (Effective 611/2013)
Top chord 2x4 SP #2
Bot chord 2x4 SP M-30 :B2 2x4 SP #2:
Webs 2x4 SP #3
:Lt Wedge 2X6 SP #2:
Lumber value set "13B" uses design values approved 1130/2013 by ALSC
Bottom chord checked for 10.00 psf non -concurrent live load.
MWFRS loads based on trusses located at least 16.94 ft. from roof edge.
17'3"13
THIS DWG. PREPARED BY THE ALPINE JOB DESIGNER PROGRAM FROM TRUSS MFR'S LAYOUT
165 mph wind, 16.94 ft mean hgt, ASCE 7-10, CLOSED bldg, not located within 9.00 ft from roof edge, RISK CAT 11, EXP D,
wind TC DL=5.0 psf, wind BC DL=5.0 psf.
Wind loads and reactions based on both MWFRS and C&C.
Right end vertical not exposed to wind pressure.
Left cantilever is exposed to wind
In lieu of rigid ceiling use pudins to brace BC @ 24" OC.
Deflection meets U360 live and U240 total load. Creep increase factor for dead load is 1.50.
5'8"6
i 6'2'7 1 5'6"11 - i 5'6"11 i5'8"6 —�
12
a 4.65
22'1"11
1- 8'11"13 - -i 8,4• i 5'8"6
23'0"3
R=1366# U=758# RL=370/-187# W=6" R=1223# U=755#
(Rigid Surface)
DESC. = B8 SEQ = 97543
PLT. TYP: WAVE DESIGN CRIT=CUSTOM MI-2037FT/RT=20%(0%y10(0) QTY= 1 TOTAL= 1 REV. 15.01.01C.0610.23 SCALE=0.2500
"WARNING" TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING.
REFER TO HIB-91 (HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
T. STILES
TC LL 30.Opsf
REF
_
O
D'ONOFRIO DR., SUITE 200, MADISON, WI. 53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE PROPERLY ATTACHED RIGID CEILING. **IMPORTANT- FURNISH A
COPY OF THIS DESIGN -TO THE INSTALLATION CONTRACTOR. -ALPINE ENGINEERED PRODUCTS. INC.-SHALL NOT BE
-- PEET
TC DL 15.0psf
BC DL 1 O.Opsf
DATE 05-31-2016
DRWG
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN: ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NDS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GA ASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
BUILDING DESIGNER PER ANSI/TPI 1-1995 SECTION 2!
CERTIFICATION
# 49200
404 SW CAMDEN AVE
STUART, FL 34994
BC LL O.Opsf
TOT.Lp, 55.Opsf
ROOF & FLOOR TRUSS SYSTEMS
O/A LEN. z30003
4175 MARTIN HIGHWAY
PALM CITY, FL 34990
OFF: (772) 286-3700
FAX: (772) 288-4234
DUR.FAC. 1.25
JOB #: KB0336
SPACING 24.0°
TYPE COMN
)D:(Kt$U33b) /Barbara Bennett mt5uajo / ou
Value Set: 138 (Effective 6/l/2013)
Top chord 2x4 SP #2
Bat chord 2x4 SP M-30 :B2 2x4 SP #2:
Webs 2x4 SP #3
:Lt Wedge 2X6 SP #2:
Lumber value set "13B" uses design values approved 1/30/2013 by ALSC
In lieu of rigid ceiling use purlins to brace BC @ 24" OC.
Bottom chord checked for 10.00 psf non -concurrent live load.
MWFRS loads based on trusses located at least 17.02 ft. from roof edge.
THIS DWG. PREPARED BY THE ALPINE JOB DESIGNER PROGRAM FROM TRUSS MFR'S LAYOUT
165 mph wind, 17.02 ft mean hgt, ASCE 7-10, CLOSED bldg, not located within 9.00 ft from roof edge, RISK CAT II, EXP D,
wind TC DL=5.0 psf, wind BC DL=5.0 psf.
Wind loads and reactions based on both MWFRS and C&C.
Right end vertical not exposed to wind pressure.
Left cantilever is exposed to wind
(a) Continuous lateral restraint equally spaced on member. Or 1x4 #3SRB SPF-S or better "T' reinforcement. 80% length of
web member. Attached with 8d Box or Gun (0.113"x2.5",min.)nails @ 6" OC.
Deflection meets U360 live and U240 total load. Creep increase factor for dead load is 1.50.
17'87 -1- 3'3"14—�
6'4" i 5'8"3 5'8"3 -1- 3'3"14 —�
12
Q 4.65
�9"8 I- 20'1"13
97"2 i8'6"5 i3'3"14
R=1252# U=672# RL=450/-167# W=8"
(Rigid Surface)
DESC. = B9
PLT. TYP.-WAVE DESIGN CRIT=CUSTOMITPI-2007
4175 MARTIN HIGHWAY
PALM CITY, FL 34990
OFF: (772) 286-3700
FAX: (772) 288-4234
21'0"5
QTY= 1 TOTAL= 1
REFER TO HIB-91 (HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
D'ONOFRIO DR., SUITE 200, MADISON, WI. 53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. ••IMPORTANT' FURNISH A
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL -NOT BE
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NDS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GA ASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
R=1109# U=736#
T. STILES
- -PEET
CERTIFICATION
# 49200
404 SW CAMDEN AVE
STUART, FL 34994
REV. 15.01.01 C.0610.23
TIC LL
30.Opsf
TIC DL
15.Opsf
BC DL - —
1 O.Opsf
BC LL
O.Opsf
TOT.LD.
55.Opsf
DUR.FAC.
1.25
SPACING
24.0"
SEQ = 97507
SCALE=0.2500
REF
DATE 05-31-2016
DRWG
O/A LEN. 210005
JOB* KB0336
TYPE COMN
/ L31 U
Value Set: 13B (Effective 6/112013)
Top chord 2x4 SP #2 :T2 2x4 SP M-30:
Bot chord 2x4 SP #2
Webs 2x4 SP #3
:Lt Wedge 2X6 SP #2:
Lumber value set "13B" uses design values approved 1/30/2013 by ALSC
In lieu of rigid ceiling use purlins to brace BC @ 24" OC.
Bottom chord checked for 10.00 psf non -concurrent live load.
MWFRS loads based on trusses located at least 17.03 ft. from roof edge.
11'4'
I- 5'11"14 i 5'41
V"8 I 181"15
THIS DWG. PREPARED BY THE ALPINE JOB DESIGNER PROGRAM FROM TRUSS MFR'S LAYOUT
165 mph wind, 17.03 ft mean hgt, ASCE 7-10, CLOSED bldg, not located within 9.00 ft from roof edge, RISK CAT 11, EXP D,
wind TIC DL=5.0 psf, wind BC DL=5.0 psf.
Wind loads and reactions based on both MWFRS and C&C.
Right end vertical not exposed to wind pressure.
Left cantilever is exposed to wind
(a) Continuous lateral restraint equally spaced on member. Or 2x6 #3 Or better "T" reinforcement. 80% length of web
member. Attached with 16d Box or Gun (0.135"x3.5",min.)nails @ 6" OC.
Deflection meets U360 live and U240 total load. Creep increase factor for dead load is 1.50.
7 2
T3
77. "6A
12
4 4.65
�— 5'11"14 5'4"1 7'8"8 —�
r 19'0"7
R=1143# U=585# RL=589/-1259 W=8" R=998# U=723#
(Rigid Surface)
DESC.= B10 SEQ = 97563
PLT. TYP.-WAVE DESIGN CRIT=CUSTOMRPI-2007FT/RT=20%(0%)HO(0) QTY= 1 TOTAL= 1 REV. 15.01.01C.0610.23 SCALE=0.2500
"WARNING• TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING.
REFER TO HIB-91 HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 683
D'ONOFRIO
T. STILES
TIC LL 30.0 Sf
p
REF
DATE 05-31-2016
DR., SUITE 200, MADISON, WI. 53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
TC DL 15.Opsf
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. **IMPORTANT** FURNISH A
-
-P E ET
- - - - -
-
O
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
BC DL 10.Opsf
DRWG
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NDS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GA ASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
CERTIFICATION
# 49200
BC LL O.Opsf
TOT.LD. 55.Opsf
ROOF & FLOOR TRUSS SYSTEMS
4175 MARTIN HIGHWAY
O/A LEN. lsoao7
DUR.FAC. 1.25
JOB #: KB0336
PALM CITY, FL 34990
OFF: (772) 286-3700
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
404 SW CAMDEN AVE
FAX: (772) 288-4234
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
STUART, FL 34994
SPACING 24.D��
COMN
BUILDING DESIGNER PER ANSI/TPI 1-19%5 SECTION 2.
TYPE
IOb:(Kt3UJJb) /barDara Bennett Kt3U33b / t311
Value'Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP M-30 :T1 2x4 SP #2:
Bot chord 2x4 SP #2
Webs 2x4 SP #3
:Lt Wedge 2X6 SP #2:
Lumber value set "13B" uses design values approved 1/30/2013 by ALSC
In lieu of rigid ceiling use purlins to brace BC @ 24" OC.
Bottom chord checked for 10.00 psf non -concurrent live load.
MWFRS loads based on trusses located at least 16.58 ft. from roof edge.
�-- 2'8"2 14'47
�-- 2-8"2 i 774 i7'2"4 ,
THIS DWG. PREPARED BY THE ALPINE JOB DESIGNER PROGRAM FROM TRUSS MFR'S LAYOUT
165 mph wind, 16.58 ft mean hgt, ASCE 7-10, CLOSED bldg, not located within 9.00 ft from roof edge, RISK CAT II, EXP D
wind TIC DL=5.0 psf, wind BC DL=5.0 psf.
Wind loads and reactions based on both MWFRS and C&C.
Right end vertical not exposed to wind pressure.
Left cantilever is exposed to wind
(a) Continuous lateral restraint equally spaced on member. Or 1 x4 #3SRB SPF-S or better "T" reinforcement. 80% length of
web member. Attached with 8d Box or Gun (0.113"x2.5",min.)nails @ 6" OC.
Deflection meets U360 live and U240 total load. Creep increase factor for dead load is 1.50.
2,8"2 7'2"4 774 —�
r 17'0"10 -
R=1027# U=575# RL=538/-92# W=8" R=882# U=607#
(Rigid Surface)
DESC. = B11 SEQ = 97532
PLT. TYP: WAVE DESIGN CRIT=CUSTOMrrPI-2D07FT/RT=20%(0%)/1D(0) QTY= 1 TOTAL= 1 REV. 15.01.01C.0610.23 SCALE=0.2500
O
- -- - - - -
**WARNING— TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING.
REFER TO HIB-91 (HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
D'ONOFRIO DR., SUITE 200, MADISON, WI. 53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. 'IMPORTANT" FURNISH A
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED -PRODUCTS, INC. SHALL NOT BE -
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NDS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GA ASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
BUILDING DESIGNER PER ANSI/TPI 1-19g SECTION 2.
T STILES
PEET
1
CERTIFICATION
# 49200
404 SW CAMDEN AVE
STUART, FL 34994
TC LL 30.Opsf
TIC DL 15.Opsf
BC DL, 10.Opsf
BC LL O.Opsf
TOT,LD, 55.Opsf
REF
DATE 05-31-2016
DRWG
ROOF & FLOOR TRUSS SYSTEMS
O/A LEN. 170010
4176 MARTIN HIGHWAY
PALM CITY, FL 34990
OFF: (772) 286-3700
FAX: (772) 288-4234
DUR.FAC. 1.25
JOB #: KB0336
SPACING 24.0"
TYpE COMN
JOD:(KbU.5:Sb1 /CarDara Cennett KbUJ;5b / 1:512
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2
Bot chord 2x4 SP #2
Webs 2x4 SP #3
:Lt Wedge 2X6 SP #2:
Lumber value set "13B" uses design values approved 1/30/2013 by ALSC
In lieu of rigid ceiling use pur ins to brace BC @ 24" OC.
Bottom chord checked for 10.00 psf non -concurrent live load.
MWFRS loads based on trusses located at least 8.01 ft. from roof edge.
14'4"7
TV's i6191,15
7'6"8 -i 6715
= 14'4'7
R=882# U=484# RL=433/-74# W=8"15
(Rigid Surface)
THIS DWG. PREPARED BY THE ALPINE JOB DESIGNER PROGRAM FROM TRUSS MFR'S LAYOUT
165 mph wind, 16,02 ft mean hgt, ASCE 7-10, CLOSED bldg, not located within 9.00 ft from roof edge, RISK CAT II, EXP D,
wind TC DL=5.0 psf, wind BC DL=5.0 psf.
Wind loads and reactions based on both MWFRS and C&C.
Right end vertical not exposed to wind pressure.
Left cantilever is exposed to wind
(a) Continuous lateral restraint equally spaced on member. Or 1x4 #3SRB SPF-S or better "T' reinforcement. 80% length of
web member. Attached with 8d Box or Gun (0.113"x2.5",min.)nails @ 6" OC.
Deflection meets U360 live and U240 total load. Creep increase factor for dead load is 1.50.
R=727# U=531#
DESC.= B12 SEQ = 97760
PLT. TYP.-WAVE DESIGN CRIT=CUST0MrrP1-2007 FTIRT=20%(0%y10(0) QTY= 1 TOTAL= 1 REV. 15.01.01 C.0610.23 SCALE=0.3750
"WARNING- TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING.
REFER TO HIB-91 (HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
T. STILES
TC LL 30.Opsf
REF
- - - -
O
D'ONOFRIO DR., SUITE 200, MADISON, WI. 53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. -IMPORTANT" FURNISH A
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NDS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GA ASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
BUILDING DESIGNER PER ANSI/TPI 1-1995 SECTION 2.
- -P E ET
CERTIFICATION
# 49200
404 SW CAMDEN AVE
STUART, FL 34994
TC DL _ 1_5.Opsf _
BC DL 10.0psf
BC LL O.Opsf
TOT.LD. 55.Opsf
DATE 05-31-2016
DRWG
ROOF & FLOOR TRUSS SYSTEMS
O/A LEN. 14D407
4175 MARTIN HIGHWAY
PALM CITY, FL 34990
OFF: (772) 2845-3700
FAX: (772) 288-4234
DUR.FAC. 1.25
JOB #: KB0336
SPACING 24.0"
TYPE MONO
JOD:(NbU.5 ND) /IsarDara tsennett r\bUSJb / bl J
Value Set: 13B (Effective 6/112013)
Top chord 2x4 SP #2
Bot chord 2x4 SP #2
Webs 2x4 SP #3
:Lt Wedge 2X6 SP #2:
Lumber value set "13B" uses design values approved 1 /3012013 by ALSC
Bottom chord checked for 10.00 psf non -concurrent live load.
MWFRS loads based on trusses located at least 7.73 ft. from roof edge.
THIS DWG. PREPARED BY THE ALPINE JOB DESIGNER PROGRAM FROM TRUSS MFR'S LAYOUT
165 mph wind, 15.46 ft mean hgt, ASCE 7-10, CLOSED bldg, not located within 9.00 ft from roof edge, RISK CAT II, EXP D,
wind TIC DL=5.0 psf, wind BC DL=5.0 psf.
Wind loads and reactions based on both MWFRS and C&C.
Right end vertical not exposed to wind pressure.
Left cantilever is exposed to wind
In lieu of rigid ceiling use pudins to brace BC @ 24" OC.
Deflection meets U360 live and U240 total load. Creep increase factor for dead load is 1.50.
6'0"9 "I' 64"
11'4"9
R=719# U=435# RL=362/-60# W=815
(Rigid Surface)
5'4"
R=561# U=455#
DESC. = B13 SEQ = 97751
PLT. TYP.-WAVE DESIGN CRIT=CUSTOM/rP1-2007FT/RT=20%(0%)/10(0) QTY= 1 TOTAL= 1 REV. 15.01.01C.0610.23 SCALE=0.5000
**WARNING- TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING.
REFER TO HIB-91 (HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
T STILES
TC LL 30.Opsf
REF
0
- - - - -
D'ONOFRIO DR., SUITE 200, MADISON, WI. 53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. **IMPORTANT** FURNISH A
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NDS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GA ASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
BUILDING DESIGNER PER ANSI/TPI 1-19 5 SECTION 2
.
- - - -P E ET
CERTIFICATION
# 49200
404 SW CAMDEN AVE
STUART, FL 34994
TIC DL 15.Opsf
BC DL 10.Opsf
BC LL O.Opsf
TOT.LD. 55.Opsf
DATE_ 05-31-2016
DRWG
ROOF & FLOOR TRUSS SYSTEMS
O/A LEN. 110409
4175 MARTIN HIGHWAY
PALM CITY, FL 34990
OFF: (772) 286.3700
FAX: (772) 288-4234
DUR.FAC. 1.25
JOB #: KB0336
SPACING 24.0"
'TYPE MONO
)D:(KbU:ssb) /tsamara I5ennett mtsussts / tf i4
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2
Bot chord 2x4 SP #2
Webs 2x4 SP #3
:Lt Wedge 2X6 SP #2:
Lumber value set "13B" uses design values approved 1/30/2013 by ALSC
Bottom chord checked for 10.00 psf non -concurrent live load.
MWFRS loads based on trusses located at least 7.50 ft. from roof edge.
=3:
T
4.1
THIS DWG. PREPARED BY THE ALPINE JOB DESIGNER PROGRAM FROM TRUSS MFR'S LAYOUT
165 mph wind, 15.00 ft mean hgt, ASCE 7-10, CLOSED bldg, not located within 4.50 ft from roof edge, RISK CAT II, EXP D,
wind TC DL=5.0 psf, wind BC DL=5.0 psf.
Wind loads and reactions based on both MWFRS and C&C.
Right end vertical not exposed to wind pressure.
Left cantilever is exposed to wind
In lieu of rigid ceiling use purlins to brace BC @ 24" OC.
Deflection meets U360 live and U240 total load. Creep increase factor for dead load is 1.50.
I - 4'6"10 -I 3'10"l -�
8'4"11
8'4"11
R=555# U=387# RL=291/45# W=8"15 R=392# U=378#
(Rigid Surface)
DESC. = B14 SEQ = 97757
PLT.TYP.-WAVE DESIGN CRIT-CUSTOM/rP1-2007FT/RT=20%(0%yI0(0) QTY=1 TOTAL=1 REV. 15.01.01C.0610.23 SCALE=0.5000
O
- - - - -
••WARNING**TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING.
REFER TO HI6-91 (HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
D'ONOFRIO DR., SUITE 200, MADISON, WI.53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. **IMPORTANT** FURNISH A _
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NDS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GA ASTM A553 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
BUILDING DESIGNER, OF THIS A S RPI COMPONENT FOR ANY
SECTION 2. PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
T . STILES
-_ _I' E ET
CERTIFICATION
# 49200
404 SW CAMDEN AVE
STUART, FL 34994
TC LL 30.Opsf
TC DL 1 _5.Opsf_ _ _
BC DL 10.0psf
BC LL O.Opsf
TOT.LD. 55.Opsf
REF
DATE _ 05-31-2016 _
DRWG
ROOF & FLOOR TRUSS SYSTEMS
O/A LEN. 80411
4175 MARTIN HIGHWAY
PALM CITY, FL 34990
OFF: (772) 286-3700
FAX. (772) 286-4234
DUR.FAC. 1.25
JOB #: KB0336
SPACING 24.0"
TYPE MONO
)D:(rwy;5 ti) /ttarnara tdennett Kt3u6m / t3i b
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2
Bot chord 2x4 SP #2
Webs 2x4 SP #3
:Lt Wedge 2X6 SP #2:
Lumber value set "13B" uses design values approved 1/30/2013 by ALSC
Bottom chord checked for 10.00 psf non -concurrent live load.
T
1
R=397# U=339# RL=222/-29# W=8"15
(Rigid Surface)
5'4"13
THIS DWG. PREPARED BY THE ALPINE JOB DESIGNER PROGRAM FROM TRUSS MFR'S LAYOUT
165 mph wind, 15,00 ft mean hgt, ASCE 7-10, CLOSED bldg, not located within 4.50 ft from roof edge, RISK CAT II, EXP D,
wind TIC DL=5.0 psf, wind BC DL=5.0 psf.
Wind loads and reactions based on both MWFRS and C&C.
Right end vertical not exposed to wind pressure.
Left cantilever is exposed to wind
In lieu of rigid ceiling use pudins to brace BC @ 24" OC.
Deflection meets U360 live and U240 total load. Creep increase factor for dead load is 1.50.
R=220# U=283#
DESC. = B15 SEQ = 97750
PLT. TYP.-WAVE DESIGN CRIT=CUSTOM/TPI-2D07FT/RT=2D%(0%y10(0) QTY= 1 TOTAL= 1 REV. 15.01.01C.0610.23 SCALE=1.0000
— - - - - -
O
**WARNING** TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING.
REFER TO HIB-91 (HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
D'ONOFRIO DR., SUITE 200, MADISON, WI. 53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. **IMPORTANT** FURNISH A
COPY OF THIS DESIGN TO.THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NOS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GA ASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
BUILDING DESIGNER PER ANSIIrPI 1-1995 SECTION 2
T. STILES
_ -
P E ET
CERTIFICATION
# 49200
404 SW CAMDEN AVE
STUART, FL 34994
TC LL 30.Opsf
TIC DL 15.Opsf
- - - -
BC DL 10.Opsf
BC LL O.Opsf
TOT.LD. 55.Opsf
REF
DATE _ 05-3.1-2016
DRWG
ROOF & FLOOR TRUSS SYSTEMS
O/A LEN. 50413
4175 MARTIN HIGHWAY
PALM CITY, FL 34990
OFF: (772) 286-3700
FAX: (772) 288-4234
DURTAC. 1.25
JOB #: KB0336
SPACING 24.0"
TYpE MONO
IOD:(IKt3U33b) tbaroara tsennen Kt woo / bib
Value Set: 13B (Effective 61112013)
Top chord 2x4 SP #2
Bot chord 2x4 SP #2
Webs 2x4 SP #3
:Lt Wedge 2X6 SP #2:
Lumber value set "136" uses design values approved 1/3012013 by ALSC
Deflection meets U360 live and U240 total load. Creep increase factor for dead load is 1.50.
T
0
1
DESC. = B16
PLT. TYP.-WAVE
— 2'4"14
R=290# U=353# RL=179# W=8"15
(Rigid Surface)
R=24/-53# Rw=33# U=71#
DESIGN CRIT=CUST0M/rP1-2007 FT/RT=20%(0%)/10(0)
THIS DWG. PREPARED BY THE ALPINE JOB DESIGNER PROGRAM FROM TRUSS MFR'S LAYOUT
165 mph wind, 15.00 ft mean hgt, ASCE 7-10, CLOSED bldg, Located anywhere in roof, RISK CAT II, EXP D, wind TC
DL=5.0 psf, wind BC DL=5.0 psf.
Wind loads and reactions based on both MWFRS and C&C.
Left cantilever is exposed to wind
In lieu of rigid ceiling use pudins to brace BC @ 24" OC.
Bottom chord checked for 10.00 psf non -concurrent live load.
QTY= 1 TOTAL= 1
���,R- G/ R.I�I� D BR II� NG), P TPI (, PLAT, INSTITUTE, oR �II��.
REFER TO HI (HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI PLATE INSTITUTE, 583
T STILES
TTRUSS
R.,
D'ONOFRIO DR., SUITE 200, MADISON, W. 53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. -IMPORTANT* FURNISH A
.
P E ET
O
COPY OF THIS _DESIGN TO THE. INSTALLATION CONTRACTOR. -ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
- -
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
CERTIFICATION
ROOF & FLOOR TRUSS SYSTEMS
WITH APPLICABLE PROVISIONS OF NDS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GA ASTM A653 GR40 GALV. STEEL
# 49200
4175 MARTIN HIGHWAY
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
PALM CITY, FL 34990
OFF: (772) 286-3700
DESIGN, POSITION CONNECTORS PER DRAWINGS 150 A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
404 SW CAMDEN AVE
STUART, FL 34994
FAX: (772) 288-4234
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
BUILDING DESIGNER_ PER ANSI1TPI 1-1925 SECTION!).
'
REV. 15.01.01C.0610.23
SEQ = 97763
SCALE=1.0000
TC LL
TC DL
BC DL
BC LL
TOT.LD.
30.Opsf
15.Opsf
10.Opsf
O.Opsf
55.Opsf
REF
DATE _ 05-31-2016
DRWG
O/A LEN. 20414
DUR.FAC.
1.25
JOB #: KB0336
SPACING
24.0"
TYPE MONO
/tiamara bennett Kkju336 / L:1
THIS DWG. PREPARED BY THE ALPINE JOB DESIGNER
FROM TRUSS MFR'S LAYOUT
Value Set: 13B (Effective 6/l/2013)
Top chord 2x4 SP #2 :T2 2x4 SP M-30:
Bot chord 2x6 SP M-26
Webs 2x4 SP #3
Lumber value set "13B" uses design values approved 1/30/2013 by ALSC
130k a 170# 6084
5'2"9 + 50"2 1 '162'11'�'2"1p'717-J1 - - 5'6'13 1�� 5'2"4
�--- 10'9"4 7'0"9 - - i 107'11
6,4"l 4,5'3 7'0"9 4,4"9 6,3"2
2.75 12 a 2.78
T1 = T2 8 T3
m =1.5x =1.5X4 W3 mT mT
N=4X12(A1 W1 =4X12(A1) Rif. NI
�+4 1
B1 - 8)2 - 83 5
P„ 7 _ 26,6"12
i 10'9"4 i 7'0"9 197"l1 �{
j 28'5"8
52"9 5'0"2 $2'1"91'2"1A'7"1$1'11"6� 5,5"13 5,2"4 �{
610 2B 1� 3D�6r7i308a�3oedT-1358{# 61a
R=4407# U=2052# W=812
(Rigid Surface)
R=4432# U=2063# W=810
(Rigid Surface)
3 Complete Trusses Required
Nail Schedule:0.120"x3", min. nails
Top Chord: 1 Row @10.25" O.C.
Bot Chord: 1 Row @ 9.25" O.C.
Webs : 1 Row @ 4" o.c.
Repeat nailing as each layer is applied. Use equal spacing
between rows and stagger nails in each row to avoid splitting.
Special loads
---(Lumber Dur.Fac.=1.25 / Plate Dur.Fac.=1.25)
TC- From 91 plf at 0.00 to 91 plf at 10.77
TC- From 91 plf at 10.77 to 91 plf at 17.82
TC- From 91 plf at 17.82 to 91 plf at 28.46
BC- From 20 plf at 0.00 to 20 pit at 28.46
TC- 130.05 lb Conc. Load at 5.22
TC- 162.24 lb Conc. Load at 10.23
TC- 462.71 lb Conc. Load at 10.81
TC- 170.20 lb Conc. Load at 12.94,14.18,15.84
TC- 608.31 lb Conc. Load at 17.78
TC- 131.53 lb Conc. Load at 23.27
BC- 60.68 lb Conc. Load at 5.22,23.27
BC- 287.06 lb Conc. Load at 10.23
BC- 985.95 lb Conc. Load at 10.81
BC- 308.23 lb Conc. Load at 12.94,14.18,15.84
BC- 1358.33 lb Conc. Load at 17.78
"' Page overflow in note placement. (RdNot)
DESC. = C1 SEQ = 97742
PLT. TYP: WAVE DESIGN CRIT=CUSTOM MI-2707FT/RT--m%(0%)HO(0) QTY= 1 PLIES= 3 TOTAL= 3 REV. 15.01.01 C.0610.23 SCALE=0.1250
"WARNING" TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING.
REFER TO HIB-91 (HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
T STILES
TC LL 30.Opsf
REF
- - - -
O
D'ONOFRIO DR., SUITE 200, MADISON, WI. 53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. **IMPORTANT** FURNISH A
COPY OF THIS DESIGN TO THE. INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NOS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GA ASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
BUILDING DESIGNER PER ANSI/TPI 1-1925 SECTION 2,
.
-PE ET
CERTIFICATION
# 49200
404 SW CAMDEN AVE
STUART, FL 34994
TC DL 15.Opsf
- - - -
BC DL 10.Opsf
BC LL O.Opsf
TOT.LD. 55.Opsf
DATE _ 05-31-2016
DRWG
ROOF & FLOOR TRUSS SYSTEMS
O/A LEN. 280508
4175 MARTIN HIGHWAY
PALM CITY, FL 34990
OFF: (772) 286-3700
FAX: (772) 288-4234
DUR.FAC. 1.25
JOB #: KB0336
SPACING 24.0"
TYPE COMN
I0D:(r%bUJ.5b) /Isaroara t3ennett Kt51LIs5b / UZ
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP M-30 :T2 2x4 SP #2:
Bot chord 2x4 SP M-31 :B2 2x4 SP #2:
Webs 2x4 SP #3
:Lt Wedge 2x4 SP #3::Rt Wedge 2x4 SP #3:
Lumber value set "1313" uses design values approved 1/30/2013 by ALSC
Deflection meets U360 live and U240 total load. Creep increase factor for dead load is 1.50.
MWFRS loads based on trusses located at least 7.50 ft. from roof edge.
12'11"7
7'0"12
THIS DWG. PREPARED BY THE ALPINE JOB DESIGNER PROGRAM FROM TRUSS MFR'S LAYOUT
165 mph wind, 15.00 ft mean hgt, ASCE 7-10, CLOSED bldg, not located within 9.00 ft from roof edge, RISK CAT II, EXP D
wind TC DL=5.0 psf, wind BC DL=5.0 psf.
Wind loads and reactions based on both MWFRS and C&C.
Left and right cantilevers are exposed to wind
In lieu of rigid ceiling use pudins to brace BC @ 24" OC.
Bottom chord checked for 10.00 psf non -concurrent live load.
Calculated vertical deflection is 0.44" due to live load and 0.59" due to dead load at X = 12-11-7.
4W'10
51101,11 44"10 -{- 5'9"13
12'9"9
F_ — is . 1
f— 7'0"12
R=1672# U=989# RL=661-66# W=8"12
(Rigid Surface)
5'10"11 - 44"10 1 69"13
30'1"10
6'11"12 �{
R=1670# U=988# W=8"10
(Rigid Surface)
DESC. = C2 SEQ = 97718
PLT. TYP.-WAVE DESIGN CRIT=CUSTOM MI-2007FT/RT=20%(0%y10(0) QTY= 1 TOTAL= 1 REV. 15.01.01C.0610.23 SCALE=0.2500
- O
••WARNING•• TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING.
REFER TO HIB-91 (HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
D'ONOFRIO DR., SUITE 200, MADISON, WI. 53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. -IMPORTANT" FURNISH A N
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NDS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GA ASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
SUITABIILI DES GNERE OF THIS A S RPI 1COMPONENT FOT OANY N 2 PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
T. STILES
_
P E ET
CERTIFICATION
# 49200
404 SW CAMDEN AVE
STUART, FL 34994
TIC LL 30.Opsf
TICDL 15.Opsf
BC DL 10.Opsf
BC LL O.Opsf
TOT.LD. 55.Opsf
REF
DATE 05-31-2016
DRWG
ROOF & FLOOR TRUSS SYSTEMS
O/A LEN. 300110
4175 MARTIN HIGHWAY
PALM CITY, FL 34990
OFF: (772) 286-3700
FAX. (772) 288-4234
DURFAC1.25
..
JOB #: KB0336
SPACING 24.0"
TYPE COMN
)D:(I\CU,J.50) inaroara nennea mt5u3st) / L;:s
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2 :T2 2x4 SP M-30:
Bot chord 2x4 SP M-30
Webs 2x4 SP #3 :W8 2x12 SP #2:
:Lt Wedge 2x4 SP #3:
Lumber value set "138" uses design values approved 1/30/2013 by ALSC
In lieu of rigid ceiling use pudins to brace BC @ 24" OC.
Deflection meets U360 live and U240 total load. Creep increase factor for dead load is 1.50.
15,11,10
THIS DWG. PREPARED BY THE ALPINE JOB DESIGNER PROGRAM FROM TRUSS MFR'S LAYOUT
165 mph wind, 15.00 ft mean hgt, ASCE 7-10, CLOSED bldg, not located within 9.00 ft from roof edge, RISK CAT II, EXP D,
wind TC DL=5.0 psf, wind BC DL=5.0 psf.
Wind loads and reactions based on both MWFRS and C&C.
Left cantilever is exposed to wind
(a) Continuous lateral restraint equally spaced on member. Or 1x4 #3SRB SPF-S or better "T" reinforcement. 80% length of
web member. Attached with 8d Box or Gun (0.113"x2.5",min.)nails @ 6" OC.
Bottom chord checked for 10.00 psf non -concurrent live load.
MWFRS toads based on trusses located at least 7.50 ft. from roof edge.
1'8"11 1 9714
8T'14 I . 6'11"12 1 1'8"11 1 4'2"3 5711 �{
25'8"11
6.11"12-}-1,8"11
26'8"2
R=1552# U=907# RL=119/-40# W=8"12 R=1403# U=799# W=3"8
(Rigid Surface) (Rigid Surface)
DESC. = C3 SEQ = 105089
PLT. TYP: WAVE DESIGN CRIT=CUSTOMlrPI-2007 FTIRT=2D%(096y10(0) QTY= 1 TOTAL= 1 REV. 15.01.01 C.0611.00 SCALE=0.2500
'•WARNING•• TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING.
REFER TO HIB-91 (HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
D'ONOFRIO DR., SUITE
T. STILES
TC LL 30.Opsf
REF
DATE 05-31-2016
200, MADISON. WI. 53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
TC DL 15.Opsf
m
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. —IMPORTANT- FURNISH A
COPY OF THIS. DESIGN
-P E ET
- - -
TO THE INSTALLATIONCONTRACTOR. ALPINE ENGINEERED PRODUCTS,-INC.SHALL NOT BE
BC DL 10.Opsf
DRWG
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH
CERTIFICATION
BC LL O.Opsf
ROOF & FLOOR TRUSS SYSTEMS
APPLICABLE PROVISIONS OF NDS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GA ASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
# 49200
TOT.Lo. 55.Opsf
4176 MARTIN HIGHWAY
O/A LEN. 250910
PALM CITY, FL 34990
OFF: (772) 288-3700
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
404 SW CAMDEN AVE
DUR.FAC. 1.25
JOB #: KB0336
FAX. (772) 286-4234
PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
1--1
STUART, FL 34994
SPACING 24.0"
SPEC
BUILDING DESIGNER. ERANSI/TPI 25 SECTION ?
TYPE
)OD:(KbUJ6b) /Barbara Bennett KCU63Jb / U4
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2
Bot chord 2x6 SP M-26 :B2 2x4 SP #2::B3 2x6 SP #2:
Webs 2x4 SP #3
Lumber value set "13B" uses design values approved 1/30/2013 by ALSC
Special loads
—(Lumber Dur.Fac.=1.25 / Plate Dur.Fac.=1.25)
TC- From 91 plf at 0.00 to 91 plf at 16.84
TC- From 91 plf at 16.84 to 91 plf at 26.08
BC- From 20 plf at 0.00 to 20 plf at 26.08
PLT- 50.00 lb Conc. Load at (20.17,12.37)
PLB- 50.00 lb Conc. Load at (16.35,11.86)
Bottom chord checked for 10.00 psf non -concurrent live load.
MWFRS loads based on trusses located at least 15.00 ft. from roof edge.
16'10"2
20'2"
THIS DWG. PREPARED BY THE ALPINE JOB DESIGNER PROGRAM FROM TRUSS MFR'S LAYOUT
2 Complete Trusses Required
Nail Schedule:0.1201lx3", min. nails
Top Chord: 1 Row @12,00" D.C.
Bot Chord: 1 Row @12.00" D.C.
Webs : 1 Row @ 4" o.c.
Use equal spacing between rows and stagger nails
in each row to avoid splitting.
All plates are 3X5 except as noted
165 mph wind, 15.00 ft mean hgt, ASCE 7-10, CLOSED bldg, not located within 9.00 ft from roof edge, RISK CAT II, EXP D,
wind TC DL=5.0 psf, wind BC DL=5.0 psf.
Wind loads and reactions based on both MWFRS and C&C
Right end vertical not exposed to wind pressure.
Left cantilever is exposed to wind
Deflection meets U360 live and U240 total load. Creep increase factor for dead load is 1.50
soa
5'10"15
9'2"13
i 5'413 37"12 17'0"5
a 2.78
Lb'Z'6
5'4"13 —f — 37'12 3'9"8 i 8' 4'8"5 T "81
12'10"2 1 1 14 }� 6'10"2 5'2"13
16'4"4
R=1527# U=804# RL=154/-36# W=812
DESC. = C4Rigid Surface)
PLT. TYP.-WAVE DESIGN CRIT=CI
26'0"15
50C
QTY= 1 PLIES= 2 TOTAL= 2
9'8"11
R=1462# U=783# W=3"8
(Rigid Surface)
REFER TO HIB-91 (HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE,�683
D'ONOFRIO DR., SUITE 200, MADISON, WI. 53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
T . STILES
O
m5dWITH
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. **IMPORTANT** FURNISH A
COPY OF THIS DESIGN TO. THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
- P E ET
- -
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
CERTIFICATION
ROOF & FLOOR TRUSS SYSTEMS
WITH APPLICABLE PROVISIONS OF NDS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GA ASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
# 49200
404 SW CAMDEN AVE
4175 MARTIN HIGHWAY
PALM CITY. FL 34990
OFF: (772) 286-3700
FAX: (772) 288-4234
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
STUART, FL 34994
BUILDING DESIGNER. PER ANSI/TPI 1-1995 SECTION 2.
REV. 15.01.01 C.0611.00
TC LL
30.Opsf
TC DL
15.Opsf _
BC DL
10.Opsf
BC LL
O.Opsf
TOT.LD.
55.Opsf
DUR.FAC.
1.25
SPACING
24.0"
SEQ = 105079
SCALE=0.2500
REF
DATE 05-31-2016
DRWG
O/A LEN. 250607
JOB #: KB0336
TYPE COMN
)OD:(Kbu6Jt5) /tsarDara tdennett KtdU33t7 / UO
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP M-30 :T2 2x4 SP #2:
Bot chord 2x6 SP #2 :B2 2x4 SP #2:
Webs 2x4 SP #3 :W1 2x4 SP #2:
:Lt Bearing Leg 2x8 SP #2:
Lumber value set "13B" uses design values approved 1/30/2013 by ALSC
Special loads
—(Lumber Dur.Fac.=1.25 / Plate Dur.Fac.=1.25)
TC- From 91 plf at 0.00 to 91 plf at 11.95
TC- From 91 plf at 11.95 to 91 plf at 22.02
BC- From 20 plf at 0.60 to 20 plf at 11.95
BC- From 20 plf at 11.95 to 20 plf at 15.95
BC- From 20 plf at 15.95 to 20 plf at 22.02
PLT- 50.00 Ib Conc. Load at (15.28,12.56)
PLB- 50.00 lb Conc. Load at (191,12.05) 14,81
Wind loads and reactions based on both MWFRS and C&C.
- 1Tl1"7
W7"
THIS DWG. PREPARED BY THE ALPINE JOB DESIGNER PROGRAM FROM TRUSS MFR'S LAYOUT
All plates are 3X5 except as noted.
165 mph wind, 15.00 ft mean hgt, ASCE 7-10, CLOSED bldg, not located within 9.00 ft from roof edge, RISK CAT 11, EXP D,
wind TC DL=5.0 psf, wind BC DL=5.0 psf.
Right end vertical not exposed to wind pressure.
Bottom chord checked for 10.00 psf non -concurrent live load.
Deflection meets U360 live and U240 total load. Creep increase factor for dead load is 1.50.
MWFRS loads based on trusses located at least 15.00 ft. from roof edge.
21'5"
W#
10'0"13
12 7 7R
6'8"15
m m
o v
0 0
to
[7"4 7 4"3 5'6"5 6 8�
[7"4 7'4"3 4' 14' 6'0"13 -I
— 11'0"2 10'4"14
50#
R=1266# U=698# RL=77/-47# W=5"5 R=1261# U=681# W=3"8
(Rigid Surface) (Rigid Surface)
DESC. = C5 SEQ = 105082
PLT. TYP.-WAVE DESIGN CRIT=CUSTOM%rPI-2rA7FT/RT=20%(0%)/10(0) QTY= 1 TOTAL= 1 REV. 15.01.01C.0611.00 SCALE=0.3750
..WARNING** TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING.
REFER TO HIB-91 (HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
T. STILES
TC LL 30.Opsf
REF
O
D'ONOFRIO DR., SUITE 200, MADISON, WI.53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. -IMPORTANT- FURNISH A
COPY OF THIS DESIGN TO THE INSTALLATION -CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE -
_ -
P E E T
TC DL 15.Opsf
-
BC DL 10.Opsf
DATE 05-31-2016
-
DRWG
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NDS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GA ASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
CERTIFICATION
# 49200
BC LL O.Opsf
TOT,LD. 55.Opsf
ROOF & FLOOR TRUSS SYSTEMS
O/A LEN. 210512
4175 MARTIN HIGHWAY
DUR.FAC. 1.25
JOB #: KB0336
PALM CITY, FL 34990
OFF: (772) 286-3700
FAX: (772) 288-4234
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
BUILDING DESIGNER PER ANSI/TPI 1-19Q5 SECTION 2
404 SW CAMDEN AVE
STUART, FL 34994
SPACING 24.0"
TYPE SPEC
)D:(Kt: u�ti) /barDara tjennett Kt1UJJti / L:6
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2
Bot chord 2x6 SP #2 :B2 2x4 SP #2:
Webs 2x4 SP #3 :W6 2x12 SP #2:
:Lt Bearing Leg 2x8 SP #2:
Lumber value set "13B" uses design values approved 1/30/2013 by ALSC
Deflection meets U360 live and U240 total load. Creep increase factor for dead load is 1.50.
8'0"1
19
1872
THIS DWG. PREPARED BY THE ALPINE JOB DESIGNER PROGRAM FROM TRUSS MFR'S LAYOUT
All plates are 3X5 except as noted.
165 mph wind, 15.00 ft mean hgt, ASCE 7-10, CLOSED bldg, not located within 9.00 ft from roof edge, RISK CAT 11, EXP D
wind TIC DL=5.0 psf, wind BC DL=5.0 psf.
Wind loads and reactions based on both MWFRS and C&C.
Right end vertical not exposed to wind pressure.
Bottom chord checked for 10.00 psf non -concurrent live load.
MWFRS loads based on trusses located at least 15.00 ft. from roof edge.
12 ,,,
10'9"5
7" 3 P1 -
�— '4"13 �} 8'- T— 65"13 I
7"4 1-- 3'4"13
R=1047# U=627# RL=32/-82# W=5"5
(Rigid Surface)
673
1'4"13
6'9"5
R=1021# U=5809 W=Y8
(Rigid Surface)
DESC. = C6 SEQ = 105094
PLT. TYP.-WAVE DESIGN CRIT=CUSTOMITPI-2007FT/RT=20%10%)/10(0) QTY= 1 TOTAL= 1 REV. 15.01.01C.0611.00 SCALE=0.3750
**WARNING** TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING.
REFER TO HIB-91 (HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
D'ONOFRIO DR., SUITE 200,
T STILES
TC ILL 30.0 Sf
p
REF
DATE 05-31-2016
MADISON, WI. 53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
"
TICDL 15.Opsf
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. —IMPORTANT" FURNISH A
COPY OF THIS DESIGN
P E E T
O
TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
— —
BC-DL - - 9 O.OPSf
DRWG --
- - -
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO- BUILD THE TRUSSES IN CONFORMANCE WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NOS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GA ASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
CERTIFICATION
# 49200
BC ILL O.Opsf
TOT.LD. 55.Opsf
ROOF & FLOOR TRUSS SYSTEMS
4175 MARTIN HIGHWAY
O/A LEN. 1Bosos
PALM CITY, FL 34990
OFF: (772) 288-3700
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
404 SW CAMDEN AVE
DUR.FAC. 1.25
JOB #: KB0336
FAX: (772) 288-4234
AND OF THIS COMPONENT FOR ANYPARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
STUART, FL 34994
SPACING 24.0"
SPEC
BSUITABILITY
UILDING DESIGNER, ERA S RPI 1ON 2-
TYPE
)D:(KtJU69 Jb) /barDara tsennett KbU6db / Ul THIS DWG. PREPARED BY THE ALPINE JOB DESIGNER PROGRAM FROM TRUSS MFR'S LAYOUT
Value Set: 13B (Effective 61112013) 3 Complete Trusses Required
Top chord 2x4 SP #2
Bot chord 2x6 SP M-26
Webs 2x4 SP #3
:Lt Wedge 2x4 SP #3::Rt Wedge 2x4 SP #3: Top Chord: Nail Chord: 1 Row @7Schedule:0.12 @12 min. nails
.00" o.c.
Lumber value set "1313" uses design values approved 1/30/2013 by ALSC Bot Chord: 2 Rows @ 5.00" o.c. (Each Row)
Webs : 1 Row @ 4" o.c.
165 mph wind, 15.00 ft mean hgt, ASCE 7-10, CLOSED bldg, not located within 4.50 ft from roof edge, RISK CAT 11, EXP D, Repeat nailing as each layer it applied. Use equal spacing
wind TC DL=5.0 pat, wind BC DL=5.0 psf. between rows and stagger nails in each row to avoid splitting.
Wind loads and'reactions based on MWFRS. Special loads
L b D F - -
Left and right cantilevers are exposed to wind
In lieu of rigid ceiling use pudins to brace BC @ 24" OC.
Deflection meets U360 live and U240 total load. Creep increase factor for dead load is 1.50.
129#
5'3" t
9D
fo
N
T
4.1
1
5.3"8
5'3"8
SYS
--( um er ur. ac..25 /Plate Dur.Fac.
TC- From 92 plf at 0.00 to 92 plf at 5.29
TC- From 46 pif at 5.29 to 46 plf at 9.83
TC- From 93 pif at 9.83 to 93 plf at 15.12
BC- From 20 plf at 0.00 to 20 pit at 3.18
BC- From 10 plf at 3.18 to 10 plf at 9.87
BC- From 20 plf at 9.87 to 20 plf at 15.12
1sw 162# T sz 28.981WConc. Load at 5.25, 9.87
`nnr- I nod of 5 g9 7 55, 9 17
8"14 -�- 1'6"12 -� 1'6"12 fJ ---� 2 15
BC- 68 2I Conc. Load at 3A8
BC- 1773.73 lb Conc. Load at 5.18
BC- 3874.55 I Concad. Loat 7.11
BC- 102.41 lb Conc. Load at 9.87
4'67
4'6'7
15'1"7
373 2 -"r 9 11 -�- 1 1 7 3- "„5� 1'6"12 7 j-- 9 1 -�
1681# "173# 73# 1020
R=5937# U=3166# W=8"
(Rigid Surface)
5'3"8
5'3"8
62"15 . I
R=3889# U=2206# W=8"
(Rigid Surface)
1m n0
io m
N N
t I
DESC. = D1 SEQ = 97766
PLT. TYP.-WAVE DESIGN CRIT=CUST0MrrPI-2D07FT/RT=20%(0%)/10(0) QTY= 1 PLIES= 3 TOTAL= 3 REV. 15.01.01 C.0610.23 SCALE=0.5000
XARNING- TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING. ER TO HIB-91 (HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
T STILES
TC LL 30.Opsf
REF
O
- - - - - - -
D'ONOFRIO DR., SUITE 200, MADISON, WI. 53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. *'IMPORTANT** FURNISH A
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
RESPONSIBLE FOR ANY DEVIATION FROM THIS -DESIGN; -ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE -
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NDS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GA ASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
_
P E ET
- ---- -- - - -
CERTIFICATION
# 49200
TC DL 15.Opsf
BC DL 10.Opsf
- - - - - - - - -
BC LL 0.Opsf
TOT.LD. 55.Opsf
DATE 05-31-2016
DRWG
ROOF & FLOOR TRUSS SYSTEMS
O/A LEN. 150107
4175 MARTIN HIGHWAY
DUR.FAC. 1.25
JOB #: KB0336
PALM CITY, FL 34990
OFF: (772) 288-3700
FAX. (772) 288-4234
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
SUITABILITY AND BUILDING DES GNERE OF HIS CPI PONES T FOT ON 2 PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
404 SW C,AMDEN AVE
STUART, FL 34994
SPACING 24.0..
TYPE HIPS