Loading...
HomeMy WebLinkAbout10duct.pdfDuct Leakage Test Report Prescriptive or Performance Method Permit if Job Information -- ---- Builder: DR HORTON Community: CREEKSIDE Lot: 10 Address: 9401 POTOMAC DRIVE Unit: City: FORT PIERCE state: FL zip: 34945 Duct Leakage Test Results Presciptive Method 0 Performance Method System 1 System 2 System 3 Sum of any additional systems Total of all systems ctm25 Y Prescriptive Method cfm25 (total) To qualify as "substantially leak free" On must be less than or equal to 0.04 cfm25 if air handler unit is installed. If air handler unit is not installed, Qn Total must be less than or equal to 0.03. This testing method meets the cfm25 requirements in accordance with Section R403.2.2 58 _ 1916 = 0.03 Qn Total of all systems Total Conditioned Square Footage 7-7 }PASS FAIL Testing Company Performance Method cfm25 (Out or Total) o qualify as "substantially leak free" On must not be greater than the roposed duct leakage On specified on Form R405-2014 Leakage Type selected on Form R405-2014 (Energy Ca1c) Qn specified on Form R405-2014 (Energy Calc) Company Name: SUN SEAL LLC Phone: 321-412-0035 1 hereby verify that the above duct leakage testing results are in accordance with the Florida Building Code requirements with the selected compliance path as stated above, either the Prescriptive Method or Performance Method. Date of Test: 02/09/2022 l Signature of Tester' --9 jj -rl Printed Name of Tester: DANIELMURPHY Lice nsefCertification # 5066440 Issuing Authority